43
® PRESSURE DROP CHARTS Armstrong Pumps Inc. 93 East Avenue North Tonawanda, New York U.S.A. 14120-6594 Tel: (716) 693-8813 Fax: (716) 693-8970 S.A. Armstrong Limited 23 Bertrand Avenue Toronto, Ontario Canada, M1L 2P3 Tel: (416) 755-2291 Fax: (416) 759-9101 Armstrong Pumps Limited Peartree Road, Stanway Colchester, Essex United Kingdom, CO3 0LP Tel: +44 (0) 1206 579491 Fax: +44 (0) 1206 760532 Armstrong Darling 9001 De L’Innovation, Suite 200 Montreal, Quebec Canada, H1J 2X9 Tel: (514) 352-2424 Fax: (514) 352-2425 © S.A. Armstrong Limited 2003 www.armstrongpumps.com 1 10 100 1000 10000 60000 VA-14 VA-16 VA-18 VA-20 VA-22 VA-24 FILE NO: 37.630 DATE: Sept. 5, 2003 SUPERSEDES: New DATE: New Vortex Air Separator - Model VA (less Strainer) Pressure drop for Models VA-2 to VA-12 Flow Rate - USgpm Pressure Drop - ft. of water Pressure drop for Models VA-14 to VA-24 Flow Rate - USgpm Pressure Drop - ft. of water

Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Embed Size (px)

Citation preview

Page 1: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

®

PRESSURE DROP CHARTS

Armstrong Pumps Inc. 93 East Avenue North Tonawanda, New York U.S.A. 14120-6594 Tel: (716) 693-8813 Fax: (716) 693-8970

S.A. Armstrong Limited 23 Bertrand Avenue Toronto, Ontario Canada, M1L 2P3 Tel: (416) 755-2291 Fax: (416) 759-9101

Armstrong Pumps Limited Peartree Road, Stanway

Colchester, Essex United Kingdom, CO3 0LP Tel: +44 (0) 1206 579491 Fax: +44 (0) 1206 760532

Armstrong Darling 9001 De L’Innovation, Suite 200

Montreal, Quebec Canada, H1J 2X9

Tel: (514) 352-2424 Fax: (514) 352-2425

© S.A. Armstrong Limited 2003 www.armstrongpumps.com

1

10

100

1000 10000 60000

Flow Rate - USgpm

Pre

ssu

re

Dro

p -

ft.

of

wat

er

VA-1

4

VA-1

6VA

-18

VA-2

0VA-2

2VA-2

4

FILE NO: 37.630 DATE: Sept. 5, 2003 SUPERSEDES: New DATE: New

Vortex Air Separator - Model VA (less Strainer)

Pressure drop for Models VA-2 to VA-12

Flow Rate - USgpm

Pres

sure

Dro

p - f

t. of

wat

er

Pressure drop for Models VA-14 to VA-24

Flow Rate - USgpm

Pres

sure

Dro

p - f

t. of

wat

er

Page 2: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

SUBMITTAL JOB:

ENGINEER: CONTRACTOR:

REPRESENTATIVE:

ORDER NO: SUBMITTED BY: APPROVED BY:

DATE: DATE: DATE:

S. A. Armstrong Limited 23 Bertrand Avenue Toronto, Ontario Canada, M1L 2P3 T: 416-755-2291 F: 416-759-9101

Armstrong Pumps Inc. 93 East Avenue North Tonawanda, New York U.S.A. 14120-6594 T: 716-693-8813 F: 716-693-8970

Armstrong Integrated Limited Wenlock Way Manchester United Kingdom, M12 5JL T: +44 (0) 8444 145 145 F: +44 (0) 8444 145 146 © S.A. Armstrong Limited 2011

For Armstrong locations worldwide, please visit www.armstrongintegrated.com

technical data

Max. Working Temperature 375°F (190°C)

Connection Type 150# Flanged ansi (rfso)

Max. Working Pressure 4" to 6" Models: 160 psi (1103 kPa) 8" to 12" Models: 165 psi (1140 kPa)

FILE NO: 37.621 DATE: Sep. 08, 2011 SUPERSEDES: 37.621 DATE: Dec. 18, 2007

Vortex Air Separators - Models VA / VAS: 4” to 12”

MODEL NO. ORDERED: _____________ QTY.: ________

TAG NO.: ________________

materials of construction

Shell 4" to 6" Models: Cast Iron 8" to 12" Models: Fabricated Steel

Strainer Steel Mesh (1/4” x 3/4”) Gasket Non-Asbestos

typical specification

Furnish & install an Armstrong Vortex® Air Separator, Model ___ va or Model ___ vas (with strainer) with flanged tangential connections as shown on plans. The unit shall be designed and built in accordance with the latest revisions of asme Pressure Vessel Code, Section VIII, Division 1. A blowdown connection is provided for routine cleaning of the unit.

All models designed and built to asme Pressure Vessel Code, Section VIII, Division 1.

model

dimension inches (mm)

max. flow rate in

usgpm (l/s) for line

velocity ft/s (m/s)

weight

lbs. (kg)

strainer

screen free

area

less

strainer

with

strainer a b c d e f h j k n

4 6 8 va vas

sq. in. (sq.

cm) (1.22) (1.83) (2.44)

va-4 vas-4 4.00 (102)

1.50 (38)

9.50(241)

18.00 (457)

2.25 (57)

6.80 (173)

22.25(565)

10.75 (273)

16.00 (406)

9.00 (229)

160 (10.1)

240 (15.1)

320 (20.2)

121 (55)

151 (69)

76 (490)

va-5 vas-5 5.00 (127)

11.00 (279)

20.00(508)

2.88 (73)

8.69 (221)

28 (711)

12.75 (324)

19.00 (483)

10.00 (254)

250 (9.84)

375 (14.8)

500 (31.6)

173 (79)

207 (94)

124 (800)

va-6 vas-6 6.00 (152)

1.50 (38)

12.50 (318)

24.00 (610)

4.00 (102)

9.85 (250)

32.24 (819)

16.00 (406)

22.00 (558)

12.00 (305)

360 (22.7)

540 (34.1)

720 (45.4)

264 (120)

306 (139)

183 (1181)

va-8 vas-8 8.00 (203)

2.00 (51)

16.00 (406)

28.00 (711)

5.00 (127)

12.81 (310)

41.25 (1048)

20.00 (508)

26.00 (660)

14.00 (356)

630 (39.8)

940 (59.3)

1250 (78.9)

228 (103)

332 (151)

302 (1949)

va-10 vas-10 10.00(254)

2.00 (51)

20.00 (508)

32.00 (813)

5.75 (146)

15.00 (381)

49.50 (1257)

24.00(610)

29.00 (737)

16.00 (406)

990 (62.5)

1500 (94.6)

1980 (124.9)

390 (177)

547 (248)

452 (2916)

va-12 vas-12 12.00(305)

2.00 (51)

26.00 (660)

38.00 (965)

7.75 (197)

17.56 (446)

61.25 (1556)

30.00(762)

36.00 (914)

19.00(483)

1400 (88.3)

2100 (132.5)

2800 (176.7)

609(276)

856 (388)

679 (4381)

1.50 (38)

model vas model va

1.5” NPT(SQ. HD. PIPE PLUG)1” NPT FOR va8, 10, 12

B NPT AIR OUTLET

outlet

inlet

A

N

JF

CH

1.5” NPT(SQ. HD. PIPE PLUG)1” NPT FOR vas8, 10, 12

*K is distance required to remove strainer.

