Upload
lambao
View
214
Download
1
Embed Size (px)
Citation preview
P O W E R G E N y S Y S P R O J E C T E X P E R I E N C E I N F O R M A T I O N - D I S T R I B U T E D G E N E R A T I O N
File: PI-93010 - Temiskaming Hospital Cogen 01.DOC 93010 - Page 1 of 10
Above: Aerial view of the Temiskaming Hospital, New Liskeard, Ontario. Project Description: 1st Hospital Cogeneration System in Ontario (1993)
In 1993 Marsh Energy Inc. was awarded a turnkey contract by the Temiskaming Hospital in New Liskeard to design, build, operate and maintain the 1st hospital cogeneration system in Ontario utilizing a natural gas reciprocating engine-generator.
The system prime-mover is a Caterpillar Model 3406 natural gas fuelled reciprocating engine-generator set, producing 225 kWe of load displacement electricity (no export), approximately 360 lbs/hr of steam at 125 psig from the exhaust heat recovery steam generator, and about 250 kWth of hot water from the oil cooler and jacket water cooling circuits. Heat recovery was not incorporated for the aftercooler circuit.
Under normal operation the plant is unmanned.
A lack of space inside the existing boiler plant facility required the engine-generator set to be located at ground level just outside and adjacent the boiler plant wall (see photos: right & below/left), in an outdoor acoustically treated enclosure, (see next page).
The fire-tube heat recovery steam generator (HRSG) was installed inside the boiler plant on a steel stand directly above large condenser water pumps. Engine exhaust was piped to the HRSG through openings in the boiler room exterior wall, (see photos below).
Temiskaming Hospital New Liskeard, Ontario Service Provider: Marsh Energy Inc., Burlington, Ontario.
Services: ( Provided by: Vito Mike Casola, P.Eng., Engineering Manager, Marsh Energy Inc. ) • Verification of Project Feasibility / Economic Analysis, • Detailed Engineering Design and Drafting, • Equipment Procurement for all Major and Auxiliary Equipment, • Preparation of Contract Documents and Contract Administration, • Project Management and Construction Supervision, • Startup / Commissioning and Operation / Maintenance, • Monthly Operational Reports.
Above: View of Caterpillar 3406 engine-generator set on concrete pad.
Above: View of genset and exhaust piping to/from HRSG in boiler room.
Above: View of HRSG inside boiler room, mounted above condenser pumps.
CAT 3406
GENSET 225 kWe
HRSG (125 psig)
Boiler Plant
Boiler Plant
Temiskaming Hospital
Typ. exhaust piping support bracket Wall opening for JW piping to HX-1
Wall opening for electrical conduits
Vibration Isolation Springs
Concrete Inertia
Pad
Exhaust Outlet
Steel Stand
Wall opening for exhaust piping to HRSG
P O W E R G E N y S Y S P R O J E C T E X P E R I E N C E I N F O R M A T I O N - D I S T R I B U T E D G E N E R A T I O N
File: PI-93010 - Temiskaming Hospital Cogen 02.DOC 93010 - Page 2 of 14
View of outdoor enclosure, muffler, heat dump radiator, and piping.
Project Description: 1st Hospital Cogeneration System in Ontario (1993), cont… Outdoor Acoustic Enclosure
Due to a lack of space in the boiler plant the engine-generator and other auxiliary equipment had to be installed in an outdoor acoustically treated enclosure adjacent the boiler room.
Engine exhaust was treated with a muffler/silencer mounted on the roof of the enclosure, piped to the HRSG in the boiler room and exhausted to
Temiskaming Hospital New Liskeard, Ontario Service Provider: Marsh Energy Inc., Burlington, Ontario.
atmosphere several feet above the building roof level. The piping was anchored at the wall opening and allowed to expand on wall mounted support brackets equipped with slide guides. A universal tied expansion joint connected to the muffler compensated for all expansion during operation. The stack, supported near the top of the building, was able to expand at the lower 90° elbow. All piping was sloped back to the HRSG where any condensate automatically drains via a float trap.
