Upload
lyhuong
View
221
Download
0
Embed Size (px)
Citation preview
POWER-ZONE®
Load Center Unit Substations
Class 6020
I
General Layout Information . . . . . . . . . . . . . . . . . . . . . . . . . .1
General InformationGeneral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4Standard Product Information . . . . . . . . . . . . . . . . . . . . . . . . . .4
Major Component General InformationHVL Metal-Enclosed Load Interrupter Switchgear . . . . . . . . .5VISI-VAC Metal-Enclosed Circuit Interrupter Switchgear . . .6Metal-Clad Switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7PZ III Low Voltage Drawout Switchgear . . . . . . . . . . . . . . . . . .8POWER-STYLE QED Switchboard Incoming Primary
Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9POWER-STYLE QED Switchboard Secondary Main
Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9POWER-STYLE QED Switchboard Distribution Sections . .10POWER-DRY VPI Dry-Type Transformer . . . . . . . . . . . . . . . .12POWER-CAST Cast-Coil Transformer . . . . . . . . . . . . . . . . . .13UNI-CAST (Cast-Coil Primary/VPI Secondary)
Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Liquid-Filled Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15MODEL 5/6 Motor Control Center . . . . . . . . . . . . . . . . . . . . .16Busway Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Special Applications and ProductsPOWER-ZONE Type 36 Compact Section
Unit Substation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18Model III POWER-ZONE Package Unit Substation . . . . . . .19
Typical Key Interlock Schemes . . . . . . . . . . . . . . . . . . . . . .20
5 and 15 kV Primary Switchgear Layout InformationHVL/VISI-VAC – POWER-DRY Transformer . . . . . . . . . . . . .29HVL/VISI-VAC – POWER-CAST and
UNI-CAST Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . .30HVL/VISI-VAC – Liquid-Filled Transformers . . . . . . . . . . . . .31Metal-Clad Switchgear – POWER-DRY, POWER-CAST,
and UNI-CAST Transformers . . . . . . . . . . . . . . . . . . . . . . . .32Metal-Clad Switchgear – Liquid-Filled Transformers . . . . . .33
25 kV Primary Switchgear Layout InformationHVL– POWER-DRY and POWER-CAST Transformers . . . .34HVL – Liquid-Filled Transformers . . . . . . . . . . . . . . . . . . . . . .35
34 kV Primary Switchgear Layout InformationHVL – POWER-CAST Transformer . . . . . . . . . . . . . . . . . . . . .36HVL – Liquid-Filled Transformer . . . . . . . . . . . . . . . . . . . . . . .37
600 V Primary Switchboard Layout InformationQED Switchboard – POWER-DRY Transformer . . . . . . . . . .38
Transformer Layout InformationPOWER-DRY Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . .39UNI-CAST Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43POWER-CAST Transformer . . . . . . . . . . . . . . . . . . . . . . . . . .45Liquid-Filled Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
5 kV Secondary Switchgear Layout InformationPOWER-DRY Transformer – HVL/VISI-VAC . . . . . . . . . . . . .52POWER-CAST Transformer – HVL/VISI-VAC . . . . . . . . . . . .53Liquid-Filled Transformer – HVL/VISI-VAC . . . . . . . . . . . . . .54POWER-DRY and POWER-CAST Transformers –
Metal-Clad Switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55Liquid-Filled Transformer – Metal-Clad Switchgear . . . . . . .56
600 V Secondary Switchboard Layout InformationPOWER-DRY, POWER-CAST and UNI-CAST Transformers –
QED Switchboard to 4000 A . . . . . . . . . . . . . . . . . . . . . . . . .57POWER-DRY, POWER-CAST and UNI-CAST Transformers –
QED Switchboard 4001 – 5000 A . . . . . . . . . . . . . . . . . . . .58Liquid-Filled Transformers – QED Switchboard to
4000 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59Liquid-Filled Transformers – QED Switchboard
4001 – 5000 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
600 V Secondary Draw-Out Switchgear LayoutInformation
POWER-DRY, POWER-CAST and UNI-CAST Transformers – PZ III Switchgear . . . . . . . . . . . . . . . . . . . . .61
Liquid-Filled Transformers – PZ III Switchgear . . . . . . . . . . .62
Table of Contents
1
General Layout Information
Please read this page before attempting to use the inter-face drawings in this catalog! As with any engineeredproduct, substation standards do change from time to time.The substation layout standards shown on the following pagesare the latest that have been produced by the Square DCompany, and are current as of the date of publication. Whenin doubt about any standard shown, please contact your localfield sales office. Please note that the dimensions shown hereare not for construction.
The interface drawings begin on Page 29.
All interfaces are shown with the primary or secondary equip-ment covered by that particular layout in solid lines, and thetransformer is shown in dotted lines. Please note dimensionsnoted as “min” or “minimum”, which denote the minimum pos-sible dimension of a piece of equipment and requires furtherclarification on a case-by-case basis either from the trans-former tables in this catalog or individual equipment dimen-sional information in another catalog. Also, reference pointsmarked as “CL” (short for “centerline”), can either represent thecenterline of the actual electrical connection between thetransformer and the piece of equipment under consideration(as is often the case in indoor units) or can represent the center-line of the hole pattern for the bolts which will hold the twopieces of equipment together (as is often the case withoutdoor units). In either case, for the purposes of this catalogthese serve only as convenient points of reference. Primaryinterfaces are drawn with the primary equipment on the left,and secondary interfaces are drawn with the secondary equip-ment on the right.
The layout standards in this catalog are covered in this order:primary interfaces are shown first, transformer dimensionalinformation is shown next, and secondary interfaces are shownlast. It is therefore recommended that the following procedurebe used for a layout:
1. Knowing the primary equipment type, its voltage class(either 600 V, 5 kV, 15 kV, 24 kV or 34 kV) and the transformertype, find the appropriate primary equipment-to-trans-former interface, noting the overlap, if any, between the frontof the primary equipment and the front of the transformer.Please read all of the footnotes! They provide valuableinformation and are necessary because in manyinstances a substantial amount of information is incor-porated into one interface drawing.
2. Find the transformer dimensional information for the trans-former in question. Please be sure that the dimensionsshown can be applied. The footnotes give a substantialamount of information about situations in which the dimen-sions shown do not apply. When in doubt, please contactyour local field sales office about transformer dimensions.
3. The offset, if any, between the rear of the transformer andthe rear of the primary equipment can now be determined.
4. Knowing the secondary equipment type and its voltageclass (5 kV or 600 V), find the transformer-to-secondaryinterface for the secondary equipment in question. For QEDswitchboards and POWER-ZONE III Low-Voltageswitchgear, please note whether the secondary full-loadcurrent is above or below 4000 A. The overlap, if any,between the transformer front and the secondary equip-ment front can now be determined, as well as any rearoverlap. Please note that because of the complex nature ofQED switchboards and POWER-ZONE III low-voltageswitchgear, these types of equipment should be laid outusing the appropriate layout manual or Quote-to-Cashproduct selector prior to substation layout. Please contactyour local field sales office for details on this process.
5. The substation layout is now complete. Facing the front ofthe substation, the primary equipment is on the left, and thesecondary equipment is on the right. If the opposite orien-tation is desired, the layout may be mirror-imaged with noloss of accuracy.
2
General Information
Secondary Unit Substation
• kVA ratings: 225-5000 kVA (higher ratings available)• Receives power up to 34,500 volts• Transforms to secondary voltages of 1000 volts and below• Distributes lower voltages to load areas• Indoor or outdoor construction
Primary Unit Substation
• kVA ratings: 225-5000 kVA (higher ratings available)• Receives power up to 34,500 volts• Transforms to secondary voltages from 2400 volts to 5000
volts• Indoor or outdoor construction
3
General Information
GeneralThe unit substation is a vital piece of equipment to be consid-ered when planning industrial, commercial, and institutionalelectrical system demands. Square D Company can provide aunit substation to receive up to 34,500 volts, transform this toa lower utilization voltage, and control its distribution to nearbyload areas. Square D Company is a single source supplier ofboth primary and secondary unit substations.
Square D considers the unit substation as a single product thatis designed, coordinated, assembled, and tested at differentmanufacturing locations as multiple self-enclosed pieces ofequipment intended for connection at the jobsite. Various com-binations of incoming sections, transformer sections, and dis-tribution sections make possible a variety of designs (See unitsubstation selection table on this page).
Both Square D Company’s primary unit substations and sec-ondary unit substations are designed, manufactured, andtested in accordance with ANSI C37.121-1989 and otherapplicable ANSI standards, and the applicable standards ofNEMA, UL, and IEEE.
When designing a unit substation, refer to the typical arrange-ments shown in Section 10 of ANSI C37.121-1989. It is alsoimportant to consider the environmental conditions, systemconditions, installation conditions, and load requirements asoutlined in ANSI C37.121-1989.
A unit substation offers the following operational and econom-ical advantages:
SavingsMedium voltage power is purchased at a lower rate than lowvoltage power can be purchased. Transformation to the utiliza-tion voltage at the load center replaces long, high current lowvoltage feeder circuits with less expensive primary cable in thedistribution system.
Better System PerformancePrimary voltage distribution systems feeding load center trans-formers will minimize system voltage drop and improve voltageregulation. Unit substations also divide the electrical systeminto independent load areas, which isolates each area from therest of the system.
SafetyLive parts of all electrical devices are completely enclosed in agrounded steel enclosure. For separate accessibility, internalsteel barriers isolate the incoming line, transformer, and lowvoltage distribution sections from each other. All equipment isdesigned and built in accordance with the latest NEMA andANSI standards. Some components of the unit substation areUL Listed.
Ease of InstallationThe equipment is divided into factory-coordinated shippingsections for ease of handling at the jobsite. Hardware is pro-vided for the connections. Incoming and outgoing connectionsare accessible for ease of installation.
Ease of ExpansionNew unit substations are easily added to primary voltage dis-tribution systems with little effect on the existing equipment.Additional incoming line or low voltage distribution sectionscan be added to an existing unit substation.
MaintenanceThe equipment consists of components designed for minimummaintenance. Refer to operation and maintenance manuals foreach section.
Seismic CalculationsSeismic calculations are available for most Square D substa-tion equipment to show that when anchored as recommended,they will remain anchored during a seismic event. All seismiccalculations are made per the Uniform Building Code. For QEDSwitchboards, seismic calculations are not available, but QEDSwitchboards have been tested and are seismically qualifiedup to seismic zone 4 when anchored as recommended (seeQED switchboard catalog, class 2742 for details).
Manufacturer’s ResponsibilitiesUnit substations are engineered and manufactured by Square DCompany. A single warranty covers the entire unit substation.Square D Company also has a field services division which isavailable for start-up service along with other services.
Unit Substation Selection Tables
Equipment type SPECRight Catalog ClassaSection
Primary Section
Metal-clad switchgear 16350-1 6055
HVL Metal enclosed load interrupter switch 16361-1 6040
VISI/VAC Metal enclosed vacuum load interrupter switchgear 16361-2 6046
Air terminal chamber 16322-1 See Transformer
QED2 Switchboards 16426-1 2742
Transformer Section
VPI conventional power-dry 16322-1 7420
Power-cast cast resin(Primary and secondary coils) 16322-1 7310
Uni-cast cast resin primary withVPI secondary coils 16322-1 7320
Liquid filled –Oil – Silicon – R-Temp® 16322-1 7240
Busway
I-Line/I-Line II 16466-1 5600
Power-Zone Metal-Enclosed 16466-2 6090
a See specific catalog class for individual equipment accessories.
4
General Information
Unit Substation Selection Tables (continued)Secondary Section
Equipment type SPECRight Catalog ClassaSection
Metal-clad switchgear 16350-1 6055
HVL Metal enclosed load interrupter switchgear 16361-1 6040
VISI/VAC Metal enclosed vacuum loadinterrupter switchgear 16361-2 6046
Air terminal chamber 16322-1 SeeTransformer
QED2, 3, 4 low voltage switchboards 16426-1 2742, 2743,2744
PZIII LVDO switchgear 16350-2 6035
Model 6 motor control center 16482-1 8998
Medium voltage motor control center (8198) 16352-1 8198
a See specific catalog class for individual equipment accessories.
SpecificationsSquare D Company offers specifications for a major portion ofits products on computer disks in a program called SPECRight.Contact your local Square D Company sales office to inquireabout this information. The column titled SPECRight Sectionfound in the table identified as the Unit Substation SelectionTable references the section in SPECRight to pull the specifi-cations for each major component in a unit substation.
Standard Product InformationPaint: ANSI 49
Enclosure Type: Indoor - NEMA Type 1Outdoor , non-walk-in - NEMA Type 3RPower Zone Center (Walk-in House)
Connections: High Voltage Windings - DeltaLow Voltage Windings - Delta or Wye
Common 34.5 kV, 24.9 kV, 13.8 kV, 13.2 kV, 12.47 kV, Primary Voltages: 7.2 kV, 4.8 kV, 4.16 kV, 2.4 kV, 480 V
Common 4.8 kV, 4.16 kV, 4.16Y/2.4 kV, 2.4 kV, Secondary Voltages: 600 V, 480 V, 480Y/277 V, 208Y/120 V
Frequency Rating: 60 Hz
Note: For additional ratings and application data, refer to thecatalog sections referenced in the Unit Substation SelectionTable on Page 1.
Power-Flow Nameplate
Power-Flow Nameplates are available showing electrical flowthrough a one line diagram.
An 11x17 (max. size) power-flow nameplate is a replacementfor mimic bus on which users usually require the use of paint,tape, or plastic strips. The nameplate consists of a white back-ground with a black core for the lettering and one line. If the cus-tomer does require mimic bus, the options are paint or plasticstrips.
M
CustomerGround
#2 B
KV
Cab
le P
er P
hase
M
5
Major Components General Information
Metal-Enclosed, Type HVL, Medium VoltageLoad Interrupter Switchgear
General Description• Primary and secondary equipment• UL Listed (if required; restrictions apply)• 2.4 to 38 kV• 600 and 1200 amperes continuous current• Unfused/fused• Current limiting/boric acid fuses• FUSELOGIC blown fuse indication
(can also coordinate with shunt trip option for auto-matic shunt trip)
• Shunt trip
• Indoor and outdoor weatherproof enclosures• Single switch bay incoming section• Duplex arrangement available• Line selector arrangement available• Utility/customer metering bay available• Multiple switch bays for distribution sections• Secondary designed for future additions
For further information, see Square D Catalog Class 6040.
Fusible Interrupter Switch 5 and 15 kV Single Bay Section
NEMA Type 115 kV Indoor Unit
NEMA Type 3R15 kV Outdoor Unit with outer door opened
6
Major Components General Information
General Description• Primary and secondary equipment• No external arcing — current interruption within vacuum
interrupters• Automatic visible circuit isolation• Long life —2500 full-load interruptions• Shunt-trip mechanism• Shunt-close mechanism• Motor operator standard for remote operation
• Protective relaying capability (phase overcurrent, groundfault, phase fault, phase failure, undervoltage, etc.)
• Requires no more floor space than conventional metal-enclosed air switches
• Retrofit opportunities with existing load interrupterswitchgear
• Secondary designed for future addition• Indoor and outdoor enclosures
See Class 6046 for further information.
Metal-Enclosed VISI/VAC®, Medium Voltage Circuit Interrupter Switchgear
(Shown here with door open) (Door closed)
7
Major Components General Information
General Description• Primary and secondary equipment• VR Circuit Breakers• 5 and 15 kV • 1200-3000 amperes• 250-1000 MVA interrupting capacity• 60 and 95 kV BIL• Indoor and outdoor enclosures• Removable circuit breaker• Fully compartmentalized construction
• Grounded metal barriers• Automatic shutters• Insulated bus• Mechanical interlocks• Disconnect type voltage transformers-CPT and VTs• Low voltage instrument/ control compartment isolated
from primary voltage area• Protective relaying and metering
See brochure 6055BR9402 for further information.
MASTERCLAD™ Metal-Clad Switchgear
Typical NEMA Type 1 Switchgear Assembly
8
Major Components General Information
POWER-ZONE® III Low Voltage DrawoutSwitchgear
General Description• Low Voltage ANSI rated switchgear meets ANSI
C37.20.1, ANSI 37.51, NEMA SG-5.• Individually mounted, ANSI rated, low voltage, power DS
(not fusible) and DSL (fusible) circuit breakers. Breakersmeet ANSI C37.13, ANSI C37.16, ANSI C37.50, NEMASG-3.
Available breakers:DS, DSL-206, DS-206H, DS-206E 800 A FrameDS, DSL-416, DS-416H 1600 A FrameDS-420 2000 A FrameDS, DSL-632 3200 A FrameDS, DSL-840 4000 A FrameDS-850 (forced-air cooled) 5000 A Frame
• Microprocessor trip device enables the user to attainoptimum system selectivity and coordination. Digitrip510 standard, POWERLOGIC Digitrip 810D available.
