Contents Description Page Table 1. Revision notes ................................................................ 4 Table 2. Circuit breaker catalog number convention.......................................... 5 Table 3. Electronic trip unit catalog number convention....................................... 6 Table 4. Thermal magnetic trip unit catalog number convention ................................ 6 Table 5. Symmetrical RMS interruption ratings I cu (kA) for each breaker frame ..................... 7 Table 6. Curve notes .................................................................. 7 Labels Figure 1. Power Defense frame 2 trip unit front labels. ....................................... 8 Curves Figure 2. PXR 20D / PXR 25 - I 2 t long delay and flat short delay for 200A - 250A frames. ............ 9 Figure 3. PXR 20D / PXR 25 - I 2 t long delay and flat short delay for 60A - 160A frames.. . . . . . . . . . . . . 10 Figure 4. PXR 20 - I 2 t long delay and flat short delay for 200A - 250A frames. .................... 11 Figure 5. PXR 20 - I 2 t long delay and flat short delay for 60A - 160A frames. .................... 12 Figure 6. PXR 20D / PXR 25 - I 2 t long delay and I 2 t short delay for all frames..................... 13 Figure 7. PXR 20 I 2 t long delay and I 2 t short delay for all frames. . .............................. 14 Figure 8. PXR 20D / PXR 25 - I 4 t long delay and flat short delay for 200A - 250A frames. ........... 15 Figure 9. PXR 25 - I 4 t long delay and flat short delay for 60A - 160A frames. .................. 16 Figure 10. PXR 20D / PXR 25 ground (earth) flat delay . ...................................... 17 Figure 11. PXR 20D / PXR 25 -ground (earth) I 2 t delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Figure 12. PXR 20 - ground (earth) flat delay . ............................................. 19 Figure 13. PXR 20 - ground (earth) I 2 t delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Figure 14. PXR 20D / PXR 25 - instantaneous and override for 60A frame. . ...................... 21 Figure 15. PXR 20D / PXR 25 - instantaneous and override for 100A frame. . ..................... 22 Figure 16. PXR 20D / PXR 25 - instantaneous and override for 150A frame. . ..................... 23 Figure 17. PXR 20D / PXR 25 - instantaneous and override for 225A frame. ..................... 24 Figure 18. PXR 20D / PXR 25 - Instantaneous and override for 63A frame. . . . . . . . . . . . . . . . . . . . . . 25 Figure 19. PXR 20D / PXR 25 - instantaneous and override for 100A frame. . .................... 26 Figure 20. PXR 20D / PXR 25 -instantaneous and override for 160A frame. ..................... 27 Figure 21. PXR 20D / PXR 25 - instantaneous and override for 200A frame. . .................... 28 Effective December 2019 Supersedes February 2019 Technical Data TD012064EN Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

ContentsDescription Page

Table 1. Revision notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Table 2. Circuit breaker catalog number convention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Table 3. Electronic trip unit catalog number convention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Table 4. Thermal magnetic trip unit catalog number convention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Table 5. Symmetrical RMS interruption ratings Icu (kA) for each breaker frame . . . . . . . . . . . . . . . . . . . . . 7Table 6. Curve notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Labels Figure 1. Power Defense frame 2 trip unit front labels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Curves Figure 2. PXR 20D / PXR 25 - I2t long delay and flat short delay for 200A - 250A frames. . . . . . . . . . . . . 9Figure 3. PXR 20D / PXR 25 - I2t long delay and flat short delay for 60A - 160A frames.. . . . . . . . . . . . . 10Figure 4. PXR 20 - I2t long delay and flat short delay for 200A - 250A frames. . . . . . . . . . . . . . . . . . . . . 11Figure 5. PXR 20 - I2t long delay and flat short delay for 60A - 160A frames. . . . . . . . . . . . . . . . . . . . . 12Figure 6. PXR 20D / PXR 25 - I2t long delay and I2t short delay for all frames. . . . . . . . . . . . . . . . . . . . . 13Figure 7. PXR 20 I2t long delay and I2t short delay for all frames. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Figure 8. PXR 20D / PXR 25 - I4t long delay and flat short delay for 200A - 250A frames. . . . . . . . . . . . 15

Figure 9. PXR 25 - I4t long delay and flat short delay for 60A - 160A frames. . . . . . . . . . . . . . . . . . . 16Figure 10. PXR 20D / PXR 25 ground (earth) flat delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Figure 11. PXR 20D / PXR 25 -ground (earth) I2t delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Figure 12. PXR 20 - ground (earth) flat delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Figure 13. PXR 20 - ground (earth) I2t delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Figure 14. PXR 20D / PXR 25 - instantaneous and override for 60A frame. . . . . . . . . . . . . . . . . . . . . . . . 21Figure 15. PXR 20D / PXR 25 - instantaneous and override for 100A frame. . . . . . . . . . . . . . . . . . . . . . . 22Figure 16. PXR 20D / PXR 25 - instantaneous and override for 150A frame. . . . . . . . . . . . . . . . . . . . . . . 23Figure 17. PXR 20D / PXR 25 - instantaneous and override for 225A frame. . . . . . . . . . . . . . . . . . . . . . 24Figure 18. PXR 20D / PXR 25 - Instantaneous and override for 63A frame. . . . . . . . . . . . . . . . . . . . . . 25Figure 19. PXR 20D / PXR 25 - instantaneous and override for 100A frame. . . . . . . . . . . . . . . . . . . . . . 26Figure 20. PXR 20D / PXR 25 -instantaneous and override for 160A frame. . . . . . . . . . . . . . . . . . . . . . 27Figure 21. PXR 20D / PXR 25 - instantaneous and override for 200A frame. . . . . . . . . . . . . . . . . . . . . . 28

Effective December 2019Supersedes February 2019Technical Data TD012064EN

Time current curves Power Defense MCCBFrame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

Page 2: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

2

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 22. PXR 20D / PXR 25 - instantaneous and override for 250A frame. . . . . . . . . . . . . . . . . . . . . . 29Figure 23. PXR 20 / PXR 10 - instantaneous and override for 60A frame. . . . . . . . . . . . . . . . . . . . . . . . 30Figure 24. PXR 20 / PXR 10 - instantaneous and override for 100A frame. . . . . . . . . . . . . . . . . . . . . . . 31Figure 25. PXR 20 / PXR 10 - instantaneous and override for 150A frame. . . . . . . . . . . . . . . . . . . . . . . 32Figure 26. PXR 20 / PXR 10 - instantaneous and override for 225A frame. . . . . . . . . . . . . . . . . . . . . . . . 33Figure 27. PXR 20 / PXR 10 - instantaneous and override for 63A frame. . . . . . . . . . . . . . . . . . . . . . . . . 34Figure 28. PXR 20 / PXR 10 - instantaneous and override for 100A frame. . . . . . . . . . . . . . . . . . . . . . . . 35Figure 29. PXR 20 / PXR 10 - instantaneous and override for 160A frame. . . . . . . . . . . . . . . . . . . . . . . . 36Figure 30. PXR 20 / PXR 10 - instantaneous and override for 200A frame. . . . . . . . . . . . . . . . . . . . . . . . 37Figure 31. PXR 20 / PXR 10 - instantaneous and override for 250A frame. . . . . . . . . . . . . . . . . . . . . . . . 38Figure 32. PXR 10 LSI profile for short flat curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Figure 33. PXR 10 LSI profile for I2t short curves.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Figure 34. PXR 10 LI style 60A frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Figure 35. PXR 10 LI style 100A frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Figure 36. PXR 10 LI style 150A frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Figure 37. PXR 10 LI style 225A frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44Figure 38. PXR 10 LI style 63A frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45Figure 39. PXR 10 LI style 100A frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46Figure 40. PXR 10 LI style 160A frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Figure 41. PXR 10 LI style 200A frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Figure 42. PXR 10 LI style 250A frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Figure 43. 15A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Figure 44. 20A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Figure 45. 25A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Figure 46. 30A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Figure 47. 35A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

