SINGLE LINE DESCRIPTION DOUBLE LINE D D SPLIT BRANCH TAKE-OFF WITH SQUARE ELBOW & SPLITTER DAMPER SPLIT BRANCH TAKE-OFF WITH RADIUS ELBOW & SPLITTER DAMPER POSITIVE PRESSURE RISER, TYPICALLY SUPPLY NEGATIVE PRESSURE RISER, TYPICALLY RETURN, EXHAUST OR OUTSIDE AIR F/S COMBINATION FIRE & SMOKE DAMPER F/S FIRE DAMPER MOTOR OPERATED DAMPER (MOD) MANUAL VOLUME DAMPER, SINGLE BLADE DAMPER (SBD) FOR ROUND OR <10" TALL, OPPOSED BLADE DAMPER (OBD) >10" TALL BACKDRAFT DAMPER BDD BDD SMOKE DAMPER SMOKE DETECTOR DUCT SIZE: FIRST NUMBER IS PLAN WIDTH, SECOND NUMBER IS DEPTH. 24x36 24x36 DUCTWORK LEGEND SD SD PRESSURE REDUCING VALVE SHOCK ABSORBER STRAINER W/ BLOW-OFF VALVE SAFETY RELIEF VALVE VACUUM BREAKER PRESSURE GAUGE W/ PIG TAIL & COCK THERMOMETER PRESSURE - TEMP. TAP AIR VENT PIPE ANCHOR FLEXIBLE CONNECTOR PIPE EXPANSION JOINT PIPE UNION DOUBLE CHECK BACKFLOW PREVENTER PUMP & EQUIPMENT CONNECTOR TEMPERATURE CONTROL VALVE (2-WAY) DRAIN VALVE W/ HOSE END PLUG VALVE IN RISER FLOW BALANCING VALVE GATE OR GLOBE VALVE IN RISER FLOW CONTROL VALVE BALL VALVE PLUG OR BALANCING VALVE CHECK VALVE GLOBE VALVE BUTTERFLY VALVE VENTURI/FLOW INDICATOR TEMPERATURE CONTROL VALVE (3-WAY) SOLENOID VALVE 90° ELBOW UP TEE UP TEE DOWN SHUT OFF (BALL, GATE, BUTTERFLY) PIPING SYMBOLS 90° ELBOW DN S FLOW SWITCH HOSE BIBB WALL HYDRANT TEMPERATURE CONTROLLER OR SENSOR STEAM TRAP TEST CHAMBER STEAM TRAP: FT-FLOAT & THERMOSTATIC TD-THERMODYNAMIC IB-INVERTED BUCKET TS-THERMOSTATIC BP-BALANCED PRESSURE EQUIPMENT ABBREVIATIONS AIR HANDLING UNIT AHU AIR SEPARATOR AS BOILER (HOT WATER) B BASE BOARD BB BUFFER TANK BT CONSTANT VOLUME BOX CV DISHWASHER EXHAUST FAN DEF ELECTRIC BASEBOARD HEATER EBH FURNACE F FAN COIL FC FAN POWERED BOX FP GLYCOL FEEDER GF HUMIDIFIER HC HEATING COIL HP HEAT PUMP HX HEAT EXCHANGER KITCHEN EXHAUST FAN KEF MAKE-UP AIR UNIT MAU MOTOR CONTROL CENTER MCC MIXING VALVE MV PUMP P RETURN (OR RELIEF) AIR FAN RF RADIANT ZONE RZ SNOWMELT AREA SA SUMP BASIN SB SUPPLY FAN SF STORAGE TANK ST THERMOSTATIC MIXING VALVE TMV UNIT HEATER UH VARIABLE VOLUME BOX VV WATER HEATER WH H CHILLER CH COOLING COIL CC CIRC PUMP CP CABINET UNIT HEATER CUH COOLING TOWER CT DUCT COIL DC ELECTRIC WATER HEATER EWH EVAPORATIVE COOLING UNIT ECU ENERGY RECOVERY UNIT ERU EXHAUST FAN EF EXPANSION TANK ET VARIABLE VOLUME BOX W/ REHEAT VR TYPE OF AIR DEVICE RE: GRD SCHEDULE. AIR DEVICE DESIGNATION KEY # CA EXH OSA RA XFR SIZE (INCHES) OR MINIMUM FREE AREA REQUIRED IN SQUARE FEET. NOTE: FOR STANDARD MODULE SIZE REGISTERS, SIZE GIVEN IS NECK SIZE. REFER TO GRD SCHEDULE FOR MODULE SIZE. INDICATES AIR INLET DEVICE. = = = = = = AIR QUANTITY (CFM) COMBUSTION AIR EXHAUST OUTSIDE AIR RETURN TRANSFER B XFR 12x6 A 150 12x6 PLAN ABBREVIATIONS ABOVE FINISHED FLOOR AIR ADMITTANCE VALVE ABOVE FINISHED GRADE AUTOMATIC BUILDING CONTROL SYSTEM BACK DRAFT DAMPER BUILDING AAV AFF AFG AUTO BCS BDD BLDG BETWEEN COMMON (OR CLOSED) COMBUSTION AIR CONTROLS CONTRACTOR CONTINUATION DESIGN BUILD B/N C CA CC CDBBC CUBIC FEET PER MINUTE (AIR FLOW RATE) CAST IN PLACE CEILING (OR COOLING) CONCRETE CONDENSATE CONNECT (OR CONNECTION) CONTRACTOR CFM CIP CLG CONC COND CONN CONTR'R CLEANOUT TO GRADE COTG DOMESTIC HOT WATER RECIRC EXISTING DWR (E) EXHAUST AIR EA ENTERING AIR TEMPERATURE ELECTRICAL CONTRACTOR ENTERING WATER TEMPERATURE EAT EC EXH EXHAUST EWT GENERAL CONTRACTOR GROUND HEAT EXCHANGER GC GHX GALLONS PER MINUTE (WATER FLOW RATE) GPM HORSEPOWER HOT WATER IN LIEU OF HP HW ILO KILOWATTS KW LEAVING AIR TEMPERATURE LINEAR FOOT LEAVING WATER TEMPERATURE LAT LF LWT MECHANICAL CONTRACTOR MC MANUFACTURER MOTOR OPERATED DAMPER NEW MFG MOD (N) NORMALLY CLOSED NC NATIONAL ELECTRIC CODE NOT IN CONTRACT NORMALLY OPEN NEC NIC NO OUTSIDE AIR OA OPPOSED BLADE VOLUME DAMPER ON CENTER OBD OC OUTSIDE AIR OSA RETURN AIR REQUIRED RA REQ'D REQUIREMENTS REQ'MTS SUPPLY AIR SQUARE FOOT (FEET) SA SF STATIC PRESSURE SP STAINLESS STEEL THROW-AWAY (TRANSFER AIR) TYPICAL SS TA TYP UNLESS NOTED OTHERWISE UNO WALL CLEANOUT WCO WITH REGARD TO WATER COOLED TRANSFER WRT W/C XFR DIAMETER Ø BY CONTRACTOR COLD WATER CW HOT WATER RECIRC HWC ABOVE ABV BELOW FINISHED GRADE BFG DOMESTIC WATER DOMESTIC HOT WATER DW DHW DOWN DN DOMESTIC HOT WATER RECIRC DHR COMBINATION FIRE/SMOKE DAMPER FURNISHED BY OWNER FSD FBO FLOOR CLEANOUT FCO FOR CONTINUATION FCT FD FIRE DAMPER REFER TO: RE: WITH W/ CLEANOUT CO FUTURE (F) FREE AREA FA FFI FOR FURTHER INFORMATION WITHOUT W/O VENT THRU ROOF VTR NOTES 1. ALL SYMBOLS, ABBREVIATIONS, AND DESIGNATIONS ON LEGEND SHEET ARE NOT NECESSARILY USED ON THIS PROJECT. 2. THIS DRAWING SET CONSISTS OF DATA GENERATED, IN PART, BY OTHER PARTIES. NOT ALL SYMBOLOGIES AND NOTATION CONVENTIONS OCCURRING IN THIS DRAWING SET ARE NECESSARILY DEFINED ON THESE LEGENDS. CONSULT THE ENGINEER IN THE EVENT SYMBOLOGY OR NOTATION INTERPRETATION IS REQUIRED. PLAN SYMBOLS CONTROL PANEL/RADIANT MANIFOLD CARBON DIOXIDE SENSOR CARBON MONOXIDE SENSOR DIAGRAM CONTINUATION REFERENCE PLUMBING/HVAC RISER POINT OF NEW CONNECTION DUCT STATIC PRESSURE SENSOR ROOM PRESSURE SENSOR EMERGENCY POWER OFF SWITCH ACCESS PANEL SNOWMELT MANIFOLD SECTION CUT LETTER/SHEET SHOWN ON POINT OF DISCONNECTION - SP CO2 EPO P CO - - - P THERMOSTAT HUMIDISTAT REMOTE TEMPERATURE SENSOR T S H H B W H TC FS ROOF DRAIN FLOOR DRAIN FLOOR SINK HORIZONTAL CLEANOUT VERTICAL CLEANOUT DECK/ROOF DRAIN ABOVE PIPING DESIGNATIONS SNOWMELT SUPPLY SNOWMELT RETURN HEATING WATER SUPPLY (HIGH TEMP) HEATING WATER RETURN (HIGH TEMP) CHILLED WATER SUPPLY CHILLED WATER RETURN CONDENSER RETURN HIGH PRESSURE STEAM HIGH PRESSURE CONDENSATE RETURN LOW PRESSURE STEAM LOW PRESSURE CONDENSATE RETURN REFRIGERANT SUCTION REFRIGERANT LIQUID FLOOR COOLING SUPPLY FLOOR COOLING RETURN HEATING WATER SUPPLY (LOW TEMP) HEATING WATER RETURN (LOW TEMP) SOLAR HEATING WATER SUPPLY SOLAR HEATING WATER RETURN GROUND LOOP SUPPLY GROUND LOOP RETURN HEATING WATER SUPPLY HEATING WATER RETURN GLYCOL FEED MEDIUM PRESSURE STEAM MEDIUM PRESSURE CONDENSATE RETURN PUMPED CONDENSATE GEOTHERMAL (OR GROUND) LOOP SUPPLY GEOTHERMAL (OR GROUND) LOOP RETURN CLOSED CONDENSER SUPPLY CLOSED CONDENSER RETURN CONDENSER SUPPLY PLUMBING PIPING CR CS CCR CCS GLR GLS CHR CHS GLR GLS GF HWR HWS HWR(LT) HWS(LT) HWR(HT) HWS(HT) FCR FCS SHWR SHWS SMS SMR PC MPR MPS LPS LPR HPR HPS RS RL STEAM & CONDENSATE PIPING HYDRONIC PIPING 90° ELBOW DOWN (ROUND DUCT ONLY) ROUND 90° ELBOW UP (ROUND DUCT ONLY) OFFSET TO CHANGE ELEVATION (AT 30° WHEN POSSIBLE) D = DROP R = RISE ROUND RADIUS ELBOW 90° STRAIGHT TEE 90° CONICAL TEE 45° BRANCH 45° CONICAL TEE SIZE OR SHAPE TRANSITION ROUND FLEXIBLE DUCT 90° ELBOW DN (NEGATIVE PRESSURE) 90° ELBOW DN (POSITIVE PRESSURE) 90° ELBOW UP (NEGATIVE PRESSURE) 90° ELBOW UP (POSITIVE PRESSURE) 90° RADIUS ELBOW 90° RADIUS ELBOW W/TURNING VANES SQUARE DUCT SPLIT ROUND DUCT SPLIT SUMP PUMP SP MECHANICAL SYSTEMS LEGEND ABOVE SEA LEVEL PROJECT ALTITUDE 5,292' ' ' ISSUE LOG KEY: # DATE ISSUE LOG MECHANICAL SHEET INDEX TITLE MECHANICAL COVER SHEET M0-01 100% DD 02.22.2018 ISSUED AS PART OF A SET ' ' NOT PART OF SET ' ' ISSUED FOR INFORMATION ONLY * MECHANICAL DEMOLITION PLAN M-1-01 MECHANICAL DETAILS M-5-01 MECHANICAL SCHEDULES M-6-01 MECHANICAL PLAN M-1-02 MECHANICAL ROOM ENLARGED PLAN M-1-03 95% CD's 04.30.2018 MECHANICAL CONTROLS M-7-01 100% CD's 05.25.2018 SAN JUAN REGIONAL MEDICAL CENTER Emergency Department Renovation Mail: Phone: 48 C.R. 25O/ STE. 3/ DURANGO Physical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774 RMKM ARCHITECTURE, P.C. ALBUQUERQUE | AVON | DENVER | FORT COLLINS 303.278.3820 www˛bgbuildingworks˛com Project No. 9659.00 Copyright 2016 MECHANICAL COVER SHEET M0-01

Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

  • Upload
    haminh

  • View
    216

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

SINGLE LINE DESCRIPTION DOUBLE LINE

D D

SPLIT BRANCH TAKE-OFF WITH SQUAREELBOW & SPLITTER DAMPER

SPLIT BRANCH TAKE-OFF WITH RADIUSELBOW & SPLITTER DAMPER

POSITIVE PRESSURE RISER,TYPICALLY SUPPLY

NEGATIVE PRESSURE RISER, TYPICALLYRETURN, EXHAUST OR OUTSIDE AIR

F/S COMBINATION FIRE & SMOKE DAMPER F/S

FIRE DAMPER

MOTOR OPERATED DAMPER (MOD)

MANUAL VOLUME DAMPER, SINGLE BLADEDAMPER (SBD) FOR ROUND OR <10" TALL,OPPOSED BLADE DAMPER (OBD) >10" TALL

BACKDRAFT DAMPERBDD BDD

SMOKE DAMPER

SMOKE DETECTOR

DUCT SIZE: FIRST NUMBER IS PLAN WIDTH,SECOND NUMBER IS DEPTH.

24x3624x36

DUCTWORK LEGEND

SDSD

PRESSURE REDUCING VALVE

SHOCK ABSORBER

STRAINER W/ BLOW-OFF VALVE

SAFETY RELIEF VALVE

VACUUM BREAKER

PRESSURE GAUGE W/ PIG TAIL & COCK

THERMOMETER

PRESSURE - TEMP. TAP

AIR VENT

PIPE ANCHOR

FLEXIBLE CONNECTOR

PIPE EXPANSION JOINT

PIPE UNION

DOUBLE CHECK BACKFLOW PREVENTER

PUMP & EQUIPMENT CONNECTOR

TEMPERATURE CONTROL VALVE (2-WAY)

DRAIN VALVE W/ HOSE END

PLUG VALVE IN RISER

FLOW BALANCING VALVE

GATE OR GLOBE VALVE IN RISER

FLOW CONTROL VALVE

BALL VALVE

PLUG OR BALANCING VALVE

CHECK VALVE

GLOBE VALVE

BUTTERFLY VALVE

VENTURI/FLOW INDICATOR

TEMPERATURE CONTROL VALVE (3-WAY)

SOLENOID VALVE

90° ELBOW UP

TEE UP

TEE DOWN

SHUT OFF (BALL, GATE, BUTTERFLY)

PIPING SYMBOLS90° ELBOW DN

S

FLOW SWITCH

HOSE BIBB

WALL HYDRANT

TEMPERATURE CONTROLLER OR SENSOR

STEAM TRAP TEST CHAMBER

STEAM TRAP:FT-FLOAT & THERMOSTATICTD-THERMODYNAMICIB-INVERTED BUCKETTS-THERMOSTATICBP-BALANCED PRESSURE

EQUIPMENT ABBREVIATIONSAIR HANDLING UNITAHU

AIR SEPARATORAS

BOILER (HOT WATER)B

BASE BOARDBB

BUFFER TANKBT

CONSTANT VOLUME BOXCV

DISHWASHER EXHAUST FANDEF

ELECTRIC BASEBOARD HEATEREBH

FURNACEF

FAN COILFC

FAN POWERED BOXFP

GLYCOL FEEDERGF

HUMIDIFIER

HC HEATING COIL

HP HEAT PUMP

HX HEAT EXCHANGER

KITCHEN EXHAUST FANKEF

MAKE-UP AIR UNITMAU

MOTOR CONTROL CENTERMCC

MIXING VALVEMV

PUMP P

RETURN (OR RELIEF) AIR FANRF

RADIANT ZONERZ

SNOWMELT AREASA

SUMP BASINSB

SUPPLY FANSF

STORAGE TANKST

THERMOSTATIC MIXING VALVETMV

UNIT HEATERUH

VARIABLE VOLUME BOXVV

WATER HEATERWH

H

CHILLERCH

COOLING COILCC

CIRC PUMPCP

CABINET UNIT HEATERCUH

COOLING TOWERCT

DUCT COILDC

ELECTRIC WATER HEATEREWH

EVAPORATIVE COOLING UNITECU

ENERGY RECOVERY UNITERU

EXHAUST FANEF

EXPANSION TANKET

VARIABLE VOLUME BOX W/ REHEATVR

TYPE OF AIR DEVICERE: GRD SCHEDULE.

AIR DEVICE DESIGNATION KEY

#CAEXHOSARAXFR

SIZE (INCHES) OR MINIMUMFREE AREA REQUIRED INSQUARE FEET.

NOTE:FOR STANDARD MODULE SIZE REGISTERS, SIZE GIVEN ISNECK SIZE. REFER TO GRD SCHEDULE FOR MODULE SIZE.

INDICATES AIRINLET DEVICE.

======

AIR QUANTITY (CFM)COMBUSTION AIREXHAUSTOUTSIDE AIRRETURNTRANSFER

BXFR12x6

A15012x6

PLAN ABBREVIATIONS

ABOVE FINISHED FLOOR

AIR ADMITTANCE VALVE

ABOVE FINISHED GRADE

AUTOMATIC

BUILDING CONTROL SYSTEM

BACK DRAFT DAMPER

BUILDING

AAV

AFF

AFG

AUTO

BCS

BDD

BLDG

BETWEEN

COMMON (OR CLOSED)

COMBUSTION AIR

CONTROLS CONTRACTOR

CONTINUATION DESIGN BUILD

B/N

C

CA

CC

CDBBC

CUBIC FEET PER MINUTE (AIR FLOW RATE)

CAST IN PLACE

CEILING (OR COOLING)

CONCRETE

CONDENSATE

CONNECT (OR CONNECTION)

CONTRACTOR

CFM

CIP

CLG

CONC

COND

CONN

CONTR'R

CLEANOUT TO GRADECOTG

DOMESTIC HOT WATER RECIRC

EXISTING

DWR

(E)

EXHAUST AIREA

ENTERING AIR TEMPERATURE

ELECTRICAL CONTRACTOR

ENTERING WATER TEMPERATURE

EAT

EC

EXH EXHAUST

EWT

GENERAL CONTRACTOR

GROUND HEAT EXCHANGER

GC

GHX

GALLONS PER MINUTE (WATER FLOW RATE)GPM

HORSEPOWER

HOT WATER

IN LIEU OF

HP

HW

ILO

KILOWATTSKW

LEAVING AIR TEMPERATURE

LINEAR FOOT

LEAVING WATER TEMPERATURE

LAT

LF

LWT

MECHANICAL CONTRACTORMC

MANUFACTURER

MOTOR OPERATED DAMPER

NEW

MFG

MOD

(N)

NORMALLY CLOSEDNC

NATIONAL ELECTRIC CODE

NOT IN CONTRACT

NORMALLY OPEN

NEC

NIC

NO

OUTSIDE AIROA

OPPOSED BLADE VOLUME DAMPER

ON CENTER

OBD

OC

OUTSIDE AIROSA

RETURN AIR

REQUIRED

RA

REQ'D

REQUIREMENTSREQ'MTS

SUPPLY AIR

SQUARE FOOT (FEET)

SA

SF

STATIC PRESSURESP

STAINLESS STEEL

THROW-AWAY (TRANSFER AIR)

TYPICAL

SS

TA

TYP

UNLESS NOTED OTHERWISEUNO

WALL CLEANOUTWCO

WITH REGARD TO

WATER COOLED

TRANSFER

WRT

W/C

XFR

DIAMETERØ

BY CONTRACTOR

COLD WATERCW

HOT WATER RECIRCHWC

ABOVEABV

BELOW FINISHED GRADEBFG

DOMESTIC WATER

DOMESTIC HOT WATER

DW

DHW

DOWNDN

DOMESTIC HOT WATER RECIRCDHR

COMBINATION FIRE/SMOKE DAMPER

FURNISHED BY OWNER

FSD

FBO

FLOOR CLEANOUTFCO

FOR CONTINUATIONFCT

FD FIRE DAMPER

REFER TO:RE:

WITHW/

CLEANOUTCO

FUTURE(F)

FREE AREAFA

FFI FOR FURTHER INFORMATION

WITHOUTW/O

VENT THRU ROOFVTR

NOTES1. ALL SYMBOLS, ABBREVIATIONS, AND DESIGNATIONS

ON LEGEND SHEET ARE NOT NECESSARILY USED ONTHIS PROJECT.

2. THIS DRAWING SET CONSISTS OF DATA GENERATED, INPART, BY OTHER PARTIES. NOT ALL SYMBOLOGIES ANDNOTATION CONVENTIONS OCCURRING IN THISDRAWING SET ARE NECESSARILY DEFINED ON THESELEGENDS. CONSULT THE ENGINEER IN THE EVENTSYMBOLOGY OR NOTATION INTERPRETATION ISREQUIRED.

PLAN SYMBOLSCONTROL PANEL/RADIANT MANIFOLD

CARBON DIOXIDE SENSOR

CARBON MONOXIDE SENSOR

DIAGRAM CONTINUATION REFERENCE

PLUMBING/HVAC RISER

POINT OF NEW CONNECTION

DUCT STATIC PRESSURE SENSOR

ROOM PRESSURE SENSOR

EMERGENCY POWER OFF SWITCH

ACCESS PANEL

SNOWMELT MANIFOLD

SECTION CUT LETTER/SHEET SHOWN ON

POINT OF DISCONNECTION

-

SP

CO2

EPO

P

CO

--

-P

THERMOSTAT

HUMIDISTAT

REMOTE TEMPERATURE SENSOR

T

S

H

H B

W H

TC

FS

ROOF DRAIN

FLOOR DRAIN

FLOOR SINK

HORIZONTAL CLEANOUT

VERTICAL CLEANOUT

DECK/ROOF DRAIN ABOVE

PIPING DESIGNATIONS

SNOWMELT SUPPLY

SNOWMELT RETURN

HEATING WATER SUPPLY (HIGH TEMP)

HEATING WATER RETURN (HIGH TEMP)

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CONDENSER RETURN

HIGH PRESSURE STEAM

HIGH PRESSURE CONDENSATE RETURN

LOW PRESSURE STEAM

LOW PRESSURE CONDENSATE RETURN

REFRIGERANT SUCTION

REFRIGERANT LIQUID

FLOOR COOLING SUPPLY

FLOOR COOLING RETURN

HEATING WATER SUPPLY (LOW TEMP)

HEATING WATER RETURN (LOW TEMP)

SOLAR HEATING WATER SUPPLY

SOLAR HEATING WATER RETURN

GROUND LOOP SUPPLY

GROUND LOOP RETURN

HEATING WATER SUPPLY

HEATING WATER RETURN

GLYCOL FEED

MEDIUM PRESSURE STEAM

MEDIUM PRESSURE CONDENSATE RETURN

PUMPED CONDENSATE

GEOTHERMAL (OR GROUND) LOOP SUPPLY

GEOTHERMAL (OR GROUND) LOOP RETURN

CLOSED CONDENSER SUPPLY

CLOSED CONDENSER RETURN

CONDENSER SUPPLY

PLUMBING PIPING

CR

CS

CCR

CCS

GLR

GLS

CHR

CHS

GLR

GLS

GF

HWR

HWS

HWR(LT)

HWS(LT)

HWR(HT)

HWS(HT)

FCR

FCS

SHWR

SHWS

SMS

SMR

PC

MPR

MPS

LPS

LPR

HPR

HPS

RS

RL

STEAM & CONDENSATE PIPING

HYDRONIC PIPING90° ELBOW DOWN (ROUND DUCT ONLY)

ROUND 90° ELBOW UP (ROUND DUCT ONLY)

OFFSET TO CHANGE ELEVATION(AT 30° WHEN POSSIBLE)

D = DROP R = RISE

ROUND RADIUS ELBOW

90° STRAIGHT TEE

90° CONICAL TEE

45° BRANCH

45° CONICAL TEE

SIZE OR SHAPE TRANSITION

ROUND FLEXIBLE DUCT

90° ELBOW DN (NEGATIVE PRESSURE)

90° ELBOW DN (POSITIVE PRESSURE)

90° ELBOW UP (NEGATIVE PRESSURE)

90° ELBOW UP (POSITIVE PRESSURE)

90° RADIUS ELBOW

90° RADIUS ELBOW W/TURNING VANES

SQUARE DUCT SPLIT

ROUND DUCT SPLIT

SUMP PUMPSP

MECHANICAL SYSTEMS LEGEND

ABOVE SEA LEVEL

PROJECT ALTITUDE5,292'

' 'ISSUE LOG KEY:

#

DA

TE

ISSUE LOG

MECHANICAL SHEET INDEX

TITLE

MECHANICAL COVER SHEETM0-01

100%

DD

02.2

2.20

18ISSUED AS PART OF A SET' ' NOT PART OF SET' ' ISSUED FOR INFORMATION ONLY*

√√√

MECHANICAL DEMOLITION PLANM-1-01

MECHANICAL DETAILSM-5-01MECHANICAL SCHEDULESM-6-01

MECHANICAL PLANM-1-02

√√MECHANICAL ROOM ENLARGED PLANM-1-03

95%

CD'

s

04.3

0.20

18

√√√

√√√

√MECHANICAL CONTROLSM-7-01 √

100%

CD'

s

√√√

√√√

05.2

5.20

18

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

MECHANICALCOVER SHEET

M0-01

Page 2: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

74"x 34"(E)

80"x 32"(E)

80"x

32"

(E)

74"x

34"

(E)

26"x20"(E)

22"x20"(E)

34"x10"(E)

34"x

10"

(E)

18"x

10"

(E)

F/S

26"x 20"(E)

26"x 20"(E)

26"x20"(E)

14"x 14"(E)

12"Ø

(E)

F/S

F/S

22"x20"(E)

16"x14"(E)

8"Ø(E

)10

"x8"

(E)

T

14"x 12"(E)

8"Ø(E

)

10"Ø

(E)

T

26"x20"(E)

26"x 20"(E)8"x 8"(E)

F/S

14"x14"(E)

12"x12"(E)

14"Ø

(E)

8"x8"(

E)

12"x10" (E)

10"Ø

(E)

T

T

22"x14"(E)12"x10"(E)

16"x

10"(

E)

T

18"x18"(E)

18"x16"(E)

16"x14"(E)

16"Ø(E)

T

T

10"Ø(E)

12"Ø(E)

10"x10"(E)

18"x16"(E)

16"x10"(E)

T

T

14"x12"(E)

38"x10"(E)

38"x10"(E)

F/S

F/S

F/S

F/S

8"x8"(

E)

F/S

F/S

F/S

F/S

F/S

F/S

F/S

14"x14"(E)

18"x16"(E)

14"x12"(E)

16"x14"(E)

MVDMVD

MVD

MVD

F/S

F/S

F/S

32"x

14"(

E)

T

16"Ø

(E)

8"x8"(E)F/S

F/S

F/S

12"x12"(E)

16"x

16"(

E)

F/S

F/S

F/S

F/S

T

24"x20"(E)

16"Ø(E)

20"x

20"(

E)

12"x12"(E)12"x12"(E)

24"x

22"(

E)

24"x

24"(

E)

26"x24"(E)

50"x

22"(

E)

24"x22"(E) 20"x20"(E) 18"x18"(E)

34"x

22"(

E)

14"x12"(E)

10"x

10"(

E)

10"x10"(E)12"x10"(E)16"x14"(E)

14"x12"(E)

12"x12"(E)

6"x6"(E)

10"x10"(E)

F/S

16"x

14"(

E)

12"x12"(E) 16"x14"(E)8"x6"(E)

10"x

10"(

E)

T

TT

T

TT

F/S

14"x14"(E)

16"x

16"(

E)

12"x10"(E)

T

18"x16"(E)

TT

T

T

T

T

T

T

T

T T

12"x

12"(

E)

8"x8

"(E

)

16"x14"(E)24"x10"(E) 20"x18"(E)28"x8"(E)

26"x12"(E)

26"x14"(E)

30"x8"(E)

12"x12"(E)

55"x20"(E)

8"Ø (E) 10"Ø (E)

10"Ø (E)8"Ø (E)

10"Ø (E)

10"Ø

(E)

8"Ø (E)

TT

111

1

1

1

1

1

1

1

1

1

1 11 1 1

1

1 1

1

1

1

1

1

1

1

1

1

1

14"x14"(E) 18"x8"(E) 12"x12"(E)

22

22

T4

55

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

MECHANICALDEMOLITION PLAN

M1-01Scale:

1 MECHANICAL DEMOLITION PLAN1/8"=1'-0"

FLAG NOTES:#

1. EXISTING TERMINAL UNIT TO REMAIN. REMOVECONTROLS INCLUDING ACTUATORS, WIRING, TUBING,AND THE ASSOCIATED THERMOSTAT.

2. REMOVE GRILLES IN THE ROOM AS SHOWN. REMOVEASSOCIATED FLEX. NOTE NECK SIZE OF EXISTINGGRILLE FOR REPLACEMENT.

3. REMOVE LOW PRESSURE DUCT BACK TO REHEATCOIL.

4. CAREFULLY REMOVE THERMOSTAT FROM WALL ANDRETAIN FOR RE-USE OR SALVAGE TO OWNER.REMOVE ANY AND ALL PNEUMATIC TUBING BACK TOMAIN LINE AND CAP. REMOVE ANY WIRINGASSOCIATED WITH THE THERMOSTAT.

5. CAREFULLY REMOVE SUPPLY GRILLE FROM CEILINGAND KEEP FOR RE-INSTALLATION IN THE NEW CEILING.

1. ADDITIONAL STORM, HYDRONIC, DOMESTIC, WASTEAND VENT PIPING MAY BE ROUTED IN SPACE THAT ISNOT REPRESENTED, BUT IS TO REMAIN. OTHERSYSTEMS MAY EXIST WITHIN THE SPACE THAT ARENOT REPRESENTED ON THESE DRAWINGS;MODIFICATIONS TO THESE SYSTEMS ARE NOTANTICIPATED.

2. FIELD VERIFY ALL COMPONENTS PRIOR TODEMOLITION. THE INFORMATION ON THIS SHEET WASOBTAINED, IN PART, FROM HISTORIC DESIGNDRAWINGS. ONLY PORTIONS OF THE SYSTEMS WEREACCESSIBLE FOR VISUAL CONFIRMATION DURINGDESIGN PROCESS.

3. PROVIDE PRELIMINARY TESTING OF EXISTINGHYDRONIC SYSTEMS. MEASURE CURRENT FLUIDFLOW RATE THROUGH ALL EXISTING COILS, RADIANT,AND SNOWMELT ZONES FOR THE CURRENTLYINSTALLED SYSTEMS. SUBMIT REPORT OF MEASUREDVALUES TO ENGINEER FOR REVIEW ANDCONFIRMATION OF SYSTEM DESIGN ASSUMPTIONSPRIOR TO DEMOLITION.

4. PROVIDE PRELIMINARY TESTING OF EXISTING HVACDUCTWORK SYSTEMS. MEASURE CURRENT AIRFLOW RATES AT ALL EXISTING SUPPLY, RETURN, ANDEXHAUST REGISTERS. MEASURE TOTAL AIR FLOWSAT MAIN DUCT BRANCHES AND ALL FAN SYSTEMS.SUBMIT REPORT OF MEASURED VALUES TOENGINEER FOR REVIEW AND CONFIRMATION OFSYSTEM DESIGN ASSUMPTIONS PRIOR TODEMOLITION.

5. (E) WASTE SYSTEM SERVING SPACE IS LOCATED INTHE CEILING OF THE SPACE BELOW.

6. REMOVE ALL MECHANICAL ITEMS INDICATED.

7. TEMPORARILY SEAL OR CAP PIPING TO BE RE-USEDFOR LATER CONNECTION.

8. SEAL ALL OPEN DUCTS DURING CONSTRUCTION TOMITIGATE DUST AND DEBRIS FROM SYSTEM. CAPDUCTWORK IN LOCATIONS THAT ARE NOT BEINGRECONNECTED.

9. REMOVE ALL DEMOLISHED COLD WATER, HOT WATERAND HOT WATER RECIRCULATION PIPING BACK TOBRANCH FROM MAIN TO ELIMINATE ALL DEAD ENDS INDOMESTIC WATER PIPING.

10. NOTIFY ENGINEER IMMEDIATELY OF ANYDISCREPANCIES OF INFORMATION REPRESENTED INTHE DOCUMENTS VERSUS WHAT IS FOUND IN THEFIELD.

11. COORDINATE PATCHING AND REPAIRS OF WALLS,CEILINGS AND FLOORS WITH ARCHITECT.

12. PATCH STRUCTURAL OPENINGS IN FLOORS, WALLSAND ROOFS THAT WERE PREVIOUSLY OCCUPIED BYSYSTEMS AND EQUIPMENT DEMOLISHED UNDER THISCONTRACT IN ACCORDANCE WITH STRUCTURALENGINEER'S REQUIREMENTS.