• Breakers are 100% rated, two-step stored energy circuitbreakers
• Use as main or feeder devices• Copper bus systems up to 5000 A• Integral ground fault protection• Key interlocking• Compartmentalized construction per ANSI C37.20.1• Optional circuit breaker lifting device mounted on the
switchgear• Indoor or outdoor construction. Outdoor construction
uses POWER-ZONE center enclosure.• Front and rear accessibility• Rear access required for loadside cable connections• UL Labeled (optional). UL 1558 for structure, UL 1066 for
DS circuit breakers
Optional BreakerLifting Device
QED POWER-STYLE® Switchboards
Incoming Primary Section
General Description• Used as incoming section of 600 volt secondary unit
substation (POWER-DRY transformer only)• Available up to 5000 amperes• Fixed or Drawout construction• Main devices:
Molded case circuit breakers-M, N, and P frames(2500 A max.)Fusible switch - BOLT-LOC (4000 A max.)Stored Energy Electronic trip circuit breakers-SE (4000 Amax.)Masterpact (5000 A max.)
• Ground fault protection and metering available• Indoor or outdoor construction• Front and rear accessibility• Incoming cable terminations available• UL Labeled
QED Secondary Mains
General Description• Used as the secondary main device or six subdivision
mains up to 4000 A • Available up to 5000 amperes• Fixed or Drawout construction• Main devices:
Molded case circuit breakers-M, N, and P frames(2500 A max.)Fusible switch-BOLT-LOC (4000 A max.)Electronic trip circuit breakers-SE (4000 A max.)Masterpact (5000 A max.)
• Ground fault protection and metering available• Indoor or outdoor construction• Top or bottom feed• Front and rear accessibility• UL Labeled
9
Major Components General Information
10
Major Components General Information
QED Distribution Section
General Description• Used as distribution sections in conjunction with QED
main devices• Available in:
I-LINE distribution section-group mounted I-LINE circuitbreakersQMB distribution section-group mounted QMB/QMJswitches
• 3000 A maximum vertical bus• 5000 A maximum main bus
• 80% or 100% rated circuit breakers available• Integral Zone Selective Interlocking• Ground Fault protection and metering available• Single or Double row construction• Indoor or outdoor construction for I-LINE panels• Copper or aluminum bus available• Front and rear accessibility• UL Labeled
QMB Distribution Section
I-LINE Distribution Section• 63" panel height for 2000 A vertical bus• 72" panel height for 3000 A vertical bus• 54" maximum single-row breaker mounting space• 117" maximum double-row circuit breaker mounting
space for 2000 A vertical bus• 112.5" maximum double-row circuit breaker mounting
height for 3000 A vertical bus• See QED catalog (class 2742) for circuit breaker mount-
ing restrictions and panel widths
QMB/QMJ Distribution Section• 3000 A maximum vertical bus rating• 72" maximum QMB/QMJ switch mounting space• Switches up to 400 A mount in 36" wide section• Switches 400 A-1200 A mount in 42" wide section
I-LINE Distribution Section
POWER-STYLE Switchboards
QED-3 Distribution Sections
QED-3 Distribution Sections with QED Main
General Description• For use with QED Main Section• Individually mounted feeders to 1200 A• 3000 A maximum vertical bus ratings• 5000 A maximum main bus• 80% or 100% rated circuit breakers• Key interlocking available• Integral zone selective interlocking available• Ground fault protection and metering available• Compartmentalized construction• Each 24" (610 mm) section has four 18" (457 mm) com-
partments for mounting circuit breakers• Indoor or outdoor construction• Copper or aluminum bus available• Rear access required for loadside cable connections• UL Labeled• See QED-3 catalog (class 2743) for circuit breaker
mounting restrictions.
QED-4 Distribution Sections
General Description• For use with QED main section• Individually mounted feeders to 2500 A (SE,NE, and NX
drawout circuit breakers)• 4000 A maximum vertical bus ratings• 5000 A maximum main bus• 100% rated circuit breakers• Integral zone selective interlocking available• Ground fault protection and metering available• Key interlocking available• Compartmentalized construction:
Barriers between the circuit breaker compartment andthe through-busBarriers between the through-bus compartment andthe lug compartment
• Each 24" wide (610 mm) section has four 18" high com-partments for mounting circuit breakers
• Optional circuit breaker lifting device mounted on theswitchboard
• Indoor or outdoor construction• Copper or aluminum bus available• Rear access required for loadside cable connections• UL Labeled• See QED-4 catalog (class 2744)
11
Major Components General Information
Distribution with Drawout SE Circuit Breakers
12
Major Components General Information
Dry Type Transformers
General Description
Ratings
Item Standard Optional
kVA Sizes 225-5000 —
Primary Voltage Classes 480 V to 26.4 kV —
Secondary Voltages 208Y/120, 240 Delta 480Y/277, 600Y/347480 Delta, 600 Delta, 2400Y, 2400 Delta 240Y/1394160Y, 4160 Delta
(Note: For specific combinations of kVA sizes with primary and secondary voltages, refer to the Medium Voltage Transformer Specification Guide.)
Basic Impulse Levels 2.4 kV-20 kV BIL —5.0 kV-30 kV BIL 60 kV BIL
15.0 kV-60 kV BIL 95 kV BIL25.0 kV-125 kV BIL —
Winding Temperature Rise 150°C 115°C, 80°C
Impedance 5.75% for 500 kVA and Above Available upon request
Insulation System 220°C —
Sound Level Per NEMA ST20 Standard Lower levels
Conductor Material Aluminum Copper
Forced Air Rating Increases kVA by 33 1/3% —
Taps (2) 2 1/2% above and below —Primary Voltage (2400 V and above)
Accessories• Lightning Arresters (intermediate or station class require
air terminal chamber or must be mounted in switchgearsection)
• Provisions for future forced air (FFA)• Forced air cooling (FA)• Electronic temperature indicators• Air terminal chambers (ATC) on primary or secondary• Strip heaters• Key interlock• Indoor or outdoor enclosure• TENV enclosures• UL Listing
Special Applications• UL Listed K-rated units for non-linear loads• Special ambients or altitudes• Low sound levels• 50 Hz requirements• Electrostatic shielding
Unusual Service Conditions - need to identify and advisefield sales or manufacturing plant
• Damaging fumes or vapors, excessive abrasive or metal-lic dust, steam, salt spray, moisture or dripping water,corrosive atmosphere, or any other special conditions
• Abnormal vibration or shock• Unusual transportation or storage conditions• Unusual space limitations• Unusual operating duty, frequency of operation, poor
wave form, unbalanced voltage, or special insulationrequirements
• Seismic requirements
For additional information see Square D catalog section Class7420/7425.
POWER CAST Transformers – Vacuum CastResin Coils
General DescriptionRatings
Item Standard Optional
kVA Sizes 225-10000 —
Primary Voltage Classes 2.4 kV to 34.5 kV —
Secondary Voltages 208Y/120, 480Y/277,480 Delta, 2.4 Delta —4.16Y, 4.16 Delta4.8 kV Delta
(Note: For specific combinations of kVA sizes with primary and secondary volt-ages, refer to the Medium Voltage Transformer Specification Guide.)
Basic Impulse Levels 2.4 kV-45 kV BIL 60 kV BIL5.0 kV-60 kV BIL 75 kV BIL
15.0 kV-95 kV BIL 110 kV BIL25.0 kV-125 kV BIL 150 kV BIL34.5 kV-150 kV BIL 200 kV BIL
Winding Temperature Rise 80°C 115°C
Impedance 5.75% ± 7.5% depending Available uponon HV, BIL, LV ratings request
Insulation System 150°C 185°C
Sound Level Per NEMA ST20 Standard Lower levels
Conductor Material Copper —
Forced Air Rating:500 - 750 kVA Increases kVA by 33 1/3% —
1000 - 5000 kVA Increases kVA by 50% —
Taps (2) 2 1/2% above and —below Primary Voltage
Optional Accessories• Lightning arresters (available with air terminal chamber
only–otherwise these must be mounted in switchgearsection)
• Provisions for future forced air (FFA)• Forced air cooling (FA)• Electronic temperature indicators (Three Phase)• Air terminal chambers (ATC) on primary or secondary• Key interlocks• Indoor or outdoor enclosure
Special Applications• Special ambients or altitudes• Low sound levels• 50 Hz requirements• Electrostatic shielding
Unusual Service Conditions - need to identify and advisefield sales or manufacturing plant
• Damaging fumes or vapors, excessive abrasive or metal-lic dust, steam, salt spray, moisture or dripping water,corrosive atmosphere, or any other special conditions
• Abnormal vibration or shock• Unusual transportation or storage conditions• Unusual space limitations• Unusual operating duty, frequency of operation, poor
wave form, unbalanced voltage, or special insulationrequirements
• Seismic requirements
For additional information see Square D catalog section Class7310.
13
Major Components General Information
UNI-CAST™ Transformers – Primary Coil –Vacuum Cast Resin; Secondary Coil – VPI
General DescriptionRatings
Item Standard Optional
kVA Sizes 500-10,000 —
Primary Voltage Classes 2.4 kV to 15 kV —
Secondary Voltages 208Y/120, 480Y/277,480 Delta, 240 Delta —
(Note: For specific combinations of kVA sizes with primary and secondary voltages, refer to the Medium Voltage Transformer Specification Guide.)
Basic Impulse Levels 2.4 kV-45 kV BIL5.0 kV-60 kV BIL Consult Factory
15.0 kV-95 kV BIL
Winding Temperature Rise 100°C 80°C
Impedance 5.75% ±7.5% depending upon Available uponKVA, HV BIL and LV rating request
Insulation System 185°C —
Sound Level Per NEMA ST20 Standard Lower levels
Conductor Material Aluminum Copper
Forced Air Rating Increases kVA by 33 1/3% —
Taps (2) 2 1/2% above and below —Primary Voltage
Optional Accessories• Lightning arresters (available with air terminal chamber
only–otherwise these must be mounted in theswitchgear section)
• Provisions for future forced air (FFA)• Forced air cooling (FA)• Electronic temperature indicators (Single Phase or Three
Phase)• Air terminal chambers (ATC) on primary or secondary• Key interlocks• Indoor or outdoor enclosure
Special Applications• Special ambients or altitudes• Low sound levels• 50 Hz requirements• Electrostatic shielding
Unusual Service Conditions - need to identify and advisefield sales or manufacturing plant
• Damaging fumes or vapors, excessive abrasive or metal-lic dust, steam salt spray, moisture or dripping water, cor-rosive atmosphere, or any other special conditions
• Abnormal vibration or shock• Unusual transportation or storage conditions• Unusual space limitations• Unusual operating duty, frequency of operation, poor
wave form, unbalanced voltage, or special insulationrequirements
• Seismic requirements
14
Major Components General Information
15
Major Components General Information
Liquid-filled Transformers
General DescriptionRatings
Item Standard Optional
kVA Sizes 225-10000 —
Primary Voltage Classes 2.5 kV, 5 kV —15 kV, 25 kV, 34.5 kV —
208Y/120 500-1500 kVA —Secondary Voltages 480Y/277, 480 Delta 500-3750 kVA —
2.4 kV, 4.16 kV, 4.8 kV 225-10000 kVA —
(Note: For specific combinations of kVA sizes with primary and secondary volt-ages, refer to the Medium Voltage Transformer Specification Guide.)
2.5 kV- 45 kV BIL 60 kV BIL5.0 kV- 60 kV BIL 75 kV BILBasic Impulse 15.0 kV- 95 kV BIL 110 kV BILLevels 25.0 kV-125 kV BIL 150 kV BIL
34.5 kV-150 kV BIL 200 kV BIL
Winding Temperature Rise 65°C 55/65°C
Coolant Mineral oil Silicone,RTEmp
Impedance 4.0%-8.0% depending —on kVA and LV ratings
Sound Level Per NEMA TR-1 Standard Lower levels
Conductor Material Aluminum/Copper (Sq D Option) Copper
Forced Air Rating: Increases kVA by 15% 225-2000 kVA —Increases kVA by 25% 2500-10000 kVA —
2-2 1/2% above and below 4-2 1/2% full Taps primary voltage capacity
primary voltage
Standard Features• Deenergized tap changer, padlockable• One inch upper filling plug and filter press connection• One inch drain valve with sampler• Dial type thermometer without alarm contacts• Liquid level gauge without alarm contacts• Pressure/vacuum gauge, with bleeder connection,
without alarm contacts• Provisions for jacking and lifting• Pressure relief valve
Optional Accessories• Alarm contacts for accessory gauges• Sudden pressure relay (with or without seal-in relay)• Key interlock on tap changers• Provisions for mounting grounding resistors• Instrument transformers (low voltage air terminal
chamber required)• Surge arresters (high voltage air terminal chamber
required-otherwise these must be mounted inswitchgear section)
• Provisions for future forced air (FFA)• Forced air cooling (FA)• Air terminal chambers on primary or secondary
Special Applications• Special ambients or altitudes• 50 Hz requirements
Unusual Service Conditions - need to identify and advisefield sales or manufacturing plant
• Damaging fumes or vapors, excessive abrasive or metal-lic dust, steam, salt spray, moisture or dripping water,corrosive atmosphere, or any other special conditions
• Abnormal vibration or shock• Unusual transportation or storage conditions• Unusual space limitations
For additional information, see Square D catalog section Class7420.
16
Major Components General Information
Model 5/6 Motor Control Centers
• Can be utilized on substation secondary with QEDswitchboard main section
• For system voltages to 600 V• Horizontal main bus and vertical distribution bus and
wireways standard• 600 A, 800 A, 1200 A, 1600 A, or 2000 A main bus rating• NEMA Type 1, 1 Gasketed• Main lugs 600 A - 2000 A• Main Circuit Breaker 110 A - 2000 A (high interrupting
circuit breakers standard)• Main Fusible Switch 200 A - 2000 A (Class R or L fuses
standard• NEMA wiring Classes 1 and 2, Types A, B, and C
available• Full-Voltage Non-Reversing, Full Voltage Reversing, Two
Speed and Reduced-Voltage Autotransformer combina-tion starter units
• Branch Feeder Circuit Breakers 15 A-1200 A (FA, KA, LA,MA, PA frames)
• Fusible Switch feeder units 30 A -1200 A (class H, R orL fuse clips depending upon current rating)
• Empty mounting units, equipped spaces, distributiontransformers and NQOD and NEHB panelboards available
Model 5 Standard Features• Al Power Bus• Steel Vertical Ground Bus• Any of the structural features from the Model 6 Standard
Features List may be purchased A la Carte
Model 6 Standard Features• Cu Power Bus• Cu Vertical Ground Bus• Vertical Wireway Barrier• Bus Barrier Closing Shutters• White Unit Interiors• MCC Buckets have easy-removal feature
17
Major Components Information
Busway Systems
I-LINE/I-LINE II Busway• I-LINE plug-in available from 225 A-600 A with aluminum
or copper conductors• I-LINE II plug-in and feeder styles available 800 A-4000 A
with aluminum conductors, to 5000 A with copper con-ductors
• Available up to 600 V• 3 and 4-pole full neutral configuration• Sandwich construction to provide superior voltage drop
characteristics• Totally enclosed housing• Compact size• Durable electro-deposition epoxy paint finish• Bus bars insulated using class B rated (130°C vendor
certified) materials• Plated Bus bars• Dielectric testing 7000 Vdc standard• One bolt joints with VISI-TITE® torque-indicating bolts
(clamping force of over 4000 lbs.) for ratings less than2000 A. For ratings higher than 2000 A, two or three boltsare used.
• EZ JOINT PACK® removable single bolt joint packageavailable (with VISI-TITE® torque-indicating bolts)
• I-LINE II uses one set of universal tie channels, speedinginstallation
• I-LINE II includes internal fire barriers• Ratings of 200,000 RMS Symmetrical available for
4000 A and 5000 A feeder busway• Outdoor busway available• Universal fittings for maximum layout flexibility• I-LINE II Busway includes integral (50%) ground bus
100 A Plug-In Busway• Totally enclosed plug-in busway• 100 A full load rating
• 3 phase, 4W 480 V or 3 phase, 3W 600 V• Round, electrical grade aluminum or copper conductors• Optional 50% ground bus• Molded phenolic insulators between bus bars• Short-circuit ratings up to 14,000 A symmetrical• High-pressure spring-type connectors at each joint• Wrap-around type hangers (UL Listed in edgewise
mounting position with 10' hanger spacing) or “C” clamp(UL Listed in flatwise mounting position with buswayhung on 5' centers) hangers available
POWER-ZONE® Metal-Enclosed Busway• Available for indoor or outdoor use• Custom designed and manufactured• Available in the following configurations
Voltage Class Continuous Current Momentary KA ASYM
600 V 1200-4000 A 75, 100, 125
5 and 15 kv 1200-5000 A 40
• Designed according to ANSI C37.23• Can be supplied with full round edge plated copper or
plated aluminum bus bars• Insulation for the 5 kV-38 kV bus is fluidized bed epoxy
rated at 130°C. 600 V bus bars are not jacketed• 5 and 15 kV shipping split bus joints are insulated with
removable boots• Bus Supports for 600 V systems are fiberglass. 5 and
15 kV supports are molded using a UL Listed glass rein-forced polyester. 38 kV supports are porcelain.
