Power System Protection Dr. Ibrahim El-Amin

Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

  • Upload
    others

  • View
    21

  • Download
    5

Embed Size (px)

Citation preview

Page 1: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Power System Protection

Dr. Ibrahim El-Amin

Page 2: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Protective Device Coordination

Page 3: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Definition

� Overcurrent Coordination

� A systematic study of current responsive devices

in an electrical power system.

Page 4: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Objective

� To determine the ratings and settings of

fuses, breakers, relay, etc.

� To isolate the fault or overloads.

Page 5: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Criteria

� Economics

� Available Measures of Fault

� Operating Practices

� Previous Experience

Page 6: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Design

� Open only PD upstream of the fault or overload

� Provide satisfactory protection for overloads

� Interrupt SC as rapidly (instantaneously) as

possible

� Comply with all applicable standards and codes

� Plot the Time Current Characteristics of

different PDs

Page 7: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Analysis

When:

� New electrical systems

� Plant electrical system expansion/retrofits

� Coordination failure in an existing plant

Page 8: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Protection vs. Coordination

� Coordination is not an exact science

� Compromise between protection and

coordination

� Reliability

� Speed

� Performance

� Economics

� Simplicity

Page 9: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Protection

� Prevent injury to personnel

� Minimize damage to components

� Quickly isolate the affected portion of the system

� Minimize the magnitude of available short-circuit

Page 10: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Spectrum Of Currents

� Load Current

� Up to 100% of full-load

� 115-125% (mild overload)

� Overcurrent

� Abnormal loading condition (Locked-Rotor)

� Fault Current

� Fault condition

� Ten times the full-load current and higher

Page 11: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Coordination

� Limit the extend and duration of service

interruption

� Selective fault isolation

� Provide alternate circuits

Page 12: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Coordination

t

I

C B A

C

D

D B

A

Page 13: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Equipment

� Motor

� Transformer

� Generator

� Cable

� Busway

Page 14: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Capability / Damage Curves

t

I

I22t

Gen

I2t

MotorXfmr

I2t

Cable

I2t

Page 15: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Transformer CategoryANSI/IEEE C-57.109

Minimum nameplate (kVA)

Category Single-phase Three-phase

I 5-500 15-500

II 501-1667 501-5000

III 1668-10,000 5001-30,000

IV above 1000 above 30,000

Page 16: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Infrequent Fault Incidence Zones for Category II & III Transformers

* Should be selected by reference to the frequent-fault-incidence protection curve or for

transformers serving industrial, commercial and institutional power systems with secondary-side

conductors enclosed in conduit, bus duct, etc., the feeder protective device may be selected by

reference to the infrequent-fault-incidence protection curve.

Source: IEEE C57

Source

Transformer primary-side protective device

(fuses, relayed circuit breakers, etc.) may be

selected by reference to the infrequent-fault-

incidence protection curve

Category II or III Transformer

Fault will be cleared by transformer

primary-side protective device

Optional main secondary –side protective device.

May be selected by reference to the infrequent-fault-

incidence protection curve

Feeder protective device

Fault will be cleared by transformer primary-side

protective device or by optional main secondary-

side protection device

Fault will be cleared by

feeder protective device

Infrequent-Fault

Incidence Zone*

Feeders

Frequent-Fault

Incidence Zone*

Page 17: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Transformer

t

(sec)

I (pu)

Thermal200

2.5

I2t = 1250

2

25Isc

Mechanical

K=(1/Z)2t

(D-D LL) 0.87

(D-R LG) 0.58

Frequent Fault

Infrequent Fault

Inrush

FLA

Page 18: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination
Page 19: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Transformer Protection

MAXIMUM RATING OR SETTING FOR OVERCURRENT DEVICE

PRIMARY SECONDARY

Over 600 Volts Over 600 Volts 600 Volts or Below

Transformer

Rated

Impedance

Circuit

Breaker

Setting

Fuse

Rating

Circuit

Breaker

Setting

Fuse

Rating

Circuit Breaker

Setting or Fuse

Rating

Not more than

6%

600 %

300 %

300 %

250%

125%

(250% supervised)

More than 6%

and not more

than 10%

400 %

300 %

250%

225%

125%

(250% supervised)

Table 450-3(a) source: NEC

Page 20: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Protective Devices

� Fuse

� Relay (50/51 P, N, G, SG, 51V, 67, 46, 79, 21, ?)

� Thermal Magnetic

� Low Voltage Solid State Trip

� Electro-Mechanical

� MCP

� Overload Heater

Page 21: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Fuse

� Non Adjustable Device

� Continuous and Interrupting Rating

� Voltage Levels

� Characteristic Curves

� Min. Melting

� Total Clearing

� Application

Page 22: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Minimum Melting

Time Curve

Total Clearing

Time Curve

Page 23: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Current Limiting Fuse(CLF)

� Limits the peak current of short-circuit

� Reduces magnetic stresses (mechanical

damage)

� Reduces thermal energy

Page 24: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination
Page 25: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Symmetrical RMS Amperes

Peak L

et-

Th

rou

gh

Am

pere

s

100 A

60 A

15% PF (X/R = 6.6)

12,500

5,200

230,000

300 A

100,000

Let-Through Chart

Page 26: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Fuse

Generally:

� CLF is a better short-circuit protection

� Non-CLF (expulsion fuse) is a better Overload

protection

Page 27: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Selectivity Criteria

Typically:

� Non-CLF: 140% of full load

� CLF: 150% of full load

Page 28: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Molder Case CB

� Thermal-Magnetic

� Magnetic Only

� Integrally Fused

� Current Limiting

� High Interrupting

Capacity

Types

� Frame Size

� Trip Rating

� Interrupting Capability

� Voltage

Page 29: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Thermal Minimum

Thermal Maximum

Magnetic

(instantaneous)

