Preliminary Functional Grading and Servicing Report
635 Erb Street West and 12 Westhill Drive, Waterloo
Prepared for BEL Communities Limited Partnership by IBI Group October 24, 2018
IBI GROUP PRELIMINARY FUNCTIONAL GRADING AND SERVICING REPORT Prepared for BEL Communities Limited Partnership
Table of Contents
i
1 Introduction ......................................................................................................................... 1
2 Existing Municipal Servicing ............................................................................................. 4
2.1 Sanitary .................................................................................................................... 4
2.2 Water Supply and Fire Flow..................................................................................... 4
2.3 Storm Sewer ............................................................................................................ 4
3 Proposed Site Conditions .................................................................................................. 4
3.1 Proposed Site Access .............................................................................................. 4
3.2 Proposed Site Grading ............................................................................................. 5
3.3 Proposed Servicing .................................................................................................. 5
3.3.1 Sanitary Servicing ....................................................................................... 5
3.3.2 Water Supply and Fire Flow ........................................................................ 5 3.3.3 Stormwater Management ............................................................................ 6
4 Erosion & Sediment Control .............................................................................................. 6
5 Utilities ................................................................................................................................. 6
6 Summary.............................................................................................................................. 7
Appendix A – Site Plans and Elevation Drawings ..................................................................... 1
Appendix B – Mechanical Loading Calculations ....................................................................... 2
Appendix C – Hydrant Test Results ............................................................................................ 3
IBI GROUP PRELIMINARY FUNCTIONAL GRADING AND SERVICING REPORT Prepared for BEL Communities Limited Partnership
1
1 Introduction IBI Group was retained to prepare a Preliminary Functional Grading, Servicing and Stormwater Management design report for the proposed re-development at 635 Erb Street West and 12 Westhill Drive in the City of Waterloo, Ontario. The purpose of this functional design report is to support a Zoning By-law Amendment application to permit the redevelopment of the noted lands with residential apartment buildings.
Photo #1: Site Aerial Photo (Photo Source: MGM Renderings)
The total development area is approximately 1.8 ha and is located on the south side of Erb Street, bordered by Westhill Drive to the west and Westhaven Street to the east (refer to Photo 1 for an aerial photo of the site, and Photos 2 and 3 for pictures of the existing street frontages).
The existing properties are undeveloped and vacant of any buildings and/or structures. Two thirteen-storey apartment buildings and three stacked townhouse blocks are proposed for the subject site.
Access to the development will consist of two vehicular driveways: one from Westhill Drive and the other from Westhaven Street. Both entrances will lead to a central parking areas which will be located underground and on the surface.
Refer to Appendix A for Site plans and building elevation drawings.
This report will describe the proposed functional grading, servicing and stormwater management controls for the site in order to demonstrate the feasibility of the proposed redevelopment from a site civil engineering perspective.
IBI GROUP PRELIMINARY FUNCTIONAL GRADING AND SERVICING REPORT Prepared for BEL Communities Limited Partnership
2
Photo #2: Site location looking south (Photo Source: MGM Renderings)
Photo #3: Site location, looking north (Photo Source: MGM Renderings)
IBI GROUP PRELIMINARY FUNCTIONAL GRADING AND SERVICING REPORT Prepared for BEL Communities Limited Partnership
3
Photo #4: From Westhaven Street looking west
Photo #5: From Westhill Drive looking northeast
IBI GROUP PRELIMINARY FUNCTIONAL GRADING AND SERVICING REPORT Prepared for BEL Communities Limited Partnership
4
2 Existing Municipal Servicing 2.1 Sanitary There is an existing 200mm diameter sanitary sewer on Westcroft Drive that extends to Westhaven Street. A second sanitary sewer is located on Westhill Drive which flows west toward Ira Needles Boulevard. Refer to Appendix A.
2.2 Water Supply and Fire Flow The existing property currently has a 200mm diameter watermain stub from Westhaven Street that connects to the existing 300mm diameter main line on Westhaven Street. There is an existing 400mm diameter watermain located on Westhill Drive that connects to the watermain on the north side of Erb Street.
On review of the site environs, three fire hydrants were located as follows:
An existing fire hydrant is located at the corner of Erbsville Court and Erb Street.
An existing fire hydrant is located on Westhaven Street approximately 40m from the centre of Erb Street and is connected to a 300mm diameter municipal watermain on Westhaven Street. Test results indicate an extrapolated fire flow of 399.0 lps is available.
An existing hydrant is located on Westhill Drive approximately 7m north of the proposed property on the east side of the street and is connected to a 400mm diameter municipal watermain on Westhill Drive. Test results indicate an extrapolated fire flow of 413.0 lps is available.