13. ALL EXISTING COMBINATION FIRE/SMOKE DAMPERSDEPICTED ON THIS SHEET SHALL BE REMOVED.

DEMOLITION NOTES:

Scale:

2 RADIOLOGY CORRIDOR FLOOR PLAN1/8"=1'-0"

Page 3: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc
Page 4: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

AHU-2 (E)1

EXISTINGMECH./ELEC

AHU-1 (E)1

OAF-1 (E)2

60"x28" (E)

60"x

28" (

E)

80"x

32" (

E)

MVD

MVD

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

MECHANICAL ROOMENLARGED PLAN

M1-03

Scale:

1 MECHANICAL ROOM ENLARGED PLAN1/4"=1'-0"

FLAG NOTES:#

1. ALL EXISTING PNEUMATIC CONTROLS SHALL BECAREFULLY REMOVED. THE HYDRONIC VALVES SHALLBE REPLACED. DAMPER ACTUATORS SHALL FIELDVERIFY THE LOCATION SIZE AND TYPE OF ALLHYDRONIC CONTROL VALVES AND ACTUATORS FORREPLACEMENT AS A PART OF THE DIRECT DIGITALCONTROLS UPGRADE. VERIFY EXISTING DAMPERACTUATORS AND REPLACE WITH NEW.

2. APPROXIMATE LOCATION FOR EXISTING OUTSIDE AIRFAN.

1. RE: _/M_ SERIES FOR MECHANICAL DIAGRAMS.

2. COORDINATE ROUTING OF CONDENSATE DRAINLINES WITH ARCHITECT PRIOR TO INSTALLATION.

3. CEILING COORDINATION OF ALL MEP SYSTEMS(LIGHTING, DUCTWORK, DIFFUSERS, ELECTRICAL,FIRE PROTECTION, ETC.) MUST BE COMPLETED BYTHE CONTRACTOR PRIOR TO THE START OF ANYINSTALLATIONS.

4. DO NOT ROUTE DUCTWORK OVER ELECTRICALROOMS OR ELECTRICAL PANELS; MAINTAIN N.E.C.CLEARANCES. COORDINATE ROUTINGS WITH DIV. 16CONTRACTOR.

5. CONTRACTOR TO MAINTAIN 8'-6" CLEAR HEAD HEIGHTIN GARAGE AND INFORM THE ENGINEER ANDARCHITECT OF ANY AREAS THAT MAY NOT MEET 8'-6"PRIOR TO INSTALLATION, MINIMUM 8'-2" CLEAR HEADHEIGHT MUST BE MAINTAINED IN ACCESSIBLE VANAREAS.

6. PROVIDE FLEXIBLE DUCT AND PIPE CONNECTIONS TOALL MOTORIZED EQUIPMENT.

7. VERIFY ALL EQUIPMENT ACCESS PANELS WITHMANUFACTURER AND ARCHITECT.

8. ALL SOURCES OF IGNITION ON MECHANICALEQUIPMENT SHALL BE MOUNTED 18" AFF.

9. PROTECT PIPING ROUTED ALONG COLUMNS, WALLS,ETC. FROM DAMAGE AS NECESSARY WITH CAGES.COORDINATE WITH ARCHITECT.

10. PEX PIPING SHALL NOT BE ALLOWED TO PENETRATEFIRE BARRIERS WHERE FIRE CAULKING IS REQUIRED.

11. THE SPACE ABOVE CEILING IS BEING UTILIZED AS ARETURN AIR PLENUM. ALL RETURN GRILLES SHALL BEPROVIDED WITH SOUND BOOTS AND A DIRECT PATHTO THE AIR HANDLING SYSTEM RETURN DUCT, OPENTO PLENUM. WHERE FULL HEIGHT WALLS AREINSTALLED AND THE RETURN AIR PATH ISCOMPROMISED, THE SOUND BOOT SHALL EXTENDTHROUGH THE WALL OR TRANSFER AIR DUCTSSHALL BE PROVIDED. OTHERWISE, PROVIDE Z- OR U-DUCT TRANSFER THROUGH WALL. TRANSFER DUCTSAND SOUND BOOTS SHALL BE LINED SHEET METAL.NON-METAL DUCT NOT PERMITTED.

12. T-STATS AND CO2 SENSORS SHALL BE LOCATEDNEAR THE LIGHT SWITCH WITHIN THE ROOM SHOWN.COORDINATE WITH ARCHITECT & ELECTRICALENGINEER TO MATCH HEIGHT AND LOCATION.

13. ALL DUCTWORK SHALL BE ROUTED AS HIGH ASPOSSIBLE IN THE CEILING SPACE. UTILIZE JOISTSPACE WHEN POSSIBLE, ESPECIALLY WHERECROSSING OTHER DUCTS, PIPES, AND ELECTRICAL.

14. ACCESS PANELS SHALL BE 24x24, U.N.O. LOCATIONSSHOWN ARE APPROXIMATE, EXACT LOCATIONSSHALL BE COORDINATED WITH THE ARCHITECTSDRAWINGS AND WITH THE LOCATIONS OF THEEQUIPMENT OR APPARATUS THAT THEY SERVE.

15. SEAL ALL DUCT PENETRATIONS OF ACOUSTICPARTITIONS.

HVAC NOTES:

Page 5: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

EXTERIOR DUCTINSULATION.

INSULATED ACOUSTICFLEX DUCT. 5'-0"MAXIMUM LENGTH

INTERNALLY LINED SUPPLYDUCT, OR AS NOTED INSPECIFICATIONS.

CONICAL SPIN-IN FITTING WITHMANUAL VOLUME DAMPER.

SHEET METALSTRAP.

S.S. WORM DRIVECLAMP.

SQUARE TO ROUND ADAPTERAS REQUIRED.

SHEET METALSHIELD.

SUPPORT AS REQUIREDFOR MIN RADIUSSPECIFIED.

MINIMUM ℄ RADIUS > 1.5 xFLEX DUCT DIAMETER.

CEILING DIFFUSER

NO SCALE

TYPICAL DIFFUSER CONNECTION DIAGRAM OFF DIAGRAM45° DUCT TAKE-

45°

NO SCALE

DAMPER IF H<8"

TAKE-OFF.AROUND ENTIRESEAL AIRTIGHT

OPPOSED BLADEDAMPER IF H>=8"

SINGLE BLADE

6" MINIMUM.1/4 OF "W" OR

ENDBEARING

W

H

GRILLE CONNECTION DIAGRAMEXHAUST/DUCTED RETURN

NO SCALE

FLEX DUCT CONNECTION FORLAY-IN CEILING, SHEET METALCONNECTION OVER HARD CEILING

SHEET METAL PLENUM(NO INSULATION). MATCHGRILLE NECK. HEIGHT 4"HIGHER THANCONNECTION.

WORM DRIVE S.S.CLAMP.

CEILING DIFFUSER.

FIRE DAMPER AND FIRE/SMOKE

NO LINING REQ'D.

SOLID METAL STUDNO LINING WITH

FRAMING.

THE WALL.EQUAL TO THAT ONMATERIAL OF RATINGWITH FIRE RESISTIVEOPENING TO BE LINED

CONCRETE OR MASONRY

METAL STUD

NO SCALE

WOOD STUD

WALLSLEEVE.

MAX. DIMENSIONS ASSOCIATED WITH THE TESTCONNECTION. ALL U.L. LISTED DAMPERS ALSO HAVESLEEVE THICKNESS IS CONTINGENT ON TYPE OFTO TERMINATE AT SLEEVES OR DAMPER FRAMES.BY U.L. STANDARD 555 ALL DUCTS ARE REQUIRED

LINKAGE ASSEMBLY OUT OF

THIS DIAGRAM IS NOT INTENDED TO

AND FIRE/SMOKE DAMPER INSTALLATION.COVER ALL CASES OF FIRE DAMPER

HOWEVER SLEEVE THICKNESS MUST ALSO NOT BELESS THAN DUCT GAGE OR THAT SPECIFICALLYAUTHORIZED BY A RECOGNIZED AUTHORITY.

SLEEVE

SHEET METAL DUCT.

DAMPER FRAME.

BREAKAWAY DUCTCONNECTION.

RECESSED DAMPER AND

RECOMMENDED MIN. SLEEVE THICKNESS

CONNECTION

CONNECTION

CONNECTION

85" UP

55"-84"

31"-54"

RATING.

18

20

22

FIRE RESISTIVE MATERIAL.

BREAKAWAY

CONNECTIONTYPE OFSLEEVE.

ANGLE.

13"-30"

RECTANGULARIN DIA. ORDUCT DIM.

12" DN

24

GAGE

26

.036"

.047"

.030"

.024"

.018"

UNCOATED STEELTHICKNESS

MIN. SLEEVECOATEDSTEEL

WALL.

RETAINING ANGLE.

CLOSURE DETAIL.

AIRSTREAM.

PROVIDE ACCESS PANELS ASREQUIRED.

1.1.

2.

NOTES:

DAMPER ASSEMBLY DIAGRAM

ROOF EXHAUST FAN DIAGRAMNO SCALE ( FLAT ROOF )

EXHAUST FAN.

BIRD SCREEN.

PRE-FAB CURB WITH11

2" INSULATION.

ROOFING.

BACKDRAFT DAMPER.

ANCHOR FAN TO CURB.

RUN FLASHING UPUNDER FAN BASE.

FLASHING AND COUNTERFLASHING.

NOTE:COORDINATE ROOF PENETRATIONS WITHROOFING MANUFACTURER.

TERMINAL UNIT DIAGRAM

HWR

HWS

NO SCALE

NOTE:PIPING COMPONENTS MAY BE INCLUDEDIN COMBINATION VALVE PACKAGED BYAUTOMATIC FLOW CONTROL VALVEMANUFACTURER.

NEW SWIVELUNION.

NEW BALLVALVE, TYP.

NEW PRESSURE ANDTEMP. TAP, TYP.

NEW 2-WAYCONTROL VALVE

W/ AUTOMATICFLOW CONTROL

PROVIDE MANUAL AIRVENT IF NOT PRESENT

NEW CONTROLS WITH24V DAMPERACTUATOR

NEWY-STRAINER

EXISTING TERMINALUNIT

EXISTING EXISTINGDUCT DUCT

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

MECHANICALDIAGRAMS

M5-01

Page 6: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

GRILLE, REGISTER, DIFFUSER & LOUVER

SYMBOL TYPE PATTERN FINISH MANUFACTURER*& MODEL # ACCESSORIES REMARKS

SUPPLY 4-WAY WHITE KRUEGER PRISM LAY- IN CEILING 24x24

SUPPLY 4-WAY WHITE KRUEGER PRISM HARD CEILING 24x24

RETURN/EXHAUST EGG CRATE WHITE KRUEGER EGC5 LAY-IN CEILING 24x24

RETURN/EXHAUST EGG CRATE WHITE KRUEGER EGC5 LAY-IN CEILING 24x12

RETURN/ EXHAUST EGG CRATE WHITE KRUEGER EGC5 HARD CEILING 12x12

RETURN/EXHAUST EGG CRATE WHITE KRUEGER EGC5 HARD CEILING 24x24

EXHAUST SIDE WALL WHITE KRUEGER 1500 OBDSEE PLANS FOR SIZES

15° DEFLECTION 7/32" BARSw/ 1/2" BAR SPACING

MANUFACTURERS:GRD PRICE, TITUS

LOUVER GREENHECK, L&D, RUSKIN

GENERAL NOTES:A:

B:

A

B

C

D

E

F

G

GRILL ANDDIFFUSERNECK SIZESCHEDULE

CFM ROUND NECKSIZE

90-130 6

131-220 8

201-330 10

331-440 12

441-540 14

541-650 15

EXHAUST FAN SCHEDULE

MARK SERVICE TYPE

FAN MOTORSOUND DATA

MANUFACTURER*& MODEL #

WEIGHT(LBS.) ACCESSORIES REMARKS

CFM

ESP

BHP HP VOLT/PHASE

IN WC 63 Hz 125 Hz 250 Hz 5000 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

EF-1 LOCKERS DOWNBLAST 100 0.35 0.02 1/4 115/1 76 76 72 66 57 56 52 46 GREENHECK G-097-VG 150 24" ROOF CURB -

EF-2 TRIAGE UTILITY SET 350 0.5 0.09 1 / 4 115 / 1 77 78 70 68 64 59 51 42 GREENHECK SWD-7-VG 150ECM MOTOR

CONTROL DIAL FORBALANCING

MANUFACTURERS: * COOK, GREENHECK

GENERAL NOTES:A:B:C:

AHU-2 TERMINAL BOX SCHEDULE

MARK LOCATION/TYPE

INLET DIA.(IN.)

MAX.COOLING

CFM

MIN.COOLING

CFM

MAX.HEATING

CFM

MAX PD (IN.W.C.)

DISCH. N.C.@ 1.0" S.P.

RADIATEDN.C. @ 1.0"

S.P.

HEATING COILMANUFACTURER* &

MODEL # ACCESSORIES REMARKSE.A.T.DB (°F)

L.A.T.DB (°F)

SENSIBLEMBH

E.W.T.(°F)

L.W.T.(°F) GPM PIPE SIZE

MAX.WATER P.D.

(FT.)

NUMBEROF ROWS

TU-18 EXAMROOMS 12 370 370 370 0.35 24 24 55 95 13.2 180 140 1.3 3/4 5 2 EXISTING -

TU-19 NURSE 8 900 900 900 0.35 24 24 55 95 32.1 180 140 3.2 3/4 5 2 EXISTING -

TU-20 TREATMENT 16 900 900 900 0.35 24 24 55 95 32.1 180 160 3.2 3/4 5 2 EXISTING -

TU-21 X-RAY 14 1410 1410 1410 0.35 24 24 55 95 50.3 180 160 5.0 1 5 2 EXISTING -

TU-22 CORRIDOR 8 620 620 620 0.35 24 24 55 95 22.0 180 160 2.2 3/4 5 2 EXISTNG

TU-23 STORAGE 6 615 615 615 0.35 24 24 55 95 22.0 180 160 2.2 3/4 5 2 EXISTNG

TU-24 PSYCH 6 125 125 125 0.35 24 24 55 95 4.5 180 160 0.5 3/4 5 2 EXISTNG

TU-25 TRAUMA 10 1160 1160 1160 0.35 24 24 55 95 41.4 180 160 4.1 1 5 2 EXISTNG

TU-26 TRAUMA 10 1160 1160 1160 0.35 24 24 55 95 41.4 180 160 4.1 1 5 2 EXISTNG

TU-27 ELEV EQUIP 8 415 415 415 0.35 24 24 55 95 14.8 180 160 1.5 3/4 5 2 EXISTNG

TU-28 ELEV LOBBY 8 275 275 275 0.35 24 24 55 95 9.9 180 160 0.9 3/4 5 2 EXISTNG

TU-29 MULTIPATIENT 8 800 800 800 0.35 24 24 55 95 28.6 180 160 2.8 3/4 5 2 EXISTNG

TU-30 WAITING 12 1300 1300 1300 0.35 24 24 55 95 46.4 180 160 4.6 1 5 2 EXISTNG

MANUFACTURERS: * ENVIROTEC, KRUEGER, TITUS

GENERAL NOTES:A: PROVIDE 120V/24V TRANSFORMER FOR NEW DDC CONTROLSB:

AHU-1 TERMINAL BOX SCHEDULE

MARK LOCATION/TYPE

INLET DIA.(IN.)

MAX.COOLING

CFM

MIN.COOLING

CFM

MAX.HEATING

CFM

MAX PD (IN.W.C.)

DISCH. N.C.@ 1.0" S.P.

RADIATEDN.C. @ 1.0"

S.P.

HEATING COILMANUFACTURER* &

MODEL # ACCESSORIES REMARKSE.A.T.DB (°F)

L.A.T.DB (°F)

SENSIBLEMBH

E.W.T.(°F)

L.W.T.(°F) GPM PIPE SIZE

MAX.WATER P.D.

(FT.)

NUMBEROF ROWS

TU-1 RESTROOM/CORRIDOR 12 1200 600 600 0.35 24 24 55 95 37.5 180 140 2.1 3/4 5 2 EXISTING -

TU-2 VESTIBULE 8 420 420 420 0.35 24 24 55 95 15.1 180 140 1.5 3/4 5 2 EXISTING -

TU-3 WAITING 16 1150 1150 1150 0.35 24 24 55 95 41.0 180 160 4.1 1 5 2 EXISTING -

TU-4 WAITING 14 750 750 750 0.35 24 24 55 95 26.8 180 160 2.7 3/4 5 2 EXISTING -

TU-5 TRIAGE 8 275 275 275 0.35 24 24 55 95 9.9 180 160 1.0 3/4 5 2 EXISTNG

TU-6 FAST TRACK 6 250 250 250 0.35 24 24 55 95 9.0 180 160 0.9 3/4 5 2 EXISTNG

TU-7 FAST TRACK 6 370 370 370 0.35 24 24 55 95 13.2 180 160 1.3 3/4 5 2 EXISTNG

TU-8 FAST TRACK 10 1000 1000 1000 0.35 24 24 55 95 35.7 180 160 3.6 1 5 2 EXISTNG

TU-9 EXAMROOMS 10 1060 1060 1060 0.35 24 24 55 95 37.8 180 160 3.8 1 5 2 EXISTNG

TU-10 SOILEDUTILITY 8 350 350 350 0.35 24 24 55 95 12.5 180 160 1.3 3/4 5 2 EXISTNG

TU-11 EXAMROOMS 8 480 480 480 0.35 24 24 55 95 17.2 180 160 1.7 v 5 2 EXISTNG

TU-12 EXAMROOMS 8 480 480 480 0.35 24 24 55 95 17.2 180 160 1.7 1 5 2 EXISTNG

TU-13 NOURISH 12 650 650 650 0.35 24 24 55 95 23.2 180 160 2.3 3/4 5 2 EXISTNG

TU-14 NURSE 10 1045 1045 1045 0.35 24 24 55 95 37.3 180 160 3.7 1 5 2 EXISTNG

TU-15 EXAMROOMS 6 170 170 170 0.35 24 24 55 95 6.1 180 160 0.6 3/4 5 2 EXISTNG

TU-16 EXAMROOMS 8 410 410 410 0.35 24 24 55 95 14.7 180 160 1.5 3/4 5 2 EXISTNG

TU-17 ISOLATION 8 500 500 500 0.35 24 24 55 95 17.9 1.8 3/4 5 2 EXISTNG

MANUFACTURERS: * ENVIROTEC, KRUEGER, TITUS

GENERAL NOTES:A: PROVIDE 120V/24V TRANSFORMER FOR NEW DDC CONTROLSB:

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

MECHANICALSCHEDULES

M6-01

Page 7: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc
Page 8: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

PRESSURE REDUCING VALVE

SHOCK ABSORBER

STRAINER W/ BLOW-OFF VALVE

SAFETY RELIEF VALVE

VACUUM BREAKER

PRESSURE GAUGE W/ PIG TAIL & COCK

THERMOMETER

PRESSURE - TEMP. TAP

AIR VENT

PIPE ANCHOR

FLEXIBLE CONNECTOR

PIPE EXPANSION JOINT

PIPE UNION

DOUBLE CHECK BACKFLOW PREVENTER

PUMP & EQUIPMENT CONNECTOR

TEMPERATURE CONTROL VALVE (2-WAY)

DRAIN VALVE W/ HOSE END

PLUG VALVE IN RISER

FLOW BALANCING VALVE

GATE OR GLOBE VALVE IN RISER

FLOW CONTROL VALVE

BALL VALVE

PLUG OR BALANCING VALVE

CHECK VALVE

GLOBE VALVE

BUTTERFLY VALVE

VENTURI/FLOW INDICATOR

TEMPERATURE CONTROL VALVE (3-WAY)

SOLENOID VALVE

90° ELBOW UP

TEE UP

TEE DOWN

SHUT OFF (BALL, GATE, BUTTERFLY)

PIPING SYMBOLS90° ELBOW DN

S

DUCT/PIPE RISER DESIGNATION KEY

CHDWHWGW VPRSTS2

FLOW SWITCH

HOSE BIBB

WALL HYDRANT

TEMPERATURE CONTROLLER OR SENSOR

STEAM TRAP TEST CHAMBER

STEAM TRAP:FT-FLOAT & THERMOSTATICTD-THERMODYNAMICIB-INVERTED BUCKETTS-THERMOSTATICBP-BALANCED PRESSURE

BAR SINKBS 1/2" 1/2" 1-1/2"1-1/2"

FIXTURE CONNECTION SCHEDULEHW CW WASTE VENT

NOTES:

1. SIZES SHOWN ARE MINIMUM PIPE SIZES TO A SINGLE FIXTURE. LARGERSIZES MAY BE INDICATED ON PLANS WHERE REQUIRED.

2. MINIMUM DOMESTIC PIPE SIZE TO (2) OR MORE FIXTURES IS 3/4".

3. RE: MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR INDIRECT WASTESIZES.

4. WASTE AND VENT SIZES SHOWN ABOVE APPLY TO INDIVIDUAL VENTING ONLY.WHERE ALLOWED, INDIVIDUAL VENT CONNECTIONS MAY BE OMITTED ORSIZES MAY VARY WHEN CIRCUIT VENTS, COMMON VENTS, WASTE STACKVENTS, WET VENTS, OR COMBINATION DRAIN AND VENT SYSTEMS ARE USED.PRIOR APPROVAL FROM THE ENGINEER IS REQUIRED TO USE THESEALTERNATIVE VENTING METHODS.

5. PROVIDE TRAP GUARD FOR ALL FLOOR DRAINS AND FLOOR SINKS NOTLOCATED IN FOOD SERVICE AREAS.

6. MINIMUM SIZE FOR WASTE AND VENT PIPING BENEATH SLAB IS 2".

7. ALL FIXTURES LISTED ARE NOT NECESSARILY USED ON THIS PROJECT.

8. REFER TO APPLIANCE SCHEDULES (BY OTHERS) FOR ADDITIONAL PLUMBINGFIXTURE CONNECTIONS SUCH AS INST-HOTS, COFFEE MAKERS, ANDGARBAGE DISPOSALS.

9. PROVIDE ICE MAKER BOX ROUGH IN W/ 1/2"CW CONNECTION FOR ALLREFRIGERATOR LOCATIONS.

ABBREV.

CS CLOTHES WASHER ROUGH-IN 1/2" 1/2" 2" 1-1/2"

DRINKING FOUNTAIN / E.W.C.DF - 1/2" 1-1/2" 1-1/2"

DISH MACHINE ROUGH-INDM 3/4" 3/4" 2" 1-1/2"

DW DISHWASHER ROUGH-IN -1/2" 2" 1-1/2"

FD FLOOR DRAIN - - 2" 1-1/2"

FS FLOOR SINK - - 3" 2"

HOSE BIBHB - - -3/4"

HAND SINKHS 1-1/2" 1-1/2"1/2" 1/2"

KITCHEN SINK W/ OR W/O DISPOSERKS 1/2" 1/2" 2" 1-1/2"

LAVATORYLAV 1/2" 1-1/2" 1-1/2"1/2"

MOP SERVICE BASINMSB 3/4" 3" 2"3/4"

SHOWER / BATHTUBSH 3/4" 3/4" 2" 1-1/2"

SERVICE SINKSS 3" 2"1/2" 1/2"

TROUGH DRAINTD - - 3" 2"

URINAL (BLOWOUT)UR 1" 2" 1-1/2"-

URINAL (WASHDOWN)UR

UR URINAL (WATERLESS)

3/4" 2" 1-1/2"

- 2" 1-1/2"

-

-

WATER CLOSET (FLUSH VALVE)WC

WATER CLOSET (FLUSH TANK)WCT

- 1" 4" 2"

- 1/2" 4" 2"

WS 3/4"3/4" 2" 1-1/2"WORK SINK

EQUIPMENT ABBREVIATIONSAIR HANDLING UNITAHU

AIR SEPARATORAS

BOILER (HOT WATER)B

BASE BOARDBB

BUFFER TANKBT

CONSTANT VOLUME BOXCV

DISHWASHER EXHAUST FANDEF

ELECTRIC BASEBOARD HEATEREBH

FURNACEF

FAN COILFC

FAN POWERED BOXFP

GLYCOL FEEDERGF

HUMIDIFIER

HC HEATING COIL

HP HEAT PUMP

HX HEAT EXCHANGER

KITCHEN EXHAUST FANKEF

MAKE-UP AIR UNITMAU

MOTOR CONTROL CENTERMCC

MIXING VALVEMV

PUMP P

RETURN (OR RELIEF) AIR FANRF

RADIANT ZONERZ

SNOWMELT AREASA

SUMP BASINSB

SUPPLY FANSF

STORAGE TANKST

THERMOSTATIC MIXING VALVETMV

UNIT HEATERUH

VARIABLE VOLUME BOXVV

WATER HEATERWH

H

CHILLERCH

COOLING COILCC

CIRC PUMPCP

CABINET UNIT HEATERCUH

COOLING TOWERCT

DUCT COILDC

ELECTRIC WATER HEATEREWH

EVAPORATIVE COOLING UNITECU

ENERGY RECOVERY UNITERU

EXHAUST FANEF

EXPANSION TANKET

VARIABLE VOLUME BOX W/ REHEATVR

TYPE OF AIR DEVICERE: GRD SCHEDULE.

AIR DEVICE DESIGNATION KEY

#CAEXHOSARAXFR

SIZE (INCHES) OR MINIMUMFREE AREA REQUIRED INSQUARE FEET.

NOTE:FOR STANDARD MODULE SIZE REGISTERS, SIZE GIVEN ISNECK SIZE. REFER TO GRD SCHEDULE FOR MODULE SIZE.

INDICATES AIRINLET DEVICE.

======

AIR QUANTITY (CFM)COMBUSTION AIREXHAUSTOUTSIDE AIRRETURNTRANSFER

BXFR12x6

A15012x6

REFERENCE SAMPLE

FFI = FOR FURTHER INFORMATIONFCT = FOR CONTINUATION

RE: B/M400 FFI

REFER TO:

DRAWING NUMBER ORDIAGRAM LETTER

SHEET NUMBER

PLAN ABBREVIATIONS

ABOVE FINISHED FLOOR

AIR ADMITTANCE VALVE

ABOVE FINISHED GRADE

AUTOMATIC

BUILDING CONTROL SYSTEM

BACK DRAFT DAMPER

BUILDING

AAV

AFF

AFG

AUTO

BCS

BDD

BLDG

BETWEEN

COMMON (OR CLOSED)

COMBUSTION AIR

CONTROLS CONTRACTOR

CONTINUATION DESIGN BUILD

B/N

C

CA

CC

CDBBC

CUBIC FEET PER MINUTE (AIR FLOW RATE)

CAST IN PLACE

CEILING (OR COOLING)

CONCRETE

CONDENSATE

CONNECT (OR CONNECTION)

CONTRACTOR

CFM

CIP

CLG

CONC

COND

CONN

CONTR'R

CLEANOUT TO GRADECOTG

DOMESTIC HOT WATER RECIRC

EXISTING

DWR

(E)

EXHAUST AIREA

ENTERING AIR TEMPERATURE

ELECTRICAL CONTRACTOR

ENTERING WATER TEMPERATURE

EAT

EC

EXH EXHAUST

EWT

GENERAL CONTRACTOR

GROUND HEAT EXCHANGER

GC

GHX

GALLONS PER MINUTE (WATER FLOW RATE)GPM

HORSEPOWER

HOT WATER

IN LIEU OF

HP

HW

ILO

KILOWATTSKW

LEAVING AIR TEMPERATURE

LINEAR FOOT

LEAVING WATER TEMPERATURE

LAT

LF

LWT

MECHANICAL CONTRACTORMC

MANUFACTURER

MOTOR OPERATED DAMPER

NEW

MFG

MOD

(N)

NORMALLY CLOSEDNC

NATIONAL ELECTRIC CODE

NOT IN CONTRACT

NORMALLY OPEN

NEC

NIC

NO

OUTSIDE AIROA

OPPOSED BLADE VOLUME DAMPER

ON CENTER

OBD

OC

OUTSIDE AIROSA

RETURN AIR

REQUIRED

RA

REQ'D

REQUIREMENTSREQ'MTS

SUPPLY AIR

SQUARE FOOT (FEET)

SA

SF

STATIC PRESSURESP

STAINLESS STEEL

THROW-AWAY (TRANSFER AIR)

TYPICAL

SS

TA

TYP

UNLESS NOTED OTHERWISEUNO

WALL CLEANOUTWCO

WITH REGARD TO

WATER COOLED

TRANSFER

WRT

W/C

XFR

DIAMETERØ

BY CONTRACTOR

COLD WATERCW

HOT WATER RECIRCHWC

ABOVEABV

BELOW FINISHED GRADEBFG

DOMESTIC WATER

DOMESTIC HOT WATER

DW

DHW

DOWNDN

DOMESTIC HOT WATER RECIRCDHR

COMBINATION FIRE/SMOKE DAMPER

FURNISHED BY OWNER

FSD

FBO

FLOOR CLEANOUTFCO

FOR CONTINUATIONFCT

FD FIRE DAMPER

REFER TO:RE:

WITHW/

CLEANOUTCO

FUTURE(F)

FREE AREAFA

FFI FOR FURTHER INFORMATION

WITHOUTW/O

VENT THRU ROOFVTR

NOTES1. ALL SYMBOLS, ABBREVIATIONS, AND DESIGNATIONS

ON LEGEND SHEET ARE NOT NECESSARILY USED ONTHIS PROJECT.

2. THIS DRAWING SET CONSISTS OF DATA GENERATED, INPART, BY OTHER PARTIES. NOT ALL SYMBOLOGIES ANDNOTATION CONVENTIONS OCCURRING IN THISDRAWING SET ARE NECESSARILY DEFINED ON THESELEGENDS. CONSULT THE ENGINEER IN THE EVENTSYMBOLOGY OR NOTATION INTERPRETATION ISREQUIRED.

EAOARASA

RISER NUMBER

--------

----

CHILLED WATERDOMESTIC WATERHEATING WATERGASWASTE AND/OR VENTPIPING RISER (MISC TYPES)STORM DRAINSECONDARY STORM DRAIN

EXHAUST AIROUTSIDE AIRRETURN AIRSUPPLY AIR

AIR SIDE:

PIPING SIDE:

PLAN SYMBOLSCONTROL PANEL/RADIANT MANIFOLD

CARBON DIOXIDE SENSOR

CARBON MONOXIDE SENSOR

DIAGRAM CONTINUATION REFERENCE

PLUMBING/HVAC RISER

POINT OF NEW CONNECTION

DUCT STATIC PRESSURE SENSOR

ROOM PRESSURE SENSOR

EMERGENCY POWER OFF SWITCH

ACCESS PANEL

SNOWMELT MANIFOLD

SECTION CUT LETTER/SHEET SHOWN ON

POINT OF DISCONNECTION

-

SP

CO2

EPO

P

CO

--

-P

THERMOSTAT

HUMIDISTAT

REMOTE TEMPERATURE SENSOR

T

S

H

H B

W H

TC

FS

ROOF DRAIN

FLOOR DRAIN

FLOOR SINK

HORIZONTAL CLEANOUT

VERTICAL CLEANOUT

DECK/ROOF DRAIN ABOVE

PIPING DESIGNATIONS

SNOWMELT SUPPLY

SNOWMELT RETURN

HEATING WATER SUPPLY (HIGH TEMP)

HEATING WATER RETURN (HIGH TEMP)

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CONDENSER RETURN

NATURAL GAS

MEDIUM PRESSURE GAS

HIGH PRESSURE STEAM

HIGH PRESSURE CONDENSATE RETURN

LOW PRESSURE STEAM

LOW PRESSURE CONDENSATE RETURN

REFRIGERANT SUCTION

REFRIGERANT LIQUID

DOMESTIC WATER

DOMESTIC HOT WATER

DOMESTIC HOT WATER (TEMP. SHOWN)

DHW RECIRCULATION

FIRE LINE

PRESSURIZED WASTE

PLUMBING VENT PIPE

WASTE PIPE

ACID WASTE PIPE

STORM DRAIN PIPE

STORM DRAIN OVERFLOW

COMPRESSED AIR PIPE

GREASE WASTE PIPE

ACID VENT PIPE

LIQUID PROPANE GAS

SECONDARY DRAIN

SAND AND OIL WASTE

FLOOR COOLING SUPPLY

FLOOR COOLING RETURN

PROPANE GAS

HEATING WATER SUPPLY (LOW TEMP)

HEATING WATER RETURN (LOW TEMP)

SOLAR HEATING WATER SUPPLY

SOLAR HEATING WATER RETURN

GROUND LOOP SUPPLY

GROUND LOOP RETURN

GROUND WATER SUPPLY

GROUND WATER RETURN

HEATING WATER SUPPLY

HEATING WATER RETURN

DRAIN PIPE

FUEL OIL SUPPLY

FUEL OIL RETURN

GLYCOL FEED

GREASE VENT

MEDIUM PRESSURE STEAM

MEDIUM PRESSURE CONDENSATE RETURN

FUEL OIL VENT

FUEL OIL FILL

PUMPED CONDENSATE

GEOTHERMAL (OR GROUND) LOOP SUPPLY

GEOTHERMAL (OR GROUND) LOOP RETURN

CLOSED CONDENSER SUPPLY

CLOSED CONDENSER RETURN

PROPANE DRAIN

CONDENSER SUPPLY

PLUMBING PIPING

NON-SOFTENED DOMESTIC WATER

CR

CS

CCR

CCS

GLR

GLS

CHR

CHS

GLR

GLS

GF

HWR

HWS

HWR(LT)

HWS(LT)

HWR(HT)

HWS(HT)

FCR

FCS

SHWR

SHWS

SMS

SMR

PC

MPR

MPS

LPS

LPR

HPR

HPS

PD

D

PG

LPG

MG

G

RS

RL

FOF

FOV

FOR

FOS

GWR

GWS

CW

HW

HWC

NS

140° HW

GV

SO

SD

ST

GW

AW

AV

V

W

PW

ST(OF)

F

CA

SOLID DRAIN PIPEDS

STEAM & CONDENSATE PIPING

HYDRONIC PIPING

SUMP PUMPSP

PR203

PLUMBING SYSTEMS LEGEND

ABOVE SEA LEVEL

PROJECT ALTITUDE5,292'

' 'ISSUE LOG KEY:

#

DA

TE

ISSUE LOG

PLUMBING SHEET INDEX

TITLE

PLUMBING COVER SHEETP0-01

100%

DD

02.2

2.20

18ISSUED AS PART OF A SET' ' NOT PART OF SET' ' ISSUED FOR INFORMATION ONLY*

√√

PLUMBING SPECIFICATION NOTES SHEETP0-02

PLUMBING DEMOLITION PLANPD1-01

PLUMBING PLANP1-01

PLUMBING DIAGRAMS SHEETP5-01

√PLUMBING MEDICAL GAS DEMOLITION PLANPD1-02

√PLUMBING SCHEDULESP6-01

√PLUMBING MEDICAL GAS PLANP1-02

1. NOT ALL REQUIRED CLEANOUTS ARE NECESSARILY SHOWN ON THESE PLANS. PROVIDE CLEANOUTS ON WASTE,VENT AND STORM PIPING AS REQUIRED BY CODE AND FOR REASONABLE MAINTENANCE BASED ON ACTUAL FIELDINSTALLATION. COORDINATE LOCATIONS WITH ARCHITECT/ENGINEER.

