27
PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003

PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 1

April 2003ICC

PILC Replacement: Getting the Lead Out

Spring ICC

Cincinnati, OH

April 30, 2003

Page 2: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 2

April 2003ICC

PILC IS GREAT!

• Low Profile• High Fault Current Capability on Shield• High Degree of Water Blocking

…So why shouldn’t you use it?

Page 3: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 3

April 2003ICC

Why the Move Away From PILC?

• Fatigue Cracks in the Lead• Oil Migration on Slopes • EPA Rulings on Lead (#1 Hazardous Material)

• Comparative Expense• Diminishing Installation Expertise

Page 4: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 4

April 2003ICC

Replacement Challenges

• Small Duct Diameters• Duct Conditions• Cable Operating Temperature• Fault Current Capability of Shield

Page 5: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 5

April 2003ICC

How to Fit Extruded Dielectric Cables Into Existing Ducts

(Without Real Design Changes)

• Reduce the cable clearance to the duct wall. (Generally recommended minimum is 1/2”)

• Reduce the thickness of the extruded jacket. (Some utilities accept a .025” thick jacket over 750 kcmil Cu 25kV Cable)

• Extrude over compact sector conductors.

Page 6: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 6

April 2003ICC

But These Options May Not Always Work

• Duct clearance should not be reduced to less than 1/2.”– Ducts are no longer in good condition.– Cable may be damaged during pulling.

• Jacket thickness should not be reduced excessively.– Thin jackets may tear rather easily.– The benefits of the jacket are then lost.

• Difficult to extrude over compact sector.– Rotation of conductor can cause problems.– Costly process.– Splicing and terminating may be a problem.

Page 7: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 7

April 2003ICC

Primary Objectives

• Utilize a DRY Cable Design• Keep a Low Profile• Match Shield to Fault Current Requirement• Match Ruggedness of Cable to Duct System• Specify an Easy-to-Install Cable

Page 8: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 8

April 2003ICC

Utilize a DRY Cable Design

• Consider the Sheath Material– Lead Over Extruded Dielectric– Corrugated and Welded Bronze– Sealed Corrugated and Folded Copper Tape

• Use Strand Filling in the Conductor• Use Other Water Swellable Components

Page 9: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 9

April 2003ICC

Keep a Low Profile

• Several Methods to Reduce the Cable Diameter– Compact the Conductor– Reduce the Thickness of Extruded Components

(Even the Insulation!)

– Use Flat Strap Concentric Neutrals

Page 10: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 10

April 2003ICC

Match Shield to Fault Current

• Although lead sheath carries a high fault current, new cable may not need to carry the equivalent rating of the lead sheath.

• Determine fault requirements to optimize metallic sheath.

• Over designing the shield will result in increased I2R losses. ($$$)

Page 11: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 11

April 2003ICC

Match Ruggedness of Cable

• What is the Condition of Your Ducts?• A Thin Wall Jacket May Be Used If It’s

Tough Enough– Consider Toughness and Heat Stability– LLDPE, HDPE, Polypropylene

• Determine Amount of Clearance Required –Can it Be Reduced to Less Than ½”?

Page 12: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 12

April 2003ICC

Specify Easy-to-install Cable

• Round Conductors vs. Sector Conductor• Flexibility is Key• Connectability to existing system• Consider Pulling Length

Page 13: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 13

April 2003ICC

Design Higher Stress Cables

• A common design practice for HV power cables is to design the cable with a high maximum stress (e.g. EPR 240kV Class @ 10kV/mm)

• In MV cables, the design operating at the highest voltage stress is the 35kV #1/0 AWG Conductor (4 kV/mm).

• If the same insulation is used, why NOT design MV cable to a higher stress?