2.3 Storm Sewer There are no existing storm sewers present on site.
The closest existing storm manhole to the site is located on Westhaven Street and is approximately 2.5m deep. The storm sewer is 525mm in diameter and flows south towards the street dead end into a temporary 525mm diameter storm sewer.
3 Proposed Site Conditions The subject development is proposed for one 12-storey apartment building, one 13-storey apartment building, and six (6) stacked townhouse buildings. One subsurface parking level and one surface level parking lot are proposed. The site will have large areas of landscape and amenity space (30% of the site) including rooftop amenity areas on both apartment buildings. Refer to Appendix A for Site plans and elevation drawings.
3.1 Proposed Site Access The proposed site will consist of two entrances: one from Westhill Drive on the west side of the site, and the second from Westhaven Street on the east side of the site. Both entrances will lead to the centre of the property where surface and underground parking will be accessible. A maximum 10% slope to the driveway ramps has been maintained for the accesses.
Access to each apartment building will be accessible internally from the underground parking lot in addition to the entrances on the ground surface.
IBI GROUP PRELIMINARY FUNCTIONAL GRADING AND SERVICING REPORT Prepared for BEL Communities Limited Partnership
5
Pedestrian access will be provided via sidewalk to proposed Building ‘A’ from Erb Street, Westhill Drive, and the parking lot. Pedestrian access will be provided via sidewalk to proposed Building ‘B’ from Erb Street and the parking lot. Pedestrian access to the townhouses will be provided via sidewalk from the parking lot on the north side of Buildings ‘C’, ‘D’, ‘E’, ‘and ‘F’, and on the west side of Buildings ‘H’ and ‘G’. A maximum sidewalk slope of 5% will be used.
3.2 Proposed Site Grading The proposed site will consist of approximately 30% landscaped areas and amenity spaces, the remaining area will consist of the proposed buildings and parking. The building’s drainage will be contained and discharged via storm sewers. Overland flow routes will be designed to convey large storm events or in emergencies should catchbasins become blocked.
Grading of the site and building access will ensure barrier free walkways to main entrance doors utilizing minimum slopes of 0.5% and maximum of 5%. Vehicular access routes will have a minimum slope of 0.5% and an ideal maximum of 5%, with an absolute maximum on ramps of 10%. Landscape areas will have minimum slopes of 2% and maximum of 33% (3:1).
3.3 Proposed Servicing
3.3.1 Sanitary Servicing Based on estimated sanitary loads for the proposed building, the proposed developments anticipated maximum drainage rate and MOE standards, the peak flow rates are:
Building ‘A’: 0.877 lps; Building ‘B’: 1.241 lps; Townhouses: 0.336 lps.
Building ‘A’ will be serviced from Westhill Drive via a 200mm sanitary sewer (min slope = 0.5%), while Building ‘B’ and the townhouses will be serviced from Westhaven Street via a 200mm sanitary sewer (min slope = 0.5%), and 100mm diameter laterals (min slope = 2.0%).
Sewage on Westhaven Street flows eastward from the subject site towards Westcroft Drive in a 200mm diameter sewer. Sewage on Westhill Drive flows westward from the subject site towards Ira Needles Boulevard in a 200mm diameter sewer. Given the sites’ relatively low peak flow compared to the municipal sewer capacity, we anticipate that capacity will not be an issue, however, the City will need to confirm this assumption as they are familiar with their sanitary collection system.
3.3.2 Water Supply and Fire Flow The proposed site will be serviced via the municipal water supply system on both Westhaven Street and Westhill Drive as follows:
Building ‘A’: A 150mm diameter service pipe that connects to the existing 400mm diameter municipal watermain on Westhill Drive will be provided.
Building ‘B’: A 150mm diameter service pipe will be provided. This pipe will connect to the existing 200mm diameter stub off Westhaven Street.
Townhouses: The existing 200mm diameter stub off Westhaven Street will be extended into the private road fronting the townhouse buildings. Individual 100mm service pipe will be provided to each townhouse building from this new watermain.
Based on the results of the hydrant flow testing conducted on existing municipal hydrants surrounding the development site, we believe the existing municipal water system has adequate capacity to provide the domestic and fire protection requirements for the proposed development.
IBI GROUP PRELIMINARY FUNCTIONAL GRADING AND SERVICING REPORT Prepared for BEL Communities Limited Partnership
6
3.3.3 Stormwater Management The stormwater management criterion for this development is based on the requirements of the City of Waterloo and Region of Waterloo. The requirements include stormwater quantity control, stormwater quality control, and infiltration to ground.
On-site runoff will be conveyed via surface grading and swales, and collected in catchbasins located throughout the site. These catchbasins will be connected to storm sewers which will be routed to the existing sewer on Westhaven Street via a 525mm diameter storm sewer. The Westhaven Street storm sewer then routes runoff to an existing stormwater management pond to the southeast of the property. This existing SWM pond is part of the Gies-Westale Subdivision and was sized to receive flows from 1.26 ha of the proposed development, based on a runoff coefficient C of 0.70.
