AReport
onPotential and Current
TransformersBy
Rupak bhattacharjeeA report submitted in partial fulfillment of the
requirement of ee-592: technical report writing
Supreme knowledge foundation group of institutions
(approved byaicte and affiliated to wbut)1, khan road, p. o.- mankundu (chandannagar),
Hooghly-712139, w.b.
Year- 2012-2013
7/28/2019 Potential and Current Rup
2/18
Transformer
A transformer is a device that transfers electrical energy from one circuit to another
through inductively coupled conductorsthe transformer's coils. A varying current in the
first or primary winding creates a varying magnetic flux in the transformer's core, and thus avarying magnetic field through the secondary winding. This varying magnetic field induces a
varying electromotive force (EMF) or " voltage" in the secondary winding. This effect is
called mutual induction.
Figure 1: Transformer-Basic Construction
If a load is connected to the secondary, an electric current will flow in the secondary
winding and electrical energy will be transferred from the primary circuit through thetransformer to the load. In an ideal transformer, the induced voltage in the secondary
winding (Vs) is in proportion to the primary voltage (Vp), and is given by the ratio of the
number of turns in the secondary (Ns) to the number of turns in the primary (Np) as follows:
7/28/2019 Potential and Current Rup
3/18
By appropriate selection of the ratio of turns, a transformer thus allows an alternating
current (AC) voltage to be "stepped up" by making Ns greater than Np, or "stepped down"
by making Ns less than Np. In the vast majority of transformers, the coils are wound around
a ferromagnetic core, air-core transformers being a notable exception.
Transformers come in a range of sizes from a thumbnail-sized coupling transformer hidden
inside a stage microphone to huge units weighing hundreds of tons used to interconnect
portions of national power grids. All operate with the same basic principles, although the
range of designs is wide. While new technologies have eliminated the need for transformers
in some electronic circuits, transformers are still found in nearly all electronic devices
designed for household ("mains") voltage. Transformers are essential for high voltage power
transmission, which makes long distance transmission economically practical.
7/28/2019 Potential and Current Rup
4/18
Instrument transformers
Instrument transformers are used for measuring voltage and current in electrical power
systems, and for power system protection and control. where a voltage or current is too
large to be conveniently used by an instrument, it can be scaled down to a standardized, low
value. Instrument transformers isolate measurement, protection and control circuitry from
the high currents or voltages present on the circuits being measured or controlled.
Figure 2: Current transformers, designed for placing around conductors
A current transformer is a transformer designed to provide a current in its secondary coil
proportional to the current flowing in its primary coil.
Voltage transformers(VTs), also referred to as "potential transformers"(PTs), are designed
to have an accurately-known transformation ratio in both magnitude and phase, over a
range of measuring circuit impedances. A voltage transformer is intended to present a
negligible load to the supply being measured. The low secondary voltage allows protective
relay equipment and measuring instruments to be operated at lower voltages.
Both current and voltage instrument transformers are designed to have predictable
characteristics on overloads. Proper operation of over-current protection relays requires
that current transformers provide a predictable transformation ratio even during a short
circuit.
7/28/2019 Potential and Current Rup
5/18
Potential Transformer (PT)
The instrument potential transformer (PT) steps down voltage of a circuit to a low value
that can be effectively and safely used for operation of instruments such as ammeters,
voltmeters, watt meters, and relays used for various protective purposes.
Figure3: A Potential Transformer (PT)
Potential transformers can be used with voltmeters for voltage measurements or they can
be used in combination with current transformers for watt-meter or watt-hour meter
measurements. They are used also to operate protective relays and devices, and for many
other applications, since they are used in a monitoring capacity, they generally require much
greater accuracy in design.
Potential Transformer is designed for monitoring single-phase and three-phase power line
voltages in power metering applications. The primary terminals can be connected either inline-to-line or in line-to-neutral configuration.
A Potential Transformer is a special type of transformer that allows meters to take
readings from electrical service connections with higher voltage(potential) than the meter is
normally capable of handling without at potential transformer.
7/28/2019 Potential and Current Rup
6/18
Potential transformers are designed to provide as accurate a voltage step-down ratio as
possible. To aid in precise voltage regulation, loading is kept to a minimum: the voltmeter is
made to have high input impedance so as to draw as little current from the PT as possible.
As you can see, a fuse has been connected in series with the PTs primary winding, for safety
and ease of disconnecting the PT from the circuit.
A standard secondary voltage for a PT is 120 volts AC, for full-rated power line voltage. The
standard voltmeter range to accompany a PT is 150 volts, full-scale. PTs with custom
winding ratios can be manufactured to suit any application. This lends itself well to industry
standardization of the actual voltmeter instruments themselves, since the PT will be sized to
step the system voltage down to this standard instrument level.