B NPT AIR OUTLET

BLIND FLG.

A

N

J F

C

K

H

outlet

inlet

jbivens
Typewritten Text
ELK CREEK AS-1
jbivens
Typewritten Text
jbivens
Rectangle
Page 3: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

BMK SERIESTECHNICAL DATA SHEET

Benchmark 750 - 6000 Condensing Hydronic Boilers

FEATURES:• NaturalGas,Propane,orDualFuel(modeldependant)• 20:1TurndownRatio(5%)dependingoncapacity• OxygenLevel(O2)MonitoringStandard• StainlessSteelFireTubeheatexchanger• CapableofvariableprimaryflowInstallations• NOxEmissionscapableof9PPMorless@allfiring

rates*dependingoncapacity• CompactFootprint• PreciseTemperatureControl• On-boardBoilerSequencingTechnology(BST)

TheAERCOBenchmark(BMK)WaterBoilerisdesignedforcondensingapplication in any closed loophydronic system. It delivers unmatchedburnermodulation tomatchenergy inputdirectly tofluctuatingsystemloads toyield thehighestpossibleseasonalefficiencies.Andnootherproductpacksasmuchcapacityintosuchasmallfootprint.

Tominimizeemissions,theBMKSeriesisfittedwithalowNOxburnerwhoseemissionswillmeetthemoststringentNOxandCOrequirements.ThefullymodulatingburneralsomaintainsAERCOstandardsforenergyefficiency,longevity,reliabilityandconstructionquality.

TheBMKSeriescomesstandardwithAERCO’sPatentPending,OxygenLevel (O2) monitoring system. This monitoring system, designed todisplaytheO2leveldirectlyontheunitinrealtime,canalsoberemotelymonitored via Modbus giving the customer the ability to measurethe emissions level and fuel economyof the boilerwithout traditionalcombustioncalibrationdevices.

The BMK boilers can be used as an individual unit or in modulararrangementsandoffersselectablemodesofoperation.Inadditiontocontrolling theboileraccording toaconstantsetpoint, indoor/outdoorresetscheduleor4-20mAsignal,oneormoreunitscanbeintegratedvia Modbus communications protocol. For boiler plants ranging from2-8 boilers, AERCO’S built-in Boiler Sequencing Technology (BST)*can be utilized. For heating plants greater than 8 boilers, AERCO’sACS (AERCO Control System) provides the right solution. Likewise,Benchmarksystemscanbeeasilyintegratedwithafacility-wideEnergyManagementorBuildingAutomationSystem.

• DuctedCombustionAirCapable• EasyOpenAccessforService• AcceptableventmaterialsAL29-4C,Polypropylene,

PVC,cPVC(modeldependant)• ReliableQuietOperation• ControlsOptions

• ConstantSetpoint• Indoor/OutdoorReset• RemoteSetpoint• 4-20mAsignalorModBus

Page 4: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

DIMENSIONS (INCHES):

RATINGS:Model Number Min Input

MBHMax Input

MBHMax Outputa

MBHEfficiency

RangeAHRI

Efficiency 80º to 180ºF

BMK 750 50 750 653-720 87%-98% 95.50%

BMK 1000 50 1000 870-960 87%-98% 96.80%

BMK 1500 75 1500 1305-1425 87%-98% 94.60%

BMK 2000 100 2000 1740-1900 87%-98% 94.60%

BMK 2500 167 2500 2175-2360 87%-98% 93.50%

BMK 3000 200 3000 2610-2880 87%-98% 93.50%

BMK 6000** 400 6000 5220-5670 87%-98% 94.50%aMaxoutputdependentuponapplication-Seeefficiencycurves**SeeseparateBMK6000TechnicalDataSheetforadditionalBMK6000details

Model (Width) A (Depth) B (Height) C D E F G H I J K L

BMK 750 28’’ 25’’ 78’’ 34’’ 10’’ 10’’ 53’’ 21’’ 17’’ 4’’ 5’’ 51.8’’

BMK 1000 28’’ 25’’ 78’’ 34’’ 10’’ 10’’ 53’’ 21’’ 17’’ 4’’ 5’’ 51.8’’

BMK 1500 28’’ 43.6’’ 78’’ 58.4’’ 7’’ 11.5’’ 57.8’’ 18’’ 22’’ 8.9’’ 4.7’’ 19.5’’

BMK 2000 28’’ 43.6’’ 78’’ 58.4’’ 7’’ 11.5’’ 57.8’’ 18’’ 22’’ 8.9’’ 4.7’’ 19.5’’

BMK 2500 28’’ 56’’ 78’’ 68.4’’ 5.4’’ 11.5’’ 57.8’’ 18’’ 22’’ 6.4’’ 3.6’’ 26’’

BMK 3000 28’’ 56’’ 78’’ 68.4’’ 5.4’’ 11.5’’ 57.8’’ 18’’ 22’’ 6.4’’ 3.6’’ 26’’

BMK 6000** 34’’ 89.3’’ 79.4’’ 108.3’’ 6.2’’ 42.1’’ N/A 15.6’’ N/A 10’’ 28.7’’ 23.7’’

**SeeseparateBMK6000TechnicalDataSheetforadditionalBMK6000dimensiondetails***BMK750/1000FeatureDualInletConnections

TCaranese
Rectangle
Page 5: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

SPECIFICATIONS:BMK750 BMK1000 BMK1500 BMK2000 BMK2500 BMK3000 BMK 6000**

Boiler Category ASMESect.IV

ASMESect.IV

ASMESect.IV

ASMESect.IV

ASMESect.IV

ASMESect.IV

ASMESect.IV

Gas Connections (NPT) 1’’ 1’’ 2’’ 2’’ 2’’ 2’’ 2’’

Max. Gas Pressure 14’’ 14’’ 14’’ 14’’ 14’’ 14’’ 2psi

Min. Gas Pressure 1 4’’ 4’’ 4’’ 4’’ 4’’ 4’’ 14’’

Max. Allowed Working Pressure 160PSIG 160PSIG 160PSIG 160PSIG 160PSIG 160PSIG 80PSIG/150

PSIGOptional

Electrical Req.120V/1PH/60Hz 2 13FLA 13FLA 16FLA 16FLA N/A N/A N/A

Electrical Req. 208V/3PH/60Hz 2 N/A N/A N/A N/A 10FLA 10FLA 19FLA

Electrical Req. 460V/3PH/60Hz 2 N/A N/A N/A N/A 5FLA 5FLA 12FLA

Water Connections (Flanged) 3’’ 3’’ 4’’ 4’’ 4’’ 4’’ 6’’

