Bulletin 04Q01A01-01E

Portable Paperless Recorder

MV1000/MV2000

www.mv1000.comwww.mv1000.com

The following product was discontinued as of July, 2012. Discontinued product: Rechargeable Battery Specification (Power supply suffix code: -3) and Battery Pack (B8805HA)
Page 2: Portable Paperless Recorder MV1000/MV2000nubilight.nubicom.co.kr › upload › datasheet › MV1000.pdf · Portable Paperless Recorder MV1000/MV2000 . The following product was discontinued

MV1000/MV2000

MV2000(48 ch) MV1000

(24 ch)

Reliable RecordingYou can now record even more

channels over even longer durations

Easy SetupThe simplified interface lets you start measuring sooner!

Easy-to-read DisplayIncredibly clear LCD monitor. Improved monitor interface!

Smart AnalysisImproved PC compatibility ensures

a smooth transition into data analysis!

Multi-point InputMV1000: 24-channel input MV2000: 48-channel input

Reliable Long-duration MemoryInternal memory: 400 MB(Approximately 148-day continuous 12-channel measurement data storage at a 1-second data storage interval)

Data can be stored in external storage media, such as a CF card and USB memory.

Setup is fast and so easy that no manual is required.

Removable input terminals make wiring easier.

Best-inClass

Best-inClass Wide Range of Input Types

Accepts thermocouple (up to 18 types), RTD (up to 12 types), DC voltage (within ±50 V), and contact inputs.

Insulated between channels, 1000 VAC withstand voltage!

The Text Save mode enables text data to be transferred directly to general-purpose software.

New aluminum body reduced the weight by approximately 20% (MV2000).

A wealth of network functionality such as E-mail, FTP, and DHCP functions are available.

Measurement scenarios that call for speed and accuracy: MVAdvanced accurately captures precious evaluation data on the test bench and in the field, and helps to cut down on manhours.

Page 3: Portable Paperless Recorder MV1000/MV2000nubilight.nubicom.co.kr › upload › datasheet › MV1000.pdf · Portable Paperless Recorder MV1000/MV2000 . The following product was discontinued

Easy SetupEasy Setup Reliable Recording

The simplified interface lets you start measuring sooner!

Quick Setup mode

We have put all the essential measuring options in one place.Setup is so simple and easy that there is no need for a manual.

USB equipped

Comes standard-equipped with two USB ports. You candownload setup files from your PC and save measured datawith the touch of a button.

Removable input terminals

Input terminals can beremoved in units of 2channels, making wiringmuch easier. And blockterminals can be pur-chased separately.

Acquire the data you need with a variety of measuring modes

The MV1000 and MV2000 are loaded with a variety of measure-ment features. By matching these features to your measurementgoals, you are sure to be able to collect the data you need.

Free mode

Data acquisition is userprompted, and acquisition of thedata sequence occurs at the setsampling rate.

Trigger modes

You can use a variety of trig-gers—such as alarm, externalcontact, time, and calculateddata—to set the timing of dataacquisition. By combining thesewith pre-trigger functions andother features, you can efficientlyacquire the data you need.

START

RecordTrigger wait

TRIG!

Page 4: Portable Paperless Recorder MV1000/MV2000nubilight.nubicom.co.kr › upload › datasheet › MV1000.pdf · Portable Paperless Recorder MV1000/MV2000 . The following product was discontinued

Easy Setup Reliable RecordingReliable Recording

You can now record even more channels over even longer durations!

Multi-channel input

The MV1000 can support up to 24 channels (2 times as manychannels as before), while the MV2000 can support up to 48(1.6 times as many channels as before)! Naturally, everychannel is isolated, and you can count on reliable data acquisition!

Measured value

Scan interval

: Measurement at 25 ms (MVAdvanced) : Measurement at 125 ms (conventional models)

Up to24ch

Up to48ch

High-speed sampling

By measuring in high-speed mode, you can attain a minimummeasurement interval of 25 ms for every channel (MV1004,MV1008, and MV2008). With a measurement interval that is 5times faster than before, you can acquire more detailed data.

MV2000

DAQMASTER MW100

48ch 300ch 348ch+48ch 300ch+ =

External input gives you up to 348 channels

By connecting to the DAQMASTER Series MW100, you canincrease channel input by a maximum of 300 channels.Connection is as easy as the touch of a button!