• Aluminum housing is standard• Painted or stainles steel available as optional• Strip heaters are provided on outdoor construction• Structural supports are available
18
Special Applications and Products
Type 36 Compact Sectional Unit Substation
General DescriptionCompact sectional load center unit substations permit easyhandling through existing doors and hallways. They can beinstalled in locations where physical space limitations will notpermit the installation of a conventional load center unit sub-station. Besides having less depth, the compact designrequires front access only. The transformer’s rectangular barrelwound core and coil and enclosure design requires no ventila-tion from the rear (ventilated rear panels are provided).
• Depth of unit substation 36" (Max.)• Indoor enclosure ONLY• ANSI 49 paint• Requires front access only
Incoming Primary Load Interrupter Switchgear - HVL• UL Listed (If Required)• 600 A Switch• Blown Fuse Indication• Cable connection to transformer• Keylock optional• Unfused or Current-Limiting Fuses Only• Shunt Trip• Two cables per phase maximum• Distribution class surge arresters (optional)• No instrument transformers or metering• 12" top pullbox required (top or bottom entry)
VPI Power-Dry Transformer RatingsItem Standard Optional
kVA Sizes 225-750 —
Primary Voltage Classes 600 V to 15.0 kV —
Secondary Voltages 208Y/120, 480Y/277, 480 Delta, 600 V Delta -10 kV BIL
Basic Impulse Levels 5.0 kV-30 kV BIL —15.0 kV-60 kV BIL —
Winding Temperature Rise 150°C 115°C (to 750 kVA)80°C (to 500 kVA)
UL Listed — 225 kVA-750 kVA(750 kVA at 150°C rise only)
Secondary Main and Distribution Sections - QED-2POWER-STYLE Switchboard
Main Section• Fixed mounted main device available up to 2500
amperes • Main devices:
Molded case circuit breakers - M, N, and P framesFusible switch - BOLT-LOCStored-energy electronic trip circuit breakers - SE
• Ground fault protection and metering available• Top or bottom feed• UL Labeled• Keylock optional
Distribution Section• Available in:
I-LINE distribution section - group mounted I-LINEcircuit breakersQMB distribution section - group mounted QMB/QMJswitches
• 80% or 100% rated circuit breakers• Single or double row construction for I-LINE circuit
breakers• Copper or aluminum bus• UL Labeled• Provisions for future extension
19
Special Applications and Products
Model III POWER-ZONE®
Package Unit Substation
General Application DataModel III POWER-ZONE package unit substations incorpo-rate—into one pre-assembled, unitized module—an HVLswitch, dry-type transformer and molded-case circuit breakerdistribution section. All components are manufactured bySquare D. The complete package unit substation is engineeredand tested as one integral unit by Square D.
The Model III is only 36" (914 mm) deep and 85" (2159 mm)high, so it will pass through most existing doorways withoutstructural renovation to the building in which it is installed. Totalweight is less than 8,000 pounds (3629 kg) and the footprintoccupies less than 22 square feet (2.04 m2) of floorspace, for afloor-loading of less than 365 lb./sq. ft. (1782 kg/m2).
The air intake is located at the front bottom; the exhaust is ontop of the transformer section, so the unit can be installedagainst a wall or in a corner without alteration or derating.
Model III POWER-ZONE package unit substations are ideal fornew installations in existing buildings as well as for spot zonedistribution in new construction.
Substations are normally shipped as two units, split betweenthe incoming line section and the transformer/low voltage dis-tribution sections. Upon request, they can be provided in onesection on a common base.
Model III POWER-ZONE package unit substations are avail-able in sizes from 75 kVA through 500 kVA with three phaseprimary voltages of 2400 volts through 13,800 volts. Whenequipped with fan cooling, ratings as high as 667 kVA are avail-able, AA/FA. Secondary voltages of 600 V delta, 480 V delta,480Y/227, 208Y/120 and 240 V delta are available. The trans-
former is built with 220°C insulation. 150°C rise is availablethrough 500 kVA. 115°C and 80°C rise are available up to300 kVA. ANSI 49 or ANSI 61 paint is available.
The secondary circuit breaker distribution section is equippedwith an I-LINE®‚ distribution panelboard which accepts thetime-tested and widely acclaimed plug-on I-LINE family ofmolded case circuit breakers. Branch circuit breakers as smallas 15 A single pole FY or FA frame with 1.5" (38 mm) mountingheight, to as large as 1200 A NA frame 3-pole breakers with 15inches (381 mm) mounting height may be installed. ME/NEframe electronic trip breakers and I-LIMITER®‚ high interruptingcapacity current limiting circuit breakers may also be used. Thissection provides 81" (2057 mm) of circuit breaker mountingheight.
Model III substations allow faster and easier installations. Theircompact design allows a greater choice of installation loca-tions. Package substations provide lower cost systemsthrough:
• Service Continuity — Substations located at each loadarea isolate outages and allow faster trouble-shooting.
• Expansion — Substations divide a system into isolatedsections which are unaffected by the addition of newload areas.
• Efficient Performance — Shorter secondary feederslower power loss and provide better voltage regulation.
• Lower Power Cost — Power is purchased at lowerprimary rates.
• Lower Equipment Costs — High voltage cable is lessexpensive than high-current, low voltage feeder circuits.Smaller, less expensive molded case breakers offset theextra transformer cost.
For additional information including layouts, see Bulletin D1-NClass 6010/02, or contact Square D/Sorgel in Milwaukee.
20
Typical Key Interlock Schemes
IntroductionKey interlocks are an integral part of many unit substations.Square D Company offers completely coordinated key inter-lock systems. For convenience, 14 commonly used key inter-lock schemes are described in the following pages. If one ormore of the key interlock schemes shown is to be included witha Square D unit substation, please mention the method numberwhen the order is placed. Other key interlock schemes areavailable – please contact your local Square D field sales office.
Method 1.Function: To prevent the operation of disconnect switch Awhen breaker B is closed.
To prevent the opening of the fuse compartment door when thedisconnect switch A is closed.
The breaker, fuse compartment door and disconnect switchare shown in closed positions. Key A-1 is held in breaker inter-lock and key A-2 is held in disconnect interlock.
To service the breaker:
1. Open the breaker.2. Turn key A-1 in L-O interlock on breaker to lock breaker
open. Key A-1 is now free.3. Insert key A-1 in L-O-C interlock on disconnecting switch
and turn to unlock. Key A-1 is now held.4. Open disconnect.5. Turn key A-1 in L-O-C interlock on disconnect switch to
lock open. Key A-1 is now free.6. Return key A-1 to breaker interlock and unlock for oper-
ation of the breaker during servicing.
Reverse the sequence to restore service.
To open the fuse compartment door:
1. Proceed from operations 1 through 4 above.2. Turn key A-2 in L-O interlock on the disconnect switch to
lock open. The key A-2 is now free.3. Insert the key A-2 in L-C interlock on the fuse compart-
ment door and turn to unlock. The key A-2 is now held.4. Open the fuse compartment door.
Reverse the sequence to restore service.
Method 2.
Function: To prevent the operation of disconnect switch Awhen breakers B, C, D and E are closed. (Breakers may beopened in any sequence.)
Disconnect A and breakers B, C, D and E are shown in theclosed position. The key A-1 is held in Transfer interlock. KeysA-2, A-3, A-4, and A-5 are held in the interlocks on Breaker B,C, D, and E.
1. Open breakers B, C, D and E.2. Turn the key in L-O interlock on each Breaker B, C, D and
E to lock the breakers open. The keys A-2, A-3, A-4, A-5are now free.
3. Insert keys A-2, A-3, A-4 and A-5 in the transfer interlock.4. Turn key A-1 in the Transfer interlock. Key A-1 is now free.
(Keys A-2, A-3, A-4 and A-5 are now held.)5. Insert key A-1 in L-O-C interlock on disconnect A and turn
to unlock. Key A-1 is now held.6. Open disconnect A.7. Turn key A-1 in L-O-C interlock on disconnect A to lock
open. Key A-1 is now free.8. Insert key A-1 in Transfer interlock and turn. Key A-1 is
now held. Keys A-2, A-3, A-4 and A-5 are now free.9. Return keys A-2, A-3, A-4 and A-5, as desired, to breaker
interlocks and unlock for operation during servicing.
Reverse the sequence to restore service.
L-O
A-2
L-C
L-O
A-1
LOC
E
A
E
E
EA 2
A 1
A 2
L-O
A
B
A 1
A 3
L-O
CA 4
L-O
DA 5
L-O
E
A-1
A-5
LOC
W
A-4W
A-3W
A-2W
E
T
21
Method 3.
Function: To prevent the operation of disconnect switch Awhen breakers B, C, D and E are closed.
Note: Breakers must be opened in prearranged sequence.
(Electrical circuit is equivalent of Method 2.)
Disconnect A and Breakers B, C, D and E are shown in theclosed positions. Key A-1 is held in the breaker B interlock. KeyA-2 is held in the breaker C interlock, key A-3 is held in thebreaker D interlock and key A-4 is held in the breaker E inter-lock. Key A-5 is held free in the breaker E interlock or is retainedby the supervisor.
1. Obtain key A-5 from supervisor.2. Open breaker E.3. Insert key A-5 in the L-O interlock on breaker E and turn
Key A-5 to lock open. Key A-5 is now held. Key A-4 isnow free.
4. Open breaker D.5. Insert key A-4 in L-O interlock on breaker D and turn key
A-3 to lock the breaker open. Key A-4 is now held. KeyA-3 is now free.
6. Open breaker C.7. Insert key A-3 in L-O interlock on breaker C and turn key
A-2 to lock the breaker open. Key A-3 is now held. KeyA-2 is now free.
8. Open breaker B.9. Insert key A-2 in L-O interlock on breaker B and turn key
A-1 to lock the breaker open. Key A-2 is now held. KeyA-1 is now free.
10. Insert key A-1 in L-O-C interlock on disconnect A andturn to unlock. Key A-1 is now held.
11. Open the disconnect.12. Turn the key A-1 in L-O-C interlock on disconnect A to
lock it open. Key A-1 is now free.13. Insert key A-1 in L-O interlock on breaker B and turn it
to unlock. Key A-1 is now held and key A-2 is free.
14. Breaker A may now be operated for servicing.15. Insert key A-2 in L-O interlock on breaker C and turn it
to unlock. Key A-2 is now held, and key A-3 is free.16. Breaker C may now be operated for servicing.17. Insert key A-3 in L-O interlock on breaker D and turn it
to unlock. Key A-3 is now held and key A-4 is free.18. Breaker D may now be operated for servicing.19. Insert key A-4 in L-O interlock on breaker E and turn it to
unlock. Key A-4 is now held and the supervisor’s key A-5 is free.
20. Breaker E may now be operated for servicing.Reverse the sequence to restore service.
Method 4.Function: To prevent the paralleling of lines A and B.
Single load, fed from either source.
To prevent the operation of disconnect switches A and B whenthe breaker C is closed.
Breaker C and the disconnect A are shown in the closed posi-tion. Disconnect B is shown in the open position. The key A-1is held in the breaker C interlock. The key A-2 is held in the dis-connect A, L-O interlock.
To service the breaker:1. Open breaker C.2. Turn key A-1 in the L-O interlock on the breaker to lock it
open. Key A-1 is now free.3. Insert key A-1 in the L-O-C interlock on disconnect A and
turn it to unlock. Key A-1 is now held.4. Open disconnect switch A.5. Turn key A-1 in the L-O-C interlock on disconnect A to
lock it open. Key A-1 is now free.6. Return key A-1 to the breaker interlock and unlock it for
operation of the breaker during servicing.
To transfer the load from line A to line B:1. Open breaker C.2. Turn key A-1 in the L-O interlock on the breaker to lock
it open. Key A-1 is now free.3. Insert key A-1 in the L-O-C interlock on disconnect A
and turn it to unlock. Key A-1 is now held.4. Open disconnect switch A.
Typical Key Interlock Schemes
A 2
L-O
A 1
L-O
A-1
LOC
A-1
LOC
A-2
L-O
C
A
A
B
B
A-2
L-O
A
BA-3
L-O
CA-4
L-O
DA-5
L-O
E
A 1 A 2 A 3 A 4
A 5
A-1
LOC
E
W
E
W
E
W
E
W
SupervisoryKey
22
Typical Key Interlock Schemes
5. Turn key A-1 in the L-O-C interlock and key A-2 in L-Ointerlock on disconnect A to lock open. Keys A-1 and A-2 are now free.
6. Insert key A-1 in the L-O-C interlock on disconnect Band turn it to unlock. Key A-1 is now held.
7. Insert key A-2 in the L-O interlock on disconnect B andturn it to unlock. Key A-2 is now held.
8. Close disconnect switch B.9. Turn key A-1 in the L-O-C interlock on disconnect B to
lock it closed. Key A-1 is now free.10. Insert key A-1 in the breaker interlock and turn it to
unlock. The key A-1 is now held.11. Close the breaker.
Reverse the sequence to restore service through line A.
Method 5.Function: To prevent the paralleling of lines A and B.
Two loads, fed from either source (one tie-breaker).
To prevent the operation of disconnect switch D when breakerA is closed.
To prevent the operation of disconnect switch E when breakerB is closed.
The disconnect switches D and E and breakers A and B areclosed. Breaker A is closed to supply the load M. Breaker B isclosed to supply the load N. Tie-Breaker C is open. Keys A-1and A-2 are held in the interlock on breaker A. Keys A-1 and A-3 are held in the interlock on breaker B. The Tie-Breaker Ccannot be closed until either breaker A or B is locked open.
To transfer load N to breaker A, proceed as follows:1. Open breaker B.2. Turn key A-1 in L-O interlock on breaker B to lock it open.
Keys A-1 and A-3 are now free.3. Insert key A-1 in L-O interlock on tie-breaker C and turn
it to unlock. Key A-1 is now held.4. Close tie-breaker C.
Reverse the sequence to restore service through breaker B.Load M can be supplied through breaker B in a similar manner.
To service Breaker B, proceed as follows:1. Open breaker B.2. Turn key A-1 in the L-O interlock on breaker B to lock it
open. Keys A-1 and A-3 are now free.3. Insert key A-3 in the L-O-C interlock on disconnect E and
turn it to unlock. Key A-3 is now held.4. Open disconnect E.5. Turn key A-3 in the L-O-C interlock on disconnect E to
lock it open. Key A-3 is now free.6. Return key A-3 to the L-O interlock on breaker B and
unlock it for operation of the breaker during servicing.Reverse the sequence to restore service.Breaker A can be serviced in a similar manner.
Method 6.Function: To prevent paralleling of lines A and B.
Two loads, fed from either source (one tie-breaker).
To prevent the operation of disconnect switch D when breakerA is closed.
To prevent the operation of disconnect switch E when breakerB is closed.
To prevent the opening of the fuse compartment door when theassociated disconnects D or E and breakers A and B areclosed.
Disconnect switch D and breaker A are closed to supply loadM. Disconnect switch E and breaker B are closed to supplyload N. Tie-breaker C is open. Keys A-1 and A-2 are held in theinterlock on breaker A. Key A-3 is held in the L-O interlock ondisconnect D. Keys A-1 and A-4 are held in the interlock on thebreaker B. Key A-5 is held in the L-O interlock on the discon-nect E. The tie-breaker C cannot be closed until either breakerA or B is locked open.
A-2 A-4
LOC
A-3
A-2
L-O
A
D
A
A-1
L-O
C
L-O
A 1
A 2
A 3
L-O LOC
A 5
E
E
L-O
A 1
A 4
E
E
L-C
A-5
A-4
L-C
E
E
E
E
M
B
E
B
N
A-2
LOC
A-1
L-O
A-3
LOC
C
A B
A
D
B
E
L-O
A 1
A 2
L-O
A 1
A 3
E
E
E
E
M N
23
To transfer load N to breaker A, proceed as follows:1. Open breaker B.2. Turn key A-1 in L-O interlock on breaker B to lock it open.
