Upload
others
View
17
Download
0
Embed Size (px)
Citation preview
10
6W
IRIN
G D
IAG
RA
M
Note
1. At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2. In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)
3. In case of using M-NET, please connect to TB5. (Transmission wire is non-polar.)
4. Symbol [S] of TB5 is the shield wire connection.
5. Symbols used in wiring diagram above are, : terminal block, :connecter.
6. The setting of the SW2, SW3 dip switches differs in the capacity. For the detail, refer to fig. 1.
7.Please set the switch SW5 according to the power supply voltage.
CN51
CN52
SW2
SW3
SW4
A.B Address board
SW1
SW5
SW11
SW12
Mode selection
Voltage selection
Address setting 1s digit
Address setting 10ths digit
SW14 Branch No.
Centrally control
Remote Indication
Switch
Switch
Capacity code
Mode selection
Model selection
ZNR Varistor
X1 Aux.relay Drain pump
FUSE Fuse (6A / 250V)
LED1 Power supply (I.B)
LED2 Power supply (I.B)
T Transformer
TH21
MF
MV
Thermistor Room temp. detection
(32ûF/15k , 77ûF/5.4k )
Pipe temp. detection / Liquid
(32ûF/15k , 77ûF/5.4k )
Pipe temp. detection / Gas
(32ûF1/15k , 77ûF/5.4k )
LEV Linear expansion valve
TH22
TH23Fan motor (with inner thermo)
Vane motor
TB15 MA-Remote Controller
[Legend]
Symbol Name
I.B Indoor controller board
CN25
CN27
CN32
Connector Humidifier
Damper
Remote switch
Symbol Name Symbol Name
DS
DP
Drain sensor
Drain pump
TB2
TB5 Transmission
Terminal
block
Power supply
Models
P06
P08
P12
P15
SW2
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
SW3
1 2 3 4 5 6 7
ONOFF
1 2 3 4 5 6 7
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
7
7
8
8
8
8
9
9
9
9
10
10
10
10
ONOFF
<fig. 1>
Mark Meaning Function
Power supply forMA-Remote controller
Main power supply (Indoor unit:208-230V)Power on Lamp is lit.
LED on indoor board for service
LED1 Main power supply
Power supply for MA-Remote controlleron Lamp is lit.
LED2
12345
5
6
MF FAN(WHT)
LED2
LED1
21 (BLU)
(M-NET)CN2M
BLU
BLU
TB5
M1
M2
TB2
PULL BOX
FUSE(15A)
BREAKER
(15A)
L1
L2
S(SHIELD)TO OUTDOOR UNIT
BC CONTROLLER
REMOTE CONTROLLER
DC24-30V
23
1 CN3A(BLU)
ORN
ORN
TB151
2
TO MA-REMOTE
CONTROLLER
DC8.7-13V
POWER SUPPLY
~ / N 208—230V 60Hz
TO NEXT INDOOR UNIT
3 2 1(BLK)GASCN29
2 1(WHT)LIQUIDCN21
2 1
DS TH23 TH22
(RED)INTAKECN20
(WHT)LEV
CN60
(GRN)REMOTE
INDICATIONCN52
2 1 6 5 4 3 2 1
15
(GRN)VANECN6V
6 5 4 3 2 1 2 1
1 2 3 4 5
TH21
(WHT)DRAINCN31
6
LEV MV
CN25
2 1
CN27
876543
43
3
21
1
21
12
34
56
78
910
SW
3
12
34
56
SW
2
12
34
5
SW
4O
N
OF
F
ON
OF
F
ON
OF
F
(RED)ADDRESS
CN81
(RED)ADDRESS
CN42
(WHT)REMOTESWITCH
CN32
3212 13
DP
X1
X1
(WHT)CNP
CND(RED)
FUSE250V
6A
T
BR
N
RE
D
OR
N
YLW
GR
N
BLU
BR
N
OR
N
YLW
RE
D
WH
T
(WHT)CENTRALLYCONTROL
CN51
15
RED
BLU
GRN / YLW
See fig. 1
8 7 6 5 4 3 2 1
4 3 2 1
8
4
0
SW
14
SW
C
BR
AN
CH
No.
0
SW
11
1s
DIG
IT
0
SW
12
10th
sD
IGIT
12
34
56
78
910
SW
1
SW
5
230V
208V
(RED)ADDRESS
CN82
(RED)ADDRESS
CN43
A.B
I.B
GR
< 2>
( 2) Use copper supply wire.