On-site infiltration of rooftop runoff will be explored at the detailed design stage and if site soils and groundwater conditions permit, infiltration will be incorporated into the design. No existing external areas drain onto the site. Refer to Site Grading and Servicing Plan in Appendix A.
Refer to the Preliminary Stormwater Management Design Brief revised October 17, 2018 for further details on stormwater management and control.
4 Erosion & Sediment Control During construction, erosion and sediment control measures will be required. Details of this control will be provided in detail during the detailed engineering design, and will include (as a minimum) the following:
Silt fence erected around site perimeter before any work begins on the site to protect adjacent areas from migration of sediment in overland flow.
A “mud mat” installed at the construction entrance(s) to the site to minimize the amount of sediment transported off site via construction vehicles;
All disturbed areas should be stabilized as quickly as possible to minimize the opportunity for erosion.
5 Utilities The various utilities (i.e., Hydro, Gas, and Communications) all have existing facilities on the surrounding municipal streets. Servicing of the development by the various utilities will be provided by the extension of these facilities. It is anticipated that each of these utilities will, as required, identify their specific requirements through the standard application circulation, review and design process.
IBI GROUP PRELIMINARY FUNCTIONAL GRADING AND SERVICING REPORT Prepared for BEL Communities Limited Partnership
7
6 Summary This Report demonstrates that the proposed development at 635 Erb Street West and 12 Westhill Drive in the City of Waterloo, Ontario can be designed and constructed from a grading and municipal servicing perspective in accordance with typical municipal standards.
We trust the foregoing is satisfactory to support the rezoning application. Should there be any questions or if further information is required, please do not hesitate to contact the undersigned.
All of which is respectfully submitted.
Yours truly
IBI GROUP
John Perks, MBA, P.Eng. Julianna Arcese, P. Eng. Associate Director Project Engineer
IBI GROUP PRELIMINARY FUNCTIONAL GRADING AND SERVICING REPORT Prepared for BEL Communities Limited Partnership
Appendix A – Site Plans and Elevation Drawings
UP
UP UP
ERB STREET (REGIONAL ROAD 9)
WESTHILL DRIVE
WES
THAV
EN S
TREE
T
BUILDING ABUILDING B
5000
SITE ENTRY
SITE ENTRY
EXIT
BUILDING C BUILDING D BUILDING E
DROP OFF AREA
DROP O
FF AREA
DROP CURB
CONC. SIDEWALK
EXIT FROM BASEMENT
5.0m SETBACK
5.0m S
ETBA
CK
7.5m SETBAC
K
5.0m SETBACK
5.0m SETBACK
5.0m SETBAC
K
5.0m SETBACK
TRANSFORMER
TRANSFORMER
EXIT
EXIT FROM BASEMENT
EX. FH
BUILDING F
BU
ILD
ING
G
BUIL
DIN
G H
LOADING & MOVINGENTRY
BUILDING B ENTRANCE
BUILDING A ENTRANCE
BUILDING A ENTRANCE
BUILDING B ENTRANCE
MA
IL B
OX
EXIT
U/G GARAGE ENTRY
U/G GARAGE ENTRY
LOADING & MOVING
ENTRY
LIN
E O
F B
AS
EM
EN
T
5148
6749
521050
87
6100
6100
MO
LOK
5500
6100
1604
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2750
6650
5500
5500
6100
5500
5500
6100
5500
5500
6100
5500
5500
6650
3909
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
6100
5500
3900 5200 5200 2800 2800 2800 2800 2800 1734
5500 6100 2800 2800 2800 2800 2800 4434
5200 5200 3900 2800 2800 2800 2800 3900 5800
5500 6100 5500 1000 5500 6100 5500
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
6486
5500
2800 2800 2800 2800 2800 2800 2800 2800 5200 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 6175
2800
2800
6700
5500 8069
6100
1170
371
528
0028
0028
0028
0028
0028
0067
000
2800
6700
6094 5500
3000
1217
8
5224
5276
5183
5128
5124
5187
13779
6628
5062
5069
6706
EXIT
2280
8
EXIT FROM BASEMENT
B.F. RAMP
18001550 15501800
RA
MP
UP
@
10%
RAMP
UP@ 10%
RAMP
DN@ 12%
MAX
RA
MP
UP
@
12%
SLO