The jacket water (JW) cooling circuit was connected (smaller pipes) to a plate-frame heat exchanger installed on the outside wall inside the boiler room and to the heat dump radiator on the enclosure roof.
Outdoor acoustic enclosure, radiator, muffler, and piping: Center-Right: Muffler and heat dump radiator mounted on roof of enclosure. Center-Left: Exhaust to HRSG / atmosphere; JW circuit to HX-1 in boiler room.
Outdoor acoustic enclosure, radiator, muffler, and piping: Center: Heat dump radiator mounted on roof of enclosure. Center-Left: Natural gas supply line and regulator; Ventilation air inlet hood.
Acoustic Enclosure
Heat Dump Radiator
Muffler
Exhaust Stack to Atmosphere
Ventilation Air Inlet Hood /
Silencer
Heat Dump Radiator
JW Circuit Coil Aftercooler Circuit Coil
Acoustic Enclosure
Exhaust Stack to Atmosphere
Exhaust Stack to Atmosphere
Heat Dump Radiator
Acoustic Enclosure
JW piping to Heat Exchanger
Exhaust piping (genset to HRSG)
Supplemental Muffler / Silencer
Universal tied expansion joint
Ventilation Air Outlet Hood /
Silencer
Exhaust piping to HRSG JW
to HX
Exhaust piping (HRSG to stack)
Muffler / Silencer
Concrete Inertia Pad
Gas Supply / Regulator
Universal tied expansion joint in exhaust piping (engine to HRSG)
Elec. conduits (enclosure to boiler room)Typ. wall mounted pipe support bracket
Jacket Water piping (Genset to HX)
P O W E R G E N y S Y S P R O J E C T E X P E R I E N C E I N F O R M A T I O N - D I S T R I B U T E D G E N E R A T I O N
File: PI-93010 - Temiskaming Hospital Cogen 03.DOC 93010 - Page 3 of 14
Temiskaming Hospital New Liskeard, Ontario
Service Provider: Marsh Energy Inc., Burlington, Ontario.
Project Description: 1st Hospital Cogeneration System in Ontario (1993), cont…
Outdoor Acoustic Enclosure - Inside
The outdoor acoustic enclosure houses the prime-mover (Caterpillar 3406 genset) and other auxiliary equipment.
Mounted on the enclosure roof is the heat dump radiator, and muffler connected to a universal tied expansion joint, which compensates for all expansion of the exhaust piping to the HRSG during operation (photo, right).
The auxiliary equipment inside the enclosure includes the electrical control panel and utility interface / sensing panel, a genset battery charger, the neutral grounding resistor and electrical unit heater, a ventilation air fan, dampers and silencers, lube oil filter, jacket water (JW) cooling circuit circulation pump, JW thermostatic 3-way mixing valve and balance valves, and the JW and aftercooler circuit piping from the genset to the radiator, (photos, below left and right).
View of acoustic enclosure entrance and genset / auxiliary equipment inside
View inside outdoor acoustic enclosure. Left: Insulated turbocharger and exhaust pipe through enclosure roof. Center-Right: JW thermostatic mixing valve, ventilation fan & motorized damper.
View inside outdoor acoustic enclosure. Center-top: Ventilation air fan and motorized damper, JW balance valves. Center-bottom: Lube oil filter, JW circulation pump.
Engine Exhaust Utility Interface / Sensing Panel Caterpillar 3406 Genset
Jacket Water Coil
Aftercooler Coil
Universal Tied Expansion Joint Muffler
Expansion Tanks
Acoustic Enclosure Entrance Door
Engine Exhaust
Ventilation Air FanMotorized Damper Utility Interface
/ Sensing Panel
Battery Charger
Lube Oil Filter
Thermostatic Mixing Valve
Genset
Ventilation Air Fan
JW Circ. Pump
Genset
P O W E R G E N y S Y S P R O J E C T E X P E R I E N C E I N F O R M A T I O N - D I S T R I B U T E D G E N E R A T I O N
File: PI-93010 - Temiskaming Hospital Cogen 04.DOC 93010 - Page 4 of 14
Temiskaming Hospital New Liskeard, Ontario
Project Description:
1st Hospital Cogeneration System in Ontario (1993), cont…
Outdoor Acoustic Enclosure - Inside, cont…
Service Provider: Marsh Energy Inc., Burlington, Ontario.
