15
9 Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solaheviduty.com. 1 Power Protection and Conditioning Surge protection devices are an effective and economical way to protect critical, microprocessor based equipment/ applications from the damaging effects of transients. Transient voltage spikes are generated externally due to lightning, utility grid switching and electrical accidents or internally due to copiers, generators and large motors. Sola surge suppression products quickly divert the high energy transients to levels that are safe for AC equipment. Sola/Hevi-Duty’s industrial surge suppression devices protect equipment with low clamping levels on all electrical paths. This not only prevents catastrophic failure but also extends the life of any electronic equipment. These devices meet UL 1449, 2 nd Edition standards and provide AIC ratings for safe distribution panel use. These surge protection devices come in a compact design allowing the user to install the product as close as possible to the sensitive load. Surge suppression is one part of a total power quality solution. They can be used alone or in conjunction with other Sola/Hevi-Duty products to solve more complex power quality problems. Surge Protective Devices (SPD) STV100K STV25K The STV25K DIN Rail Series This series provides point-of-use protection, at the dedicated equipment level, against damaging transients. Ideal for installation in electronic control cabinets found in harsh industrial environments such as the factory floor or at remote locations. These devices provide 50,000 amps of surge protection, sinewave tracking, LED status indication and form “C” dry contacts. This DIN Rail series also provides protection on all electrical paths and comes with a standard ten year product warranty. The STV25K DIN Rail series surge suppressors are UL recognized to Standard 1449, 2 nd Edition. The STV100K Hardwired Series Sola/Hevi-Duty’s STV100K series is a hardwired surge suppressor designed for installation at the service entrance, branch panel or a dedicated sensitive electronic load. These units feature all mode protection, LED and audible alarm status indication, sinewave tracking and form “C” dry contacts. The STV100K series also contains the highest levels of safety built into the product including thermal fusing and a fault current fusing level of 65 kAIC. Related Products • DIN Rail Power Supplies • Industrial Control Transformers • Line Reactors Related Products • Power Conditioners • UPS • Drive Isolation Transformers • K-Factor Transformers

Power Protection and Conditioning - Steven Engineering

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

9Contact Technical Services at (800) 377-4384 with any questions.

Visit our website at www.solaheviduty.com.

1Power Protection and Conditioning

Surge pro tec tion devices are an ef fec tive and economical way to protect critical, mi cro pro ces sor based equipment/ap pli ca tions from the damaging effects of transients. Transient voltage spikes are generated ex ter nal ly due to lightning, utility grid switch ing and electrical accidents or internally due to copiers, generators and large motors. Sola surge sup pres sion products quickly divert the high energy tran sients to levels that are safe for AC equipment.

Sola/Hevi-Duty’s industrial surge suppression devices protect equipment with low clamping levels on all electrical paths. This not only prevents catastrophic failure but also extends the life of any electronic equipment.

These devices meet UL 1449, 2nd Edition stan dards and provide AIC ratings for safe distribution panel use. These surge protection devices come in a compact design allowing the user to install the product as close as possible to the sensitive load.

Surge suppression is one part of a total power quality solution. They can be used alone or in conjunction with other Sola/Hevi-Duty products to solve more complex power quality problems.

Surge Protective Devices (SPD)

STV100K STV25K

The STV25K DIN Rail Series This series provides point-of-use protection, at the dedicated equip ment level, against dam ag ing transients. Ideal for in stal la tion in elec tron ic control cabinets found in harsh industrial environments such as the factory fl oor or at remote locations. These devices provide 50,000 amps of surge pro tec tion, sinewave tracking, LED status in di ca tion and form “C” dry contacts. This DIN Rail series also pro vides pro tec tion on all electrical paths and comes with a standard ten year product war ran ty. The STV25K DIN Rail series surge suppressors are UL rec og nized to Standard 1449, 2nd Edition.

The STV100K Hardwired Series Sola/Hevi-Duty’s STV100K series is a hardwired surge suppressor designed for installation at the service entrance, branch panel or a dedicated sensitive elec tron ic load. These units feature all mode protection, LED and audible alarm status indication, sinewave tracking and form “C” dry con tacts. The STV100K series also contains the highest levels of safety built into the product including thermal fusing and a fault current fusing level of 65 kAIC.

Related Products• DIN Rail Power Supplies• Industrial Control Transformers• Line Reactors

Related Products• Power Conditioners• UPS• Drive Isolation Transformers• K-Factor Transformers

Contact Technical Services at (800) 377-4384 with any questions.Visit our website at www.solaheviduty.com. 10

1 Power Protection and Conditioning

Catalog Number Input Voltage

STV25K-10S 120 V Single Phase(L - N)

STV25K-24S 240 V Single Phase(L1 - L2)

Selection Table

STV25K Specifi cations

The STV25K DIN Rail Series

Dimensions

Features• Compact and narrow design maximizes panel space.• Low clamping levels for more effective protection. • Easy access terminal screws for quick mounting and in stal la tion.• 50,000 amps of surge pro tec tion.• Sinewave tracking and all mode protection provide consistent and reliable protection on all electrical paths.• Patented thermal fusing prevents MOV overheating caused by excessive current levels.