Figure 48. 40A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Figure 49. 45A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Figure 50. 50A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57Figure 51. 60A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58Figure 52. 70A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59Figure 53. 80A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60Figure 54. 90A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61Figure 55. 100A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Figure 56. 110A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63Figure 57. 125A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64Figure 58. 150A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65Figure 59. 15A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66Figure 60. 20A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Figure 61. 25A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68Figure 62. 30A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69Figure 63. 35A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70Figure 64. 40A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71Figure 65. 45A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72Figure 66. 50A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73Figure 67. 60A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74Figure 68. 70A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75Figure 69. 80A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76Figure 70. 90A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77Figure 71. 100A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78Figure 72. 110A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79Figure 73. 125A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80Figure 74. 150A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81Figure 75. 175A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

Page 3: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

3

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 76. 200A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83Figure 77. 225A fixed thermal fixed magnetic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84Figure 78. 160A/200A/250A adjustable thermal and adjustable magnetic. . . . . . . . . . . . . . . . . . . . . . . . 85Figure 79. 240V let-through current 150A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86Figure 80. 240V let-through energy 150A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .87Figure 81. 240V let-through current 225A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88Figure 82. 240V let-through energy 225A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89Figure 83. 415V-480V let-through current 225A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90Figure 84. 600V let-through current 150A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91Figure 85. 600V let-through energy 150A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92Figure 86. 600V let-through current 225A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93Figure 87. 600V let-through energy 225A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

Page 4: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

4

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Table 1. Revision notes

ote: N Unless noted below, all curves remain unchanged from their prior revision.

Revision Curve number Page Date1 Power Defense frame 2 initial release 02/15/2019

2 Short delay time tolerance changes on PXR curves. Updated let through curves. 12/2019

Page 5: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

5

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

This information is provided only as an aid to understand the catalog numbers.

It is not to be used to build catalog numbers for circuit breakers or trip units as all combinations may not be available.

Table 2. Circuit breaker catalog number convention

ote: N IEC standard breakers include the CE mark; GB standard breakers include the CCC mark.

Poles

1 = 1 pole

2 = 2 pole

3 = 3 pole

4 = 4 pole with 100% neutral protection

6 = 4 pole with 60% neutral protection

0 = 4 pole with 0% neutral protection

Interrupting rating designator

kA at 480 V (UL)

IA at 415 V (IEC)

F = 25 25

G = 35 35

K = 50 50

M = 65 70

N = 85 70

P = 100 100

Continous current rating

0015 = 15 A

0020 = 20 A

0025 = 25 A

0030 = 30 A

0035 = 35 A

0040 = 40 A

0045 = 45 A

0050 = 50 A

0060 = 60 A

0063 = 63 A IEC only

0070 = 70 A

0080 = 80 A

0090 = 90 A

0100 = 100 A

0110 = 110 A

0125 = 125 A

0150 = 150 A

0160 = 160 A IEC only

0175 = 175 A

0200 = 200 A

0225 = 225 A

0250 = 250 A IEC only

Terminals included

N = No terminals

J = Line and load terminals

K = Line only terminals

L = Load only terminals

ETU trip unit style

B = PXR 10

E = PXR 20

D = PXR 200

P = PXR 25Thermal magnetic style

T = Thermal

V = Thermal 50° C calibrated

Breaker family

PDG2 = Frame 2 Global UL / CSA / IEC / GB

PDF2 = Frame 2 Global-100% UL / CSA / IEC / GB (uses PDG trip units)

PDD2 = Frame 2 IEC / GB

PDC2 = Frame 2 IEC / GB

PDC9 = Frame 9 IEC / GB

PDG2 3 M 0225 P 2 M J

Features

N = None

R = Relays

Z = ZSI

M = Modbus

C = CAM interface

D = Modbus & CAM interface

W = ZSI & Modbus

X = ZSI & CAM interface

Y = ZSI, Modbus, & CAM interface

Magnetic Protection

A = Adjustable magnetic

F = Fixed magnetic

ETU protection style

1 = LI

2 = LSI

3 = LSIG

4 = LSI ARMS

5 = LSIG ARMSThermal magnetic style

F = Thermal

A= Thermal 50° C calibrated

Page 6: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

6

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Table 3. Electronic trip unit catalog number convention

ote: N IEC standard breakers include the CE mark; GB standard breakers include the CCC mark.

This information is provided only as an aid to understand the catalog numbers.

It is not to be used to build catalog numbers for circuit breakers or trip units as all combinations may not be available.

Table 4. Thermal magnetic trip unit catalog number convention

ote: N IEC standard breakers include the CE mark; GB standard breakers include the CCC mark.

Poles

3 = Electronic

4 = Electronic

Trip unit

PXR = Electronic Ampere frame rating

0060 = 60 A frame

0063 = 63 A frame IEC only

0100 = 100 A frame

0150 = 150 A frame

0160 = 160 A frame IEC only

0200 = 200 A frame

0225 = 225 A frame

0250 = 250 A frame IEC only

ETU trip unit style

B = PXR 10

E = PXR 20

D = PXR 200

P = PXR 25

Stlye family

PDG2 = Frame 2 Global UL / CE / CSA / CCC

PDC2 = Frame 2 CE / CCC

Features

N = None

R = Relays

Z = ZSI

M = Modbus

C = CAM interface

D = Modbus & CAM interface

W = ZSI & Modbus

X = ZSI & CAM interface

Y = ZSI, Modbus, & CAM interface

ETU protection style

1 = LI

2 = LSI

3 = LSIG

4 = LSI ARMS

5 = LSIG ARMS

PDG2 x PXR 3 0225 D 2 W

Accessaries

x = As installed

Poles

3 = 3 pole

4 = 4 pole with 100% neutral protection

6 = 4 pole with 60% neutral protection

0 = 4 pole with 0% neutral protection

Trip unit

TFA = Thermal fixed - adjustable magnetic

TAA = Thermal adjustable- adjustable magnetic

VFA = Thermal fixed 50%C calibrated- adjustable magnetic

VAA = Thermal adjustable 50% °C calibrated- adjustable magnetic

Ampere frame rating

0016 = 60 A frame

0032 = 32 A frame

0063 = 63A frame

0250 = 250 A frame

Stlye family

PDG2 = Frame 2 Global UL / CE / CSA / CCC

PDC2 = Frame 2 CE / CCC

PDC2 x TFA 3 0100

Accessories

x = As installed

Ampere frame rating

0015 = 15 A frame

0020 = 20 A frame

0025 = 25 A frame

0030 = 30 A frame

0035 = 35 A frame

0040 = 40 A frame

0045 = 45 A frame

0050 = 50 A frame

0060 = 60 A frame

0070 = 70 A frame

0080 = 80 A frame

0090 = 90 A frame

0100 = 100 A frame

0110 = 110 A frame

0125 = 125 A frame

0150 = 150 A frame

0175 = 175 A frame

0200 = 200 A frame

0225 = 225 A frame

Page 7: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

7

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Table 5. Symmetrical RMS interruption ratings Icu (kA) for each breaker frame

UL / CSA IEC / CCC

Voltage Frame 240V 480V 600V 240V 415V 440V 480V 525V 690V 125Vdc 250Vdc*

Globally rated

PDG2xF 35 25 14 35 25 25 20 18 - 10 10

PDG2xG 65 35 18 55 36 30 25 20 8 10 10

PDG2xK 85 50 22 85 50 35 35 30/25 10 10 10

PDG2xM 100 65 25 100 70 50 50 30/25 10 22 22

PDG2xN 150 85 30/25 150 70 70 65 30/25 10 22 22

PDG2xP 200 100 35/25 200 100 100 65 35/25 10 22 22

IEC / GB PDC2xF - - - 35 25 25 20 18 - 10 10

PDC2xG - - - 55 36 30 25 20 8 10 10PDC2xK - - - 85 50 35 35 30/25 10 10 10PDC2xM - - - 100 70 50 50 30/25 10 22 22PDC2xN - - - 150 70 70 65 30/25 10 22 22

UL/CSA Rated up to 240V

PDD2xF 35 - - - - - - - - 10 10PDD2xG 65 - - - - - - - - 10 10PDD2xK 85 - - - - - - - - 10 10PDD2xM 100 - - - - - - - - 22 22PDD2xN 150 - - - - - - - - 22 22PDD2xP 200 - - - - - - - - 22 22

* Two poles in series

Table 6. Curve notes

1. These curves apply for 50Hz and 60Hz applications

2. The maximum voltage rating for the frame style is stated in Table 5.

3. These curves are comprehensive for Power Defense style circuit breakers including frame sizes, ratings and constructions stated.