2. COORDINATE ROUTING OF CONDENSATE DRAIN LINES WITH ARCHITECT PRIOR TO INSTALLATION.

3. PIPING ON EXTERIOR WALLS OR PRE-CAST CONCRETE WALLS TO BE ROUTED IN FRAMED WALL ON INTERIOR SIDEOF INSULATION.

4. INSTALL THERMOSTATIC MIXING VALVES, ASSE 1070 LISTED, AT EACH PUBLIC HANDWASHING LAVATORY/SINK.SIZE TO MATCH HW PIPE SIZE.

5. TERMINATE PLUMBING VENTS NOT LESS THAN 12" ABOVE ROOF.

6. DO NOT ROUTE PIPING OVER ELECTRICAL ROOMS OR ELECTRICAL PANELS; MAINTAIN N.E.C. CLEARANCES.COORDINATE ROUTINGS WITH DIV. 16 CONTRACTOR.

7. CONTRACTOR TO MAINTAIN 8'-6" CLEAR HEAD HEIGHT IN GARAGE AND INFORM THE ENGINEER AND ARCHITECT OFANY AREAS THAT MAY NOT MEET 8'-6" PRIOR TO INSTALLATION, MINIMUM 8'-2" CLEAR HEAD HEIGHT MUST BEMAINTAINED IN ACCESSIBLE VEHICLE AREAS.

8. PROVIDE FLEXIBLE PIPE CONNECTIONS TO ALL MOTORIZED EQUIPMENT.

9. ROUTE DOMESTIC HOT WATER RECIRC TO WITHIN 10 FEET OF ALL HOT WATER FIXTURES. CONNECT WITHIN 3FEET OF 0.5 GPM AND LOWER FAUCETS.

10. VERIFY ALL EQUIPMENT ACCESS PANELS WITH MANUFACTURER AND ARCHITECT.

11. PROTECT PIPING ROUTED ALONG COLUMNS, WALLS, ETC. FROM DAMAGE AS NECESSARY WITH CAGES.COORDINATE WITH ARCHITECT.

12. PEX PIPING SHALL NOT BE ALLOWED TO PENETRATE FIRE BARRIERS WHERE FIRE CAULKING IS REQUIRED.

13. ALL VALVES SHALL BE INSTALLED ABOVE DROP-IN CEILINGS IN ACCESSIBLE LOCATIONS, OR WITH ACCESSPANELS IN HARD-LID CEILINGS.

14. ALL PIPING SHALL BE ROUTED AS HIGH AS POSSIBLE IN THE CEILING SPACE. UTILIZE JOIST SPACE WHENPOSSIBLE, ESPECIALLY WHERE CROSSING OTHER PIPES, DUCTS, AND ELECTRICAL.

15. ACCESS PANELS SHALL BE 24x24, U.N.O. LOCATIONS SHOWN ARE APPROXIMATE, EXACT LOCATIONS SHALL BECOORDINATED WITH THE ARCHITECTS DRAWINGS AND WITH THE LOCATIONS OF THE EQUIPMENT OR APPARATUSTHAT THEY SERVE.

16. SEAL ALL PIPING PENETRATIONS THROUGH ACOUSTIC PARTITIONS.

17. EXPOSED SOIL OR WASTE PIPING SHALL NOT BE INSTALLED ABOVE ANY WORKING, STORAGE, OR EATINGSURFACES IN FOOD SERVICE ESTABLISHMENTS.

GENERAL NOTES:

√ENLARGED PLUMBING PLANP4-01

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

PLUMBINGCOVER SHEET

P0-01

Page 9: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

GENERAL SPECIFICATIONS:

1. CONTROLS SYSTEM COMPONENTS SHALL BE COMPATIBLE WITH EXISTING BUILDING AUTOMATION SYSTEM (AUTOMATED LOGIC). CONTROLS SHALL BEFIELD INSTALLED. CONTROLS CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING AND INSTALLING ALL DEVICES REQUIRED FOR A FULLY FUNCTIONALCONTROL SYSTEM FOR THIS PROJECT, REGARDLESS OF VOLTAGE. IF THE CONTRACTOR CANNOT SELF PERFORM WORK REQUIRING LINE VOLTAGE THENTHE CONTRACTOR SHALL COORDINATE WITH AND COMPENSATE THE ELECTRICAL CONTRACTOR AS REQUIRED. CONTROLS CONTRACTOR SHALLCOORDINATE WITH EQUIPMENT SUPPLIERS TO ENSURE THAT ALL DEVICES ARE COMPATIBLE WITH THE EXISTING CONTROLS SYSTEM AND EXISTINGMECHANICAL EQUIPMENT. CONTROLS CONTRACTOR SHALL PROVIDE READ-ONLY ACCESS TO THE BAS VIA THE INTERNET FOR A PERIOD OF ONE YEAR TOASSIST WITH TROUBLESHOOTING ANY ISSUES RELATED TO THE HVAC SYSTEM IN THE AREA OF THIS PROJECT.

2. CONTROLS CONTRACTOR SHALL ALSO HAVE IN HIS BID AS A LINE ITEM FOR THE POTENTIAL NEED FOR THE TIME AND RESOURCES REQUIRED TO ASSISTTHE COMMISSIONING AGENT IN THE COMMISSIONING OF THE MECHANICAL AND ELECTRICAL SYSTEMS ASSOCIATED WITH THE TENANT FINISH WORKUTILIZING A WEB BASED COMMISSIONING PROCESS. WORK SHALL INCLUDE BUT NOT LIMITED TO: ATTENDING COMMISSIONING SCOPE MEETING,PERFORMING AND DOCUMENTING PRE-FUNCTIONAL CHECK LISTS, PROVIDING ASSISTANCE IN THE FUNCTIONAL TESTING OF EQUIPMENT AND PROVIDINGTOOLS REQUIRED TO PERFORM FUNCTIONAL TESTING.

3. ALL CONTROL WIRING TO BE INSTALLED IN PLENUM RATED CONDUIT.

4. NO NETWORKED CONTROL POINTS ARE ALLOWED. ALL SENSORS TO BE HARDWIRED DIRECTLY TO CONTROLLING MODULE.

CONTROLS SYSTEM NOTES

1. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS IN FIELD PRIOR TO COMMENCEMENT OF WORK. REFER TO ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS.

2. ALL SUBCONTRACTORS SHALL BE LICENSED, EXPERIENCED, AND THOROUGHLY KNOWLEDGEABLE IN THEIR RESPECTIVE AREAS OF THE CONSTRUCTION INDUSTRYAND SHALL PERFORM IN A RESPONSIBLE MANNER WITH ESTABLISHED CONSTRUCTION SEQUENCE, SHALL RECOGNIZE THE PRIORITY OF THE CONSTRUCTIONDOCUMENTS, AND SHALL INFORM THE PRIME CONTRACTOR OF POTENTIAL PROBLEMS WHEN THE CONSTRUCTION DOCUMENTS ARE UNCLEAR OR INCONSISTENT.

3. SUBCONTRACTORS SHALL BE RESPONSIBLE TO NOTIFY THE PRIME CONTRACTOR OF DISCREPANCIES OR CONFLICTS IN THE CONSTRUCTION DOCUMENTS FOUNDDURING BIDDING AND/OR PRIOR TO PERFORMING THE WORK.

4. EXAMINATION OF BIDDING DOCUMENTS.

A. EACH BIDDER SHALL EXAMINE THE BIDDING DOCUMENTS CAREFULLY, AND NOT LATER THAN SEVEN (7) DAYS PRIOR TO THE DATE OF RECEIPT OF BIDS, SHALLMAKE WRITTEN REQUEST TO THE ARCHITECT FOR INTERPRETATION OR CORRECTION OF ANY DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORSTHEREIN WHICH HE MAY DISCOVER (REFER TO ARCHITECTURAL REQUIREMENTS). THE ARCHITECT WILL ISSUE ANY INTERPRETATION OR CORRECTION AS ANADDENDUM. ONLY A WRITTEN INTERPRETATION OR CORRECTION BY ADDENDUM SHALL BE BINDING. NO BIDDER SHALL RELY UPON INTERPRETATIONS ORCORRECTIONS GIVEN BY ANY OTHER METHOD. IF DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS ARE NOT COVERED BY ADDENDUM ORWRITTEN DIRECTIVE, CONTRACTOR SHALL INCLUDE IN THEIR BID, LABOR MATERIALS AND METHODS OF CONSTRUCTION RESULTING IN HIGHER COST. AFTERAWARD OF CONTRACT, NO ALLOWANCE OR EXTRA COMPENSATION WILL BE MADE ON BEHALF OF THE CONTRACTOR DUE TO THEIR FAILURE TO MAKE THEWRITTEN REQUESTS AS DESCRIBED ABOVE.

B. FAILURE TO REQUEST CLARIFICATION DURING THE BID PERIOD OF ANY INADEQUACY, OMISSION, OR CONFLICT WILL NOT RELIEVE THE CONTRACTOR OF THEIRRESPONSIBILITIES. THE SIGNING OF THE CONTRACT WILL BE CONSIDERED AS IMPLICITLY DENOTING THAT THE CONTRACTOR HAS A THOROUGHCOMPREHENSION OF THE FULL INTENT AND SCOPE OF THE CONSTRUCTION CONTRACT DRAWINGS AND SPECIFICATIONS.

5. PROVIDE A BASE BID WHICH SHALL INCLUDE ONLY SPECIFIED EQUIPMENT OR EQUIPMENT LISTED AS EQUIVALENT. NO SUBSTITUTIONS FOR THE LISTEDEQUIPMENT SHALL BE ALLOWED IN THE BASE BID.

A. THE MANUFACTURER OF EQUIPMENT OR MATERIALS FIRST NAMED ON THE DRAWINGS IS THE BASIS OF DESIGN. OTHER MANUFACTURERS LISTED ARECONSIDERED GENERAL EQUIVALENTS ONLY.

B. COORDINATION OF GENERAL EQUIVALENTS AND SUBSTITUTIONS: WHERE CONTRACT DOCUMENTS PERMIT SELECTION FROM SEVERAL GENERALEQUIVALENTS, OR WHERE SUBSTITUTIONS ARE AUTHORIZED, COORDINATE CLEARANCE AND OTHER INTERFACE REQUIREMENTS WITH MECHANICAL ANDOTHER WORK.

1) PROVIDE NECESSARY ADDITIONAL ITEMS SO THAT SELECTED OR SUBSTITUTED ITEM OPERATES EQUIVALENT TO THE BASIS OF DESIGN AND PROPERLYFITS IN THE AVAILABLE SPACE ALLOCATED FOR THE BASIS OF DESIGN.

2) PROVIDE ALL FEATURES WHICH ARE STANDARD ON THE BASIS OF DESIGN PLUS ANY SPECIFIED OPTIONS.

3) BE RESPONSIBLE FOR ASSURING THAT PIPING, CONDUIT, DUCT, FLUE, AND OTHER SERVICE LOCATIONS FOR GENERAL EQUIVALENTS OR SUBSTITUTIONSDO NOT CAUSE ACCESS, SERVICE, OR OPERATIONAL DIFFICULTIES ANY GREATER THAT WOULD BE ENCOUNTERED WITH THE BASE DESIGN.

6. INASMUCH AS DESIGN FOR REMODEL AND/OR REHABILITATION REQUIRES THAT CERTAIN ASSUMPTIONS BE MADE REGARDING EXISTING CONDITIONS, ANDBECAUSE SOME OF THESE ASSUMPTIONS CANNOT BE VERIFIED WITHOUT DESTROYING OTHERWISE ADEQUATE OR SERVICEABLE PORTIONS OF THE BUILDING, THEENGINEER CANNOT ASSURE THE OWNER OR THE CONTRACTOR THAT THE PROFESSIONAL CONSULTING SERVICES HEREIN ENCOMPASS ALL CONTINGENCIES.FIELD COORDINATION DURING CONSTRUCTION IS IMPERATIVE. MAKE REASONABLE ALLOWANCES FOR UNSEEN CONDITIONS.

7. THE EXISTING BUILDING WILL BE OCCUPIED BY THE OWNER DURING CONSTRUCTION. CONTINUED OPERATION OF THE FACILITY SHALL NOT BE HINDERED BY THISWORK. ACCOUNT FOR ALL ADDITIONAL COSTS WHICH MAY BE INCURRED DUE TO THE DIFFICULTY OF WORKING OVER AND AROUND EMPLOYEES, FURNITURE,EQUIPMENT, ETC.; AND DUE TO THE HOURS OF THE DAY IN WHICH AN AREA MAY BE ACCESSIBLE WHEN COMPILING HIS BID.

8. BE RESPONSIBLE TO FIELD VERIFY EXISTING EQUIPMENT OR DUCTWORK REMAINING TO BE CONNECTED TO NEW OR EXISTING SYSTEMS. PROVIDE DUCTWORK,PIPING, CONTROLS, DIFFUSERS, ETC., AS REQUIRED TO RESTORE CONTINUITY OF SYSTEMS, OR TO MAKE NEW WORK MEET EXISTING CONDITIONS, WHETHERINDICATED OR NOT.

9. SUBCONTRACTOR SHALL VERIFY EXISTENCE AND LOCATION OF ALL UTILITY SERVICES AND COORDINATE AS REQUIRED BY THEIR RESPECTIVE AREA OF THECONSTRUCTION, NOTIFYING THE PRIME CONTRACTOR OF VARIATIONS OR CONFLICTS.

10. IF NOT SPECIFICALLY DEFINED IN THESE CONSTRUCTION DOCUMENTS, MATERIALS AND/OR EQUIPMENT SHALL BE IDENTIFIED BY THE SUBCONTRACTOR WITHSUFFICIENT TIME TO ALLOW SELECTION, PURCHASE, AND DELIVERY TO MAINTAIN CONSTRUCTION SCHEDULE.

11. PROVIDE MECHANICAL DEMOLITION AS REQUIRED. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR LOCATION AND EXTENT OF DEMOLITION REQUIRED.VISIT SITE PRIOR TO BID TO DETERMINE EXTENT OF WORK INVOLVED. EXISTING FIXTURES, MECHANICAL EQUIPMENT, ETC., BEING REMOVED SHALL BE RETURNEDTO THE OWNER. DISPOSE OF ALL REMOVED PIPING, DUCTWORK, ETC. UNLESS NOTED OTHERWISE. PIPES, DUCTWORK, EQUIPMENT, ETC. TO BE REMOVED, ARESHOWN HATCHED, UNLESS OTHERWISE NOTED.

12. VERIFY EXACT LOCATIONS OF EXISTING AND NEW UNDERGROUND UTILITIES, PIPING, AND RACEWAY SYSTEMS IN CEILING SPACES ABOVE AND BELOW SPACE.

13. ALL DUCTWORK, DIFFUSERS, PIPING, FIXTURES, AND EQUIPMENT SHOWN IN LIGHT DASHED LINE WEIGHT IS EXISTING, NEW INDICATED BY HEAVIER LINE WEIGHT,EXCEPT WHERE NOTED. PIPES, DUCTWORK, EQUIPMENT, ETC. TO BE REMOVED, ARE SHOWN HATCHED.

14. OFFSET PIPING, DUCTWORK, ETC. AS NECESSARY TO ACCOMMODATE STRUCTURE, BEAMS, AND COLUMNS, AND EXISTING EQUIPMENT.

15. ALL EXISTING SUPPORT RODS AND STRAPS NOW SUPPORTING DUCTS, PIPES, AIR TUBING, ELECTRICAL CONDUIT, ETC. THAT ARE REMOVED TO ALLOW ROOM FORINSTALLATION OF NEW EQUIPMENT SHALL BE RELOCATED AND REINSTALLED, OR REPLACED IF DAMAGED.

16. ALL “CAPPED” SANITARY AND VENT LINES SHALL BE RECONNECTED OR RE-ROUTED AS NECESSARY TO PREVENT “DEAD-ENDS” IN THE PIPING. ALL PIPING SHALLDRAIN TO ACTIVE SANITARY WASTE LINES AND ALL BRANCHES WITH TRAPS SHALL BE ADEQUATELY VENTED.

17. CAP ALL DEMOLISHED AND ABANDONED DUCT TAKE-OFFS AT TRUNK DUCT.

18. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT, OWNER, AND ENGINEER.

19. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PERFORM HIS/HER WORK IN CONFORMANCE WITH ALL APPLICABLE CODES, ORDINANCES AND LIFE SAFETY FEATURESAS REQUIRED BY LOCAL, STATE, OR NATIONAL AUTHORITIES. THE CONTRACTOR SHALL VERIFY WITH THE ARCHITECT IF MODIFICATION OF HIS/HER WORK ISREQUIRED FOR COMPLIANCE.

20. ALL WORK OF ALL TRADES MUST BE IN STRICT COMPLIANCE, OR EXCEED THE MINIMUM MATERIAL AND METHOD REQUIREMENTS OF THE ADOPTED NEW MEXICOSTATE CODES INCLUDING THE INTERNATIONAL BUILDING CODE, UNIFORM MECHANICAL AND PLUMBING CODES, FIRE AND ELECTRICAL CODES, MOST CURRENTNFPA, THE 2010 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES, ALL LOCAL ORDINANCES AND AMENDMENTS AND MANUFACTURER'SINSTALLATION RECOMMENDATIONS. IF A CONFLICT BETWEEN THOSE PUBLICATIONS EXISTS, THE MOST STRINGENT REQUIREMENT SHALL APPLY.

21. PAY FOR AND SECURE ALL REQUIRED PERMITS AND INSPECTIONS. PRIOR TO FINAL PAYMENT, TURN OVER TO ARCHITECT ALL CERTIFICATES OF COMPLETION.

22. WARRANTY THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP. THE WARRANTY SHALL BE FOR A PERIOD OF ONE YEAR AFTER OWNER'SACCEPTANCE. DEFECTS SHALL BE PROMPTLY REMEDIED WITHOUT COST TO THE OWNER.

23. SUBMIT RECORD DOCUMENTS TO ARCHITECT. DOCUMENTS SHALL INCLUDE ALL ADDENDUM ITEMS, CHANGE ORDERS, ALTERATIONS, REROUTINGS, ETC.

24. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS OPERATION PRIOR TO ACCEPTANCE BY THE OWNER.

25. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. PERFORM AT A MINIMUM ALL CODE REQUIRED TESTS OR SYSTEMS. IF TESTS OF WORK ARE DEFECTIVE,CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY AT NO ADDITIONAL COST TO OWNER.

26. ALL MATERIALS AND/OR EQUIPMENT SHALL BE HANDLED AND INSTALLED AS PER MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS.

27. SUBMIT ALL MECHANICAL DIVISION SHOP DRAWING AND PRODUCT DATA AT ONE TIME. SUBMITTAL SHALL BE BOUND AND INDEXED IN A NEAT AND ORDERLYMANNER. PARTIAL SUBMITTALS WILL BE REJECTED. SUBMITTALS SHALL INCLUDE, BUT NOT BE LIMITED TO: EQUIPMENT, FIXTURES, INSULATION, DIFFUSERS,PUMPS, PIPING, VALVES, CONTROLS, AND FIRE PROTECTION.

28. FAILURE TO ORDER, OR RELEASE ORDER FOR MATERIALS AND/OR EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO SUBSTITUTE ALTERNATE MATERIALS,EQUIPMENT, OR INSTALLATION METHODS.

29. PROVIDE NECESSARY TRENCHING, BACKFILL, EXCAVATION, SUPPORTS, SAWCUTTING AND PATCHING, CONCRETE/PAVING, ETC., AS REQUIRED. PATCH TO MATCHEXISTING FLOOR LEVEL.

30. REPAIR ALL ACCIDENTAL OR INTENTIONAL DAMAGE TO MATCH EXISTING CONSTRUCTION WITH NO NOTICEABLE DIFFERENCE IN CONTINUITY, APPEARANCE ORFUNCTION.

31. TEMPORARY HEAT SHALL BE FURNISHED BY THE GENERAL CONTRACTOR. USE OF THE PERMANENT HEATING SYSTEM WILL NOT BE ALLOWED.

32. COORDINATE ALL PENETRATIONS OF THE FLOOR SLAB PRIOR TO COMMENCING WORK. UTILIZE X-RAY AND VISUAL INVESTIGATION OF EXISTING CONDITIONS ASREQUIRED PRIOR TO DRILLING OR CUTTING. COORDINATE ALL NEW PENETRATIONS WITH OTHER DIVISIONS OF THE WORK. ALL CONTRACTORS ARE INDIVIDUALLYRESPONSIBLE FOR ALL PENETRATIONS REQUIRED BY THEIR DIVISIONS.

33. FIRE STOPPING REQUIREMENT. PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE SEALED WITH A MATERIAL CAPABLE OF PREVENTING THEPASSAGE OF FLAMES AND HOT GASSES WHEN SUBJECTED TO THE REQUIREMENTS OF THE TEST STANDARD SPECIFIC FOR FIRE STOPS ASTM-E-814. ACCEPTABLEMATERIALS INCLUDE: DOW CORNING RTV FIRE STOP FOAM FOR BARE PIPE, METAL CONDUIT, AND ELECTRICAL CABLE; 3M FIRE DAM 150 CAULK FOR BARE PIPE,METAL CONDUIT, AND BUILDING CONSTRUCTION GAPS; 3M CP-25 CAULK AND FS-195 INTUMESCENT STRIPS FOR INSULATED PIPES, PLASTIC PIPE OR CONDUIT, ANDELECTRICAL CABLE. SUBMIT UL LISTED APPLICATION DATA FOR EACH TYPE OF PENETRATION ENCOUNTERED.

34. DUCTS, PIPING, AND CONDUITS PENETRATING THROUGH ROOF SHALL HAVE ROOF FLASHING COMPATIBLE WITH THE ROOFING SYSTEM. SEE ARCHITECTURALDRAWINGS. IN THE ABSENCE OF ANY OTHER REQUIREMENTS, PROVIDE SHEET LEAD TYPE FLASHING FOR PLUMBING VENTS IN BUILT-UP ROOFS, TALL CONE WITHEPDM BOOT FOR PIPE AND CONDUIT IN SINGLE PLY MEMBRANE ROOFS, AND CURBED ROOF PENETRATIONS IN ALL TYPES OF ROOF. INSTALLATION SHALL BEWATERTIGHT.

35. ALL FLOOR DRAINS CONNECTED TO THE SEWER SYSTEM SHALL BE EQUIPPED WITH TRAP PRIMERS OR TRAP GUARDS. PROVIDE TRAP PRIMERS WITH BACKFLOWPREVENTERS AND CONNECT TO THE NEAREST COLD WATER PIPING ADJACENT TO A FLUSHING FIXTURE. PROVIDE ELECTRONIC TRAP PRIMERS FOR ANY AREASWHERE THE NEAREST ADJACENT FLUSHING FIXTURES ARE NOT WITHIN A REASONABLE DISTANCE OR STRUCTURAL OBSTRUCTIONS PREVENT GRAVITY SLOPING OFTRAP PRIMER LINES. ADDED COST OF ELECTRIC POWER FOR ELECTRONIC TRAP PRIMERS SHALL BE BORNE BY PLUMBING CONTRACTOR. INSTALL ALL TRAPPRIMER VALVES AND ASSOCIATED SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.

36. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR ALL CEILING PENETRATIONS AND AIR DEVICE LOCATIONS.

37. COORDINATE ARCHITECTURAL, STRUCTURAL, MECHANICAL, FIRE PROTECTION, ELECTRICAL, LANDSCAPING, AND INTERIOR DESIGN DRAWINGS PRIOR TOINSTALLATION.

38. CAREFULLY VERIFY ELECTRICAL SERVICE VOLTAGE AND PHASE AVAILABLE.

39. MOUNT ALL STATS AT 48” A.F.F. IN “ACCESSIBLE” AREAS, 4'6” A.F.F. IN OTHER AREAS, UNLESS NOTED OTHERWISE (REFER TO ARCHITECTURAL). COORDINATELOCATION WITH WALL FINISH, AND TO AVOID CASEWORK, FURNITURE, DOOR SWINGS, HEAT SOURCES, AND EXTERIOR WALLS (COORDINATE WITH ARCHITECH ANDOWNER). NOTIFY ENGINEER OF ANY CONFLICTS PRIOR TO BEGINNING THERMOSTAT INSTALLATION.

40. SUBMIT A WRITTEN BALANCE REPORT BY A NEBB OR AABC CERTIFIED BALANCING CONTRACTOR. BALANCING PROCEDURES SHALL BE IN ACCORDANCE WITH NEBBOR AABC GUIDELINES FOR PROPORTIONAL BALANCE. SUBMIT REPORT ON STANDARD NEBB FORMS OR SUBMIT FORMS FOR REVIEW PRIOR TO BALANCING.MEASUREMENTS SHALL INCLUDE ALL MOTOR AMPERAGE AND VOLTAGE READINGS; MOTOR AND FAN RPMS; STATIC PRESSURE AT INLET AND OUTLET OF ALLPACKAGED EQUIPMENT, FANS, COILS, AND FILTERS; PITOT TUBE MEASUREMENT OF SUPPLY, EXHAUST, RETURN, AND OUTSIDE AIR MAIN DUCTS, AT MINIMUM

OUTSIDE AIR, AND 100% (ECONOMIZER) OUTSIDE AIR; VELOCITY DISTRIBUTION ACROSS THE FACE OF FILTERS; AIR INLET AND OUTLETS; WATER FLOW AT ALL FLOWMEASUREMENT STATIONS; INLET AND OUTLET PRESSURE AT PUMPS WITH FLOW CALCULATED FROM THE PUMP CURVE; WATER FLOW, TEMPERATURE DROP, ANDPRESSURE DROP AT ALL COILS.

A. PROVIDE BELTS AND SHEAVES AS REQUIRED FOR DRIVE CHANGES TO ADJUST FAN SPEED.

B. ADJUST FLOWS TO WITHIN 10% OF REQUIRED QUANTITY. WHERE ROOM AIR PRESSURE RELATIONSHIP ARE REQUIRED TO BE MAINTAINED AS SHOWN BY ADIFFERENTIAL OF SUPPLY AND EXHAUST/RETURN OR BY NOTE, ADJUST SUPPLY TO WITHIN 10% AND THEN ADJUST EXHAUST/RETURN TO PROVIDE THEINDICATED ROOM PRESSURE. IF ACTUAL QUANTITY IS LESS THAN 90%, INVESTIGATE CAUSE, ATTEMPT TO RECTIFY AND NOTIFY ENGINEER. SUBMITTAL OFBALANCE REPORT WITH LESS THAN REQUIRED FLOWS WITHOUT EXPLANATION IS CAUSE FOR REJECTION OF REPORT.

C. SUBMIT THREE (3) COPIES OF ALL SUBMITTALS IN ADDITION TO ANY REQUIRED BY THE CONTRACTOR AND HIS SUPPLIERS. THESE COPIES SHALL BE RETAINEDBY THE OWNER, ARCHITECT, AND ENGINEER.

41. DUCTWORK:

A. FLEXIBLE DUCTWORK SHALL HAVE AN OUTER JACKET OF FIRE RETARDANT POLYETHYLENE VAPOR BARRIER MATERIAL, UNIFORM LAYER OF FIBERGLASSINSULATION, HIGH-STRENGTH GALVANIZED STEEL HELIX ENCAPSULATED IN REINFORCED “RIP STOP” ALUMINUM LAMINATE INTERIOR CORE, UL LISTED ANDLABELED, CLASS 1 AIR DUCT. WORKING PRESSURE RATING: POS. 6”, NEC. 4”. FLEXMASTER TYPE 5 OR EQUIVALENT. SUBMIT SAMPLES TO DETERMINEEQUIVALENCE.

B. FLEXIBLE CONNECTION: EQUIVALENT TO VENTFAB, FIREPROOF GLASS CLOTH, 10” W.C. RATED.

C. ROUND DUCT: SPIRAL SEAM, GALVANIZED STEEL. DIE STAMPED OR 5 GORE ELBOWS. “SNAP-LOCK”, LONGITUDINAL SEAM DUCT, OR ADJUSTABLE FITTINGS AREACCEPTABLE ON INDIVIDUAL GRILLE/DIFFUSER RUNOUTS ONLY.

D. INSULATION:

1) EXTERNALLY WRAP ALL RECTANGULAR AND ROUND SUPPLY AIR DUCTS WITH FLEXIBLE GLASS FIBER, ANSI/ASTM C612; 0.002 INCH FOIL SCRIM FACING.

E. DUCTWORK: G60 GALVANIZED SHEET STEEL; LOCK FORMING QUALITY; CONSTRUCTED TO THE LATEST EDITION OF SMACNA “HVAC DUCT CONSTRUCTIONSTANDARDS”; +/- 1” W.C. PRESSURE CLASSIFICATION, SEAL CLASS “C”; WITH GALVANIZED STEEL FASTENERS, ANCHORS, ANGLES, STRAPS, ETC.

F. SEAL ALL SEAMS (LONGITUDINAL AND TRANSVERSE) AIRTIGHT WITH UNITED MCGILL “UNI-GRIP” UL LISTED, WATER BASED, NON-HARDENING, ELASTIC SEALANTOR EQUIVALENT. TAPE NOT ALLOWED.

42. PROVIDE ¼” GALVANIZED MESH SCREEN ON ALL COMBUSTION AIR DUCTS OR OPENINGS, AND ALL OPEN END RETURN AND EXHAUST DUCTS.

43. ALL DUCTWORK DIMENSIONS ARE FREE AREA DIMENSIONS.

44. DUCTWORK NOTES:

A. DIFFUSER NECK SIZE IS SAME AS FLEXIBLE DUCT SIZE.

B. UNLESS OTHERWISE NOTED, ALL CHANGES IN DIRECTION SHALL BE MADE WITH RADIUS ELBOWS WITH RADIUS TO CENTERLINE EQUAL TO 1.5 DUCT WIDTH.

1) WHERE REQUIRED FOR SPACE CONSTRAINTS, PROVIDE SQUARE THROAT ELBOWS WITH SINGLE WIDTH (NON-AIRFOIL) TURNING VANES.

2) FOR DUCT DEPTHS OF 36” OR LESS, PROVIDE MANUFACTURED SINGLE WIDTH (NON-AIRFOIL) TURNING VANES, WITH SPACING IN ACCORDANCE WITHSMACNA DUCT CONSTRUCTION STANDARDS FOR “STANDARD SPACING”. USE DOUBLE THICKNESS BLADES FOR DUCT DEPTHS GREATER THAN 36”. USE NOTRAILING EDGES.

C. ALL FLEXIBLE DUCTS SHALL NOT EXCEED SIX FEET IN LENGTH.

D. RETURN AIR PLENUM: OTHER HVAC SYSTEMS IN THE PROJECT AREA USE THE SPACE ABOVE THE CEILING ON EACH FLOOR AS A RETURN AIR PLENUM.CONFORM TO THE REQUIREMENTS OF NFPA AND LOCAL CODE REQUIREMENTS FOR ALL MATERIAL INSTALLED IN THE RETURN AIR PLENUM.

