PICV vs Manual Balancing With Dp Controller

Embed Size (px)

Citation preview

  • 7/28/2019 PICV vs Manual Balancing With Dp Controller

    1/1

    Conparison Table Between Pressure Independent Control Valve vs Manual Valve with Differential Pressure Controller

    FLOWCON

    Low head requirement with just 1 valve

    (Typically at 16/35kpa depending on index Loop)

    Pressure Independent Control Valve require at terminal only

    Lowest pump head requirement

    Higher head requirement for all balancing valve in series(Main, riser, branch and terminal)( 12-20kpa)

    + Control valve(16-35kpa) + Dp Controller(10-25kpa)

    Higher pump head requirement

    ACCURACY +/-5% (Factory Pre-set) +/-10% (Site setting)

    No time spent in calculating Cv valves

    (Least nos of valves in system)

    Installation time for just 1 valve

    No Balancing required - Self Balancing System

    Time spent in calculating Cv valves

    (Most nos of valves in system)

    Installation time for all valves = Time Consuming

    Commissioning time for all terminal units, branches, riser and mian

    Control Valve Authority can be easily sized at 50% depending on the available KV value for the control valve and

    setting on the Dp controller in the distribution loop.

    In event of a long loop with ahu and fcu, fluctuating Dp will still occur within the control loop, which will affect the

    authority and cause the controller to hunt for the setpoint

    PART LOAD

    OPERATION

    At full/part load, design flow will always be maintained with no

    overflow at all time.At full load, design flow can be maintained. But at part load, slight overflow with occur within the control loop.

    + Branch return side + Terminal

    PUMP HEAD

    +

    +

    +

    COST

    TIME

    Install at the return line with

    balancing valve at the supply

    connected with a capillary

    tube

    APPLICATION

    Just 1 Pressure Independent Control Valve at terminal

    Installation cost for just 1 valve

    No commissioning required

    Manual Balancing Valve + 2-way Control Valve(Terminal) + Manual balancing valves + DP Controller(Branches) +

    extra set of balancing valve at main, risers

    Installation cost for all the valves

    Expensive Balancing Instruments + Additional Labour to commission valves

    None (Pressure Independent Characteristic-Spacing Saving)Placed at a safe distance of

    2D - 5D on pipe

    +

    +

    +

    +

    Static Cv valve - Tedious Cv

    calculations required

    Select dPL in tables, pipe size

    , check desired Q < spec. Q.

    Only One PICV to one Terminal(FCU/AHU)

    No more additional balancing valve or dp controller require at

    main, riser or branches

    Main, riser, branch and

    terminal

    REMARKS

    VS

    +

    Tedious Cv calculations for authority sizing

    Restricted to limited CV Value

    (Control Valve often oversized; 50% Valve

    Authority

    PLUMBING

    RESTRICTIONS

    MODEL

    DEFINITION

    RETROFITTING /

    ADDENDUM

    FEATURE -

    SME/SM valve controls and balances Q at varying dP

    (Full Load & Part Load)DESCRIPTION

    Balance Q manually @

    specific constant dP

    Equipment added do not require to rebalancing as the PICV will

    adjust automatically to maintain the required flowrate.

    Allow project to run in phases without having to rebalance the

    system

    Equipment added will require rebalancing as the DP Controller only maintain constant Dp and balancing will be

    require at terminal level for individual branch

    Project running in phases will require some rebalancing of system

    OTHER

    Manual Balancing ValveDifferential Pressure

    Controller2-Way Pressure Dependent Control ValveSME / SM

    Pressure Independent Control Valve

    (Modulating Control + DP Controller + Automatic Balancing)Manual Balancing Valve

    Differential Pressure

    Controller2-Way Pressure Dependent Control Valve

    + +

    ENERGY

    SAVINGS

    1 valve --> inaccuracies, losses, head, pump head,

    motor power, overall cost, time spent, energy savings

    valves, inaccuracies, losses, head, pump head, motor power, total cost, time spent, energy

    savings

    Control Q @ specific constant dPMaintain dP constant within

    individual loop/branch

    N.A.

    SIZING

    Dynamic Variable Cv valve -- No Cv calculations required; simply

    know the Q and tune the settings

    (100% Valve Authority)

    CONTROL

    VALVE

    AUTHORITY

    Pressure Independent Control Valve Authority is always at 100%due to the in-build Dp Controller which equalize the pressure

    during variable flow in the distribution loop

    With 100% control valve authority, the output odf the controller

    for the setpoint will not be affected by fluctuating DP