POWER MONITORINGvikingcontrols.com/_documents/product/CS1150A.pdf · POWER MONITORING POWER MONITORING CURRENT-OPERATED ADJUSTABLE SWITCHES MODELS CS1150A, SCS1150A ... CS1150A–LED

Embed Size (px)

Citation preview

Page 1: POWER MONITORINGvikingcontrols.com/_documents/product/CS1150A.pdf · POWER MONITORING POWER MONITORING CURRENT-OPERATED ADJUSTABLE SWITCHES MODELS CS1150A, SCS1150A ... CS1150A–LED

POW

ER M

ON

ITO

RIN

G

POWER MONITORINGCURRENT-OPERATED ADJUSTABLE SWITCHESMODELS CS1150A, SCS1150A

2004 KELE CATALOG • www.kele.com • USA 888-397-5353 • International 901-382-6084 123

Switch rating 1-135 VAC/DC, 0.3ASwitch type Normally open, solid stateOff-state leakage ZeroPolarity Not polarity sensitive, switch AC

or DCMonitored AC current

CS1150A 1-150A*SCS1150A 1.75-150A*

Max currentsContinuous 150AFor 6 sec 400AFor 1 sec 1000A

Monitored frequency 60 Hz max, 6 Hz min**

Trip point adjustmentSplit core 4-turn potSolid core 15-turn pot

* For loads with higher FLAs and for larger diameter conductors, use an external current transformer.

** Specifically designed to accommodate variablespeed drives. Monitored frequency may go to less than 6 Hz without contact chattering.

Hysteresis1A setting 0.3A max50A setting 2.5A max150A setting 7.5A max

Operating temp -58° to 149°F (-50° to 65°C)Case ABS (meets UL flammability

rating 94V-0)Insulation class 600VWeight 0.25 lb (0.11 kg) Approvals UL listed, File #E170092;

CE certified

Dimensions CS1150A

Unit 2.2"H x 2.4"W x 0.9"D (5.6 x 6.1 x 2.3 cm)

Mounting base 3.5"L (8.9 cm) with 3.0" (7.6 cm)mounting centers

Through-hole 0.75" (1.9 cm) dia, for up to 250MCM cable

SCS1150AUnit 2.5"H x 2.6"W x 1.15"D

(6.4 x 6.6 x 2.9 cm)Mounting base 3.5"L (8.9 cm) with 3" (7.6 cm)

mounting centersThrough-hole 0.85" (2.2 cm) square aperture,

for up to 350 MCM cable

DESCRIPTION

The Kele Model CS1150A and SCS1150A are solid-state switches that operate when the AC current levelsensed by the internal current transformer exceeds anadjustable trip point. Internal circuits are totally poweredby induction from the conductor being monitored. Thereis zero off-state leakage current in the solid state relayoutput that can switch AC or DC circuits. The smart LEDindication option eliminates the need for meters whensetting the adjustable trip point of the current switch.

FEATURES

• Adjustable trip point• Switch AC or DC circuits• Smart LED option• Monitor motors for status or broken belts and

couplings• Applicable for VFD applications down to 6 Hz• Powered by monitored line

SCS1150A-LED CS1150A-LED

SPECIFICATIONS

• Split-core model clamps easily around cables• Five-year warranty• UL listed, CE certified

RC US

Page 2: POWER MONITORINGvikingcontrols.com/_documents/product/CS1150A.pdf · POWER MONITORING POWER MONITORING CURRENT-OPERATED ADJUSTABLE SWITCHES MODELS CS1150A, SCS1150A ... CS1150A–LED

POW

ER M

ON

ITO

RIN

GPOWER MONITORING

CURRENT-OPERATED ADJUSTABLE SWITCHESMODELS CS1150A, SCS1150A

2004 KELE CATALOG • www.kele.com • USA 888-397-5353 • International 901-382-6084124

Bldg Automation System, Energy Mgmt System,

DDC, SCADA, etc.

1-135VAC/DC max0.3A

Relay, Lamp,Small Contactor,or Similar ACor DC Load

CS1150A/SCS1150A

CS1150A/SCS1150A

Terminals not polarity sensitive

DigitalInput

Terminals not polarity sensitive

Monitored Conductor Monitored Conductor

WIRING

Sensors can be mounted in any position or hung directly on wires. For larger mounting screws, drill out mounting holes. Use upto #14 AWG copper wire to terminals. Tighten to 7 in-lb torque.

Adjustment1. With the sensor wired as shown, use a voltmeter across the sensor contacts. A full voltage across the contact confirms the

switch is open. Turn on the motor or other load being monitored.2. The sensor is shipped with the multi-turn adjustment set to the most sensitive position (CW). If the sensor now operates, turn

the adjustment counter-clockwise (CCW) until the operation reverses. The meter will indicate this action.3. Now, turn the adjustment CW until the sensor just operates its controlled circuit. It is desirable to turn the adjustment slightly

beyond this threshold point to provide a margin for normal current variations.4. The smart LED eliminates the need for a voltmeter. The LED will switch from rapid to slow flashing when going below the trip

point. (Option –LED).

Smart LED Indicator (Option–LED)The LED indicates three states:1. Rapid Flashing : Current has tripped the switch.2. Slow Flashing: Current is present but is below the trip point.3. No Flashing: Current is either OFF or below the bottom of the range.The smart LED indicator has zero off-state leakage.

Application Notes: 1. Make sure that switched current (connected to terminals) is limited to 0.3A continuous. Switched voltage should be no higher

than 135 VAC/DC.2. Important! Monitoring excessive current and damage the sensor.Make sure monitored currents do not exceed maximum

ratings.3. For proper operation of the split core model, make certain that the mating surfaces of the magnetic core are clean.

TroubleshootingProblem Probable Causes & Corrections1. Adjustment has no stops. The multi-turn adjustment pot has a slip-clutch that prevents damage at either end of its

Keeps turning. rotation. To know where the adjustment is, turn the pot 15 turns CW (4 turns for split core models); this sets it to the most sensitive position.

2. Sensor does not switch at all, Adjustment pot is probably backed off completely, which disables the sensor. regardless of current level. See Installation/Adjustment immediately above for instructions.

Verify that mating surfaces of the split core are free of foreign particles.

INSTALLATION / ADJUSTMENT

MODEL DESCRIPTIONCS1150A Solid-Core Current Switch, Adjustable, Normally OpenSCS1150A Split-Core Current Switch, Adjustable, Normally OpenCS1150A–LED Solid-Core Current Switch, Adjustable, Normally Open with Smart LEDSCS1150A–LED Split-Core Current Switch, Adjustable, Normally Open with Smart LED

Note: For normally closed applications, 240V switching applications, or current switches with multiple contacts, contact Kele.

ORDERING INFORMATION