16
1 Essential Expertise for Water, Energy and Air Essential Expertise for Water, Energy and Air SM SM Essential Expertise for Water, Energy and Air Environmental Sustainability through the use of Nalco 3D TRASAR Technology for Sea Water Cooling tower Water Arabia Bahrain Feb 2011

Postch frederic - SAWEA · 2013. 2. 9. · Title: Microsoft PowerPoint - Postch_frederic Author: User Created Date: 2/13/2011 8:26:25 AM

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

  • 1Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    Essential Expertise for Water, Energy and Air

    Environmental Sustainability through the use of Nalco 3D TRASAR Technology for Sea

    Water Cooling tower

    Water Arabia Bahrain Feb 2011

  • 2Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    Sustainability

    Lasting environmental performance improvements generate economic and social benefits.

    • Asset Reliability and Protection

    • Production Efficiency• Process Throughput• Process Improvement• Health, Safety and Env.

    Compliance• Consistent cost focus Financial Performance

    Revenue/ Capital

    Standards Compliance

    Voluntary Mandatory / License to operate

    Resource Management

    Renewable/Non-Renewable

  • 3Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    Nalco is Uniquely Positioned to Improve Sustainability

    • Providing customers with solutions that are technically, economically and environmentally sustainable has been integral to Nalco’s business offerings since our founding in 1928 and explicit in our mission for many years.

    • A recent example for cooling systems:

  • 4Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    Sea Water Cooling Towers

    • Key reasons to install a sea water cooling tower:– Reduce water make up and discharge flows– Reduce thermal discharge pollution

    • Seawater cooling towers are normally operated at 1.2 – 1.6 cycles because a significant reduction of water consumption occurs in this cycle range providing important savings in pumping costs of 2-4 $cents/m3 ( based on pump efficiency, power costs, suction and discharge pressures ).

  • 5Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    Low Stress Causes:

    • High water usage because of low cycles of concentration

    – High make-up water consumption– High blow-down losses

    • High energy usage– Increased pumping costs etc– Larger CO2 Footprint

    • High treatment chemical usage– Compliance considerations– Excessive treatment costs

  • 6Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    Excessively High Stress Causes:

    • Corrosion

    • Scale

    • Deposition/Fouling

    • Microbiological Growth

  • 7Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    Optimize Stress, Minimize Cost and Environmental Impact

    Environmental Impact/Total

    Cost of Operation

    (TCO) System Stress

    Minimum TCO & Env Impact

    High Stress = operational problems

    Low Stress = high operating costs

  • 8Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    Parameter Value Remarks

    Cycles of Concentration

    1.2 – 1.6/1.7* Operation at >1.5 requires advanced scale control

    Alkalinity 200 - 225 ppm maxas CaCO3

    Depends on makeup alkalinity, cycles, acid feed.

    Skin temperature 65°C max Higher temp. require specific treatment to control potential precipitation of Mg(OH)2 and/or CaSO4

    Flow velocity 1 - 2.5 m/s Depending on erosion resistance of the metallurgy

    Reynolds number 30000-60000 Low values promote the deposition of suspended solids

    Suspended solids < 8 mg/l or < 15 mg/l For film fill and splash fill, respectively

    Typical Operating Conditions:Sea Water Cooling Towers

  • 9Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    System Considerations: Cycles on Water Usage

    Water Usage vs. Cycles of Concentrationfor 26,850 m3/hr & 7 C Temp Rise

    0

    500

    1000

    1500

    2000

    2500

    3000

    1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0

    Cycles

    m3

    / hou

    r

    Evaporation Make Up Total Blowdown

    -31% Make Up-48% Blowdown

    - Pumping Cost Reduction- Chemical Use Reduction- Lower Impact on Marine Environment

  • 10Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    Sea Water Scale

    • Seawater is naturally very stable; but severe scaling problems may occur as temperature and cycles increase.

    • Scale control requirements vary with the operating conditions:– Cycles of Concentration– Temperature– pH– Alkalinity– Water velocity– Suspended solids

  • 11Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    Predicting Scale Formation in Sea Water

    • Traditional scaling indices do not apply to sea water.

    • Nalco Research developed a new application model for seawater scale inhibition.– Accurate calculations of scale saturation indices.– Calculation of inhibitor dose requirements based on research

    testing and field experience.

  • 12Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    Scale InhibitorAutomation & Control

    • Sea water recirculating cooling system operate with high blow down rate and low cycles

    • Scale inhibitor is applied at a very low dosage – 0.5 – 5 ppm as product / Make up

    • An automated control system is needed to assure the right amount of scale inhibitor is fed into the system while maintaining the optimum cycles of concentration– 3D Trasar® system enables treatment on demand– 3D Trasar® system provides continuous on line analyses of

    water parameters– 3D Trasar® automatically follow changes in load

  • 13Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    Scale control Management

    Continuous measurement of the inhibitor level, and control of the injection.

    Conventional Water treatment

    Inhibitor consumption

    3D TRASAR

    Time

  • 14Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    3D TRASAR

    3D TRASARFluorometer

    pH en ORP probes

    Conductivity probe

    Corrosion probes

    Measured and logged parameters:

    • pH• ORP• Conductivity• Corrosion rate Steel and Copper• Temperature• Turbidity• Inert Trasar (Total dosed product)• Fouling fluorometer• 4 x 4-20 external mA signal

    All parameters can be transferred on line to any computer, desk top, lap top or mobile phone via land line or satellite

    communications for constant and instant monitoring and alert messages

  • 15Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    Example: 10,000 m3/h recirculation rate and 5 deg C delta T cooling tower

    Make up water pumping cost, in $/year

    0

    50,000

    100,000

    150,000

    200,000

    250,000

    300,000

    350,000

    400,000

    1.05 1.10 1.15 1.20 1.25 1.30 1.35 1.40 1.45 1.50

    Cycles of concentration

  • 16Essential Expertise for Water, Energy and AirEssential Expertise for Water, Energy and AirSMSM

    3DTrasar on Sea Water Cooling Towers

    By providing constant, accurate and online monitoring and control of the inhibitor levels in the Sea Water, 3DTrasar generates important savings in energy and chemicals consumptions while maintaining the integrity of the system.