High-capacity memory

Equipped with 400 MB (330 times more memory than before) ofinternal flash memory! By backing up with external media (CFcard), you can further ensure the safety of your data!

If a power outage should occur, then the unit will automaticallyresume measurement when power returns.

Example of saving data to internal memory**Condition

• Sampling interval: 1 sec• Measurement channel: 12 ch• Binary save mode

Approx. 148 daysMVAdvanced400 MB

Page 5: Portable Paperless Recorder MV1000/MV2000nubilight.nubicom.co.kr › upload › datasheet › MV1000.pdf · Portable Paperless Recorder MV1000/MV2000 . The following product was discontinued

Easy-to-read DisplayEasy-to-read Display Smart Analysis

Incredibly clear LCD monitor.Improved monitor interface!

Incredibly clear wide-angle LCD monitor

With a wider viewing angle and a well-defined, vivid display, wehave dramatically improved the viewing experience.

We have also included brightness adjustment and screensaving features.

Conventional model MVAdvanced

Example screens

Display rate change Auto span display

Pause function High-speed scroll

Fine grid function Top display function

Relative time display Auto zone display

Full of display features you can use

Integral bar graph display

For example, when connecting to a flow meter or a powermonitor, you can use bar graphs to check integrated values!

Page 6: Portable Paperless Recorder MV1000/MV2000nubilight.nubicom.co.kr › upload › datasheet › MV1000.pdf · Portable Paperless Recorder MV1000/MV2000 . The following product was discontinued

Easy-to-read Display Smart AnalysisSmart Analysis

Improved PC compatibility ensures asmooth transition into data analysis!

Application software [DAQSTANDARD DXA120]

This is the software package that comes standard with the MVAdvanced.You can use your PC to analyze data saved on the MVAdvanced. You canalso arrange settings on your PC and download them to the unit.

DAQLOGGERA data logging softwareprogram that enables you touse the Ethernet and serial

communication simultaneously. You cancombine up to 32 machines, such as theMVAdvanced, DXAdvanced, DARWIN,and µR recorder for a total of 1600channels of data acquisition.

DAQEXPLORERThis is a software package that,on top of the features of theDAQSTANDARD package, also

has both file transfer and PC monitoringfunctions. You can easily make full use ofthe MVAdvanced’s wide range ofnetworking features.

Package software [DAQWORX]

DAQWORX is a software package that enables you to integrate the Yokogawa recorders, data loggers, and controllers in your dataacquisition system. DAQWORX enables you to build a system that can handle anything from small scale networks to distributed multi-channel data acquisition.

Text save mode

Data measured using the MV1000/MV2000 can be saved in textformat to a CF card or to USB memory. This enables you to viewdata directly without using dedicated software. If you areconcerned with security, the option to save data in binary formatis also available.

Page 7: Portable Paperless Recorder MV1000/MV2000nubilight.nubicom.co.kr › upload › datasheet › MV1000.pdf · Portable Paperless Recorder MV1000/MV2000 . The following product was discontinued

Hardware to ensure reliability

Rotatable handleDesigned for easy hand carrying. The rotatable handle allows for easy storage.

Storage media slots (CF Card and USB port)

CF card slotHighly-reliable, and easy-to-use CompactFlash cards serve as the external media. Up to 1GB CF cards are available as optional accessories.

USB slotUsing the USB interface, you can save data to USB memory. With easy-to-use USB memory, data transfer to a PC is simpler than ever.

Lightweight aluminum bodyFeaturing a lightweight aluminum case, the MV2000 is now 20% lighter than previous models.

MV2000MV1000

High-breakdown-voltage solid-state relays

MVAdvanced uses high-breakdown-voltage solid-state relays asscanners for switching input signals. These relays consist ofMOSFETs capable of withstanding high voltage (1500 V DC)with low leakage current (3 nA), and power-outputphotocouplers. They provide high-speed scanning (125 ms/48channels in the MV2048) while increasing scanner life andeliminating noise.

Isolated channel inputs

DC voltage and thermocoupleinputs in all MVAdvanced modelsare channel-isolated. (Channelisolation for RTD inputs isoptional on some models.) Thehigh common mode noisecharacteristic enabled byisolated channel inputs ensuresstable measurements in a widerange of applications.

Compliance with safety standards and EMC standards

Another indication of the reliability ofMVAdvanced is their compliancewith the stringent specifications forinternational safety and electromag-netic compatibility (EMC) standards.Of course, MVAdvanced have alsobeen approved for the CE stan-dards.