Keys A-1 and A-4 are now free.3. Insert key A-1 in L-O interlock on tie-breaker C and turn
it to unlock. Key A-1 is now held.4. Close tie-breaker C.
Reverse the sequence to restore service through breaker B.Load M can be supplied through breaker B in a similar manner.
To service breaker B, proceed as follows:1. Open breaker B.2. Turn key A-1 in L-O interlock on breaker B to lock it open.
Keys A-1 and A-4 are now free.3. Insert key A-4 in the L-O-C interlock on disconnect E and
turn it to unlock. Key A-4 is now held.4. Open disconnect E.5. Turn key A-4 in L-O-C interlock on disconnect E to lock it
open. Key A-4 is now free.6. Return key A-4 to L-O interlock on breaker B and unlock
it for operation of breaker during servicing.Reverse the sequence to restore service. Breaker A can be ser-viced in a similar manner.
To enter the fuse compartment on line B, proceed as follows:1. Open breaker B.2. Turn key A-1 in L-O interlock on breaker B to lock it open.
Keys A-1 and A-4 are now free.3. Insert key A-4 in L-O-C interlock on disconnect E and turn
to unlock. Key A-4 is now held.4. Open disconnect E.5. Turn key A-4 in L-O-C interlock on disconnect E to lock it
open. Key A-4 is now free.6. Turn key A-5 in L-O interlock on disconnect E to lock it
open. Key A-5 is now free.7. Insert keys A-4 and A-5 in L-C interlock on the fuse com-
partment door and turn it to unlock. Keys A-4 and A-5 arenow held.
8. Open the fuse compartment door.Reverse the sequence to restore service.The fuse compartment on line A can be entered in a similarmanner.
Method 7.Function: To prevent the paralleling of three power sourcesthrough a common tie bus not normally in service.
To permit the feeding of any load bus from a second powersource through the tie bus.
Breakers A, B, and C are normally closed. Breakers D, E, and Fare normally open. Under normal conditions, key A-1 and A-5are held in breaker A interlock, keys A-2 and A-5 are held inbreaker B interlock and keys A-3 and A-5 are held in breaker Cinterlock.To transfer the load from line No. 1 to line No. 2 or lineNo. 3 through tie bus, proceed as follows:
1. Open breaker A.
2. Turn key A-1 in L-O interlock on breaker A to lock thebreaker open. Keys A-1 and A-5 are now free.
3. Insert key A-1 in L-O interlock on breaker D and turn tounlock. Key A-1 is now held.
4. Close breaker D.5. Insert key A-5 in L-O interlock on either breaker E or F and
turn to unlock. Key A-5 is now held.6. Close breaker E or F (whichever is selected).
Reverse the sequence to restore load to line No. 1.
To transfer the load from lines No. 1 and No. 2 to line No. 3through tie bus, proceed as follows:
1. Close breaker D as per steps 1 to 4 above.2. Open breaker B.3. Turn key A-2 in L-O interlock on breaker B to lock the
breaker open. Keys A-2 and A-5 are now free.4. Insert key A-2 in L-O interlock on breaker E and turn to
unlock. Key A-2 is now held.5. Close breaker E.6. Insert one of the A-5 keys from either breaker A or B in
L-O interlock on breaker F and turn to unlock. Key A-5 isnow held.
7. Close breaker F.Reverse the sequence to restore load to lines No. 1 and No. 2.
Method 8.Function: To prevent the paralleling of three power sourcesthrough a common tie bus not normally in service.
To permit the feeding of any load bus from a second powersource through the tie bus only when authorized by supervisor.
To permit only one power source to supply all three load busesthrough the tie bus only when authorized by supervisor.
Typical Key Interlock Schemes
L-O
A 1
A 5
L-O
A-5
A-1
AE
E
D
Line 1
Load Bus
Tie Bus
L-O
A 2
A 5
L-O
A-5
A-2
BE
E
E
Line 2
L-O
A 3
A 5
L-O
A-5
A-3
CE
E
F
Line 3
24
Typical Key Interlock Schemes
Breakers A, B, and C are normally closed. Breakers D, E and Fare normally open. Under normal conditions Key A-1 is held inbreaker A interlock, Key A-2 is held in breaker B interlock, andKey A-3 is held in breaker C interlock. Key A-5 is retained bythe supervisor.To transfer the load from line No. 1 to line No. 2 or lines No. 3through tie bus, proceed as follows:
1. Open breaker A.2. Turn key A-1 in L-O interlock on breaker A to lock the
breaker open. Key A-1 is now free.3. Insert key A-1 in L-O interlock on breaker D and turn to
unlock. Key A-1 is now held.4. Close breaker D.5. Insert supervisor’s key A-5 (only one A-5 is available) in
L-O interlock on either breaker E or F and turn to unlock.Key A-5 is now held.
6. Close breaker E or F (whichever is selected).Reverse sequence to restore the load to line No. 1.
To transfer the load from lines No. 1 and No. 2 to line No. 3through tie bus, proceed as follows:
1. Close breaker D as per steps 1 to 4 above.2. Open breaker B.3. Turn key A-2 in L-O interlock on breaker B to lock the
breaker open. Key A-2 is now free.4. Insert key A-2 in L-O interlock on breaker E and turn to
unlock. Key A-2 is now held.5. Close breaker E.6. Insert supervisor’s key A-5 in L-O interlock on breaker F
and turn key to unlock. Key A-5 is now held.7. Close breaker F.
Reverse the sequence to restore the load to lines No. 1 and No. 2.
Method 9.
Function: To prevent the paralleling of incoming primarysources, lines 1 and 2, through primary tie bus disconnect.
To prevent the operation (open or closed) of disconnects underload.
It permits one power source to supply both loads through tie bus.
Under normal conditions, breakers A and B are closed, discon-nects C and D are locked closed, and tie bus disconnect T islocked open. Keys A-1 are held in L-O interlock on breaker A andL-C interlock on tie bus disconnect T. Keys A-2 are held in L-Ointerlock on disconnects C and D. Keys A-3 are held in L-O inter-lock on breaker B and L-C interlock on tie bus disconnect T. KeysA-4 (free keys) are shown removably held in the L-C interlocks ondisconnects C and D.
To transfer load No. 1 from line 1 to line 2 through bus tie dis-connect T, proceed as follows:
1. Open breaker A.2. Turn key A-1 in L-O interlock on breaker A to lock open.
Key A-1 is now free.3. Insert key A-1 in L-C interlock on disconnect C and turn
to unlock. Keys A-1 and A-4 are now held.4. Open disconnect C.5. Turn key A-2 in L-O interlock on disconnect C to lock
open. Key A-2 is now free.6. Insert keys A-2 and free key A-4 (from L-C interlock on
disconnect D) in L-O interlock on bus tie disconnect Tand turn to unlock. Keys A-2 and A-4 are now held.
7. Close bus tie disconnect T.8. Turn key A-3 in L-C interlock on disconnect T to lock
closed. Keys A-1 and A-3 are now free.9. Insert key A-1 in L-O interlock on breaker A and turn to
unlock. Key A-1 is now held.10. Close breaker A.
L-O
A-5
A-1
A
D
Line 1
Load Bus
Tie Bus
L-O
A-5
A-2
B
E
Line 2
L-O
A-5
A-3
C
F
Line 3
L-O
A 1
L-O
A 2
A 5
L-O
A 3
SupervisoryKey
L-C
A-1
A 4
L-C
A-3
A 4
L-C
A 1
A 3
A 2 E
E
E
E
L-O
A-2
A-4E
E
E
E
Line 1
Load 1
L-O
A 2
L-O
A 1
L-O
A 3
L-O
C D
A
Line 2
Load 2
B
T
25
Typical Key Interlock Schemes
Reverse the sequence to restore load No. 1 to line 1.To transfer load No. 2 from line 2 to line 1 through the bus tiedisconnect T, proceed in a similar manner.
Method 10.Function: To prevent the paralleling of incoming primarysources, lines 1 and 2, through the primary tie bus disconnector the secondary tie bus breaker.
To prevent the operation (open or closed) of the disconnectsunder load.
It permits one power source to supply both loads through eitherthe primary or secondary tie bus.
Under normal conditions, breakers A and B are closed, breaker Cis locked open, disconnects D and E are locked closed, and tie dis-connect T is locked open. Keys A-1 are held in the L-O interlockon breaker A and the L-C interlock on primary tie bus disconnectT. Keys A-2 are held in the L-O interlocks on disconnects D and E.Keys A-3 are held in the L-O interlock on breaker B, and L-C inter-lock on primary tie bus disconnect T. Keys A-4 (free keys) areshown removably held in the L-C interlocks on disconnects D andE. Keys A-5 are held in the L-O interlocks on breakers A and B.
To transfer load No. 1 from line 1 to line 2 through primary bustie disconnect T:
1. Open breaker A.2. Turn key A-1 in the L-O interlock on breaker A to lock
open. Keys A-1 and A-5 are now free.3. Insert key A-1 and “free key A-4” in the L-O interlock on
disconnect D and turn to unlock. Keys A-1 and A-4 arenow held.
4. Open disconnect D.5. Turn key A-2 in L-O interlock on disconnect D to lock
open. Key A-2 is now free.
6. Insert key A-2 and free key A-4 (from the L-C interlockon disconnect E) in the L-O interlock on primary bus tiedisconnect T and turn to unlock. Keys A-2 and A-4 arenow held.
7. Close bus tie disconnect T.8. Turn key A-3 in the L-C interlock on bus tie disconnect T
to lock closed. Keys A-1 and A-3 are now removable.9. Insert Key A-1 in the L-O interlock on breaker A and turn
to unlock. Key A-1 is now held.10. Close breaker A.
Reverse this procedure to restore service to line 1.
Load No. 2 can be supplied from No. 1 through the primary bustie in a similar manner.
To transfer load No. 1 from line 1 to line 2 through secondary tiebreaker C:
1. Open breaker A.2. Turn key A-1 in the L-O interlock on breaker A to lock
open. Keys A-1 and A-5 are now removable.3. Insert key A-5 in the L-O interlock on tie breaker C and
turn to unlock. Key A-5 is now held.4. Cost tie breaker C.
Reverse this procedure to restore service on line 1.
Load No. 2 can be supplied from line No. 1 through the sec-ondary tie breaker C in a similar manner.
Method 11.
L-O
A
C
A 1
B 1
E
E
E
A 2
L-C
A-3
L-C
B-3B 2
L-O
L-O
A 2
LOC
A-4
L O
T-1
B 2
L-O
B-4
LOC
Line 1
F
T
K
Load 1
B
D
G
Line 2
H
L
Load 2
L C
T 1
A 3
A 1
A 4
E
EL-O
A-1
A-2
E
EL-C
B-1
B-2
T 1
B 3
E
EL-C
E
EL-O
E
EL-O
B 1
B 4
E
EL-O
A-5
L-O
L-O
L-C
A C B
L-O
L-C L-O
A 1
A 5
L-O
A 3
A 5
E
E
E
E
Load 1 Load 2
A 1
A 3 A-2
A-4E
E
E
E
A 4A 2
L-O
A 2
A-1
L-C
A 4
A-3
E
E
E
E
Line 1
ED
Line 2
T
26
Typical Key Interlock Schemes
Function: To prevent the paralleling of incoming primarysources, lines 1 and 2.
To prevent the operation (open or closed) of the disconnectsunder load. (Permits transformer primary disconnects (K & L) toopen and close the transformer magnetizing current.*)
Permits isolating breakers for servicing.
Permits one power source to supply both loads through tie bus.
Under normal conditions, breakers A, B, C, and D are closed, dis-connects E, F, G, H, K, and L are locked closed, and bus tie dis-connect T is locked open. Keys A-1 are held in the L-O interlockon breaker C, and the L-C interlock on bus tie disconnect T. KeysA-2 are held in the L-O interlocks on breaker A and disconnectE. Key A-3 is held in the L-O interlock on disconnect F. Key A-4is held in the L-O interlock on breaker C. Keys B-1 are held in theL-O interlock on breaker D, and the L-C interlock on bus tie dis-connect T. Keys B-2 are held in the L-O interlocks on breaker Band disconnect G. Key B-3 is held in the L-O interlock on dis-connect H. Key B-4 is held in the L-O interlock on breaker D. KeysT-1 are held in the L-O interlocks on disconnects F and H.
To transfer load No. 1 from line 1 to line 2 through bus tie dis-connect T:
1. Open breaker A.2. Turn key A-2 in the L-O interlock on breaker A to lock the
breaker open. Key A-2 is now free.3. Open breaker C.4. Turn key A-4 in the L-O interlock breaker C to lock the
breaker open. Keys A-1 and A-4 are now free.5. Insert key A-2 from the L-O interlock on breaker A and key
A-1 from the L-O interlock on breaker C, in the L-C inter-lock on disconnect F and turn to unlock. Keys A-1 and A-2 are now held.
6. Open disconnect F.
7. Turn key A-3 in the L-O interlock on disconnect F to lockopen. Keys A-3 and T-1 are now free.
8. Insert key T-1 in the L-O interlock on bus tie disconnectT and turn to unlock. Key T-1 is now held.
9. Close bus tie disconnect T.
10. Turn key B-1 in the L-C interlock on bus tie disconnectT to lock closed. Keys A-1 and B-1 are now free.
11. Insert key A-1 in the L-O interlock on breaker C and turnto unlock. Keys A-1 and A-4 are now held.
12. Close breaker C.Reverse the sequence to restore load No. 1 to line 1.
To transfer load No. 2 from line 2 to line 1, proceed in a similarmanner.
To isolate breaker A for servicing:1. Proceed from normal position with operations as in 1
through 7 above.
2. Insert key A-3 in the L-C interlock on disconnect E andturn to unlock. Key A-3 is now held.
3. Open disconnect E.4. Turn key A-2 in the L-O interlock on disconnect E to lock
open. Key A-3 is now free.5. Return key A-2 to breaker A and unlock for operation
during servicing.Reverse the sequence to restore service.
To isolate breaker B for servicing, proceed in a similar manner.
To isolate breaker C for servicing, proceed as follows:1. Open breaker C.2. Turn key A-4 in the L-O interlock on breaker C to lock
breaker open. Keys A-1 and A-4 are now free.3. Insert key A-4 in the L-O-C interlock on disconnect K and
turn to unlock. Key A-4 is now held.4. Open disconnect K.5. Turn key A-4 in the L-O-C interlock on disconnect K to
lock disconnect open. Key A-4 is now free.6. Return key A-4 to breaker C and unlock for operation
during servicing.Reverse the sequence to restore service.
To isolate breaker D for servicing, proceed in a similar manner.
*To prevent primary disconnects (K & L) from opening magne-tizing current only, additional interlocks should be provided fordisconnects K & L.
Method 12.Function: To prevent paralleling lines A and B — requires drop-ping load when shifting from one source to another.
To prevent closing both interrupter switch A and B at the sametime — (permits both interrupter switches to be opened at thesame time).
To prevent operation (open or closed) of either interrupterswitch when breaker is closed.
Permits the breaker to be serviced and operated while bothinterrupter switches are locked open.
A-1EE
A 2
LOC
A-1EE
A-2
LOCL-O
A 1
L-O
L-OA B
27
Typical Key Interlock Schemes
The Breaker and Interrupter A are shown in closed position.Interrupter B is shown in the open position. Key A-1 is held inbreaker interlock. Key A-2 is held in interrupter A interlock.
To service the breaker:
1. Open the breaker.2. Turn key A-1 in the L-O interlock on breaker to lock
breaker open. Key A-1 is now free.3. Insert key A-1 in the L-O-C interlock on interrupter A and
turn to unlock. Key A-1 is now held.4. Open interrupter A.5. Turn key A-1 in L-O-C interlock on interrupter A to lock
open. Key A-1 is now free.6. Return key A-1 to breaker interlock and unlock for oper-
ation of breaker during servicing.Reverse the sequence to restore service.
To transfer load from interrupter A to interrupter B.1. Proceed from normal positions with operations as in 1
through 4 above.2. Turn key A-1 in L-O-C interlock and key A-2 in L-O interlock
on interrupter A to lock open. Keys A-1 and A-2 are nowfree.
3. Insert key A-1 in L-O-C interlock and key A-2 in L-O inter-lock on interrupter B and turn to unlock. Keys A-1 and A-2 are now held.
4. Close interrupter B.5. Turn key A-1 in L-O-C interlock on interrupter B to lock
closed. Key A-1 is free and key A-2 is held.6. Insert key A-1 in L-O interlock on breaker and turn to
unlock. Key A-1 is now held.7. Close breaker.
Reverse the sequence to restore service through interrupter A.
Method 13.
Function: To prevent operation (closed, open or closed) of inter-rupter switch when breaker is closed.
