Upload
others
View
57
Download
1
Embed Size (px)
Citation preview
1
GRID
PGFECondenser Bushings
bushings
Customer Benefits• Even voltage distribution
across the bushing thanks to the capacitance-graded condenser core.
• No deterioration of grounded part for CT installation real-ized internally and protected by porcelain.
• Belleville washers to absorb conductor dilatation and vibrations in service.
• Installation in any position.
Manufacturing of the bushing
The main electrical insulation is provided by a condenser body made of a continuous sheet of pure kraft paper bonded with pre-polymerised epoxy resin and wound around a tube or conductor rod.
During winding, a series of cylindrical semi-conducting foils made of graphite printed paper are inserted coaxially between the layers of paper. These foils assure the best possible distribution of the radial and longitudinal electrical gradient between the conductor and the fixing flange, which is grounded. Winding is computer-controlled, the final shape is ob-tained by subsequent machining on a lathe.
After winding, the bushing is placed in an oven for final polymerization of the resin.
Depending on the overall dimensions of the bushing, when the gradients are very low, the insulation can be achieved directly by a tube impregnated in epoxy resin and reinforced by a fiber glass filament winding.
AN ALSTOM COMPANY
Design, components and manufacturing tech-nology guarantee an average life time of over 40 years under normal operating conditions.
The bushing is designated as follows:PGFE.24.125.25000 P Condenser bushings
(“P” from the Italian word “Passante”) G Power generator F High current application (force cooled) E Epoxy resin bonded paper (ERBP)
24 Rated voltage in kV
125 BIL class in kV
25000 Rated current in A
Epoxy resin bonded paper for AC generators
PGFE are bushings designed for use on AC power generators. The dielectricinsulation is achieved by a capacitance-grade condenser body, for installation in any position.
22
CoNDENsER BusHINgs PGFE
Condenser bushings
Rated voltages up to 30 kV
outer envelopes: Porcelain and/or Fiberglass tube
Cooling: Natural, hydrogen, water
Coupling by means of a Belleville washer placed on the air side
Inner conductor made of aluminum or copper casting
Dry filling (polyurethane foam) of the space between the porcelain and condenser body
Installation in any position
CT accommodation on request
Flange made of aluminum or stainless steel, low permeability
Maximum current rating up to 45,000 A
All o-ring gaskets, FPM material: elastomer
Fig. 1(24 kV - 9,000 A)
Fig. 2(24 kV - 12,000 A)
Fig. 3(24 kV - 25,000 A)
Fig. 4(24 kV - 25,000 A)
Fig. 5(24 kV - 20,000 A)
Fig. 7(20 kV - 10 kA)
Fig. 6(24 kV - 25,000 A)
33
CoNDENsER BusHINgs PGFE
The most common solutions and their respective maximum current ratings are:
Natural cooling up to about 10,000/12,000 A
Forced hydrogen cooling up to about 25,000 A
Forced water cooling up to about 45,000 A
All bushings are tested and have electrical and mechanical characteristics that comply with the main standards:
IEC 60137 “Bushings for alternating voltage above 1000 V”
ANsI/IEEE C57.19
Din 48123
The prevailing technical specification in the field of AC power generators (general Electric, siemens-Westinghouse, Mitsubishi, Alstom-ABB, ect.).
Test
Envelope
For outdoor application, the air side envelope is made of brown porcelain, with a creepage distance for very highly polluted atmospheres (31 mm/kV).
For indoor application, the air side envelope is made of porcelain or a tube impregnated in epoxy resin and reinforced by a fiber glass filament winding. The hydrogen side envelope can be made of porcelain or fila-ment winding tube.
Flange
The flange is made of low-permeability, stainless steel casting. It is made of aluminum only for low current ratings (natural cooling applications).
Gaskets
The o-ring type gaskets are made of FPM. They are compatible with the fluids they are in contact with. Air side, the gaskets are sealed to protect them effectively from polluting weather conditions.