CSA: CSA22.2 No61010-1, installation categoryII, pollution degree 2UL: UL61010-1 (CSA NRTL/C)CE: EMC directive: EN61326 compliance (Emission: Class A, Immunity: Annex A)

EN61000-3-2 compliantEN61000-3-3 compliantEN55011 compliant, Class A Group 1

Low voltage directive: EN61010-1 compliant, measurement category II, pollutiondegree 2

C-Tick: AS/NZS CISPR11 compliant, Class A Group 1

Yokogawa EMC laboratory

Signal input circuit diagram(The dotted section are isolated.*)* If the three-wire isolated RTD option isspecified, the b terminal is also isolatedbetween channels.

A/DConverter

/A

/B

/b

/A

/B

/b

/A

/B

/b

Page 8: Portable Paperless Recorder MV1000/MV2000nubilight.nubicom.co.kr › upload › datasheet › MV1000.pdf · Portable Paperless Recorder MV1000/MV2000 . The following product was discontinued

Comprehensive network functions

We have made the network functions more comprehensive. In addition to e-mail, Web server, and FTP functions, this model comes with timesynchronization (SNTP), and automatic network configuration (DHCP). We have equipped this model with all of the latest network technology.

E-mail transmission functions

The MVAdvanced can send alarm information, periodicinstantaneous values, report data, and other information via e-mail. The MVAdvanced also features a POP Before SMTPfunction for transmission authentication.

Easy monitoring via Web browser

The MVAdvanced has Web server features that make it easy touse a Web browser, such as Internet Explorer, to monitor thedevice and retrieve files stored in internal memory.

Time synchronization (SNTP) function

By using the SNTP client function, you can synchronize thetime on the MVAdvanced to an SNTP server. You can also setup the MVAdvanced for use as an SNTP server.

A rich variety of options and accessories

The MVAdvanced features a rich variety of options and accessories. Get the most out of the MVAdvanced by combining these options andaccessories to suit your needs.

Modbus/RTU (RS-422/485 connection)

RS-422/485

Modbus master

UT/UP series controllerPower monitor

The data of slave units can be displayed and saved on the MVAdvanced using the Modbus RTU function*.* MATH option required

Up to 16 slaves can be connected

File transfer using FTP

With the MVAdvanced’s FTP server/client features, it is easy touse a fileserver for data sharing and centralized data manage-ment.

Automatic network configuration (DHCP)

The DHCP function makes it possible to set the IP Address andother network settings of the MVAdvanced automatically, thusmaking it easier to use the MVAdvanced on a network.

Modbus/TCP function Modbus/RTU function

You can connect the MVAdvanced to other devices and load/save data using the Modbus protocol.

In this type of setup, e-mail messages are sentthrough an existing mail server (SMTP server).

Internete-mail-capable

cellular phone

Mail reception

Sending e-mail using an existing mail system

Internet

MVAdvancedMail server

(SMTP server)Mail reception

LAN

Mail reception

FTP client function FTP server function

Files on storage media, including:- Display data files- Event data files- Report files

- Display data files- Event data files- Report files- Display image

files

FTP client

FTP servers

Primary SecondaryFTP servers

Service request

EthernetEthernet

LAN

Rechargeable battery model (MV1000 only)

The rechargeablebattery model isequipped with abattery that lasts forup to about 13 hours(3x times the durationof previous models).This enables you toacquire data in places where there is nopower supply. (Note: The maximum periodof continuous use will vary according tooperating conditions.)

Calculation functions

In addition to basic arithmetic, it ispossible to calculate the highest valuewithin a set time period, the lowest value,the average value, and the integratedvalue.The results of these calculations can beproduced in hourly, daily, or monthlyreports.

Block terminals (for use with clamp terminals)

These are remov-able terminals thatare useful whenconnecting anddisconnecting anykind of sensor.Extremely conve-nient for users whochange sensors frequently.

Vertical stand (MV1000 only)

A stand for installingthe MVAdvancedvertically. Convenientwhen you place theMVAdvanced on thefloor or other low-levelplaces.

Carrying case (MV1000/MV2000)

A soft carrying casefor the MVAdvanced.Useful for businesstrips and any othertime you changelocations.