The potential transformer is designed for measuring the voltages ranging in kV or even
higher. The simple voltmeters may easily burn upon measuring these voltages. So these
transformers are designed to eliminate this harm and successfully recording the powersystem voltages.
7/28/2019 Potential and Current Rup
7/18
Principle of operation
The standards define a voltage transformer as one in which "the secondary voltage is
substantially proportional to the primary voltage and differs in phase from it by an angle
which is approximately zero for an appropriate direction of the connections."
This, in essence, means that the voltage transformer has to be as close as possible to the
"ideal" transformer. In an "ideal" transformer, the secondary voltage vector is exactly
opposite and equal to the primary voltage vector, when multiplied by the turns-ratio.
In a "practical" transformer, errors are introduced because some current is drawn for themagnetization of the core and because of drops in the primary and secondary windings due
to leakage reactance and winding resistance. One can thus talk of a voltage error, which is
the amount by which the voltage is less than the applied primary voltage, and the phase
error, which is the phase angle by which the reversed secondary voltage vector is displaced
from the primary voltage vector.
7/28/2019 Potential and Current Rup
8/18
The Task of Measuring Voltage
In the world of electricity, the typical measurement is that of voltage. A volt meter will
measure the voltage, usually within a range of up to hundreds of volts. In the power
industry, the transmission of electricity occurs at thousands and tens of thousands of volts.
This would destroy nearly all typical voltmeters. How then, do technicians measure the high
voltages they encounter every day? The trick is to use a potential transformer.
The Potential Transformer
The potential transformer works along the same principle of other transformers. It
converts voltages from high to low. It will take the thousands of volts behind power
transmission systems and step the voltage down to something that meters can handle.
These transformers work for single and three phase systems, and are attached at a point
where it is convenient to measure the voltage.
What Gives a Transformer Potential?
The biggest feature that a potential transformer has over regular transformers is the
voltage conversion is constant and linear. That is to say, if the first day of operation 50,000
volts is stepped to 50 volts, then on the last day of operation 50,000 steps to 50 volts.
Linearity states that when the voltage drops in a linear fashion, then the stepped down
voltage drops accordingly. This feature ensures that the meter will scale accordingly. The
potential transformer makes the measure of very high voltages much easier.
7/28/2019 Potential and Current Rup
9/18
Applications
The potential transformers that we manufacture are widely used to scale down the line to
neutral voltage of Wye (Y) system or the line-to-line voltage of a Delta system to the rated
input scale of the meter (typically 120 V).
Transformers can also be used in electrical instrumentation systems. Due to transformers'
ability to step up or step down voltage and current, and the electrical isolation they provide,
they can serve as a way of connecting electrical instrumentation to high-voltage, high
current power systems.
They are used in the transmission lines for the purpose of voltage measurement, power
metering, and the protection of the lines.
The potential transformers (like the current transformers) are used for the substation
service.
7/28/2019 Potential and Current Rup
10/18
Current Transformer (CT)
The instrument current transformer (CT) steps down the current of a circuit to a lower
value and is used in the same types of equipment as a potential transformer. This is done by
constructing the secondary coil consisting of many turns of wire, around the primary coil,
which contains only a few turns of wire. In this manner, measurements of high values of
current can be obtained. A current transformer should always be short-circuited when not
connected to an external load. Because the magnetic circuit of a current transformer is
designed for low magnetizing current when under load, this large increase in magnetizing
current will build up a large flux in the magnetic circuit and cause the transformer to act as a
step-up transformer, inducing an excessively high voltage in the secondary when under no
load.
Figure 4: A simple Current Transformer (CT)
Because CTs are designed to be powering ammeters, which are low-impedance loads, and
they are wound as voltage step-up transformers, they should never, ever be operated with
an open-circuited secondary winding. Failure to heed this warning will result in the CTproducing extremely high secondary voltages, dangerous to equipment and personnel alike.
To facilitate maintenance of ammeter instrumentation, short-circuiting switches are often
installed in parallel with the CT's secondary winding, to be closed whenever the ammeter is
removed for service: (Figure 5)
7/28/2019 Potential and Current Rup
11/18
Figure 5: Short-circuit switch allows ammeter to be removed from an active current
transformer circuit.
Though it may seem strange to intentionally short-circuit a power system component, it is
perfectly proper and quite necessary when working with current transformers.
The reason why a current transformer is used in place of the ordinary ammeter (current
measuring device), is that the ammeter cannot measure the very high amounts of current in
the high voltage (HV) applications. Therefore there is a need for an instrument that can
measure the high values of currents without any harm or burning of the device itself.