PM
FY
-P06N
BM
U-E
PM
FY
-P08N
BM
U-E
PM
FY
-P12N
BM
U-E
PM
FY
-P15N
BM
U-E
11
Note
1. At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2. In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)
3. In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)
4. Symbol [S] of TB5 is the shield wire connection.
5. Symbols used in wiring diagram above are, : terminal block, :connector.
6. The setting of the SW2, SW3 dip switches differs in the capacity. For the detail, refer to fig. 1.
7. Please set the switch SW5 according to the power supply voltage.
CN51
CN52
SW2
SW3
SW4
A.B Address board
SW1
SW5
SW11
SW12
Mode selection
Voltage selection
Address setting 1s digit
Address setting 10ths digit
SW14 Branch No.
Centrally control
Remote Indication
Switch
Switch
Capacity code
Mode selection
Model selection
ZNR Varistor
X1 Aux.relay Drain pump
FUSE Fuse (6A / 250V)
LED1 Power supply(I.B)
LED2 Power supply(I.B)
T Transformer
TH21
MF
MV
Thermistor Room temp. detection
(32ûF/15k , 77ûF/5.4k )
Pipe temp. detection / Liquid
(32ûF/15k , 77ûF/5.4k )
Pipe temp. detection / Gas
(32ûF/15k , 77ûF/5.4k )
LEV Linear expansion valve
TH22
TH23Fan motor
Vane motor
TB15 MA-Remote Controller
[Legend]
Symbol Name
I.B Indoor controller board
CN25
CN27
CN32
Connector Humidifier
Damper
Remote switch
Symbol Name Symbol Name
DS
DP
Drain sensor
Drain pump
TB2
TB5 Transmission
Terminal
block
Power supply
Models
P06
P08
P12
P15
SW2
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
SW3
1 2 3 4 5 6 7
ONOFF
1 2 3 4 5 6 7
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
7
7
8
8
8
8
9
9
9
9
10
10
10
10
ONOFF
<fig. 1>
Mark Meaning Function
Power supply forMA-Remote controller
Main power supply (Indoor unit:208-230V)Power on Lamp is lit.
LED on indoor board for service
LED1 Main power supply
Power supply for MA-Remote controlleron Lamp is lit.
LED2
6
1
3MS3~MF FAN
(WHT)
LED2
LED1
2
1 (BLU)(M-NET)CN2M
BLU
BLU
TB5
TB2
PULL BOX
FUSE
(15A)
BREAKER
(15A)
(SHIELD)
TO OUTDOOR UNIT
BC CONTROLLER
REMOTE CONTROLLER
DC24-30V
CN3A(BLU)
ORN
ORN
TB15TO MA-REMOTE
CONTROLLER
DC8.7-13V
POWER SUPPLY
~ / N 208-230V 60Hz
TO NEXT INDOOR UNIT
(BLK)GASCN29
(WHT)LIQUIDCN21
DS TH23 TH22
(RED)INTAKECN20
(WHT)LEVCN60
(GRN)REMOTE
INDICATIONCN52
15
(GRN)VANECN6V
6 16 1
1 5
2 12 12 12 13 1
TH21
(WHT)DRAINCN31
LEV
M M
MV
CN252 1CN27 8
4
1
1
12
34
56
78
910
SW
3
12
34
56
SW
2
12
34
5
SW
4O
N
OF
F
ON
OF
F
ON
OF
F
(RED)ADDRESS
CN81
(RED)ADDRESS
CN42
(WHT)REMOTESWITCH
CN32
M1~
DP
X1
(WHT)CNP
CND(RED)
FUSE
T
BR
N
RE
D
OR
N
YLW
GR
N
BLU
BR
N
OR
N
YLW
RE
D
WH
T
(WHT)CENTRALLYCONTROL
CN51
15
RED
BLU
GRN / YLW
See fig. 1
8 1
4 1
8
4
SW
14
SW
C
BR
AN
CH
No.
SW
11
1s
DIG
IT
SW
12
10th
sD
IGIT
12
34
56
78
910
SW
1
SW
5
230V
208V
(RED) ADDRESSCN82
(RED)ADDRESS
CN43
A.B
I.B
< 2>
< 2>Use Copper Supply Wire.
t° t° t° t°
3
1
3
1
313 1
1
2
L1
L2
GR
U
M1
M2
S
01
2
3456 78
9A
BCDEF
01
2 3
45
6
78
90
1
2 3
45
6
78
9
PM
FY
-P06N
BM
U-E
1 PM
FY
-P08N
BM
U-E
1 PM
FY
-P12N
BM
U-E
1 PM
FY
-P15N
BM
U-E
1
12
Note
1. At servicing for outdoor unit, always follow the wiring diagram
of outdoor unit.
2. In case of using MA-Remote controller, please connect to
TB15. (Remote controller wire is non-polar.)
3. In case of using M-NET, please connect to TB5.
(Transmission line is non-polar.)
4. Symbol [S] of TB5 is the shield wire connection.
5. Symbols used in wiring diagram above are, : terminal
block, :connector.
6. The setting of the SW2, SW3 dip switches differs in the capacity.
For the detail, refer to fig. 1.