Page 14: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 14

April 2003ICC

Electric Stress Variations Within Cable Insulation

Conductor

Conductor Shield

Insulation

Insulation Shield

Metallic Shield

Electric Stress DistributionWithin The Insulation

Page 15: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 15

April 2003ICC

April 2003

S@S@DDxx = = 2.0 x E2.0 x E

DDxx x LNx LN DDdd

Where:

S@Dx = Stress at diameter “Dx” , volts/milE = Voltage across insulation, voltsDx = Diameter of interest, milsD = Diameter over insulation, milsd = Diameter over conductor shield, mils

Calculation of Voltage Stress in Cables

Page 16: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 16

April 2003ICC

Reducing the Insulation Thickness Is The Last Step

• Compact Conductor• Use a Flat Strap Neutral• Reduce the Jacket Thickness• Reduce Thickness of the Conductor and

Insulation Shields• Reduce Clearance to Duct• THEN Reduce the Insulation Thickness

Page 17: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 17

April 2003ICC

750 KCM2.95 INCH OD

3/C 750 KCM3.50 INCH OD

175 MILS EPR140 MILS JKT

3-1/C 750 KCM3.65 INCH OD

175 MILS EPR 80 MILS JKT

PILC

CABLE DESIGN SELECTIONStandard Designs - 15 KV

Page 18: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 18

April 2003ICC

3/C 750 KCM2.95 INCH OD

PILC

3/C 750 KCM3.10 INCH OD

125 MILS EPR120 MILS JKT

140 MILS EPR110 MILS JKT

3-1/C 750 KCM3.10 INCH OD

125 MILS EPR50 MILS JKT

CABLE DESIGN SELECTIONReduced Wall Designs - 15 KV

Page 19: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 19

April 2003ICC

Testing the Design

• Testing should show that the proposed design will stand up to the rigors on the installation and operation.

• Electrical and Mechanical Tests• Testing should be at or above proposed

operational limits.– (AEIC CG11-02 recommends same test level as used on the 100%

insulation level.)

Page 20: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 20

April 2003ICC

Electrical Testing

• AC Breakdown Study• Ionization Factor• AEIC Qualification

(As Applicable)

• Accelerated Water Treeing Testing (AWTT)

• Accelerated Cable Life Testing (ACLT)

Page 21: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 21

April 2003ICC

Mechanical Testing

• Should replicate the actual installation conditions, or be more severe

• May include such factors as:– Reverse Bends– High Sidewall Pressure– Small Minimum Bending Radii– Several Cycles of Pulls

• Electrical Testing Should Follow with No Significant Reduction in Electrical Properties

Page 22: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 22

April 2003ICC

Page 23: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 23

April 2003ICC

Reduced Insulation Wall Summary

• In Use for Over Ten Years• Tested with Accessories• A Definite Design Alternative for Tight

Duct Situations

Page 24: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 24

April 2003ICC

Accessories

• In general, premolded accessories may not pass corona tests when installed on reduced insulation thickness cables.

• Cold-shrink and heat-shrink accessories should pass electrical tests.– Trifurcating splices are available.

• Electrical Stress on Reduced Insulation Wall Cables Must Be Controlled at Both Conductor Shield and Insulation Shield Interfaces.

Page 25: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 25

April 2003ICC

Accessories

• Joint size should allow installation in existing smaller manholes.

• Cold-shrink terminations can be used to replace potheads.

• Compression connectors can be used to shape sector conductors.

• Should be qualified to IEEE Std. 404.

Page 26: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 26

April 2003ICC

Summary & Conclusions

• Overall cable design is more important than any individual component.

• Complete redesign not always necessary.• Several types of shields are available.• High temperature jackets should be considered.• Reduced Insulation Wall Is a Viable Option

Page 27: PILC Replacement: Getting the Lead Out · 3/c 750 kcm 2.95 inch od pilc 3/c 750 kcm 3.10 inch od 125 mils epr 120 mils jkt 140 mils epr 110 mils jkt 3-1/c 750 kcm 3.10 inch od 125

PILC Replacement

Page 27

April 2003ICC

Summary & Conclusions• Properly designed PILC replacement cables have

been found to be both electrically and mechanically suitable for installation and operation on utility network systems.

• Whatever the design chosen:– There should be no significant change in the electrical

and physical properties when comparing the reduced wall samples to the full wall samples.

– There should be no significant change in the electrical and physical properties after severe mechanical conditioning.