4. The total clearing times shown include the response time for the trip unit, the breaker opening and the interruption of the current. The bottom of the time band is the minimum commit to trip time.

5. The end of the curve is determined by the application or the interrupting rating of the circuit breaker.

6. Thermal Magnetic trip unit calibration based on 40°C ambient, cold start. Tested with 4 feet of rated wire (75°C) per terminal. Tested in open air with current in all poles.

7. Thermal Magnetic trip unit instantaneous calibration based on single pole testing.

8 All time current data for PXR is based on 3 phase testing. For ground testing refer to Instruction Leaflet IL012125EN..

Page 8: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

8

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Labels

PXR 25 and PXR 20 – unit with LSIG protection pictured

PXR 20 – unit with LSIG protection pictured

PXR 10 – unit with LSI protection pictured

Adjustable thermal, adjustable magnetic unit pictured

Figure 1. Power Defense frame 2 trip unit front labels.

ote: N Trip unit drawings in Figure 1 are representative of the face plates provided. Values on the trip unit dials will change based upon the specific breaker and trip unit. Refer to the time current curve of the breaker or the PXR User Guide for the specific settings.

Page 9: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

9

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Curves

Figure 2. PXR 20D / PXR 25 - I2t long delay and flat short delay for 200A - 250A frames. December 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PXR20D / PXR25 - I2t Long Delay and Flat Short Delay Curves (200A - 250A Frames)

0.5

1.5 12

0.05

tr setting range

Isdsetting range

tsd setting range

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR

20D / PXR 25Irsetting

PDG 225A

Min. 80AMax. 225A

Irsetting

PDC2200A

PDC2 250A

Min. 50A 63A

Max. 200A 250A

Notes: 1. Long delay pickup is 110% of the Ir setting at steps of

1A with ±5% tolerance.2. Long delay time settings adjustable from 0.5s - 24s at

steps of 0.1s with +0%/-30% tolerance.3. If thermal memory is enabled, trip times may be shorter

than indicated in this curve.4. Short delay pickup settings adjustable from 1.5x - 12.0x

at steps of 0.1x with ±5% tolerance.5. Short delay time settings adjustable from 0.050s -

0.500s at steps of 0.010s with tolerance as follows: time delay settings 0.500s to 0.200s have tolerances of +0%/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0%/-30%, time delay settings between 0.150s to 0.100s have tolerances of +0%/-40% and time delay settings between 0.090s to 0.050s have tolerances of +20%/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled, tripping times for 3-phase faults, no auxiliary power will be a maximum of 60ms for 60Hz and 68ms for 50Hz.

Page 10: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

10

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 3. PXR 20D / PXR 25 - I2t long delay and flat short delay for 60A - 160A frames. December 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PXR20D / PXR25 - I2t Long Delay and Flat Short Delay Curves (60A - 160A Frames)

0.5

1.5 12

0.05

tr setting range

Isdsetting range

tsd setting range

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR 20D /

PXR 25Irsetting

PDG 60A

PDG 100A

PDG 150A

Min. 15A 32A 50AMax. 60A 100A 150A

Irsetting

PDC963A

PDC9 100A

PDC9160A

Min. 16A 25A 40A

Max. 63A 100A 160A

Irsetting

PDC2160A

Min. 40A

Max. 160A

Notes: 1. Long delay pickup is 110% of the Ir setting at steps of 1A

with ±5% tolerance.2. Long delay time settings adjustable from 0.5s - 24s at steps

of 0.1s with +0%/-30% tolerance.3. If thermal memory is enabled, trip times may be shorter than

indicated in this curve.4. Short delay pickup settings adjustable from 1.5x - 12.0x at

steps of 0.1x with ±5% tolerance.5. Short delay time settings adjustable from 0.050s - 0.500s at

steps of 0.010s with tolerance as follows: time delay set-tings 0.500s to 0.200s have tolerances of +0%/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0%/-30%, time delay settings between 0.150s to 0.100s have tolerances of +0%/-40% and time delay settings between 0.090s to 0.050s have tolerances of +20%/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled, tripping times for 3-phase faults, no aux-iliary power will be a maximum of 60ms for 60Hz and 68ms for 50Hz.

Page 11: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

11

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 4. PXR 20 - I2t long delay and flat short delay for 200A - 250A frames. December 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Sec

onds

Current in Multiples of Long Delay Setting (Ir)

PXR20 - I2t Long Delay and Flat Short Delay Curves (200A - 250A Frames)

0.5

1.5

6

54

3

12

2

8

0.4

0.05

0.1

0.2

0.3

0.15

10

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance.2. Long delay time settings as shown have +0%/-

30% tolerance.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve.4. Short delay pickup settings as shown have ±5%

tolerance.5. Short delay time settings are shown with toler-

ances. 6. If the long delay time is projected to be faster

than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled, tripping times for 3-phase faults, no auxiliary power will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20Ir PDG

225A1 80A2 90A3 100A4 110A5 125A6 150A7 160A8 175A9 200A10 225A

Ir PDC2200A

PDC2 250A

1 50A 63A2 63A 80A3 80A 100A4 90A 125A5 100A 150A6 125A 160A7 150A 175A8 160A 200A9 175A 225A10 200A 250A

Page 12: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

12

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 5. PXR 20 - I2t long delay and flat short delay for 60A - 160A frames. December 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PXR20 - I2t Long Delay and Flat Short Delay Curves (60A - 160A Frames)

0.5

1.5

6

54

3

12

2

8

0.4

0.05

0.1

0.2

0.3

0.15

10

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance.2. Long delay time settings as shown have +0%/-

30% tolerance.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve.4. Short delay pickup settings as shown have ±5%

tolerance.5. Short delay time settings are shown with toler-

ances. 6. If the long delay time is projected to be faster

than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled, tripping times for 3-phase faults, no auxiliary power will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20Ir PDG

60APDG 100A

PDG 150A

1 15A 32A 50A2 16A 35A 60A3 20A 40A 63A4 25A 50A 70A5 30A 60A 80A6 35A 63A 90A7 40A 70A 100A8 45A 80A 110A9 50A 90A 125A10 60A 100A 150A

Ir PDC963A

PDC9 100A

PDC9160A

1 16A 25A 40A2 18A 32A 50A3 20A 40A 63A4 25A 50A 70A5 32A 55A 80A6 40A 63A 90A7 45A 70A 100A8 50A 80A 125A9 55A 90A 150A10 63A 100A 160A

Ir PDC2160A

1 40A2 50A3 63A4 70A5 80A6 90A7 100A8 125A9 150A10 160A

Page 13: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

13

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 6. PXR 20D / PXR 25 - I2t long delay and I2t short delay for all frames. December 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Sec

onds

Current in Multiples of Long Delay Setting (Ir)