7. Please set the switch SW5 according to the power supply
voltage.
CN51
CN52
SW2
SW3
SW4
SWE A.B Address board
SW1
SW5
SW11
SW12
Mode selection
Voltage selection
Address setting 1s digit
Address setting 10ths digit
SW14 Branch No.
Centrally control
Remote Indication
Switch
Switch
Capacity code
Mode selection
Model selection
DRAIN UP MACHINE(TEST MODE)
ZNR Varistor
X1 Aux.relay Drain pump
FUSE Fuse (T6.3AL 250V)
LED1 Power supply (I.B)
LED2 Power supply (I.B)
TH21
MF
MV
Thermistor Room temp. detection
(32°F/15k , 77°F/5.4k )
Pipe temp. detection / Liquid
(32°F/15k , 77°F/5.4k )
Pipe temp. detection / Gas
(32°F/15k , 77°F/5.4k )
LEV Linear expansion valve
TH22
TH23
Fan motor
Vane motor
TB15 MA-Remote Controller
[Legend]
Symbol Name
I.B Indoor controller board
CN25
CN27
CN32
Connector Humidifier
Damper
Remote switch
Symbol Name
DS
DP
Drain sensor
Drain pump
TB2
TB5 Transmission
Terminal
block
Power supply
Models
P06
P08
P12
P15
SW2
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
SW3
1 2 3 4 5 6 7
ONOFF
1 2 3 4 5 6 7
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
7
7
8
8
8
8
9
9
9
9
10
10
10
10
ONOFF
<fig. 1>
Mark Meaning Function
Power supply forMA-Remote controller
Main power supply (Indoor unit:208-230V)Power on Iamp is lit
LED on indoor board for service
LED1 Main power supply
Power supply for MA-Remote controlleron Iamp is lit
LED2
< 2> Use Copper Supply Wire.
SWE
ON OFF
GR
CN2M(BLU)
M-NET
CN3A(BLU)
REMOCON
TB5
(SHIELD)
M1 M2TB2
TB15
1 S
TH23
TH22
CN20(RED)
INTAKE
CN60(WHT)
LEV
CN52(GRN)
REMOTEINDICATION
CN6V1(GRN)
VANE
TH21
CNMF2(WHT)
CNMF1(WHT)
CN31(WHT)
DRAIN
CN44(WHT)
LIQUID/GAS
CN25(WHT)
CN27(RED)
ADDRESS
CN81 (RED)
CN42(RED)
ADDRESS
CN32 (WHT)
REMOTE SWITCH
X1
CNP(YLW)
D.U.M
CND (BLK)
FUSE
DSA
ZNR01DC311~339V
ZNR02U
CN51 (WHT)
CENTRALLYCONTROL
CN41(WHT)
HA
48
5
5
LEV
M
DS
DP
t°
t°
t°
t°
2L1 L2
1 2 3 4 5 6 7 8 910
SW3
1 2 3 4 5 6
SW2
1 2 3 4 5
SW481
5 1
51 3
6
1
6
1
5
1
4
1
2
1
2
1
2
1
4
1
1
3
3
1
3
1
31
21
2 1
1
4
1357
8 6 4 2
I.B
M1~
M
U
MS3~
PULL BOXFUSE(15A)
BREAKER(15A)
POWER SUPPLY~ / N208-230V 60Hz
TO NEXTINDOORUNIT
BLU
BRN
ORN
YLW
RED
WHT
SW14SWC
BRANCH
No.