Page 30: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

LVPCB

� Voltage and Frequency Ratings

� Continuous Current / Frame Size

� Override (12 times cont. current)

� Interrupting Rating

� Short-Time Rating (30 cycle)

� Fairly Simple to Coordinate

Page 31: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

480 kV

CB 2

CB 1

CB 2CB 1

IT

ST PU

ST Band

LT PU

LT Band

If=30 kA

Page 32: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Motor Protection

� Motor Starting Curve

� Thermal Protection

� Locked Rotor Protection

� Fault Protection

Page 33: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Motor Overload Protection (NEC Art 430-32)

� Thermal O/L (Device 49)

� Motors with SF not less than 1.15

� 125% of FLA

� Motors with temp. rise not over 40

� 125% of FLA

� All other motors

� 115% of FLA

Page 34: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Locked Rotor Protection

� Thermal Locked Rotor (Device 51)

� Starting Time (TS < TLR)

� LRA

� LRA sym

� LRA asym (1.5-1.6 x LRA sym) + 10% margin

Page 35: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Fault Protection (NEC Art 430-52)

� Non-Time Delay Fuses� 300% of FLA

� Dual Element (Time-Delay Fuses)� 175% of FLA

� Instantaneous Trip Breaker� 800% of FLA*

� Inverse Time Breakers� 250% of FLA

*MCPs can be set higher

Page 36: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

200 HP

MCP

O/L

Starting Curve

I2T

(49)

MCP (50)

(51)ts

tLR

LRAs LRAasym

Page 37: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Overcurrent Relay

� Time-Delay (51 – I>)

� Short-Time Instantaneous ( I>>)

� Instantaneous (50 – I>>>)

� Electromagnetic (induction Disc)

� Solid State (Multi Function / Multi Level)

� Application

Page 38: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination
Page 39: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Time-Overcurrent Unit

� Ampere Tap Calculation

� Ampere Pickup (P.U.) = CT Ratio x A.T. Setting

� Relay Current (IR) = Actual Line Current (IL) / CT

Ratio

� Multiples of A.T. = IR/A.T. Setting

= IL/(CT Ratio x A.T. Setting)IL

IR

CT

51

Page 40: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Instantaneous Unit

� Instantaneous Calculation

� Ampere Pickup (P.U.) = CT Ratio x IT Setting

� Relay Current (IR) = Actual Line Current (IL) / CT

Ratio

� Multiples of IT= IR/IT Setting

= IL/(CT Ratio x IT Setting)IL

IR

CT

50

Page 41: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

41

Relay Coordination

� Time margins should be maintained between T/C curves

� Adjustment should be made for CB opening time

� Shorter time intervals may be used for solid state relays

� Upstream relay should have the same inverse T/C characteristic as the downstream relay (CO-8 to CO-8) or be less inverse (CO-8 upstream to CO-6 downstream)

� Extremely inverse relays coordinates very well with CLFs

Page 42: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Fixed Points

� Motor starting curves

� Transformer damage curves & inrush

points

� Cable damage curves

� SC maximum fault points

� Cable ampacities

Points or curves which do not change

regardless of protective device settings:

Page 43: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Situation

Calculate Relay Setting (Tap, Inst. Tap & Time Dial)

For This System

4.16 kV

DS 5 MVA

Cable

1-3/C 500 kcmilCU - EPR

CB

Isc = 30,000 A

6 %

50/51 Relay: IFC 53CT 800:5

Page 44: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Solution

AInrsuh

328,869412I =×=

A338.4800

5II LR =×=

Transformer: AkV

kVA

L694

16.43

000,5I =

×

=

IL

CTR

IR

Set Relay:

A 55 1.52800

5328,8)50(

1

)38.1(6/4.338 0.6

4.5338.4%125

=>=×=

=

=

=

AInst

TD

ATAP

A

Page 45: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Question

What is ANSI Shift Curve?

Page 46: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Answer

� For delta-delta connected transformers, with

line-to-line faults on the secondary side, the

curve must be reduced to 87% (shift to the left

by a factor of 0.87)

� For delta-wye connection, with single line-to-

ground faults on the secondary side, the curve

values must be reduced to 58% (shift to the left

by a factor of 0.58)

Page 47: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Question

What is meant by Frequent and

Infrequent for transformers?

Page 48: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

AnswerInfrequent Fault Incidence Zones for Category II & III Transformers

Source

Transformer primary-side protective device

(fuses, relayed circuit breakers, etc.) May be selected by reference to the infrequent-fault-

incidence protection curve

Category II or III Transformer

Fault will be cleared by transformer

primary-side protective device

Optional main secondary –side protective device.

May be selected by reference to the infrequent-fault-

incidence protection curve

Feeder protective device

Fault will be cleared by transformer primary-side

protective device or by optional main secondary-

side protection device

Fault will be cleared by

feeder protective device

Infrequent-Fault

Incidence Zone*

Feeders

Frequent-Fault

Incidence Zone*

Page 49: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Question

What T/C Coordination interval should be

maintained between relays?

Page 50: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Answer

At

I

B

CB Opening Time

+

Induction Disc Overtravel (0.1 sec)

+

Safety margin (0.2 sec w/o Inst. & 0.1 sec w/ Inst.)

Page 51: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Question

What is Class 10 and Class 20

Thermal OLR curves?

Page 52: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Answer

� Class 10 for fast trip, 10 seconds or less

� Class 20 for, 20 seconds or less

� There is also a Class 30 for long trip time

Page 53: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination

Answer