PE
UP
@
5%
DETAILS OF DEVELOPMENT
SETB
ACKS
Front Yard (m)Rear Yard (m)Ext. Side Yard (m)Int. Side Yard (m)
5.07.53.03.0
GROSS LOT AREA (m²)
BUILDING AREA (m²)
BUILDING COVERAGE(%)
BUILDING HEIGHT (m)
DENSITY (Unit/ha) NUMBER OF UNITS
NUMBER OF STOREYS GARBAGE ENCLOSURE
LANDSCAPE AREA (m²)
PARKING 1.25 SPACE / UNIT
BIKE RACKS 2/UNITTOTAL BEDROOMSMIN. FRONTAGE (m)
MIN. FLANKAGE YARD (m)
B.F. PARKING SPACES
LANDSCAPE AREA (%)
NET LOT AREA (m²)
AREA OF ROW & DLT (m²)
ZONING
PROVISION REQUIRED PROVIDED
DEN
SITY
Combination SY (m) 10.0Low rise residential (m)
MR-12
5.0
5.05.05.0
17998.865
4550
25.3635 ERB STREET WATERLOO ON
N/A5.0 5.0
200
36 4012 12
359 335n/a 559(TBC)
419 413
11 11
680 TBC
INDOOR & OUTDOOR
540030 TBC
TBC
17998.865
N/A187
10.0
5.07.5 & 1/2H
is a member of the IBI Group of companies
DATE:
ISSUE
SHEET TITLE
PROJECT
SCALE:
CHKD' BY:
DRAWN BY:
PROJECT NO:
SHEET NUMBER
PRIME CONSULTANT
SUB CONSULTANT
SEAL
CLIENT
COPYRIGHT:
ISSUES
ibigroup.com
Any reproduction or distribution for any purpose other than authorized by IBI Group is forbidden. Written dimensions shall have precedence over scaled
dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and IBI Group shall be informed of any variations from the
dimensions and conditions shown on the drawing. Shop drawings shall be submitted to IBI Group for general conformance before proceeding with
fabrication.
IBI Group Architects (Canada) Inc.
APR.25, 2018
As indicated
SITE PLAN
102225
LY
12/07/16
A0.1
BEL COMMUNITIESPARTNERSHIP LIMITED
JD
635 ERB STREET W., WATERLOO ON
BEL COMMUNITIESPARTNERSHIP LTD.
101-410 ALBERT STREETWATERLOO ONtel (519) 585-2255 fax (519) 585-2269
IBI GROUP
SCALE: 1 : 300A0.1SITE PLAN1
SUBJECT SITE
NO. ISSUANCE BY DATE2 Issued for Preconsultation LY APR 25, 20181 Issued for ZBA&OPA LY OCT 20, 2017
DN
5.0m SETBACK
5.0m S
ETBA
CK
7.5m SETBAC
K
5.0m SETBACK
5.0m SETBACK
5.0m SETBAC
K
5.0m SETBACK
ERB STREET (REGIONAL ROAD 9)
WESTCROFT DRIVE
WES
THAV
EN S
TREE
T
SITE ENTRY
BUILDING B ENTRANCE
BUILDING A ENTRANCE
BUILDING A ENTRANCE
EXIT
EXIT
DROP OFF AREA
DROP O
FF AREA
DROP CURB
CONC. SIDEWALK
BUILDING B ENTRANCE
EXIT
EXIT
EX. FH
RA
MP
UP
@
10%
TRANSFORMER
RAMP
UP@ 10%
RAMP
DN@ 12%
MAX
RA
MP
UP
@
12%
SLO
PE
UP
@
5%
MA
IL B
OX
TRANSFORMER
UNITTYPE B
UNITTYPE A
(BF)
UNITTYPE B
UNITTYPE B
LOBBY
VEST
VEST
OFFICE
UNITTYPE A
UNITTYPE A
UNITTYPE B
UNITTYPE A
(BF)
UNITTYPE A
UNITTYPE A
MO
LOK
5500
6100
1604
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2750
6650
5500
5500
6100
5500
5500
6100
5500
5500
6100
5500
5500
6650
3909
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
6100
5500
5500 6100 2800 2800 2800 2800 2800 4434
5500 6100 5500 1000 5500 6100 5650
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
2800
6486
5500
2800 2800 2800 2800 2800 2800 2800 2800 5200 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800 2800
2800
2800
6700
5500 8069
6100
1170
371
528
0028
0028
0028
0028
0028
0028
0039
0028
00
5200 5200 3900 2800 2800 2800 2800 1500 8200
U/G GARAGE ENTRY
SITE ENTRY
UNITTYPE B
UNITTYPE B
UNITTYPE A
UNITTYPE B
UNITTYPE A
UNITTYPE B
UNITTYPE A
UNITTYPE A
UNITTYPE B
UNITTYPE A
UNITTYPE A
BUILDING C BUILDING D BUILDING E BUILDING F
BUIL
DIN
G G
BUIL
DIN
G H
U/G GARAGE ENTRY
LOBBY
VEST
MAILVEST
OFFICE6094 5500
is a member of the IBI Group of companies
DATE:
ISSUE
SHEET TITLE
PROJECT
SCALE:
CHKD' BY:
DRAWN BY:
PROJECT NO:
SHEET NUMBER
PRIME CONSULTANT
SUB CONSULTANT
SEAL
CLIENT
COPYRIGHT:
ISSUES
ibigroup.com
Any reproduction or distribution for any purpose other than authorized by IBI Group is forbidden. Written dimensions shall have precedence over scaled
dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and IBI Group shall be informed of any variations from the
dimensions and conditions shown on the drawing. Shop drawings shall be submitted to IBI Group for general conformance before proceeding with
fabrication.