Permits the breaker to be serviced and operated while the inter-rupter switch is locked open.
The Breaker and Interrupter are shown in closed position,connected to line B. Key A-1 is held in breaker interlock.
To service breaker:1. Open breaker.2. Turn key A-1 in L-O interlock on breaker to lock breaker
open. Key A-1 is now free.3. Insert key A-1 in L-C-O-C interlock on interrupter and turn
to unlock. Key A-1 is now held.4. Open interrupter.5. Turn key A-1 in L-C-O-C interlock on interrupter lock
open. Key A-1 is now free.6. Return key A-1 to breaker interlock and unlock for oper-
ation of breaker during servicing.Reverse the sequence to restore service through either line Aor line B.
To transfer interrupter from line B to line A:1. Proceed from normal position with operations as in steps
1, 2, and 3 above.2. Open interrupter switch from line B and connect to line A.3. Turn key A-1 in L-C-O-C interlock on interrupter to lock
closed. Key A-1 is now free.4. Insert key A-1 in L-O interlock on breaker and turn to
unlock. Key A-1 is now held.5. Close breaker.
Reverse the sequence to restore service through either line Aor line B.
EA 1
L-O
EA-1
LCOC
A B
Method 14.
Function: To prevent operation (closed, open or closed) of theinterrupter switch when breaker is closed.
To prevent opening the fuse compartment door when the inter-rupter switch A is closed.
To prevent closing the interrupter switch until fuse compart-ment door is locked closed.
Permits the breaker to be serviced and operated while the inter-rupter switch is locked open.
The breaker, fuse compartment door, and interrupter are shownin closed position, connected to line B. Key A-1 is held inbreaker interlock and key A-2 is held in interrupter interlock.
To service breaker:1. Open breaker.2. Turn key A-1 in L-O interlock on breaker to lock breaker
open. Key A-1 is now free.3. Insert key A-1 in L-C-O-C interlock on interrupter and turn
to unlock. Key A-1 is now held.4. Open interrupter.5. Turn key A-1 in L-C-O-C interlock on interrupter to open.
Key A-1 is now free.6. Return key A-1 to breaker interlock and unlock for oper-
ation of breaker during servicing.
Reverse the sequence to restore service through either line Aor line B.To open fuse compartment door:
1. Proceed from normal position with operations as in steps1 through 4 above.
2. Turn key A-2 in L-O interlock on interrupter to lock open.Key A-2 is now free.
3. Insert key A-2 in L-C interlock on fuse compartment doorand turn to unlock. Key A-2 is now held.
4. Open fuse compartment door.
Reverse the sequence to restore service.
To transfer interrupter from line B to line A:
1. Proceed from normal position with operations as in steps1, 2, and 3 above.
2. Open interrupter switch from line B and connect to line A.3. Turn key A-1 in L-C-O-C interlock on interrupter to lock
closed. Key A-1 is now free.4. Insert key A-1 in L-O interlock on breaker and turn to
unlock. Key A-1 is now held.5. Close breaker.
Reverse the sequence to restore service through line B.
28
Typical Key Interlock Schemes
EA 1
L-O
EA 2
L-O
EA-1
LCOC
A B
A-2
L-C
E
29
Layout Information – Primary Section
HVL/VISI-VAC Switchgear - Power Dry Transformer Primary Connection
5 and 15 kV
Approx. Weights: 1200lbs./545kg indoor 1400lbs./636kg outdoor
Notes :1. Transformer dimensions vary depending upon kVA, BIL and temperature rise ratings. See TRANSFORMER section for complete table of transformer dimensions.
2. Extra 1.5" in height (91.5" vs 90") if 1.5" base channel is included in HVL or VISI-VAC.
3. Units are front-aligned (.5" difference in indoor units). Units are rear-aligned if transformer depth is 54" for indoor units, 60" for outdoor units.
34.00864
2.0051
2.0051
2.0051
Top View
Front View
6.00152
6.00152 6.00
152
1.7544
94.002388Min.
(See Note 1)
38.00965
19.00483
97.502477
64.001626
63.501613Min.
(See Note 1)
28.00711
27.75705
OutdoorIndoor
CL
34.00864
2.0051
Floor Plan
4.00102
6.00152 6.00
15260.001524
60.001524Min.
(See Note 1)
26.00660
26.00660
CL
Front View
94.002388Min.
(See Note 1)
38.00965
90.002286
or91.502324
(See Note 2)
34.00864
2.0051
Floor Plan
4.00102
6.00152 6.00
15254.501384
54.001372Min.
(See Note 1)
10.63270
10.13660
CL
34.00864
2.0051
Top View
4.00102
6.00152 6.00
152 2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
54.501384
54.001372Min.
(See Note 1)
10.63270
10.13660
CL
DANGERHIGH
VOLTAGE
(See Note 3)
(See Note 3)
(See Note 3)(See Note 3)
30
Layout Information – Primary Section
HVL/VISI-VAC® Switchgear — POWER-CAST® and UNI-CAST™ TransformersPrimary Connection
5 and 15 kV
Approx. Weights: 1200lbs./545kg indoor 1400lbs./636kg outdoor
Notes :1. Transformer dimensions vary depending upon kVA, BIL and temperature rise ratings. See TRANSFORMER section for a table of transformer dimensions. If connection is required to be a hard-
bus connection, the minimum depths shown here will increase, and the factory must be consulted for the transformer dimensions.
2. Extra 1.5" in height (91.5" vs 90") if 1.5" base channel is included in HVL or VISI-VAC.
3. Indoor units are front-aligned (.5 difference at front), outdoor units are not front-aligned.
54.001372Min.
(See Note 1)
34.00864
2.0051
2.0051
2.0051
Top View
Front View
6.00152
6.00152 6.00
152
38.00965
19.00483
97.502477
64.001626
54.001372Min.
(See Note 1)
28.00711
19.75502
OutdoorIndoor
CL
34.00864
2.0051
Floor Plan
4.00102
6.00152 6.00
152
60.001524
26.00660
19.75502
6.25159
CL
Front View
38.00965
90.002286
or91.502324
(See Note 2)
34.00864
2.0051
Floor Plan
4.00102
6.00152 6.00
15254.501384
10.63270
10.13660
CL
34.00864
2.0051
Top View
4.00102
6.00152 6.00
15254.501384
54.001372Min.
(See Note 1)
10.63270
10.13660
CL
DANGERHIGH
VOLTAGE
94.002388Min.
(See Note 1)
94.002388Min.
(See Note 1)
(See Note 3)
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
(See Note 3)
(See Note 3)
54.001372Min.
(See Note 1)
(See Note 3)
31
HVL/VISI-VAC® Switchgear — Liquid-filled Transformer Primary Connection to 3750 kVA (see note 5)
5 and 15 kV
Approx. Weights: 1200lbs./545kg indoor 1400lbs./636kg outdoor
Notes :1. Liquid-filled transformer standard enclosure dimensions are given in the TRANSFORMER section. They are applicable only for mineral-oil units under certain conditions (see TRANSFORMER
section for details).
2. Extra 1.5" in height (91.5" vs 90") if 1.5" base channel is included in HVL or VISI/VAC.
3. Units are not necessarily front or rear aligned.
4. Transition section height is 65" if transformer is up to 2500 kVA, 85" if transformer is over 2500 kVA.
5. If transformer is over 3750 kVA, variations to the dimensions shown here will be necessary.
Layout Information – Primary Section
H(See Note 1)
19.00483
65.00 or 85.00 1651 2159Transition Section Height(See Note 4)
38.00965
D1D1
D2D2
38.00965
Indoor
Front View
38.00965
90.002286
or91.502324
(See Note 2)
34.00864
2.0051
Floor Plan
4.00102
6.00152 6.00
15254.501384
CL
34.00864
2.0051
Top View
4.00102
6.00152 6.00
15254.501384
20.50521
20.50521
CL
DANGERHIGH
VOLTAGE
34.00864
2.0051
2.0051
2.0051
Top View
Front View
6.00152
6.00152 6.00
152
H(See Note 1)
38.00965
19.00483
97.502477
64.001626
28.00711
38.00965
Outdoor
CL
34.00864
2.0051
Floor Plan
4.00102
6.00152 6.00
15260.001524
26.00660
CL
65.00 or 85.00 1651 2159Transition Section Height(See Note 4)
38.00965
2.00 x 4.00 51 102Control Conduit Area
D1
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
(See Notes 1, 3, 5)(See Notes 1, 3, 5)
(See Notes 1, 3, 5)
D1
(See Notes 1, 3, 5)
32
Layout Information – Primary Section
Metal-Clad Switchgear — POWER-DRY™, POWER-CAST® and UNI-CAST™ Transformers PrimaryConnection
Approx. Weights (less breakers): 2200lbs./999kg indoor 2700lbs./1226kg outdoor1200 A breaker: 360lbs./163kg 2000 A breaker: 410lbs./186kg 3000 A breaker: 480lbs./218kg
Notes :1. Transformer dimensions vary depending upon kVA, BIL and temperature rise ratings. See TRANSFORMER section for a complete table of transformer dimensions.
2. Units will be rear-aligned when transformers have the depths shown. For transformers with larger depths, transformer will protrude in rear.
20.005088.00
203
Floor Plan
20.00508
96.932462
51.301303
1.7043
.103
8.00203
5.90150
6.30160
54.001372
(Power-Cast, Uni-Cast)or
60.001524Min.
(Power-Dry)(See Note 1)
41.181046
(Fixed)(Power-Cast, Uni-Cast)
or35.18
894(Fixed)
(Power-Dry)
CL
ControlConduitArea
109.102771
51.301303
54.001372
(Power-Cast, Uni-Cast)or
60.001524Min.
(Power-Dry)(See Note 1)
49.181249
(Fixed)(Power-Cast, Uni-Cast)
or43.18
1097(Fixed)
(Power-Dry)
CL
Top View
Front View
36.00914
22.00559
3.0076
108.502756
Outdoor
94.002388Min.
(See Note 1)
Indoor
18.00457
9.00229
Top View
Front View
3.5089
9.00229
9.00229
1.0025
8.00203
92.002337
(With Door)
95.002413
36.00914
22.00559
3.0076
54.001372Min.
(See Note 1)
37.00940
(Fixed)
94.002388Min.
(See Note 1)
2.0051
1.7551
8.00203
10.12257
CL
ControlConduitArea
18.00457
9.00229
Floor Plan
3.5089
9.00229
9.00229
1.0025
91.002311
54.001372Min.
(See Note 1)
47.1211972.00
51
.205
8.00203
2.5064
3.5089
1.0025
37.00940
(Fixed)
CL
ControlConduitArea
(See Note 2)
(See Note 2) (See Note 2)
(See Note 2)
Roof Overhang
5 kV and 15 kV
33
Layout Information – Primary Section
Metal-Clad Switchgear — Liquid-Filled Transformer Primary Connection to 3750 kVA (see note 3)
Approx. Weights (less breakers): 2200lbs./999kg indoor 2700lbs./1226kg outdoor1200 A breaker: 360lbs./163kg 2000 A breaker: 410lbs./186kg 3000 A breaker: 480lbs./218kgNotes:
1. Liquid-filled transformer standard enclosure dimensions are given in the TRANSFORMER section. They are applicable only for mineral-oil units under certain conditions (see TRANSFORMERsection for details).
2. Flange height is 65" if transformer is up to 2500 kVA, 85" if transformer is over 2500 kVA.3. If transformer is over 3750 kVA, variations to the dimensions shown here will be necessary.4. Units are not necessarily front or rear aligned. Transformer radiators may extend behind switchgear.
20.005088.00
203
Floor Plan
6.30160
20.00508
96.932462
49.181249
45.001143
1.7043
.103
8.00203
5.90150
CL
109.102771
49.181249
8.00203
CL
Top View
Front View
36.00914
22.00559
108.502756
Outdoor
H(See Note 1)
22.00559
3.0076
D1
D2
D1(See Note 1)
D1(See Note 1)
38.00965
38.00965
38.00965
38.00965
Front View
36.00914
95.002413
Indoor
18.00457
9.00229
Top View
3.5089
9.00229
9.00229
1.0025
92.002337
(With Door)
45.0011432.00
51
1.7544
8.00203
1.0025
3.5089
CL
18.00457
9.00229
Floor Plan
3.5089
9.00229
9.00229
1.0025
91.002311
2.0051
.205
8.00203
2.5064
CL
D1
D2
65.00 or 85.00 1651 2159 Flange Height (See Note 2)
H(See Note 1)
3.0076
65.00 or 85.00 1651 2159 Flange Height (See Note 2)
(See Note 1)
(See Note 1)
Radiators MayExtend Behind
Switchgear.(See Note 4)
Radiators MayExtend Behind
Switchgear.(See Note 4)
Roof Overhang
5 kV and 15 kV
34
Layout Information – Primary Section
HVL Switchgear — POWER-DRY™ and POWER-CAST® Transformers Primary Connection
Approx. Weights: 2000lbs./908kg indoor 2500lbs./1135kg outdoor
Notes :1. Please consult the manufacturing location for 25 kV transformer enclosure dimensions.
2. Units are neither front nor rear aligned.
40.001016
5.00127
Top View
Front View
6.00152
6.00152 6.00
152
94.002388Min.
(See Note 1)
48.001219
24.00610
127.003226
90.002286
66.001676Min.
(See Note 1)32.75
832
8.00203
40.751035
Outdoor
CL
40.001016
4.00102
Floor Plan
4.00102
6.00152 6.00
15286.002184
38.75984
32.75832
CL
Indoor
Front View
94.002388Min.
(See Note 1)
48.001219
24.00610
120.003048
44.001118
2.0051
Floor Plan
4.00102
6.00152 6.00
15280.502045
66.001676Min.
(See Note 1)
66.001676Min.
(See Note 1)32.75
83233.25
845
CL
44.001118
2.0051
Top View
4.00102
6.00152 6.00
152 2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area80.50
2048
66.001676Min.
(See Note 1)
33.25845
32.75832
CL
DANGERHIGH
VOLTAGE
(See Note 2)
(See Note 2)
(See Note 2)
6.00152
(See Note 2)
25 kV
35
Layout Information – Primary Section
HVL Switchgear — Liquid-filled Transformer Primary Connection to 3750 kVA (see note 4)
Approx. Weights: 2200lbs./908kg indoor 2700lbs./1135kg outdoorNotes :1. Liquid-filled transformer standard enclosure dimensions are given in the TRANSFORMER section. They are applicable only for mineral-oil units under certain conditions (see TRANSFORMER
section for details).
2. Transition section height is 65" for transformers up to 2500 kVA, 85" for transformers over 2500 kVA.
3. Units are not necessarily front or rear-aligned.
4. If transformer is over 3750 kVA, slight variations to the dimensions shown here will be necessary.
40.001016
(See Note 2)
44.001118
44.001118
(See Note 2)
40.001016
(See Note 2)
2.0051
5.00127
2.0051
Top View
Front View
6.00152
6.00152 6.00
152
H(See Note 1)
127.003226
90.002286
42.001067
Outdoor
CL
Floor Plan
4.00102
4.00102
6.00152 6.00
15286.002184
39.501033
CL
59.001499
H(See Note 1)
65.00 or 85.00 1651 2159Transition Section Height(See Note 2)
65.00 or 85.00 1651 2159Transition Section Height(See Note 2)
59.001499
D1 D1
Indoor
Front View
48.001219
24.00610
48.001219
24.00610
120.003048
2.0051
Floor Plan
4.00102
6.00152 6.00
152
34.00864
CL
2.0051
Top View(See Note 3)
4.00102
6.00152 6.00
15280.502045
80.502045
34.00864
59.001499
CL
DANGERHIGH
VOLTAGE
D1
D2
(See Notes 1, 3, 4)
D1
D2
(See Notes 1, 3, 4)
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
(See Notes 1, 3, 4) (See Notes 1, 3, 4)
25 kV
36
Layout Information – Primary Section
HVL Switchgear — POWER-CAST® Transformer Primary Connection
34 kV
Approx. Weights: 2200lbs./999kg indoor 2700lbs./1226kg outdoor
Notes :1. Please contact the manufacturing location for 34 kV POWER-CAST transformer enclosure dimensions.
2. CT = cabinet depth ÷ 2. Units are not necessarily front or rear-aligned.
Indoor
56.001422
2.0051
Top View
4.00102
6.00152 6.00
152
80.502045
38.75984
CL CL
Front View
60.001524
24.00610
120.003048
2.0051
56.001422
2.0051
Floor Plan
4.00102
6.00152 6.00
152
80.502045
39.501003
CL
DANGERHIGH
VOLTAGE
DANGERHIGH
VOLTAGE
24.00610
CL
52.001321
5.00127
Top View
6.00152
6.00152 6.00
152
90.002286
44.751137
Outdoor
60.001524
127.003226
52.001321
4.00102
Floor Plan
4.00102
6.00152 6.00
152
86.002184
45.001143
CT(See Note 2)
CT(See Note 2)
62.001575Min.