Applications (20 Amp Max)• Control cabinets for industrial automation• Point of use industrial/service equipment• Remote commercial or industrial equipment• Instrumentation and large test equipment• Commercial and building automation systems

DescriptionCatalog Number

STV25K-10S STV25K-24S

Input Voltage120 VAC,

Single Phase 0-135 VRMS

240 VAC, Single Phase0-260 VRMS

Maximum Continuous Operating Voltage (MCOV)

120 VAC - 150 VRMS

240 VAC - 275 VRMS

Line Frequency 47-63 Hz

Connection/Mounting Type

DIN Rail Mount (Chassis Mount Bracket Optional order

SDN-PMBRK2) with screw terminals for #12 AWG.

Input Current Rating 20 Amps

Phase Confi guration 2 wire + GND

Weight 3 lbs

Dimensions (H x W x D) 4.87 x 2.5 x 4.375 (in) includes mounting bracket

Modes Of Protection All Mode: L - N, L - L, L - G, N-G

Safety Agency Approvals UL 1449-2,

UL 1449 (2nd Edition)Suppressor Classifi cation 120 VAC Normal/Common Mode 240 VAC Normal/Common Mode

400 VAC800 VAC

Status Indication Green LED, Form C Contacts

Packaging Metal DIN Rail Mount Enclosure, IP20

Response Time < 0.5 nsec

Operating Temperature -40°C to +60°C

Operating Humidity 0% to 95% Non-condensing

Noise Attenuation

Normal ModeCommon Mode

50 dB Min40 dB Min

Peak Surge Current Capability (8 x 20 µs)

Line to NeutralLine to Ground

Neutral to Ground

25 kA25 kA25 kA

Warranty 10 Years

11Contact Technical Services at (800) 377-4384 with any questions.

Visit our website at www.solaheviduty.com.

1Power Protection and Conditioning

The STV100K Series Features

• 100,000 amp peak current rating provides all mode protection against severe transients.• Low clamping levels for more effective protection• 65 kAIC fault current fus ing level provides safety and NEC conformance• LED status and audible alarms• Listed to UL 1449, 2nd Edition, UL 1283• Compact, rugged metal NEMA 12 enclosure

Applications• Distribution panels (<1200 A)• Branch, lighting and control panels • Factory automation installations• Dedicated industrial equipment

Selection TableDimensionsCatalog

Number Input Voltage

STV100K-10S 120/240 V Single Phase 3 wire + Ground

STV100K-10Y 208Y/120 V Three Phase Wye 4 wire + Ground

STV100K-10N 120 V Single Phase 2 wire + Ground

STV100K-24L 240 V Single Phase 2 wire + Ground

STV100K-23Y 380Y/220 V Three Phase Wye 4 wire + Ground

STV100K-27Y 480Y/277 V Three Phase Wye 4 wire + Ground

STV100K-24D 240 V Three Phase ∆ 3 wire + Ground

STV100K-48D 480 V Three Phase ∆ 3 wire + Ground

STV100K-10D4 240/120 CT Three Phase ∆ 4 wire + Ground

STV100K-24D4 480/240 CT Three Phase ∆ 4 wire + Ground

Contact Technical Services at (800) 377-4384 with any questions.Visit our website at www.solaheviduty.com. 12

1 Power Protection and Conditioning

100 K Specifi cations

DescriptionCatalog Number

STV100K-10S STV100K-10N STV100K-24L STV100K-10Y STV100K-23Y STV100K-27Y STV100K-24D STV100K-48D STV100K-10D4 STV100K-24D4

Input VAC120/240 V 120 V 240 V 208Y/120 V 380Y/220 V 480Y/277 V 240 V 480 V 120/240 CT 240/480 CT

Single Phase 3 wire + Ground Single Phase 2 wire + Ground Three Phase Wye 4 wire + Ground Three Phase ∆ 3 wire + Ground Three Phase ∆ 4 wire + Ground

Maximum Continuous Operating Voltage (MCOV)