SW11
1s
DIGIT
SW12
10ths
DIGIT
1 2 3 4 5 6 7 8 910
SW1
SW5
230V208V
(RED)
ADDRESS
CN82
(RED)
ADDRESS
CN43
A.B
8
1
4
1
01234
5
6789AB
CD
EF0 1
23
456
78
90 1
23
456
78
9
TO MA-REMOTECONTROLLERDC8.7-13V
TO OUTDOOR UNITBC CONTROLLERREMOTE CONTROLLERDC24-30V
RED BL
U
GR
N/Y
LW
MF
MV
ORN
*See fig. 1
ORN
BLU
BLU
BLU
BLU
LED2
LED1
GRNYLWORNREDBRN
BLK
PM
FY
-P06N
BM
U-E
#2
PM
FY
-P08N
BM
U-E
#2
PM
FY
-P12N
BM
U-E
#2
PM
FY
-P15N
BM
U-E
#2
PM
FY
-P06N
BM
U-E
R3
PM
FY
-P08N
BM
U-E
R3
PM
FY
-P12N
BM
U-E
R3
PM
FY
-P15N
BM
U-E
R3
PM
FY
-P06N
BM
U-E
R4
PM
FY
-P08N
BM
U-E
R4
PM
FY
-P12N
BM
U-E
R4
PM
FY
-P15N
BM
U-E
R4
13
REFRIGERANT SYSTEM DIAGRAM7
Strainer (#100mesh)
Strainer pipe (#100mesh)
Strainer(#100mesh)
Strainer(#50mesh)
Heat exchanger
Thermistor TH21<Room temperature detection>
Thermistor TH23<Gas pipe temperature detection>
Thermistor TH22 <Liquid pipe temperature detection>
Linear expansion valve
1 2
Gas pipe
Liquid pipe
Flare connection
PMFY-P06NBMU-E PMFY-P08NBMU-E PMFY-P12NBMU-E PMFY-P15NBMU-E
PMFY-P06NBMU-E1 PMFY-P08NBMU-E1 PMFY-P12NBMU-E1 PMFY-P15NBMU-E1
PMFY-P06NBMU-E#2 PMFY-P08NBMU-E#2 PMFY-P12NBMU-E#2 PMFY-P15NBMU-E#2
PMFY-P06NBMU-ER3 PMFY-P08NBMU-ER3 PMFY-P12NBMU-ER3 PMFY-P15NBMU-ER3
PMFY-P06NBMU-ER4 PMFY-P08NBMU-ER4 PMFY-P12NBMU-ER4 PMFY-P15NBMU-ER4
PMFY-P06/P08/P12/P15NBMU-EPMFY-P06/P08/P12/P15NBMU-E1
PMFY-P06/P08/P12/P15NBMU-E#2PMFY-P06/P08/P12/P15NBMU-ER3PMFY-P06/P08/P12/P15NBMU-ER4
Gas pipe [1/2"(12.7)
Liquid pipe [1/4"(6.35)
Unit: in.(mm)
Service Ref.
Item.
PMFY-P06/P08NBMU-EPMFY-P06/P08NBMU-E1
PMFY-P06/P08NBMU-E#2PMFY-P06/P08NBMU-ER3PMFY-P06/P08NBMU-ER4
PMFY-P12/P15NBMU-EPMFY-P12/P15NBMU-E1
PMFY-P12/P15NBMU-E#2PMFY-P12/P15NBMU-ER3PMFY-P06/P08NBMU-ER4
Capillary tube W1 O.D.[4.6 × I.D.Ø3.4 ×R200 O.D.[3.6 × I.D.Ø2.4 ×R200
Capillary tube W2 O.D.[3.6 × I.D.Ø2.4 ×R80
Unit: mm
30
DISASSEMBLY PROCEDURE10
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
Be careful when removing heavy parts.
PMFY-P06NBMU-E PMFY-P08NBMU-E PMFY-P12NBMU-E PMFY-P15NBMU-EPMFY-P06NBMU-E1 PMFY-P08NBMU-E1 PMFY-P12NBMU-E1 PMFY-P15NBMU-E1
PMFY-P06NBMU-E#2 PMFY-P08NBMU-E#2 PMFY-P12NBMU-E#2 PMFY-P15NBMU-E#2PMFY-P06NBMU-ER3 PMFY-P08NBMU-ER3 PMFY-P12NBMU-ER3 PMFY-P15NBMU-ER3PMFY-P06NBMU-ER4 PMFY-P08NBMU-ER4 PMFY-P12NBMU-ER4 PMFY-P15NBMU-ER4
1. Removing the grille
Opening the air intake grille
(1) Press the PUSH of the air intake grille. (See Figure 1)(2) Put your fingers on the both ends of nut of the air intake
grille and put it down after the grille clicked.
Removing the air intake grille
(1) Press the PUSH of the air intake grille, and pull down the both ends of nut with your fingers after the grille clicked.
(See Figure 1)
(2) Pull out the handle of air intake grille strongly toward you.
(See Figure 2)
(3) Draw the string of the air intake grille to prevent the air
intake grille from dropping. (See Figure 3)
Photo 1
Figure 1
Air filter
Figure 2
Figure 3
Points for securing the grille
Points for securing the grille
Points for securing the grille
Drainage pan
Ceiling surface
Make sure these surfaces are ß ush with each other (0-3 mm).
Checks before setting the grille in place
(1) Before installing the grille, make sure the indoor unit is
square with the ceiling opening (or parallel to the angle
between the wall and the ceiling).
(2) Check that the 4 points where the grille will be secured are
in contact with the ceiling surface.
(3) Check that the insulation for the refrigerant pipes, drain-
age pipes, etc. is in place and that wiring connections and
arrangements are complete.
Air intake grille
Air outlet
grille
Nozzle
PUSH
String for dropping prevention
Figure 4
Figure 5
31
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
Figure 6
Figure 7
Figure 8
Removing the grille
(1) Open the intake grille by pressing PUSH of the air intake grille and remove the air Þ lter (× 2). (See Figure 1)
(2) Remove the screw cover in the middle of the air outlet. (See
Figure 7)
(3) Open the upper and lower ß aps on the indoor unit com-
pletely. (See Figure 7)
(4) Remove the securing screws (× 7).