(See Note 1)
112.00 2845Min.
(See Note 1)
62.001575Min.
(See Note 1)
CT(See Note 2)
2.0051
112.002845Min.
(See Note 1)
62.001575Min.
(See Note 1)
CT(See Note 2)
62.001575Min.
(See Note 1)
Front View
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
37
Layout Information – Primary Section
HVL Switchgear — Liquid-Filled Transformer Primary Connection to 3750 kVA (see note 4)
Approx. Weights: 2200lbs./999kg indoor 2700lbs./1226kg outdoor
Notes:1. Liquid-filled transformer standard enclosure dimensions are given in the TRANSFORMER section. They are applicable only for mineral-oil units under certain conditions (see TRANSFORMER
section for details).
2. Transition section height is 65" if transformer is up to 2500 kVA, 85" if transformer is over 2500 kVA.
3. Units are not necessarily front or rear-aligned.
4. If transformer is over 3750 kVA, variations to the dimensions shown here will be necessary.
Indoor
56.001422
2.0051
Top View
4.00102
6.00152 6.00
152
80.502045
(See Notes 1, 3, 4)
(See Notes 1, 3, 4) (See Notes 1, 3, 4)
(See Notes 1, 3, 4)
37.50953
D1
D2
D1
D2
CL CL
Front View Front View
H(See Note 1)
60.001524
24.00610
120.003048
56.001422
59.001499
2.0051
Floor Plan
4.00102
6.00152 6.00
152
59.001499
59.001499
80.502045
D1
39.501003
CL
DANGERHIGH
VOLTAGE
DANGERHIGH
VOLTAGE
H(See Note 1)
24.00610
D1
59.001499
CL
52.001321
5.00127
Top View
6.00152
6.00152 6.00
152
90.002286
49.501257
Outdoor
60.001524
127.003226
52.001321
4.00102
Floor Plan
4.00102
6.00152 6.00
152
86.002184
41.501054
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
2.00 x 4.00 51 102Control Conduit Area
65.00 or 85.00 1651 2159Transition Section Height (See Note 2)
65.00 or 85.00 1651 2159Transition Section Height (See Note 2)
34 kV
38
Layout Information – Primary Section
QED Switchboard — POWER-DRY™ Transformer Primary Connection
600 V
Weight will vary according to switchboard components.
Notes :1. Transformer dimensions vary depending upon voltage class, kVA size and BIL rating. See TRANSFORMER section for a complete table of transformer dimensions.
2. Please consult QED layout manual for conduit area dimensions and section width.
Indoor
Front View
94.002388Min.
(See Note 1)
91.502324
Floor Plan
54.001372
54.001372Min.
(See Note 1)
30.00762
30.00762
CL
Top View
54.001372
30.00762
30.00762
54.001372Min.
(See Note 1)CL
W(See Note 2)
39
Layout Information – Transformer Section
5 kV Class - 30 kV BIL
80°C Temperature Rise 115°C/150°C Temperature Rise
kVA Height Width Weight Height Width Weight (lbs.)(H) (W) (lbs.) (H) (W) (115°C/150°C)
225 94.0 56.0 2300 94.0 56.0 2300/2100
300 94.0 56.0 3300 94.0 56.0 2500/2300
500 94.0 56.0 4200 94.0 56.0 3500/3300
750 94.0 72.0 5500 94.0 56.0 4400/4200
1000 94.0 84.0 6400 94.0 72.0 5800/5500
1500 94.0 84.0 8300 94.0 84.0 6700/6400
2000 94.0 84.0 10500 94.0 84.0 8600/8300
2500 102.0 108.0 13000 94.0 96.0 10800/10500
3000 112.0 108.0 18000 102.0 108.0 13500/13000
3750 112.0 108.0 22000 112.0 108.0 18500/18000
15 kV Class - 45 and 60 kV BIL
80°C Temperature Rise 115°C/150°C Temperature Rise
kVA Height Width Weight Height Width Weight (lbs.)(H) (W) (lbs.) (H) (W) (115°C/150°C)
225 94.0 56.0 3400 94.0 56.0 3400/3200
300 94.0 56.0 3900 94.0 56.0 3600/3400
500 94.0 72.0 5100 94.0 56.0 4100/3900
750 94.0 72.0 5800 94.0 72.0 5400/5200
1000 94.0 84.0 7300 94.0 72.0 6100/5800
1500 94.0 84.0 9000 94.0 84.0 7600/7300
2000 94.0 96.0 10800 94.0 84.0 9300/9000
2500 102.0 108.0 13500 94.0 96.0 11300/10800
3000 112.0 108.0 18500 102.0 108.0 14000/13500
3750 112.0 108.0 22500 112.0 108.0 19000/18500
15 kV Class - 95 kV BIL
80°C Temperature Rise 115°C/150°C Temperature Rise
kVA Height) Width Weight Height Width Weight (lbs.)(H) (W) (lbs.) (H) (W) (115°C/150°C)
225 94.0 56.0 3800 94.0 56.0 3700/3500
300 94.0 56.0 4600 94.0 56.0 4000/3800
500 94.0 72.0 6000 94.0 72.0 5000/4800
750 94.0 84.0 7400 94.0 84.0 6400/6200
1000 94.0 84.0 8400 94.0 84.0 7700/7400
1500 94.0 96.0 10600 94.0 96.0 9100/8800
2000 102.0 108.0 13100 94.0 96.0 10900/10600
2500 102.0 108.0 14600 102.0 108.0 13600/13100
3000 120.0 120.0 22100 102.0 108.0 15000/14600
3750 120.0 120.0 27100 120.0 120.0 22600/22100
Notes:
These dimensions are for cable-connected primaries only. For primaries above 530A, theprimary must be bus-connected. Please contact the factory for these cases.
For units in the 5 kV class with 45 or 60 kV BIL, use dimensions shown in the 15 kV class.
Units are 54" deep except for units over 108" wide x 102" high, which will be 66" deep.
It is recommended that ventilation openings have 12" min. clearance from any obstacle tosatisfy NEC 450-9.
All weights are approximate; for copper windings add 15% to weight.
Units close-coupled to 4001-5000 A switchgear are 60" deep minimum. Contact the factoryfor dimensions of units close-coupled to secondary metal-clad switchgear or when ULListing is required.
Indoor POWER-DRY™ Transformers
600 V, 5 kV and 15 kV (contact factory for 25 kV units)
H
W
600 V Class – 10-30 kV BIL
80°C Temperature Rise 115°C/150°C Temperature Rise
kVA Height Width Weight Height Width Weight (lbs.)(H) (W) (lbs.) (H) (W) (115°C/150°C)
225 94.0 56.0 2300 94.0 56.0 2300/2100
300 94.0 56.0 3300 94.0 56.0 2500/2300
500 94.0 56.0 4200 94.0 56.0 3500/3300
750 94.0 72.0 5500 94.0 56.0 4400/4200
1000 94.0 84.0 6400 94.0 72.0 5800/5500
1500 94.0 84.0 8300 94.0 84.0 6700/6400
2000 94.0 84.0 10500 94.0 84.0 8600/8300
2500 102.0 108.0 13000 94.0 96.0 10800/10500
3000 102.0 108.0 17100 102.0 108.0 13500/13000
3750 112.0 108.0 22000 102.0 108.0 17600/17100
40
Layout Information – Transformer Section
5 kV Class - 30kV BIL
80°C Temperature Rise 115°C/150°C Temperature Rise
kVA Height Width Weight Height Width Weight (lbs.)(H) (W) (lbs.) (H) (W) (115°C/150°C)
225 94.0 56.0 3000 94.0 56.0 3000/2800
300 94.0 56.0 4000 94.0 56.0 3200/3000
500 94.0 72.0 5000 94.0 56.0 4200/4000
750 94.0 84.0 6300 94.0 72.0 5200/5000
1000 94.0 96.0 7300 94.0 84.0 6600/6300
1500 102.0 108.0 9500 94.0 96.0 7600/7300
2000 108.0 116.0 11900 102.0 108.0 9800/9500
2500 108.0 116.0 13000 108.0 116.0 12300/11800
3000 108.0 116.0 16000 108.0 116.0 14000/13500
15 kV Class - 45 and 60 kV BIL
80°C Temperature Rise 115°C/150°C Temperature Rise
kVA Height Width Weight Height Width Weight (lbs.)(H) (W) (lbs.) (H) (W) (115°C/150°C)
225 94.0 56.0 4100 94.0 56.0 4100/3900
300 94.0 56.0 4600 94.0 56.0 4300/4100
500 94.0 72.0 5800 94.0 56.0 4800/4600
750 94.0 84.0 6600 94.0 72.0 6100/5900
1000 94.0 96.0 8200 94.0 84.0 6800/6600
1500 102.0 108.0 10200 94.0 96.0 8500/8200
2000 108.0 116.0 12100 102.0 108.0 10500/10200
2500 108.0 116.0 14500 108.0 116.0 12600/12100
3000 108.0 116.0 17000 108.0 116.0 15000/14500
15 kV Class - 95 kV BIL
80°C Temperature Rise 115°C/150°C Temperature Rise
kVA Height) Width Weight Height Width Weight (lbs.)(H) (W) (lbs.) (H) (W) (115°C/150°C)
225 94.0 56.0 4500 94.0 56.0 4400/4200
300 94.0 56.0 5300 94.0 56.0 4700/4500
500 94.0 72.0 6700 94.0 72.0 5600/5400
750 94.0 84.0 8100 94.0 72.0 7000/6800
1000 94.0 96.0 9300 94.0 84.0 8400/8100
1500 102.0 108.0 11700 94.0 96.0 9900/9600
2000 108.0 116.0 14000 102.0 108.0 12000/11700
2500 108.0 116.0 15500 108.0 116.0 14500/14000
3000 108.0 116.0 18000 108.0 116.0 16000/15500
Notes:
These dimensions are for cable-connected primaries only. For primaries above 530A, theprimary must be bus-connected. Please contact the factory for these cases.
For units in the 5 kV class with 45 or 60 kV BIL, use dimensions shown in the 15 kV class.
Units are 60" deep except for units over 108" wide x 102" high, which will be 66" deep.
It is recommended that ventilation openings have 12" min. clearance from any obstacle tosatisfy NEC 450-9.
All weights are approximate. Add 15% to weight for copper windings. Contact the factory forunits close-coupled to HVL or metal-clad secondary swtichgear for when UL Listing isrequired.
Outdoor POWER-DRY Transformers
5 and 15 kV (for 25 kV units consult factory)
W
H
41
Layout Information – Transformer Section
POWER-DRY™ TransformerFront and Rear Access Air Terminal Chamber
Weight will vary according to switchboard components.
Note:1. Transformer dimensions vary depending upon voltage class, kVA size and BIL rating. See TRANSFORMER section for complete table of transformer dimensions.
Front View Front View
30.00762
94.002388
30.00762
24.00610
3.0076
6.00152
94.00 2388
(See Note 1)
94.00 2288Min.
(See Note 1)
60.001524Min.
(See Note 1)
60.001524Min.
(See Note 1)
94.002388
54.001372Min.
(See Note 1)
60.00 1524
60.001542
48.00 1219
6.00152
6.00152
Indoor
Outdoor
Top View
54.001372Min.
(See Note 1)
Floor Plan
Top View
42.001067
6.00152
54.001372
24.00610
3.0076
6.00152
Floor Plan
42.001067
6.00152
54.001372
42
Layout Information – Transformer Section
POWER-DRY™ TransformerEnd Access Air Terminal Chamber
Weight will vary according to switchboard components.
Note:1. Transformer dimensions vary depending upon voltage class, kVA size and BIL rating. See TRANSFORMER section for a complete table of transformer dimensions.
Front View
Floor Plan
20.00508
94.002388
Front View
20.00508
16.00406
2.0051
42.001067
6.00152
54.001372
94.00 2388Min.
(See Note 1)
94.002288Min.
(See Note 1)
60.001524Min.
(See Note 1)
94.002388
16.00406
2.0051
42.001067
6.00152
54.001372
6.00152
14.00356
3.0076
54.001372Min.
(See Note 1)
54.001372Min.
(See Note 1)
60.001524
60.001542Min.
(See Note 1)
60.001542
48.00 1219
6.00152
Indoor
Outdoor
Top View
Top View
Floor Plan
Indoor UNI-CAST™ Transformers5 and 15 kV primary (Cable-Connected only)600 V secondary
kVA Height (H) Width (W) Depth (D) Weight
500 94.00 72.00 54.00 4000
750 94.00 78.00 54.00 5500
1000 94.00 84.00 54.00 6000
1500 94.00 90.00 54.00 8000
2000 94.00 96.00 54.00 10000
2500 94.00 102.00 54.00 12000
3000 100.00 108.00 60.00 14000
Please consult the factory for dimensions of transformersdeviating from the following characteristics:
3 Phase, 60 Hz
High Voltage: 4160, 12470, 13200 and 13800 V, 95 kV BIL max.
Low Voltage: 480Y/277, 480 Delta, 208Y/120, 10 kV BIL max.208Y/120 not available above 1000 kVADelta-Delta, Wye-Delta and Delta-Wye connections only
Taps: ±2 at 2.5% above and below normal
Temp. Rise: 100°C over 30°C ambient
Impedance: 5.75%
Non-Loss Evaluated Designs
Noise Levels: Per NEMA TR1
Aluminum Windings and Terminations
All terminations tin-plated
Overload capacity: 33%Notes:
Primaries rated above 530 A must be bus-connected; please contact the factory for thesecases.
All weights are approximate.
It is recommended that ventilation openings have 12" min. clearance from any obstacle tosatisfy NEC 450-9.
Coordinated with HVL, VISI-VAC and METAL-CLAD primary and QED and PZ III secondary
43
Layout Information – Transformer Section
H
W
D
44
Layout Information – Transformer Section
Outdoor UNI-CAST™ Transformers5 and 15 kV primary (Cable-Connected only)600 V secondary
kVA Height (H) Width (W) Depth (D) Weight
500 94.00 72.00 54.00 4350
750 94.00 78.00 54.00 5850
1000 94.00 84.00 54.00 6350
1500 94.00 90.00 54.00 8350
2000 94.00 96.00 54.00 10350
2500 94.00 108.00 54.00 12500
3000 100.00 114.00 60.00 14500
Please consult the factory for dimensions of transformersdeviating from the following characteristics:
3 Phase, 60 Hz
High Voltage: 4160, 12470, 13200 and 13800 V, 95 kV BIL max.
Low Voltage: 480Y/277, 480 Delta, 208Y/120, 10 kV BIL max.208Y/120 not available above 1000 kVADelta-Delta, Wye-Delta and Delta-Wye connections only
Taps: ±2 at 2.5% above and below normal
Temp. Rise: 100°C over 30°C ambient
Impedance: 5.75%
Non-Loss Evaluated Designs
Noise Levels: Per NEMA TR1
Aluminum Windings and Terminations
All terminations tin-plated
Overload capacity: 33%Notes:
Primaries rated above 530 A must be bus-connected; please contact the factory for thesecases.
All weights are approximate.
It is recommended that ventilation openings have 12" min. clearance from any obstacle tosatisfy NEC 450-9.
Coordinated with HVL, VISI-VAC and Metal-Clad primary and QED and PZ III secondary
H
W
D
45
Layout Information – Transformer Section
Indoor POWER-CAST® Transformers5 and 15 kV primary (Cable-Connected only)600 V secondary
kVA Height (H) Width (W) Depth (D) Weight
500 94.00 84.00 54.00 5600
750 94.00 84.00 54.00 6300
1000 94.00 90.00 54.00 8350
1500 100.00 96.00 54.00 11600
2000 100.00 108.00 60.00 13500
2500 100.00 108.00 60.00 15950
3000 112.00 124.00 62.00 18750
3750 112.00 124.00 62.00 23500
Please consult the factory for dimensions of transformersdeviating from the following characteristics:
3 Phase, 60 Hz
High Voltage: 2.4 kV - 13.8 kV, 110 kV BIL max.
Low Voltage: 480Y/277, 480 Delta, 208Y/120, 30 kV BIL max.208Y/120 not available above 1500 kVADelta-Delta, Wye-Delta and Delta-Wye connections only
Taps: ±2 at 2.5% above and below normal
Temp. Rise: 80°C over 30°C ambient
Impedance: 5.75%
Non-Loss Evaluated Designs
Noise Levels: Per NEMA TR1
Copper Windings and Terminations
All terminations tin-plated
Overload capacity: 33% or 50% (50% not available for trans-formers 500 - 750 kVA or above 5000 kVA)Notes:
Primaries rated above 530 A must be bus-connected; please contact the factory for thesecases.