Inside enclosure: JW thermostatic 3-way mixing valve, ventilation fan.
Inside enclosure: Ventilation fan, JW circuit balance valves, electrical cables.
Inside enclosure: Jacket Water Circulation Pump. Inside enclosure: Startup & Commissioning - Balancing JW cooling circuit.
Inside enclosure: Utility interface/sensing panel, genset power and control panel. Inside enclosure: Neutral grounding resistor, ventilation inlet damper, gas train.
JW Thermostatic 3-Way Mixing Valve
Motorized Damper
Utility Interface / Sensing Panel
Natural Gas Train
Genset
Variable Speed
VentilationFan
JW Circuit Balance Valves
JW Circ. Pump
Neutral GroundingResistor
Neutral Grounding Resistor
Acoustic Enclosure Entrance
Door
JW Circuit Balance Valves
Power cables & control wiring
to building
Power Disconnect Switches
Aftercooler circuit piping
Power cables in cable tray from control panel to electrical room
Ventilation Inlet Air Motorized Damper
Normally Closed Manual Bypass
JW from HX-1 JW from Rad
Genset
Genset Power & Control Panel
Electric Unit
Heater
Power cables from generator to control panel
JW to
HX-1
JW to
Rad
JW from Rad
Variable Speed
VentilationFan
Power Disconnect Switches
JW from HX-1
Strainer
JW to
Rad
JW to
HX-1
P O W E R G E N y S Y S P R O J E C T E X P E R I E N C E I N F O R M A T I O N - D I S T R I B U T E D G E N E R A T I O N
File: PI-93010 - Temiskaming Hospital Cogen 05.DOC 93010 - Page 5 of 14
Temiskaming Hospital New Liskeard, Ontario
Service Provider: Marsh Energy Inc., Burlington, Ontario.
Project Description: 1st Hospital Cogeneration System in Ontario (1993), cont…
Outdoor Acoustic Enclosure - Inside, cont…
Electrical equipment located inside the enclosure includes the generator power and control panel (see photos right), the utility interface / sensing panel (UIP), neutral grounding resistor and genset battery charger (see photos bottom-left and bottom-right). The UIP includes double (redundant) utility grade protection relays.
The generator power and control panel includes annunciation lights to indicate trouble and warnings. Also included is a generator control switch and control dials / buttons (see photo right-middle). The genset control switch allows for manual and auto operation. Other dials and buttons (left to right in photo) include a voltage adjust dial, an alarm accept button, an emergency stop button, a lamp test button, a frequency adjust dial, and a load set dial.
Genset Power & Control Panel Generator Motorized Breaker: 52-G
Inside enclosure: Utility interface/sensing panel, Battery charger
Inside enclosure: Battery charger
Battery Charger
Battery Charger
Genset Power & Control Panel
Generator Breaker
Annunciation Lights
Genset Synchronization
Annunciation lights
Engine control switches and buttons
Utility Interface / Sensing Panel
P O W E R G E N y S Y S P R O J E C T E X P E R I E N C E I N F O R M A T I O N - D I S T R I B U T E D G E N E R A T I O N
File: PI-93010 - Temiskaming Hospital Cogen 06.DOC 93010 - Page 6 of 14
Temiskaming Hospital New Liskeard, Ontario
Service Provider: Marsh Energy Inc., Burlington, Ontario.