Rack mounting bracket (MV1000/MV2000)

Bracket provided for installation on the 19-inch rack (JIS or ANSI).

Page 9: Portable Paperless Recorder MV1000/MV2000nubilight.nubicom.co.kr › upload › datasheet › MV1000.pdf · Portable Paperless Recorder MV1000/MV2000 . The following product was discontinued

Standard specifications

Input Range Measurement accuracy Display resolution(when the integration time is 16.7 ms or more)

DCV 1-5 V ±(0.05% of rdg+3 digits) 1 mV

Thermocouple* K ±(0.15% of rdg+0.7°C) 0.1°C

Resistance thermometer detector Pt100 ±(0.15% of rdg+0.3°C) 0.1°C

* Does not include the accuracy of reference junction compensation

Sample time(400 MB)

Sampling interval 1 sApprox. 148 days

5 sApprox. 2 years

10 sApprox. 4 years

60 sApprox. 24 years

120 sApprox. 48 years

125 msApprox.18 days

Max. savable data files: 400 (savable display data files and event data filescombined)

Manual save: Saves data files to the internal memory manually.You can save all data or only selected data.Destination drive: CF card or USB memory

Auto save: Save displayed data: Saves data to the CF card at aset intervalSave event data: Saves data to the CF card at a setinterval (in Free Trigger mode) Save when finishedsampling (when setting the trigger)

Data formats: When saving to external media, both event data anddisplay data can be saved in either binary or text for-mat (data is always stored to internal memory in bi-nary format).

Sampling interval: Display data: Varies according to the waveform up-date rateEvent data: User-set

Manual sample data: You can choose when to save measurement/MATH channel data files to the internal memoryor to a CF card.

Report data (only available if the unit is equipped with the calculation option):Saves calculation results as data files to a CF card atthe set times.

Types: Hourly, daily, hourly + daily, daily + weekly, daily +monthly

Trigger function: Data can be saved using Free mode or Trigger mode.When using Trigger mode, the user must set the datalength, pre-trigger, and trigger source.

Snapshot function: Saves the displayed screen image data to a CF card.Data file loading: Data files saved to a CF card or to USB memory (if

equipped with the USB option) can be loaded anddisplayed.Loading and saving setup data: Settings data can be savedand loaded in Binary format.

USB interface: USB specification 1.1 hostPorts: 2 (front and back)Connectable devices: Keyboards: 104 keyboards (US) compliant withUSB

HID Class Version 1.1109 keyboards (Japanese)External media: USB memory (not all types of USBmemory are guaranteed to work)

Alarm functionsAlarms settable per channel: 4Alarm types: High/low limit, delay high/low limit, difference high/low

limit, high/low limit on rate of changeDelay alarm time: Can be set according to channel (cannot be set

according to level)Range: 1 to 3600 seconds

Time intervals for the rate-of-change alarm:A factor of 1 to 32 times the measurement interval(applies to all channels)

Display: When an alarm occurs, the state (the alarm type) orcommon alarm state appears on the digital display

Event action functionDescription: A set action occurs in response to a set event.

Security functionsDescription: You can customize key lock and login security

functions for any transmission or keyboard command.Key Lock: Sets a password-protected key lock on all command

keys and FUNC screen operations.Login: Limits access to the MVAdvanced with a login that

prompts for username and password.Security levels and user numbers: System administrators: 5

General users: 30

Clock functionsClock: Comes with a calendar function (for the western

calendar)Clock accuracy: ±10 ppm (does not include the less than one second

delay that occurs when turning the power on)

Communication functions (Ethernet)Electrical specifications: IEEE 802.3 compliant (DIX frame)Transmission media: Ethernet (10BASE-T)Protocols implemented: TCP, UDP, IP, ICMP, ARP, DHCP, HTTP, FTP, SMTP,

SNTP, Modbus, and MV dedicated protocolE-mail transmission functions (E-mail client):

Automatically sends an e-mail in response to alarmsand other events.