IBI Group Architects (Canada) Inc.
APR.25, 2018
1 : 300
GROUND FLOORPLAN
102225
Author
04/24/18
A0.2
BEL COMMUNITIESPARTNERSHIP LIMITED
Checker
635 ERB STREET W., WATERLOO ON
BEL COMMUNITIESPARTNERSHIP LTD.
101-410 ALBERT STREETWATERLOO ONtel (519) 585-2255 fax (519) 585-2269
IBI GROUP
SCALE: 1 : 300A0.2GROUND FLOOR PLAN1
NO. ISSUANCE BY DATE2 Issued for Preconsultation LY APR 25, 20181 Issued for ZBA&OPA LY OCT 20, 2017
5.0m SETBACK
5.0m S
ETBA
CK
7.5m SETBAC
K
5.0m SETBACK
5.0m SETBACK
5.0m SETBAC
K
5.0m SETBACK
BASEMENT ENTRY
LOADING & MOVINGENTRY
TRANSFORMER
U/G GARAGE ENTRY
711 5200 874 3900 2800600
3900 3900 1200 2800 2800 2800600
2800 2800 1200 3000 4822 2800 3000
6193 5500 5500 6100 5500 5500 6100 5500
5500 6150 5500 5500 6100 5500 5500 6100 5500 165600
5500 6100 5500 5500 6100 5500 5500 6100 5500 2123
3167 5500 6100 5500 5500 6100 5500
2800 2800 2800600
2800 2800 2800600
3000 748 3000600
2800 2800 2800600
3000 2911 600 3000 2800 3042 6002800 2800 2800600
3000 3000
5500
6700
2800
3000
650
2800
2800
2800
600
3000
2800
2800
600
2800
2800
2800
600
3000
2800
2800
600
2800
2800
2800
774
2800
2800
2800
1848
6100
5500
UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT
GYM THEATRE
RECREATION LOCKER
GARBAGE
BIKE
MOVINGROOM
TRANSFORMER
THEATRE GYM LOCKER
MOVINGROOMBIKE
GARBAGE
UNIT UNIT UNIT UNIT
UNIT
UNIT
UNIT
UNIT
UNIT
UNIT
UNIT
UNIT
200
2800
2800
2800
600 28
0028
0030
00
5500
6700
2800
3000
650
2800
2800
2800
600
3000
2800
2800
600
2800
2800
2800
600
3000
2800
3400
2800
2800
2800
1122
255
0049
2
2800
3000
650
2800
2800
2800
600
3000
2800
2800
600
2800
2800
2800
600
3000
2800
2800
3400
2800
2800
600
2800
2800
2800
8122
5500
250
5500
8340
2800
600 28
0028
0060
0 2800
2800
600 28
0028
0060
0 2800
3000
2800
600
3000
2800
2800
700
2800
2800
2800
600
3000
3000
600 28
00
3000
2800
2800
600
3000
1950
5500
6240
5500
2800
2800
600 28
0028
0060
0 2800
2800
600 28
0030
00
5500
2800
2800
600 28
0028
0060
0 2800
2800
600 28
0037
0029
0028
0028
0028
0060
0 2800
2800
2800
6700
5500
1104
2800
2800
600 28
0028
0060
0 2800
2800
1000
028
0028
0028
0060
0 2800
2800
2800
6793
5500
2800
2800
2800
3900
5500 8069
6100
5500 6100 5500 5500 6100 5500 5500 6100 5500 2123
5500 7848 2800 2800 911 2800 6642 2800 2800 2800 9300
2800
067
0028
0028
0028
0028
0028
0028
0012
418
1167 6094 5500
3000 3000
5034 3900 6002800 2800 2800
8934
6193
BUILDING C BUILDING D BUILDING E BUILDING F
BU
ILD
ING
G
BUIL
DIN
G H
MOVINGLOADING
ENTRY MO
LOK
RAMP UP@ 12% MAX
RA
MP
UP
@
12%
SERVICE
VE
ST. VE
ST.
VE
ST.
VE
ST.
SERVICE
VEST.
VE
ST
EXIT
VEST.
EXITEXIT
EXIT
2015
EXIT VEST.