PXR20D / PXR25 - I2t Long and I2t Short Delay Curves for all Frames

1.5

0.067

0.3

8

tr setting range

Isdsetting range

tsd setting range⑤

12

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR

20D / PXR 25Irsetting

PDG 60A

PDG 100A

PDG 150A

PDG 225A

Min. 15A 32A 50A 80AMax. 60A 100A 150A 225A

Irsetting

PDC963A

PDC9 100A

PDC9160A

Min. 16A 25A 40A

Max. 63A 100A 160A

Irsetting

PDC2160A

PDC2200A

PDC2 250A

Min. 40A 50A 63A

Max. 160A 200A 250A

Notes: 1. Long delay pickup is 110% of the Ir setting at steps of

1A with ±5% tolerance.2. Long delay time settings adjustable from 0.5s - 24s at

steps of 0.1s with +0%/-30% tolerance.3. If thermal memory is enabled, trip times may be shorter

than indicated in this curve.4. Short delay pickup settings adjustable from 1.5x - 8.0x

at steps of 0.1x with ±5% tolerance.5. Short delay I2t slope time settings adjustable from

0.067s to 0.300s at steps of 0.010s with tolerances as follows: I2t slope time delay settings 0.300s to 0.200s have tolerances of +0/-30%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, time delay settings between 0.150s to 0.100s have tol-erances of +0/-40% and time delay settings between 0.090s to 0.067s have tolerances of +0/-50%. After approximately 8x the I2t slope will go flat and those times have tolerances as follows: time delay settings 0.300s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have toler-ances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have toler-ances of +0/-50%..

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled, tripping times for 3-phase faults, no auxiliary power will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 14: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

14

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 7. PXR 20 I2t long delay and I2t short delay for all frames. December 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Sec

onds

Current in Multiples of Long Delay Setting (Ir)

PXR20 - I2t Long Delay and I2t Short Delay Curves

1.5 6

0.067

0.3

0.15

3 42

1085

12

Notes:1. Long delay pickup is 110% of the Ir setting with

±5% tolerance.2. Long delay time settings as shown have

+0%/-30% tolerance.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve.4. Short delay pickup settings as shown have ±5%

tolerance.5. Short delay time settings are shown with toler-

ances. 6. If the long delay time is projected to be faster

than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled, tripping times for 3-phase faults, no auxiliary power will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Time current curves Power Defense circuit breakersStyle: Frame 2 for all framesConfiguration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20Irset ting

PDG60A

PDG 100A

PDG 150A

PDG 225A

1 15A 32A 50A 80A2 16A 35A 60A 90A3 20A 40A 63A 100A4 25A 50A 70A 110A5 30A 60A 80A 125A6 35A 63A 90A 150A7 40A 70A 100A 160A8 45A 80A 110A 175A9 50A 90A 125A 200A10 60A 100A 150A 225A

Irset-ting

PDC963A

PDC9 100A

PDC9160A

1 16A 25A 40A2 18A 32A 50A3 20A 40A 63A4 25A 50A 70A5 32A 55A 80A6 40A 63A 90A7 45A 70A 100A8 50A 80A 125A9 55A 90A 150A10 63A 100A 160A

Irset-ting

PDC2160A

PDC2200A

PDC2 250A

1 40A 50A 63A2 50A 63A 80A3 63A 80A 100A4 70A 90A 125A5 80A 100A 150A6 90A 125A 160A7 100A 150A 175A8 125A 160A 200A9 150A 175A 225A10 160A 200A 250A

Page 15: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

15

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 8. PXR 20D / PXR 25 - I4t long delay and flat short delay for 200A - 250A frames. December 2019

0.01

0.1

1

10

100

1000

10000

100000

0.1 1 10 100

Tim

e in

Sec

onds

Current in Multiples of Long Delay Pickup (Ir)

PXR20D / PXR25 - I4t Long Delay and Flat Short Delay Curves

0.5

0.05

1.5 12Isd

setting range tsd setting range

tr setting range

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 4-polesTrip unit type: Power Xpert Release-PXR

20D / PXR 25Irsetting

PDG 225A

Min. 80AMax. 225A

Irsetting

PDC2200A

PDC2 250A

Min. 50A 63A

Max. 200A 250A

Notes:1. Long delay pickup is 110% of the Ir setting at steps

of 1A with ±5% tolerance.2. Long delay time settings adjustable from 0.5s - 7s at

steps of 0.1s with +0%/-30% tolerance.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve.4. Short delay pickup settings adjustable from 1.5x -

12.0x at steps of 0.1x with ±5% tolerance.5. Short delay time settings adjustable from 0.050s

- 0.500s at steps of 0.010s with tolerances as fol-lows: time delay settings 0.500s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +20/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled, tripping times for 3-phase faults, no auxiliary power will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 16: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

16

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 9. PXR 25 - I4t long delay and flat short delay for 60A - 160A frames. December 2019

0.01

0.1

1

10

100

1000

10000

100000

0.1 1 10 100

Tim

e in

Sec

onds

Current in Multiples of Long Delay Pickup (Ir)

PXR20D / PXR25 - I4t Long Delay and Flat Short Delay Curves

0.5

0.05

1.5 12Isd

setting range tsd setting range

tr setting range

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 4-polesTrip unit type: Power Xpert Release-PXR

20D / PXR 25Irsetting

PDG 60A

PDG 100A

PDG 150A

Min. 15A 32A 50AMax. 60A 100A 150A

Irsetting

PDC963A

PDC9 100A

PDC9160A

Min. 16A 25A 40A

Max. 63A 100A 160A

Irsetting

PDC2160A

Min. 40A

Max. 160A

Notes:1. Long delay pickup is 110% of the Ir setting at steps

of 1A with ±5% tolerance.2. Long delay time settings adjustable from 0.5s - 7s at

steps of 0.1s with +0%/-30% tolerance.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve.4. Short delay pickup settings adjustable from 1.5x -

12.0x at steps of 0.1x with ±5% tolerance.5. Short delay time settings adjustable from 0.050s

- 0.500s at steps of 0.010s with tolerances as fol-lows: time delay settings 0.500s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +20/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled, tripping times for 3-phase faults, no auxiliary power will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 17: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

17

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 10. PXR 20D / PXR 25 ground (earth) flat delay. December 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10

Tim

e in

Sec

onds

Current in Multiples of Rating (In)

PXR20D / PXR25 - Ground (Earth) Flat Delay Curves

0.2 1.0

0.1

1.0

Igsetting range

tg setting range

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR

20D / PXR 25

Notes:1. Ground pickup settings adjustable from 0.2x - 1.0x

at steps of 0.010x for residual sensing with a toler-ance of± 10%.

2. Ground time delay settings adjustable from 0.100s - 1.00s at steps of 0.010s with tolerances as follows: time delay settings 1.00s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +20/-40%.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. With ZSI enabled, tripping times for 3-phase faults, no aux. power will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 18: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

18

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 11. PXR 20D / PXR 25 -ground (earth) I2t delay. December 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10

Tim

e in

Sec

onds

Current in Multiples of Rating(In)

PXR20D / PXR25 - Ground (Earth) I2T Delay Curves

0.2 1.0

0.067

0.300

①Ig

setting range

tg setting range

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR

20D / PXR 25

Notes:1. Ground pickup settings adjustable from 0.2x - 1.0x

at steps of 0.01x are for residual sensing with a tolerance of ± 10%.