7/28/2019 Potential and Current Rup
12/18
Principle of operation
A current transformer is defined as "as an instrument transformer in which the secondarycurrent is substantially proportional to the primary current (under normal conditions of
operation) and differs in phase from it by an angle which is approximately zero for an
appropriate direction of the connections."This highlights the accuracy requirement of the
current transformer but also important is the isolating function, which means no matter
what the system voltage the secondary circuit need be insulated only for a low voltage.
The current transformer works on the principle of variable flux. In the "ideal" current
transformer, secondary current would be exactly equal (when multiplied by the turns-ratio)
and opposite to the primary current. But, as in the voltage transformer, some of the primary
current or the primary ampere-turns is utilized for magnetizing the core, thus leaving less
than the actual primary ampere turns to be "transformed" into the secondary ampere-turns.
This naturally introduces an error in the transformation. The error is classified into two-the
current or ratio error and the phase error.
7/28/2019 Potential and Current Rup
13/18
Applications
The current transformers are used for control circuits as well as for instrumentation in
high current power applications.
These transformers can be used to detect single-phasing on a three phase power system.
If one phase of the power line to a three phase motor becomes defective, the motor would
run under increased current and stress. The current transformer on each phase could detect
the loss of current in the line and open a control relay to take the motor off the circuit.
The current transformers perform the roles for safety protection and current limiting.
They can be used for the current monitoring of the power systems, when the current
reaches a specified level. Current monitoring is necessary at frequencies from the 50 Hz/60
Hz power line to the higher frequencies of transformers that range into the hundreds of kHz.
7/28/2019 Potential and Current Rup
14/18
Basic Difference between the PT & CT
The potential transformers are used as the high voltage voltmeters, as the ordinary
voltmeters. The current transformers are used in place of the ordinary ammeters, to
measure the high values of the currents in the high voltage power applications.
There are several different windings of the primary in the potential transformer. But in
the current transformer, there is only the single winding i.e. the main live line.
PT is used to step-down the higher magnitudes of the power transmission voltages,
stepping-up the current. On the other hand, the CT steps-down the high values of currents
and steps-up the voltage at the same time.
There is one potential transformer required for the three phase transmission line. But for
the same three phase line, three current transformers are needed, one on each phase.
7/28/2019 Potential and Current Rup
15/18
Summary
Transformers can be used to transform impedance as well as voltage and current. When
this is done to improve power transfer to a load, it is called impedance matching.
A Potential Transformer (PT) is a special instrument transformer designed to provide a
precise voltage step-down ratio for voltmeters measuring high power system voltages.
A Current Transformer (CT) is another special instrument transformer designed to step
down the current through a power line to a safe level for an ammeter to measure.
Transformers can be used in electrical instrumentation systems and for the protection
purposes.
The current transformers are used for control circuits as well as for instrumentation in
high current power applications. They can also be used to detect single-phasing on a three
phase power system. The current transformers perform the roles for safety protection and
current limiting.
7/28/2019 Potential and Current Rup
16/18
ACKNOWLEDGEMENT
I have no appreciating words to express my sincere thanks to my parents and my family
members who have made unbelievable sacrifice while I snatched away valuable time and
money from them throughout this period of time.
I deem it is a pleasure to express my deep gratitude and grateful thanks to Mr. Shiladitya
Sarkar, Lecturer, Department of Electrical Engineering, Sir J. C. Bose School of Engineering,
Supreme Knowledge Foundation Group of Institutions, Mankundu, Hooghly, who directed
me through her timely advice which eased my task of completing this Technical Report.
I also express my thanks to all my classmates for their continuous inspiration and help.
Finally, I am indebted to Professor (Dr.) B. N. Biswas, Chairman (Educational Division) of
Supreme Knowledge Foundation Group of Institutions, Mankundu, for the inspiration I
received from him.
7/28/2019 Potential and Current Rup
17/18
STATEMENTS BY THE CANDIDATE
RUPAK BHATTACHARJEE, B. Tech, 3rd
year
Department of Electrical Engineering
Sir J. C. Bose School of Engineering
Mankundu, Hooghly.
I hereby state that the Technical Report on POTENTIAL AND CURRENT TRANSFORMER
is a report done by me as a part of the Technical Report Writing: EE- 592 during the period
July12- December12.
Signature
(RUPAK BHATTACHARJEE)
7/28/2019 Potential and Current Rup
18/18
STATEMENTS BY THE SUPERVISER
Mr. SHILADITYA SARKAR,M. Tech (Electrical Engineering)
Lecturer
Department of Electrical Engineering
Sir J. C. Bose School of Engineering
Mankundu, Hooghly.