Project Description: 1st Hospital Cogeneration System in Ontario (1993), cont…
Jacket Water / Oil Cooler Circuit Heat Recovery: Boiler Room
The prime-mover (Caterpillar 3406 genset) Jacket Water (JW) and Oil Cooler are combined in a single cooling circuit. This JW cooling circuit was connected to a plate and frame heat exchanger (HX-1), inside the boiler room on the outdoor wall adjacent to the outdoor enclosure, to recover this thermal energy in the form of hot water (photos, right).
The JW cooling circuit was also connected in parallel with the heat dump radiator, mounted on the roof of the enclosure. The radiator was sized for 100% cooling of the both JW and Aftercooler circuits.
The other side of HX-1 is connected to the building’s hot water heating (HWH) system. A circulation pump draws HWH from a branch line connected to the HWH main return line (upstream of the heating boilers) to HX-1 where it is heated by the JW circuit and returns it back to the same heating return line (downstream of the extraction point).
JW Heat Recovery: Heat Exchanger (HX-1), HWH to/from HX-1/Boiler Return.
HWH Circulation Pump, Turbine Flow Meter with normally closed bypass.
Cogeneration system hot water heat recovery tie-in to hot water boiler return.
JW HX-1, JW to/from genset, HWH to/from HX-1, BTU meter.
Genset
JW from HX-1 to genset JW from genset to HX-1
Strainer
JW Cooling Circuit
Heat Exchanger
HX-1
Circ. Pump
Normally Closed Manual Bypass
Hot Water Heating (HWH) Boiler Return Line to HX-1 HX-1 to Boiler Return Line Flow Meter to be installed
Auto Air Vent (AAV)
Turbine Flow Meter
HWH: HX-1 to
Boiler Return
HWH: Boiler Return to HX-1
HWH Circ.
Pump
JW: HX-1 to gensetJW: genset to HX-1
Heat Exchanger
HX-1
Manual Bypass
RTD
RTD
BTU Meter
HWH:Boiler Return to HX
HWH:HX to Boiler Return
Circ. Pump
Strainer
BoilerFeedwaterto HRSG
Temp. Gauge
HWH:from HX-1
HWH:Boiler Return to HX-1
HWH: HX-2 to Boiler Return
HWH:HX-1
to HX-2
HWH Boiler Return
Manual Bypass
Hot Water Heating Boiler
B-1
JW: HX-1 to genset
JW: genset
to HX-1
BlowdownLine
TurbineFlow Meter
P O W E R G E N y S Y S P R O J E C T E X P E R I E N C E I N F O R M A T I O N - D I S T R I B U T E D G E N E R A T I O N
File: PI-93010 - Temiskaming Hospital Cogen 07.DOC 93010 - Page 7 of 14
Temiskaming Hospital New Liskeard, Ontario
Service Provider: Marsh Energy Inc., Burlington, Ontario.
Project Description: 1st Hospital Cogeneration System in Ontario (1993), cont…
JW thermal energy transferred to Domestic Hot Water: Boiler Room
The previous page outlines how thermal energy recovered from the cogeneration system JW circuit is transferred to the building’s hot water heating (HWH) system via HX-1.
Part of this thermal energy is diverted to a secondary shell-and-tube heat exchanger (HX-2) (photos, middle left/right), via a branch HWH circuit (photos, bottom-left, middle-right) where it is transferred to heat domestic water, stored in a new primary storage tank (photos, top-right, middle-left).
A new circulation pump (photo, bottom-right), circulates domestic water between an existing domestic hot water storage tank (not shown) and the new primary DHW storage tank, with domestic water being heated by the thermal energy recovered from the cogen JW circuit via HX-2/HX-1.
Domestic Hot Water Storage Tank heated by cogen via JW HX-1 HX-2.
Domestic Hot Water Storage Tank heated by cogen via JW HX-1 HX-2.
Branch HWH circuit from HX-1 to HX-2 for heating DHW.
Cogeneration system hot water heat recovery tie-in to boiler return & HX-2.