(A: M5 × 0.8 × 16, 6pcs)
(B: 4 × 16, 1pc)
(5) Remove the temporary holding tabs on the grille to the
hooks on the indoor unit.
Attaching the grille
(1) Open the upper and lower ß aps on the indoor unit com-
pletely.
(2) Hook the temporary holding tabs on the front panel to the
hooks on the indoor unit.
(3) Adjust the grille so that it Þ ts properly in the angle between
the ceiling and the wall, and install the securing screws A
(supplied with this grille) in their 4 places at left and right,
leaving them slightly loose.
(4) Tighten the securing bolts A and securing screws B in the
centre 3 places. (See Figure 6)
(5) Tighten the securing bolts A in the 4 places at left and right.
* Make sure there are no gaps between the indoor unit and
the grille, and between the grille and the ceiling surface.
If there are gaps, the wind may come in and it may cause
water to drip. (See Figure 8)
* Tighten the securing bolts A and securing screws B com-
pletely.
(6) Replace the air Þ lter and screw cover, and press PUSH of the intake grille until you hear it snap into place.
Checks after setting the grille
(1) Check that there are no gaps between the indoor unit and
the grille, between the grille and the ceiling surface. If there
are gaps, the wind may come in and condensation may
result.
(2) Check that the air Þ lter is in place.
Hooks
Temporary holding tabs
BA
AA
A
AA
Hooks Upper and lower ß aps* Open completely
Temporary holding tabs
Temporary holding tabs
Screw cover
Indoor unit
No gaps between the indoor unit and the grille
GrilleCeiling surface
32
3. Removing the nozzle
Note when the nozzle is removed.
· The insulation material (white) which prevents water
drop is mounted to the side of vane motor. Remove the
insulation material before removing nozzle.
(See Figure 4)
· After completing the service, re-mount the insulation
material as before as shown in right figure.
· After service, mount the double layer insulation without
fail.
The hard material side should be faced toward the nozzle.
(See Figure 4)
(1) Remove the panel.
(2) Remove the room temperature thermistor.
(3) Unhook the claws in the middle of nozzle and remove the
drain pan. (5 screws) (See Photo 2)
(4) Remove the nozzle side of the heat exchanger. (2 screws)
(5) Remove the address board cover. (See Photo 3)
(6) Remove the electrical parts cover. (See Photo 3)
(7) Disconnect the connector of vane motor.
(8) Remove the insulation material (white) on the right side of
nozzle.
(9) Remove the nozzle. (6 screws)
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
2. Removing the electrical parts box
(1) Remove the panel.
(2) Remove the address board cover.
(3) Remove the electrical parts cover.
(4) Disconnect the connectors of
fan motor, vane motor,
drain pump, room temperature thermistor,
pipe temperature thermistor (Liquid. Gas),
condenser/evaporator temperature thermistor,
and drain sensor on the electrical controller board.
(5) Disconnect the lead wire and earth wire from terminal
block.
(6) Remove the electrical parts box.
4. Removing the vane motor
(1) Remove the nozzle. Refer to above-mentioned
3. Removing the nozzle.
(2) Remove the vane motor from the nozzle.
Photo 5
Photo 4
Photo 3
Photo 2
Vane motor
Nozzle
Vane motor
Nozzle
Drain pan
Hard side of insulation
Insulation material
Electrical parts
Soft side of insulation
Room temperature thermistor
NozzleClaw in middle
of nozzle
Electrical parts
cover
Figure 9
Heat exchanger
Address board
cover
Vane motor
33
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
5. Removing the drain pump
(1) Remove the panel.
(2) Unhook the claw in the middle of nozzle and remove the
drain pan. (See Photo 2)
(3) Remove the address board cover. (See Photo 3)
(4) Remove the electrical parts cover. (See Photo 3)
(5) Disconnect the connector of drain pump.
(6) Remove the drain hose.
(7) Remove the drain pump.(2 screws)
6. Removing the fan motor and line flow fan
(1) Remove the panel.
(2) Unhook the claw in the middle of nozzle and remove the
drain pan. (See Photo 2)
(3) Unscrew 2 screws at the nozzle side of the heat exchanger.
(4) Remove the address board cover. (See Photo 3)
(5) Remove the electrical parts cover. (See Photo 3)
(6) Disconnect the connector of vane motor, fan motor and
drain pump.
(7) Remove the nozzle side of the heat exchanger.(2 screws)
(8) Remove the nozzle.
(9) Remove the drain pump.
(10) Unscrew 2 screws in the motor support.
(11) Remove the fan motor and line flow fan. (The fan motor
and line flow fan can be removed without removing the
heat exchanger.)
