68
Power Transformers

Power Transformers 2

Embed Size (px)

Citation preview

Page 1: Power Transformers 2

Power Transformers

Page 2: Power Transformers 2

Three Phase Transformer Connections

Three identical single phase two winding transformers may be connected to form a three phase bank

The windings may be connected as:

Y - Y

Y - ∆

∆ - Y

∆ - ∆

Page 3: Power Transformers 2

Three Phase Transformer Connections

Page 4: Power Transformers 2

Three Phase Transformer Connections

Page 5: Power Transformers 2

Three Phase Transformer Connections

∆ - Y commonly used as a generator step-up transformer

Advantages:

3rd harmonic magnetizing current remains trapped in the ∆ winding

Y winding provides neutral point for grounding on HV side (has an effect on the insulation requirements of the winding)

Page 6: Power Transformers 2

Three Phase Transformer Connections

Y - Y seldom used because of harmonics in the magnetising current

∆ - ∆ has the advantage that one phase can be removed for maintenance while the remaining phases continue to operate as a three phase bank

Operation is reduced to 58% of the original bank

Page 7: Power Transformers 2

Example – Exercise 3.36

Three single phase transformers each rated at 25 MVA, 34.5/13.8 kV, are connected to form a three phase ∆ - ∆ bank. A resistive Y connected load absorbs 75 MW at 13.8 kV. If one of the single phase transformers is removed (resulting in an open ∆ connection) and the load is simultaneously reduced to 43.3 MW, determine

Page 8: Power Transformers 2

Example – Exercise 3.36

a) The load voltages Van, Vbn and Vcn

b) Load currents Ia, Ib and Ic

c) The MVA supplied by each of the two remaining transformers

Are balanced voltages still applied to the load?

Is the open - ∆ transformer overloaded?

Page 9: Power Transformers 2

Exercise 3.36

Page 10: Power Transformers 2

Exercise 3.36

Page 11: Power Transformers 2

Exercise 3.36

Page 12: Power Transformers 2

Exercise 3.36

Page 13: Power Transformers 2

Exercise 3.36

Page 14: Power Transformers 2

Three Phase Transformer Connections

Y – Y

No phase shift for +ve sequence

∆ - ∆

Y - ∆

HV quantities lead LV quantities by 300

for +ve sequence

∆ - Y

Page 15: Power Transformers 2

Three Phase Transformer

Page 16: Power Transformers 2

Three Phase Transformer

Page 17: Power Transformers 2

Three Phase Transformer

All six windings placed on a common core Advantages Cores contains less iron Costs less Weighs less Less space required Slightly higher efficiency Disadvantages Winding failure requires replacement of the transformer

Page 18: Power Transformers 2

Equivalent Circuit of three phase two winding transformer

Y – Y or ∆ - ∆

Page 19: Power Transformers 2

Equivalent Circuit of three phase two winding transformer

Y – ∆ or ∆ - Y

Page 20: Power Transformers 2

Three Winding Transformers

Page 21: Power Transformers 2

Three Winding Transformers

Page 22: Power Transformers 2

Three Winding Transformers

For an ideal three winding transformer:

I1pu = I2pu+ I3pu

E1pu = E2pu== E3pu

Page 23: Power Transformers 2

Three Winding Transformers

Page 24: Power Transformers 2

Three Winding Transformers

For a practical three winding transformer Open circuit test determines shunt admittance (Gc and Bm) Short circuit test determines leakage impedances (Z12, Z13 and Z23 ) Z12 = pu leakage impedance measured from winding 1 with winding 2 shorted and winding 3 open Z13

Z23

Page 25: Power Transformers 2

Three Winding Transformers

Short Circuit Test Z12 = Z1 + Z2

Z13 = Z1 + Z3

Z23 = Z2 + Z3

Series impedances can be calculted from above using

Z1 = 1

2(Z12 + Z13 - Z23)

Z2 = 1

2(Z12 + Z23 - Z13)

Z3 = 1

2(Z13 + Z23 - Z12)

Page 26: Power Transformers 2

Exercise 3.51

The ratings of a three phase three winding transformer are: Primary (1): Y connected 66 kV, 15 MVA Secondary (2): Y connected 13.2 kV, 10 MVA Tertiary (3): ∆ connected 2.3 kV, 5 MVA Neglecting winding resistances and exciting current, the per unit leakage reactances are X12 = 0.08 on a 15 MVA, 66 kV base

X13 = 0.10 on a 15 MVA, 66 kV base X23 = 0.09 on a 10 MVA, 13.2 kV base

Page 27: Power Transformers 2

Exercise 3.51

(a) Determine the p u reactances X1 , X2 and X3

on a 15 MVA, 66 kV base at the primary terminals

(b) Purely resistive loads of 7.5 MW at 13.2 kV and 5 MW at 2.3 kV are connected to the secondary and tertiary sides of the transformer respectively. Draw the per unit impedance diagram, showing the per unit impedances on a 15 MVA, 66 kV base at the primary terminals

Page 28: Power Transformers 2

Exercise 3.51

Page 29: Power Transformers 2

Exercise 3.51

Page 30: Power Transformers 2

Exercise 3.51

Page 31: Power Transformers 2

Exercise 3.51

Page 32: Power Transformers 2

Exercise 3.51

Page 33: Power Transformers 2

Autotransformers

Two windings of a single phase transformer are connected in series.