Consult the factory for Metal-Clad and HVL secondaries.
All weights are approximate.
It is recommended that ventilation openings have 12" min. clearance from any obstacle tosatisfy NEC 450-9.
Coordinated with HVL, VISI-VAC and Metal-Clad primary and QED and PZ III secondary
H
W
D
46
Layout Information – Transformer Section
Outdoor POWER-CAST® Transformers5 and 15 kV primary (Cable-Connected only)600 V secondary
kVA Height (H) Width (W) Depth (D) Weight
500 94.00 84.00 54.00 5950
750 94.00 84.00 54.00 6650
1000 94.00 90.00 54.00 8700
1500 100.00 96.00 54.00 11950
2000 100.00 108.00 60.00 13850
2500 100.00 108.00 60.00 16300
3000 112.00 124.00 62.00 19100
3750 112.00 124.00 62.00 23850
Please consult the factory for dimensions of transformersdeviating from the following characteristics:
3 Phase, 60 Hz
High Voltage: 2.4 kV - 13.8 kV, 110 kV BIL max.
Low Voltage: 480Y/277, 480 Delta, 208Y/120, 30 kV BIL max.208Y/120 not available above 1500 kVADelta-Delta, Wye-Delta and Delta-Wye connections only
Taps: ±2 at 2.5% above and below normal
Temp. Rise: 80°C over 30°C ambient
Impedance: 5.75%
Non-Loss Evaluated Designs
Noise Levels: Per NEMA TR1
Copper Windings and Terminations
All terminations tin-plated
Overload capacity: 33% or 50% (50% not available for trans-formers 500 - 750 kVA or above 5000 kVANotes:
Primaries rated above 530 A must be bus-connected; please contact the factory for thesecases.
Consult the factory for Metal-Clad and HVL secondaries.
All weights are approximate.
It is recommended that ventilation openings have 12" min. clearance from any obstacle tosatisfy NEC 450-9.
Coordinated with HVL, VISI-VAC, and Metal-Clad primary and QED and PZ III secondary
H
W
D
47
Layout Information – Transformer Section
POWER-CAST® and UNI-CAST™ TransformerAir-Terminal Chambers
Front View
36.00914
13.00330
Indoor/Outdoor
Top View
Variable
Variable
1.5038
1.5038
1.5038
1.5038
Floor Plan
Variable
Variable
Variable
Variable
RemovableTop Plate
Notes:1. Standard ATC is end access only. Front and rear access ATC is available but will increase the width of the ATC.
2. Suitable for indoor or outdoor use.
3. Removable top-plate is provided on top-feed applications.
4. Dimensions marked as variable will vary with voltage class, lightning arresters and accessories.
48
OA Cooling, 208Y/120 V or 480 V Delta Secondary – 30 kv BIL Max.
Width (W) Width (W) Height Approx.kVA Figure 1 Figure 2 (H) D1 D2 Weight
500 52 61 70 20 30 5500
750 59 68 70 21 33 7000
1000 61 70 70 20 38 7500
1500 64 73 70 22 51 9500
OA Cooling, 480Y/277 V Secondary – 30 kV BIL Max.
Width (W) Width (W) Height Approx.kVA Figure 1 Figure 2 (H) D1 D2 Weight
500 52 61 70 20 30 5500
750 59 68 70 21 33 6500
1000 61 70 70 21 41 7500
1500 64 73 70 22 49 9000
2000 73 82 70 23 45 11500
2500 74 83 85 24 48 14500
3000 75 84 96 26 52 15500
3750 76 85 96 27 67 19500
OA/FFA or OA/FA Cooling, 208Y/120 V or 480 V Delta Secondary – 30 kV BIL Max.
Width (W) Width (W) Height Approx.kVA Figure 1 Figure 2 (H) D1 D2 Weight
500 52 61 77 26 39 5500
750 59 68 77 27 38 7000
1000 61 70 77 26 38 7500
1500 64 73 77 28 51 9500
OA/FFA or OA/FA Cooling, 480Y/277 V Secondary – 30 kV BIL Max.
Width (W) Width (W) Height Approx.kVA Figure 1 Figure 2 (H) D1 D2 Weight
500 52 61 77 26 39 5500
750 59 68 77 27 38 6500
1000 61 70 77 27 41 7500
1500 64 73 77 28 49 9000
2000 73 82 77 29 45 11500
2500 74 83 92 30 48 14500
3000 75 84 98 31 52 15500
3750 76 85 98 32 67 19500
Please consult the factory for dimensions of transformersdeviating from the following characteristics:
Aluminum windings, 3 Phase, 60 Hz, Taps: ± 2.5% 2 aboveand 2 below normal, 65 degree rise over 30 degree ambient,4.5% Impedance at 500 kVA, 5.75% Impedance 750 kVA andabove.
Standard accessories: Padlockable tap changer (de-energizedoperation), 1" upper filter plug through 2500 kVA, 1" upper filtervalve above 2500 kVA, 1" drain valve with 3⁄8" sampler through2500 kVA, 2" drain valve with 3⁄8" sampler above 2500 kVA,pressure relief valve for all kVA sizes, pressure relief devicewithout alarm contacts on transformer cover above 2500 kVA,magnetic liquid-level gauge without alarm contacts, dial-typethermometer without alarm contacts, pressure/vacuum gaugewith bleeder connection, without alarm contacts.
Figures 1 and 2 include 3" flange on primary (included in width
given in tables), for connection to HVL, VISI/VAC or Metal-CladSwitchgear; for Primary ATC subtract 3" from width given intable and add width of appropriate ATC on page 51.
Figure 1 includes 3" flange on secondary (included in widthgiven in tables), for connection to Indoor PZ III Switchgear. ForSecondary ATC subtract 3" from width given in table and addwidth of appropriate ATC on page 51.
Figure 2 includes 12" throat on secondary (included in widthgiven in tables), for connection to QED switchboard or outdoorPZ III Switchgear. For Secondary ATC subtract 12" from widthgiven in table and add width of appropriate ATC on page 51.
Layout Information – Transformer Section
Indoor and Outdoor Liquid-Filled Transformers (Mineral Oil Only)
12470 V Delta, 13200 V Delta, 13800 V Delta Primary – 95 kv BIL max.
D2
D1
W
H
Figure 1
W
H
Figure 2
49
Layout Information – Transformer Section
OA Cooling, 480Y/277 V Secondary – 30 kV BIL Max.
Width (W) Width (W) Height Approx.kVA Figure 1 Figure 2 (H) D1 D2 Weight
500 62 71 70 20 28 5500
750 67 76 70 21 32 7000
1000 74 83 70 22 32 8000
1500 75 84 70 22 49 10000
2000 81 90 70 23 45 12000
2500 82 91 85 24 52 13500
3000 83 92 96 27 55 16500
3750 84 93 96 27 65 20500
OA/FFA or OA/FA Cooling, 480Y/277 V Secondary – 30 kV BIL Max.
Width (W) Width (W) Height Approx.kVA Figure 1 Figure 2 (H) D1 D2 Weight
500 62 71 77 26 37 5500
750 67 76 77 27 37 7000
1000 74 83 77 28 37 8000
1500 75 84 77 28 49 10000
2000 81 90 77 29 45 12000
2500 82 91 92 30 52 13500
3000 83 92 98 32 55 16500
3750 84 93 98 32 65 20500
Please consult the factory for dimensions of transformersdeviating from the following characteristics:
Aluminum windings, 3 Phase, 60 Hz, Taps: ± 2.5% 2 aboveand 2 below normal, 65 degree rise over 30 degree ambient,4.5% Impedance at 500 kVA, 5.75% Impedance 750 kVA andabove.
Standard Accessories: Padlockable tap changer (de-energizedoperation), 1" upper filter plug through 2500 kVA, 1" upper filtervalve above 2500 kVA, 1" drain valve with 3⁄8" sampler through2500 kVA, 2" drain valve with 3⁄8" sampler above 2500 kVA, pres-sure relief valve for all kVA sizes, pressure relief device withoutalarm contacts on transformer cover above 2500 kVA, magneticliquid-level gauge without alarm contacts, dial-type thermome-ter without alarm contacts, pressure/vacuum gauge withbleeder connection, without alarm contacts.
Figures 1 and 2 include 10" flange on primary (included in widthgiven in tables), for connection to HVL Switchgear ; for PrimaryATC subtract 10" from width given in table and add width ofappropriate ATC on page 51.
Figure 1 includes 3" flange on secondary (included in widthgiven in tables), for connection to Indoor PZ III Switchgear. ForSecondary ATC subtract 3" from width given in table and addwidth of appropriate ATC on page 51.
Figure 2 includes 12" throat on secondary (included in widthgiven in tables), for connection to QED switchboard or outdoorPZ III Switchgear. For Secondary ATC subtract 12" from widthgiven in table and add width of appropriate ATC on page 51.
Indoor and Outdoor Liquid-Filled Transformers (Mineral Oil Only)
24940 V Delta Primary – 125 kV BIL max.
D2
D1
W
H
Figure 1
W
H
Figure 2
29.50749
59.001499
59 Inch Dimension isover Primary Flange
50
Layout Information – Transformer Section
OA Cooling, 480Y/277 V Secondary – 30 kV BIL Max.
Width (W) Width (W) Height Approx.kVA Figure 1 Figure 2 (H) D1 D2 Weight
500 64 73 70 22 29 6000
750 68 77 70 22 32 7500
1000 68 77 70 22 38 8000
1500 74 83 70 22 42 9500
2000 75 84 70 23 58 11500
2500 85 94 69 25 52 14000
3000 84 93 96 27 57 17000
3750 84 93 96 27 69 20500
OA/FFA or OA/FA Cooling, 480Y/277 V Secondary – 30 kV BIL Max.
Width (W) Width (W) Height Approx.kVA Figure 1 Figure 2 (H) D1 D2 Weight
500 64 73 77 28 38 6000
750 68 77 77 28 37 7500
1000 68 77 77 28 38 8000
1500 74 83 77 28 42 9500
2000 75 84 77 29 58 11500
2500 85 94 76 31 52 14000
3000 84 93 98 32 57 17000
3750 84 93 98 32 69 20500
Please consult the factory for dimensions of transformersdeviating from the following characteristics:
Aluminum windings, 3 Phase, 60 Hz, Taps: ± 2.5% 2 aboveand 2 below normal, 65 degree rise over 30 degree ambient,4.5% Impedance at 500 kVA, 5.75% Impedance 750 kVA andabove.
Standard Accessories: Padlockable tap changer (de-ener-gized operation), 1" upper filter plug through 2500 kVA, 1"upper filter valve above 2500 kVA, 1" drain valve with 3⁄8"sampler through 2500 kVA, 2" drain valve with 3⁄8" samplerabove 2500 kVA, pressure relief valve for all kVA sizes, pressurerelief device without alarm contacts on transformer coverabove 2500 kVA, magnetic liquid-level gauge without alarmcontacts, dial-type thermometer without alarm contacts, pres-sure/vacuum gauge with bleeder connection, without alarmcontacts.
Figures 1 and 2 include 10" flange on primary (included in widthgiven in tables), for connection to HVL Switchgear ; for PrimaryATC subtract 3" from width given in table and add width ofappropriate ATC on page 51.
Figure 1 includes 3" flange on secondary (included in widthgiven in tables), for connection to Indoor PZ III Switchgear. ForSecondary ATC subtract 3" from width given in table and addwidth of appropriate ATC on page 51.
Figure 2 includes 12" throat on secondary (included in widthgiven in tables), for connection to QED switchboard or outdoorPZ III Switchgear. For Secondary ATC subtract 12" from widthgiven in table and add width of appropriate ATC on page 51.
Indoor and Outdoor Liquid-Filled Transformers (Mineral Oil Only)
34500 V Delta Primary – 150 kV BIL max.
D2
D1
W
H
Figure 1
W
H
Figure 2
29.50749
59.001499
59 Inch Dimension isover Primary Flange
Liquid-Filled TransformerAir-Terminal Chambers/Boxes
Primary and Secondary Air Terminal Box
110 BIL and Below (15 kV class)
kVA A B C D
225-2500 18 38 29 373000-5000 24 38 36 44
125 BIL (25 kV class)
kVA A B C D
225-2500 24 38 36 443000-5000 24 38 36 44
Primary and Secondary Full Length Air TerminalChamber
110 BIL and Below (15 kV class)
kVA A B C D E
225-2500 18 38 55 10 673000-5000 24 44 75 10 87
125 BIL (25 kV class)
kVA A B C D E
225-2500 24 38 55 10 673000-5000 24 44 75 10 87
Note: For primary or secondary intermediate or station class arresters use 125 BIL cabinetfor 125 BIL and below.
51
Layout Information – Transformer Section
D
OutsideTankWall
CBushingHeight
Removable Sill
RemovableCover Panel
EATC
Height
BATC Width A
ATC Depth
CLBushing
E - 2.00 51 Inside
B - 4.00 102 Inside
OutsideTank Wall
AATB Depth
BATB Width
DATB
Height
3.0076
C
Removable Plate
CLBushing
B - 6.00 152
A - 10.00 254
A - 3.00 76
D - 4.00 102 Inside
B - 4.00 102 Inside
52
Layout Information – Secondary Section
POWER-DRY™ Transformer – HVL/VISI-VAC® SwitchgearSecondary Connection (3 wire secondary only – see note 3)
Approx Weights: 1200lbs./545kg indoor 1400lbs./636kg Outdoor
Notes:1. Transformer dimensions vary depending upon kVA, BIL and temperature rise ratings. See TRANSFORMER section for a complete table of indoor POWER-DRY transformer dimensions.
Contact the manufacturing location for outdoor POWER-DRY dimensions.
2. Indoor and outdoor units are front-aligned (.5" difference in indoor units).
3. Please contact the manufacturing location for 4-wire secondaries.
34.00864
2.0051
Floor Plan
4.00102
6.001526.00
152 60.001524
60.001524Min.
(See Note 1)
45.001143
45.001143
CL
2.00 x 4.00 51 102 Control Conduit Area
(See Note 2)
34.00864
2.0051
Top View
Front View
6.00152
6.001526.00
152
1.75 (Typ.) 44
1.75 (Typ.) 44
94.002388Min.
(See Note 1)
38.00965
22.00559
97.502477
64.001626
63.501613Min.
(See Note 1)
47.00119446.75
1187
Outdoor
CL
3.0076
(Flange)
3.0076
(Flange)
(See Note 2)
Indoor
Front View
94.002388Min.
(See Note 1)
90.00 2286
38.00965
22.00559
34.00864
2.0051
Floor Plan
4.00102
6.001526.00
15254.501384
54.001372Min.
(See Note 1)
39.501003
39.00991
CL
34.00864
2.0051
Top View
4.00102
6.001526.00
152
2.00 x 4.00 51 102 Control Conduit Area
2.00 x 4.00 51 102 Control Conduit Area
2.00 x 4.00 51 102 Control Conduit Area
54.501384
54.001372Min.
(See Note 1) 39.501003
39.00991
DANGERHIGH
VOLTAGE
DANGERHIGH
VOLTAGE
CL
(See Note 2)
(See Note 2)
5 kV
53
Layout Information – Secondary Section
POWER-CAST® Transformer – HVL/VISI-VAC® SwitchgearSecondary Connection (3 wire secondary only-See note 3)
5 kV
Approx. Weights: 1200lbs./545kg indoor 1400lbs./636kg outdoor
Notes:1. Transformer dimensions vary depending upon kVA, BIL and temperature rise ratings. Please contact the manufacturing location for transformer dimensions. Standard transformer dimensions
are not available for POWER-CAST transformers with 5 kV class secondaries.
2. Indoor units are front-aligned (.5" difference), outdoor units have a 6" difference in alignment.
3. Please contact the manufacturing location for 4-wire secondaries.
34.00864
2.0051
Floor Plan
4.00102
6.001526.00
152
6.00152
60.001524
45.001143
CL
2.00 x 4.00 51 102 Control Conduit Area
(See Note 2)
34.00864
2.0051
Top View
Front View
6.00152
6.001526.00
1522.00 x 4.00 51 102 Control Conduit Area
2.00 x 4.00 51 102 Control Conduit Area
38.00965
22.00559
97.502477
64.001626
54.001372Min.
(See Note 1) 47.001194
39.00991
Outdoor
CL
3.0076
(Flange)
(See Note 2)
94.002388Min.
(See Note 1)
54.001372Min.
(See Note 1)
39.00991
54.001372Min.
(See Note 1)
39.00991
Indoor
Front View
94.002388Min.