Min. Water Flow (GPM) 25 25 25 25 25 25 75

Max. Water Flow (GPM) 175 175 250 350 350 350 600

Water Volume Gallons 16.25 14.25 44 40 58 55 110

Water Pressure Drop 3.0PSIG@

100GPM

3.0PSIG@

100GPM

3.0PSIG@

170GPM

3.0PSIG@

170GPM

3.0PSIG@

218GPM

3.0PSIG@

261GPM

4.0PSIG@

500GPM

Turndown 15:1(7%) 20:1(5%) 20:1(5%) 20:1(5%) 15:1(7%) 15:1(7%) 15:1(7%)

Vent/Air Intake Connections 6Inch 6Inch 6Inch 8Inch 8Inch 8Inch 14Inch

Vent Materials AL29-4CPolypro,

CPVC,PVC

AL29-4CPolypro,

CPVC,PVC

AL29-4CPolypro

AL29-4CPolypro

AL29-4Polypro

AL29-4CPolypro AL29-4C

Type of Gas NaturalGas,Propane

NaturalGas,Propane

NaturalGas,Propane,Dual

Fuel

NaturalGas,Propane,Dual

Fuel

NaturalGas,Propane,Dual

Fuel

NaturalGas,Propane,Dual

Fuel

NaturalGas,DualFuel

NOx Emissions <9ppmCapability* ✓ ✓ ✓ ✓ N/A

(<20ppm)N/A

(<20ppm) ✓Temperature Control Range 50ºFto190ºF

Ambient Temperature Range 0ºFto130ºF

Standard Listings & Approvals UL,CUL,CSD-1,ASME,AHRI

Gas TrainOperations FMCompliantorFactoryInstalledDBB(IRI)(BMK750-BMK3000Only)FMCompliant(BMK6000)

Weight (dry) Ibs. 669 700 1406 1500 2,000 2,170 3,000

Weight (wet) Ibs. 802 817 1654 1760 2,332 2,580 3,920

Shipping Weight Ibs. 862 900 1606 1700 2,200 2,370 3,800

**SeeseparateBMK6000TechnicalDataSheetforadditionalBMK6000details

2 SeeBenchmarkElectricalPowerGuideGF-2060forServiceDisconnectSwitchamperagerequirements.

1 ValuesareforNaturalGasFMCompliantgastrainsonly.SeeBenchmarkGasComponents&SupplyDesignGuideGF-2030forPropane,DBB&DualFuelgastrainminimumgaspressurerequirements.

TCaranese
Rectangle
TCaranese
Rectangle
Page 6: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

RepresentedBy:

Specificationssubjecttochangewithoutpriornotice.ConsultwebsiteorcontactAERCO.BMKSERIES03/2014NY

WATERHEATERS•BOILERS•PARTS&ACCESSORIESAERCOINTERNATIONAL,INC.

100ORITANIDR.•BLAUVELT,NY10913(845)580-8000•FAX(845)580-8090

www.aerco.com

NOTES:

Page 7: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Sound Power by Octave BandSoundData 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 88 91 84 79 76 72 66 60 83 71 21

Reference assembly view drawings for actualdimensions with mounted accessories

*Overall height may be greater depending on motor

*

46

58.75

8.88

38.5

1.75

Model: GB-330-30Belt Drive Centrifugal Roof Exhaust Fan

DimensionalQuantity 1

Weight w/o Acc's (lb) 207

Weight w/ Acc's (lb) 211

Max T Motor Frame Size 215

Roof Opening (in.) 38.5 x 38.5

PerformanceRequested Volume (CFM) 13,500

Actual Volume (CFM) 13,500

External SP (in. wg) 0.25

Total SP (in. wg) 0.25

Fan RPM 606

Operating Power (hp) 2.52

Elevation (ft) 7,600

Airstream Temp.(F) 70

Air Density (ft3) 0.057

Drive Loss (%) 4.6

Tip Speed (ft/min) 5,713

Static Eff. (%) 22

MotorMotor Mounted Yes

Size (hp) 3

V/C/P 208/60/3

Enclosure ODP

Motor RPM 1725

Windings 1NEC FLA* (Amps) 10.6

Notes:All dimensions shown are in units of in.*FLA - based on tables 150 or 148 of National ElectricalCode 2002. Actual motor FLA may vary, for sizing thermaloverload, consult factory.LwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ft - dBA levels are notlicensed by AMCA InternationalSones - calculated using AMCA 301 at 5 ft

1/8/2015Printed Date: ElkJob:

EF-16Mark:

CAPS 4.16.1333 C:\Users\tcaranese\Documents\CAPS\Jobs\Elk.gfcj Page 1 of 3

Page 8: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Model: GB-330-30Belt Drive Centrifugal Roof Exhaust FanStandard Construction Features:- Aluminum housing - Backward inclined aluminum wheel - Curb cap withprepunched mounting holes - Motor and drives isolated on shock mounts -Birdscreen - Ball bearing motors - Adjustable motor pulley - Adjustable motorplate - Fan shaft mounted in ball bearing pillow blocks - Bearings meet or exceedtemperature rating of fan - Static resistant belts - Corrosion resistant fasteners -Sizes 141 and larger have internal Lifting lugsOptions & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12Switch, NEMA-1, Toggle, Junction Box Mounted & WiredBearings with Grease Fittings, L10 life of 100,000 hrs (L50 avg. life 500,000 hrs)Unit Warranty: 1 Yr (Standard)

1/8/2015Printed Date: ElkJob:

EF-16Mark:

CAPS 4.16.1333 C:\Users\tcaranese\Documents\CAPS\Jobs\Elk.gfcj Page 2 of 3

Page 9: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) includes transmission losses.

Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shownare based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 andcomply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type A:Free inlet, Free outlet. Power rating (BHP/kW) includes transmission losses. Performance ratings include the effects ofbirdscreen. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free fieldcalculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. dBAlevels are not licensed by AMCA International. The AMCA Certified Ratings Seal applies to sone ratings only

AMCA

1/8/2015Printed Date: ElkJob:

EF-16Mark:

CAPS 4.16.1333 C:\Users\tcaranese\Documents\CAPS\Jobs\Elk.gfcj Page 3 of 3

Page 10: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Sound Power by Octave BandSoundData 62.5 125 250 500 1000 2000 4000 8000 LwA dBA

Inlet 59 54 52 40 34 25 26 27 46 32

MOUNTINGBRACKET

AIR FLOW

8

14

11.25 8 10

12.875

11.8751 1

15.5

6.75

Model: CSP-A200Inline Cabinet FanStandard Construction Features:- Corrosion resistant galvanized steel scroll and housing - Sound absorbinginsulation - Rectangular inlet and outlet duct collar - Outlet with integral springloaded back draft damper - Double inlet forward curved wheel - Plug typedisconnect - Adjustable mounting brackets - Field rotatable dischargeOptions & Accessories:Motor with Thermal OverloadMotor with 40 Degree C Ambient TemperatureUL/cUL 507 Listed - Electric FanPolypropylene Wheel Material

DimensionalQuantity 1

Weight w/o Acc's (lb) 23

Weight w/ Acc's (lb) 23

PerformanceRequested Volume (CFM) 160

Actual Volume (CFM) 174

External SP (in. wg) 0.25

Total SP (in. wg) 0.296

Fan RPM 900

Watts (W) 48

Amps (A) 0.43

Elevation (ft) 7,600

Airstream Temp.(F) 70

Air Density (ft3) 0.057

Sones 1.0

MotorMotor Mounted Yes

Watts (W) 48

V/C/P 115/60/1

Enclosure ODPNEC FLA* (Amps) NA

Notes:All dimensions shown are in units of in.*FLA is approximate and will vary slightly with the motor.LwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ftSones - calculated using AMCA 301 at 5 ftAMCA certified ratings seal applies to sone ratings only.Wattage is shown at free air.