2. Ground I2t slope time settings are adjustable from 0.067s - 0.300s at steps of 0.010s with tolerances as follows: I2t slope time delay settings 0.300s to 0.200s have tolerances of +0/-30%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.067s have tolerances of +20%/-50%. After approximately 1x the I2t slope will go flat and those times have tolerances as follows: time delay settings 0.300s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +20%/-50%.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. With ZSI enabled, tripping times for 3-phase faults, no aux. power will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 19: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

19

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 12. PXR 20 - ground (earth) flat delay. December 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10

Tim

e in

Sec

onds

Current in Multiples of Rating (In)

PXR20 - Ground (Earth) Flat Delay Curves

0.2

0.2 0.4 0.6 0.8 1.0

0.1

0.3

0.75

0.5

①0.3

0.15

1.0

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20

Notes:1. Ground pickup settings as shown are for residual

sensing with a tolerance of ± 10% 2. Ground slope flat time setting are shown with

tolerances.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve. 4. With ZSI enabled, tripping times for 3-phase faults,

no aux. power will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 20: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

20

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 13. PXR 20 - ground (earth) I2t delay. December 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10

Tim

e in

Sec

onds

Current in Multiples of Rating (In)

PXR20 - Ground (Earth) I2T Delay Curves

0.150

0.2 0.5 1.0

0.067

0.300

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20

Notes:1. Ground pickup settings as shown are for residual

sensing with a tolerance of ± 10%. 2. Ground slope I2t time settings are shown with

tolerances.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve. 4. With ZSI enabled, tripping times for 3-phase faults,

no aux. power will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 21: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

21

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 14. PXR 20D / PXR 25 - instantaneous and override for 60A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Sec

onds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 60A Frame Instantaneous Curves

Max18.3

2

IiSetting range

0.01

0.1

1

10

100 1000 10000

Tim

e in

Sec

onds

Current in Amps

60A Frame Override Curve

600V415V-480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20D / PXR 25Frame: PDG2

Notes:1. The instantaneous pickup settings adjustable from

2x – 18.3x(max) at steps of 0.10x with a ±10% tolerance.

2. For high fault current levels a fixed instantaneous override is provided at 1100A and has a ±15% tolerance.

Page 22: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

22

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 15. PXR 20D / PXR 25 - instantaneous and override for 100A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 100A Frame Instantaneous Curves

Max11

2

IiSetting range

0.01

0.1

1

10

100 1000 10000

Tim

e in

Seco

nds

Current in Amps

100A Frame Override Curve

600V415V-480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20D / PXR 25Frame: PDG2

Notes:1. The instantaneous pickup settings adjustable from

2x – 11x(max) at steps of 0.10x with a ±10% tolerance.

2. For high fault current levels a fixed instantaneous override is provided at 1100A and has a ±15% tolerance.

Page 23: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

23

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 16. PXR 20D / PXR 25 - instantaneous and override for 150A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 150A Frame Instantaneous Curves

2

Max14

IiSetting range

0.01

0.1

1

10

100 1000 10000

Tim

e in

Seco

nds

Current in Amps

150A Frame Override Curve

600V415V-480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20D / PXR 25Frame: PDG2

Notes:1. The instantaneous pickup settings as shown with a

±10% tolerance.2. For high fault current levels a fixed instantaneous

override is provided at 2100A and has a ±15% tolerance.

Page 24: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

24

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 17. PXR 20D / PXR 25 - instantaneous and override for 225A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Sec

onds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 225A Frame Instantaneous Curves

2

Max9.3

IiSetting range

0.01

0.1

1

10

100 1000 10000

Tim

e in

Seco

nds

Current in Amps

225A Frame Override Curve

600V415V-480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20D / PXR 25Frame: PDG2

Notes:1. The instantaneous pickup settings adjustable from

2x – 9.3x(Max) at steps of 0.10x with a ±10% tolerance.

2. For high fault current levels a fixed instantaneous override is provided at 2100A and has a ±15% tolerance.

Page 25: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

25

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 18. PXR 20D / PXR 25 - Instantaneous and override for 63A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 63A Frame Instantaneous Curves

Max17.5

2

IiSetting range

0.01

0.1

1

10

100 1000 10000

Tim

e in

Seco

nds

Current in Amps

63A Frame Override Curve

690V415/440V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20D / PXR 25Frame: PDC2

Notes:1. The instantaneous pickup settings adjustable from

2x – 17.5x(Max) at steps of 0.10x with a ±10% tolerance.

2. For high fault current levels a fixed instantaneous override is provided at 1100A and has a ±15% tolerance.

Page 26: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

26

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 19. PXR 20D / PXR 25 - instantaneous and override for 100A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 100A Frame Instantaneous Curves

Max11

2

IiSetting range

0.01

0.1

1

10

100 1000 10000

Tim

e in

Seco

nds

Current in Amps

100A Frame Override Curve

690V415/440V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20D / PXR 25Frame: PDC2

Notes:1. The instantaneous pickup settings adjustable from

2x – 11x(Max) at steps of 0.10x with a ±10% tolerance.

2. For high fault current levels a fixed instantaneous override is provided at 1100A and has a ±15% tolerance.

Page 27: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

27

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 20. PXR 20D / PXR 25 -instantaneous and override for 160A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 160A Frame Instantaneous Curves

2

Max13.1

IiSetting range

0.01

0.1

1

10

100 1000 10000

Tim

e in

Seco

nds

Current in Amps

160A Frame Override Curve

690V415/440V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20D / PXR 25Frame: PDC9, PDC2

Notes:1. The instantaneous pickup settings adjustable from

2x – 13.1x(Max) at steps of 0.10x with a ±10% tolerance

2. For high fault current levels a fixed instantaneous override is provided at 2100A and has a ±15% tolerance.

Page 28: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

28

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 21. PXR 20D / PXR 25 - instantaneous and override for 200A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 200A Frame Instantaneous Curves

2

Max10.5

IiSetting range

0.01

0.1

1

10

100 1000 10000

Tim

e in

Seco

nds

Current in Amps

200A Frame Override Curve

690V415/440V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20D / PXR 25Frame: PDC2

Notes:1. The instantaneous pickup settings adjustable from

2x – 10.5x(Max) at steps of 0.10x with a ±10% tolerance.

2. For high fault current levels a fixed instantaneous override is provided at 2100A and has a ±15% tolerance.

Page 29: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

29

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 22. PXR 20D / PXR 25 - instantaneous and override for 250A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Sec

onds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 250A Frame Instantaneous Curves

2

Max8.4

IiSetting range

0.01

0.1

1

10

100 1000 10000

Tim

e in

Seco

nds

Current in Amps

250A Frame Override Curve

690V415/440V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20D / PXR 25Frame: PDC2

Notes:1. The instantaneous pickup settings adjustable from

2x – 8.4x(Max) at steps of 0.10x with a ±10% tolerance

2. For high fault current levels a fixed instantaneous override is provided at 2100A and has a ±15% tolerance.

Page 30: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

30

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 23. PXR 20 / PXR 10 - instantaneous and override for 60A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20 / PXR 10 - 60A Frame Instantaneous Curves

2

①Max18.38

12

10

6

5

43

15

0.01

0.1

1

10

100 1000 10000

Tim

e in

Sec

onds

Current in Amps

60A Frame Override Curve

600V415V-480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20 / PXR 10Frame: PDG2

Notes:1. The instantaneous pickup settings shown have a

±10% tolerance. 2. For high fault current levels a fixed instantaneous

override is provided at 1100A and has a ±15% tolerance.

Page 31: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

31

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 24. PXR 20 / PXR 10 - instantaneous and override for 100A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20 / PXR 10 - 100A Frame Instantaneous Curves

2

①Max118

9

7

6

5

43

10

0.01

0.1

1

10

100 1000 10000

Tim

e in

Sec

onds

Current in Amps

100A Frame Override Curve

600V415V-480V

240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20 / PXR 10Frame: PDG2

Notes:1. The instantaneous pickup settings shown have a

±10% tolerance.2. For high fault current levels a fixed instantaneous

override is provided at 1100A and has a ±15% tolerance.