Photo 6 Drain pump
Fan motor
Drain sensor
Photo 7
Fan motorLine flow fan
7. Removing the thermistor<Room temperature detection>
(1) Remove the panel.
(2) Remove the address board cover.
(3) Remove the electrical parts cover.
(4) Remove the thermistor. <intake temperature detector>
(5) Disconnect the lead wire from the cord clamp. (5 points)
(6) Disconnect the connector (CN20) on the indoor controller
board.
8. Removing the thermistor
<Liquid pipe temperature detection>
<Gas pipe temperature detection>
(1) Remove the panel.
(2) Remove the address board cover.
(3) Remove the electrical parts cover.
(4) Remove the drain pan.
(5) Remove the thermistor <Gas pipe temperature detection>/
<Liquid pipe temperature detection>.
(6) Disconnect the lead wire from the cord clamp.
(7) Disconnect the connector (CN21)/(CN29), (CN44) on the
indoor controller board.
Connector (CN21) / Liquid (NBMU(1))
(CN29) / Gas (NBMU(1))
(CN44) / Liquid and Gas (NBMU#2, NBMUR3,
NBMUR4)
12
WIRING DIAGRAM7
PLFY-P08NCMU-E.TH PLFY-P12NCMU-E.TH PLFY-P15NCMU-E.TH
PLFY-P08NCMU-E1.TH PLFY-P12NCMU-E1.TH PLFY-P15NCMU-E1.TH
DP
WHT(DRAIN)
WHT
FAN(FAN)
See Fig.1
MODELS
P08
P12
P15
<Fig.1>
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
SW2
Power supply for MA-Remote controller on Lamp is lit.
Main power supply(Indoor unit:208-230V) power on Lamp is lit.Main power supply
Power supply forMA-Remote controller
LED2
LED1
Mark Meaning
LED on indoor controller board for service
Function
CN
32(R
EM
OT
E S
WIT
CH
) W
HT
32
1
DC24-30VCONTROLLER
TO NEXT INDOOR UNIT
PULL BOX
FUSE(15A)
BREAKER (15A)
60Hz
HA
1234
WHT
CN41 CN51
WHT(CENTRALLY CONTROL)
5 4 3 2 1
CN52
(REMOTE INDICATION)
GRN
12345
REMOTE SWITCHCN32
X7 FAN MOTOR (Me)X6 FAN MOTOR (Hi)X5 FAN MOTOR (Lo)
SW1 SWITCH MODE SELECTION
CONNECTION No.SW14SW12SW11 ADDRESS SETTING 1ST DIGIT
ADDRESS SETTING 2ND DIGIT
MODEL SELECTIONMODE SELECTIONCAPACITY CODE
SW4SW3SW2
(32 F/15k 77 F/5.4k )
(32 F/15k 77 F/5.4k )
DP DRAIN PUMPDS DRAIN SENSORH2 DEW PREVENTION HEATER
FAN MOTOR (LL)DRAIN PUMP/DEW PREVENTION HEATERX1 AUX. RELAY
SYMBOL NAME
VARISTOR
INDOOR POWER BOARDP.B
ZNR
X4
I.B
CN41CN51CN52FUSE FUSE (6.3A/250V)
REMOTE INDICATIONCENTRALLY CONTROLHA TERMINAL-A
CONNECTORINDOOR CONTROLLER BOARD
[LEGEND]
NAMESYMBOL
PIPE TEMPERATURE DETECTION/GASTH23
TRANSMISSIONTERMINALBLOCK
POWER SUPPLYTB5TB15
TB2
(32 F/15k 77 F/5.4k )THERMISTOR ROOM TEMPERATURE DETECTION
TH22
TH21
LEV LINEAR EXPANSION VALVE
MVMF
VANE MOTORFAN MOTOR (WITH THERMAL FUSE)
CAPACITOR (FAN MOTOR)C1
PIPE TEMPERATURE DETECTION/LIQUID
MA-REMOTE CONTROLLER
LED2
LED1
31 1 3CND
(POWER)
YLW
21
YLW
1 3 BLU
(D•U•M)CNC
(D•HEATER) RED ORN
FUSE
ZNR
CNP
X1
RED
ORN
GRILLE
BLU
5
WHT
BLU
RED
ORN
YLW
REDRED
1
10
7
2
3
6
4
5
8
9
3
5
5
5
5
C1
1 5
BLK
YLW
WHTBR
N
7 9
X6 X5 X4 X7
X4 X7X5X6
MF
I.B
CN20
CN31
123
BLU
WHT
ORN
RED
YLW 6
6 5 4 3 2 1
(VANE)CN6V
GRN
RED
ORN
BLU
6 5 4 3 2 1
(LEV)CN60
WHT
WHT
YLW
BRN
BLK
2 2 11
(LIQUID)(INTAKE)CN21
RED WHT
2 1
(GAS)CN29
(RE
MO
CO
N)
WH
T
13
RE
DP.B
RED
CNDK
(POWER BORD)
123
AC208-230VCNSK(RED)
TB2L1
L2
GR
RED
BLU
GRN/YLW
~/N 208-230V POWER SUPPLY
TRANSDC13.1VCN2S(WHT)
21
21
(PO
WE
R B
OR
D)
CN
2D
WH
T
WHT
BLK
M1
1
2CONTROLLERDC8.7-13V
TO MA-REMOTE
CN
2M(M
-NE
T) 1
23
1
CN
3A
BLU
BLU
M2
TB15
S(SHIELD)
M-NET REMOTE
TO OUTDOOR UNITBC CONTROLLERTB5
X1
TH23TH22TH21DSLEV
5
3RDDIGIT
0
O0
0N0FF
SW1
1 2 3 4 5 6 7 8 9 10
SW12 SW11
1STDIGIT
0
2NDDIGIT
SW14
CONNECTIONNo.
