Building Science Corporation Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality by Armin Rudd Building Science Consortium USDOE Building America Program for Durability and Disaster Mitigation In Wood-Frame Housing Conference Madison, Wisconsin 08 November 2000 PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 1 of 34

Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Building Science Corporation

Practical Approaches to ResidentialVentilation for Improved Durability and

Indoor Air Quality

by

Armin RuddBuilding Science Consortium

USDOE Building America Program

forDurability and Disaster Mitigation In Wood-Frame Housing Conference

Madison, Wisconsin08 November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 1 of 34

Page 2: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Building Science Corporation

ProvidingProviding durability durability forlittle or no incremental

cost is a goal of theBuilding America program

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 2 of 34

Page 3: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

DurabilityDurability and maintenance cost are directfunctions of:

•• Moisture Moisture•• Heat Heat

•• U ltra-violet light Ultra-violet light

Of these three, MoistureMoisture is the most significant

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 3 of 34

Page 4: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

DurabilityDurability can be insured with respect tomoisture by:

•• Providing a building envelope design that can dry Providing a building envelope design that can dryshould it get wetshould it get wet

•• Preventing excessive pressurization and Preventing excessive pressurization anddepressurization of occupied spaces and cavitiesdepressurization of occupied spaces and cavities

•• Installing controlled mechanical ventilation Installing controlled mechanical ventilationsystemssystems

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 4 of 34

Page 5: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Building Science Corporation

Purposes of mechanical ventilation

1. Point-source ventilation - Remove Pollutants– exhaust fans: kitchen, bath, laundry

2. Whole-building ventilation - Dilute Pollutants– supply, exhaust, or balanced fans distributing to all

rooms

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 5 of 34

Page 6: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Climate Specific Design SolutionsClimate Specific Design Solutions

November 2000

Building Science Consortium

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 6 of 34

© buildingscience.com

Page 7: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Central-fan-integrated supply ventilationInterior closet or basement configuration

Cooling/Dehumidifying

Apparatus

Heating/HumidifyingApparatus

Thermostat

Humidistat(optional)

Return AirFrom Interior Space

Supply AirTo Interior Space

Air Distribution Fan

BalancingDamper

Control WiringTerminals

Air Handler Unit

Filter/Air Cleaner Register boxadapted withslide-in filter

Field measurement of outsideair duct pressure, used to setbalancing damper position

Ventilation Air Intake(locate away frompollutant sources)

Wall Cap withInsect Screen

ExteriorWall

6" InsulatedOutside Air DuctAirCyclerTM

Control

Building Science Consortium

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 7 of 34

© buildingscience.com

Page 8: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Ventilation Air Distribution and Mixing ControlWires to low voltage terminals on central air handler unit

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 8 of 34

© buildingscience.com

Page 9: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Building Science Corporation

Intermittent Operation

• Sizing– intermittent flow equals constant flow reduced

by low background infiltration amount whenblower is not on, all divided by duty cyclefraction

&( & ( ( )))

QQ

IV f

fin

co

=− −

601

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 9 of 34

Page 10: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Building Science Corporation

Intermittent Operation

• where,

total

on

offon

on

t

t

tt

tf =

+=

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 10 of 34

Page 11: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Very cold climate

ventilation and moisture control designsventilation and moisture control designsHDD > 8000HDD > 8000

• 1st choice is continuously operating single-point exhaustwith intermittent central-fan-integrated supply limited to7% of AHU flow

• 2nd choice is continuously operating single-point exhaustwith central fan recycling for distribution and mixing(sealed combustion space/DHW heating)

• 3rd choice is balanced heat recovery ventilation withcentral fan recycling for distribution, or fully ducted to allrooms

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 11 of 34

Page 12: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Builders Pulte Home Corp. Centex Homes

Town & Country HomesLocation Minneapolis, MinnesotaSubdiv isions The Grove at Elm Creek

Regatta Eden Prairie

Climate very coldNo. Homes 300+

Ventilation systems

• Continuously operating single-point exhaust with central fan recycling forwhole-house distribution and mixing, and with intermittent central-fan-integrated supply limited to 7% of AHU flow

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 12 of 34

Page 13: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Minneapolis ventilation study

0

0.1

0.2

0.3

0.4

0.5 Ai

r Cha

nges

Per

Hou

r (1/

h)

1 2 3 4 5 6 7 8 9 10 11 12 13Test ID Number

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 13 of 34

Page 14: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Cold climateCold climateventilation and moisture control designsventilation and moisture control designs