Page 32: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

32

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 25. PXR 20 / PXR 10 - instantaneous and override for 150A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20 / PXR 10 - 150A Frame Instantaneous Curves

2

Max14

13

8

10

6

5

43

12

0.01

0.1

1

10

100 1000 10000

Tim

e in

Seco

nds

Current in Amps

150A Frame Override Curve

600V415V-480V

240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20 / PXR 10Frame: PDG2

Notes:1. The instantaneous pickup settings as shown with a

±10% tolerance.2. For high fault current levels a fixed instantaneous

override is provided at 2100A and has a ±15% tolerance.

Page 33: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

33

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 26. PXR 20 / PXR 10 - instantaneous and override for 225A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20 / PXR 10 - 225A Frame Instantaneous Curves

2

Max9.3

8

7

6

5

43

9

0.01

0.1

1

10

100 1000 10000

Tim

e in

Seco

nds

Current in Amps

225A Frame Override Curve

600V415V-480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20 / PXR 10Frame: PDG2

Notes:1. The instantaneous pickup settings shown have a

±10% tolerance2. For high fault current levels a fixed instantaneous

override is provided at 2100A and has a ±15% tolerance.

Page 34: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

34

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 27. PXR 20 / PXR 10 - instantaneous and override for 63A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20 / PXR 10 - 63A Frame Instantaneous Curves

2

①Max17.58

12

10

6

5

43

15

0.01

0.1

1

10

100 1000 10000

Tim

e in

Sec

onds

Current in Amps

63A Frame Override Curve

690V415/440V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20 / PXR 10Frame: PDC9

Notes:1. The instantaneous pickup settings shown have a

±10% tolerance.2. For high fault current levels a fixed instantaneous

override is provided at 1100A and has a ±15% tolerance.

Page 35: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

35

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 28. PXR 20 / PXR 10 - instantaneous and override for 100A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20 / PXR 10 - 100A Frame Instantaneous Curves

2

①Max118

9

7

6

5

43

10

0.01

0.1

1

10

100 1000 10000

Tim

e in

Sec

onds

Current in Amps

100A Frame Override Curve

600V415V-480V

240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20 / PXR 10Frame: PDC9

Notes:1. The instantaneous pickup settings shown have a

±10% tolerance.2. For high fault current levels a fixed instantaneous

override is provided at 1100A and has a ±15% tolerance.

Page 36: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

36

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 29. PXR 20 / PXR 10 - instantaneous and override for 160A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20 / PXR 10 - 160A Frame Instantaneous Curves

2

Max13.1

13

8

10

6

5

43

12

0.01

0.1

1

10

100 1000 10000

Tim

e in

Seco

nds

Current in Amps

160A Frame Override Curve

690V415/440V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20 / PXR 10Frame: PDC9, PDC2 Notes:1. The instantaneous pickup settings shown have a

±10% tolerance2. For high fault current levels a fixed instantaneous

override is provided at 2100A and has a ±15% tolerance

Page 37: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

37

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 30. PXR 20 / PXR 10 - instantaneous and override for 200A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20 / PXR 10 - 200A Frame Instantaneous Curves

2

Max10.5

8

9

7

6

5

43

10

0.01

0.1

1

10

100 1000 10000

Tim

e in

Seco

nds

Current in Amps

200A Frame Override Curve

690V415/440V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20 / PXR 10Frame: PDC2

Notes:1. The instantaneous pickup settings shown have a

±10% tolerance.2. For high fault current levels a fixed instantaneous

override is provided at 2100A and has a ±15% tolerance.

Page 38: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

38

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 31. PXR 20 / PXR 10 - instantaneous and override for 250A frame. December 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20 / PXR 10 - 250A Frame Instantaneous Curves

2

Max8.4

8

6.5

7

6

5

43

7.5

0.01

0.1

1

10

100 1000 10000

Tim

e in

Seco

nds

Current in Amps

250A Frame Override Curve

690V415/440V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-

PXR 20 / PXR 10Frame: PDC2

Notes:1. The instantaneous pickup settings shown have a

±10% tolerance2. For high fault current levels a fixed instantaneous

override is provided at 2100A and has a ±15% tolerance.

Page 39: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

39

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 32. PXR 10 LSI profile for short flat curves. December 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Sec

onds

Current in Multiples of Long Delay Setting (Ir)

PXR 10 - LSI Profile for Short Flat Curves

642 10

0.3

0.15A

B

D F

G

H

J

IrPDG60A

PDG 100A

PDG 150A

PDG 225A

1 15A 32A 50A 80A2 16A 35A 60A 90A3 20A 40A 63A 100A4 25A 50A 70A 110A5 30A 60A 80A 125A6 35A 63A 90A 150A7 40A 70A 100A 160A8 45A 80A 110A 175A9 50A 90A 125A 200A10 60A 100A 150A 225A

IrPDC963A

PDC9 100A

PDC9160A

1 16A 25A 40A2 18A 32A 50A3 20A 40A 63A4 25A 50A 70A5 32A 55A 80A6 40A 63A 90A7 45A 70A 100A8 50A 80A 125A9 55A 90A 150A10 63A 100A 160A

IrPDC2160A

PDC2200A

PDC2 250A

1 40A 50A 63A2 50A 63A 80A3 63A 80A 100A4 70A 90A 125A5 80A 100A 150A6 90A 125A 160A7 100A 150A 175A8 125A 160A 200A9 150A 175A 225A10 160A 200A 250A

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR 10

Notes: 1. Long delay pickup is 110% of the Ir setting with ±5% toler-

ance.2. Long delay time setting has +0%/-30% tolerance. It is fixed

at a 10s time band.3. Instantaneous pickup settings have ±10% tolerance.4. Short delay pickup settings as shown have ±5% toler-

ance.5. If thermal memory is enabled, trip times may be shorter than

indicated in this curve.6. Setting J in the table is the default value but can be pro-

grammed from a minimum of 2x to a maximum of 10x in steps 0.5x and a time delay of 50ms to 300ms in steps of 50ms using the Power Xpert Protection Manager software (PXPM).

7. When Profile K is selected, PXR 10 LI style curve should be used.

ProfileIsd(n x Ir)

tsd(s)

A. 2 0.150

B. 2 0.300

C. 2 I2tD 4 0.150E 4 I2tF 6 0.150G 6 0.300H 10 0.150J 10 0.300K OFF

Page 40: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

40

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 33. PXR 10 LSI profile for I2t short curves. December 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Sec

onds

Current in Multiples of Long Delay Setting (Ir)

PXR 10 - LSI Profile for Short I2t Curves

42

0.67

E

C

IrPDG60A

PDG 100A

PDG 150A

PDG 225A

1 15A 32A 50A 80A2 16A 35A 60A 90A3 20A 40A 63A 100A4 25A 50A 70A 110A5 30A 60A 80A 125A6 35A 63A 90A 150A7 40A 70A 100A 160A8 45A 80A 110A 175A9 50A 90A 125A 200A10 60A 100A 150A 225A

IrPDC963A

PDC9 100A

PDC9160A

1 16A 25A 40A2 18A 32A 50A3 20A 40A 63A4 25A 50A 70A5 32A 55A 80A6 40A 63A 90A7 45A 70A 100A8 50A 80A 125A9 55A 90A 150A10 63A 100A 160A

IrPDC2160A

PDC2200A

PDC2 250A

1 40A 50A 63A2 50A 63A 80A3 63A 80A 100A4 70A 90A 125A5 80A 100A 150A6 90A 125A 160A7 100A 150A 175A8 125A 160A 200A9 150A 175A 225A10 160A 200A 250A

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR 10

Notes: 1. Long delay pickup is 110% of the Ir setting with ±5% toler-

ance.2. Long delay time setting has +0%/-30% tolerance.3. Instantaneous pickup settings have ±10% tolerance.4. Short delay pickup settings as shown have ±5% toler-

ance.5. If thermal memory is enabled, trip times may be shorter than

indicated in this curve.6. Setting J in the table is the default value but can be pro-

grammed from a minimum of 2x to a maximum of 10x in steps 0.5x and a time delay of 50ms to 300ms in steps of 50ms using the Power Xpert Protection Manager software (PXPM).