1/9/2015Printed Date: ElkJob:

EF-24Mark:

CAPS 4.16.1333 C:\Users\tcaranese\Documents\CAPS\Jobs\Elk.gfcj Page 1 of 2

Page 11: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

AMCA Licensed for Air Performance. Power rating (BHP/kW) does not include transmission losses.

Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shownare based on tests and procedures performed in accordance with AMCA Publication 211 and comply with therequirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings seal applies to air performanceratings only. Performance certified is for installation type D: Ducted inlet, Ducted outlet. Performance ratings include theeffects of a backdraft damper. Speed (RPM) shown is nominal. Performance is based on actual speed of test. Thesound ratings shown are for loudness values in spherical sones at 5 ft. (1.5m) in a spherical free field calculated perAnnex B of AMCA 311. Values shown are for installation type D: ducted inlet spherical sone levels. Ratings do notinclude the effects of duct end correction. Ratings are based on 10 ft. of insulated duct. The AMCA Certified Ratings Sealapplies to air performance only.

AMCA

1/9/2015Printed Date: ElkJob:

EF-24Mark:

CAPS 4.16.1333 C:\Users\tcaranese\Documents\CAPS\Jobs\Elk.gfcj Page 2 of 2

Page 12: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Project # : 466350.1 rev1Submittal

Product: ExpansionModel: Expansion Equipment

Project Number: 466350.1.1 Representative:1440 South Lipan StreetDenver, CO 80223

Name: JCSD Elk Creek ESReference: 466350.1.1

Phone: 303-761-2291, Fax: 303-761-0325Date:

Location: Pine, COOrder No: 3/5/2015Engineer: Envision Mechanical EngineersSubmitted by: Larry Gelin Date: 12/23/2014 Contractor:Approved by: Date:

SYSTEM DATATag Num : ET-1 Fluid : Polypropylene GlycolService : Glycol Heating Contents : 800.0 us galLocation : Flow Temperature : 160 °FQty Return Temperature : 50 °F: 1Selection Method : Automatic Static Height : 30.0 ft

Max System Press. : 157.5 ftEXPANSION TANK

Tank Model :A200-L Tank Qty : 1Tank Volume Max. Working Pres. : 288.8 ft:52.8 us gal

• Not for Domestic Potable Water Systems.Charge Pressure: 40.2 ft• Designed and constructed per ASME, Section VIII, Division 1.Standard factory charge is 12 psi (83 kPa)

unless otherwise specified. • California Code Sight-glass available upon request.• Allow a minimum of 18" (457 mm) clearance for system piping.

Shell : Carbon Steel WORKING TEMPERATURE : 35°F - 240°F (1.7°C - 115°Bladder : Heavy Duty Butyl WORKING PRESSURE : 125 psi (862 kPa)

www.armstrongfluidtechnology.com 12/23/2014, Ref. # 466350.1 rev1 Page 9 of 13

Page 13: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Submittal Ref. #: 466350.1 rev1

Flo-trex valve

Model: FTV-F (2.5 to 12 inch)

Project name: JCSD Elk Creek ES

Location: Pine, CO Representative:

Date submitted: 3/5/2015 Phone number: 303-761-2291

Engineer: Envision Mechanical Engineers e-mail: [email protected]

Contractor: Submitted by: Larry Gelin

Application design data

Designflowrate

Tag Qty Model Size Config Flange ratingPressure

Drop*Associated pump

HWP-1, 2 2 FTV-4FA Angle ANSI-125 3.4 ft HWP-1, 2 4300 IVS User-Drive-3x3x10-10 hp Pump (Factory Choice Motor)

*at design flow

Materials of construction

FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 O rings: BUNA (STEM) Elastomers & EPDM

Seat: EPDM 2 metering ports: Brass Body with EPDM Check and

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

Operating limits (temperature - pressure)

FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged

Maximum pressure: 175 psi

Maximum temperature: 230 F

www.armstrongfluidtechnology.com 12/23/2014, Ref. # 466350.1 rev1 Page 10 of 13

Page 14: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Dimensional data (not for construction)

Model: FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 59 lb

Side view Front view

Not to scale Units of measure: inches [millimeters]Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 12/23/2014, Ref. # 466350.1 rev1 Page 11 of 13

Page 15: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Submittal Ref. #: 466350.1 rev1

Suction guide

Model: SG (2 to 12 inches)

Project name: JCSD Elk Creek ES

Location: Pine, CO Representative:

Date submitted: 3/5/2015 Phone number: 303-761-2291

Engineer: Envision Mechanical Engineers e-mail: [email protected]

Contractor: Submitted by: Larry Gelin

Application design data

Design flowrate

Tag Qty Model System PumpPressure

Drop*Associated pump

HWP-1, 2 2 SG-43 4 in 3 in 3.1 ft HWP-1, 2 4300 IVS User-Drive-3x3x10-10 hp Pump (Factory Choice Motor)

*at design flow

Materials of construction

SG-43

Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

*Remove start up strainer after 24 hours

Operating limits (temperature - pressure)

SG-43-Suction Guide-ANSI-125

Maximum pressure: 175 psi

Maximum temperature: 230 F

Units are hydrostatically tested to 150% of maximum working pressure

www.armstrongfluidtechnology.com 12/23/2014, Ref. # 466350.1 rev1 Page 12 of 13

Page 16: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Dimensional data (not for construction)

SG-43 Weight: 52 lb

Side view Top view

Not to scaleUnits of measure: inches [millimeters]Tolerance of +/- 0.125 inch (+/- 3 mm) should be usedFor certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 12/23/2014, Ref. # 466350.1 rev1 Page 13 of 13

Page 17: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

L SERIES | PRE-CHARGED (ASME) E XPANSION TANK | S U B M I T T A L

File No: 37.52Date: sep. 16, 2014Supersedes: 37.52Date: feb. 18, 2010

Job:

Engineer:

Contractor:

Representative:

Order no.: Date:

Submitted by: Date:

Approved by: Date:

t ypic al specific ation

oper ating conditions

notes

Model no. ordered: Qty:

Tag no.: Charge pressure: psi/kPa

Optional California sight-glass and seismic clips: Yes No

Standard factory charge is 12 psi (83 kPa) unless otherwise specified.

Furnish and install, as shown on the plans, Armstrong Model ______-l asme pre-charged bladder Expansion Tank, stamped for 125 psi (862 kPa) workingpressure. Each tank will be supplied with a heavy duty butyl replaceable bladder.Tank shall be supplied with a ring base, lifting rings, and npt system connection.An air charging valve connection (standard tire valve) shall be provided tofacilitate adjusting pre-charge pressure to meet actual system conditions.