4500<HDD<80004500<HDD<8000

• 10 cfm/person design– 1st choice is central-fan-integrated supply limited to

10% of AHU flow• 20 cfm/person design

– 1st choice is continuously operating single-pointexhaust with intermittent central-fan-integrated supplylimited to 10% of AHU flow

– 2nd choice is continuously operating single-pointexhaust with central fan recycling for distribution andmixing (sealed combustion space/DHW heating)

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 14 of 34

Page 15: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Builder Sturbridge ConstructionSubdiv ision Prairie CrossingLocation Grayslake, IllinoisClimate coldNo. Homes 350

Ventilation systems

• In 1996, started with low-cost blending supply system - separate inline fan, no filter, 2 pickups, 1 supply - complaints: fan noise and cold basement• In 1997, changed to central-fan-integrated supply with fan recycling - 6” insulated OA duct to AHU return, with balancing damper - 7% outside air fraction, minimum 33% duty cycle - filtration by AHU filter - builder provides customer education - no complaints after over 3 years

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 15 of 34

Page 16: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Builder Town & Country HomesSubdiv ision Centennial CrossingLocation Vernon Hills, IllinoisClimate coldNo. Homes 191

Ventilation system

• Central-fan-integrated supply with fan recycling - 6” insulated OA duct to AHU return, with balancing damper - 7% outside air fraction, minimum 33% duty cycle - filtration by AHU filter - no complaints after over three years

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 16 of 34

Page 17: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Building Science Corporation

Monitored Runtime DataCentennial Crossing, Lot 22

Cool ON Heat ON Vent ON Cost(%) (%) (%) ($)

Apr (27-30) 0 12 12 0.24May 1 2 15 3.06Jun 7 1 10 2.05Jul 10 0 12 2.58Aug 10 0 13 2.72Sep 5 0 15 2.96Oct 0 4 15 3.07Nov 0 13 10 1.99Dec 0 20 6 1.31Jan 0 31 3 0.60Feb 0 23 5 0.95Mar (1-9) 0 25 4 0.23

Notes: Fan recycling control set for 25 min OFF, 6 min ON (19% duty cycle)

Fan Recycling

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 17 of 34

Page 18: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Building Science Corporation

Monitored Runtime DataCentennial Crossing, Lot 176

Cool ON Heat ON Vent ON Cost(%) (%) (%) ($)

Aug 21 0 17 3.52Sep 10 0 21 4.24Oct 0 5 20 4.12Nov 0 15 12 2.33Dec 0 27 6 1.35Jan 0 35 3 0.54Feb 0 24 5 1.00

Notes: Fan recycling control set for 20 min OFF, 8 min ON (29% duty cycle)

Fan Recycling

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 18 of 34

Page 19: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Building Science Corporation

Monitored Runtime DataCentennial Crossing, Lot 179

Cool ON Heat ON Vent ON Cost(%) (%) (%) ($)

Oct 0 5 24 4.97Nov 0 15 14 2.81Dec 0 25 9 1.81Jan 0 34 3 0.68Feb 0 26 6 1.18Mar (1-8) 0 31 3 0.17

Notes: Fan recycling control set for 20 OFF 10 ON (33% duty cycle)

Fan Recycling

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 19 of 34

Page 20: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Mixed climateMixed climateventilation and moisture control designsventilation and moisture control designs

HDD<4500HDD<4500

• 10 cfm/person design– 1st choice is central-fan-integrated supply limited to

13% of AHU flow

• 20 cfm/person design– 1st choice is continuously operating exhaust with

intermittent central-fan-integrated supply limited to 13%of AHU flow

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 20 of 34

Page 21: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Builder The Lee Group/Braemar Urban VenturesSubdiv ision Village GreenLocation Los Angeles, CaliforniaClimate mixed-dryNo. Homes 186

Ventilation system

• Specified single-point exhaust with central fan recycling for whole-housedistribution and mixing

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 21 of 34

Page 22: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Hot-dry climate ventilation designsHot-dry climate ventilation designs>45 F, <20” rain>45 F, <20” rain

• 1st choice is central-fan-integrated supply limited to 15%of air handler flow

• 2nd choice is central-fan-integrated supply withcontinuously operating single-point exhaust (sealedcombustion if in conditioned space)

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 22 of 34

Page 23: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Central-fan-integrated supply ventilationUnvented-cathedralized attic configuration

Central Return Box

Coo

ling

Coi

l

Hea

ting

Coi

l

Return Grille and Filter

Supply Air

Main Return Duct

WallCap

Gable End Wall

AirCycler TM

Control

Gypsum Ceiling

Outside Air Duct6" Insulated Flex-duct

Circular Filter(cut from blankand friction fit)