Weight and dimensionsMV1000 external dimensions: 189 (W) 177 (H) 259 (D)MV1000 weight: Approx. 3.5 kg (MV1024)MV2000 external dimensions: 307 (W) 273 (H) 260 (D)MV2000 weight: Approx. 5.6 kg (MV2048)

Input componentsNumber of inputs: MV1000: 4, 6, 8, 12, or 24 channels

MV2000: 8, 10, 20, 30, 40 or 48 channelsMeasurement intervals: MV1004, MV1008, MV2008: 125 ms, 250 ms, or 25

ms in High-Speed modeMV1006, MV1012, MV1024, MV2010, MV2020, MV2030,MV2040, MV2048: 1 s (100 ms not possible for A/Dintegration time), 2 s, 5 s,or 125 ms in High-Speed mode* A/D integration time is fixed at 1.67 ms in High-Speed mode

Points to consider when using High-Speed mode:When using High-Speed mode (an A/D integrationtime of 1.67 ms) with the MVAdvanced, power supplynoise and other factors may cause the measuredvalues to fluctuate.If this is the case, then measure using Normal mode(an A/D integration time of 16.7 ms, 20 ms, or 100 ms).

Input types: DCV (DC voltage: 20, 60, 200 mV, 2, 6, 20, 50 V, 1-5 V)TC (thermocouple type: R, S, B, K, E, J, T, N, W, L,U, WRe)RTD (resistance temperature detector: Pt100, JPt100)DI (at the contact input or the TTL level)DCA (DC current; with external shunt resistor)

Measuring range, measurement accuracy, and display resolution by typical input type

DisplayDisplay device: MV1000: 5.5-inch TFT color LCD (320 240 dots)

MV2000: 10.4-inch TFT color LCD (640 480 dots)Note: The LCD may contain some pixels that arealways lighted or that never light, and variations inbrightness may occur due to the characteristics ofliquid crystals. Please note that these are not defects.

Display groups: Number of display groups:MV1000: 10 groups, MV2000: 36 groupsMaximum number of channels assignable per group:MV1000: 6 channels, MV2000: 10 channels

Displayed colors: Trend/bar graph display: 24 available colorsBackground: White or black

Trend display: Display types: Vertical, horizontal, horizontal wide,separated horizontal.

Bar graph display: Direction: Vertical or horizontalDigital display: Update rate: 1 sOverview display: Channel number: Displays a list of all measurement

and MATH channels along with their alarm states.Information display: Alarm Summary display, MessageSummary display, Memory Summary display, Reportdisplay, Relay Condition display, Modbus Conditiondisplay

Log display: Log display content: Log-in log, Error log, Trans-mission log, FTP log, Web log, E-mail log, SNTP log,DHCP log, Modbus log

Tag display: Max. displayable characters: 16Displayable characters: Alphanumeric characters

Message display: Max. displayable characters: 32Displayable characters: Alphanumeric charactersHistorical display function: Allows for the display ofdata stored to internal or external memory.

LCD screen saver function: You can to dim or turn OFF the LCD backlight ifthere are no keystrokes for a set time (1, 2, 5, 10, 30min, or 1 hour).

Display screen registration function:You can assign a name to a display screen andregister it.Max. registered screens: 8

Memory functionsExternal media: Media: Compact Flash (CF) cardInternal memory: Media: Flash memory

Memory size: 400 MBSample time: Examples of internal memory sample times (with the

MV1012 recording only event data files for 12measuring channels and no calculation channels).

Page 10: Portable Paperless Recorder MV1000/MV2000nubilight.nubicom.co.kr › upload › datasheet › MV1000.pdf · Portable Paperless Recorder MV1000/MV2000 . The following product was discontinued

Supply voltage With LCD screen saver on Normal use Maximum100 VAC 15 VA 30 VA 45 VA240 VAC 25 VA 40 VA 60 VA 12 VDC 7 VA 14 VA 24 VA

Supply voltage With LCD screen saver on Normal use Maximum100 VAC 28 VA 40 VA 65 VA240 VAC 38 VA 54 VA 90 VA 12 VDC 9 VA 18 VA 35 VA

MV1000 Rear panel MV2000 Rear panel

FTP client functions: Automatically sends data files to an FTP serverTransmittable files: Display data files, event data files,report data files, screen snapshot data files

FTP server functions: Can transfer and delete files, manipulate directories,and produce file lists remotely from a network computer.

Web server function: Displays MV screen images on a Web browser.SNTP client function: Queries a specified SNTP server for the time and

synchronizes with it.Time query methods: Set interval, start of memorysample, manual

SNTP server function: Transmits the MV time settings via SNTP protocol.DHCP client function: Automatically retrieves the network address settings

from a DHCP server.Information retrieved automatically:IP address, subnet mask, default gateway, DNSinformation

Modbus client function: Loads data from other devices using Modbus protocol.** The calculation option (/M1) or the external inputchannel option (/MC1) is required to load data.