E. PROVIDE A COMPLETE DUCTED RETURN AIR PATH BETWEEN ALL NEW AND MODIFIED RETURN AIR DEVICES (GRILLES ETC.) AND THEIR RESPECTIVE HVAC UNIT.

F. ALL BRANCH DUCTS TO DIFFUSERS/GRILLES TO BE PROVIDED WITH A BALANCING DAMPER.

45. SUPPORT PIPE WITH ROD AND CLEVIS, RING HANGERS, TRAPEZE, OR CLAMPS. NO PIPE TAPE OR STRAPPING ALLOWED. ALL HANGERS SHALL BE SIZED FOR OD OFINSULATION, IF ANY. PROTECT INSULATED LINES WITH 20 GA SHEET METAL SHIELDS FOR PIPING 1-1/2” AND LESS. PROVIDE CALCIUM SILICATE INSULATION INSERTSFOR ALL INSULATED PIPING 2” AND LARGER. MAINTAIN VAPOR BARRIER ON ALL COLD LINES. ISOLATE BARE COPPER LINES FROM HANGERS WITH VIBRASORB OREQUIVALENT, COPPER COATED HANGERS ARE NOT SUFFICIENT, WRAPPING PIPE WITH TAPE NOT ACCEPTABLE.

46. NEW HOT AND COLD WATER BRANCHES TO BE ROUTED FROM NEAREST HOT WATER AND COLD WATER OF LINE SIZE EQUAL TO OR GREATER THAN NEWBRANCH--TYPICAL. EXISTING HOT AND COLD WATER BRANCHES TO BE REMOVED MUST BE CAPPED BACK AT MAINS, NO DEAD LEGS ALLOWED

47. PROVIDE LINE SIZE ISOLATION VALVES ON ALL BRANCH PIPING TO INDIVIDUAL ROOMS.

48. REFER TO PLUMBING FIXTURE CONNECTIONS SCHEDULE FOR PIPE SIZES TO INDIVIDUAL PLUMBING FIXTURES, UNLESS NOTED OTHERWISE.

49. PROVIDE SHOCK ARRESTERS AT ALL DOMESTIC HOT AND COLD WATER BRANCHES SERVING FIXTURES AND EQUIPMENT WITH QUICK CLOSING VALVES. SUCHFIXTURES AND EQUIPMENT INCLUDES FLUSH VALVE WATER CLOSETS, DISHWASHERS, ICE MACHINES, AND CLOTHES WASHERS. SHOCK ARRESTERS SHALL BECONSTRUCTED WITH A PISTON IN A SEALED COPPER TUBE CHAMBER, AND APPROVED FOR INSTALLATION WITHIN WALLS WITHOUT ACCESS PANELS. SIOUX CHIEFOR EQUIVALENT. BELLOWS TYPE NOT ACCEPTABLE.

50. DOMESTIC HOT AND COLD PIPING INSIDE BUILDING--BURIED LINES, TYPE “K” SOFT ANNEALED COPPER WATER TUBE, SINGLE LENGTH TO AVOIDFITTINGS, (WROUGHT COPPER FITTINGS WHERE UNAVOIDABLE) AND 1100°F SOLDER. NON-BURIED LINES, TYPE “L” HARD COPPER WATER TUBE, WROUGHT COPPERFITTINGS AND NO LEAD 95-5 SOLDER.

51. COPPER PIPE VALVES AND SPECIALTIES

A. GATE VALVES - BRONZE, CLASS 125, 200 LB. W.O.G.B. BALL VALVES - BRONZE, CLASS 125, 600 LB. W.O.G.C. CHECK VALVES - BRONZE, CLASS 125, 200 LB. W.O.G.D. BALANCING VALVES - 125 PSI W.P. FOR 250 DEGREE FARENHEIGHT SERVICE TIGHT SHUTOFF, TOUR AND ANDERSON STA, ARMSTRONG CBV, GERAND, OR

FLOWSET, BELL AND GOSSETT CIRCUIT SETTER.E. DIRECT UNIONS: FURNISH AND INSTALL A DIELECTRIC UNION AT EACH CONNECTION BETWEEN DISSIMILAR METALS.

52. MATERIALS; SOIL, WASTE, AND VENT PIPING (INSIDE BUILDING)

A. LINES ABOVE/BELOW GROUND--STANDARD WEIGHT, C.I. EPOXY COATED SOIL PIPE, AND FITTINGS. HUB AND SPIGOT WITH NEOPRENE GASKETS, OR NO HUBWITH 4-BAND HEAVY DUTY CLAMPS. UP THROUGH 2-1/2” MAY BE STANDARD WEIGHT, GALVANIZED STEEL PIPE WITH BLACK, W.I. DRAIN FITTINGS, OR DWVCOPPER TUBE WITH DWV FITTINGS AND 95-5 NO LEAD SOLDER.

53. PROVIDE EXPANSION JOINTS OR LOOPS ON ALL CHILLED WATER PIPING RUNS IN EXCESS OF 50 FEET AND IN ACCORDANCE WITH THE MANUFACTURER'SRECOMMENDATIONS.

54. GRADE AND VALVE ALL CHILLED WATER PIPING WITH 3/4” HOSE END VALVES TO PERMIT COMPLETE DRAINAGE OF THE SYSTEM. VENT ALL HIGH POINTS INEQUIPMENT ROOMS AS NECESSARY WITH AUTOMATIC AIR VENTS PIPED TO CONVENIENT DRAIN. ALL HIGH POINTS IN SYSTEM OUTSIDE OF EQUIPMENT ROOMSWITH COMBINATION AUTOMATIC/MANUAL AIR VENTS AS REQUIRED TO RELIEVE AIR IN THE SYSTEM.

55. GAS PIPING: SCHEDULE 40 BLACK STEEL PIPE, 150 LB. MALLEABLE IRON SCREWED FITTINGS ON ABOVE GROUND PIPE, WELDED FITTINGS WITH ALL PIPING COATEDAND WRAPPED ON BURIED PIPE.

56. GAS VALVES: NON-LUBRICATED BALL STYLE VALVE WITH RESILIENT SEATS, AND ADJUSTABLE GLAND PACKING NUT, AGA AND UL LISTED FOR NATURAL GASSERVICE.

57. PROVIDE PLASTIC GROMMETS ON ALL HEATING WATER PIPING PASSING THROUGH WOOD JOISTS AND STUDS.

58. MATERIALS; HYDRONIC PIPING

A. ABOVE GRADE, UP THROUGH 2-1/2”: SCHEDULE 40 STEEL PIPE WITH MALLEABLE IRON THREADED FITTINGS, OR TYPE “L” COPPER TUBE WITH WROUGHTCOPPER FITTINGS AND 95-5 NO LEAD SOLDER.

B. ABOVE GRADE, 3” AND LARGER: SCHEDULE 40 STEEL PIPE WITH CAST IRON OR STEEL WELDING FITTINGS.

C. BELOW GRADE, UP THROUGH 1-1/4”: TYPE “K” SOFT ANNEALED COPPER TUBE, SINGLE LENGTH TO AVOID FITTINGS, (WROUGHT COPPER FITTINGS WHEREUNAVOIDABLE) AND 1100 DEGREE FARENHEIGHT SOLDER INSULATE WITH 1” THICK CLOSED CELL ELASTOMERIC INSULATION. ALL BURIED PIPE SHALL BESURROUNDED WITH 4” OF CLEAN SAND.

D. BELOW GRADE, 1-1/2” AND LARGER: JACKETED, PRE-INSULATED PIPING, WITH FLUID CARRIER PIPE EQUAL TO ABOVESPECIFICATION. ROVANCO, RICWELL/PERMA-PIPE OR EQUIVALENT.

59. DRAIN PAN PIPING--NOT BURIED--TYPE “M” COPPER, WROUGHT COPPER FITTINGS, AND 95-5 SOLDER; BURIED--TYPE L” COPPER WROUGHT COPPERFITTINGS, AND 95-5 SOLDER. ALL BURIED PIPE SHALL BE SURROUNDED WITH 4” OF CLEAN SAND.

60. INSULATE ALL CONDENSATE PIPING, CHILLED WATER, DOMESTIC WATER, DOMESTIC HOT WATER, DOMESTIC HOT WATER RECIRCULATION, AND STORM ANDOVERFLOW PIPING WITH U.L. APPROVED, WHITE, ALL SERVICE, GLASS FIBER, SNAP-ON, PIPE INSULATION. INSULATE FITTINGS WITH GLASS FIBER BLANKETINSULATION AND PREMOLDED P.V.C. COVERS. ALL MATERIALS SHALL HAVE A SMOKE DEVELOPED RATING OF 50 OR LESS AND A FLAME SPREAD RATING OF 25 ORLESS. INSULATION SHALL PASS UNINTERRUPTED THROUGH HANGERS. VAPOR BARRIERS SHALL BE CONTINUOUS, AND SEALED WITH “NON-BREATHING” MASTIC ONCOLD PIPING. ALL RAW EDGES OF INSULATION SHALL BE NEATLY TRIMMED AND SEALED WITH MASTIC.

A. INSULATION THICKNESS BELOW BASED ON INSULATION CONDUCTIVITY VALUE NOT EXCEEDING 0.27 BTU*IN/(HR*FT^2*°F):

1) CHILLED WATER, HEATING WATER - ALL PIPE SIZES, 1.” THICK. - . RUNOUTS WITHIN 4 FEET OF TERMINAL AND 1” PIPE DIAMETER OR LESS - 1/2” THICK.

2) DOMESTIC HOT WATER (DHW) AND DOMESTIC HOT WATER RECIRCULATION: ALL PIPE SIZES - 1” THICK; NON-RECIRCULATED DHW RUNOUTS WITHIN 8 FEETOF FIXTURES - 1/2” THICK.

3) DOMESTIC COLD WATER AND CONDENSATE: ALL PIPE SIZES - 1/2” THICK.

4) HORIZONTAL STORM AND OVERFLOW PIPING: ALL SIZES - 1” THICK.

61. EQUIPMENT LABELS: LABEL ALL PIPING AND EQUIPMENT. PROVIDE FULL BAND OR STRIP TYPE MARKERS AND FLOW ARROWS ON PIPING. PROVIDE TAPE BANDINGON EACH END OF LABEL/FLOW ARROW. PROVIDE ENGRAVED PLASTIC VALVE TAGS WITH VALVE NUMBER AND ATTACH WITH STANDARD CHAIN OR S-HOOKS.PROVIDE ENGRAVED PLASTIC SIGN ON OR NEAR SPECIFIED EQUIPMENT.

62. MEDICAL GAS SYSTEMS

A. REGULATORY REQUIREMENTS:

1) CONFORM TO NFPA 99.

B. SUBMITTALS:

1) PRIOR TO START OF WORK, THE CONTRACTOR'S MEDICAL GAS CERTIFIER SHALL REVIEW AND PROVIDE COMMENT TO ENGINEERS DESIGN TO INSUREFINAL COMPLIANCE.

2) SUBMIT MANUFACTURER'S PRODUCT DATA ON THE FOLLOWING:

a. MEDICAL GAS TUBING.b. STATION OUTLETS.c. MEDICAL GAS RAIL SYSTEMS.d. BRAZER CERTIFICATIONS.

C. PIPING MATERIALS

1) PIPING: COPPER, TYPE “L” OR MEDICAL QUALITY TYPE ACR, HARD TEMPER, CLEANED, CAPPED AND LABELED FOR OXYGEN SERVICE.

2) FITTINGS: WROUGHT COPPER, SOLDER JOINT, LONG RADIUS, CLEANED, CAPPED AND LABELED FOR OXYGEN SERVICE.

D. STATION OUTLETS:

1) OUTLETS TO BE GAS SPECIFIC AND ACCEPT ONLY SPECIFIC CONNECTIONS COMPATIBLE SPECIFIED. OUTLETS SHALL BE UL LISTED, CSA APPROVED AND MEET NFPA 99 STANDARD.

E. WASHING:

1) ON-SITE WASHING OF PIPE AND FITTINGS SHALL BE LIMITED TO RE-CLEANING SURFACES IN THE IMMEDIATE VICINITY OF JOINTS WHICH HAVE BECOME CONTAMINATED PRIOR TO JOINING.

F. JOINING:

1) ALL WORK SHALL BE PERFORMED BY BRAZERS CERTIFIED IN ACCORDANCE WITH AWS B2.2.

2) USE SILVER BRAZING ALLOY ANSI/AWS A5.8.

3) USE NO FLUX.

4) MAINTAIN A FLOW OF DRY OIL-FREE NITROGEN IN TUBING WHILE BRAZING TO PREVENT INTERNAL CORROSION.

5) JOINTS SHALL BE BRAZED WITHIN ONE HOUR OF BEING CLEANED. USE ONLY PLASTIC CAPS ON OD OF PIPE WHEN STOPPING WORK. DO NOT USE TAPE.

G. TESTS BY CONTRACTOR:

1) PERFORM THE INITIAL LEAK TEST, BLOWDOWN TEST, PRESSURE TEST, PIPING PURGE, AND CROSS CONNECTION TEST AS SPECIFIED IN NFPA 99. ISOLATEANY EQUIPMENT NOT RATED FOR THE TEST PRESSURE.

H. CERTIFICATION:

1) THE MEDICAL GAS SYSTEM SHALL BE TESTED BY A FACTORY TRAINED SERVICE REPRESENTATIVE OF THE MEDICAL GAS EQUIPMENT MANUFACTURERAFTER INSTALLATION OF THE SYSTEM HAS BEEN COMPLETED. THE REPRESENTATIVE SHALL PERFORM THE FOLLOWING SYSTEM VERIFICATION TESTS INACCORDANCE WITH NFPA 99: CROSS CONNECTION TEST, FLOW TEST, PIPING PURGE TEST, PIPING, PURITY TEST, AND CONCENTRATION TEST. APPROVEDMEDICAL GAS CERTIFICATION CONTRACTORS ARE SOUTHWEST MEDICAL GAS OR HEALTH CHOICE ENTERPRISES.

2) AT THE CONCLUSION OF TESTING, THE CERTIFIER SHALL PRESENT A TEMPORARY CERTIFICATE TO THE OWNER OR THE APPROPRIATE RESPONSIBLEPARTY, ANY ABNORMALITIES SHALL BE NOTED. IN ADDITION, IF REPAIR TO ANY PIECE OF MEDICAL GAS EQUIPMENT IS NECESSARY, PERFORM THIS REPAIRIN A REASONABLE TIME PERIOD. THE W

63. FIRE PROTECTION DESIGN/BUILD REQUIREMENTS:

A. PROVIDE MODIFICATIONS AND EXPANSION TO THE EXISTING AUTOMATIC SPRINKLER SYSTEM SERVING EXISTING BUILDING. COMPLETE DRAWINGS,SPECIFICATIONS, AND DETAILS SHALL BE SUBMITTED BY THE FIRE SPRINKLER DESIGN-BUILD CONTRACTOR.

B. THE FIRE SPRINKLER CONTRACTOR SHALL SERVE AS THE ENGINEER OF RECORD FOR ALL WORK PERFORMED UNDER THIS DIVISION. IF REQUIRED BY THEAUTHORITY HAVING JURISDICTION, (A.H.J.) SUBMIT COMPLETE FIRE SPRINKLER SYSTEM SHOP DRAWINGS AND HYDRAULIC CALCULATIONS, GENERATED BYCONTRACTOR. SHOP DRAWINGS SHALL BE A MINIMUM 1/8” SCALE, AND SHALL SHOW DEVICE AND APPLIANCE LOCATIONS, BUILDING BACKGROUNDINFORMATION, ROOM OCCUPANCY DESCRIPTIONS, DOOR SWINGS, FIRE RATINGS AND FIRE PROTECTION SYSTEM LAYOUT AND DETAILS. SHOP DRAWINGS ANDHYDRAULIC CALCULATIONS SHALL BE SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF NEW MEXICO. SUBMIT SHOP DRAWINGS ANDHYDRAULIC CALCULATIONS TO THE BUILDING AND FIRE DEPARTMENTS AND OBTAIN THEIR APPROVAL BEFORE SUBMISSION TO THE ARCHITECT.

C. WHERE REQUIRED BY THE A.H.J., ALL NEW SPRINKLER HEADS SHOULD HAVE THE CONNECTING MAIN AND BRANCH PIPE SIZES SHOWN.

1) SHOW THE CONNECTING MAIN AND BRANCH PIPE SIZES FOR ALL NEW, RELOCATED AND EXISTING SPRINKLER HEADS.

2) CONFORM TO LIGHT HAZARD OCCUPANCY REQUIREMENTS OF NFPA 13.

3) PROVIDE FLOW TEST INDICATING STATIC AND RESIDUAL PRESSURED DEVELOPED UNDER FIRE FLOW CONDITIONS AS REQUIRED BY A.H.J.

D. EXTEND THE EXISTING SPRINKLER SYSTEM, RELOCATE EXISTING AND ADD NEW SPRINKLER HEADS IN ACCORDANCE WITH NFPA 13, ALL APPLICABLE CODESAND ORDINANCES AND PROJECT REQUIREMENTS TO COMPLETE THE WORK.

E. SYSTEM SHALL BE INSTALLED COMPLETE AND OPERATIONAL, INCLUDING WATER FLOW INDICATOR, CONNECTIONS TO EXISTING ALARM, DRAIN PIPING,IDENTIFICATION SIGNS, ETC.

F. WORK SHALL BE PERFORMED BY A QUALIFIED FIRE SPRINKLER INSTALLER WITH A MINIMUM OF FIVE (5) YEARS EXPERIENCE IN SIMILAR INSTALLATIONS.

G. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO AND DURING INSTALLATION.

H. PROVIDE AN EXTRA STOCK OF SIX (6) SPRINKLER HEADS, THREE (3) OF EACH TYPE, AND A SPRINKLER WRENCH. SPRINKLER HEADS SHALL MATCH EXISTING INADJACENT AREAS.

64. COMBINATION FIRE AND SMOKE DAMPERS:

A. UNITS SHALL BE LABELED ACCORDING TO UL 555S. COMBINATION FIRE AND SMOKE DAMPERS SHALL BE LABELED ACCORDING TO UL 555 FOR 1-1/2HOUR RATING.

B. FUSIBLE LINKS SHALL BE REPLACEABLE AND 212 DEG F RATED.

C. FRAME AND BLADES SHALL BE AT LEAST 0.064-INCH THICK GALVANIZED SHEET STEEL, MOUNTING SLEEVE SHALL BE AT LEAST 0.052-INCH THICKGALVANIZED SHEET STEEL.

D. ELECTRICAL CONNECTION: 115V, SINGLE PHASE, 60 HZ.

A. BOOKS OF OPERATING AND MAINTENANCE INSTRUCTIONS SHALL BE PERSONALLY DELIVERED TO THE OWNER'S AUTHORIZED REPRESENTATIVE AND THEOWNER INSTRUCTED AS TO THEIR USE AND THE EQUIPMENT INVOLVED. (PROVIDE TWO BOOKS FOR EACH BUILDING). ALSO, INSTRUCT THE OWNER'SPERSONNEL ON EACH VALVE.

B. THE BOOK SHALL CONTAIN, BUT NOT BE LIMITED TO, THE FOLLOWING GENERAL ITEMS:1. SPARE PARTS LISTS FOR EACH PIECE OF EQUIPMENT.2. OPERATING MANUALS FOR EACH PIECE OF EQUIPMENT AND CONTROL.3. LUBRICATION CHARTS SHOWING TYPE OF LUBRICANT AND APPLICATION METHODS AND FREQUENCIES.4. FILTER CLEANING OR REPLACEMENT SCHEDULE. (ON CONTRACTOR'S LETTERHEAD STATIONARY).5. PREVENTIVE MAINTENANCE SCHEDULE FOR CHECKING ALL ITEMS SUCH AS BELT DRIVE, SAFETY CONTROLS AND OIL AND REFRIGERANT CHARGES.

CLEANING SCHEDULE OF ALL STRAINERS, TRAPS, COILS, TUBES, TOWER PANS, SPRAYS, ETC. (ON CONTRACTOR'S LETTERHEAD STATIONARY).6. NORMAL OPERATING INSTRUCTIONS INCLUDING A SEQUENCE OF OPERATION FOR EACH SYSTEM. (ON CONTRACTOR'S LETTERHEAD STATIONARY).7. INSTRUCTIONS AS TO PROCEDURE TO BE FOLLOWED FOR ANY EMERGENCY SITUATION, SUCH AS ALARMS OR SAFETY ITEMS BEING TRIPPED. (ON

CONTRACTOR'S LETTERHEAD STATIONARY).8. INSTRUCTIONS ON WHO TO CALL FOR SERVICE DURING GUARANTEE PERIOD. (ON CONTRACTOR'S LETTERHEAD STATIONARY).9. RECORD OF EQUIPMENT INSTALLED (COPY OF EACH SHOP DRAWING AS SET FORTH UNDER "SHOP DRAWING" PARAGRAPH).10. ALL WARRANTIES PROVIDED BY MANUFACTURERS ON THEIR EQUIPMENT THAT RUN LONGER THAN THE ONE YEAR GUARANTEE BY THE CONTRACTOR.

C. BOOKS SHALL BE ARRANGED IN SEQUENCE TO MATCH THE EQUIPMENT SCHEDULES INCLUDED IN THE SPECIFICATIONS.

D. PROVIDE RECORD DRAWINGS

E. APPROVAL WILL NOT BE GIVEN FOR FINAL PAYMENT UNTIL THE TESTS, BALANCING AND OPERATING INSTRUCTION PORTIONS HAVE BEEN COMPLETED.

OPERATION AND MAINTENANCE INSTRUCTIONS

1. ALL REFRIGERATION, BOILERS, AND PACKAGED EQUIPMENT SHALL BE STARTED BY THE MANUFACTURER OR UNDERTHE MANUFACTURER'S SUPERVISION. START-UP DATA SHALL BE RECORDED IN LOGS. COPIES OF START-UP LOGSSHALL BE FORWARDED TO MECHANICAL ENGINEER AND INCLUDED IN OPERATION AND MAINTENANCE

EQUIPMENT START-UP

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

PLUMBINGSPECIFICATIONNOTES SHEET

P0-02

Page 10: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

1"

2-1/2"

4"

(E) 6"SD

6"6"

4" 1-1/

2"

1"2"

2"

(E) 4"V

4"

2"2"

4"

4"

7

7 (E) 1

-1/2

"HW

(E) 2

"CW

(E) 2

"HW

(E) 2

-1/2

"CW

7 7

7

TYP.

(E) 2

"W

(E) 4"W

7

1(E) 4"VTR

6

6

6

6

7

TYP.

7

TYP.

7

7

7

7

7

(E) 1"HW(E) 2-1/2"CW

(E) 2"HW(E) 2-1/2"CW

(E) 4"W

7 7

7

7 77

7

7

7

TYP.

7TYP.

(E) CO

(E) 2"HW(E) 3"CW

(E) 2

"HW

(E) 3

"CW

(E) FS

(E) 4"W

(E) FS

(E) 4"W

(E) 6

"W(E

) 6"W

(E) 3"W

(E) 4

"WBELOW GRADE

ROUTED INCEILING SPACE

(E) 4

"W

(E) 3

/4"C

W(E

) 3/4

"HW

1

(E) 1

-1/4

"HW

(E) 3

/4"H

W

(E) 3

/4"C

W(E

) 3"W

(E) 4"W

(E) 1"HW(E) 2-1/2"CW

6

11

2

41

1

3

3

5

(E) 6"SD

(E) 4"SD

(E) 4

"SD

(E) 2"V

(E) 6

"SD

(E) 6"SD

(E) 6"SD

(E) 6

"SD

(E) 6

"SD

(E) 6

"SD

(E) 6

"SD

(E) 1

"HW

C(E

) 2-1

/2"C

W(E

) 3"C

W

(E) 3"CW

1

4

10

(E) 2" V

(E) 2

" V

.

8

8

9

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

PLUMBINGDEMOLITION PLAN

PD1-01Scale:

1 PLUMBING DEMOLITION PLAN1/8"=1'-0"

NOTES:

FLAG NOTES:#

1. ADDITIONAL STORM, HYDRONIC, DOMESTIC, WASTE,VENT AND MEDICAL GAS PIPING MAY BE ROUTED INSPACE THAT IS NOT REPRESENTED, BUT IS TOREMAIN. OTHER SYSTEMS MAY EXIST WITHIN THESPACE THAT ARE NOT REPRESENTED ON THESEDRAWINGS; MODIFICATIONS TO THESE SYSTEMS ARENOT ANTICIPATED.

2. FIELD VERIFY ALL COMPONENTS PRIOR TODEMOLITION. THE INFORMATION ON THIS SHEET WASOBTAINED, IN PART, FROM HISTORIC DESIGNDRAWINGS. ONLY PORTIONS OF THE SYSTEMS WEREACCESSIBLE FOR VISUAL CONFIRMATION DURINGDESIGN PROCESS.

3. (E) WASTE SYSTEM SERVING SPACE IS LOCATED INBELOW GRADE. THERE IS CURRENTLY AN EXISTINGROOF DRAIN SYSTEM LOCATED IN THE CEILINGSPACE ABOVE.

4. REMOVE ALL PLUMBING IFIXTURES INDICATED.

5. TEMPORARILY SEAL OR CAP PIPING TO BE RE-USEDFOR LATER CONNECTION.

6. REMOVE ALL DEMOLISHED COLD WATER, HOT WATERAND HOT WATER RECIRCULATION PIPING BACK TOBRANCH FROM MAIN TO ELIMINATE ALL DEAD ENDS INDOMESTIC WATER PIPING.

7. NOTIFY ENGINEER IMMEDIATELY OF ANYDISCREPANCIES OF INFORMATION REPRESENTED INTHE DOCUMENTS VERSUS WHAT IS FOUND IN THEFIELD.

8. COORDINATE PATCHING AND REPAIRS OF WALLS,CEILINGS AND FLOORS WITH ARCHITECT.

9. PATCH STRUCTURAL OPENINGS IN FLOORS, WALLSAND ROOFS THAT WERE PREVIOUSLY OCCUPIED BYSYSTEMS AND EQUIPMENT DEMOLISHED UNDER THISCONTRACT IN ACCORDANCE WITH STRUCTURALENGINEER'S REQUIREMENTS.

10. COORDINATE WITH OWNER FOR DISPOSAL ORRE-USE REQUIREMENTS OF PLUMBING FIXTURES TOBE REMOVED.

1. REMOVE EXISTING SINK COMPLETE. REMOVEEXISTING WASTE PIPING DOWN TO BELOW GRADEAND SEAL AND CAP. REMOVE EXISTING HW/CW ANDVENT LINES BACK TO NEAREST ACTIVE MAIN. FIELDVERIFY EXISTING CONDITIONS AND EXACT LOCATIONOF ALL PIPING.

2. REMOVE EXISTING WALL HUNG DRINKING FOUNTAINCOMPLETE. REMOVE EXISTING WASTE PIPING DOWNTO BELOW GRADE AND SEAL AND CAP. REMOVEEXISTING CW AND VENT LINES BACK TO NEARESTACTIVE MAIN AND CAP. REMOVE EXISTING SUPPORTSYSTEM. FIELD VERIFY EXISTING CONDITIONS ANDEXACT LOCATION OF ALL PIPING.

3. REMOVE EXISTING FLOOR DRAIN COMPLETE.REMOVE EXISTING WASTE PIPING DOWN TO BELOWGRADE AND SEAL AND CAP. REMOVE EXISTING VENTCOMPLETE BACK TO EXISTING ACTIVE MAIN AND CAP.REMOVE ASSOCIATED TRAP PRIMER DEVICE ANDASSOCIATED SUPPLY PIPING. REMOVE CW FROMTRAP PRIMER BACK TO ACTIVE AMIN AND CAP. FIELDVERIFY EXISTING CONDITIONS AND EXACT LOCATIONOF ALL PIPING.

4. REMOVE EXISTING WATER CLOSET COMPLETE.REMOVE EXISTING WASTE PIPING DOWN TO BELOWGRADE AND SEAL AND CAP. REMOVE EXISTING VENTCOMPLETE BACK TO EXISTING ACTIVE MAIN AND CAP.REMOVE EXISTING CW SUPPLY COMPLETE BACK TONEAREST ACTIVE MAIN. FIELD VERIFY EXISTINGCONDITIONS AND EXACT LOCATION OF ALL PIPING.

5. REMOVE EXISTING URINAL COMPLETE. REMOVEEXISTING WASTE PIPING DOWN TO BELOW GRADEAND SEAL AND CAP. REMOVE EXISTING VENTCOMPLETE BACK TO EXISTING ACTIVE MAIN AND CAP.REMOVE EXISTING CW SUPPLY COMPLETE BACK TONEAREST ACTIVE MAIN. FIELD VERIFY EXISTINGCONDITIONS AND EXACT LOCATION OF ALL PIPING.

6. EXISTING STORM PIPING FROM ROOF ABOVE TOREMAIN. STORM PIPING TO REMAIN ACTIVE DURINGCONSTRUCTION. PROTECT PIPING DURINGCONSTRUCTION AND COORDINATE EXISTINGLOCATION WITH OTHER DISCIPLINES.

7. EXISTING PLUMBING FIXTURES TO REMAIN. PROTECTPLUMBING FIXTURE DURING CONSTRUCTION.

8. REMOVE EXISTING MEDICAL GAS STATIONCOMPLETE. REMOVE ALL ASSOCIATED A,V,O2 PIPINGCOMPLETE BACK TO NEAREST ACTIVE MAIN INCEILING SPACE AND CAP. FIELD VERIFY EXISTINGCONDITIONS AND EXACT LOCATION.

9. EXISTING MEDICAL GAS VALVE BOX TO REMAIN.FIELD VERIFY EXISTING CONDITIONS AND EXACTLOCATION.

10. REMOVE EXISTING HOSE BIBB HYDRANT ANDASSOCIATED CW SUPPLY LINE COMPLETE. FIELDVERIFY EXISTING CONDITIONS AND EXACT LOCATION.

11. EXISTING STORM DRAINAGE FROM CEILING SPACEDOWN TO BELOW GRADE IS TO REMAIN. EXISTINGSTORM DRAINAGE PIPING BELOW GRADE TOEXTERIOR IS REMAIN, BUT IS NOT SHOWN. TAKEPRECAUTION TO AVOID DAMAGING DURINGCONSTRUCTION. FIELD VERIFY EXISTING CONDITIONSAND EXACT LOCATION.

Scale:

2 RADIOLOGY CORRIDOR DEMOLITION PLAN1/8"=1'-0"

Page 11: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

2"3/4"3/4"

(E)V(E)A

(E)O2(E)DPSS

(E)V(E)A

(E)O2

(E)DPSS2"

3/4"3/4"

(E)V

(E)A

(E)O

2

3/4"

1/2"

1/2"

(E)V

(E)A

(E)O

2

(E)V

(E)A

(E)O

2

3/4"

3/4"

1/2"

1/2"

(E)V(E)A

(E)O2

(E)DPSS2"

3/4"3/4"

(E)D

PS

S

(E)V

(E)A

(E)O

2

2"3/4"

3/4"

1

2

34

5

4

5

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

PLUMBINGMEDICAL GASDEMOLITION PLAN

PD1-02Scale:

1 PLUMBING MEDICAL GAS DEMOLITION PLAN1/8"=1'-0"

NOTES:

FLAG NOTES:#

1. ADDITIONAL STORM, HYDRONIC, DOMESTIC, WASTE,VENT AND MEDICAL GAS PIPING MAY BE ROUTED INSPACE THAT IS NOT REPRESENTED, BUT IS TOREMAIN. OTHER SYSTEMS MAY EXIST WITHIN THESPACE THAT ARE NOT REPRESENTED ON THESEDRAWINGS; MODIFICATIONS TO THESE SYSTEMS ARENOT ANTICIPATED.

2. FIELD VERIFY ALL COMPONENTS PRIOR TODEMOLITION. THE INFORMATION ON THIS SHEET WASOBTAINED, IN PART, FROM HISTORIC DESIGNDRAWINGS. ONLY PORTIONS OF THE SYSTEMS WEREACCESSIBLE FOR VISUAL CONFIRMATION DURINGDESIGN PROCESS.

3. (E) WASTE SYSTEM SERVING SPACE IS LOCATED INBELOW GRADE. THERE IS CURRENTLY AN EXISTINGROOF DRAIN SYSTEM LOCATED IN THE CEILINGSPACE ABOVE.

4. REMOVE ALL PLUMBING IFIXTURES INDICATED.

5. TEMPORARILY SEAL OR CAP PIPING TO BE RE-USEDFOR LATER CONNECTION.

6. REMOVE ALL DEMOLISHED COLD WATER, HOT WATERAND HOT WATER RECIRCULATION PIPING BACK TOBRANCH FROM MAIN TO ELIMINATE ALL DEAD ENDS INDOMESTIC WATER PIPING.

7. NOTIFY ENGINEER IMMEDIATELY OF ANYDISCREPANCIES OF INFORMATION REPRESENTED INTHE DOCUMENTS VERSUS WHAT IS FOUND IN THEFIELD.

8. COORDINATE PATCHING AND REPAIRS OF WALLS,CEILINGS AND FLOORS WITH ARCHITECT.

9. PATCH STRUCTURAL OPENINGS IN FLOORS, WALLSAND ROOFS THAT WERE PREVIOUSLY OCCUPIED BYSYSTEMS AND EQUIPMENT DEMOLISHED UNDER THISCONTRACT IN ACCORDANCE WITH STRUCTURALENGINEER'S REQUIREMENTS.