125% of the nominal level for 120 V; 115% for all other input voltages

Line Frequency 47-63 Hz

Connection/Mounting Type Parallel/Flange

Enclosure Metal, NEMA 12 Enclosure

Dimensions (H x W x D) 4 in x 6 in x 4 in

Weight 8 lbs. Max

Modes Of Protection All Mode: L - N, L - L, L - G, N - G

Safety Agency Approvals UL 1449-2, cUL, UL 1283

UL 1449 (2nd Edition) Suppressor Classifi cation

L - N 400 V 400 V N/A 400 V 800 V 800 V N/A N/A 400 V 800 V

L - L 800 V N/A 800 V 800 V 1500 V 1500 V 1500 V 1500 V 800 V 1500 V

L - G 400 V 400 V 800 V 400 V 800 V 800 V 1500 V 1500 V 400 V 800 V

N - G 400 V 400 V N/A 400 V 800 V 800 V N/A N/A 400 V 800 V

A/C Rating 65 kAIC

Status Indication 3-Green LEDs, 1 per phase, 1-Red LED, Form C Contacts, Audible Alarm

Response Time < 0.5 nsec

Operating Temperature -40°C to +60°C

Operating Humidity 0% to 95% Non-condensing

Fusing Thermal and Fault Current

Noise Attenuation 40 dB Max

Peak Surge Current Capability

Per PhaseLine to Neutral

Line to LineLine to Ground

Neutral to Ground

100 kA50 kA50 kA50 kA50 kA

100 kA50 kAN/A

50 kA50 kA

100 kAN/A

50 kA50 kAN/A

100 kA50 kA50 kA50 kA50 kA

100 kA50 kA50 kA50 kA50 kA

100 kA50 kA50 kA50 kA50 kA

100 kAN/A

50 kA50 kAN/A

100 kAN/A

50 kA50 kAN/A

100 kA50 kA50 kA50 kA50 kA

100 kA50 kA50 kA50 kA50 kA

Warranty 10 years

13Contact Technical Services at (800) 377-4384 with any questions.

Visit our website at www.solaheviduty.com.

1Power Protection and Conditioning

Superior voltage regulation of ±1% sets the CVS series apart from other power conditioning technologies on the market. Extremely tight regulation is accomplished by Sola/Hevi-Duty’s patented ferroresonant transformer technology. The CVS recreates a well regulated sinusoidal waveform that is well isolated from input disturbances including:

• Impulses • Swells• Brownouts • Sags• Severe waveform distortion

No other power conditioning technology provides as complete a solution against these power quality disturbances. The CVS series is ideal for applications where even a small change in voltage level can lead to unscheduled downtime, misoperation, incorrect data or scrapped production.

Features• Superior voltage regulation of ±1%• Surge suppression tested to ANSI/IEEE C62.41, Class A&B Waveform• Harmonic filtering• Hardwired• Acts as a Step-up/Step-down Transformer• Galvanic isolation provides exceptional circuit protection.

• 25 year typical Mean Time Before Failure• No maintenance required

Selection Tables: Single Phase

Group 1 – CVS Series, 60 Hz

CVS Hardwired Series – Constant Voltage Transformers

* This unit is not CSA Certified.

Applications• Industrial automation and control equipment PLCs• Analytical laboratory and factory automating equipment• Photo processing equipment• Sound/recording systems• Photographic enlargers• Broadcast equipment

Related Products• On-line UPS (S4K Industrial)• Surge Suppression• Three Phase Power Conditioners

VA Catalog Number Voltage Input Voltage Output

Height (inch)

Width (inch)

Depth (inch)

Ship Weight (lbs)

Design Style

Elec Conn

30 23-13-030-2 120 120 7 4 5 9 1 J

60 23-13-060-2 120 120 7 4 5 9 1 J

120 23-22-112-2 120, 240 120 8 4 5 13 1 J

250 23-23-125-8 120, 240, 480 120 11 6 8 29 1 G

500 23-23-150-8 120, 208, 240, 480 120, 240 13 9 7 42 1 H

1000 23-23-210-8 120, 208, 240, 480 120, 240 17 9 7 65 1 H

2000 23-23-220-8 120, 208, 240, 480 120, 240 18 13 10 111 1 H

3000 23-23-230-8 120, 208, 240, 480 120, 240 19 13 10 142 1 H

5000 23-23-250-8 120, 208, 240, 480 120, 240 28 13 10 222 1 H

7500* 23-28-275-6 240, 480 120, 240 27 25 9 365 2 J

Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solaheviduty.com. 14

1 Power Protection and Conditioning

Design Styles (CVS and MCR Hardwired)

Style 1 Style 2 Style 3

CVS Hardwired Series – Constant Voltage Transformers

Specifications

Parameter Condition Value

Input

VoltageContinuous at full load (lower input voltage possible at lighter load) +10% to -20% of nominal

For temporary surge or sags +20% to -35% of nominal

Current1 at Full Load & 80% of nominal input voltage Iin ≅ (VA/.87)/(Vin x 80%)