Modbus server function: Data can be read from the MV using the Modbus protocol.

Batch functionDescription: Allows for data display, data management, text field

functions, and batch comment input using batches.

Power supplyAC power supply: Rated supply voltage: 100 to 264 VAC (auto switching)DC power supply: Rated supply voltage: 12 VDC/24 VDCAC power supply: Operating supply voltage range:

90 to 132, 180 to 264 VACDC power supply: Operating supply voltage range:

10.0 to 28.8 VDCPower consumptionMV1000 power consumption

MV2000 power consumption

Rechargeable battery drive Powered by a dedicated AC adapter or the dedicated Ni-(MV1000 only) MH battery pack.

The dedicated Ni-MH battery pack can only be chargedwhen connected to the main unit.If both the AC adapter and battery pack are connected,the AC adapter will be used.

Continuous operation time 13 hours maximum (room temperature) under thefollowing conditions: No USB connection; no optionterminals; LCD backlight saver: OFF; transition time:1 minute; external media saving: Auto-save.Continuous operation time differs according to variousconditions.

Normal operating conditionsSupply voltage: AC power supply: 90 to 132, 180 to 250 VAC

DC power supply: 10.0 to 28.8 VDCSupply frequency: 50 Hz±2%, 60 Hz±2%Ambient temperature: 0 to 40°CAmbient humidity: 20 to 80% RH (at 5 to 40°C)

Optional specifications Alarm output relays (/A1, /A2, /A3, /A4)

Activates the relay output on the rear panel when analarm occurs

Output points: Choose from 2, 4, 6, or 12** Only with the MV2000Not installable on the MV1008 or MV1024

Serial communication (/C2, /C3)Media: EIA RS-232 (/C2) and RS-422/485 (four-wire) (/C3)

compatibleProtocols implemented: The dedicated protocol and the Modbus (master/

slave) protocolSettings/measurement server functions:

Using the dedicated protocol, the following functionsare availableSettings and commands equivalent to the unit’s keycommands.Data output

Modbus master/slave functions: Loads data from other devices using Modbus protocol.** The calculation option (/M1) or the external input channel option (/MC1) is requiredto load data.

Fail/status output relay (/F1) Activates a relay output upon the detection of a CPUabnormality on the MV or a set condition.

Calculation functions (/M1) Performs calculations as well as displays and recordsthe trends or numeric values of calculation channels

listed below.Max. calculation channels: MV1004, MV1008: 12 channels

MV1006, MV1012, MV1024: 24 channelsMV2008: 12 channelsMV2010, MV2020, MV2030, MV2040, MV2048: 60channels

Max. equation length: 120 charactersCalculation types: General calculations: Basic arithmetic, square root,

absolute value, common logarithm, natural logarithm,exponent, power, relational operations (<, ≤, >, ≥, =,≠), logical operations (AND, OR, NOT, XOR)Statistical calculations: TLOG (maximum value,minimum value, average value, integrated value, andP-P value for time series data)CLOG (maximum value, minimum value, averagevalue, integrated value, and P-P value for a set channel)Special calculations: PRE, HOLD(a):b, RESET(a):b,CARRY(a):bConditional statement: [a?b:c]Max. settable constants: 60 (K01 to K60)

Report function: Report types: Hourly, daily, hourly + daily, daily +weekly, daily + monthlyCalculation types: Reports can be calculated using acombination of up to four of the following: Average,maximum value, minimum value, integrated value, andinstantaneous value.

Cu10/Cu25 RTD input/3-wire isolated RTD input (/N1)Enables the use of Cu10 and Cu25 inputs in additionto the standard inputs.

3-wire isolated RTD input (/N2)All RTD (resistance thermometer detector) terminals(A, B, and b) are isolated.Note: Only available with the MV1006, MV1012,MV2010, MV2020, MV2030, MV2040, and MV2048

External input (/N3) Enables the use of the following thermocouples andRTDs in addition to the standard inputs.TC: Kp vs Au7Fe, PLATINEL, PR40-20, NiNiMo, W/Wre26, TypeN(AWG14)RTD: Pt25, Pt50, Ni100(SAMA), Ni100(DIN), Ni120,J263*B, Cu53, Cu100

Remote control (/R1) The MV can be controlled through contact input (up to8 inputs can be set).