Windings are coupled electrically and magnetically

Page 34: Power Transformers 2

Autotransformers

Page 35: Power Transformers 2

Autotransformers

Advantages

Smaller leakage impedance

Lower losses

Lower exciting current

Lower cost for small turns ratio

Disadvantages

Higher short circuit currents

Electrical coupling of windings allows transient over-voltages to pass through more easily

Page 36: Power Transformers 2

Transformers with off –nominal turns ratio

Page 37: Power Transformers 2

Transformers with off –nominal turns ratio

A transformer whose rated voltages is not in proportion to the selected base voltages is said to have an “off nominal turns ratio”.

𝑉1𝑟𝑎𝑡𝑒𝑑

𝑉2𝑟𝑎𝑡𝑒𝑑 ≠

𝑉𝑏𝑎𝑠𝑒−1

𝑉𝑏𝑎𝑠𝑒−2

Page 38: Power Transformers 2

Transformers with off –nominal turns ratio

Page 39: Power Transformers 2

𝑉1𝑟𝑎𝑡𝑒𝑑 = 𝑎𝑡 𝑉2𝑟𝑎𝑡𝑒𝑑 (1)

If the base voltages on either side of the transformer are known the

𝑉𝑏𝑎𝑠𝑒1 = b 𝑉𝑏𝑎𝑠𝑒2 (2)

Page 40: Power Transformers 2

Then equation (1) can be written as

𝑉1𝑟𝑎𝑡𝑒𝑑 = 𝑎𝑡 𝑉2𝑟𝑎𝑡𝑒𝑑

= b (𝑎𝑡

𝑏) 𝑉2𝑟𝑎𝑡𝑒𝑑 (3)

Letting c = 𝑎𝑡

𝑏 equation 3 becomes

𝑉1𝑟𝑎𝑡𝑒𝑑 = bc 𝑉2𝑟𝑎𝑡𝑒𝑑 (4)

Page 41: Power Transformers 2

𝑉1𝑟𝑎𝑡𝑒𝑑 = bc 𝑉2𝑟𝑎𝑡𝑒𝑑 can be represented by two transformers in series as shown below

Page 42: Power Transformers 2
Page 43: Power Transformers 2

Transformers with off –nominal turns ratio

Per unit equivalent circuit

Page 44: Power Transformers 2

Transformers with off –nominal turns ratio

π circuit representation for real c

Page 45: Power Transformers 2

Transformers with off –nominal turns ratio

𝐼1

−𝐼2=

𝑌11 𝑌12

𝑌21 𝑌21

𝑉1

𝑉2

Page 46: Power Transformers 2

Transformers with off –nominal turns ratio

Parallel connected transformers with different turns ratios

Tap changing transformers

Voltage regulating transformers

Phase angle regulating transformers

Page 47: Power Transformers 2

Transformers with off –nominal turns ratio

Tap changing transformers

Page 48: Power Transformers 2

Transformers with off –nominal turns ratio

Tap changing transformers

Page 49: Power Transformers 2

Example 3.12

Page 50: Power Transformers 2

Example 3.12

Page 51: Power Transformers 2

Example 3.12

Per unit equivalent circuit

Page 52: Power Transformers 2

Example 3.12

Page 53: Power Transformers 2

Example 3.12

Page 54: Power Transformers 2

Example 3.12

Per unit equivalent circuit

Page 55: Power Transformers 2

Transformers with off –nominal turns ratio

Regulating transformers

Voltage magnitude

Phase angle regulating

Page 56: Power Transformers 2

Voltage magnitude regulating transformer

Page 57: Power Transformers 2

Voltage magnitude regulating transformer

Page 58: Power Transformers 2

Modelling as a off nominal turns ratio transformer

c = (1 + ∆v) for voltage increase at bus abc

c = (1 + ∆v)-1 for voltage increase at bus a’b’c’

Page 59: Power Transformers 2

Phase angle regulating transformer

Page 60: Power Transformers 2

Modelling as a off nominal turns ratio transformer

c = 1∠α for a phase increase at bus abc

c = 1∠-α for a phase increase at bus a’ b’ c’

Page 61: Power Transformers 2

Example 3.13

Page 62: Power Transformers 2

Example 3.13

Page 63: Power Transformers 2

Example 3.13

Page 64: Power Transformers 2

Example 3.13

Page 65: Power Transformers 2

Example 3.13

Page 66: Power Transformers 2

Example 3.13

Page 67: Power Transformers 2

Example 3.13

Page 68: Power Transformers 2

Tutorial 4 – Exercise 3.59

The 2 lines in example 3.13 supply a balanced load with a load current of 1∠-300. Determine the real and reactive power supplied to the load bus from each parallel line with (a) no regulating transformer (b) the voltage regulating transformer in example 3.13(a), and (c) the phase angle regulating transformer in example 3.13(b), Assume that the voltage at bus abc is adjusted so that the voltage at bus a’b’c’ remains constant at 1.0∠00 per unit.