VEST.
VEST.VEST.
R 6100
is a member of the IBI Group of companies
DATE:
ISSUE
SHEET TITLE
PROJECT
SCALE:
CHKD' BY:
DRAWN BY:
PROJECT NO:
SHEET NUMBER
PRIME CONSULTANT
SUB CONSULTANT
SEAL
CLIENT
COPYRIGHT:
ISSUES
ibigroup.com
Any reproduction or distribution for any purpose other than authorized by IBI Group is forbidden. Written dimensions shall have precedence over scaled
dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and IBI Group shall be informed of any variations from the
dimensions and conditions shown on the drawing. Shop drawings shall be submitted to IBI Group for general conformance before proceeding with
fabrication.
IBI Group Architects (Canada) Inc.
APR.25, 2018
1 : 300
BASEMENT PLAN
102225
Author
08/09/17
A0.3
BEL COMMUNITIESPARTNERSHIP LIMITED
Checker
635 ERB STREET W., WATERLOO ON
BEL COMMUNITIESPARTNERSHIP LTD.
101-410 ALBERT STREETWATERLOO ONtel (519) 585-2255 fax (519) 585-2269
IBI GROUP
SCALE: 1 : 300A0.3BASEMENT PLAN1
NO. ISSUANCE BY DATE2 Issued for Preconsultation LY APR 25, 20181 Issued for ZBA&OPA LY OCT 20, 2017
DATE:
PROJECT NO:
PROJECT
SCALE:
CHKD' BY:DRAWN BY:
SHEET NUMBER
ISSUES
101 - 410 Albert StreetWaterloo ON N2L 3V3 Canadatel 519 585 2255 fax 519 585 2269ibigroup.com
IBI GROUP ARCHITECTS
KEY PLAN
SHEET TITLE
# DATE BY REVISIONS
THIS DRAWING, AS AN INSTRUMENT OF SERVICE, IS THE PROPERTY OF THE ARCHITECT/ENGINEER AND MAY NOT BE REPRODUCED WITHOUT THEIR PERMISSION AND UNLESS THE REPRODUCTION CARRIES THEIR NAME. ALL DESIGN AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR THE USE ON THE SPECIFIED PROJECT ONLY AND SHALL NOT BE USED OTHERWISE WITHOUT WRITTEN PERMISSION OF THE ARCHITECT/ENGINEER.
WRITTEN DIMENSIONS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND OF ANY VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN ON THE DRAWING AND REPORT ANY DISCREPANCIES TO THE ARCHITECT/ENGINEER PRIOR TO PROCEEDING WITH THE WORK.
SHOP DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER FOR APPROVAL BEFORE PROCEEDING WITH FABRICATION.
THESE DRAWINGS SHALL NOT BE SCALED.
ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL OTHER RELATED DOCUMENTS AND SPECIFICATIONS.
1 : 300
M.M
12/07/16
A0.35102225
BEL COMMUNITIESPARTNERSHIP LIMITED
Y.L
635 ERB STREET W., WATERLOO ON
FLOOR PLANS
1 OCT 20, 2017 LY ISSUED FOR ZBA & OPA - 1st
SCALE: 1 : 300A0.35LOWER FLOOR PLANS1 BUILDING A - 2-10th FLOOR, BUILDING B - 2-4th FLOOR
UP
UPSTAIR B
ELEV
STAI
R A
is a member of the IBI Group of companies
DATE:
ISSUE
SHEET TITLE
PROJECT
SCALE:
CHKD' BY:
DRAWN BY:
PROJECT NO:
SHEET NUMBER
PRIME CONSULTANT
SUB CONSULTANT
SEAL
CLIENT
COPYRIGHT:
ISSUES
ibigroup.com
Any reproduction or distribution for any purpose other than authorized by IBI Group is forbidden. Written dimensions shall have precedence over scaled
dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and IBI Group shall be informed of any variations from the
dimensions and conditions shown on the drawing. Shop drawings shall be submitted to IBI Group for general conformance before proceeding with
fabrication.
IBI Group Architects (Canada) Inc.
APR.25, 2018
1 : 300
FLOOR PLANS
102225
Author
04/24/18
A0.40
BEL COMMUNITIESPARTNERSHIP LIMITED
Checker
635 ERB STREET W., WATERLOO ON
BEL COMMUNITIESPARTNERSHIP LTD.