10. COORDINATE WITH OWNER FOR DISPOSAL ORRE-USE REQUIREMENTS OF PLUMBING FIXTURES TOBE REMOVED.

1. REMOVE MEDICAL GAS STATION COMPLETE.FIELD VERIFY EXACT LOCATION.

2. REMOVE MEDICAL VALVE BOX COMPLETE. FIELDVERIFY EXACT LOCATION.

3. REMOVE AND CAP O2 TO VALVE. FIELD VERIFYEXACT LOCATION AND CONDITIONS.

4. REMOVE AND CAP A TO VALVE. FIELD VERIFYEXACT LOCATION AND CONDITIONS.

5. REMOVE AND CAP VAC BACK TO NEARESTACTIVE MAIN. FIELD VERIFY EXACT LOCATIONAND CONDITIONS.

Page 12: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

4"

(E) 6"SD

6"6"

4"

4"

(E) 1

-1/2

"HW

(E) 2

"CW

(E) 2

"HW

(E) 2

-1/2

"CW

(E) 2

"W

(E) 4"W

(E) 4"VTR

(E) 1"HW

(E) 2"HW(E) 2-1/2"CW

(E) 4"W

(E) CO

(E) 2"HW(E) 3"CW

(E) 2

"HW

(E) 3

"CW

(E) FS

(E) 4"W

(E) FS

(E) 4"W

(E) 6

"W(E

) 6"W

(E) 3"W

(E) 4

"WBELOW GRADE

ROUTED INCEILING SPACE

(E) 4

"W

(E) 3

/4"C

W(E

) 3/4

"HW

(E) 1

-1/4

"HW

(E) 3

"W

(E) 4"W

(E) 1"HW

(E) 6"SD

(E) 4"SD

(E) 4

"SD

(E) 6

"SD

(E) 6"SD

(E) 6"SD

(E) 6

"SD

(E) 6

"SD

(E) 6

"SD

(E) 6

"SD

(E) 1

"HW

C(E

) 2-1

/2"C

W(E

) 3"C

W

(E) 3"CW

1 & 2P4-01

P6

P16

P17

P19

P6

P5

P5

P5

2" W

4" W

4" W

P7 P7

P7

P8

P10

3/4"

HW

3/4"

CW

3/4" H

W

3/4"

HW

3/4"

HW

1-1/

2" C

W

2-1/2" CW

21

5

4

3

5

7

1

1

1

5

P11

P14

2" W

2" W

3" W

2" W

P11

P6

(E)4" VTR

3" V

3" V

2" V

2" V

2" V

2" V

1-1/2" V

2" V

2" V 3" V

1-1/

2" C

W

3/4" HWC

(E)2-1/2"CW

3/4"

HW

3/4"

CW

3/4"

HW

3/4"

CW

P18

3/4" HW/CW

3/4"HW/CW

3/4"

CW

P6

2" V

ELEV.

MED.GAS

STAIRX1-SX

STAIR1067

EXTERIOR COURTYARD - NO PUBLIC ACCESS

TELE.

OFFICE1031

EXAM1032

EXAM1033

EXAM1034

EXAM1036

EXAM1037

EXAM1038

EXAM1039

EXAM1041

CORRIDOR1029

TRIAGE/ASSESMENT

1019

RECEPTION/ASSESMENT

1018

SECURITY1018A

WAITING1013

WHEELCHAIRSTORAGE

1002

QUIETWAITING

1011

ENTRYVESTIBULE

1001

WOMEN1008

MEN1009

HSKP1004

VENDING1007

CORRIDOR1005

CORRIDOR1161

CONSULT1024

MULTI-PATIENTEXAM/HOLDING

1026

PATIENT/SPECIMENTOILET

1022

CORRIDOR1021

CORRIDOR1020

FAST TRACK1023

MEDICATION/SUPPLY

1014

NUTRITION1016

FAST TRACK1023B

FAST TRACK1023C

FAST TRACK1023A

FAST TRACK1023D

FAST TRACK1023E

FAST TRACK1023F

FAST TRACK1023G

TREATMENT1078

CONTROL1082

TREATMENT1081

ALCOVE1076

CLEAN SUPPLY/EQUIPMENT

1074

TREATMENT1077

PATIENTTOILET

1079

X-RAY1083

COMM.1084

CORRIDOR1028

ELEC.1085

ALCOVE1088A

ALCOVE1088BALCOVE

1088C

CORRIDOR1087

MEDICATION1093

NOURISHMENT1094

PYXIS1098

STAFFTOILET

1097

PATIENTTOILET

1098

SOILEDUTILITY

1099NURSESTATION

1092

CORRIDOR1091

CRASH CART1111

CORRIDOR1109

ALCOVE1108

EXAM1101

EXAM1106

OBEXAM1102

OBEXAM1107

PATIENTTLT./SHWR

1103

PATIENTTOILET11034

CORRIDOR1027

EXAM1042

EXAM1043

EXAM1044

ISOLATION1046

ANTE1048FIRE

1047

NURSESTATION

1073CORRIDOR1072

EXAM1049

EXAM1051

WHEELCHAIRSTORAGE

1052

VESTIBULE1053

DECONSHOWER

1054

EMSCLOSET

1056

PSYCH.1057

TRAUMA1058

TRAUMA1059

CORRIDOR1071

HSKP1061

ELEV.EQUIP.

1068

ELEV.LOBBY

1064

ALCOVE1062

RESULTSWAITING

1117

OFFICE1123

STAFFLOCKERS

1124

OFFICE1123 STAFF

LOUNGE1152

OFFICE1112

OFFICE1113

TLT./SHOWER1114

CORRIDOR1134

CORRIDOR1127

(E) 4"W

WCO

(E) 2" V

(E) 2

" V

WCOWCO

3/4" HW/CW2" V

5

(E) 1

-1/2

"HW

(E) 1

-1/2

"HW

(E) CW

5

WCO

WCO

WCO

WCO

WCO

WCO

WCOWCO

WCO

WCO

WCO

2" W

3" W

WHA

1/2" CW

1/2"HW

8

2

12

11

5

11

2

2

8

8

9

6

P11

P17

1-1/4" CW

12

1

P10

13

P11

2" W

14

P13

3/4" CW

1

TOILET

PASSAGEWAYX1XX

BEDSTORAGE

X1XX

EXAM #1X1XX

OFFICEX1XX

XRAYREADING

X1XX

PHYSICIAN'SREADING RM.

X1XX

CORRIDOR

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

PLUMBINGPLAN

P1-01

Scale:

1 PLUMBING PLAN1/8"=1'-0"

NOTES:

1. CONNECT NEW CW TO EXISTING CW OF SAME SIZEOR LARGER IN CEILING SPACE. FIELD VERIFYEXISTING CONDITIONS AND EXACT LOCATION. SIZEPER PLAN.

2. CONNECT NEW CW/HW TO EXISTING CW/HW OFSAME SIZE OR LARGER. FIELD VERIFY EXISTINGCONDITIONS EXACT LOCATION. SIZE PER PLAN.

3. CONNECT NEW HWC TO EXISTING HWC OF SAMESIZE OR LARGER IN CEILING SPACE. FIELD VERIFYEXISTING CONDITIONS EXACT LOCATION. SIZE PERPLAN.

4. CIRCUIT SETTER BALANCING VALVE. SET TO (1.5GPM) ADJUSTABLE. PROVIDE WITH ISOLATION BALLVALVE BEFORE AND AFTER CIRCUIT SETTER VALVE.

5. CONNECT NEW WASTE LINE TO EXISTING WASTEOF SAME SIZE OR LARGER. FIELD VERIFY EXISTINGCONDITIONS, EXISTING INVERT AND EXACTLOCATION. SIZE PER PLAN.

6. ROUTE 1/2" HW/CW DOWN IN WALL AND CAP FORFUTURE CONNECTION. PROVIDE STUB-OUT FORFUTURE LAVATORY.

7. ROUGH-IN 2" WASTE AND 1-1/2" VENT IN WALL FORFUTURE SINK CONNECTION.

8. CONNECT NEW VENT TO EXISTING VENT OF SAMESIZE OR LARGER IN CEILING SPACE. FIELD VERIFYEXISTING CONDITIONS EXACT LOCATION. SIZE PERPLAN.

9. EXISTING STORM DRAIN LEADER DOWN TO BELOWGRADE TO REMAIN. FIELD VERIFY EXACT LOCATION.FURR-OUT AROUND EXISTING PIPING AS REQUIRED.PROVIDE ACCESS FOR STORM CLEAN-OUT.PROTECT EXISTING PIPING DURING DEMOLITIONAND CONSTRUCTION.

10. CONNECT NEW HW TO EXISTING HW OF SAME SIZEOR LARGER IN CEILING SPACE. FIELD VERIFYEXISTING CONDITIONS EXACT LOCATION. SIZE PERPLAN.

11. CONNECT NEW CW TO EXISTING CW OF SAME SIZEOR LARGER IN CEILING SPACE. FIELD VERIFYEXISTING CONDITIONS EXACT LOCATION. SIZE PERPLAN.

12. CONNECT NEW VENT TO EXISTING 4" VTR. FIELDVERIFY EXISTING CONDITIONS AND EXACTLOCATION.

13. 3/4" HW/CW DOWN IN WALL. ROUTE 1/2" HW/CW TOCOUNTER SINK. EXTEND 1/2" HW/CW TO WATERDISPENSERS BY OTHERS AND CONNECT PERMANUFACTURERS REQUIREMENTS WITH QUARTERTURN ANGLE STOPS. EXTEND 1/2" CW TO ICEMAKER BOX. ROUTE DRAIN FROM ICE MACHINE TOCOUNTER SINK TAIL PIECE AND TERMINATEINDIRECTLY ABOVE TRAP.

14. INSTALL FLOOR DRAIN FLUSH WITH FLOORDEPRESSION FOR WHEEL CHAIR SCALE.COORDINATE EXACT LOCATION WITH WHEEL CHAIRSCALE MANUFACTURERS INSTALLATIONREQUIREMENTS.

FLAG NOTES:#

1. REFER TO P0-01 FOR PLUMBING GENERAL NOTES.

2. REFER TO P5-01 FOR PLUMBING DIAGRAMS.

3. REFER TO P0-01 FOR THE PLUMBING FIXTURECONNECTION SCHEDULE FOR PIPE SIZES TOINDIVIDUAL FIXTURES.

4. THE RENOVATION IS TO BE EXECUTED IN PHASES.REFER TO ARCHITECTURAL PLANS FOR PROJECTPHASING.

Scale:

2 RADIOLOGY CORRIDOR FLOOR PLAN1/8"=1'-0"

1. EXISTING WET AND DRY FIRE PROTECTION SYSTEMIN AREA INDICATED SHALL BE MODIFIED TOPROVIDE COVERAGE FOR THE REDESIGNEDEXISTING SPACE. MODIFY AS REQUIRED ORPROVIDE NEW SPRINKLER HEAD LAYOUT FORCOMPLETE COVERAGE OF THE RENOVATED AREA.MODIFY PIPING OR REPOSITION EXISTING FIRESPRINKLER HEADS AS REQUIRED.

FIRE PROTECTION NOTESX

Page 13: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

2"3/4"3/4"

(E)V(E)A

(E)O2(E)DPSS

(E)V(E)A

(E)O2

(E)DPSS2"

3/4"3/4"

(E)V(E)A

(E)O2

(E)DPSS2"

3/4"3/4"

(E)D

PS

S

(E)V

(E)A

(E)O

2

2"3/4"

3/4"

1/2" O21/2" A

1" VAC

1/2"

O2

1/2"

A1"

VA

C

MVB-1

1/2"

O2

1/2"

A1"

VA

C

MGS-1

MGS-1

MGS-1

1

MGS-1

MGS-2

1/2" O21/2" A

1" VAC

1/2" O21/2" A

1" VAC

1/2" O21/2" A1" VAC1/2" O2

1/2" A1" VAC

MGS-2

MGS-2

MGS-2MGS-2

2"3/4"3/4"

(E)V(E)A

(E)O2

2

1

LPA-1

MVB-2

1/2"

O2

1/2"

A1"

VA

C

1/2" O21/2" A

1" VAC

MGS-1

MGS-1

3

3

3 3

3

3

3

3

3

3

3

1/2"

MGS-13

1"

MGS-1

3

MGS-1

3

LPA-2

ELEV.

MED.GAS

STAIRX1-SX

STAIR1067

EXTERIOR COURTYARD - NO PUBLIC ACCESS

TELE.

OFFICE1031

EXAM1032

EXAM1033

EXAM1034

EXAM1036

EXAM1037

EXAM1038

EXAM1039

EXAM1041

CORRIDOR1029

TRIAGE/ASSESMENT

1019

RECEPTION/ASSESMENT

1018

SECURITY1018A

WAITING1013

WHEELCHAIRSTORAGE

1002

QUIETWAITING

1011

ENTRYVESTIBULE

1001

WOMEN1008

MEN1009

HSKP1004

VENDING1007

CORRIDOR1005

CORRIDOR1161

CONSULT1024

MULTI-PATIENTEXAM/HOLDING

1026

PATIENT/SPECIMENTOILET

1022

CORRIDOR1021

CORRIDOR1020

FAST TRACK1023

MEDICATION/SUPPLY

1014

NUTRITION1016

FAST TRACK1023B

FAST TRACK1023C

FAST TRACK1023A

FAST TRACK1023D

FAST TRACK1023E

FAST TRACK1023F

FAST TRACK1023G

TREATMENT1078

CONTROL1082

TREATMENT1081

ALCOVE1076

CLEAN SUPPLY/EQUIPMENT

1074

TREATMENT1077

PATIENTTOILET

1079

X-RAY1083

COMM.1084

CORRIDOR1028

ELEC.1085

ALCOVE1088A

ALCOVE1088B

ALCOVE1088C

CORRIDOR1087

MEDICATION1093

NOURISHMENT1094

PYXIS1098

STAFFTOILET

1097

PATIENTTOILET

1098

SOILEDUTILITY

1099NURSESTATION

1092

CORRIDOR1091

CRASH CART1111

CORRIDOR1109

ALCOVE1108

EXAM1101

EXAM1106

OBEXAM1102

OBEXAM1107

PATIENTTLT./SHWR

1103

PATIENTTOILET11034

CORRIDOR1027

EXAM1042

EXAM1043

EXAM1044

ISOLATION1046

ANTE1048FIRE

1047

NURSESTATION

1073

CORRIDOR1072

EXAM1049

EXAM1051

WHEELCHAIRSTORAGE

1052

VESTIBULE1053

DECONSHOWER

1054

EMSCLOSET

1056

PSYCH.1057

TRAUMA1058

TRAUMA1059

CORRIDOR1071

HSKP1061

ELEV.EQUIP.

1068

ELEV.LOBBY

1064

ALCOVE1062

RESULTSWAITING

1117

OFFICE1123

STAFFLOCKERS

1124

OFFICE1123 STAFF

LOUNGE1152

OFFICE1112

OFFICE1113

TLT./SHOWER1114

CORRIDOR1134

CORRIDOR1127

1/2" O21/2" A1" VAC

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

PLUMBINGMEDICAL GAS PLAN

P1-02Scale:

1 PLUMBING MEDICAL GAS PLAN1/8"=1'-0"

NOTES:

1. CONNECT O2, A, AND VAC TO EXISTING. FIELDVERIFY EXACT LOCATIONS AND EXISTINGCONDITIONS.

2. 1/2" O2, 1/2" A AND 1" VAC TO MBV-2 FROMEXISTING. FIELD VERIFY EXACT LOCATIONS ANDEXISTING CONDITIONS.

3. CONNECT 1/2" A, 1/2" O2 AND 1" VAC TO MGS-1.FIELD VERIFY EXACT LOCATIONS.

FLAG NOTES:#

1. REFER TO P0-01 FOR PLUMBING GENERAL NOTES.

2. REFER TO P5-01 FOR PLUMBING DIAGRAMS.

3. REFER TO SHEET P6-01 FOR MEDICAL GASSCHEDULES.

4. THE RENOVATION IS TO BE EXECUTED IN PHASES.REFER TO ARCHITECTURAL PLANS FOR PROJECTPHASING.

A. PIPING LAYOUT IS DIAGRAMMATIC ONLY. SIZESSHOWN ARE NOMINAL INSIDE DIAMETER. ALLRECESSED PIPING SHALL BE SEAMLESS COOPERTUBING TYPE K SOFT TAMPER ASTM DESIGNATIONNO. B-88 FOR ASSEMBLY WITH L COPPER TUBINGSHALL BE USED. EXPOSED PIPING TO BE SAMEEXCEPT HARD TAMPER. THE USE OF FITTINGS ISMANDATORY. TUBING BENDERS AND MACHINESWHICH DRAW FITTINGS FROM THE TUBING NOTACCEPTABLE.

B. ENSURE THAT THE MEDICAL GAS AND VACUUMLINES ARE ELECTRICALLY GROUNDED AT SEVERALPOINTS.

C. ISOLATE PIPING FROM STUDS, HANGERS, ETC.,WHERE THERE ARE ABERRATIONS OR WHEREDISSIMILAR MATAL'S COME IN CONTACT WITH EACHOTHER.

D. COORDINATE ALL OTHER TRADES TO INSTALLMEDICAL GAS PIPING WITHOUT CONFLICT.

E. P.C. SHALL HAVE MEDICAL GASES AND ALLASSOCIATED EQUIPMENT CERTIFIED BY ANORGANIZATION AUTHORIZED TO CERTIFY MEDICALGASES.

F. PROVIDE AND INSTALL ALL MEDICAL GASES TOCOMPLY WITH THE REQUIREMENTS OF NFPA 99,NFPA 50 AND LOCAL BUILDING CODES.

G. MARK ALL MEDICAL GAS LINES WITH COLOR CODEMARKERS THAT COMPLY WITH NFPAREQUIREMENTS.

H. CONTRACTOR SHALL PROVIDE A MOCK-UP OF O2,VAC, AIR & SLIDE LAYOUT PRIOR TO INSTALLATIONOF ALL MEDICAL GAS STATION FOR APPROVAL.LOCATE SLIDE NEXT TO VAC.

I. ALL PRESSURE SENSORS SHALL BE WIRED TOLOCAL AREA ALARM PANEL.

J. ALL NEW MEDICAL GAS EQUIPMENT (VALVE BOXES,OUTLETS, AND ALARMS SHALL MATCH CURRENTSJRMC FACILITY GUIDELINES STANDARDS ANDCURRENT EXISTING SYSTEM REQUIREMENTS.

MED GAS NOTES:

Page 14: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

(E) 1" HW

2-1/2" CW

3/4"

HW

2" C

W2"

CW

3/4" CW

1

1

1

1/2" CW

1-1/2" CW

1-1/2" CW

3/4" CW

3/4" CW

2-1/2" CW

1-1/2" CW

WHA

WHA

(E) 6"SD

(E) 4" W

4" W

2" W

4" W

4" W

4" W

4" W

3" V

2" V

2" V

2" V

2" V2" V

3/4" CW

3

2" V

WCO

WCOWCO

WCO

WCO

WCO SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

ENLARGED PLUMBINGWASTEA VENT AND WATER ENLARGEMENT PLANS

P4-01Scale:

1 ENLARGED PLUMBING WATER PLAN1/4"=1'-0"

NOTES:

1. CONNECT NEW HW TO EXISTING HW OF SAME SIZEOR LARGER IN CEILING SPACE. FIELD VERIFYEXISTING CONDITIONS AND EXACT POINT OFCONNECTION.

2. WATER HAMMER ARRESTOR. PROVIDE IN ACCESSPANEL. COORDINATE LOCATION WITH WALLFINISHES AND ACCESSORIES.

3. CONNECT NEW WASTE LINE TO EXISTING WASTEOF SAME SIZE OR LARGER. FIELD VERIFY EXISTINGCONDITIONS, EXISTING INVERT AND EXACTLOCATION.

FLAG NOTES:#

1. REFER TO P0-01 FOR PLUMBING GENERAL NOTES.

2. REFER TO P5-01 FOR PLUMBING DIAGRAMS.

3. REFER TO P0-01 FOR THE PLUMBING FIXTURECONNECTION SCHEDULE FOR PIPE SIZES TOINDIVIDUAL FIXTURES.

4. REFER TO ARCHITECTURAL DRAWINGS FOR PHASINGREQUIREMENTS.

Scale:

2 ENLARGED WASTE AND VENT PLAN1/4"=1'-0"

P1aP1P1

P3 P3

P3 P3

P4P1a

P1

P2

P9

WCO

P1aP1P1

P3 P3

P3 P3

P4P1a

P1

P2

P9

P11

P11

Page 15: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

PIPE THRU ROOF DIAGRAMNO SCALE

6" M

IN.

24 GA. GALV. ROOF JACK W/6" FLANGE BY M.C., SET INPLASTIC CEMENT BY G.C.

PIPE BY M.C.

24 GA. GALV. STORM COLLARBY M.C., CLAMP IN PLACE &CAULK WEATHERTIGHT.

PIPE SLEEVE & CAULKING BYM.C.

SOLDERED LAP SEAM

2 LAYERS OF FELT BY G.C.

FINISHED ROOF FELTS BYG.C.

2" MIN.

NOTE:COOR'D ROOF PENETRATIONAND SEALING WITH ROOFMANUFACTURER ANDINSTALLING CONTRACTOR.

CLEANOUT DIAGRAMS

FLOOR CLEANOUT (FCO)

NO SCALE

SLOPE DN @ 1/4"/L.F.

CLEANOUT TO GRADE (COTG)

WASTE LINE

FINISHED GRADE

6"

ADJUSTABLE GRADE CLEANOUT AND ACCESS ENCLOSURE WITH ANCHOR FLANGE,HEAVY DUTY TOP, AND VANDAL PROOF FASTENERS, ZURN, Z-1400-HD-KBRASSCLEANOUT PLUG W/COUNTER SUNK HEAD.

ADJUSTABLE CLEANOUTAND ACCESS COVER ZURNZB-1400. TOP OF COVER TOBE FLUSH W/ TOP OF FLOOR.

16" CONC. PAD TROWELSMOOTH & EDGE.

1/8 C.I. BEND

BALANCE OF PIPING SAMEAS CLEANOUT TO GRADE.

FLOOR LINE

1/8 C.I. BEND

C.I. WASTE LINE.LGTH TO SUIT.

1/8 BEND IF CLEANOUTOCCURS AT END OF LINE.

PROVIDE FOLLOWING OPTIONS AS APPROPRIATECARPET MARKER - FOR CARPETED AREAS.SQUARE TOP - FOR CERAMIC TILE ORSIMILAR SQUARE PATTERN FLOOR.FLASHING CLAMP - FOR ABOVE GRADEWATER PROOFED AREAS.

DESIGNER NOTE:1. COORDINATE C.O.T.G.

WITH CIVIL ENGINEER.

WALL CLEANOUTDIAGRAMNO SCALE

1'-0

"

MAY EXTEND AS AWASTE OR VENT.

CHROME WALLCOVERAND SCREW.

PLUGGED TEE WITHCLEANOUT.

WALL.

FLOOR LINE.

1/8 C.I. BEND.

BALANCE OF PIPINGSAME AS CLEANOUTTO GRADE.

WASTE LINE

SLOPE DN @ 1/4"/L.F.

TWO-WAY CLEANOUT TO GRADE DIAGRAMSNO SCALE

6"

FINISHED GRADE

ADJUSTABLE GRADE CLEANOUT AND ACCESS ENCLOSUREWITH ANCHOR FLANGE, HEAVY DUTY TOP, AND VANDALPROOF FASTENERS, ZURN, Z-1400-HD-KBRASS CLEANOUTPLUG W/COUNTER SUNK HEAD.

24" X1 6"Ø CONC. PAD TROWELSMOOTH & EDGE.

C.I. WASTE LINE.LGTH TO SUIT.

1/8 C.I. BEND

DESIGNER NOTE:1. COORDINATE C.O.T.G. WITH

CIVIL ENGINEER.

WATER HAMMER ARRESTOR DIAGRAM (WHA) NO SCALE

CW/HW TO FIXTURE, TYP.

PD1 SIZING:SIZE FIXTURE UNITS

AA 1-4A 4-11B 12-32C 33-60

CW/HW BRANCH TO FIXTURES

WATER HAMMER ARRESTORON END OF BRANCH.

DIAGRAM & ISOMETRICDRINKING FOUNTAIN MOUNTING

NO SCALE

& TRIMPLATE.MANUFACTURER'S WALL HANGER

WALL.

S.S. PLATE.

CONCEAL WALLDAMAGE WITH

AGAINST WALL.P-TRAPS FLAT

34"

REPLACE (E) SINGLE INLET

FITTING.WITH (N) DOUBLE INLET

ISOMETRIC

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

PLUMBINGDIAGRAMS

P5-01

Page 16: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

PLUMBING FIXTURE SCHEDULE

SYMBOL TYPE A.D.A. FINISH MANUFACTURER* &MODEL #

FAUCET TRIM MFR.* &MODEL # INSTALLATION ACCESSORIES REMARKS POWER

FLOOR MOUNTEDWATER CLOSET NO VITREOUS CHINA AMERICAN STANDARD

MADERA 2234.128SLOAN ROYAL

111-1.28 FLOOR MOUNTED

AMERICAN STANDARDOPEN-FRONT SEAT:

5901.100T W/ EVERCLEANSURFACE. PROVIDE WITH

WATER HAMMER ARRESTORW/ ISOLATION VALVE IN

ACCESS PANEL. COORDINATELOCATION OF WHA WITH WALL

FINISHES AND TOILETACCESSORIES.

1.28 GPF NO

FLOOR MOUNTEDWATER CLOSET YES VITREOUS CHINA AMERICAN STANDARD

MADERA 3461.128SLOAN ROYAL

111-1.28 FLOOR MOUNTED

AMERICAN STANDARDOPEN-FRONT SEAT:

5901.100T W/ EVERCLEANSURFACE. PROVIDE WITH

WATER HAMMER ARRESTORW/ ISOLATION VALVE IN

ACCESS PANEL. COORDINATELOCATION OF WHA WITH WALL

FINISHES AND TOILETACCESSORIES.

1.28 GPF NO

URINAL YES VITREOUS CHINA AMERICAN STANDARDWASHBROOK 6590.501

SLOAN ROYAL186-0.5

WALL MOUNTED WITHCONCEALED ARM SUPPORT

CARRIER

COORDINATE INSTALLATIONHEIGHT WITH

ARCHITECTURAL. PROVIDEWITH DRAIN STRAINER.

.05 GPF NO

COUNTER MOUNTLAVATORY YES VITREOUS CHINA AMERICAN STANDARD

RONDALYN 0491.019

AMERICAN STANDARDMONTERRREY WITH GRID

STRAINER 5502.175COUNTER MOUNTED

PROVIDE WITH 17 GA. P-TRAP,TRUBRO ADA UNDER-SINK

TRAP AND SUPPLYPROTECTION, 1/4 TURN

ANGLE STOPS AND SUPPLIES.

PROVIDE WITH 0.5 GPM AERATOR.PROVIDE WITH WALL CLEANOUT.

PROVIDE WITH ASSE 1070TEMPERATURE LIMITING DEVICE

FOR HOT WATER SUPPLY. PROVIDEWCO.

NO

WALL HUNGLAVATORY YES VITREOUS CHINA AMERICAN STANDARD

LUCERNE 0355.012

AMERICAN STANDARDMONTERRREY WITH GRID

STRAINER 5502.175WALL MOUNTED

PROVIDE WITH 17 GA. P-TRAP,TRUBRO ADA UNDER-SINK

TRAP AND SUPPLYPROTECTION, FLOOR

MOUNTED CONCEALED ARMWALL CARRIER, 1/4 TURN

ANGLE STOPS AND SUPPLIES

PROVIDE WITH 0.5 GPM AERATOR.PROVIDE WITH WALL CLEANOUT.

PROVIDE WITH ASSE 1070TEMPERATURE LIMITING DEVICE

FOR HOW WATER SUPPLY. PROVIDEWCO.

NO

DRINKING FOUNTAIN YES STAINLESS STEEL ELKAYLZSVR8 - - WALL MOUNT

PROVIDE FLOOR MOUNTEDCONSEALED ARM CARRIER, 1/4 TURN

ANGLE STOPS, P-TRAP AND FLEXCONNECTION PROVIDE ELECTRICALCONNECTION. COORDINATE OUTLET

LOCATION WITH ELECTRICAL.PROVIDE WCO.

YES115V/60Hz, 5 AMPS, 370 WATTS

SINGLECOMPARTMENTCOUNTER SINK

YES STAINLESS STEEL ELKAYLRAD172055

AMERICAN STANDARDMONTERREY 7500.175 COUNTER MOUNTED

1.5 GPM OUTLET AERATOR,PROVIDE WITH 17 G.A. P-TRAP,

TRUBRO UNDER-SINKPROTECTION, 1/4 TURN

ANGLE STOPS AND SUPPLIES,PROVIDE WITH ASSE 1071

LISTED POINT OF USETHERMOSTATIC MIXING

VALVE.

PROVIDE WITH PLASTER TRAP BYZURN IF REQUIRED IN PROCEDURE

ROOMS, REFER TO FLOOR PLAN FORLOCATION. PROVIDE WITH A REARCENTERED DRAIN. PROVIDE WCO.

NO

HAND SINK YES VITREOUS CHINA AMERICAN STANDARDLUCERNE 0355.012

AMERICAN STANDARDMONTERRREY WITH GRID

STRAINER 5502.175WALL MOUNTED

PROVIDE WITH 17 GA. P-TRAP,TRUBRO ADA UNDER-SINK

TRAP AND SUPPLYPROTECTION, FLOOR

MOUNTED CONCEALED ARMWALL CARRIER, 1/4 TURN

ANGLE STOPS AND SUPPLIES

PROVIDE WITH 0.5 GPM AERATOR.PROVIDE WITH WALL CLEANOUT.

PROVIDE WITH ASSE 1070TEMPERATURE LIMITING DEVICE

FOR HOW WATER SUPPLY. PROVIDEWCO.

NO

EXAM SINK YES STAINLESS STEEL ELKAYLRAD222255

AMERICAN STANDARDMONTERREY 7500.175 COUNTER MOUNTED

PROVIDE WITH 17 GA. P-TRAP,TRUBRO ADA UNDER-SINK

TRAP AND SUPPLYPROTECTION, 1/4 TURN

ANGLE STOPS AND SUPPLIES

PROVIDE WITH 0.5 GPM AERATOR.PROVIDE WITH WALL CLEANOUT.

PROVIDE WITH ASSE 1070TEMPERATURE LIMITING DEVICE

FOR HOW WATER SUPPLY. PROVIDEWCO.

NO

SINGLECOMPARTMENT

BREAKROOM SINKYES STAINLESS STEEL ELKAY

LRADQ221955AMERICAN STANDARDMONTERREY 7500.175 COUNTER MOUNTED

PROVIDE WITH 17 GA. P-TRAP,TRUBRO ADA UNDER-SINK

TRAP AND SUPPLYPROTECTION, 1/4 TURN

ANGLE STOPS AND SUPPLIES

PROVIDE WITH 0.5 GPM AERATOR.PROVIDE WITH WALL CLEANOUT.

PROVIDE WITH ASSE 1070TEMPERATURE LIMITING DEVICE

FOR HOW WATER SUPPLY. PROVIDEWCO.

NO

MOP SINK - PRECAST TERRAZZO FIAT TSB100

SERVICE SINK FAUCET WITHVACUUM BREAKER AND PAIL HOOK

BY FIATMODEL: 830-AA

SERVICE SINK FAUCET WITHVACUUM BREAKER AND PAIL

HOOK BY FIATMODEL: 830-AA

PROVIDE WITH HOSE ANDBRACKET(832AA), BUMPERGAURDS(1239BB), AND SS

WALL GAURDS(MSG)

PROVIDE WITH MOP HANGER NO

NO

FLOOR DRAIN - CAST IRON ZURN Z415 - - PROVIDE WITH SURE SEALTRAP GUARD - NO

FLOOR SINK - CAST IRON ZURN Z1902 - - PROVIDE WITH SURE SEALTRAP GUARD

PROVIDE PRO-VENT TRAP GUARD,DOME STRAINER, HALF GRATE ONCONDENSATE RECEPTORS, FULL

GRATE ON REMAINDER

NO

HOSE BIBBFREEZELESS

TRENCH DRAINSYSTEM YES

STAINLESS STEELGRATE - POLY

TRENCH

NDS TRENCH DRAIN SYSTEM: 2TRENCHES, 5 GRATES, AND 1

CATCH BASIN- -

PROVIDE WITH 2X(DS-224) ENDCAPS. CATCH BASIN SHALL

HAVE #1242 - 3" OUTLET. EACHTRENCH DRAIN SHALL BE

PROVIDED WITH TWO - 2FT SSADA GRATES. CATCH BASIN

SHALL BE PROVIDED WITH 1 -2FT SS ADA GRATE. TOTAL OF

5 GRATES IN ALL. GRATESHALL BE STAINLESS STEEL

PERFORATED MODEL - DS-226

TRENCH DRAIN GRATE SHALL BENON-REMOVABLE/VANDAL PROOF.PROVIDE WITH VANDAL RESISTANT

SCREWS AND TOOL (DS-650-VR).(INSTALL FOR A COMPLETE TRENCHDRAIN SYSTEM. TOTAL LENGTH OF

10 FT.PROVIDE 2X(DS-091) 4 FTSLOPED TRENCH DRAINS WITH 1 -

2FT - DS-340 CENTER CATCH BASINWITH BOTTOM 3" OUTLET.