Shell: Carbon steel

Bladder: Heavy Duty Butyl

Temperature Range: 40°f - 240°f (4.4°c - 115.5°c)

Maximum Pressure: 125 psi (862 kPa)

materials of construction pump design data

• Not for Domestic Potable Water Systems.

• Designed and constructed per asme, Section viii, Division 1.

• California code sight-glass and seismic clips available as an option.

• Allow a minimum of 18" (457 mm) clearance for system piping.

Page 18: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

submittall seriesPre-charged (asme) expansion tank

2

b i r m i n g h a m

b u f f a l o

t o r o n t o

m a n c h e s t e r

b a n g a l o r e

s h a n g h a i a r m s t r o n g f lu i dt ec h n o lo g y. co m

+91 (0) 80 4906 3555

+44 (0) 8444 145 145

+44 (0) 8444 145 145

+1 716 693 8813

+1 416 755 2291

+86 21 3756 6696

a r m s t r o n g f lu i d t ec h n o lo g y established 1934

model tank volume

maximum acceptance volume

a bsystem connection npt

drainplug

shipping weight

gal.(L) inches (mm) inches (mm) lbs.(kg)

a200-l 53 (200) 53 (200) 24.00 (610) 38.40 (1475) 1.50 (38) 0.75 (19) 225 (102.1)

a300-l 80 (300) 80 (300) 24.00 (610) 52.27 (1328) 1.50 (38) 0.75 (19) 285 (129.3)

a400-l 106 (400) 106 (400) 24.00 (610) 66.14 (1680) 1.50 (38) 0.75 (19) 350 (158.8)

a500-l 132 (500) 132 (500) 24.00 (610) 80.14 (2036) 1.50 (38) 0.75 (19) 410 (186.0)

a600-l 158 (600) 158 (600) 30.00 (762) 64.75 (1645) 1.50 (38) 0.75 (19) 430 (195.0)

a800-l 211 (800) 211 (800) 30.00 (762) 82.44 (2094) 1.50 (38) 0.75 (19) 525 (238.1)

a1000-l 264 (1000) 264 (1000) 36.00 (914) 73.90 (1877) 1.50 (38) 0.75 (19) 565 (256.3)

a1200-l 317 (1200) 317 (1200) 36.00 (914) 86.00 (2184) 1.50 (38) 0.75 (19) 680 (308.4)

a1400-l 370 (1400) 370 (1400) 36.00 (914) 98.50 (2502) 1.50 (38) 0.75 (19) 750 (340.2)

1600-l 422 (1600) 422 (1600) 48.00 (1219) 71.00 (1803) 1.50 (38) 0.75 (19) 1183 (538)

2000-l 528 (2000) 528 (2000) 48.00 (1219) 85.00 (2159) 1.50 (38) 0.75 (19) 1264 (575)

2500-l 660 (2495) 660 (2495) 48.00 (1219) 102.00 (2591) 2.00 (51) 0.75 (19) 1435 (652)

3000-l 792 (2994) 792 (2994) 48.00 (1219) 122.00 (3099) 2.00 (51) 0.75 (19) 1550 (705)

4000-l 1056 (3992) 1056 (3992) 60.00 (1524) 102.00 (2591) 2.00 (51) 0.75 (19) 2638 (1199)

5000-l 1320 (4997) 1320 (4997) 60.00 (1524) 125.00 (3175) 2.00 (51) 1.00 (25) 3246 (1472)

charging valve charging

valve

systemconnection

systemconnectionlifting

ring

liftingring

liftingring

liftingring

drainplug drain

plug

a a

b b

models a200 -l to 2500 -l models 3000 -l to 5000 -l

Page 19: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

HHEERR5500 1/40 208-230 1 0.50 60 1550 Totally 5/16 SleeveHHEERR7755 Enclosed

Shaded Pole

HHEERR110000 TotallyHHEERR112255 EnclosedHHEERR115500 1/15 208-230 1 1.28 60 1050 Shaded 1/2 SleeveHHEERR220000 PoleHHEERR225500

EElleeccttrriiccaall UUnniitt HHeeaatteerr MMooddeellssDDiimm.. HHEERR5500 HHEERR7755 HHEERR110000 HHEERR112255 HHEERR115500 HHEERR220000 HHEERR225500

OOuuttlliinnee DDiimmeennssiioonnss ((iinncchheess))

MMoottoorr SSppeecciiffiiccaattiioonnss

AA

BB

CC

DD

EE

FF

GG

HH

KK

LL

MM

OO

FFaannDDiiaa..

WWtt..**LLbbss..

16-7/8

20-7/8

14-3/4

14-1/2

13

8-7/8

13-1/2

20-1/4

2-1/4

3-1/4

2-1/4

12-3/4

12

52

16-7/8

20-7/8

14-3/4

14-1/2

13

8-7/8

13-1/2

20-1/4

2-1/4

3-1/4

2-1/4

12-3/4

12

52

16-7/8

20-7/8

14-3/4

14-1/2

13

9-5/8

13-1/2

21-1/4

2-1/4

3-1/4

2-1/4

12-3/4

12

67

16-7/8

20-7/8

14-3/4

14-1/2

13

9-5/8

13-1/2

21-1/4

2-1/4

3-1/4

2-1/4

12-3/4

12

65

16-7/8

20-7/8

14-3/4

14-1/2

13

9-5/8

13-1/2

21-1/4

2-1/4

3-1/4

2-1/4

12-3/4

12

74

18-7/8

24

20

16-1/2

16

12-5/8

15-1/2

26-1/2

3-1/4

4-1/4

2-1/2

14-1/2

14

97

18-7/8

24

20

16-1/2

16

12-5/8

15-1/2

26-1/2

3-1/4

4-1/4

2-1/2

14-1/2

14

98

* Approx. Shipping Weight…Add 7 lbs. for 480 Volt Models.

MMoottoorr SShhaafftt BBeeaarriinnggTTyyppee DDiiaa.. TTyyppee

MMooddeell HHPP VVoollttaaggee PPhhaassee AAmmpp.. HHeerrttzz RRPPMM WW//TTooll ((IInn..))

A

G F

C

HAPPROX.

K LA

O

G

B

(2) MOUNTING HOLES 3/8-16 N.C. TAP

7/8" DIAFOR CONTROL

FOR POWER SUPPLY

MINUMUM CLEARANCES,12" TO SIDES AND TOP,24" TO BOTTOM

DOPENING

M5H67781B

September, 2002

SSUUBBMMIITTTTAALL DDAATTAAhhoorriizzoonnttaall eelleeccttrriicc uunniitt hheeaatteerrssmmooddeellss HHEERR5500 tthhrruu HHEERR225500

2-420.12

CCoommmmeerrcciiaall HHVVAACC&&RR DDiivviissiioonn •• Modine Manufacturing Company • 1500 DeKoven Avenue • Racine, Wisconsin 53403-2552 Phone: 1.800.828.4328 (HEAT) • FAX: 414.636.1665 •• www.modine.com© Modine Manufacturing Company 2002 9/02 - M Litho in USA

TToottaall**MMooddeell PPoowweerr AAmmppss MMiinn.. WWiirree MMiinn.. CCoonndduuiitt