101-410 ALBERT STREETWATERLOO ONtel (519) 585-2255 fax (519) 585-2269
IBI GROUP
SCALE: 1 : 300A0.40TYPICAL FLOOR PLAN1
NO. ISSUANCE BY DATE2 Issued for Preconsultation LY APR 25, 20181 Issued for ZBA&OPA LY OCT 20, 2017
BUILDING A - 2-10th FLOOR, BUILDING B - 5-9th FLOOR
UP
UP
UPUP
UP
UP
DATE:
PROJECT NO:
PROJECT
SCALE:
CHKD' BY:DRAWN BY:
SHEET NUMBER
ISSUES
101 - 410 Albert StreetWaterloo ON N2L 3V3 Canadatel 519 585 2255 fax 519 585 2269ibigroup.com
IBI GROUP ARCHITECTS
KEY PLAN
SHEET TITLE
# DATE BY REVISIONS
THIS DRAWING, AS AN INSTRUMENT OF SERVICE, IS THE PROPERTY OF THE ARCHITECT/ENGINEER AND MAY NOT BE REPRODUCED WITHOUT THEIR PERMISSION AND UNLESS THE REPRODUCTION CARRIES THEIR NAME. ALL DESIGN AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR THE USE ON THE SPECIFIED PROJECT ONLY AND SHALL NOT BE USED OTHERWISE WITHOUT WRITTEN PERMISSION OF THE ARCHITECT/ENGINEER.
WRITTEN DIMENSIONS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND OF ANY VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN ON THE DRAWING AND REPORT ANY DISCREPANCIES TO THE ARCHITECT/ENGINEER PRIOR TO PROCEEDING WITH THE WORK.
SHOP DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER FOR APPROVAL BEFORE PROCEEDING WITH FABRICATION.
THESE DRAWINGS SHALL NOT BE SCALED.
ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL OTHER RELATED DOCUMENTS AND SPECIFICATIONS.
1 : 300
M.M
12/07/16
A0.42102225
BEL COMMUNITIESPARTNERSHIP LIMITED
Y.L
635 ERB STREET W., WATERLOO ON
FLOOR PLANS- BUILDING A
1 OCT 20, 2017 LY ISSUED FOR ZBA & OPA - 1st
SCALE: 1 : 300A0.42TOP FLOOR PLANS1 BUILDING A - 11-13th FLOOR, BUILDING B - 10-12th FLOOR
is a member of the IBI Group of companies
DATE:
ISSUE
SHEET TITLE
PROJECT
SCALE:
CHKD' BY:
DRAWN BY:
PROJECT NO:
SHEET NUMBER
PRIME CONSULTANT
SUB CONSULTANT
SEAL
CLIENT
COPYRIGHT:
ISSUES
ibigroup.com
Any reproduction or distribution for any purpose other than authorized by IBI Group is forbidden. Written dimensions shall have precedence over scaled
dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and IBI Group shall be informed of any variations from the
dimensions and conditions shown on the drawing. Shop drawings shall be submitted to IBI Group for general conformance before proceeding with
fabrication.
IBI Group Architects (Canada) Inc.
APR.25, 2018
BUILDING MASSINGSTUDY
102225
Author
04/24/18
A0.55
BEL COMMUNITIESPARTNERSHIP LIMITED
Checker
635 ERB STREET W., WATERLOO ON
BEL COMMUNITIESPARTNERSHIP LTD.
101-410 ALBERT STREETWATERLOO ONtel (519) 585-2255 fax (519) 585-2269
IBI GROUP
SCALE:A0.55VIEW FROM SOUTHEAST1
SCALE:A0.55VIEW FROM NORTHEAST2
SCALE:A0.55VIEW FROM SOUTHWEST3
SCALE:A0.55VIEW FROM NORTHWEST4
NO. ISSUANCE BY DATE1 Issued for Preconsultation LY APR 25, 2018
IBI GROUP PRELIMINARY FUNCTIONAL GRADING AND SERVICING REPORT Prepared for BEL Communities Limited Partnership
Appendix B – Mechanical Loading Calculations
Project:
Location:
Date:
123
10" @ 1% slope
10" @ 1% slope
4"
Fire Flow: 392 USGPM
1861.5
1558
Sept 14'17
124Kitchen Sink
11226187Washroom Group
Total Fixture Units
(FU)
Fixture Units Each
(FU)
Number of Fixture
TypeFixture Type
2502125
Sanitary Drain:
TOTAL (FU):
SITE SERVICE CALCULATIONS
Number of Suites:
Sanitary Load Calculation
Building Information
Washing Machines
635 Erb St - Building A
Waterloo
Storm Drain:
Storm Load
Water Load Calculation
Fixture TypeNumber of Fixture
Type
Total Fixture Units
(FU)
Washroom Group 187 6 1122
*For roof drains of Building A only, this does
not include any site or terrace drains.