7. When Profile K is selected, PXR 10 LI style curve should be used.

ProfileIsd(n x Ir)

tsd(s)

A. 2 0.150

B. 2 0.300

C. 2 I2tD 4 0.150E 4 I2tF 6 0.150G 6 0.300H 8 0.150J 8 0.300K OFF

Page 41: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

41

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 34. PXR 10 LI style 60A frame. December 2019

0.01

0.1

1

10

100

1000

10000

10 100 1000 10000 100000

Tim

e in

Seco

nds

Current in Amperes

PXR 10 - 60A, I2t Long Delay, Instantaneous, Override Curves

5

43

6

12

8

15

Max

2

10

600V415V-480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR 10

Irsetting

PDG 60A

1. 15A

2. 16A

3. 20A4 25A5 30A6 35A7 40A8 45A9 50A10 60A

Notes: 1. Long delay pickup is 110% of the Ir setting with ±5%

tolerance.2. Long delay time setting has +0%/-30% tolerance.3. Instantaneous pickup settings have ±10% toler-

ance.4. For high fault current levels a fixed instantaneous

override is provided at 1100A and has a ±15% toler-ance.

5. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

Page 42: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

42

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 35. PXR 10 LI style 100A frame. December 2019

0.01

0.1

1

10

100

1000

10000

10 100 1000 10000 100000

Tim

e in

Seco

nds

Current in Amperes

PXR 10 - 100A, I2t Long Delay, Instantaneous, Override Curves

5

43

6

9

8

7

Max

2

10

600V415V-480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR 10

Irsetting

PDG 100A

1. 32A

2. 35A

3. 40A4 50A5 60A6 63A7 70A8 80A9 90A10 100A

Notes: 1. Long delay pickup is 110% of the Ir setting with ±5%

tolerance.2. Long delay time setting has +0%/-30%

tolerance.3. Instantaneous pickup settings have ±10%

tolerance.4. For high fault current levels a fixed instantaneous

override is provided at 1100A and has a ±15% tolerance.

5. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

Page 43: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

43

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 36. PXR 10 LI style 150A frame. December 2019

0.01

0.1

1

10

100

1000

10000

10 100 1000 10000 100000

Tim

e in

Seco

nds

Current in Amperes

PXR 10 - 150A, I2t Long Delay, Instantaneous, Override Curves

5

43

6

12

8

15

Max

2

10

600V415V-480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR 10

Irsetting

PDG 150A

1. 50A

2. 60A

3. 63A4 70A5 80A6 90A7 100A8 110A9 125A10 150A

Notes: 1. Long delay pickup is 110% of the Ir setting with ±5%

tolerance.2. Long delay time setting has +0%/-30%

tolerance.3. Instantaneous pickup settings have ±10%

tolerance.4. For high fault current levels a fixed instantaneous

override is provided at 2100A and has a ±15% tolerance.

5. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

Page 44: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

44

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 37. PXR 10 LI style 225A frame. December 2019

0.01

0.1

1

10

100

1000

10000

10 100 1000 10000 100000

Tim

e in

Seco

nds

Current in Amperes

PXR 10 - 225A, I2t Long Delay, Instantaneous, Override Curves

5

4

3

6

7

8

9

Max

210

600V415V-480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR 10

Irsetting

PDG 225A

1. 80A

2. 90A

3. 100A4 110A5 125A6 150A7 160A8 175A9 200A10 225A

Notes: 1. Long delay pickup is 110% of the Ir setting with ±5%

tolerance.2. Long delay time setting has +0%/-30%

tolerance.3. Instantaneous pickup settings have ±10%

tolerance.4. For high fault current levels a fixed instantaneous

override is provided at 2100A and has a ±15% tolerance.

5. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

Page 45: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

45

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 38. PXR 10 LI style 63A frame. December 2019

0.01

0.1

1

10

100

1000

10000

10 100 1000 10000 100000

Tim

e in

Seco

nds

Current in Amperes

PXR 10 - 63A, I2t Long Delay, Instantaneous, Override Curves

5

43

6

12

8

15

Max

2

10

690V415/440V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR 10

Irsetting

PDC963A

1. 16A

2. 18A

3. 20A4 25A5 32A6 40A7 45A8 50A9 55A10 63A

Notes: 1. Long delay pickup is 110% of the Ir setting with ±5%

tolerance.2. Long delay time setting has +0%/-30%

tolerance.3. Instantaneous pickup settings have ±10%

tolerance.4. For high fault current levels a fixed instantaneous

override is provided at 1100A and has a ±15% tolerance.

5. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

Page 46: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

46

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 39. PXR 10 LI style 100A frame. December 2019

0.01

0.1

1

10

100

1000

10000

10 100 1000 10000 100000

Tim

e in

Seco

nds

Current in Amperes

PXR 10 - 100A, I2t Long Delay, Instantaneous, Override Curves

5

43

6

9

8

7

Max

2

10

690V415/440V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR 10

Irsetting

PDC2100A

1. 32A

2. 35A

3. 40A4 50A5 60A6 63A7 70A8 80A9 90A10 100A

Notes: 1. Long delay pickup is 110% of the Ir setting with ±5%

tolerance.2. Long delay time setting has +0%/-30%

tolerance.3. Instantaneous pickup settings have ±10%

tolerance.4. For high fault current levels a fixed instantaneous

override is provided at 1100A and has a ±15% tolerance.

5. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

Page 47: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

47

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 40. PXR 10 LI style 160A frame. December 2019

0.01

0.1

1

10

100

1000

10000

10 100 1000 10000 100000

Tim

e in

Seco

nds

Current in Amperes

PXR 10 - 160A, I2t Long Delay, Instantaneous, Override Curves

5

43

6

12

8

13

Max2

10

690V415/440V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR 10

Irsetting

PDC2/9160A

1. 40A

2. 50A

3. 63A4 70A5 80A6 90A7 100A8 125A9 150A10 160A

Notes: 1. Long delay pickup is 110% of the Ir setting with ±5%

tolerance.2. Long delay time setting has +0%/-30%

tolerance.3. Instantaneous pickup settings have ±10%

tolerance.4. For high fault current levels a fixed instantaneous

override is provided at 2100A and has a ±15% tolerance.

5. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

Page 48: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

48

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 41. PXR 10 LI style 200A frame. December 2019

0.01

0.1

1

10

100

1000

10000

10 100 1000 10000 100000

Tim

e in

Seco

nds

Current in Amperes

PXR 10 - 200A, I2t Long Delay, Instantaneous, Override Curves

5

4

3

6

7

8

9

Max

210

690V415/440V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR 10

Irsetting

PDC2200A

1. 50A

2. 63A

3. 80A4 90A5 100A6 125A7 150A8 160A9 175A10 200A

Notes: 1. Long delay pickup is 110% of the Ir setting with ±5%

tolerance.2. Long delay time setting has +0%/-30%

tolerance.3. Instantaneous pickup settings have ±10%

tolerance.4. For high fault current levels a fixed instantaneous

override is provided at 2100A and has a ±15% tolerance.

5. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

Page 49: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

49

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 42. PXR 10 LI style 250A frame. December 2019

0.01

0.1

1

10

100

1000

10000

10 100 1000 10000 100000

Tim

e in

Seco

nds

Current in Amperes

PXR 10 - 250A, I2t Long Delay, Instantaneous, Override Curves

5

4

3

6

7

6.5

7.5

Max

2 8

415/440V 690V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR 10

Irsetting

PDC2250A

1. 63A

2. 80A

3. 100A4 125A5 150A6 160A7 175A8 200A9 225A10 250A

Notes: 1. Long delay pickup is 110% of the Ir setting with ±5%

tolerance.2. Long delay time setting has +0%/-30%

tolerance.3. Instantaneous pickup settings have ±10%

tolerance.4. For high fault current levels a fixed instantaneous

override is provided at 2100A and has a ±15% tolerance.

5. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

Page 50: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

50

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 43. 15A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

15A Fixed Thermal Fixed Magnetic

MaximumTolerance

Maximum Single PoleTrip Times at 25°C

MinimumTolerance

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 51: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

51

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 44. 20A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

20A Fixed Thermal Fixed Magnetic

MaximumMinimumTolerance

Maximum Single Pole Trip

Tolerance

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 52: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

52

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 45. 25A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

25A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 53: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

53

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 46. 30A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

30A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 54: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

54

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 47. 35A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

35A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 55: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

55

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 48. 40A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

40A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 56: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

56

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 49. 45A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

45A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 57: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

57

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 50. 50A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

50A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 58: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

58

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 51. 60A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

60A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 59: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

59

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 52. 70A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

70A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 60: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

60

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 53. 80A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

80A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 61: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

61

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 54. 90A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

90A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 62: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

62

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 55. 100A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

100A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 63: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

63

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 56. 110A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

110A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 64: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

64

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 57. 125A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

125A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 65: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

65

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 58. 150A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

150A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 66: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

66

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 59. 15A fixed thermal fixed magnetic. December 2019.

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

15A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V

415V-480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 67: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

67

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 60. 20A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

20A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 68: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

68

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 61. 25A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

25A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 1, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 69: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

69

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 62. 30A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

30A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 70: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

70

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 63. 35A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

35A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 71: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

71

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 64. 40A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

40A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 72: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

72

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 65. 45A fixed thermal fixed magnetic. December 2019.

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

45A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 73: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

73

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 66. 50A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

50A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 74: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

74

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 67. 60A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

60A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC Instantaneous trip values are approximately 40% higher.

Page 75: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

75

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 68. 70A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

70A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 76: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

76

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 69. 80A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

80A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 77: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

77

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 70. 90A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

90A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

FDC 200 100 35 22 --

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 78: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

78

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 71. 100A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

100A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 79: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

79

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 72. 110A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

110A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 80: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

80

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 73. 125A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

125A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V415/480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 81: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

81

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 74. 150A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.010

0.100

1.000

10.000

100.000

1000.000

10000.000

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

150A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 82: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

82

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 75. 175A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.010

0.100

1.000

10.000

100.000

1000.000

10000.000

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

175A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 83: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

83

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 76. 200A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.010

0.100

1.000

10.000

100.000

1000.000

10000.000

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

200A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 84: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

84

Technical Data TD012064ENEffective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 77. 225A fixed thermal fixed magnetic. December 2019

Eaton Corporation January 2012

0.010

0.100

1.000

10.000

100.000

1000.000

10000.000

10 100 1000 10000 100000 1000000

Tim

e in

Sec

onds

Current in Amperes

225A Fixed Thermal Fixed Magnetic

MaximumTolerance

MinimumTolerance

Maximum Single Pole Trip Times at 25°C

interruption rating and application determines end of curve

600V480V240V

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Fixed thermal - fixed magneticBreaker frame: PDG or PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 85: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

85

Technical Data Effective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 78. 160A/200A/250A adjustable thermal and adjustable magnetic. December 2019

Eaton Corporation January 2012

0.001

0.01

0.1

1

10

100

1000

10000

1 10 100 1000

Tim

e in

Sec

onds

Current in Mutiples of In

160A/200A/250A Adjustable Thermal and Adjustable Magnetic

Maximum

5X 10X

Minimum

Time current curves Power Defense circuit breakersStyle: Frame 2Configuration: 2, 3, 4 poleTrip unit type: Thermal magneticTrip unit style: Adjustable thermal -

adjustable magneticBreaker frame: PDC style

Notes: 1. Single pole test data at 25°C based on NEMA procedures

(AB 4) for verifying performance of molded case circuit breakers.

2. DC instantaneous trip values are approximately 40% higher.

Page 86: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

86

Technical Data Effective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 79. 240V let-through current 150A. December 2019.

Eaton Corporation September 2017 Rev. 1

1

10

100

1 10 100 1000

Peak

Let

-Thr

ough

Cur

rent

, kA

Available Short Circuit Current, kA rms

PD2 150A 240VPeak Let Through Current

240V

Page 87: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

87

Technical Data Effective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 80. 240V let-through energy 150A. December 2019.

Eaton Corporation September 2017 Rev. 1

10000

100000

1000000

10000000

1 10 100 1000

Peak

Let

-Thr

ough

Ene

rgy

I2 t, A

2 sec

Available Short Circuit Current, kA rms

PD2 150A 240VPeak Let Through Energy

240V

Page 88: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

88

Technical Data Effective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 81. 240V let-through current 225A. December 2019

Eaton Corporation September 2017 Rev. 1

1

10

100

1 10 100 1000

Peak

Let

-Thr

ough

Cur

rent

, kA

Available Short Circuit Current, kA rms

PD2 225A 240VPeak Let Through Current

240V

Page 89: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

89

Technical Data Effective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 82. 240V let-through energy 225A. December 2019

Eaton Corporation September 2017 Rev. 1

10000

100000

1000000

10000000

1 10 100 1000

Peak

Let

-Thr

ough

Ene

rgy

I2 t, A

2 sec

Available Short Circuit Current, kA rms

PD2 225A 240VPeak Let Through Energy

240V

Page 90: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

90

Technical Data Effective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 83. 415V-480V let-through current 225A. December 2019

Eaton Corporation September 2017 Rev. 1

1

10

100

1 10 100 1000

Peak

Let

-Thr

ough

Cur

rent

, kA

Available Short Circuit Current, kA rms

PD2 225A 415V- 480VPeak Let Through Current

415V-480V

Page 91: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

91

Technical Data Effective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 84. 600V let-through current 150A. December 2019

Eaton Corporation September 2017 Rev. 1

1

10

100

1 10 100

Peak

Let

-Thr

ough

Cur

rent

, kA

Available Short Circuit Current, kA rms

PD2 150A 600VPeak Let Through Current

600V

Page 92: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

92

Technical Data Effective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 85. 600V let-through energy 150A. December 2019

Eaton Corporation September 2017 Rev. 1

100000

1000000

10000000

1 10 100

Peak

Let

-Thr

ough

Ene

rgy

I2 t, A

2se

c

Available Short Circuit Current, kA rms

PD2 150A 600VPeak Let Through Energy

600V

Page 93: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

93

Technical Data Effective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 86. 600V let-through current 225A. December 2019

Eaton Corporation September 2017 Rev. 1

1

10

100

1 10 100

Peak

Let

-Thr

ough

Cur

rent

, kA

Available Short Circuit Current, kA rms

PD2 225A 600VPeak Let Through Current

600V

Page 94: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

94

Technical Data Effective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 87. 600V let-through energy 225A. December 2019

Eaton Corporation September 2017 Rev. 1

100000

1000000

10000000

1 10 100

Peak

Let

-Thr

ough

Ene

rgy

I2 t, A

2se

c

Available Short Circuit Current, kA rms

PD2 225A 600VPeak Let Through Energy

600V

Page 95: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

95

Technical Data Effective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Notes

Page 96: Power Defense time current curve Frame 2 - PD2 · 3 Technical Data TD012064EN Effective December 2019 Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic

Eaton 1000 Eaton BoulevardCleveland, OH 44122United States877-ETN-CARE (877-386-2273)Eaton.com

© 2019 Eaton All Rights ReservedPrinted in USAPublication No. TD012064EN / TBG001440December 2019

Eaton is a registered trademark.

All other trademarks are property of their respective owners.

Technical Data Effective December 2019

Time current curves Power Defense MCCB Frame 2 thermal-magnetic and PXR electronic trip units

Standards: UL, CSA, IEC, CCC