Balancing DamperAbove

Building Science Consortium

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 23 of 34

© buildingscience.com

Page 24: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Central-fan-integrated supply ventilationOutside air duct (filtered) connected to return filter grille pan

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 24 of 34

© buildingscience.com

Page 25: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Builder Pulte Home CorporationSubdiv isions: Angel Park (2), Cypress Pointe (116), Crown Ridge (105), Arbor View (88), Stallion Mountain (760)Location Las Vegas, NevadaClimate hot-dryNo. Homes over 1000

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 25 of 34

Page 26: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Building Science Corporation

-6

-4

-2

0

2

4

6

Tem

per

atu

re V

aria

tio

n (

F)

ReturnStorage

MbedHall

GreatDining

Bed 2

max

min

avg

Indoor temperature variationfrom the house average

Lot 6Arbor View

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 26 of 34

© buildingscience.com

Page 27: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Builder Watt HomesSubdiv ision Four SeasonsLocation Las Vegas, NevadaClimate hot-dryNo. Homes 106

Ventilation system

• Central-fan-integrated supply with fan recycling - 5” insulated OA duct to AHU return, with balancing damper - 7% outside air fraction, minimum 33% duty cycle - washable filter behind central return filter grille - no complaints after over 3 years

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 27 of 34

Page 28: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Builder Pulte Home CorporationSubdiv ision Arroyo RidgeLocation Tucson, ArizonaClimate hot-dryNo. Homes 2

Ventilation system

• Central-fan-integrated supply with fan recycling - 6” insulated OA duct to AHU return, with balancing damper - 7% outside air fraction, minimum 33% duty cycle - washable filter behind central return filter grille - no complaints or concerns after over 2 years

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34

Page 29: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Builder Pulte Home CorporationSubdiv ision Retreat at the BluffsLocation Tucson, ArizonaClimate hot-dryNo. Homes 156

Ventilation system

• Single-point exhaust - upgraded fan in laundry room, wall switch - complaints: fan noise, lack of filtration and distribution

• Changed to central-fan-integrated supply on following project:Spanish Trails

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 29 of 34

Page 30: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Builder Artistic HomesSubdiv isions Mirabella, Tuscany,

Desert SpringsLocation Albuquerque, NMClimate mixed-dryNo. Homes 15 (will soon be 800/yr)

Ventilation system

• Central-fan-integrated supply with fan recycling - 6” insulated OA duct to AHU return, with balancing damper - 7% outside air fraction, minimum 33% duty cycle - filtration by AHU filter - no complaints after three months

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 30 of 34

Page 31: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Hot-humid climateHot-humid climateventilation and moisture control designsventilation and moisture control designs

>45 F, >20” rain>45 F, >20” rain

• Central-fan-integrated supply with fan recycling,damper, and dehumidifier– air handler unit in conditioned space closet, placed on

platform high enough to place dehumidifier underneath– dehumidifier controlled by dehumidistat in conditioned

space– normal thermostat driven cycling of air handler, and fan

recycling, distributes both ventilation air and dry air towhole house

Building Science Consortium

November 2000

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 31 of 34

Page 32: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Central-fan-integrated supply ventilationHot-humid climate interior mechanical closet configuration

Building Science Corporation

Thermostat

Return AirFrom Interior Space

BalancingDamper

Field measurement of outsideair duct pressure, used to setbalancing damper position

Ventilation Air Intake(locate away frompollutant sources)

Wall Cap withInsect Screen

Exterior Wall

6" InsulatedOutside Air Duct(slope up for first 4')

Cooling/Dehumidifying

Apparatus

Heating/HumidifyingApparatus

Humidistat(optional)

Supply AirTo Interior Space

Central Fan(blower)

Control WiringTerminals

Air Handler Unit

AirCyclerTM

Control

40 pint/daydehumidifier

Duct extension atair handler return(open at bottom)

Floor

PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 32 of 34

© buildingscience.com

Page 33: Practical Approaches to Residential Ventilation for ... · PR-0002: Practical Approaches to Residential Ventilation for Improved Durability and Indoor Air Quality Page 28 of 34. Builder

Builder Pulte Home CorporationSubdiv ision East HamptonLocation Jacksonville, FloridaClimate hot-humidNo. Homes 2

Ventilation system• Central-fan-integrated supply with fan recycling - 6” insulated OA duct to AHU return, balancing damper - 7% outside air fraction, minimum 33% duty cycle - filtration at air handler unit - no complaints or concerns after over 6 months

Additional moisture control system• 40 pint per day dehumidifier under air handler unit, with central fanrecycling for whole-house distribution and mixing

Building Science Consortium

November 2000