Domestic Hot Water Circ. Pump: Existing DHW storage tank to new storage tank.
New Primary DHW Storage Tank
heated by cogen system: JW HX-1 HX-2
HX-2 to be installed on metal stand
DWH
DWH
HX-2
Thermostatic 3-way mixing valve
New PrimaryDHW Storage Tank heated by cogen:
JW HX-1 HX-2
HX-2
Thermostatic3-way mixing valve
Circuit Balance
Valve
Circuit Balance
Valve
HWH branch circuit:HX-1 HX-2 Boiler Return
Circulating Pump:Circulates domestic water between an existing DHW storage tank and the new DHW storage tank with DHW heated via HX-2.
HWH:from HX-1
HWH:Boiler Return
to HX-1
HWH Boiler Return
Hot Water Heating Boiler B-1
HWH branch: HX-2 Boiler Return
HWH branch: HX-1 HX-2
CircuitBalance
Valve
DWH
DWH
P O W E R G E N y S Y S P R O J E C T E X P E R I E N C E I N F O R M A T I O N - D I S T R I B U T E D G E N E R A T I O N
File: PI-93010 - Temiskaming Hospital Cogen 08.DOC 93010 - Page 8 of 14
Temiskaming Hospital New Liskeard, Ontario
Service Provider: Marsh Energy Inc., Burlington, Ontario.
Project Description: 1st Hospital Cogeneration System in Ontario (1993), cont…Engine Exhaust Heat Recovery via Heat Recovery Steam Generator: Thermal energy is recovered from the engine exhaust as high pressure steam. Approximately 360 lbs/hr of steam at 125 psig is generated by a Heat Recovery Steam Generator (HRSG) located inside the boiler room.
Engine Exhaust Heat Recovery Steam Generator (HRSG).
Engine Exhaust Heat Recovery Steam Generator (HRSG).
HRSG: Boiler Feedwater Line, Feedwater Valve, and Chemical Feed Line.
Foreground: HRSG Boiler Feedwater Pumps. Background: HX-1 & JW/HWH piping.
HRSG, Boiler Feedwater Line and Metering, and Blowdown Line.
HRSG Steam Supply, Backpressure Valve, and Excess Steam Blowoff.
HRSG steam supply tie-in to main steam header, HWH to/from boiler return/HX-1.
Engine Exhaust Heat Recovery
Steam Generator ( HRSG )
360 lbs/hr Steam @ 125 psig
HX-1
Feedwater Meter
Steam Boiler Feedwater Pumps
Clorius Boiler FeedwaterMagnetic Flow Meter
ExhaustINLET
ExhaustOUTLET
Engine exhaust condensate (drained through float trap)
HRSG drain
ChemicalFeed Line
HRSG 360 lbs/hr
@ 125 psig
ExhaustOUTLET
Boiler Feedwater Line to pneumatic
Feedwater Valve
Feedwater Manual Bypass
ChemicalManual Bypass
Chemical Feed Line
Water Level Control Station
Pneumatic Feedwater
Valve
Feedwater connection
To blowdown tank
Combimeter 3 VPD
Blowdown
Meter
Feedwater
Hot Water Heating Boiler
(B-3)
To blowdown tank
Feedwater
Bypass
Hot Water Heating Boiler
(B-3)
JW to HX-1
HWH: HX-1 toBoiler Return
Blowdown
HWH: Boiler Return to HX-1
HRSG
HWH: Boiler Return to HX-1
HWH: HX-1 to Boiler Return
125 psig HRSG steam tie-in to steam header Steam Header
Isolation Valve
HRSG Steam Supply
125 psig HRSG steam
supply to main steam header
Backpressure Steam Valve
(Set at 125 psig) Excess Steam Blowoff Valve
(Set at 135 psig)
Excess Steam Blowoff Outlet to atmosphere
Condensate to float trap
HRSG Steam Supply
P O W E R G E N y S Y S - P R O J E C T E X P E R I E N C E I N F O R M A T I O N - D I S T R I B U T E D G E N E R A T I O N
File: PI-93010 - Temiskaming Hospital Cogen 09.DOC 93010 - Page 9 of 14
Temiskaming Hospital New Liskeard, Ontario
Service Provider: Marsh Energy Inc., Burlington, Ontario.