24 VDC transmitter power supply (/TPS2*, /TPS4*)Output voltage: 22.8 to 25.2 VDC (for rated current load)Rated output current: 4 to 20 mADCMaximum output current: 25 mADC (overcurrent protection level: approximately

68 mADC)* /TPS2 is only available for the MV1000, /TPS4 isonly available for the MV 2000

Pulse input (/PM1) Contact and open-collector pulse input is possiblethrough the use of special remote input terminals.The calculation functions (/M1) and remote control(R1) options are included in the pulse input option.Number of Inputs: 3 channels (however, if the remotecontrol input terminals are used for pulse input, thenup to 8 channels can be made available)Input methods: Photocoupler isolation (no isolationbetween channels)Internal isolated power supply (approx. 5 V)Input types: Dry contact, open collector (TTL or transistor)

Input value correction (/CC1) Ten-segment linearizer approximation can be used onevery measurement channel to correct input values.Settable broken-line points: 2 to 16

Channel expansion (/MC1, only available on the MV2000)You can use the Modbus master function to load datafrom other devices, and set data through the use ofcommunication input commands. Additional channelsare provided for communication input.Note 1: Only available with the MV2010, MV2020,MV2030, MV2040, and MV2048Note 2: When equipped with the external input channeloption, the High-Speed mode measurement interval isunavailable.Number of external input channels: 240 channels(channel numbers 201 to 440)

Page 11: Portable Paperless Recorder MV1000/MV2000nubilight.nubicom.co.kr › upload › datasheet › MV1000.pdf · Portable Paperless Recorder MV1000/MV2000 . The following product was discontinued

Unit : mm

NOTICE Before operating the product, read the user's manual thoroughly for proper

and safe operation. If this product is for use with a system requiring safeguards that directly

involve personnel safety, please contact the Yokogawa sales offices.

MV1000

Model code

MV1004MV1006MV1008 *9

MV1012MV1024 *9

Internal MemoryExternal MediaLanguage

Input Terminal

Power Supply

Power Cord

Options

Optionalcode

/A1/A2/A3/C2/C3/F1/M1/N1/N2/N3/R1/TPS2/PM1/CC1

Description

4 ch, 125 ms (Fast sampling mode: 25 ms)6 ch, 1 s (Fast sampling mode: 125 ms)8 ch, 125 ms (Fast sampling mode: 25 ms)12 ch, 1 s (Fast sampling mode: 125 ms)24 ch, 1 s (Fast sampling mode: 125 ms)400 MBCF card (with Media) + USBEnglish/German/FrenchKoreanClamped terminalScrew terminal (M4)100 VAC,240 VAC12 VDC *1

Rechargeable battery *1

Power cord UL/CSA StandardPower cord VDE StandardPower cord SAA StandardPower cord BS/PSB Standard *11

Power cord GB StandardPower cord EK Standard *10

without AC adapter, Power cord *2

Alarm output 2 points *3 *9

Alarm output 4 points *3 *9

Alarm output 6 points *3 *4 *9

RS-232 interface *5

RS-422/485interface *5

FAIL/Status output *4 *9

Mathematical functions Cu10, Cu25 RTD input/3 leg isolated RTD3 leg isolated RTD *6

Extended input type (PR40-20, Pt50, etc.)Remote control *9

24 VDC transmitter power supply (2 loops) *7 *9

Pulse input (including remote control and mathematical functions) *8 *9

Calibration correction function

*1 An AC adapter is included as a standard accessory. *2 W can be specified for only 12 VDC *3 /A1, /A2 and /A3 cannot be specified together. *4 /A3 and /F1 cannot be specified together. *5 /C2 and /C3 cannot be specified together. *6 /N2 can be specified for only MV1006, MV1012 and MV1024. *7 In case that /TPS2 is specified, /A2, /A3, /F1 and /PM1 cannot be specified together. *8 In case that /PM1 is specified, /A3, /M1, /R1 and /TPS2 cannot be specified together. And combination of /A2/F1 cannot

be specified together. *9 In case that MV1008, MV1024 is specified, /A1, /A2, /A3, /F1, /R1, /TPS2 and /PM1 cannot be specified. *10 In case that 100 VAC, 240 VAC is specified, P cannot be specified together. *11 BS standard is specified only 100 VAC,240 VAC