NO

LIGATURE RESISTANTWATER CLOSET YES

304 STAINLESS STEELWITH WHITE POWDER

COAT EXTERIORFINISH

WHITEHALL MODEL"WH2142-ADA-W-EGE10

PROVIDE WHITEHALL LIGATURERESISTANT FLUSH VALVE AND

ACCESS PANEL MODEL:WH2898-ADA

FLOOR WASTE OUTLET.ATTACH FIXTURE TO WALL

PROVIDE WITH LIGATURERESISTANT SEAT COVER.

COLOR WHITE.(WH-LRSC-WHITE). PROVIDE

WITH WATER HAMMERARRESTOR .

1.28 GPF NO

LIGATURE RESISTANTADA WALL HUNG

LAVATORYYES SOLID SURFACE

POLYMER RESIN WHITEHALL MODEL: WH3775

WHITE HALL MODEL: WH3373LAIR-CONTROL, SINGLE TEMP,

METERING CONICAL SPRAYHEAD& PUSHBUTTONS. PROVIDE WITH

ASSE 1070 COMPLIANTTEMPERATURE-PRESSUREBALANCING MIXING VALVE.WHITEHALL MODEL: MXTP

WALL MOUNTED

PROVIDE WITH 17 GA. P-TRAP,CONCEALED ARM WALL

CARRIER, 1/4 TURN ANGLESTOPS AND SUPPLIES

PROVIDE WITH 0.5 GPM AERATOR.PROVIDE WITH ASSE 1070

TEMPERATURE LIMITING DEVICE .PROVIDE WCO.

NO

SINGLE TEMP HOSESUPPLY BOX WITHVACUUM BREAKER

NO STAINLESS STEEL ACORN MODEL: 8104PROVIDE WITH -SSLF (STAINLESS

STEEL LEAD FREE OPTION) WALL MOUNTED

PROVIDE WITH ACORNCONTROLS LEAD FREETHERMOSTATIC MIXING

VALVE. ASSE 1017 COMPLIANT.ACORN MODEL:MV-17-2.

PROVIDE WITH LOCKABLEACCESS PANEL. PROVIDE

WITH T&S BRASS SPRAYERMODEL: PG-35AV-CH01.

VALVE SHALL BE A REPLACEABLECARTRIDGE TYPE WITH

VANDAL-RESISTANT LOCKSHIELDBONNET, REMOVABLE LOOSE KEY

WHEEL HANDLE AND SCREWDRIVEROPERATED STOP.

NO

EXAM SINK YES STAINLESS STEEL ELKAYLRAD222255

WHITE HALL MODEL: WH3373LAIR-CONTROL, SINGLE TEMP,

METERING CONICAL SPRAYHEAD& PUSHBUTTONS. PROVIDE WITH

ASSE 1070 COMPLIANTTEMPERATURE-PRESSUREBALANCING MIXING VALVE.WHITEHALL MODEL: MXTP

COUNTER MOUNTED

PROVIDE WITH 17 GA. P-TRAP,TRUBRO ADA UNDER-SINK

TRAP AND SUPPLYPROTECTION, 1/4 TURN

ANGLE STOPS AND SUPPLIES

PROVIDE WITH 0.5 GPM AERATOR.PROVIDE WITH WALL CLEANOUT.

PROVIDE WITH ASSE 1070TEMPERATURE LIMITING DEVICE

FOR HOW WATER SUPPLY. PROVIDEWCO.

NO

MANUFACTURERS:FIXTURE: AMERICAN STANDARD, KHOLER

FAUCET: DELTA, AMERICAN STANDARD, T&S, CHICAGO

DRAIN: ZURN, J.R. SMITH, WATTS

GENERAL NOTES:A: REFER TO FLOOR PLANS FOR FIXTURE LOCATIONS.B: ALL FIXTURES SHALL BE APPROVED BY OWNER.

P1

P1a

P2

P3

P3a

P4

P5

P6

P7

P8

P9

P10

P11

P12

P13

P14

P16

P17

P18

P19

MEDICAL GAS OUTLETALL EQUIPMENT USED IN THIS SCHEDULE SHALL BE AS MANUFACTURED BY " BEACONMEDAEZ MEDICAL" AND SHALL MATCH EXISTING SJRMC FACILITY REQUIREMENTS.

GAS SERVICE STOCK NUMBER (WALL) REMARKS

SERVICE OUTLET:THE ROUGH-IN ASSEMBLY SHALL BE OF MODULAR DESIGN AND INCLUDE GAS-SPECIFIC 16-GAUGE STEELMOUNTING PLATE DESIGNED TO PERMIT ON-SITE GANGING OF MULTIPLE OUTLETS, IN ANY ORDER, ON 5"CENTERLINE SPACING. A MACHINED BRASS OUTLET BLOCK SHALL BE PERMANENTLY ATTACHED TO THEMOUNTING BRACKET TO PERMIT THE 1/2" OD (3/8" NOMINAL) TYPE-K COPPER INLET TUBE SWIVEL 360° FORATTACHMENT TO THE PIPING SYSTEM. THE LATCH-VALVE ASSEMBLY SHALL INCLUDE A SINGLE COMPRESSIONSEAL PRIMARY VALVE, BE GAS SPECIFIC FOR THE LABELED SERVICE, AND ACCEPT ONLY CORRESPONDINGGEOMETRICALLY SHAPED HOSE AND APPARATUS ADAPTERS. A DIE CAST, LIGHT GRAY, EPOXY POWDER COATEDTRIM PLATE SHALL BE PROVIDED TO TRIM EACH WALL OUTLET AND TO FILL THE SPACE BETWEEN ADJACENTOUTLETS. THE TRIM PLATE SHALL ALLOW LATCH VALVES TO BE INDIVIDUALLY REMOVED FOR SERVICING.

*MANUFACTURED ACCORDING TO ALL APPLICABLE NFPA AND CGA STANDARDS.*REMOVABLE COVER PLATES PROVIDE EASY ACCESS FOR PERIODIC INSPECTION OR MAINTENANCE.*LISTED BY UNDERWRITERS LABORATORIES, INC.

*NOTE: OUTLET CONNECTION TYPE SHALL BE VERIFIED AND COORDINATED WITH OWNER FOR REQUIREDCONNECTION TYPE REQUIEMENTS PRIOR TO SUBMITTAL AND ORDERING.

O2 6-121020 BEACON MADAEZ QUICK CONNECT WALL OUTLETSVAC 6-121023 BEACON MADAEZ QUICK CONNECT WALL OUTLETS

SLIDE 6-121020

MEDICAL VALVE BOX SCHEDULE

TYPE(RECESSED)

TYPE OF GAS AND SIZE

REMARKSO2

MVB-1

N20 VAC N2O EVAC N

ALL EQUIPMENT USED IN THIS SCHEDULE SHALL BE AS MANUFACTURED BY" BEACON MEDAEZ MEDICAL"

STOCKNUMBER

SHUT-OFF VALVES*BE FULL-PORT, BALL VALVES*BE THREE-PIECE CONSTRUCTION FOR EASY INSTALLATION AND MAINTENANCE*HAVE TEFLON SEALS FOR LONG-LASTING, SMOOTH, EASY OPERATION*BE DESIGNED FOR WORKING PRESSURES OF 400 PSI OR 29" VACUUM*HAVE BLOW-OUT PROOF STEM*BE CLEANED FOR OXYGEN SERVICE*BE AVAILABLE IN 1/2" THROUGH 4" DIAMETER SIZES WITH TYPE K COPPER TUBING EXTENSIONS BRAZED TO FLANGES*HAVE A CORROSION-RESISTANT BRONZE BODY*REQUIRE ONLY ONE QUARTER OF A TURN TO COMPLETELY OPEN OR CLOSE

VALVES BOXESVALVE BOXES WILL:*INCLUDE A 1-1/2" LINE PRESSURE MONITORING GAUGE*BE AVAILABLE TO ACCOMMODATE ONE TO FOUR VALVES OF VARIOUS SIZES*BE LABELED FOR GAS IDENTIFICATION*BE ENCLOSED WITH A TRANSPARENT WINDOW DISPLAYING THE FOLLOWING CAUTION PERNFPA 99 (1990) AND CSA Z-305.1-M1984, "CAUTION: MEDICAL GAS SHUT-OFF VALVES. DO NOTCLOSE EXCEPT IN EMERGENCY."

REFERTO MFG. 1/2" 1"

A

1/2"

A 6-121022 BEACON MADAEZ QUICK CONNECT WALL OUTLETS

MEDICAL GAS STATION SCHEDULEMANUFACTURED BY "BEACON MEDAEZ MEDICAL"

STATIONGAS SERVICES & NO. OF OUTLETS REMARKS

O2

MGS-1

N20 VAC N2 EVAC SLIDE

WALL MOUNTED

NOTE: ALL GAS OUTLETS SHALL MATCH EXISTING MANUFACTURER TYPE. GAS OUTLET SHALL BEAS MANUFACTURED BY "BEACON MEDAEZ MEDICAL" UNLESS OUTLET TYPE IS NOT AVAILABLE.

MEDICAL GAS ABBREVIATIONS SCHEDULEMANUFACTURED BY "BEACON MEDAEZ MEDICAL"

MGO MEDICAL GAS OUTLET

MGS MEDICAL GAS STATION

MVB MEDICAL VALVE BOX

LPA LINE PRESSURE ALARM

O2 OXYGEN

N2O NITROUS OXIDE

V VACUUM

EV EVAC

A MEDICAL AIR

N NITROGEN

MAS MASTER ALARM STATION

1 1 11

A

EXISTING OUTLET CONNECTION TYPE AND MANUFACTURER SHALL BE VERIFIED ANDCOORDINATED WITH SJRMC FOR REQUIRED CONNECTION TYPE REQUIREMENTSPRIOR TO SUBMITTAL AND ORDERING.

MEDICAL GAS LINE PRESSURE ALARM PANEL

MARKTYPE OF GAS SERVICE

REMARKSO2

LPA-1

N20 VAC N2O EVAC N

ALL EQUIPMENT USED IN THIS SCHEDULE SHALL BE AS MANUFACTURED BY" BEACON MEDAEZ MEDICAL"

STOCKNUMBER

THE AREA PANEL SHALL CONSIST OF A POWER MODULE, DIGITAL MODULE, AND SENSORMODULE. THE POWER MODULE SHALL BE CAPABLE OF SUPPORTING UP TO EIGHT DIGITALMODULES AND CONVERTING 115/120 VAC TO LOW VOLTAGE DC. THIS MODULE SHALL CONTAINA FUSE TO PROTECT THE SYSTEM FROM VOLTAGE AND AMPERAGE SURGES AND A YELLOWPOWER ON INDICATOR THAT ILLUMINATES WHEN ELECTRICAL POWER IS AVAILABLE. DIGITALSHALL BE USED AS EITHER A MASTER ALARM OR AREA ALARM AND INCORPORATE A DIGITALLIQUID CRYSTAL DISPLAY (LCD) THAT CONTINUOUSLY INDICATES THE PRESSURE OR VACUUMIN THE SEGMENT OF THE PIPING SYSTEM BEING MONITORED. SENSOR MODULE SHALLCONTAIN A TRANSDUCER CAPABLE OF PROVIDING CALIBRATED SIGNALS TO THE DIGITALMODULE. SENSOR MODULES SHALL BE GAS SPECIFIC AND CAPABLE OF MOUNTING DIRECTLYIN THE MEDICAL GAS PIPELINE OR IN STANDARD WALL CONSTRUCTION.

*INCLUDES DRY CONTACT RELAYS (NO/MC) FOR CONNECTION OF REMOTE ALARMS.*COMPLETELY FACTORY ASSEMBLED AND PREWIRED.*LED INDICATOR LIGHTS PROVIDE FULL VISIBILITY WITH EXTENDED SERVICE LIFE.

REFERTO MFG. X X

A

X

LPA-2 REFERTO MFG. X X X

NEAR RECEPTION 1018

MVB-2 REFERTO MFG. 1/2" 1" 1/2"

CORRIDOR 1020 NEARTRIAGE 1019CORRIDOR 1071 NEARNURSE STATION 1073

NEAR NURSE STATION 1073

MGS-2 1 1 11ALL MGS-2STATIONS/OUTLETS SHALL BETAMPER PROOF/VANDALRESISTANT

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

PLUMBINGSCHEDULES

P6-01

Page 17: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

GFCI DUPLEX RECEPTACLE

DUPLEX RECEPTACLE; HALF SWITCHED

ISOLATED GROUND DUPLEX RECEPTACLE

WALL MOUNTED SPECIAL OUTLET AS NOTED

SPECIAL OUTLET AS NOTED

JUNCTION BOX

WALL MOUNTED JUNCTION BOX

FLOOR MOUNTED JUNCTION BOX

DUPLEX RECEPTACLE MOUNTED ABOVE COUNTERC

FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE

FLUSH FLOOR MOUNTED DOUBLE DUPLEX RECEPTACLE

FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE; HALF SWITCHED

FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE AND TELECOM

DIVISION 15 EQUIPMENT POWER CONNECTION

FUSED DISCONNECT

NON FUSED DISCONNECT

MOTOR STARTER

ENCLOSED CIRCUIT BREAKER

PULL BOX

PUSH BUTTON

TRANSFORMER

PANELBOARD OR LOADCENTER

CONTACTOR

ELECTRIC MOTOR

METER

THERMOSTAT

ATS AUTOMATIC TRANSFER SWITCH

ONE-LINE DIAGRAM SYMBOLS

CIRCUIT HOMERUN

CONDUIT RUN

CONDUIT RUN BELOW GRADE

CONDUIT UP

CONDUIT DOWN

DISCONNECT SWITCH

FUSE

CIRCUIT BREAKER

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

METER

SURGE SUPPRESSION DEVICE

VOLT-METER

SELECTOR SWITCH

GROUND

GF GROUND FAULT PROTECTION

AMP-METER

ST SHUNT TRIP

NORMALLY OPEN CONTACT

NORMALLY CLOSED CONTACT

COLD WATER GROUND CONNECTION

BUILDING STEEL GROUND CONNECTION

TIMER SWITCH

MULTI-OUTLET PLUG STRIP

TIME CLOCK

PHOTO-CELL

SWITCH

THERMAL OVERLOAD SWITCH

VARIABLE SPEED SWITCH

KEY SWITCH

LIGHTING FIXTURE SYMBOLSRECESSED LIGHTING FIXTURE

WALL MOUNTED LIGHT

WALL MOUNTED UP-LIGHT

PENDANT MOUNTED LIGHT

SURFACE MOUNTED LIGHT

DIRECTIONAL/ADJUSTABLE RECESSED LIGHTING FIXTURE

MONO-POINT LIGHTING FIXTURE

RECESSED STEP LIGHT

FLUORESCENT STRIP LIGHT

WALL MOUNTED LINEAR FLUORESCENT LIGHT

RECESSED OR SURFACE MOUNTED FLUORESCENT TROFFER

FIXTURE WITH EMERGENCY BACKUP OR ON EM CIRCUIT

WALL MOUNTED EXIT SIGN W/ FACES & ARROWS AS SHOWN

EMERGENCY LIGHTS

CEILING MOUNTED EXIT SIGN W/ FACES & ARROWS AS SHOWN

SWITCH

THREE-WAY SWITCH

FOUR-WAY SWITCH

DOOR JAMB SWITCH

LIGHTING CONTROL SYMBOLS

EXTERIOR POLE MOUNTED LIGHT

EXTERIOR POST (BOLLARD) MOUNTED LIGHT

DAYLIGHT PHOTO SENSORDL

KEY SWITCH

LV

VARIABLE SPEED SWITCH

DIMMER

THREE-WAY DIMMER

LOW VOLTAGE SWITCH

WALL OCCUPANCY SENSOR/SWITCH

THERMAL OVERLOAD SWITCH

OCCUPANCY SENSOR - WALL MOUNTED

OCCUPANCY SENSOR - CORRIDOR CEILING MOUNTED

S

S3

ST

SO

D3

D

SV

SK

SJS4

SKSV

ST

S

PC

TC

TS

A

V

SS

M

T

C

T

PB

CB

N

--

J

J

J

ABBREVIATIONSPOWER SYMBOLSSINGLE RECEPTACLE

DUPLEX RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

NOTE:ALL SYMBOLS SHOWN ON LEGEND ARENOT NECESSARILY USED.

ELECTRICAL SYSTEMS LEGEND

OS

OS OCCUPANCY SENSOR - CEILING MOUNTED

OS

NOTES:· LIGHT LINEWEIGHT INDICATES EXISTING.

· HATCHED AREAS INDICATE DEMOLITION.

· 'C' ADJACENT TO A DEVICE INDICATESMOUNTING ABOVE COUNTERTOP.

AFC

AFF

AFG

AHJ

- ABOVE FINISHED CEILING

- ABOVE FINISHED FLOOR

- ABOVE FINISHED GRADE

- AUTHORITY HAVING JURISDICTION

AL - ALUMINUM

AWG - AMERICAN WIRE GAUGE

BFG

BMS

BAS - BUILDING AUTOMATION SYSTEM

- BELOW FINISH GRADE

- BUILDING MANAGEMENT SYSTEM

C

CATV

CCTV

- CONDUIT

- COMMUNITY (CABLE) ANTENNA TELEVISION SYSTEM

- CLOSED CIRCUIT TELEVISION

CKT - CIRCUIT

CT - CURRENT TRANSFORMER

DISP - GARBAGE DISPOSAL

DW - DISHWASHER

(E) - EXISTING

EM - EMERGENCY

EWC - ELECTRIC WATER COOLER

GFI

FA

FACP

GRD

GC

- FIRE ALARM

- FIRE ALARM CONTROL PANEL

- GENERAL CONTRACTOR

- GROUND FAULT CIRCUIT INTERRUPTER

- GROUND

IAW IN ACCORDANCE WITH-

IC

IDF

IG

IR

LAN

- INTERMEDIATE CROSS-CONNECT

- INTERMEDIATE DISTRIBUTION FRAME

- ISOLATED GROUND

- INFRARED

- LOCAL AREA NETWORK

NIC

MDF

(N)

MAIN DISTRIBUTION FRAME-

NEW-

NOT IN CONTRACT-

NL NIGHT LIGHT-

NTS NOT TO SCALE-

OC

PA

ON CENTER-

PUBLIC ADDRESS-

REF REFRIGERATOR-

TVSS

TTB TELECOMMUNICATIONS TERMINAL BOARD-

TRANSIENT VOLTAGE SURGE SUPPRESSOR-

TVTB TELEVISION TERMINAL BOARD-

UG

UNO

W

V

UNDERGROUND-

UNLESS NOTED OTHERWISE-

VOLT-

WATT-

WP

XP

WAN

WLAN

WAP

WIDE AREA NETWORK-

WIRELESS ACCESS POINT-

WIRELESS LOCAL AREA NETWORK-

WEATHERPROOF-

EXPLOSIONPROOF-

+18"DEVICE ABOVE FINISH FLOOR (VERIFY W/ ARCH ELEVS)MOUNTING HEIGHT TO CENTERLINE OF-

C

LOUDSPEAKER BAR - LEFT/CENTER/RIGHT

LOUDSPEAKER BAR - STEREO

LOUDSPEAKER - POWERED SUBWOOFER

LOUDSPEAKER BAR - CENTER CHANNEL

FIRE ALARM SYMBOLSFIRE ALARM CONTROL PANEL

REMOTE ANNUNCIATOR PANEL

SMOKE DETECTOR

HEAT DETECTOR

COMBO SMOKE/HEAT DETECTOR

FIRE ALARM HORN

FIRE ALARM STROBE

FIRE ALARM COMBO HORN/STROBE

FIRE ALARM PULL STATION

F FIRE ALARM SPEAKER

S FIRE ALARM COMBO SPEAKER/STROBE

FIREMAN'S PHONE JACK

DUCT DETECTOR

SPRINKLER SYSTEM FLOW SWITCH

SPRINKLER SYSTEM TAMPER SWITCH

FIRE/SMOKE DAMPERFSD

FT

FF

F

F

H

H

ANN

FACP

H

SMOKE DETECTOR SOUND BARRIERSB

COSMOKE DETECTOR W/ CARBON MONOXIDE

BDT

BDR

BEAM TYPE SMOKE DETECTOR TRANSMITTER

BEAM TYPE SMOKE DETECTOR RECEIVER

INDIVIDUAL ADDRESSABLE MODULE

MONITORED RELAY

POST-INDICATOR VALVE

CARBON MONOXIDE DETECTOR

PIV

MR

IAM

CO

FIRE ALARM CHIME

FIRE ALARM CHIME/STOBE

REMOTE TESTER SWITCHRTS

CTR

LR

LCR

S

TELEVISION OUTLET - FLOORBOX

AUDIOVISUAL OUTLET - CEILING MOUNTED

AUDIOVISUAL OUTLET - WALL MOUNTED

AUDIOVISUAL OUTLET - FLOORBOX

AV

AV

TELEVISON OUTLET - CEILING MOUNTED

TELEVISION OUTLET - WALL MOUNTED

LOUDSPEAKER - CEILING MOUNTED

LOUDSPEAKER - WALL MOUNTED

MICROPHONE OUTLET - FLOORBOX

MICROPHONE OUTLET - WALL MOUNTED

AUDIOVISUAL SYMBOLS

SPEAKER ZONE HOMERUN

VIDEO PROJECTOR

TV

AV

PROJECTION SCREEN, TELEVISION, OR OTHER DISPLAY EQPT

SPK LOUDSPEAKER OUTLET

M

INTERACTIVE (ELECTRONIC) WHITEBOARD

S

S

TV

TV

M

LOW TEMPERATURE SENSORLT

GENERAL NOTES:1. THESE DRAWINGS ACCOMPANY THE CONSTRUCTION DOCUMENT

SPECIFICATIONS..

2. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON ARCHITECTURALDRAWINGS AND IN FIELD PRIOR TO COMMENCEMENT OF WORK.

3. VISIT SITE PRIOR TO BID AND VERIFY THAT CONDITIONS ARE ASINDICATED. CONTRACTOR SHALL INCLUDE IN HIS BID COSTSREQUIRED TO MAKE HIS WORK MEET EXISTING CONDITIONS.

4. SYSTEM OUTAGES SHALL BE PERMITTED ONLY AT TIMES APPROVEDBY OWNER - IN WRITING. WORK WHICH COULD RESULT IN ANACCIDENTAL OUTAGE (BEYOND BRANCH CIRCUITS) SHALL BEPERFORMED WITH THE OWNER'S MAINTENANCE PERSONNELADVISED OF SUCH WORK.

5. SERVICE SHALL BE MAINTAINED TO EXISTING AREAS DURINGCONSTRUCTION. CONTRACTOR SHALL PROVIDE PORTABLEGENERATORS, CABLES, OUTLETS, ETC. AS REQUIRED TO MAINTAINCONTINUITY OF SERVICE. PLACEMENT OF SUCH PORTABLEEQUIPMENT SHALL BE SUBJECT TO OWNER APPROVAL.

6. REVIEW ARCHITECTURAL, MECHANICAL AND OTHER DRAWINGSPRIOR TO BID.

7. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THESATISFACTION OF THE ARCHITECT.

8. WORK, MATERIALS, AND EQUIPMENT SHALL CONFORM TO THELATEST EDITIONS OF LOCAL, STATE OF NEW MEXICO, AND NATIONALCODES AND ORDINANCES.

9. PROVIDE PERMITS AND INSPECTIONS REQUIRED.

10. PROVIDE WITH SHOP DRAWING SUBMITTAL, ¼” SCALE LAYOUTDRAWINGS OF ROOMS WITH ELECTRICAL SWITCHBOARDS ANDTRANSFORMERS. LAYOUTS SHALL SHOW LOCATIONS OF, AND SHALLBE COORDINATED WITH MECHANICAL EQUIPMENT. ALL EQUIPMENTSHALL BE DRAWN TO SCALE.

11. CONTRACTOR'S FAILURE TO ORDER OR RELEASE ORDER FORMATERIALS AND/OR EQUIPMENT WILL NOT BE ACCEPTED AS AREASON TO SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT, ORINSTALLATION METHODS.

12. FIELD VERIFY EXISTING EQUIPMENT OR CIRCUITS THAT AREREMAINING TO BE RECONNECTED TO NEW OR EXISTINGSWITHBOARDS/PANELBOARDS. PROVIDE SWITCHES, RECEPTACLES,CONDUIT, WIRE, ETC. AS REQUIRED, TO RESTORE CONTINUITY OFCIRCUIT(S).

13. EXISTING SYSTEMS AND CONDITIONS SHOWN ON DRAWINGS FOREXISTING BUILDINGS ARE TO BE NOTED “FOR GUIDANCE ONLY”. THEELECTRICAL CONTRACTOR TO FIELD CHECK ALL EXISTINGCONDITIONS PRIOR TO BIDDING AND TO INCLUDE IN HIS BID ANALLOWANCE FOR REMOVAL AND/OR RELOCATION OF EXISTINGCONDUITS, WIRES, DEVICES, FIXTURES, OR OTHER EQUIPMENT ASINDICATED ON THE PLANS OR AS REQUIRED TO COORDINATE ANDADAPT NEW AND EXISTING ELECTRICAL SYSTEM TO ALL OTHERWORK AS REQUIRED.

14. PROVIDE ELECTRICAL DEMOLITION REQUIRED. REFER TOMECHANICAL AND ELECTRICAL DEMOLITION DRAWINGS FORLOCATION AND EXTENT OF DEMOLITION REQUIRED. CONTRACTORSHALL VISIT SITE PRIOR TO BID TO DETERMINE EXTENT OF WORKINVOLVED. PROVIDE LABOR AND MATERIALS REQUIRED TO MAINTAINAND/OR RESTORE CONTINUITY OF SERVICE TO EXISTING CIRCUITS.

15. PROVIDE ALL NECESSARY DEMOLITION TO REMOVE EXISTINGUNUSED CONDUIT, WIRE, CABLE, J-BOXES, RECEPTACLES, SWITCHES,LIGHTS, FIRE ALARMS DEVICES, ETC. COMPLETE WITH ASSOCIATEDCIRCUITING TO SOURCE. WHERE IT IS NOT FEASIBLE TO REMOVETHE ABOVE, OUTLET SHALL BE ABANDONED, WIRE REMOVED, ANDBLANK COVER PLATES PROVIDED.

16. ALL (E) EQUIPMENT BEING REMOVED SHALL BE DISCARDED INACCORDANCE WITH APPLICABLE EPA REQUIREMENTS.

17. EXISTING ELECTRICAL EQUIPMENT, ETC. BEING REMOVED SHALL BERETURNED TO THE OWNER, EXCEPT FOR THOSE ITEMS BEINGRELOCATED.

18. VERIFY EXACT LOCATION OF EQUIPMENT TO BE FURNISHED BYOTHERS PRIOR TO ROUGH-IN.

19. REVIEW MECHANICAL DRAWINGS AND PROVIDE LIGHTS, SWITCHES,RECEPTACLES, TELECOM OUTLETS, EQUIPMENT CONNECTIONS, ETC.AND ASSOCIATED CIRCUITING IN NEW AND REMODELED AREAS.

20. INSTALL ALL MATERIALS IN ACCORDANCE WITH THEMANUFACTURER'S RECOMMENDATIONS. ANY DEVIATIONS SHALL BEBROUGHT TO THE ARCHITECT/ENGINEER'S ATTENTION PRIOR TOINSTALLATION.

21. FINAL CONNECTIONS TO EQUIPMENT SHALL BE IN ACCORDANCE WITHMANUFACTURER'S APPROVED WIRING DIAGRAMS, DETAILS, ANDINSTRUCTIONS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TOPROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENTACTUALLY SUPPLIED.

22. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING EQUIPMENTWHICH IS DAMAGED DUE TO INCORRECT FIELD WIRING PROVIDEDUNDER THIS SECTION, OR FACTORY WIRING IN EQUIPMENT PROVIDEDUNDER THIS SECTION.

23. WHERE THE RE-USE OF EXISTING CONDUITS, WIRES, DEVICES, ETC, ISPERMISSIBLE, MAKE CERTAIN THAT THE WIRING FOR SAME ISCONTINUOUS FROM OUTLET TO OUTLET AND THAT SUCH CIRCUIT ORSYSTEMS SHALL PASS THROUGH NO OUTLET OR JUNCTION BOXESWHICH MAY BE RENDERED INACCESSIBLE BY THE STRUCTURALCHANGES TO BE MADE TO THE BUILDING. EXISTING CONDUITS, WIRE,DEVICES. WHICH ARE NOT INDICATED FOR REUSE SHALL BECOMETHE PROPERTY OF THIS CONTRACTOR HOWEVER LIGHTINGFIXTURES, PANEL FUSED SWITCHES, CIRCUIT BREAKERS, FIRE ALARMEQUIPMENT, WIRE, ETC. SHALL BECOME THE PROPERTY OF THEOWNER.

24. ALL ELECTRICAL SYSTEMS COMPONENTS SHALL BE LISTED ORLABELED BY U.L. OR OTHER RECOGNIZED TESTING FACILITY.

25. WIRING DEVICES SHALL BE SPECIFICATION GRADE AND RATED AT 20AMPERES FOR LIGHT SWITCHES, AND 20 AMPERES FOR DUPLEXRECEPTACLES. THE COLOR OF THE DEVICES AND COVER PLATESSHALL BE AS DIRECTED BY ARCHITECT.

26. ALL WIRING SHALL BE INSTALLED IN LISTED METALLICRACEWAYS. EMT FITTINGS SHALL BE MALLEABLE IRON ORSTEEL. CONNECTORS SHALL BE INSULATED THROAT TYPE. MINIMUMCONDUIT SIZE IS ¾”. FOLLOW NEC FOR MAXIMUM NUMBER OFCONDUCTORS PER CONDUIT. CONDUIT SHALL BE OF SUFFICIENTSIZE AND CONDUCTOR QUANTITY SHALL BE LIMITED TO ELIMINATETHE NEED TO DE-RATE CONDUCTORS. METAL CLAD CABLE IS NOTPERMITTED.

27. WIRE SHALL BE COPPER, 75 DEGREE CELSIUS RATED FOR GENERALUSE. WIRING WITHIN 3 INCHES OF FLUORESCENT BALLASTS WIRESHALL BE COPPER, MINIMUM 90 DEGREE CELSIUS RATED. SIZESINDICATED ARE FOR INSTALLATION IN A MAXIMUM 30 DEGREECELSIUS AMBIENT. CONDUCTOR AMPACITY SHALL BE DERATED FORHIGHER AMBIENT INSTALLATIONS.

28. PROVIDE NEW UPDATED PANELBOARD DIRECTORIES FOR EXISTINGAND NEW CIRCUITS BEING UTILIZED FOR COMPLETION OF PROJECT.

29. PANEL DIRECTORIES SHALL BE REMOVABLE. ROOM NAMES ANDNUMBERS SHALL BE AS DIRECTED BY OWNER. DIRECTORIES SHALLBE TYPED AND INSTALLED UNDER CLEAR PLASTIC COVERS.

30. FINAL CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHERVIBRATING EQUIPMENT SHALL BE SEAL TITE FLEX AND APPROVEDFITTINGS. DO NOT SECURE CONDUITS, DISCONNECTS, OR DEVICESTO DUCTWORK OR MECHANICAL EQUIPMENT.

31. FOR LOW VOLTAGE WIRING ROUTED IN CONDUIT , PROVIDE PULLBOXES WHERE THE ROUTE IS LONGER THAN 100 FEET, OR HAS MORETHAN TWO (2) 90 DEGREE BENDS.

32. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTSSHOW THAT WORK IS DEFECTIVE, CONTRACTOR SHALL MAKECORRECTIONS NECESSARY AT NO COST TO OWNER.

33. GUARANTEE THE INSTALLATION AGAINST DEFECTS IN MATERIALSAND WORKMANSHIP WHICH MAY OCCUR UNDER NORMAL USAGE FORA PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. DEFECTSSHALL BE PROMPTLY REMEDIED WITHOUT COST TO THE OWNER.

34. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FORCONTINUOUS OPERATION. LIGHTS, SWITCHES, RECEPTACLES,MOTORS, ETC. SHALL BE CONNECTED AND OPERABLE.

35. MAINTAIN A CURRENT SET OF AS-BUILT RECORD DRAWINGS WHICHSHALL BE AVAILABLE FOR REVIEW DURING ENGINEER'S SITEOBSERVATIONS. UPON COMPLETION, PROVIDE RECORD DRAWINGSTO ARCHITECT. DRAWINGS SHALL INCLUDE ALL ADDENDUM ITEMS,CHANGE ORDERS, ALTERATIONS, REROUTINGS, ETC.

36. FOR 120V BRANCH CIRCUITS THAT EXCEED 75' IN LENGTH AND 277VBRANCH CIRCUITS THAT EXCEED 175' IN LENGTH INCREASE TO NEXTWIRE SIZE. (12 AWG GOES TO 10 AWG).