Project Description: 1st Hospital Cogeneration System in Ontario (1993), cont… Drawing M-4: Outdoor Enclosure – PLAN Layout: Plan View of Outdoor Enclosure, Radiator, Exhaust Piping, HRSG, HX-1 and JW Piping.
P O W E R G E N y S Y S - P R O J E C T E X P E R I E N C E I N F O R M A T I O N - D I S T R I B U T E D G E N E R A T I O N
File: PI-93010 - Temiskaming Hospital Cogen 10.DOC 93010 - Page 10 of 14
Temiskaming Hospital New Liskeard, Ontario
Service Provider: Marsh Energy Inc., Burlington, Ontario.
Project Description: 1st Hospital Cogeneration System in Ontario (1993), cont… Drawing M-5: Outdoor Enclosure - South Elevation: Elevation View of Outdoor Enclosure, Radiator, Exhaust Piping, JW Piping and Gas Supply.
P O W E R G E N y S Y S - P R O J E C T E X P E R I E N C E I N F O R M A T I O N - D I S T R I B U T E D G E N E R A T I O N
File: PI-93010 - Temiskaming Hospital Cogen 11.DOC 93010 - Page 11 of 14
Temiskaming Hospital New Liskeard, Ontario
Service Provider: Marsh Energy Inc., Burlington, Ontario.
Project Description: 1st Hospital Cogeneration System in Ontario (1993), cont… Drawing M-6: Outdoor Enclosure – West Elevation: West Elev. of Outdoor Enclosure, Radiator, Exhaust & JW Piping, HRSG, HX-1 & Gas Line.
P O W E R G E N y S Y S - P R O J E C T E X P E R I E N C E I N F O R M A T I O N - D I S T R I B U T E D G E N E R A T I O N
File: PI-93010 - Temiskaming Hospital Cogen 12.DOC 93010 - Page 12 of 14
Temiskaming Hospital New Liskeard, Ontario
Service Provider: Marsh Energy Inc., Burlington, Ontario.
Project Description: 1st Hospital Cogeneration System in Ontario (1993), cont… Drawing M-7: Inside of Outdoor Enclosure – Layout & Elevation: Views inside enclosure: Genset, Gas Train, Circ. Pump & Piping, Vent Fan, & Elec. Panels.
P O W E R G E N y S Y S - P R O J E C T E X P E R I E N C E I N F O R M A T I O N - D I S T R I B U T E D G E N E R A T I O N
File: PI-93010 - Temiskaming Hospital Cogen 13.DOC 93010 - Page 13 of 14
Temiskaming Hospital New Liskeard, Ontario
Service Provider: Marsh Energy Inc., Burlington, Ontario.
Project Description: 1st Hospital Cogeneration System in Ontario (1993), cont… Drawing M-8: Inside of Outdoor Enclosure – Ceiling Plan & Inside Wall Elevations: Views inside enclosure: Cooling Circuit Piping & Pump, Vent Fan, & Elec. Panels & Cables.
P O W E R G E N y S Y S - P R O J E C T E X P E R I E N C E I N F O R M A T I O N - D I S T R I B U T E D G E N E R A T I O N
File: PI-93010 - Temiskaming Hospital Cogen 14.DOC 93010 - Page 14 of 14
Temiskaming Hospital New Liskeard, Ontario
Service Provider: Marsh Energy Inc., Burlington, Ontario.
Project Description: 1st Hospital Cogeneration System in Ontario (1993), cont… Drawing M-9: Inside Boiler Room – North Wall Elevation: View of HRSG, Level Control Station, Boiler Feedwater, Energy Meters, HX-1 & JW Piping.