Suffix code

-3-4

-2-4

-1-2

-1-2-3

DFRQHPW

MV2000

Model code

MV2008MV2010MV2020MV2030MV2040MV2048Internal memoryExternal MediaDisplay Language

Input Terminal

Power Supply

Power Cord

Options

Optionalcode

/A1/A2/A3/A4/C2/C3/F1/M1/N1/N2/N3/R1/TPS4/PM1/CC1/MC1

Description

8 ch, 125 ms (Fast sampling mode: 25 ms)10 ch, 1 s (Fast sampling mode: 125 ms)20 ch, 1 s (Fast sampling mode: 125 ms)30 ch, 1 s (Fast sampling mode: 125 ms)40 ch, 1 s (Fast sampling mode: 125 ms)48 ch, 1 s (Fast sampling mode: 125 ms)400 MBCF card (with Media)+USBEnglish/German/FrenchKoreanClamped terminalScrew terminal (M4)100 VAC, 240 VAC12 VDC *1

Power cord UL/CSA StandardPower cord VDE StandardPower cord SAA StandardPower cord BS/PSB Standard *11

Power cord GB StandardPower cord EK Standard *10

without AC adapter, Power cord *2

Alarm output 2 points *3

Alarm output 4 points *3

Alarm output 6 points *3

Alarm output 12 points *3*4

RS-232 interface *5

RS-422/485interface *5

FAIL/Status output *4

Mathematical functionCu10,Cu25 RTD input /3 leg isolated RTD3 leg isolated RTD *6

Extended input type (PR40-20, Pt50, etc.)Remote control24 VDC transmitter power supply (4 loops) *7

Pulse input (including remote control and mathematical functions) *8

Calibration correction functionExternal input function *9

*1 An AC adapter is included as a standard accessory. *2 W can be specified for only 12 VDC*3 /A1, /A2, /A3 and /A4 cannot be specified together. *4 /A4 and /F1 cannot be specified together.*5 /C2 and /C3 cannot be specified together.*6 /N2 can be specified for only MV2010, MV2020, MV2030, MV2040 and MV2048.*7 In case that /TPS4 is specified, /A4 cannot be specified together. And combination of /A3/F1 cannot be specified together.*8 In case that /PM1 is specified, /A4, /M1, /R1 cannot be specified together. And combination of /A2/F1 and /A3/TPS4

cannot be specified together.*9 /MC1 can be specified for only MV2010, MV2020, MV2030, MV2040 and MV2048.*10 In case that 100 VAC, 240 VAC is specified, P cannot be specified together.*11 BS standard is specified only 100 VAC, 240 VAC

Suffix code

-3-4

-2-4

-1-2

-1-2

DFRQHPW

MODEL AND SUFFIX CODES

DIMENSIONS

STANDARD ACCESSORIES

Qty,151111 *1

1 *2

ProductDAQSTANDARDTerminal ScrewInstruction manual (First step guide: by paper)Instruction manual (Mainunit/commuication/DAQSTANDARD: CD-ROM)128 MB CF CARDPower cordAC adapter + Power cord

*1 100 VAC/240 VAC Power supply (When the “-1” Power supply specification code is specified)*2 12 VDC Power supply (When specified the “-2” Power supply specification code) or Rechargeable battery (When

specified the “-3” Power supply specification code)

ACCESSORIES

APPLICATION SOFTWARE

Model codeDXA120

DescriptionDAQSTANDARD

OSWindows2000, XP, Vista, 7

307

281

260

334

273

189 259

162.423

2

177

MV1000

MV2000Product

Shunt resistor(For screw input terminal)

Shunt resistor(For clamped input terminal)

CF card adapter (not including CFcard)CF CARD (not including adapter)

Soft carrying case

Rack mount bracket (JIS)Rack mount bracket (ANSI)Rack mount bracket (JIS)Rack mount bracket (ANSI)Vertical standBattery PackRemovable clamped input terminal

Code (Parts NO.)415920415921415922438920438921438922772090772093772094772095790501701964

B8805JUB8805JTB8806JUB8806JTB8805JLB8805HAA1923JT

Specification250Ω±0.1%100Ω±0.1%10Ω±0.1%

250Ω±0.1%100Ω±0.1%10Ω±0.1%

512 MB1 GB2 GB

For MV1000For MV2000For MV1000For MV1000For MV2000For MV2000For MV1000

Using for Battery modelfor 2 channels