Frequency See Operating Characteristics section for details. 60 HZ

Output

Line Regulation Vin >80% and <110% of nominal ±1%

Overload Protection At Nominal Input Voltage Current limited at 1.65 times rated current

Output Harmonic Distortion At Full Load within Input Range 3% total RMS content

Noise Attenuation -Common Mode -Transverse Mode

40 dB 40 dB

General

Efficiency At Full Load Up to 92%

Storage Temperature Humidity <95% non-condensing -20° to 80°C

Operating Temperature Humidity <95% non-condensing -20° to 50°C

Audible Noise Full Resistive Noise 32 dBA to 65 dBA

Approvals 60 Hz Models UL1012, CSA2

Warranty See General Information section for details 10 + 2 Years

These styles are single phase only.

Notes: 1 - Consult user manual for fuse sizing. 2 - Applies to all models except 23-28-275-6.

15Contact Technical Services at (800) 377-4384 with any questions.

Visit our website at www.solaheviduty.com.

1Power Protection and Conditioning

The MCR Hardwired Series provides excellent noise filtering and surge suppression to protect connected equipment from damage, degradation or misoperation. Combined with the excellent voltage regulation inherent to Sola/Hevi-Duty’s patented ferroresonant design, the MCR can increase the actual Mean Time Before Failure (MTBF) of protected equipment. The MCR is a perfect choice where dirty power, caused by impulses, swell, sags, brownouts and waveform distortion can lead to costly downtime because of damaged equipment.

Features• ±3% output voltage regulation• Noise attenuation - 120 dB common mode - 60 dB transverse mode• Surge suppression tested to ANSI/IEEE C62.41 Class A & B Waveform: - <10 V let through typical• Acts as a step-up or step-down transformer• Harmonic filtering• Hardwired• Galvanic isolation provides exceptional circuit protection.

• 25 year typical MTBF• No maintenance required

Applications• Industrial automation and control equipment PLCs• Machine tools• Computer loads and electronic equipment• Robotics• Semiconductor fabrication equipment

MCR Hardwired Series – Power Line Conditioning with Voltage Regulation

Selection Tables: Single PhaseGroup 2 – MCR Series, 60 Hz Only

* Canadian option: cULus certified units must be ordered by changing “-8” (UL only) to “-C8”.** UL Listed Only. Use Group 3 for cULus.

VA Catalog Number Voltage Input Voltage Output Height (inch)

Width (inch)

Depth (inch)

Ship Weight (lbs)

Design Style

Elec Conn

120 63-23-112-4 120, 208, 240, 480 120 9 4 5 15 1 D

250 63-23-125-4 120, 208, 240, 480 120 10 6 8 27 1 D

500 63-23-150-8 120, 208, 240, 480 120, 208, 240 13 9 7 37 1 E

750 63-23-175-8 120, 208, 240, 480 120, 208, 240 14 9 7 52 1 E

1000* 63-23-210-8 120, 208, 240, 480 120, 208, 240 17 9 7 62 1 E

1500* 63-23-215-8 120, 208, 240, 480 120, 208, 240 17 13 9 95 1 E

2000* 63-23-220-8 120, 208, 240, 480 120, 208, 240 18 13 9 109 1 E

3000* 63-23-230-8 120, 208, 240, 480 120, 208, 240 19 13 9 142 1 E

5000* 63-23-250-8 120, 208, 240, 480 120, 208, 240 28 13 9 222 1 E

7500** 63-28-275-8 208, 240, 480 120, 208, 240 27 26 9 362 2 F

10000** 63-28-310-8 208, 240, 480 120, 208, 240 28 26 9 446 2 F

15000** 63-28-315-8 208, 240, 480 120, 208, 240 28 38 10 710 3 F

Related Products• On-line UPS (S4K Industrial)• Surge Suppression• Three Phase Power Conditioners

Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solaheviduty.com. 16

1 Power Protection and Conditioning

Group 4 – MCR Series, 50 Hz Only (±5% output voltage regulation)

Selection Tables: Single PhaseGroup 3 – MCR Series, 60 Hz Only

Specifications

VA Catalog Number Voltage Input Voltage Output Height (inch)

Width (inch)

Depth (inch)

Ship weight (lbs)

Design Style

Elec Conn

500 63-31-150-8 600 120, 208, 240 13 9 7 38 1 B

1000 63-32-210-8 600 120, 208, 240 17 9 7 62 1 B

2000 63-32-220-8 600 120, 208, 240 18 13 10 109 1 B

3000 63-32-230-8 600 120, 208, 240 19 13 10 142 1 B

5000 63-29-250-8 208, 240, 480, 600 120, 208, 240 28 13 10 221 1 A

7500 63-29-275-8 208, 240, 480, 600 120, 208, 240 27 25 10 360 2 A

10000 63-29-310-8 208, 240, 480, 600 120, 208, 240 28 25 10 441 2 A

15000 63-29-315-8 208, 240, 480, 600 120, 208, 240 28 38 10 706 3 A

VA Catalog Number Voltage Input Voltage Output Height (inch)