NNoo.. SSuuppppllyy ((AApppprrooxx..)) SSiizzee ((AAwwgg)) SSiizzee

208/1 24.5 8 3/4240/1 21.3 10 1/2

HER 50 208/3 14.4 12 1/2240/3 12.6 12 1/2480/3 6.6 14 1/2208/1 36.5 6 1240/1 31.8 8 3/4

HER 75 208/3 21.3 10 1/2240/3 18.5 10 1/2480/3 9.6 14 1/2208/1 49.1 4 1240/1 42.7 6 1

HER 100 208/3 28.8 8 3/4240/3 25.1 8 3/4480/3 13.2 12 1/2208/3 35.8 6 1

HER 125 240/3 31.2 8 3/4480/3 16.1 10 1/2208/3 42.7 6 1

HER 150 240/3 37.2 6 1480/3 19.2 10 1/2208/3 56.6 3 1-1/4

HER 200 240/3 49.2 4 1480/3 25.2 8 3/4208/3 70.5 2 1-1/4

HER 250 240/3 61.2 3 1-1/4480/3 31.2 8 3/4

WWiirriinngg DDaattaa

* NEC fuse requirements are 125 percent of total amperes. Check with local code.

TCaranese
Highlight
TCaranese
Highlight
TCaranese
Highlight
Page 20: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Glycol Feed Systems

BULLETIN GLY-08

Glycol Feed Systems

MODELG-50-1

Purpose

Neptune Glycol Feeders are designed for theaddition of glycol solution to closed loop chilledor hot water systems. The system automaticallymaintains pressure in the loop by adding glycol solutionto make up for losses which occur due to leakage.

Glycol addition is controlled by a pressure switch withadjustable low and high set points.

Standard Pressure Switch:Cut-In Range: 10-45 PSI Cut-Out Range: 20-60 PSIAdjustable Differential: 10-30 PSIOther pressure switches available.

When the pressure in the loop reaches the low set point,the pump begins to feed glycol into the system until thehigh pressure set point is achieved and stops the pump.

Features

• 50 gallon polyethylene tank mounted in a steel frame

• Bronze rotary gear pump (1.5 gpm @ 100 psi)

• Float switch for low level pump shutoff and alarm

• NEMA 4X control panel

Panel includes:• Hand-off-auto selector switch for pump motor

• Pump “on” indicator light

• “Low” tank level indicator light

• Dry contact for remote low level indication

• Power cord with plug, 115V 60C

Optional audible alarm and pushbutton silence available.(Audible alarm isnot watertight.)

Each Neptune Glycol Feeder is fully pipedand wired with the following components:

Discharge assembly includes:

• Schedule 40 brass pipe and fittings

• PVC ball valve • Brass check valve • Pressure gauge

• Brass relief valve with return to tank tubing

Suction assembly includes:

• PVC tubing and fittings

• PVC ball valve

• Cast iron “Y” strainer

Page 21: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

SELECTION CHART

MODEL DESCRIPTION

G-50-1 Complete system including 1.5 gpm (@ 100 psi) pump and low level light.

G-50-1A Complete system including 1.5 gpm (@ 100 psi) pump, low level light andaudible alarm.

G-50-2A Complete system including two 1.5 gpm (@ 100 psi) pumps, low level light andaudible alarm. Separate discharges and pressure switches allow feedingtwo separate closed loop systems independently from a single tank.

LP Option to furnish larger pump rated 3.75 gpm (@ 100 psi).Add “LP” to Model Number to specify larger pump; Example G-50-1-LP.

MODEL G-50-1 & G-50-1A MODEL G-50-2A

EACH DISCHARGE ASSEMBLYCONTAINS:1⁄2" S40/BRASS/PIPE w/NPT FITTINGS1⁄2" BALL VALVE/PVC1⁄2" CHECK VALVE/BRASS1⁄2" RELIEF VALVE/BRASS (SET @ 100 PSI)

w/PVC RETURN LINE

PRESSURE GAUGE (0–100 PSI)

PRESSURE SWITCH

EACH SUCTION ASSEMBLYCONTAINS:1⁄2" S80/PVC/PIPE w/NPT

FITTINGS & PVC TUBING1⁄2" BALL VALVE/PVC1⁄2" Y-STRAINER/CAST IRON

55"

49"

41 1/2"

© 2008 Neptune Chemical Pump Company All Rights Reserved Bulletin GLY-08 P/N ZL106837 Printed in U.S.A.

SOLD BY:

P.O. Box 247 • Lansdale, PA 19446-0247Tel: 215-699-8700 • Fax: 215-699-0370Toll-Free Tel: 1-888-3NEPTUNE (1-888-363-7886)Toll-Free Fax: 1-800-255-4017Web Site: http://www.neptune1.comE-mail: [email protected]

Page 22: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Submittal Ref. #: 466350.1 rev1

Horizontal base mounted end suction pump

Model: Series 4030 IVS User-Drive-3x2.5x10-10 hp Pump (Factory Choice Motor)

Project name: JCSD Elk Creek ES

Location: Pine, CO Representative:

Date submitted: 3/5/2015 Phone number: 303-761-2291

Engineer: Envision Mechanical Engineers e-mail: [email protected]

Contractor: Submitted by: Larry Gelin

Application design data

Tag number: BMES HWP-1, 2 IVS Pipe orientation: Single

Suction pressure: 0 psigService: Glycol Heating

Location: Fluid: PropyleneGlycol:30

Quantity: 2 Operating temperature: 140 F

Viscosity: 31.025 SSUDuty flow per pump: 375 USgpm

Specific gravity: 0.9994Duty head: 70 ft

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (B584-844)

Rating: ANSI-125 Pump shaft: Carbon Steel

Connections: Inlet: 3 in, Outlet: 2.5 in Shaft sleeve: 304 SS

Casing (volute): Cast Iron (A48-30) Flexible coupling: Woods Duraflex Coupling

Bearings: Anti-Friction Grease Lubricated Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data

Seal type: Inside Single Spring Rotating face: Resin Bonded Carbon

Manufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: EPDM

Rotating hardware: Stainless Steel

Motor electrical data

Supplier: Factory Choice Insulation class: Class F Insulation

Size: 10 hp Inverter motor type: Inverter Duty

Frame number: 215TC Efficiency: NEMA Prem (12.12)

Enclosure: ODP Speed: 1766 rpm

Motor Electrics: 208/3/60

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 250 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

www.armstrongfluidtechnology.com 1/7/2015, Ref. # 466350.1 rev1 Page 4 of 12

Page 23: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Performance curve

--- Admin Data --- Tag Num: BMES HWP-1, 2 IVS Service: Glycol Heating Location:

--- Motor Data --- Motor Size: 10 hp

--- Design Duty Point --- Flow: 375 usgpm Head: 70 ft Impeller: 9.54 in

--- Performance Data --- • NPSHR: 11.3 ft • Eff. @ Design: 71.51 % • BHP @ Design: 9.26 hp • Mtr Capability @ Rated Spd: 9.98 hp • %Mtr Safety: 7.69% ->Contract Efficiency NCP req. • BEP @ Design Imp.: 74.49 % @ 294.8 usgpm • %max imp. range: 70.31 % • Outlet Velocity: 25.13 ft/s • VFD Setting: 59.9 Hz