37. THIS RENOVATION PROJECT IS TO BE EXECUTED IN MULTIPLEPHASES. SEE ARCHITECTURAL PLANS FOR PROJECT PHASING.

FIRE ALARM BELLB

NO SCALETYPICAL DEVICE ALIGNMENT

EQ EQ

6"MIN.

DOOR WINDOW

EQ EQ

LIGHTINGCONTROL ℄

OFFSET COMMUNICATIONSDEVICES FROM POWERDEVICES TO EITHEROPPOSITE SIDE OF STUD BAY,OR ADJACENT STUD BAY.

NOTES:1. IF ALIGNMENT OF DEVICES INDICATED HERE IS IN CONFLICT

WITH ADA REQUIREMENTS DUE TO INSTALLATION DETAIL, ADADIMENSIONS SHALL GOVERN.

2. REFERENCE ARCHITECTURAL INTERIOR ELEVATIONS.LOCATIONS SHOWN ON INTERIOR ELEVATIONS SHALLSUPERCEDE LOCATIONS SHOWN HERE, UNLESS LOCATIONSSHOWN ON INTERIOR ELEVATIONS ARE NOT CODE COMPLIANT.

EQ

BACKSPLASH

ABOVECOUNTERDEVICE

RECEPTACLE

COUNTERTOP

EQ

FINISHED FLOOR

FINISHED CEILING

6"MIN.

20"MAX.

ALIGN DEVICES (OUTLETS,CONTROLS, ETC.)VERTICALLY. DO NOTVERTICALLY ALIGN POWERAND COMMUNICATIONSDEVICES SIMULTANEOUSLY.

NORMAL CALL DOME LIGHT - WALL MOUNT

NURSECALL SYMBOLS

Z

J

NC

NCTC

T

B

D

P

Z

2

1

NORMAL CALL DOME LIGHT - SINGLE LED - WALL MOUNT

NURSE CALL ZONE LIGHT - WALL MOUNT

NORMAL CALL DOME LIGHT - CEILING MOUNT

NORMAL CALL DOME LIGHT - SINGLE LED - CEILING MOUNT

NURSE CALL ZONE LIGHT - CEILING MOUNT

DOMELESS CONTROLLER - ABOVE MOUNT

NURSE CALL MASTER STATION

NURSE CALL TERMINAL CABINET

CODEBLUE EMERGENCY STATION

TOILET EMERGENCY STATION w/ PULL CORD

STAFF EMERGENCY STATION

SINGLE PATIENT STATION

DOUBLE PATIENT STATION

STAFF PRESENCE PAD

STAFF STATION

DUTY STATION

PATIENT BED HANDHELD CONTROL

SE

CB

SS

'*' ISSUED FOR INFORMATION ONLY' ' NOT PART OF SET' ' ISSUED AS PART OF A SETISSUE LOG KEY:

#

DA

TE

ISSUE LOG

ELECTRICAL SHEET INDEX

TITLE

ELECTRICAL COVER SHEETE0-01

02.2

2.20

1810

0% D

D

ELECTRONIC SAFETY & SECURITY SYMBOLS

L

CEILING MOUNTED CAMERA

WALL MOUNTED CAMERA

MAGNETIC DOOR CONTACT SWITCH

ADA ACCESS CONTROL MAIN PANELADA

CR CARD READER

S ELECTRIC LOCK - STRIKE

LM ELECTRIC LOCK - MAGNETIC

LR ELECTRIC LATCH / ROD RETRACTOR

SM MAGNETIC DOOR CONTACT SWITCH

PANIC BUTTONP

INTRUSION MOTION SENSOR

SECURITY KEYPAD

MON CCTV MONITOR

ACCESS CONTROL MAIN PANELACP

EXIT PANIC/CRASH BAR SENSORREX

SECURITY CENTRAL PROCESSING UNITCPU

SECURITY/ACCESS CONTROL WORKSTATIONWS

K

I

MULTI-OUTLET WIREWAY

VOICE/DATA SYMBOLS

COMBO VOICE/DATA OUTLET (1 DATA, 1 VOICE UNO)

(1) VOICE WALL OUTLET

(1) DATA WALL OUTLET

(1) VOICE FLOOR OUTLET

(1) DATA FLOOR OUTLET

COMBO VOICE/DATA FLOOR OUTLET

VOICE/DATA/FIBER OUTLETOF

POINT OF SALE (POS) OUTLETPOS

AUTOMATED TELLER MACHINE (ATM) STATIONATM

PUBLIC PAYPHONE OUTLETPP

ELEVATOR PHONE OUTLETE

POWER/TELECOM POLE

WIRELESS LAN (WI-FI) ACCESS POINT OUTLET (2 CABLES)

FAX/COPIER OUTLET

EMERGENCY SERVICES PHONE OUTLETEM

F

C

EC - ELECTRICAL CONTRACTOR

MC MECHANICAL CONTRACTOR-

PC PLUMBING CONTRACTOR-

ELECTRICAL LIGHTING PLANE1-01

ELECTRICAL POWER PLANE1-02

ELECTRICAL SPECIAL SYSTEMS PLANE1-03

ELECTRICAL DIAGRAMSE5-01

ELECTRICAL ONE-LINE DIAGRAM AND SCHEDULESE0-02

MECHANICAL EQUIPMENT WIRING AND CONNECTIONS

ITEM FURNISHEDUNDER

SET IN PLACE ORMTD. UNDER

WIRED /CONNECTED

UNDER

1. EQUIPMENT MOTORS AND THERMAL OVERLOADS, RESISTANCEHEATERS MD MD ED

2. VFDs, MOTOR CONTROLLERS; MAGNETIC STARTERS, REDUCEDVOLTAGE STARTERS AND OVERLOAD RELAYS MD ED(a) ED

3.DISCONNECT SWITCHES (FUSED OR NON-FUSED), HP RATEDSWITCHES, THERMAL OVERLOAD SWITCHES AND FUSES, ANDMANUAL OPERATING SWITCHES

ED(a) ED(a) ED

4.

PUSHBUTTON STATIONS, PILOT LIGHTS, MULTI-SPEEDSWITCHES, FLOAT SWITCHES, THERMOSTATS, CONTROLRELAYS, TIMECLOCKS, CONTROL TRANSFORMERS, CONTROLPANELS, MOTOR VALVES, DAMPER ACTUATORS, SOLENOIDVALVES, EP AND PE SWITCHES AND INTERLOCKS

MD MD MD(b)

5. 120 VOLT POWER FOR BAS PANELS, FIRE PROTECTION ANDBOILER CONTROLS ED ED ED

6. FIRE/SMOKE DAMPERS AND ELEVATOR VENT DAMPERS MD MD ED(c)

MD = MECHANICAL DIVISIONED = ELECTRICAL DIVISION

NOTES:

( a ) IF FURNISHED AS PART OF FACTORY-WIRED EQUIPMENT, THEN WIRING AND CONNECTIONS ONLY BY ED

( b ) IF ANY OF THESE DEVICES CARRY THE FULL LOAD CURRENT TO ANY MOTOR THEY SHALL BE CONNECTED BY ED. CONTROLDEVICES CARRYING FULL LOAD CURRENT FURNISHED BY MD AND WIRED BY ED SHALL BE LOCATED AT THE DEVICE BEINGCONTROLLED, UNLESS SHOWN ON DRAWINGS OR MUTUAL AGREEMENT IS MADE BETWEEN THE CONTRACTORS WITH NOCHANGE IN THE CONTRACT PRICE.

( c ) WIRING FROM ALARM CONTACTS TO ALARM SYSTEM BY ED; ALL CONTROL FUNCTION WIRING BY MD. DUCT DETECTORSFURNISHED BY ED, SET IN PLACE BY MD

GENERAL NOTE: THE ABOVE LIST DOES NOT ATTEMPT TO INCLUDE ALL COMPONENTS. ALL ITEMS NECESSARY FOR A COMPLETESYSTEM SHALL BE INCLUDED IN THE BASE CONTRACT.

04.3

0.20

1895

% C

D

E1-04

ELECTRICAL DEMOLITION PLAN

05.2

5.20

18PE

RMIT

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

ELECTRICALCOVER SHEET

E0-01

Page 18: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

SCALE:1 PARTIAL ELECTRICAL ONE-LINE DIAGRAMNTS

PANELDPDA

PANELDPAE

FIRST FLOOR

PANELDPC

PANELDPN

PANELDPM

SWITCHBOARDEQUIPMENTBRANCH(NORTH)

BASEMENT

UPPER LEVEL

SWITCHBOARDCRITICALBRANCH

SWITCHBOARDEQUIPMENTBRANCH(SOUTH)

SWITCHBOARDNORMALPOWER

SWITCHBOARDLIFE SAFETYBRANCH

T

PANELLSL

PANELLSP

PANELNL

PANELCL

T

PANELNP

PANELNP1

T

PANELCP

T

PANELNP2

T

PANELME

PANEL: CP (EXISTING)2-SECTION

VOLTAGE: 120/208V, 3PH, 4WMINIMUM BUS: 225

LOCATION: ELEC CLOSET MAIN: MLOMOUNTING: SURFACE MINIMUM AIC:

NO.LOAD

TYPE LOAD DESCRIPTIONBREAKER BUS BREAKER

TYPE LOAD DESCRIPTIONLOAD

NO.A B C POLE TRIP A B C TRIP POLE A B C

1 1200 L EXAM LIGHTS 1 20 + 20 1 E TIME CLOCK 200 23 400 M ER DOOR ENTRY 1 20 + 20 1 L HELI DECK LIGHTS 1200 45 360 R RECEP SECURITY 1 20 + 20 1 L HELI DECK LIGHTS 1200 67 1440 R RECEP EXAM 14-15 1 20 + 20 1 R RECEP EXAM 8-9 1440 89 1440 R RECEP EXAM 12-13 1 20 + 20 1 R RECEP EXAM 6-7 1440 1011 1440 R RECEP EXAM 10-11 1 20 + 20 1 R RECEP EXAM 4-5 1440 1213 180 R RECEP NOURISHMENT 1 20 + 20 1 R RECEP MEDICATION 180 1415 540 R RECEP ALCOVE 1108 1 20 + 20 1 R RECEP MEDICATION 180 1617 720 R RECEP EXAM 1 1 20 + 20 1 R RECEP MEDICATION 180 1819 720 R RECEP EXAM 2 1 20 + 20 1 R RECEP N NURSE STA 540 2021 900 R RECEP OB EXAM 1 1 20 + 20 1 R RECEP N NURSE STA 360 2223 900 R RECEP OB EXAM 2 1 20 + 20 1 R RECEP N NURSE STA 1080 2425 400 E ISOLATION RM MONITOR 1 20 + 20 1 R RECEP RM 1048 ANTE 180 2627 1080 R WIRE MOLD NURSE STA 1 20 + 20 1 R RECEP EXAM 16-17 1440 2829 540 R RECEP S NURSE STA 1 20 + 20 1 R RECEP PHYSH RM 540 3031 360 R RECEP S NURSE STA 1 20 + 20 1 R RECEP TRAUMA 1 1080 3233 1080 R RECEP S NURSE STA 1 20 + 20 1 R RECEP TRAUMA 1 1080 3435 1080 R RECEP TRAUMA 2 1 20 + 20 1 M AUTO DOOR ENTRY 800 3637 1080 R RECEP TRAUMA 2 1 20 + 20 1 R RECEP RECEPTION 720 3839 360 R WP RECEP 1 20 + 20 1 R RECEP TRIAGE 720 4041 360 R RECEP PYXIS EQUIP 1 20 + 20 1 R RECEP TRIAGE 360 4243 360 R IT CLOSET SOUTH 1 20 + 20 1 R OUTSIDE ED #4 360 4445 360 R IT CLOSET SOUTH 1 20 + 20 1 R RECEP RECEPTION 720 4647 180 R HALLWAY EXIT 1 20 + 20 1 M DOOR AMB ENTRY 800 4849 720 R RECEP FAST TRACK 1 20 + 20 1 R RECEP FAST TRACK 720 5051 720 R RECEP FAST TRACK 1 20 + 20 1 E PNUMATIC TUBE NS 600 5253 180 R RECEP PATIENT MNTR 1 20 + 20 1 R RECEP ALCOVE 1062 180 5455 720 R RECEP MIDLAND/QA 1 20 + 20 1 R RECEP ALCOVE 1076 180 5657 360 R RECEP MULTI-PATIENT 1 20 + 20 1 R RECEP ASSESS 720 5859 360 R RECEP MULTI-PATIENT 1 20 + 20 1 R RECEP MULTI-PAT CP 360 6061 540 R RECEP RESULTS WAIT 1 20 + 20 1 R FAST TRACK 2 BED RM 1080 6263 560 R RECEP SUPPLY EQUIP 1 20 + 20 1 R RECEP TREATMENT 540 6465 540 R RECEP SUPPLY EQUIP 1 20 + 20 1 R RECEP TREATMENT 540 6667 1200 E

250V OUTLET X-RAY 2 15 + 20 1 R RECEP TREATMENT 540 6869 1200 E + 20 1 E DOOR POWER 1000 7071 540 R FAST TRK COMPS 1 20 + 20 1 E DOOR POWER 800 7273 900 R FAST TRK PRINTER 1 20 + SPACE 7475 SPACE + SPACE 7677 SPACE + SPACE 7879 SPACE + SPACE 8081 2400 E

FILM PROCESSOR 2 30 + SPACE 8283 2400 E + SPACE 84

LOAD TYPE PANEL TOTAL FEED THRUTOTAL

SUBFEEDTOTAL

FEEDERSUBTOTAL DEMAND FEEDER TOTAL

GENERAL NOTES:A. CRITICAL BRANCH POWER

(L) LIGHTING 3600 3600 125% 4500 B. SQUARE D NQOD

(R) RECEPTACLES 40520 40520 NEC 220 25260 C. NEW CIRCUITS SHOWN IN BOLD, USE EXISTING SPARE

(LM) LARGEST MOTOR 0 0 25% 0 OR CIRCUIT THAT IS NO LONGER IN USE.

(M) MOTORS (ALL) 2000 2000 100% 2000 D. EXISTING CIRCUITS NO LONGER USED RENAME 'SPARE'.

(E) EQUIPMENT 10200 10200 100% 10200 SPECIFIC NOTES:(A) APPLIANCES 0 0 0 0 (1) PROVIDE NEW 20A CB IN SPACE 72.

PANEL TOTAL (KVA): 42.0 (2)

(3)

PANEL TOTAL (A): 117 (4)

(5)

PANEL: NP (EXISTING)2-SECTION

VOLTAGE: 120/208V, 3PH, 4WMINIMUM BUS: 225

LOCATION: ELEC CLOSET MAIN: MLOMOUNTING: SURFACE MINIMUM AIC:

NO.LOAD

TYPE LOAD DESCRIPTIONBREAKER BUS BREAKER

TYPE LOAD DESCRIPTIONLOAD

NO.A B C POLE TRIP A B C TRIP POLE A B C

1 1080 R EXAM 14, 15 1 20 + 20 1 R CATV 360 23 900 R EXAM 12, 13 1 20 + 20 1 R RECEP EXAM 8, 9 900 45 1080 R EXAM 10, 11 1 20 + 20 1 R RECEP EXAM 6, 7 900 67 500 A NOURISH REFRG 1 20 + 20 1 R RECEP EXAM 4, 5 900 89 500 A NOURISH REFRG 1 20 + 20 1 R RESTROOM RECEPS 540 1011 720 R RECEP MEDICATION 1 20 + 20 1 R RECEP SOILED UTILITY 1080 1213 900 R RECEP ALCOVE 1088 1 20 + 20 1 SPARE 1415 1080 R RECEP OB EXAM 1 1 20 + 20 1 R RECEP EXAM 1 720 1617 1080 R RECEP OB EXAM 2 1 20 + 20 1 R RECEP EXAM 2 720 1819 1080 R EXAM 16, 17 1 20 + 20 1 M EXHAUST FANS EF-1 696 2021 400 A RECEP STAFF LOUNGE 1 20 + 20 1 M EXHAUST FANS EF-2 696 2223 1000 A RECEP STAFF LOUNGE 1 20 + 20 1 SPARE 2425 800 A RECEP STAFF LOUNGE 1 20 + 20 1 SPARE 2627 900 R RECEP PHYSH RM 1 20 + 20 1 SPARE 2829 720 R RECEP TRAUMA 1 1 20 + 20 1 R RECEP DARK RM/CNTRL 720 3031 720 R RECEP TRAUMA 1 1 20 + 20 1 R RECEP TRAUMA 2 900 3233 240 R ELEV PIT RECEP & LT 1 20 + 20 1 R RECEP TRAUMA 2 900 3435 270 L ELEV EQUIP RM LIGHTS 1 20 + 20 1 R RECEP J/C ELEV LOBBY 1260 3637 9500

PANEL NP1 3 100+ 20 1 R BLANKET WARMER 1500 38

39 10840 + 20 1 A ICE-MACHINE 1340 4041 10140 + 20 1 A U.C. REFRIG, CONV. 580 4243 1250 E HAND DRYER 1 20 + 20 1 M PNUMATIC TUBE 1176 4445 1250 E HAND DRYER 1 20 + 20 1 A HOT/COLD WATER 1500 4647 1250 E HAND DRYER 1 20 + 20 1 SPARE 4849 SPARE 1 20 + 20 1 SPARE 5051 1200 R VENDING MACHINE 1 20 + 20 1 SPARE 5253 1200 R VENDING MACHINE 1 20 + 20 1 SPARE 5455 900 R RECEP RM #3 1 20 + 20 1 R WIRE MOLD EQUIP STR 900 5657 540 R RECEP SECURITY 1 20 + 20 1 R WIRE MOLD EQUIP STR 1080 5859 360 R RECEP WAITING 1 20 + 20 1 R BLK TRAUMA 1080 6061 720 R BATHROOM SLEEP 1 20 + 20 1 R RED ED OPEN 720 6263 1260 R RECEP SLEEP 1 20 + 20 1 R RECEP TRIAGE/TRACK 1080 6465 1000 E VACUUM TUBE 1 20 + 20 1 R RECEP STAFF LOUNGE 720 6667 1000 E RESPITORY EQUIP CLT 1 20 + 20 1 R NORTH HALL TV 360 6869 600 E IT SPLIT UNIT 1 20 + 20 1 R CENTER HALL TV 360 7071 360 R RECEP TVS TRACK 1 20 + 20 1 R SOUTH HALL TV 360 7273 1080 R RECEP RR/TELE/QUIET 1 20 + 20 1 R RECEP TREATMENT 900 7475 900 R RECEP SUPPLY/EQUIP 1 20 + 20 1 R RECEP TREATMENT 1260 7677 720 R POWER STRIP HALLWAY 1 20 + 20 1 R RECEP TREATMENT 1260 7879 720 R POWER STRIP HALLWAY 1 20 + 20 1 SPARE 8081 720 R RECEP EQUIP STORAGE 1 20 + SPACE 8283 SPARE 1 20 + 20 1 R HOUSE KP, DRINK FTN 720 84

LOAD TYPE PANEL TOTAL FEED THRUTOTAL

SUBFEEDTOTAL

FEEDERSUBTOTAL DEMAND FEEDER TOTAL

GENERAL NOTES:A. NORMAL BRANCH POWER

(L) LIGHTING 270 1280 1550 125% 1938 B. SQUARE D NQOD

(R) RECEPTACLES 43380 14184 57564 NEC 220 33782 C. NEW CIRCUITS SHOWN IN BOLD, USE EXISTING SPARE

(LM) LARGEST MOTOR 0 0 0 25% 0 OR CIRCUIT THAT IS NO LONGER IN USE.

(M) MOTORS (ALL) 2568 11076 13644 100% 13644 D. EXISTING CIRCUITS NO LONGER USED RENAME 'SPARE'.

(E) EQUIPMENT 6350 2500 8850 100% 8850 SPECIFIC NOTES:(A) APPLIANCES 6620 0 6620 3 5958 (1) PROVIDE GFCI CIRCUIT BREAKER IN SPACE 84

PANEL TOTAL (KVA): 64.2 (2)

(3)

PANEL TOTAL (A): 178 (4)

(5)

PANEL: NP1 (EXISTING)VOLTAGE: 120/208V, 3PH, 4WMINIMUM BUS: 225

LOCATION: ELEC CLOSET MAIN: MLOMOUNTING: SURFACE MINIMUM AIC:

NO.LOAD

TYPE LOAD DESCRIPTIONBREAKER BUS BREAKER

TYPE LOAD DESCRIPTIONLOAD

NO.A B C POLE TRIP A B C TRIP POLE A B C

1 SPACE + SPACE 23 SPACE + SPACE 45 SPACE + SPACE 67 480 L X-RAY LIGHTS 1 20 + 20 1 X-RAY RECEP'S 720 89 SPACE + 20 1 X-RAY RECEP'S 720 1011 SPACE + SPACE 1213 SPACE + SPACE 1415 3300 M

AIR CURTAINAMB. ENTRY 3 40

+ SPACE 1617 3300 M + SPACE 1819 3300 M + 20 2 SPARE

2021 1000 E X-RAY (TIED TO 23) 1 20 + 2223 1000 E X-RAY 1 20 + 20 1 R CHART ROOM 900 2425 500 E ER DOORS 1 20 + 20 1 R CHART ROOM 900 2627 864 R GARDEN FOUNTAIN 1 20 + 20 1 R CHART ROOM 900 2829 800 L GARDEN LIGHTS 1 20 + 20 1 R CHART ROOM 900 3031 900 R RECEP CONSULT 1 20 + 20 1 R CHART ROOM 900 3233 720 R RECEP MULTI-PATIENT 1 20 + 20 1 R RECEP VERTICAL 1080 3435 540 R RECEP MULTI-PATIENT 1 20 + 20 1 R RECEP VERTICAL 1260 3637 720 R RECEP REC/SCL/DOOR 1 20 + 20 1 R RECEP VERTICAL 1080 3839 1176 M ER HALLWAY EXHAUST 1 20 + 20 1 R RECEP VERTICAL 1080 4041 360 R ED TV MONITOR 1 20 + 20 1 R RECEP OFFICE/VERT 1080 42

LOAD TYPE PANEL TOTAL FEED THRUTOTAL

SUBFEEDTOTAL

FEEDERSUBTOTAL DEMAND FEEDER TOTAL

GENERAL NOTES:A. NORMAL BRANCH POWER

(L) LIGHTING 1280 1280 125% 1600 B. SQUARE D NQOD

(R) RECEPTACLES 14184 14184 NEC 220 12092 C. NEW CIRCUITS SHOWN IN BOLD, USE EXISTING SPARE

(LM) LARGEST MOTOR 0 0 25% 0 OR CIRCUIT THAT IS NO LONGER IN USE.

(M) MOTORS (ALL) 11076 11076 100% 11076 D. EXISTING CIRCUITS NO LONGER USED RENAME 'SPARE'.

(E) EQUIPMENT 2500 2500 100% 2500 SPECIFIC NOTES:(A) APPLIANCES 0 0 0 0 (1)

PANEL TOTAL (KVA): 27.3 (2)

100A UPSTREAM BREAKER (3)

PANEL TOTAL (A): 76 (4)

(5)

WIRING SCHEDULE - COPPERAMPS

(2WG) (3WG) (4WG)

1Ø, 2 WIRE, GROUND 1Ø, 3 WIRE, GROUND OR 3Ø, 3 WIRE, GROUND 3Ø, 4 WIRE, GROUND

20 (2#12 & 1#12 G) 3/4"C (3#12 & 1#12 G) 3/4"C (4#12 & 1#12 G) 3/4"C

30 (2#10 & 1#10 G) 3/4"C (3#10 & 1#10 G) 3/4"C (4#10 & 1#10 G) 3/4"C

CONDUCTOR SIZES ARE BASED ON 60° TERMINATIONS LESS THAN 100A AND 75° TERMINATIONS GREATER THAN 100A

CONDUIT SIZES ARE BASED ON NEC TABLE 4 (RNC) AND TABLE 5 (THHN INSULATION).

NOTE:ALL ITEMS ARE EXISTING TO REMAIN.ONE-LINE DIAGRAM SHOWN FORREFERENCE ONLY.

LUMINAIRE SCHEDULETYPE DESCRIPTION MOUNTING RECESS

DEPTHLED INPUT

WATTS VOLT MANUFACTURER CATALOG NUMBER SPECIFICNOTESLUMENS TEMP

R12x4 RECESSED LED TROFFER, WHITE ALUMINUM FRAME,10% 0-10V DIMMING, 90+ CRI RECESSED 4-1/2" 4000 3500 34 277 MARK WHSPR 2X4 4000LM 35K 90CRI

MIN10 MVOLT SWC

R22x2 RECESSED LED TROFFER, WHITE ALUMINUM FRAME,10% 0-10V DIMMING, 90+ CRI RECESSED 4-1/2" 3300 3500 30 277 MARK WHSPR 2X2 3300LM 35K 90CRI

MIN10 MVOLT SWC

R3 2x4 RECESSED FLANGED TROFFER, MINIMUM SECURITYCONFINEMENT GRADE, LED, 0-10V DIMMING RECESSED 3" 5500 3500 50 277 NEWSTAR 37M24-GJ-L2351-BB-27-DB

R4 2x2 RECESSED LED TROFFER, WHITE ALUMINUM FRAME,10% 0-10V DIMMING RECESSED 4-1/2" 2000 3500 18 277 MARK WHSPR 2X2 2000LM 35K 90CRI

MIN10 MVOLT SWC

R5 4" DIA LED DOWNLIGHT, HAZE ALZAK CONE, WHITE TRIMRING, FLOOD DISTRIBUTION RECESSED 6" 1000 3500 16 277 JUNO IC4AL 10LM 35K 90CRI FL

MVOLT ZT 42L HZWH

R6 6" DIA LED DOWNLIGHT RETROFIT TRIM, WHITEREFLECTOR AND TRIM RING RECESSED 4-1/2" 1500 3500 20 277 JUNO JCLR6S 15LM 35K 90CRI

MVOLT ZT WWH

R7 2x4 RECESSED LED TROFFER, WHITE ALUMINUM FRAME,10% 0-10V DIMMING RECESSED 4-1/2" 3000 3500 25 277 MARK WHSPR 2X4 3000LM 35K 90CRI

MIN10 MVOLT SWC

R8 2x4 RECESSED FLANGED LED TROFFER, WHITEALUMINUM FRAME, 10% 0-10V DIMMING, 90+ CRI RECESSED 4-1/2" 4000 3500 34 277 MARK WHSPR 2X4 4000LM 35K 90CRI

MIN10 MVOLT SWC 3

W1 4' LINEAR LED VANITY, 1.5" SQUARE PROFILE DIFFUSER,WHITE

WALLSURFACE 888 3500 16 277 VODE 707-Z2-4/0-48-CM-AE-120-

0-Z-LO-35-S6-0-WH-0 2

S1 4' LED UTILITY STRIP WITH LENS SURFACE 3000 3500 25 277 LITHONIA ZL1N L48 SMR 3000LM FST MVOLT 35K 80CRI WH

S224" UNDER CABINET LED FIXTURE, HIGH-IMPACT ACRYLICLENS, ANTI-MICROBIAL WHITE SURFACE 1220 3500 12 277 SPECTRA HUC523-MVOLT-LED35-S1

LX12-AM

X1 EXIT SIGN, SINGLE FACE, WHITE THERMOPLASTIC BODY,GREEN LETTERS SURFACE N/A LED GREEN 2 277 LITHONIA LQM S W 3 G 120/277 1

X2 EXIT SIGN, DOUBLE FACE, WHITE THERMOPLASTIC BODY,GREEN LETTERS SURFACE N/A LED GREEN 2 277 LITHONIA LQM S W 3 G 120/277 1

GENERAL NOTES:A. THE LUMINAIRE SCHEDULE CAN NOT BE USED INDEPENDENTLY OF THE DRAWINGS AND SPECIFICATIONS TO OBTAIN LUMINAIRE COSTS. THE INDIVIDUAL ESTABLISHING LUMINAIRE COSTS SHALL NOT

QUOTE PRICING WITHOUT FIRST SEEING APPLICABLE ELECTRICAL DRAWINGS AND ELECTRICAL DIVISION SPECIFICATIONS. THE CONTRACTOR IS REPONSIBLE FOR PROVIDING NECESSARY DRAWINGS ANDSPECIFICATIONS TO THE INDIVIDUAL QUOTING LUMINAIRE PRICING.

B. REFER TO DRAWINGS FOR FIXTURES CONNECTED TO BATTERY INVERTER SYSTEM (SHOWN BY HATCH IN/OVER SYMBOL).C. ALL LEDS ARE TO BE 3500° KELVIN COLOR TEMPERATURE

SPECIFIC NOTES:(1) INCLUDE EXIT DIRECTION ARROWS AS INDICATED ON PLAN.(2) INSTALL ABOVE MIRROR(S). COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL ELEVATIONS.(3) PROVIDE WITH MUD IN FLANGE.(4)

SCOPE OF WORKINCLUDES BRANCHCIRCUITS IN THESEPANELS ONLY.

TRANSFORMER75kVA 480/277V,208/120Y SEC

TRANSFORMER75kVA 480/277V,208/120Y SEC

DISCONNECTSWITCH 400A,225A FUSE

DISCONNECTSWITCH 200A,200A FUSE

SCOPE OF WORKINCLUDES BRANCHCIRCUITS IN THESEPANELS ONLY.

TRANSFORMER30kVA 480/277V,208/120Y SEC

PANEL: ME (EXISTING)VOLTAGE: 120/208V, 3PH, 4WMINIMUM BUS: 100

LOCATION: 2ND FLOOR MAIN: 100/3 CBMOUNTING: SURFACE MINIMUM AIC:

NO.LOAD

TYPE LOAD DESCRIPTIONBREAKER BUS BREAKER

TYPE LOAD DESCRIPTIONLOAD

NO.A B C POLE TRIP A B C TRIP POLE A B C

1 800 E FOAM RM HEATER EX 1 20 + 20 1 M N. BOILER FAN 696 23 800 E HEATER MECH RM 1 20 + 20 1 E BOILER CTL POWER 400 45 696 M EX-FAN NW MECH RM 1 20 + 20 1 M S. BOILER FAN 696 67 1200 E IT RACK UPS 1 20 + 20 1 M ELEV PIT PUMP 696 89 400 E WIND SOCK 1 20 + 20 1 M BOILER ROOM EX FAN 696 1011 400 E HVAC CONTROL PANEL 1 20 + 20 1 E TU WEST UNITS 950 1213 696 M CIRC PUMPS AHU 1 20 + 20 1 R RECEP FOPR AIR DRY 1080 1415 400 E C/P ON AHU 1 20 + 20 1 M EF6 696 1617 200 L ELEV CAB LIGHTS 1 20 + 20 1 ELEVATOR SHUNT TRIP 1819 400 E HVAC CONTROLS 1 20 + 20 1 M EF-3 696 2021 1200 E

CTL AIR COMP 3 15+ 20 1 E TU EAST UNITS 550 22

23 1200 E +30 3

MHANGER DOOR

2400 2425 1200 E + M 2400 2627

SPARE 2 40 + M 2400 2829 + SPACE 30

LOAD TYPE PANEL TOTAL FEED THRUTOTAL

SUBFEEDTOTAL

FEEDERSUBTOTAL DEMAND FEEDER TOTAL

GENERAL NOTES:A. EQUIPMENT BRANCH POWER

(L) LIGHTING 200 200 125% 250 B. SQUARE D NQOD

(R) RECEPTACLES 1080 1080 NEC 220 1080 C. NEW CIRCUITS SHOWN IN BOLD, USE EXISTING SPARE

(LM) LARGEST MOTOR 0 0 25% 0 OR CIRCUIT THAT IS NO LONGER IN USE.

(M) MOTORS (ALL) 12768 12768 100% 12768 D. EXISTING CIRCUITS NO LONGER USED RENAME 'SPARE'.

(E) EQUIPMENT 9900 9900 100% 9900 SPECIFIC NOTES:(A) APPLIANCES 0 0 0 0 (1)

PANEL TOTAL (KVA): 24.0 (2)

(3)

PANEL TOTAL (A): 67 (4)

(5)

MECHANICAL EQUIPMENT SCHEDULE

MARK DESCRIPTION VOLT /PHASE HP WATTS FLA MCA MOCP STARTER DISCONNECT/

FUSE SIZE FEEDER CIRCUIT SPECIFIC NOTES

EF-1 EXHAUST FAN 120/1 1/4 SNAP SWITCH 30A(2WG) NP-20 1

EF-2 EXHAUST FAN 120/1 1/4 SNAP SWITCH 20A(2WG) NP-22 1

TU TERMINAL UNIT (EXISTING) 120/1 50 SNAP SWITCH 20A(2WG) SEE SHEET E1-03 2

GENERAL NOTES:A. SEE SPECIFICATIONS FOR ELECTRICAL DIVISION AND MECHANICAL DIVISION MOTOR STARTER COORDINATION.B. PROVIDE PHASE PROTECTION FOR ALL THREE PHASE MOTORS ABOVE 7-1/2 HP.C. PROVIDE ALL EXTERIOR DISCONNECTS WITH NEMA 3R RATING.D. WHEN EQUIPMENT IS LISTED WITH ONLY A HORSEPOWER RATING THE DISCONNECT AND FEEDER ARE SIZED PER THE N.E.C.