Width (inch)

Depth (inch)

Ship weight (lbs)

Design Style

Elec Conn

120 63-23-612-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 9 6 8 24 1 C

250 63-23-625-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 11 6 8 27 1 C

500 63-23-650-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 13 9 7 40 1 C

1000 63-23-710-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 18 9 7 64 1 C

2000 63-23-720-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 18 13 10 113 1 C

3000 63-23-730-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 27 13 10 162 1 C

5000 63-23-750-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 30 13 10 266 1 C

7500 63-28-775-8 220, 240, 380, 415 110, 120, 220, 240 28 26 10 393 2 C1

10000 63-28-810-8 220, 240, 380, 415 110, 120, 220, 240 30 26 10 490 2 C2

15000 63-28-815-8 220, 240, 380, 415 110, 120, 220, 240 30 38 10 776 3 C2

Parameter Condition Value

Input

VoltageContinuous at full load (lower input voltage possible at lighter load) +10% to -20% of nominal

For temporary surge or sags +20% to -35% of nominal

Current1 at Full Load & 80% of nominal input voltage Iin ≅ (VA/.89)/(Vin x 80%)

Frequency See Operating Characteristics section for details. 50 Hz or 60 Hz depending on model

Output

Line Regulation Vin >80% and <110% of nominal ± 5% for 50 Hz units, ± 3% for 60 Hz units

Overload Protection At Nominal Input Voltage Current limited at 1.65 times rated current

Output Harmonic Distortion At full load within input range 3% total RMS content

Noise Attenuation -Common Mode -Transverse Mode

120 dB 60 dB

General

Efficiency At Full Load Up to 92%

Storage Temperature Humidity <95% non-condensing -20° to +85°C

Operating Temperature Humidity <95% non-condensing -20° to 50°C

Audible Noise Full Resistive Noise 35 dBA to 65 dBA

Approvals60 Hz Models UL1012, CSA evaluated by UL

50 Hz Models CE (EMC & LVD)

Warranty See General Information section for details 10 + 2 Years

Notes: 1 - Consult user manual for fuse sizing.

17Contact Technical Services at (800) 377-4384 with any questions.

Visit our website at www.solaheviduty.com.

1Power Protection and Conditioning

Electrical Connections

MCR 60 Hz 5000–15000 VA MCR 60 Hz 500–3000 VA MCR 50 Hz 120–5000 VA

MCR 50 Hz 7500 VA MCR 50 Hz 10000–15000 VA MCR 60 Hz 120–250 VA

A B C

C1 C2 D

Primary Voltage Interconnect Connect Lines To

208 H1 to H4 H2 to H5 H1 & H5

240 H1 to H4 H3 to H6 H1 & H6

480 H3 to H4 H1 & H6

600 H3 to H4 H1 & H7

Secondary Voltage Interconnect Connect Lines To

120 X1 & X2 or X3 & X2

208 X4 & X5

240 X1 & X3

Primary Voltage Interconnect Connect Lines To

600 H1 & H2

Secondary Voltage Interconnect Connect Lines To

120 X1 & X2 or X3 & X2

208 X4 & X5

240 X1 & X3

Primary Voltage Interconnect Connect Lines To

110-120 H1 to H3H2 to H4 H1 & H4

220-240 H2 to H3 H1 & H4

380-415 H2 to H3 H1 & H5

Secondary Voltage Interconnect Connect Lines To

110 X1 & X2 or X3 & X2

120 X4 & X2 or X5 & X2

220 X1 & X3

240 X4 & X5

Primary Voltage Interconnect Connect Lines To

220-240 H1 to H3H2 to H5 H1 & H5

380-415 H2 to H3 H1 & H4

Secondary Voltage Interconnect Connect Lines To

110 X1 & X2 or X2 & X3

120 X4 & X2 or X5 & X2

220 X1 & X3

240 X4 & X5

Primary Voltage Interconnect Connect Lines To

220-240 H2 to H3 H1 & H4

380-415 H2 to H3 H1 & H5

Secondary Voltage Interconnect Connect Lines To

110 X1 & X2 or X3 & X2

120 X4 & X2 or X5 & X2

220 X1 & X3

240 X4 & X5

Primary Voltage Interconnect Connect Lines To

120 H1 & H2

208 H1 & H3

240 H1 & H4

480 H1 & H5

Secondary Voltage Interconnect Connect Lines To

120 X1 & X2

Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solaheviduty.com. 18

1 Power Protection and Conditioning

MCR 60 Hz 500–5000 VA MCR 60 Hz 7500, 10000 and 15000 VA CVS 60 Hz 250 VA only

CVS 60 Hz 500–5000 VA

E F G

H JSeries-Multiple Primarywith Tap for two input voltages

Electrical Connections

CVS 60 Hz 30–120 VA & 7500 VA

Note: Secondaries are not grounded. Ground X2 per Code.