Series 4030IVS User-Drive

3x2.5x10 @ 1766 rpm

0 80 160 240 320 400 4800

20

40

60

80

100

120

Flow (usgpm)

Head

(ft)

10.19 in

8.00 in

System

9.54 in

7.5 hp

10 hp

15 hp

75

75

73

73

68615137

PropyleneGlycol:30, spgr= 0.9994

PT52-2-0 (3.17.1.7)ANSI/HI 14.6.3.4.1

76

--- Admin Data --- Tag Num: BMES HWP-1, 2 IVS Service: Glycol Heating Location:

--- Motor Data --- Motor Size: 10 hp

--- Design Duty Point --- Flow: 375 usgpm Head: 70 ft Impeller: 9.54 in

--- Control Data --- 1. Hmax @ 59.9 Hz: • 375 @ 70, 9.26 hp 2. Control (QPC) @ 54.9 Hz: • 332.3 @ 61, 7.05 hp 3. Control (QPC) @ 49.8 Hz: • 286.3 @ 52.5, 5.15 hp 4. Control (QPC) @ 44.7 Hz: • 236.5 @ 44.7, 3.59 hp 5. Control (QPC) @ 39.7 Hz: • 179.3 @ 37.6, 2.29 hp 6. Index @ 34.4 Hz: • 93.8 @ 30.6, 1.15 hp 7. Hmin: 28 ft 32.6 Hz: • Setting= 40.00% Hmax

Series 4030IVS User-Drive

3x2.5x10 @ 9.54 in

0 80 160 240 320 400 4800

20

40

60

80

100

120

Flow (usgpm)

Head

(ft)

63.0 Hz

59.9 Hz

34.4 Hz 32.6 Hz

18.0 Hz System

Avg.Load (QPC)

10 hp

7574

74

72

72

676050

Index Flow (25.0% Duty Flow)

PropyleneGlycol:30, spgr= 0.9994

PT52-2-0 (3.17.1.7)ANSI/HI 14.6.3.4.1

1

2

34

56

www.armstrongfluidtechnology.com 1/7/2015, Ref. # 466350.1 rev1 Page 5 of 12

Page 24: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

25900

Dimensional data (not for construction)

Top viewSide view

Weight: 280 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 3 7.5ANSI-125 4 0.6256

Outlet 2.5 7ANSI-125 4 0.6255.5

*Equally spaced straddling centreline

Special instructions

The Program has defaulted to motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors. %Motor Safety is less than standard test tolerance, motor may overload on site.

.

Selected options Couplings-Woods Duraflex Coupling

www.armstrongfluidtechnology.com 1/7/2015, Ref. # 466350.1 rev1 Page 6 of 12

Page 25: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Internal View

Width and Height furnished approximately 0.250 in. under size.

ESD-4354 in. Frame, 35 deg BladeApplication & DesignESD-435 is a weather louver designed to protect air intake and exhaustopenings in building exterior walls. Design incorporates drain gutters in the headmember and horizontal blades to channel water to the jambs where water isfurther channeled through vertical downspouts and out at the sloped sill. TheESD-435 is an extremely efficient louver with AMCA LICENSEDPERFORMANCE DATA enabling designers to select and apply with confidence.

Construction FeaturesFrame Depth (in.): 4 Frame Thickness (in.): 0.081 Louver Material: AluminumFrame Type: Channel Sizing: Nominal Fixed Blade Thick. (in.): 0.081Shape: Rectangular Welded Construction: No

Options and AccessoriesFinishLouver Finish Type: Mill

BirdScreenBird Screen: Internal Bird Screen Mat'l: Aluminum Bird Screen Type: 3/4x0.050 Flat Exp.Bird Screen Finish: Mill

WarrantyProduct Warranty: 1 Yr (Standard)

Summary

ID # Tag Qty. W (in.) H (in.) Free Area (ft2) Sect. Wide Sect. High Sect. Ship1-1 LVR-1 1 40.000 36.000 5.21 1 1 1

PerformanceID # Application Volume (CFM) Press. Drop (in. wg) Free Area Velocity (ft/min) BPWP (ft/min)1-1 Intake N/A N/A N/A 1,151

**Calculated pressure drop does not include the effects of screens, filters or other accessories

Larger openings may require field assembly of multiple louver panels to make up the overall opening size. Individual louver panels are designed to withstand windloads up to a maximum of 25PSF (size and configuration dependent). Design, materials and installation of structural reinforcement required to adequately support large sections or multiple section assemblies within a largeopening are not provided by Greenheck. Unless specifically indicated, the following are NOT included in the quote provided: structural steel, installation hardware (anchors, angle clips,continuous angles, shims, fasteners, inserts, backer rod and sealant), field measuring and/or installation, miscellaneous flashing, trim or enclosures, blank off panels, mullion covers or mullionhardware, hinged frames or removable subframes, custom bird/insect screen, 3-coat, metallic and/or exotic paint finishes, bituminous paints for unlike metals, any applicable taxes, stamped andsealed structural calculations seismic calculations or job specific engineered submittal drawings.

1/7/2015Printed Date: Elk CreekJob:

LVR-1Mark:

CAPS 4.16.1333 C:\Users\tcaranese\Documents\CAPS\Jobs\Elk Creek.gfcj Page 1 of 3

Page 26: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Louvers Product Limited WarrantyThank you for purchasing Greenheck louvers. Greenheck warrants this equipment to be free from defect in material and workmanship for a period of 1year from the date of product shipment. Any units or parts, which prove defective during the warranty period, will be repaired or replaced at our optionwhen returned to our factory, transportation prepaid. Unless agreed upon otherwise Greenheck will not be held responsible for costs associated withremoval or installation of product(s).

The legal remedies described in this Limited Warranty are the sole exclusive remedy of Customer. This limited warranty will be void if payment fromCustomer is not received within a commercially reasonable time frame. GREENHECK MAKES NO OTHER WARRANTY, EITHER EXPRESS ORIMPLIED, REGARDING ITS PRODUCTS, OR ITS SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO, COMPLIANCE WITHBUILDING CODES, SAFETY CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR PURPOSE. This limited warranty is extendedsolely to the Customer. It is nontransferable and non-assignable, and the Customer shall not permit or authorize its employees, agents, representativesor customers to claim, represent or imply that this limited warranty extends or is available to anyone other than the Customer.

In the event of material breach by the Customer of any of the conditions of this warranty, Greenheck shall have no liability for and product failure claims.

Failure to pay Greenheck in full for original services will automatically make this warranty null and void.

Greenheck will not be held liable for incidental or consequential damages of any kind. The limited warranty of product(s) replaced or repaired under thislimited warranty shall be limited to the remainder of the original warranty period. Greenheck reserves the right to reasonable field access to diagnoseand repair any product alleged to be defective. This limited warranty may not be modified by anyone and may not be changed by such things aspurchase order forms or acceptance forms, unless otherwise agreed upon by Greenheck.

This limited warranty is provided in lieu of any other warranty requirements or obligations, including, but not limited to, those within project specifications.

All notices and claims given under or pursuant to this agreement shall be in writing and sent by certified or registered mail, postage prepaid, returnreceipt requested to: Greenheck, Attn: Louver Sales, 525 Western Road, Schofield, WI 54476.