Assembling
The porcelain and metal parts (top fixing plate, flange and bottom fixing plate) are coupled by means of springs, generally Belleville washer type springs, placed in the air side of the bushing. The Belleville washers are very effective against the vibration and impact load stress caused by the normal service of the bushing installed on the power generator.
The air and hydrogen side envelopes consist of two completely separate parts, and the flange is fixed between them. This design avoids any pos-sible movement of the flange during the life time of the bushing.
The space between the porcelain and condenser body is filled with dry insulating material (no fluids are used).
Current Rating
The PgFE bushing has been designed to satisfy any requirement in terms of current ratings and cooling method.
The inner conductor is made of an aluminum or copper tube.
44
CoNDENsER BusHINgs PGFE
Grid
-ITR_
PGFE
-L3-
7190
9-V2
-201
2_03
-EN
© -
Alst
om, t
he A
lsto
m lo
go a
nd a
ny a
ltern
ativ
e ve
rsio
n th
ereo
f are
trad
emar
ks a
nd s
ervi
ce m
arks
of A
lsto
m. T
he o
ther
nam
es m
entio
ned,
regi
ster
ed o
r not
, are
the
prop
erty
of t
heir
resp
ectiv
e co
mpa
nies
. The
tech
nica
l and
ot
her d
ata
cont
aine
d in
this
doc
umen
t are
pro
vide
d fo
r inf
orm
atio
n on
ly. N
eith
er A
lsto
m, i
ts o
ffice
rs n
or e
mpl
oyee
s ac
cept
resp
onsi
bilit
y fo
r or s
houl
d be
take
n as
mak
ing
any
repr
esen
tatio
n or
war
rant
y (w
heth
er e
xpre
ss o
r im
plie
d) a
s to
the
accu
racy
or c
ompl
eten
ess
of s
uch
data
or t
he a
chie
vem
ents
of a
ny p
roje
cted
per
form
ance
crit
eria
whe
re th
ese
are
indi
cate
d. N
o lia
bilit
y is
acc
epte
d fo
r any
relia
nce
plac
ed u
pon
the
info
rmat
ion
cont
aine
d in
this
bro
chur
e. A
lsto
m re
serv
es th
e rig
ht to
revi
se o
r cha
nge
thes
e da
ta a
t any
tim
e w
ithou
t fur
ther
not
ice.
Prin
ted
on p
aper
mad
e w
ith p
ure
ECF
(Ele
men
tal C
hlor
ine
Free
) eco
logi
cal c
ellu
lose
pro
duce
d fr
om tr
ees
grow
n in
pro
duct
ion
fore
sts
unde
r res
pons
ible
man
agem
ent,
and
sele
cted
recy
cled
thre
e-la
yer fi
bres
.
GRID
Alstom Grid Worldwide Contact Centre www.grid.alstom.com/contactcentreTel.: +44 (0) 1785 250 070 www.grid.alstom.com
To contact the manufacturerViale suzzani, 229 20162 MILANo (Italy)Tel.: +39 02 661 221Fax: +39 02 647 09 06Email: [email protected]
Following the acquisition of PAssoNI & VILLA, ALsToM gRID now offers a large portfolio of condenser bushings for AC or DC operation. If you require any further information, please address your queries to
[email protected] AN ALSTOM COMPANY
Nameplate
Each bushing is provided with a nameplate with all the electrical data and serial number, in accordance with the requirements of IEC standards and the customer’s technical requirements. The plate is made of stainless steel and is affixed to the flange by nails. The plate indicates:
MILANITALY
MILANITALY
1
2 3 4
P G F E - 2 2 50 - 11 0 0 0 0 N .
2 0 k V 0 01 0 A0 6 0 k g *
5
6
Alstom Grid can satisfy any special test requirements such as:
Mechanical impact load test Vibration test Equivalent thermal test with or without cooling simulation Inside pressure test at any pressure level Leakage test, including by leak meter Drop flow rate