1620
290
Domestic Water Service Line:
Fire Flow Calculation
TOTAL (GPM):
TOTAL (FU):
Kitchen Sink 124 2 248
Washing Machines 125 2 250
Fixture Units Each
(FU)
Site Services Calculations 635 Erb St - Building A 1 of 1
Project:
Location:
Date:
174
10" @ 1% slope
10" @ 1% Slope
6"
Fire Flow: 392 USGPM
2280
355
Domestic Water Service Line:
Fire Flow Calculation
TOTAL (GPM):
TOTAL (FU):
Kitchen Sink 175 2 350
Washing Machines 176 2 352
Fixture Units Each
(FU)
Total Fixture Units
(FU)
Washroom Group 263 6 1578
Storm Drain:
Storm Load
Water Load Calculation
Fixture TypeNumber of Fixture
Type
2176
Sanitary Drain:
TOTAL (FU):
SITE SERVICE CALCULATIONS
Number of Suites:
Sanitary Load Calculation
Building Information
Washing Machines
635 Erb St - Building B
Waterloo
*For roof drains of Building B only, this does
not include any site or terrace drains.
262.51.5
2192.5
Sept 14'17
175Kitchen Sink
15786263Washroom Group
Total Fixture Units
(FU)
Fixture Units Each
(FU)
Number of Fixture
TypeFixture Type
352
Site Services Calculations 635 Erb St - Building B 1 of 1
Project:
Location:
Date:
38
8" @ 1% slope
8" @ 1.5% slope
4"
Fire Flow: 392 USGPM
*For roof drains of Townhouses only, this
does not include any site or terrace drains.
384
692
172
Domestic Water Service Line:
Fire Flow Calculation
TOTAL (GPM):
TOTAL (FU):
Kitchen Sink 38 2 76
Washing Machines 38 2 76
Fixture Units Each
(FU)
Total Fixture Units
(FU)
Powder Room 26 6 156
Washroom Group 64 6 384
Storm Drain:
Storm Load
Water Load Calculation
Fixture TypeNumber of Fixture
Type
38
Sanitary Drain:
TOTAL (FU):
SITE SERVICE CALCULATIONS
Number of Suites:
Sanitary Load Calculation
Building Information
Washing Machines
635 Erb St - Town houses
Waterloo
Washroom Group 64 6
571.5
660
Sept 14'17
38Kitchen Sink
1435.526Powder Room
Total Fixture Units
(FU)
Fixture Units Each
(FU)
Number of Fixture
TypeFixture Type
762
Site Services Calculations 635 Erb St - Town houses 1 of 1
IBI GROUP PRELIMINARY FUNCTIONAL GRADING AND SERVICING REPORT Prepared for BEL Communities Limited Partnership
Appendix C – Hydrant Test Results
Hydrant Flow Test - WO# 21294Westhaven Street & Westcroft DriveWaterloo
Static Hydrant at **End of Westhaven St.**Flowing Hydrant at**Corner of Westhaven St. & Westcroft Drive**Static Pressure (Psi) Pitot Reading 1 52 # of Outlets Flowed 1 1
70 Outlet Size 1 2.5 # of Outlets Flowed 2 2Residual Pressure 1 (Psi) Pitot Reading 2 38+34 # of Outlets Flowed 3 0
68 Outlet Size 2 2.5 Graph Data:Residual Pressure 2 (Psi) Pitot Reading 3 Pressure Values (y-axis) Flow Values (x-axis)
64 Outlet Size 3 70 0Residual Pressure 3 (Psi) Flow 1 Calculated 68 1210
1210.38 64 2013Flow 2 Calculated
2012.75 Time of Test :Co efficient value Flow 3 Calculated 27-Oct-17
0.9 0.00 Performed by: L.M
10:00am
636465666768697071
0 500 1000 1500 2000 2500
Pres
sure
(Psi
)
Flow (USGPM)
Water Graph
70 psi
64psi @ 2013 USGPM
68psi @ 1210USGPM
Hydrant Flow Test - WO# 21294Westhill DriveWaterloo
Static Hydrant at **7 Westhill Drive**Flowing Hydrant at**51 Westhill Drive**Static Pressure (Psi) Pitot Reading 1 47 # of Outlets Flowed 1 1
62 Outlet Size 1 2.5 # of Outlets Flowed 2 2Residual Pressure 1 (Psi) Pitot Reading 2 30+30 # of Outlets Flowed 3 0
60 Outlet Size 2 2.5 Graph Data:Residual Pressure 2 (Psi) Pitot Reading 3 Pressure Values (y-axis) Flow Values (x-axis)
58 Outlet Size 3 62 0Residual Pressure 3 (Psi) Flow 1 Calculated 60 1151
1150.72 58 1838Flow 2 Calculated
1838.09 Time of Test :Co efficient value Flow 3 Calculated 27-Oct-17
0.9 0.00 Performed by: L.M
10:30am
57.558
58.559
59.560
60.561
61.562
62.5
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Pres
sure
(Psi
)
Flow (USGPM)
Water Graph
62 psi
58psi @ 1838 USGPM
60psi @ 1151USGPM