1 2 3 4 50FF0N
SW4SW2
654321 109876543210FF
0NSW3
MV
H2
MV
MV
MV
Notes:
1. At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2. In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)
3. In case of using M-NET, please connect to TB5. (Transmisson wire is non-polar.)
4. Symbol[S] of TB5 is the shield wire connection.
5. Symbols used in wiring diagram above are, :terminal block, :connecter.
6. The setting of the SW2 dip switch differs in the capacity. For the detail, refer to Fig.1.
7. Use copper supply wire.
13
(RED)
(RED)
MODELS
P08
P12
P15
<Fig.1>
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
SW2
Power supply for MA-Remote controller on Lamp is lit.
Main power supply(Indoor unit:208-230V) power on Lamp is lit.Main power supply
Power supply forMA-Remote controller
LED2(RED)
LED1(RED)
Mark Meaning
LED on indoor controller board for service
Function
Notes:
1. At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2. In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)
3. In case of using M-NET, please connect to TB5. (Transmisson wire is non-polar.)
4. Symbol [S] of TB5 is the shield wire connection.
5. Symbols used in wiring diagram above are, : terminal block, :connecter.
6. The setting of the SW2 dip switch differs in the capacity. For the detail, refer to Fig.1.
7. Use copper supply wire.
Fig.1
PLFY-P08NCMU-ER2.TH PLFY-P12NCMU-ER2.TH PLFY-P15NCMU-ER2.TH
14
REFRIGERANT SYSTEM DIAGRAM8
Strainer (#50mesh)
Strainer (#100 mesh)
Strainer1 (#50 mesh)Strainer2 (#100 mesh)
Heat exchanger
Room temperature thermistor TH21
Gas pipe thermistor TH23
Liquid pipe thermistor TH22
Linear expansion valve
Gas pipe
Liquid pipe
Flare connection
Gas pipe
Liquid pipe
1/2
1/4
Refrigerant flow in coolingRefrigerant flow in heating
Unit : inch
PLFY-P08NCMU-E.TH PLFY-P12NCMU-E.TH PLFY-P15NCMU-E.TH
PLFY-P08NCMU-E1.TH PLFY-P12NCMU-E1.TH PLFY-P15NCMU-E1.TH
PLFY-P08NCMU-ER2.TH PLFY-P12NCMU-ER2.TH PLFY-P15NCMU-ER2.TH
29
DISASSEMBLY PROCEDURE11
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
1. Removing the air intake grille
(1) Slide the knob of air intake grille to the direction of the
arrow 1 to open the air intake grille.
(2) Remove the string hook from the panel to prevent the grille
from dropping.
(3) Slide the hinge of the intake grille to the direction of the
arrow 2 and remove the air intake grille.
4. Removing the electrical parts
(1) Remove the 2 screws and the control box cover.
<Electrical parts in the control box>
• Indoor controller board (I.B)
• Indoor power board (P.B)
• Fan motor capacitor (C1)
• Fuse (FUSE)
• Varistor (ZNR)
• Terminal block (TB)
Be careful when removing heavy parts.
Photo 3
Figure 1
Air intake grille
Grille
2. Removing the fan guard
(1) Open the air intake grille.
(2) Remove the 3 screws of fan guard.
Air intake grille knob
3. Removing the panel
(1) Remove the air intake grille. (Refer to 1)
Corner panel (See Figure 2)
(1) Remove the screw of the corner.
(2) Slide the corner panel to the direction of the arrow 3, and
remove the corner panel.
Panel (See Photo 2)
(1) Disconnect the connector that connects with the unit.
(2) Remove the 2 screws from the panel and loose other
2 screws, which are fixed to the oval hole, have different
diameter.
(3) Rotate the panel a little to remove the screws.(Slide the
panel so that the screw comes to a larger diameter of the
oval hole, which has two different diameters.)