Open MCR/CVS terminal

Primary Voltage Interconnect Connect Lines To

120 H1 & H2

208 H1 & H3

240 H1 & H4

480 H1 & H5

Secondary Voltage Interconnect Connect Lines To

120 X1 & X2 or X3 & X2

208 X4 & X5

240 X1 & X3

Primary Voltage Interconnect Connect Lines To

208 H2 & H3

240 H2 & H4

480 H1 & H4

Secondary Voltage Interconnect Connect Lines To

120 X1 & X2 or X3 & X2

208 X4 & X5

240 X1 & X3

Primary Voltage Interconnect Connect Lines To

120 H1 to H3 H5 to H7 H2 to H4 H6 to H8 H1 & H2

240 H2 to H3 H6 to H7 H1 to H5 H4 to H8 H1 & H4

480 H2 to H3 H4 to H5 H6 to H7 H1 & H8

Secondary Voltage Interconnect Connect Lines To

120 X1 & X2

30 & 60 VAPrimary Voltage

120 VAPrimary Voltage

7500 VAPrimary Voltage Interconnect Connect

Lines To

120 N/A N/A Note: H3 & H4are not used H1 & H2

N/A 120 240 H1 to H3H2 to H4 H1 & H4

N/A 240 480 H2 to H3 H1 & H4

30 & 60 VASecondary Voltage

120 VASecondary Voltage

7500 VASecondary Voltage Interconnect Connect

Lines To

120 120 N/A X1 & X2

N/A N/A 120 X1 & X2 orH3 & X2

N/A N/A 240 X1 & X3

Primary Voltage Interconnect Connect Lines To

120 H1 to H3 to H6 to H8H2 to H5 to H7 to H10 H1 & H2

208 H2 to H3 H7 to H8H1 to H6 H4 to H9 H1 & H4

240 H2 to H3 H7 to H8H1 to H6 H5 to H10 H1 & H5

480 H2 to H3 H5 to H6H7 to H8 H1 & H10

Secondary Voltage Interconnect Connect Lines To

120 X1 & X2 or X3 & X2

240 X1 & X3

19Contact Technical Services at (800) 377-4384 with any questions.

Visit our website at www.solaheviduty.com.

1Power Protection and Conditioning

The MCR provides ex cel lent noise fi ltering and surge protection to protect con nect ed equip ment from damage, deg ra da tion or misoperation. Com bined with the ex cel lent voltage reg u la tion inherent to Sola/Hevi-Duty’s patented ferroresonant design, they can increase the actual Mean Time Before Failure (MTBF) of pro tect ed equipment. These units are a perfect choice where dirty power caused by impulses, swell, sags, brownouts and waveform distortion can lead to costly down time because of damaged equip ment.

Features• ±3% output voltage regulation• Noise attenuation

- 120 dB common mode - 60 dB transverse mode

• Surge suppression tested to ANSI/IEEE C62.41 Class A & B Waveform (<10 V let-through typical)• Harmonic fi ltering• Galvanic isolation provides exceptional circuit pro tec tion. • Point-of-use Protection (cord & plug connected)

- Easy & Flexible Installation• 25 year typical MTBF• No maintenance required

Applications• Computers/ Printers • Telephone/FAX systems• POS terminals • Security systems• Laboratory equipment • LAN networks

Specifi cations

MCR Portable Series

MCR Portable Series – Power Line Conditioning with Voltage Regulation

Parameter Condition Value

Input

VoltageContinuous at full load (lower input voltage possible at lighter load) +10% to -20% of nominal

For temporary surge or sags +20% to -35% of nominal

Current At Full Load & 80% of nominal input voltage Iin ≅ (VA/.89)/(Vin x 80%)

Frequency See Operating Characteristics section for details. 60 Hz depending on model

Output

Line Regulation Vin >80% and <110% of nominal ± 3% for 60 Hz units

Overload Protection At Nominal Input Voltage Current limited at 1.65 times rated current

Output Harmonic Distortion At full load within input range 3% total RMS content

Noise Attenuation -Common Mode -Transverse Mode

120 dB 60 dB

Let-Through ANSI/IEEE C62.41 Class A & B Waveform <10V typical

General

Effi ciency At Full Load 92% Typical

Storage Temperature Humidity <95% non-condensing -20° to +85°C

Operating Temperature Humidity <95% non-condensing -20° to 40°C

Audible Noise Full Resistive Noise 35 dBA to 65 dBA

Approvals 60 Hz Models UL10121 ,CSA (or cUL)1

Warranty See General Information section for details 10 + 2 Years

Notes: 1 - Depending on model, see selection tables to confi rm agency approvals for specifi c model numbers.