SPECIFIC NOTES:(1) ON ROOF.(2) MULITPLE UNITS WITH SAME DESIGNATION. CONNECT CPT'S PROVIDED BY MC AT EXISTING UNIT.(3)(4)

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

ELECTRICALONE-LINE DIAGRAMAND SCHEDULES

E0-02

Page 19: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

2

SCOPE OF WORK

1SCOPE OF WORK

CP

NP

NP1

TTB(E)

1SCOPE OF WORK

JJ 2

3

3

3 4

1

5

1SCOPE OF WORK

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

ELECTRICALDEMOLITION PLAN

E1-01

Scale:

1 ELECTRICAL DEMOLITION PLAN1/8"=1'-0"

A. THE ENGINEER HAS UNDERTAKEN NO FIELDVERIFICATION OF EXISTING DEVICES. ALL DEVICESSHOWN ARE FROM RECORD DRAWINGS. CONTRACTORSHALL FIELD VERIFY ALL EXISTING DEVICES THATPERTAIN TO THIS PROJECT.

B. FOR ALL ITEMS TO BE DEMOLISHED, REMOVE CIRCUITBACK TO POINT OF CONNECTION. MAKE BRANCHCIRCUIT WITH REMAINING DEVICES CONTINUOUS.

C. ELECTRICAL CONTRACTOR SHALL REMOVE ALLDEMOLISHED ITEMS FROM SITE UNLESS OWNERWISHES TO RETAIN. ITEMS REMOVED FROM SITESHALL BE DISPOSED OF IN A LEGAL MANNER.

D. THIS RENOVATION PROJECT IS TO BE EXECUTED INMULTIPLE PHASES. SEE ARCHITECTURAL PLANS FORPROJECT PHASING.

NOTES:

1. UNLESS NOTED OTHERWISE, REMOVE ALL EXISTINGELECTRICAL AND SPECIAL SYSTEM DEVICES IN AREAOF WORK AND REMOVE ALL EXISTING LIGHTINGFIXTURES AND LIGHTING CONTROLS IN AREA OFWORK. REMOVE ALL ASSOCIATED CONDUIT ANDCONDUCTORS SERVICING DEVICES, LIGHTING ANDMECHANICAL EQUIPMENT BEING REMOVED.

2. DISCONNECT DOOR MOTOR POWER FROM CRITICALBRANCH CIRCUIT.

3. MAINTAIN EXISTING CRITICAL BRANCH LIGHTINGHOMERUN FOR REUSE WITH NEW LIGHTING.

4. MAINTAIN EXISTING LIFE SAFETY BRANCH LIGHTINGHOMERUN FOR REUSE WITH NEW LIGHTING.

5. REROUTE EXISTING HOMERUN (CL-6 PER EXISTINGDRAWINGS) AFTER DEMOLITION OF UP-STREAMLIGHTING.

FLAG NOTES:#

Scale:

2 ELECTRICAL DEMOLITION PLAN1/8"=1'-0"

Page 20: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

1

TYPICAL IN ENTRYVESTIBULE EXCEPTLIFE SAFETY

DDD

D

D

D D

DD

OS

OS

D

SS

D

SO

S

D

LSL

2

R1R1

R1 R1

R1

R1

R1

R1

R3 R3

R1 R1 R1 R2 R1 R1

D

R4 R4 R4 R4

R4

R4 R4

R4

R4

R4

R4

R4R4

R4

R2

R2

R2R2

R4 R4 R4

R4 R4

R4

R4R4R4

R4 R4 R4

R4R4R4

R4

R4

R4

R4

R4

R4

R4

R4

R4

R4

R1

R1

R1 R1

W1

W1

S1

X2

X1

X1

X1

X1

X1

X1

R4

R4

R6

R6

R6

R6

R6

R6

R6

R6

R5

R5

R5

R5

R5

R5

R5

R5

R5

R5 R5R5

R5

R5

R5

R5

R5

R5 R5 R5

R5

R5 R5

R5 R5

R5

R5

R5

R5

R5

R5

R5R5

R5

R5R5

R5

R5

R5

R5

R5R5R5

R4

R5

R5

SO

D

3

3

3

3

3

3

CL

(E)

6

R5 R5 R5

5

R5

5

R5

R4

5

5

4

7

S

D

ELEV.

MED.GAS

STAIRX1-SX

STAIR1067

EXTERIOR COURTYARD - NO PUBLIC ACCESS

OFFICE1031

EXAM1032

EXAM1033

EXAM1034

EXAM1036

EXAM1037

EXAM1038

EXAM1039

EXAM1041

CORRIDOR1029

TRIAGE/ASSESMENT

1019

RECEPTION/ASSESMENT

1018

SECURITY1018A

WAITING1013

WHEELCHAIRSTORAGE

1002

QUIETWAITING

1011

ENTRYVESTIBULE

1001

WOMEN1008

MEN1009

HSKP1004

VENDING1007

CORRIDOR1005

CORRIDOR1161

CONSULT1024

MULTI-PATIENTEXAM/HOLDING

1026

PATIENT/SPECIMENTOILET

1022

CORRIDOR1021

CORRIDOR1020

FAST TRACK1023

MEDICATION/SUPPLY

1014

NUTRITION1016

FAST TRACK1023B

FAST TRACK1023C

FAST TRACK1023A

FAST TRACK1023D

FAST TRACK1023E

FAST TRACK1023F

FAST TRACK1023G

TREATMENT1078

CONTROL1082

TREATMENT1081

ALCOVE1076

CLEAN SUPPLY/EQUIPMENT

1074

TREATMENT1077

PATIENTTOILET

1079

X-RAY1083

COMM.1084

CORRIDOR1028

ELEC.1085

ALCOVE1088A

ALCOVE1088B

ALCOVE1088C

CORRIDOR1087

MEDICATION1093

NOURISHMENT1094

PYXIS1098

STAFFTOILET

1097

PATIENTTOILET

1098

SOILEDUTILITY

1099NURSESTATION

1092

CORRIDOR1091

CRASH CART1111

CORRIDOR1109

ALCOVE1108

EXAM1101

EXAM1106

OBEXAM1102

OBEXAM1107

PATIENTTLT./SHWR

1103

PATIENTTOILET11034

CORRIDOR1027

EXAM1042

EXAM1043

EXAM1044

ISOLATION1046

ANTE1048FIRE

1047

NURSESTATION

1073

CORRIDOR1072

EXAM1049

EXAM1051

WHEELCHAIRSTORAGE

1052

VESTIBULE1053

DECONSHOWER

1054

EMSCLOSET

1056

PSYCH.1057

TRAUMA1058

TRAUMA1059

CORRIDOR1071

HSKP1061

ELEV.EQUIP.

1068

ELEV.LOBBY1064

ALCOVE1062

RESULTSWAITING

1117

OFFICE1123

STAFFLOCKERS

1124

OFFICE1123

STAFFLOUNGE

1152

OFFICE1112

OFFICE1113

TLT./SHOWER1114

CORRIDOR1134

CORRIDOR1127

R3 R3

R3 R3

D

D

D

D

R8

R8

R5

8

R5

R5

R4 R4

R4 R4 R4 R4

R4R4R4R4

R4 R4 R4 R4

(E)9

9

R4 R4

R4R4

R4 R4

R1

R1

R1

R1R1

R1

R2

R2

R2

R2

R2

R2

S

SS S

S

S2 S2

S2

S2

S2S2

S

S2

S2

S2

S

S2

S2

S2

R5

R55

5'

X1

4

5

TOILET

PASSAGEWAYX1XX

BEDSTORAGE

X1XX

EXAM #1X1XX

XRAYREADING

X1XX

PHYSICIAN'SREADING RM.

X1XX

CORRIDOR

R7R7

R7SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

ELECTRICALLIGHTING PLAN

E1-02

A. ALL DIMMER SWITCHES SHALL BE LUTRON DIVA#DVSTV OR EQUIVALENT UNLESS NOTED OTHERWISE.

B. ALL CEILING MOUNTED OCCUPANCY SENSORS SHALLBE PASSIVE INFRARED WATT STOPPER #C1-305 OREQUIVALENT.

C. ALL WALL MOUNTED OCCUPANCY SENSORS SHALL BEDUAL TECHNOLOGY WATT-STOPPER #DSW-301 OREQUIVALENT.

D. THE LOWER CASE LETTERS NEXT TO LIGHT FIXTURESINDICATE WHICH LIGHTING CONTROL DEVICE (MANUALAND AUTOMATIC) CONTROLS LIGHT FIXTURES.

E. PROVIDE STAINLESS STEEL COVER PLATES ON ALLSWITCHES.

F. CONNECT EXIT SIGNS TO LIFE SAFETY LIGHTINGCIRCUIT.

G. THIS RENOVATION PROJECT IS TO BE EXECUTED INMULTIPLE PHASES. SEE ARCHITECTURAL PLANS FORPROJECT PHASING.

NOTES:

1. INSTALL IN CUTOUTS FROM EXISTING FIXTURES.CONNECT TO EXISTING CIRCUITING AND CONTROLS.

2. APPROXIMATE LOCATION OF LIFE SAFETY ANDCRITICAL BRANCH (480V) PANELS IN THE ELEC/MECHROOM ON SECOND FLOOR.

3. REPLACE LAMPS IN EXISTING INDIRECT/DIRECTCYLINDER LIGHT FIXTURE WITH COMPATIBLE LED60W EQUIVALENT RETROFIT LAMP.

4. CONNECT TO EXISTING CORRIDOR LIFE SAFETYLIGHTING CIRCUIT AND CONTROLS.

5. CONNECT TO EXISTING CORRIDOR NORMALLIGHTING CIRCUIT AND CONTROLS.

6. CONNECT TO EXISTING CRITICAL BRANCH LIGHTINGCIRCUIT (CL-5 PER EXISTING DRAWINGS).

7. HOMERUN TO SPARE 20/1 CIRCUIT BREAKER INCIRCUIT BRANCH PANEL CL IN MECH/ELEC ROOM ON2ND FLOOR.

8. CONNECT LIGHTING ON NORMAL BRANCH POWER TOEXISTING HOMERUN (NL-6 PRE-EXISTING DRAWINGS)AND CONTROLS.

9. CONNECT TO EXISTING CRITICAL BRANCH LIGHTINGCIRCUIT (CL-2 PER EXISTING DRAWINGS) ANDCONTROLS.

FLAG NOTES:#

Scale:

1 ELECTRICAL LIGHTING PLAN1/8"=1'-0"

Scale:

2 ELECTRICAL LIGHTING PLAN1/8"=1'-0"

Page 21: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

JJ

CP

NP

NP1

TTB(E)

3 3

CP-66+42"

CP-68+42"

+42"

C

C

C

C

C

C

2

C

C

C

+78"

+42"

LSL

4

CP-65+42"

5 TYPICAL THISROOM

(E)(E)

(E)

(E)

(E) (E)(E)

6

CP-64+42"

CP

-63

CP

-63

CP

-65

CP-66

CP-68

CP-55

CP-55

NP-78 NP-78

NP-78

NP-76

NP

-78

NP

-76

NP-76

NP-76

NP-74

NP-75

NP-75

NP-75

NP-75

NP-74

NP-74

C

CP-51CP-49

CP-41

CP-41

NP-73

CP-49

CP-50

CP-42

CP-42CP-46

CP-46

CP-58

CP-58

CP-57 CP-57

CP-59 CP-59

CP-61

CP-64

NP-21

NP-66

NP-23

NP-25

NP-66

NP-66

NP-84

NP-51

NP-53NP-84

NP-84

NP-73

NP-73

NP-73

NP-73

NP-59

NP1-31

NP1-31

NP1-31

NP1-31

NP1-31

NP1-33

NP1-33NP1-33

NP1-33

NP1-35

NP1-35NP1-35

CP-60

NP1-37

NP1-37

NP1-37

NP1-37

NP1-34

NP1-34

NP1-34

NP1-34

NP1-36

NP1-36

NP1-36

NP1-36NP1-38NP1-38

NP1-40

NP1-40

NP1-40

NP1-40

NP1-42NP1-42

NP-64

NP-64

NP-64

ELEV.

MED.GAS

STAIRX1-SX

STAIR1067

EXTERIOR COURTYARD - NO PUBLIC ACCESS

OFFICE1031

EXAM1032

EXAM1033

EXAM1034

EXAM1036

EXAM1037

EXAM1038

EXAM1039

EXAM1041

CORRIDOR1029

TRIAGE/ASSESMENT

1019

RECEPTION/ASSESMENT

1018

SECURITY1018A

WAITING1013

WHEELCHAIRSTORAGE

1002

QUIETWAITING

1011

ENTRYVESTIBULE

1001

WOMEN1008

MEN1009

HSKP1004

VENDING1007

CORRIDOR1005

CORRIDOR1161

CONSULT1024

MULTI-PATIENTEXAM/HOLDING

1026

PATIENT/SPECIMENTOILET

1022

CORRIDOR1021

CORRIDOR1020

FAST TRACK1023

MEDICATION/SUPPLY

1014

NUTRITION1016

FAST TRACK1023B

FAST TRACK1023C

FAST TRACK1023A

FAST TRACK1023D FAST TRACK

1023EFAST TRACK

1023F

FAST TRACK1023G

TREATMENT1078

CONTROL1082

TREATMENT1081

ALCOVE1076

CLEAN SUPPLY/EQUIPMENT

1074

TREATMENT1077

PATIENTTOILET

1079

X-RAY1083

COMM.1084

CORRIDOR1028

ELEC.1085

ALCOVE1088A

ALCOVE1088B

ALCOVE1088C

CORRIDOR1087

MEDICATION1093

NOURISHMENT1094

PYXIS1098

STAFFTOILET

1097

PATIENTTOILET

1098

SOILEDUTILITY

1099NURSESTATION

1092

CORRIDOR1091

CRASH CART1111

CORRIDOR1109

ALCOVE1108

EXAM1101

EXAM1106

OBEXAM1102

OBEXAM1107

PATIENTTLT./SHWR

1103

PATIENTTOILET11034

CORRIDOR1027

EXAM1042

EXAM1043

EXAM1044

ISOLATION1046

ANTE1048FIRE

1047

NURSESTATION

1073

CORRIDOR1072

EXAM1049

EXAM1051

WHEELCHAIRSTORAGE

1052

VESTIBULE1053

DECONSHOWER

1054

EMSCLOSET

1056

PSYCH.1057

TRAUMA1058

TRAUMA1059

CORRIDOR1071

HSKP1061

ELEV.EQUIP.

1068

ELEV.LOBBY1064

ALCOVE1062

RESULTSWAITING

1117

OFFICE1123

STAFFLOCKERS

1124

OFFICE1123 STAFF

LOUNGE1152

OFFICE1112

OFFICE1113

TLT./SHOWER1114

CORRIDOR1134

CORRIDOR1127

+30"

NP1-40+86"

NP-64+86"

NP-78+86"

NP-76+86"

NP-74+86"

NP-75+86"

NP-59

+78"

+78"

+78"

+78"NP-73

NP1-36+86"

NP1-38+86"

NP1-42+86"

C

C

NP-46NP-40

NP-40

NP-42NP-38

10

CP-71

CP-71

LSPJNP-45

9

8

J

9

NP-43

J

9

NP-41

LSP-11 LSP-11

TU14

S

T

T T

T

T

T

T

T

T

T

T

T

TU18

S

TU19

S

TU17

S

TU06

S

TU06

S

TU06

S

TU03

S

TU07

S

TU16

S

TU19

S

TU18

S

TU02

STU10

S TU10

S

TU19

ST

TU21

S TU17

S

TU17

STU15

S

TU19

S

TU24

S

TU05

STU22

S

TU08

S

TU16

S

TU16

S

TU24

S

TU06

S

TU22

S

EF1

S

EF2

S

(ON ROOF)

(ON ROOF)

J

1

CP-70

+30"+30"

NP1-34+86"

+30"

+30"

+30"

+30"NP1-36

NP1-42+30"+30"

+30"NP1-38+30"

+30"

NP1-38+30"

+30"

+30" +30"

+86"

+30"

+30"

CP-50

+30"

+30"

+30"

NP-64+30"

+30"

+30"

+30"+30"

C

+60"

CNP-66

C

+42"

+42"

+42"

NP1-42

ME

4

ME-12

ME-12

ME-12

ME-12

ME-12

ME-12

ME-12ME-12

ME-12

ME-12

ME-12

ME-12

ME-12 ME-12 ME-12 ME-12 ME-12

ME-12ME-12

ME-22

ME-22

ME-22

ME-22 ME-22

ME-22

ME-22

ME-22ME-22

ME-22

ME-22

8

8

8

8 8

8

CP-51

CP-71

NP-71+86"

CP-73

JCP-70

JCP-70

1

JCP-70

1

J CP-70

1

JCP-63

1

J

11

ME-19

J CP-72

1

JCP-72

1

JCP-72

JCP-72

1

1

7

TOILET

PASSAGEWAYX1XX

BEDSTORAGE

X1XX

EXAM #1X1XX

XRAYREADING

X1XX

PHYSICIAN'SREADING RM.

X1XX

CORRIDOR

J

J

1

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

ELECTRICALPOWER PLAN

E1-03

A. ALL DEVICES, WIRING, ETC. IN PATIENT CARE AREASSHALL COMPLY WITH ARTICLE NEC-517. PROVIDE REDRECEPTACLE OUTLETS FOR EMERGENCY BRANCHCIRCUITS.

B. VERIFY EXACT LOCATION AND HEIGHT OF ALL DEVICESWITH ARCHITECT PRIOR TO ROUGH-IN.

C. THE NUMBER NEXT TO ELECTRICAL DEVICESINDICATES BRANCH CIRCUIT.

D. NEW RECEPTACLES IN WAITING AREAS, CORRIDORS,AND OFFICES SHALL BE TAMPER- RESISTANT.

E. THIS RENOVATION PROJECT IS TO BE EXECUTED INMULTIPLE PHASES. SEE ARCHITECTURAL PLANS FORPROJECT PHASING.

NOTES:

1. CONNECT DOOR POWER SUPPLY (120V).

2. COORDINATE RECEPTACLE LOCATION WITHDRINKING FOUNTAIN SHOP DRAWINGS. PROVIDEGFCI CIRCUIT BREAKER IN PANEL NP.

3. CONNECT EXISTING ENTRY DOOR MOTOR POWER TOLIFE SAFETY BRANCH, CIRCUIT VACATED DURINGDEMOLITION.

4. APPROXIMATE LOCATION OF LIFE SAFETY ANDEQUIPMENT BRANCH PANELS IN THE MECH/ELECROOM ON SECOND FLOOR.

5. HOSPITAL GRADE TAMPER PROOF RECEPTACLE.

6. REPLACE (E) RECEPTACLE WITH GFCI TYPE.DOWNSTREAM GFI PROTECTION IS NOT REQUIRED.

7. CONNECT TO NEAREST RECEPTACLE CIRCUIT ONNORMAL POWER BRANCH. VERIFY TOTAL NUMBEROF RECEPTACLES ON CIRCUIT IS LESS THAN (8).

8. VERIFY LOCATION OF COMPUTER STATION WITHARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN.

9. CONNECT RECESSED HAND DRYER PERMANUFACTURER'S DIRECTION.

10. INSTALL RECEPTACLE FOR UNDER COUNTERREFRIGERATOR BELOW SINK. GROMMET CASEWORKFOR CORD PASS-THRU.

11. PROVIDE DEDICATED 120V CIRCUIT FROMEQUIPMENT BRANCH PANEL 'ME' FOR HVACCONTROL PANEL. COORDINATE LOCATION WITHCONTROLS CONTRACTOR.

FLAG NOTES:#

Scale:

1 ELECTRICAL POWER PLAN1/8"=1'-0"

Scale:

2 ELECTRICAL POWER PLAN1/8"=1'-0"

Page 22: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

D

SED

SE

SE

SE

T

SE

SE

SE

SE

SE

SE SE SE

CR

CR

CR

CR

CR

CR

CR

CR

CR

1

CR

360°

360°

J

4

2

360°

360°

3

3

ELEV.

MED.GAS

STAIRX1-SX

STAIR1067

EXTERIOR COURTYARD - NO PUBLIC ACCESS

TELE.

OFFICE1031

EXAM1032

EXAM1033

EXAM1034

EXAM1036

EXAM1037

EXAM1038

EXAM1039

EXAM1041

CORRIDOR1029

TRIAGE/ASSESMENT

1019

RECEPTION/ASSESMENT

1018

SECURITY1018A

WAITING1013

WHEELCHAIRSTORAGE

1002

QUIETWAITING

1011

ENTRYVESTIBULE

1001

WOMEN1008

MEN1009

HSKP1004

VENDING1007

CORRIDOR1005

CORRIDOR1161

CONSULT1024

MULTI-PATIENTEXAM/HOLDING

1026

PATIENT/SPECIMENTOILET

1022

CORRIDOR1021

CORRIDOR1020

FAST TRACK1023

MEDICATION/SUPPLY

1014

NUTRITION1016

FAST TRACK1023B

FAST TRACK1023C

FAST TRACK1023A

FAST TRACK1023D

FAST TRACK1023E

FAST TRACK1023F

FAST TRACK1023G

TREATMENT1078

CONTROL1082

TREATMENT1081

ALCOVE1076

CLEAN SUPPLY/EQUIPMENT

1074

TREATMENT1077

PATIENTTOILET

1079

X-RAY1083

COMM.1084

CORRIDOR1028

ELEC.1085

ALCOVE1088A

ALCOVE1088B

ALCOVE1088C

CORRIDOR1087

MEDICATION1093

NOURISHMENT1094

PYXIS1098

STAFFTOILET

1097

PATIENTTOILET

1098

SOILEDUTILITY

1099NURSESTATION

1092

CORRIDOR1091

CRASH CART1111

CORRIDOR1109

ALCOVE1108

EXAM1101

EXAM1106

OBEXAM1102

OBEXAM1107

PATIENTTLT./SHWR

1103

PATIENTTOILET11034

CORRIDOR1027

EXAM1042

EXAM1043

EXAM1044

ISOLATION1046

ANTE1048FIRE

1047

NURSESTATION

1073

CORRIDOR1072

EXAM1049

EXAM1051

WHEELCHAIRSTORAGE

1052

VESTIBULE1053

DECONSHOWER

1054

EMSCLOSET

1056

PSYCH.1057

TRAUMA1058

TRAUMA1059

CORRIDOR1071

HSKP1061

ELEV.EQUIP.

1068

ELEV.LOBBY1064

ALCOVE1062

RESULTSWAITING

1117

OFFICE1123

STAFFLOCKERS

1124

OFFICE1123 STAFF

LOUNGE1152

OFFICE1112

OFFICE1113

TLT./SHOWER1114

CORRIDOR1134

CORRIDOR1127

CR

+30"

TV+86"

TV+86"

TV+86"

TV+86"

TV+86"

TV+86"TV

+86"

TV

+86"

TV+86"

TV+86"

TV+86"

TV

+78"

TV+78"

TV+78"

TV+78"

5

CR

TV+78"

+30"

+30"

+30"+30"

J4

CR

+36"

+36"

+36"+36"+36"

+36"

+36"

+30"

+30"

+30"+30"+30"

+30"

+30"

5

5

5 5 5

5

SM

LS

SM

LS

SM

LS

SM

LS

SM

LS

LM

LS

LM

LS

W

SM

LS

SM

LS

S

S

S

S

S

S

S

S

S

S

S

S

3

TV

TV

+86"

+86"

S

6

FAC

P

7

EXISTING TTB

EXISTING RACK

+84"

+84"

+84"

+84"

+84" +84"

+84"

8

8

8

ELEC.X1XXTOILET

X1XXX1XX

TOILET

PASSAGEWAYX1XX

BEDSTORAGE

X1XX

EXAM #1X1XX

XRAYREADING

X1XX

PHYSICIAN'SREADING RM.

X1XX

SECURITYX1XX

EXISTINGELEVATOR 4

X-EL4

CORRIDORJ

J

4

CR

SM

LSS

CR

SM

LS

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

ELECTRICALSPECIAL SYSTEMSPLAN

E1-04

A. VERIFY EXACT LOCATION AND HEIGHT OF ALL DEVICESWITH ARCHITECT PRIOR TO ROUGH-IN.

B. ALL DEVICES, WIRING, ETC. IN PATIENT CARE AREASSHALL COMPLY WITH NEC ARTICLE 517.

C. VOICE/DATA, CATV, ACCESS CONTROL, AND CCTVDEVICES, CABLING, TERMINATIONS, ANDCONNECTIONS SHALL BE BY THE OWNER'S ON-CALLCONTRACTOR(S) AND SHALL CONFORM WITH LOCALSTANDARDS. ELECTRICAL CONTRACTOR SHALLPROVIDE AND INSTALL ALL OUTLET BOXES ANDPATHWAYS.

D. VOICE/DATA, CATV, SECURITY, AND CCTV SHALL BEROUTED VIA CONDUIT FROM OUTLET BOX TO ABOVEACCESSIBLE CEILING. CABLE SHALL BE ROUTED VIAJ-HOOKS, ARLINGTON LOOPS, OR SIMILAR CABLEMANAGEMENT SPACED NO GREATER THAN 5'-0"ABOVE ACCESSIBLE CEILINGS FROM OUTLET CONDUITTO TELECOM ROOM. E.C. SHALL PROVIDECOMMUNICATIONS PATHWAYS; COORDINATE ROUTINGWITH OWNER'S IT CONTRACTOR.

E. CONNECT NEW FIRE ALARM DEVICES TO EXISTINGSYSTEM.

F. CONNECT NEW SPEAKERS TO EXISTINGINTERCOM/PAGING SYSTEM.

G. NEW NURSE CALL SYSTEM DEVICES AND CABLINGSHALL BE BY THE OWNER'S ON-CALL CONTRACTOR(S).THE NEW DEVICES SHALL BE CONNECTED TO THEEXISTING NURSE CALL SYSTEM.

H. THIS RENOVATION PROJECT IS TO BE EXECUTED INMULTIPLE PHASES. SEE ARCHITECTURAL PLANS FORPROJECT PHASING.

NOTES:

1. PUSH BUTTON FOR REMOTE BUZZ-IN OF DOOR.

2. INSTALL ON MULLION.

3. REPLACE EXISTING CAMERAS WITH NEW.

4. MOTORIZED DOOR TO OPERATE UPON CARDREADER.

5. VERIFY LOCATION AT COMPUTER STATION WITHARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN.

6. VOICE/DATA, CATV, AND CCTV CABLING RUN BACKTO THIS ROOM. OWNER'S ON-CALL CONTRACTORSHALL PROVIDE ADDITIONAL EQUIPMENT ASNECESSARY TO ACCOMMODATE NEW DEVICES.

7. EXISTING FIRE ALARM CABINET AND POWERSUPPLIES.

8. CONNECT MAGNETIC HOLD OPENS TO FIRE ALARMSYSTEM TO RELEASE UPON ALARM.

FLAG NOTES:#

Scale:

1 ELECTRICAL SPECIAL SYSTEMS PLAN1/8"=1'-0"

Scale:

2 ELECTRICAL SPECIAL SYSTEMS PLAN1/8"=1'-0"

Page 23: Physical: 48 C.R. 25O/ STE. 3/ DURANGO · pressure - temp. tap air vent pipe anchor flexible connector pipe expansion joint pipe union double check backflow preventer ... cc cdbbc

18"

64"

78"

90"

48"

ELECTRICAL DEVICES

96"

WALL-MOUNTOC

DLVS

CBC

TSTC

120"MAX.

TOP OF DEVICE

9'-0"+ CEILING

8'-0" CEILING

TOP OF CABINET

TOP OF CABINET

TOP OF DEVICE

CL OF DEVICE

18"

TOP OF DEVICE

48"

MINIMUM, TOP OF DEVICE

BOTTOM OF DEVICE

TOP OF CABINET

TOP OF CABINET90"

6"MIN.

96"

NOTES:1. IF MOUNTING HEIGHT OF DEVICES INDICATED HERE IS IN

CONFLICT WITH ADA REQUIREMENTS DUE TO INSTALLATIONDETAIL, ADA DIMENSIONS SHALL GOVERN.

2. REFERENCE ARCHITECTURAL INTERIOR ELEVATIONS.LOCATIONS SHOWN ON INTERIOR ELEVATIONS SHALLSUPERCEDE LOCATIONS SHOWN HERE, UNLESS LOCATIONSSHOWN ON INTERIOR ELEVATIONS ARE NOT CODE COMPLIANT.

TYPICAL DEVICE MOUNTING HEIGHTS

I

I

CR

FINISHED FLOOR

48"

84"

FINISHED CEILING

90"

78"

64"

24"

NO SCALE

I

WALL-MTDCABINET

CPUAPSACP

KCVCTCK

MAVTV

SANN

FACP

SH

SH

F

80"MIN.

96"MAX.

120"MAX.

CL OF DEVICE

CL OF DEVICE

TOP OF DEVICE

TOP OF CABINET

8'-0" CEILING

9'-0"+ CEILING

CL OF DEVICE

LOW VOLTAGE DEVICES FIRE ALARM DEVICES

B

A

T568B STANDARD8-POSITION / 8-CONDUCTOR DEVICE WIRING DIAGRAM

1

1

PAIR 2

PAIR 2

4

5

1

2

PIN

MODULAR CONNECTOR PINOUTS

8764 532

72 3 54 6

PAIR 1PAIR 3

PAIR 3PAIR 1

8

PAIR 4

PAIR 4

2

3

4

1

PAIR COLOR CODE

2

3

4

1

3

6

7

8

BLUE

WHITE/BLUE

WHITE/ORANGE

ORANGE

WHITE/GREEN

GREEN

WHITE/BROWN

BROWN

NO SCALE

OUTLET PATHWAY DIAGRAM - DRYWALL PARTITIONNO SCALE

OUTLET ASSEMBLY.

CONDUIT STUBBED ABOVEACCESSIBLE CEILING.

6" RADIUS MINIMUMCONDUIT SWEEP.

FINISHED FLOOR.

WALL SURFACE (GYP BD).

ACCESSIBLE CEILING.

PROVIDE INSULATED BUSHINGON END OF CONDUIT.

ADHERE TO ONE OF THE FOLLOWINGMETHODS FOR ROUTING CONDUIT FROMOUTLET:

1. STUB INTO SPACE ABOVEACCESSIBLE CEILING;

2. ROUTE TO NEAREST ARLINGTONLOOP PATHWAY;

3. ROUTE TO SERVING IDF/MDF.

CCOMMUNICATIONS OUTLET BOX DIAGRAM

THREADED NIPPLE WITHPROTECTIVE BUSHING.

COMMUNICATIONS CABLING.

CONDUIT PATHWAY,UP ORDOWN FROM OUTLET BOX.

SINGLE DEVICE MUD-RING.

ELECTRICAL OUTLET BOX;4-11/16" x 4-11/16" x 2-1/2".TYPICAL UNO.

NO SCALE

D

NOTES:1. PROVIDE LEVEL 1 ADMINISTRATION

PER ANSI/TIA/EIA-606.

2. PROVIDE LABEL ON FRONT OFFACEPLATE.

3. PROVIDE VOICE AND DATA PORTSAS INDICATED ON THE PLANS.PROVIDE ONLY ONE DATA PORT IFNOT INDICATED ON PLANS.

4PR CAT5E UTP CABLE(WHITE JACKET).

MODULAR COMMUNICATIONSFACEPLATE, BEIGE COLOR.

MODULAR CAT5E CONNECTOR(IVORY). TERMINATE T568B.

1"C.

MODULAR CAT5ECONNECTOR(DARK RED).TERMINATET568B.

4PR CAT5E UTP CABLE(BLUE JACKET).

VOICE/DATA OUTLET DIAGRAMNO SCALE

BLANK PORTFILLER. COLORTO MATCHFACEPLATE.

6"x6"x4" JUNCTION BOX, ABOVECEILING.

CARD READER, ONUNSECURED SIDE OFDOOR. 4"x4" OUTLET BOXWITH SINGLE-GANGMUDRING.

ELECTRIFIED LOCKSET IN DOOR,-OR- ELECTRONIC LATCHRETRACTION MECHANISM. SEEDOOR HARDWARE SCHEDULE.

DOOR POSITION SWITCH,IN DOOR FRAME.

1"C

.

3/4"

C.

1"C

.

STUB CONDUIT IN ACCESSIBLECEILING SPACE. ROUTE CABLING TOCONTROL PANELS VIA ARLINGTONLOOP PATHWAYS.

DOOR POWER SUPPLY, ABOVECEILING.

3/4"C.

120V

3/4"

C.

ELECTRIC POWERTRANSFER.

NOTE:ON ELECTRIC SLIDING DOORS, OMIT THEPOWER TRANSFER SWITCH AND TAKE ANINPUT FROM ACCESS CONTROL PANEL TOTRIGGER DOOR OPERATION.

EELECTRONIC ACCESS DOOR CONTROLNO SCALE

SAN JUAN REGIONALMEDICAL CENTER

Emergency Department Renovation

Mail: Phone:

48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774

RMKM ARCHITECTURE, P.C.

ALBUQUERQUE | AVON | DENVER | FORT COLLINS

303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016

ELECTRICALDIAGRAMS

E5-01