Photo 1
Screws
Air intake grille
Photo 2
Figure 2
Corner
panel
ScrewCorner
panel Panel
Panel
Screws
Connector
Screws
Fan guard
Indoor controllerboard (I.B)
Fuse(FUSE)
Indoor powerboard(P.B)
Terminalblock(TB2)
Indoor controllerbox
PLFY-P08/12/15NCMU-E.TH PLFY-P08/12/15NCMU-E1.TH
PLFY-P08/12/15NCMU-ER2.TH
Terminalblock(TB5)
Varistor (ZNR)
Fan motor Capacitor(C1)
Terminalblock(TB15)
30
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
7. Removing the pipe temperature detection/liquid (TH22)
and pipe temperature detection/gas (TH23)
(1) Remove the panel. (Refer to 3)
(2) Remove the drain pan. (Refer to 6)
(3) Disconnect the liquid or gas from the holder.
(4) Remove the 3 screws fixed to the piping cover, and remove
the piping cover. (See Photo 9)
(5) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
Pipe temperature detection/liquid (TH22)
(6) Remove the connector (CN21) from the indoor controller
board, and disconnect the pipe temperature detection/Liquid.
Pipe temperature detection/gas (TH23)
(6) Remove the connector (CN29) from the indoor controller
board, and disconnect the pipe temperature detection/Gas
with its holder.
8. Removing the fan motor (MF)
(1) Remove the panel. (Refer to 3)
(2) Remove the drain pan. (Refer to 6)
(3) Remove the nut and the washer from the turbo fan, and
remove the turbo fan.
(4) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(5) Disconnect the connectors of the (FAN) from the indoor
controller board.
(6) Remove the 3 screws fixed to the piping cover, and remove
the piping cover. (See photo 9)
(7) Remove the 6 screws fixed to the flat plate, and remove
the flat plate.
(8) Disconnect the lead wires to the direction of the fan motor,
and remove 3 nuts of the fan motor.
Photo 5
6. Removing the drain pan
(1) Remove the panel. (Refer to 3)
(2) Remove the room temperature detection and the 2 lead
wires held with fastener; wireless controller board relay
connector (9P red) and panel relay connector (10P white).
(3) Remove the 4 screws fixed to the drain pan, and remove
the drain pan.
(4) Remove the fan guard. (Refer to 2)
Photo 4
Control box
Thermistor
(Pipe temperature
detection/ Liquid)
(TH22)
Screw
Screw
ScrewScrew
Room
temperature
detection
(TH21)
Drain pan
Control box
Photo 6
Fanmotor(MF)
Nuts
Flat plate
Screws
Lead wires
Nut
Screws
Screws
5. Removing the room temperature detection (TH21)
(1) Remove the panel. (Refer to 3)
(2) Pull out the room temperature detection from the drain pan.
(3) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(4) Remove the connector (CN20) from the indoor controller
board, and disconnect the room temperature detection.
Fan guard
Drain plug
Connectors
Thermistor
(Pipe temperature
detection/ Gas)
(TH23)
LEV
31
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
10. Removing the heat exchanger
(1) Remove the panel. (Refer to 3 )
(2) Remove the drain pan. (Refer to 6)
(3) Remove the nut and the washer from the turbo fan, and
remove the turbo fan.
(4) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(5) Disconnect the connectors of the (FAN) from the indoor
controller board.
(6) Remove the 3 screws fixed to the piping cover, and remove
the piping cover. (See photo 9)
(7) Remove the pipe temperature thermistor/liquid and
condenser/evaporator temperature thermistor. (Refer to 7)
(8) Disconnect the lead wires to the direction of the fan motor.
(9) Remove 1 coil support screw, 2 inside coil screws (See
photo 10), and 4 outside coil screws (See photo 9) from the
heat exchanger, and remove the heat exchanger.
9. Removing the drain pump (DP) and drain sensor (DS)
(1) Remove the panel. (Refer to 3 )
(2) Remove the drain pan. (Refer to 6)
(3) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(4) Remove the connectors of the (CNP) and the (CN31)
from the indoor controller board.
(5) Remove the 1 screw fixed to the cover, and remove the
cover.(See photo 7)
(6) Disconnect the lead wires to the direction of the drain
pump.
(7) Remove the 3 screws of the drain pump.(See photo 8)
(8) Cut the drain hose fixing band, pull out the drain hose
from the drain pump.
(9) Pull out the drain pump.
(10) Remove the drain sensor and the holder.
Photo 7
Screw
Screws
Drain sensor (DS) Drain pump (DP)
Drain hose
Fixing band
Photo 9
Photo 10
Heat exchanger
Coil screws
Coilsupport
Coilsupport Screw
Control box
Cover
Screw
Control box
Photo 8
Screws of
piping coverControl box
Piping cover Lead wires
Coil
screws
Lead wires