Plug & Receptacle Reference Chart

5-15R5-15P L5-30P

Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solaheviduty.com. 20

1 Power Protection and Conditioning

Selection Tables: Single Phase

MCR Portable Series – Power Line Conditioning with Voltage Regulation

Group A – MCR Portable Series, 60 Hz Only

* This unit is CULUS certified.** This unit is not CSA certified.

VA Catalog Number

VoltageInput/Output

Height (inch)

Width (inch)

Depth (inch)

Ship Weight (lbs)

Receptacle (No.) Type (NEMA)

Plug (NEMA)

70 63-13-070-6 120 6 7 9 18 (4) 5-15R 5-15P150 63-13-115-6 120 6 7 9 21 (4) 5-15R 5-15P250 63-13-125-6 120 6 7 9 26 (4) 5-15R 5-15P500 63-13-150-6 120 9 9 16 32 (4) 5-15R 5-15P750 63-13-175-6 120 9 9 16 64 (4) 5-15R 5-15P

1000 63-13-210-6 120 9 9 16 69 (4) 5-15R 5-15P1500* 63-13-215-6 120 11 11 17 95 (6) 5-15R 5-20P2000** 63-13-220-6 120 11 11 17 115 (4) 5-15R, (1) L5-30R L5-30P3000** 63-13-230-6 120 11 11 17 143 (4) 5-15R, (1) L5-30R 5-50P

Back Panels

60 Hz, 2000–3000 VA, (4) 5-15R and (1)

L5-30R Receptacle

60 Hz, 70 – 1000 VA, (4) 5-15R Receptacles

25Contact Technical Services at (800) 377-4384 with any questions.

Visit our website at www.solaheviduty.com.

1Power Protection and Conditioning

SOLATRON™ Plus Series - Three Phase Power ConditionersFeatures

• Rugged, industrial design• High overload capability• High MTBF - No fans used• No power factor restriction on loads• Tight regulation of ±3% typical for protection against sag (-25%) and swell (+15%) conditions• Failsafe, no-break, auto-bypass• Status indicating lights• Shielded, copper wound isolation transformer• Surge suppression to ANSI/IEEE and IEC Standards• High efficiency (96%) microprocessor controlled tap switcher• Automatic under voltage protection• UL1012, UL1449-2, CULUS Listed• Two-year limited warranty

Related Products• STV100K• Isolation Transformers

Applications• Automatic Packaging Machinery• Large Machine Tool Equipment• UPS Bypass Circuits• Retail Store• Process Equipment

Mechanical Specifications

Environmental Specifications

IndicatorsIndicating Lamps: 2 amber (over temperature and bypass mode), 1 green (regulated output present)

Connections Field wired, terminal blocks

Size H W D

in 42 28 26

mm 1016 712 661

Safety Agency Approvals

UL1012 and UL1449-2cUL (Canadian Standard C22.2 No 125) Complies with Part 15 Subpart J of FCC rules for a Class A computing device.

Audible Noise Less than 50 dBA at 3 feet

Ambient Temperature 0° to 40°C Operating, 0° to 80°C Storage

Operating Altitude 10,000 feet without derating Operating Humidity 95% relative (non-condensing)

Design Style

Electrical SpecificationsPower Ratings 20, 30, 50, 75 KVA, Three Phase*

Nominal Voltages See Selection Table

Input Voltage Range -25% to +15% of nominal rated voltage

Output VoltageRange

Regulated to a max of ± 5% (3% typical) of nominal voltage with an input voltage range of –25% to +15%.

Response Time Responds to any line variation in <1.5 cycles typical.

TechnologyEnhance Voltage Regulation (EVR), Microprocessor controlled electronic tap switching. 6 taps switched at zero current crossing with no output interruption.

Operating Frequency 57-63 Hz

Load Power Factor No Restriction

Insulation Resistance 100 megohms from winding to core measured at 500 VDC

Efficiency 96% typical

Overload Capability 1000% of rated load for 1 second200% of rated load for 1 minute

EMI Less than 0.2 gauss at a distance of 3 ft.

* Contact Technical Services for other ratings.

Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solaheviduty.com. 26

1 Power Protection and Conditioning

Three Phase Power ConditionersNoise Suppression Performance Specifications

Selection Table

Protection Specifications

Under Voltage

Output voltage will switch to bypass mode when input is less than 50% of nominal. Regulated output voltage will be re-established once input voltage is with specifications.

Short Circuit Protection Input circuit breaker

Over Temperature Protection

Amber lamp indication of over temperature at approximately 180°C. Unit switches to by-pass mode until internal temperature is reduced to specified values.

Common Mode Noise Attenuation 150 dB at 100 kHz

Normal Mode Noise Attenuation 65 dB at 100 kHz

Surge Suppression Tested to ANSI/IEEE standard C62.41 A&B (IEEE 587 Cat A and B), 1000-4, 1000-5

Output KVA Catalog Number VAC Input VAC Output Ship Weight (lbs/kg)

208 VAC Input, 208Y/120 VAC Output, 60 Hz

20 63TAA320 208 208Y/120 600/273

30 63TAA330 208 208Y/120 750/341

50 63TAA350 208 208Y/120 950/432

75 63TAA375 208 208Y/120 1200/545

480 VAC Input, 208Y/120 VAC Output, 60 Hz

20 63TCA320 480 208Y/120 600/273

30 63TCA330 480 208Y/120 750/341

50 63TCA350 480 208Y/120 950/432

75 63TCA375 480 208Y/120 1200/545

480 VAC Input, 480Y/277 VAC Output, 60 Hz

20 63TCC320 480 480Y/277 600/273

30 63TCC330 480 480Y/277 750/341

50 63TCC350 480 480Y/277 950/432

75 63TCC375 480 480Y/277 1200/545

600 VAC Input, 208Y/120 VAC Output, 60 Hz

20 63TDA320 600 208Y/120 600/273

30 63TDA330 600 208Y/120 750/341

50 63TDA350 600 208Y/120 950/432

75 63TDA375 600 208Y/120 1200/545

Custom Voltages240 VAC Input, 240Y/139 VAC Output, 60 Hz480 VAC Input, 240Y/139 VAC Output, 60 Hz600 VAC Input, 240Y/139 VAC Output, 60 Hz

Contact Technical Services.

Visit our website at www.solaheviduty.com or contact Technical Services at (800) 377- 4384 with any questions.28

2 Drive Isolation & Protection

SLR Line ReactorsSola/Hevi-Duty introduces DIN Rail mounted line reactors as the latest addition to a family of power quality products with a reputation for increasing industrial automation system performance.

The SLR Series is a CE style, DIN Rail Mounted line reactor that provides safe, compact protection for high frequency drives and electronic equipment. The SLR inductive filter prevents damage to any three phase electronic system plagued by capacitor or large load switching. Other benefits include reduced harmonics and input line distortion.

For SCR drive protection, Sola/Hevi-Duty recommends our Drive Isolation Transformers (from 7.5 to 440 KVA) to completely isolate the negative effects of SCR drive technology.

No matter what the drive protection, Sola/Hevi-Duty has the complete solution.

Applications• Variable Frequency Drives• Any three phase electronic products subject to high

current anomalies such as Power Factor Correction capacitor switching.

• SCR Drives

Related Products• Drive Isolation transformers• K-13 Rated Transformers for Variable Speed Drives

Selection Table

Features and Benefits• Compact, IP 20 finger safe packaging• 2-20 HP available• DIN Rail mount through 20HP• Reduces stress on drive components keeping drives

running longer.• Removes harmonics and helps keep line voltage

smooth through notching.• Reduces nuisance tripping to provide stable system

performance.• Eliminates drive cross-talk and interference.• 10-Year Sola/Hevi-Duty Warranty

Catalog Number Power Output Amperage

Impedance (%Z) mH Phase I/O

Voltage Mounting Dimensions (H x W x D)

Ship Weight (lbs)

SLR-2H-480-3 2 HP 3.4 A 3 5513 3 480 VAC DIN Rail 4.84 in x 4.80 in x 4.56 in 6

SLR-3H-480-3 3 HP 4.8 A 3 3675 3 480 VAC DIN Rail 4.84 in x 4.80 in x 4.56 in 6

SLR-5H-480-3 5 HP 7.6 A 3 2757 3 480 VAC DIN Rail 4.84 in x 4.80 in x 4.56 in 6

SLR-7H-480-3 7.5 HP 11.0 A 3 1838 3 480 VAC DIN Rail 4.84 in x 4.80 in x 4.56 in 7

SLR-10H-480-3 10 HP 14.0 A 3 1376 3 480 VAC DIN Rail 4.84 in x 4.80 in x 4.56 in 7

SLR-15H-480-3 15 HP 21.0 A 3 1050 3 480 VAC DIN Rail 4.84 in x 5.90 in x 4.56 in 9