(See Note 1)
90.00 2286
38.00965
22.00559
3.0076
Flange
34.00864
2.0051
Floor Plan
4.00102
6.001526.00
15254.501384
39.501003
CL
34.00864
2.0051
Top View
4.00102
6.001526.00
152
2.00 x 4.00 51 102 Control Conduit Area
54.501384
54.001372Min.
(See Note 1) 39.501003
39.00991
DANGERHIGH
VOLTAGE
DANGERHIGH
VOLTAGE
CL
(See Note 2)
(See Note 2)
54
Layout Information – Secondary Section
Liquid-filled Transformer – HVL/VISI-VAC® SwitchgearSecondary Connection (3-wire secondary only-see note 5) To 3750 kVA (see note 4)
5 kV
Approx. Weights: 1200lbs./545kg indoor 1400lbs./636kg outdoor
Notes:1. Please contact the factory for transformer dimensions. Standard liquid-filled transformer dimensions are not available for units with 5 kV class secondaries.
2. Extra 1.5" in height if base channel is included in HVL/VISI-VAC.
3. Units are not necessarily front or rear-aligned.
4. If transformer is over 3750 kVA, variations to the dimensions shown here will be necessary.
5. Please contact the manufacturing location for 4-wire secondaries.
34.00864
2.0051
4.00102
6.001526.00
152 60.001524
2.00 x 4.00 51 102 Control Conduit Area
34.00864
2.0051
Top View
Front View
6.00152
6.001526.00
152
38.00965
22.00559
97.502477
64.001626
28.00711
Outdoor
3.00 (Flange on HVL) 76
3.00 (Flange on HVL) 76
Indoor
Front View
90.00 2286
or91.502324
(See Note 2)
38.00965
22.00559
34.00864
2.0051
Floor Plan
4.00102
6.001526.00
15254.501384
20.50521
CL
34.00864
2.0051
Top View
4.00102
6.001526.00
152
2.00 x 4.00 51 102 Control Conduit Area
2.00 x 4.00 51 102 Control Conduit Area
2.00 x 4.00 51 102 Control Conduit Area
54.501384
20.50508
DANGERHIGH
VOLTAGE
DANGERHIGH
VOLTAGE
(See Notes 1, 3, 4)
(See Notes 1, 3, 4) (See Notes 1, 3, 4)
(See Notes 1, 3, 4)
D1
D2
D1
Floor Plan
D1
D1
D2
H(See Note 1)
H(See Note 1)
26.00660
CL
55
Layout Information – Secondary Section
POWER-DRY™ and POWER-CAST® TransformersMetal-Clad Switchgear Secondary Connection (3 wire secondary only-see note 2)
5 kV
Approx. Weights (less breakers): 2200lbs./999kg indoor 2700lbs./1226kg outdoor 1200 A breaker: 360lbs./163kg 2000 A breaker: 410lbs./186kg 3000 A breaker: 480lbs./218kg
Notes :1. Please contact the manufacturing location for transformer dimensions. Standard dimensions are not available for transformers with 5 kV class secondaries.
2. Please contact the manufacturing location for 4-wire secondaries.
3. Units will be rear-aligned when units have the depths shown. For transformers with larger depths, transformers will protrude in rear.
54.001372
(Power-Cast)or
60.001524Min.
(Power-Dry)(See Note 1)
109.102771
39.00991
(Fixed)(Power-Cast)
or45.001143
(Fixed)(Power-Dry)
54.001372
(Power-Cast)or
60.001524Min.
(Power-Dry)(See Note 1)
CL
Top View
Front View
36.00914
3.0076
(Flange)
108.502756
3.0076
(Flange)
Outdoor
94.002388Min.
(See Note 1)
20.00508
20.00508
8.00203
Floor Plan
6.30160
96.932462
1.7043
.10 3
8.00203
CL
5.90150
39.00991
(Power-Cast)or
45.001143
(Power-Dry)
36.93938
(Fixed)(Power-Dry)
or42.931090
(Fixed)(Power-Cast)
Indoor
18.00457
9.00229
Front View
3.5089
9.00229
9.00229
8.00203
1.0025
92.002337
(With Door)
95.002413
36.00914
54.001372Min.
(See Note 1)
94.002388Min.
(See Note 1)
39.00991
2.0051
1.7544
8.00203
1.0025
CL
18.00457
9.00229
Floor Plan
3.5089
9.00229
9.00229
1.0025
91.002311
54.001372Min.
(See Note 1) 39.00991
2.0051
.205
8.00203
2.5064
3.5089
CL
Top View
38.00965
(Fixed)
37.00940
(Fixed)
(See Note 3)
(See Note 3) (See Note 3)
(See Note 3)
Roof Overhang
56
Layout Information – Secondary Section
Liquid-Filled Transformer – Metal-Clad Switchgear Secondary Connection (3 wire secondary only-see note 2) To 3750 kVA (see note 3)
Approx. Weights (less breakers): 2200lbs./999kg indoor 2700lbs./1226kg outdoor1200 A breaker: 360lbs./163kg 2000 A breaker: 410lbs./186kg 3000 A breaker: 480lbs./218kg
Notes :1. Please contact the manufacturing location for transformer dimensions. Standard dimensions are not available for transformers with 5 kV secondaries.2. If transformer is over 3750 kVA, variations to the dimensions shown here will be necessary.3. Please contact the manufacturing location for 4-wire secondaries.4. Units are not necessarily front or rear aligned. Transformer radiators may extend behind switchgear.
109.102771
49.181249
CL
Top View
Front View
36.00914
22.00559
108.502756
OutdoorIndoor
18.00457 9.00
229
Top View
Front View
3.5089
9.00229
9.00229
1.0025
92.002337
(With Door)
95.002413
36.00914
22.00559
3.00 (Flange - on Metal-Clad) 76
46.0011682.00
51
2.5064
2.5063
5.90150
1.7544
8.00203
8.00203
CL
18.00457
9.00229
Floor Plan
3.5089
9.00229
9.00229
1.0025
91.002311
2.0051
45.001143
.205
8.00203
CL
H(See Note 1)
(See Note 1)
D1
D2
(See Note 1)
D1
(See Note 1)
D1
(See Note 1)
D1
D2
49.181249
3.0076
(Flange-on Metal-Clad)
H(See Note 1)
20.005088.00
203
Floor Plan
6.30160
96.932462
20.00508
1.7043
.10 3
8.00203
CL
1.0025
Radiators May ExtendBehind Switchgear.
(See Note 4)Radiators May Extend
Behind Switchgear.(See Note 4)
5 kV
57
Layout Information – Secondary Section
POWER-DRY™, POWER-CAST®, UNI-CAST™ Transformers – QED Switchboard to 4000 ASecondary Connection
600 V
54.00 1372Min.
(See Note 1) 36.00914
54.001372Min.
(See Note 3)
36.00914
94.002388Min.
(See Note 1)
91.502324
W(See Note 3)
54.00 1372
(See Note 1)
54.001372Min.
(See Note 3)
36.00914
36.00914
(See Note 2)
(See Note 2)
69.031753Min.
(See Note 3)
42.031068
54.001372
(Power-Cast, Uni-Cast)or
60.001524Min.
(Power-Dry)(See Note 1)
54.001372
(Power-Cast, Uni-Cast)or
60.001524Min.
(Power-Dry)(See Note 1)
CL
CL
CT
94.002388Min.
(See Note 1)
91.502324
W(See Note 3)
3.0076
65.501664Min.
(See Note 3)
41.001041
CL
CL
CT
OutdoorIndoor
Front View
Front View
Floor Plan
Floor Plan
Top View
Top View
(See Note 2)
(See Note 2)
Weight varies according to switchboard componentsand enclosure construction.
Notes:1. Transformer dimensions vary depending upon kVA, BIL and temperature rise ratings. See
TRANSFORMER section for a complete table of transformer dimensions.
2. Indoor units are front-aligned, outdoor units are not necessarily front or rear-aligned.Please see table for the value of distance CT on outdoor units.
3. Please consult QED layout manual or Q2C product selector for conduit area dimensionsand cabinet width. Outdoor enclosures are shown with rear covers; add 1.5" to theoutdoor floor-plan depth and 2" to the outdoor top view depth for rear doors. Units withQED-3 or a QED-4 secondaries may require a transition section – please contact themanufacturing location for details.
Distance CT
POWER-DRY Transformer POWER-CAST/UNI-CAST Transformer
CT = 39" Cabinet DepthCT = +9"2
58
Layout Information – Secondary Section
POWER-DRY™, POWER-CAST®, UNI-CAST™ Transformers – QED Switchboard 4001-5000 ASecondary Connection
600 V
60.001524Min.
(See Note 1)37.50
952
60.001524Min.
(See Note 3)
37.50952
100.002540Min.
(See Note 1)
91.50 2324
W(See Note 3)
60.001524Min.
(See Note 1)
60.001524Min.
(See Note 3)
37.50953
37.50953
(See Note 2)
75.031906Min.
(See Note 3)
42.031068
60.001524Min.
(See Note 2)
60.001524Min.
(See Note 1)
CLCL
CL
100.002540Min.
(See Note 1)
91.502324
3.0076
71.501816Min.
(See Note 3)
41.001041
CL
(See Note 2)
(See Note 2)
(See Note 2)
OutdoorIndoor
Front View Front View
Floor Plan Floor Plan
Top ViewTop View
W(See Note 3)
CT
CT
Weight varies according to switchboard components and enclosure construction.
Notes:1. Transformer dimensions vary depending upon kVA, BIL and temperature rise ratings. See
the TRANSFORMER section for a complete table of transformer dimensions (minimumdepth is 60").
2. Indoor units are front-aligned, indoor units are not necessarily front or rear-aligned.Please see table above for the value of distance CT on outdoor units.
3. Please consult QED layout manual or Q2C product selector for conduit area dimensionsand cabinet width. Outdoor enclosures are shown with rear covers; add 1.5" to theoutdoor floor-plan depth and 2" to the outdoor top view depth for rear doors. Units withQED3 or QED-4 distribution sections may require a transition section – please contactmanufacturing location for details.
Distance CT
POWER-DRY Transformer POWER-CAST/UNI-CAST Transformer
CT = 39" Cabinet DepthCT = +10.5"2
59
Layout Information – Secondary Section
Liquid Filled Transformer to 3750 kVA (see note 4) – QED Switchboard to 4000 ASecondary Connection
600 V
Weight varies according to switchboard components and enclosure construction.
Notes:1. Liquid-filled transformer standard enclosure dimensions are given in the TRANSFORMER section. They are applicable only for mineral-oil units under certain conditions (see TRANSFORMER
section for details).
2. Units are not necessarily front- or rear-aligned.
3. Please consult QED layout manual or Q2C product selector for conduit area dimensions and cabinet width. Outdoor enclosures are shown with rear covers; add 1.5" to the outdoor floor-plandepth and 2" to the outdoor top view depth for rear doors. For units with QED-3 or QED-4 distribution sections, a transition section may be necessary – please contact the manufacturing loca-tion for details.
4. If transformer is over 3750 kVA, variations to the dimensions shown here may be necessary.
69.031753Min.
(See Note 3)
H(See Note 1)
Outdoor
Front View
Floor Plan
Top View
CL
CL
43.031093
65.501664Min.
(See Note 3)
42.001067
91.502324
W
(See Note 3)
Front View
(See Note 3)
54.001372Min.
(See Note 3)
H(See Note 1)
D1
D2
D1
D2
Indoor
Floor Plan
Top View
CL
(See Notes 1, 2, 4)(See Notes 1, 2, 4)
D1
CL
31.00787
54.001372Min.
(See Note 3)
D131.00787
91.502324
W
12.00305
Throat Includedin Transformer
Dimensions
12.00305
Throat Includedin Transformer
Dimensions
(See Notes 1, 2, 4) (See Notes 1, 2, 4)
60
Layout Information – Secondary Section
Liquid-Filled Transformer to 3750 kVA (see note 4) – QED Switchboard 4001 A-5000 ASecondary Connection
600 V
Weight varies according to switchboard components and enclosure construction.
Notes:1. Liquid-filled transformer standard enclosure dimensions are given in the TRANSFORMER section. They are applicable only for mineral-oil units under certain conditions (see TRANSFORMER
section for details).
2. Units are not necessarily front- or rear-aligned.
3. Please consult QED layout manual or Q2C product selector for conduit area dimensions and cabinet width. Outdoor enclosures are shown with rear covers; add 1.5" to the outdoor floor-plandepth and 2" to outdoor top view depth for rear doors. A transition section may be necessary – please contact the manufacturing location for details.
4. If transformer is over 3750 kVA, slight variations to the dimensions shown here may be necessary.
75.031906Min.
(See Note 3)
H(See Note 1)
Outdoor
Front View
Floor Plan
Top View
CL
CL
43.031093
71.501816Min.
(See Note 3)
42.001067
91.502324
W
(See Note 3)(See Note 3)
60.001524Min.
(See Note 3)
H(See Note 1)
(See Notes 1, 2, 4) (See Notes 1, 2, 4)
D1
D1
D1
D1
Indoor
Front View
Floor Plan
Top View
CL
D1
CL
31.00787
60.001524Min.
(See Note 3)
31.00787
91.502324
W
(See Notes 1, 2, 4)(See Notes 1, 2, 4)
D1
12.00305
Throat Includedin Transformer
Dimensions
12.00305
Throat Includedin Transformer
Dimensions
61
Layout Information – Secondary Section
POWER-DRY™, POWER-CAST®, UNI-CAST™ Transformers – PZ III Drawout SwitchgearSecondary Connection
Weight varies according to switchboard components and enclosure construction.Notes:1. Outdoor units must be coordinated with POWER-ZONE® NEMA Type 3R walk-in or non-walk-in enclosures on a case-by-case basis. Please consult the Power-Zone Center group in Smyrna,
TN for details.
2. Transformer dimensions may vary depending upon kVA, BIL and temperature rise ratings. See TRANSFORMER section for a complete table of transformer dimensions. Transformers close-coupling to 4001 A-5000 A PZ III gear are 60" deep minimum. Power-Cast/Uni-Cast transformers close-coupling to 4001-5000 A PZ III gear will be a minimum of 100" in height.
3. Please consult the PZ III layout guide or Q2C product selector for conduit area dimensions and cabinet width and depth.
4. Larger offset values are for switchgear with DS-840 or DSL switchgear.
54.001372
or60.001524Min.
(See Note 2)
.5614or
8.56217
(See Note 4)
.5614or
8.56217
(See Note 4)
91.502324
W(See Note 3)
Indoor
Front View
Top View
54.001372
or60.001524Min.
(See Note 2)
Top View
94.002388Min.
(See Note 2)
6 Depths Available3 for DS Switchgear3 for DSL Switchgear
(See Note 3)
6 Depths Available3 for DS Switchgear3 for DSL Switchgear
(See Note 3)
Outdoor(See Note 1)
Front View
Top View
Floor Plan
CL
CL
600 V
62
Layout Information – Secondary Section
Liquid Filled Transformer to 3750 kVA (see Note 5) – PZ III Drawout SwitchgearSecondary Connection
Weight varies according to switchgear components and enclosure construction.Notes:1. Outdoor units must be coordinated with POWER-ZONE® NEMA Type 3R walk-in or non-walk-in enclosures on a case-by-case basis. Please consult the Power-Zone Center group in Smyrna,
TN for details.
2. Liquid-filled transformer standard enclosure dimensions are given in the TRANSFORMER section. They are applicable only for mineral-oil units under certain conditions (see TRANSFORMERsection for details).
3. Please consult the PZ III layout guide or Q2C product selector for conduit area dimensions and cabinet width and depth.
4. Larger values shown are for switchgear with DS-840 or DSL switchgear.
5. For transformers over 3750 kVA, slight changes to the dimensions shown here may be necessary.
35.25895or
43.251099Min.
(See Note 4)
35.25895or
43.251099Min.
(See Note 4)
CL
(See Notes 2, 4, 5)
91.502324
12.50318 W
(See Note 3)
CL
Indoor
Front View
Floor Plan
Top View
D1
D2
D1
6 Depths Available3 for DS Switchgear
3 for DSL Switchgear(See Note 3)
(See Notes 2, 4, 5)
6 Depths Available3 for DS Switchgear
3 for DSL Switchgear(See Note 3)
CL
CL
Outdoor
Front View
Floor Plan
Top View
600 V
Order No. 6020CT9401 July 97 Printed in U.S.A. ©1997 Square D All Rights Reserved
POWER-CAST, POWER-STYLE, POWER-ZONE, VISI-VAC, SQUARE D ands are Registered Trademarks of Square D Company.POWER-DRY and UNI-CAST are Trademarks of Square D Company.