By proceeding to use our products and services on your project, you accept the terms of these limited warranties.

1/7/2015Printed Date: Elk CreekJob:

LVR-1Mark:

CAPS 4.16.1333 C:\Users\tcaranese\Documents\CAPS\Jobs\Elk Creek.gfcj Page 2 of 3

Page 27: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Greenheck Fan Corporation certifies that the louver shown herein is licensed to bear the AMCA Seal. The ratings shownare based on tests and procedures performed in accordance with AMCA Publication 511 and comply with therequirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance andwater penetration ratings. The AMCA licensed performance data has been modified for installation, appurtenances,accessories, etc. not included in the certified data. The modified performance is not AMCA licensed but is provided to aidin selection and applications of the air control device.

AMCA

1/7/2015Printed Date: Elk CreekJob:

LVR-1Mark:

CAPS 4.16.1333 C:\Users\tcaranese\Documents\CAPS\Jobs\Elk Creek.gfcj Page 3 of 3

Page 28: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.221 (SN: 7691904-9M8DQKJC)

1A 1B 1C 1D 2

3

4 5A 5B 5C 6A 6B 6C 7

8

9

10

11

12

13

14A

14B

15

16

17

18

19

20

21

22

23

R L - 1 9 0 - 8 - 0 - H 0 0 0 - 0 0 0 : B G D H - D D M - Q C Z - 0 0 0 - D 0 0 B 0 B 5 - E C - U B N 0 0 0 0 0 B Tag: AHU-1Job Information Unit Information

Job Name: Approx. Op./Ship Weights: Job Number: Supply CFM/ESP: Site Altitude: Pre-Filter FV / Qty:

Exhaust CFM/ESP/TSP: Outside CFM: Ambient Temperature: Return Temperature:

Elk Creek 14544 / 14544 lbs. (±5%)PS-14-480 61100 / 1.5 in. wg.7600 ft 366.60 fpm / 60

61100 / 0.50 / 0.98 in. wg.2138595 ºF DB / 75 ºF WB75 ºF DB / 62 ºF WB

Static Pressure External: Economizer: Evaporator: Heating: Filters Clean: Cabinet: Dirt Allowance Total:

1.50 in. wg. 0.20 in. wg.0.00 in. wg. 0.21 in. wg.0.16 in. wg. 0.77 in. wg.0.35 in. wg. 3.19 in. wg.

Cooling Section Heating Section No Cooling is Selected

Supply Air Fan: SA Fan RPM / Width: Exhaust Air Fan: EA Fan RPM / Pitch:

BT - 4 x 330 @ 12.65 BHP Ea.1235 / 7.490"2 x MW4816-40 @ 11.03 BHP Ea.990 / 40º

PreHeat Type: Total Capacity: OA Temp: RA Temp: Entering Air Temp: Preheat Leaving Air Temp: Entering Glycol: Leaving Glycol: GPM / Head: Glycol % / Velocity: FA / RD / FPI / FV:

Hot Water Preheat1213.3 MBH-20.0 DB / -21.0ºF WB67.0 ºF DB / 50.0 ºF WB36.6 DB / 32.3 ºF WB59.4 DB / 43.0ºF WB160.0 ºF143.0 ºF150 / 1.3 ft30 / 2.17 fps58.33 ft² / 1 / 10 / 1047.4

Heating Type: No Heat

Electrical Data Rating: Minimum Circuit Amp: Unit FLA: Maximum Overcurrent:

208/3/60 347332 400

Qty HP VAC Phase RPM FLA RLA Supply Fan: 4 20.00 208 3 1760 59.4 Exhaust Fan: 2 15.00 208 3 1170 46.2 Control Circuit: 1 120 1 2.9

Cabinet Sound Power Levels*

Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW(dB): 101 101 102 98 95 89 82 79 Return LW(dB): 96 93 92 87 86 83 80 78 *Sound power levels are given for informational purposes only. The sound levels are not guaranteed.

Unit Rating

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/23/2014 4:56:11 PM

Ramon
Highlight
Ramon
Highlight
Ramon
Highlight
Ramon
Highlight
Ramon
Highlight
Page 29: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.221 (SN: 7691904-9M8DQKJC)

JOB INFORMATION: WHEEL SPECIFICATION: Job Name: Max RPM: Job Tag: Diameter x Qty: Rep Firm: Width%: Date: Tip Speed:

Inertia:

Elk Creek 1,760AHU-1 33.5 in. x 4

10012/23/2014 10,831 FPM

150 WR²

OPERATING CONDITIONS: MOTOR SELECTION: Air Flow: Rated HP / Bypass: Static Pressure: Frame Size: Plenum DP: Nominal RPM: Inlet Grill DP: VAC/PH/HZ: TSP: Efficiency Site Altitude: Enclosure Type: TSP @ Sea Level: Max Inertial Load:

61,100 CFM 20 x 4 / No3.02 in. Wg. 256T0.06 in. Wg. 17600.11 in. Wg. 208/3/603.19 in. Wg. Premium / 0.937600.00 Ft ODP4.23 in. Wg. 236 WR²

FAN PERFORMANCE: FAN SOUND POWER x 4 Fans (In/Out): RPM: Octave Band: (Re 10^-12 watts) BHP: 1 2 3 4 5 6 7 8 Efficiency: In/Out Velocity: Plenum Out Velocity: SOUND POWER A-Weighted: 100 / 106 dB Max Duct SP with Blocked Airway: 1.4 in. Wg. @ 1235 rpm

123512.6560.8% 93 93 94 95 95 94 92 901992/2793 FPM 100 98 100 104 102 99 99 96690 FPM

RPMBHPSYSTEMEfficiencySP SurgeCFM Min

Supply Fan M odel: 330 @ 1235 RPM and 100% WidthDesign Condit ions: 15275 CFM @ 4.24" SP

CFM x 100020181614121086420

SP

5

4

3

2

1

0

BHP

3230

2826

2422

2018

1614

1210

86

42

0

50%

0%

R P M : 1 2 3 5

B H P : 1 2 . 6 5

EFFICIENCY: 60.78

33.0" STAR Plenum

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/23/2014 4:56:11 PM

Ramon
Highlight
Ramon
Highlight
Ramon
Highlight
Ramon
Highlight
Page 30: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.221 (SN: 7691904-9M8DQKJC)

JOB INFORMATION: WHEEL SPECIFICATION: Job Name: Max RPM: Job Tag: Diameter x Qty: Rep Firm: CFM: Date: Tip Speed:

Inertia:

Elk Creek 1,170AHU-1 48.0 in. x 2

3055012/23/2014 12,441 FPM

38 WR²

OPERATING CONDITIONS: MOTOR SELECTION: Air Flow: Rated HP / Bypass: Static Pressure: Frame Size: Relief Dampers DP: Nominal RPM:

VAC/PH/HZ: TSP: Efficiency Site Altitude: Enclosure Type: TSP @ Sea Level: Max Inertial Load:

61,100 CFM 15 x 2 / No0.50 in. Wg. 284T0.48 in. Wg. 1170

208/3/600.98 in. Wg. Premium / 0.9177600.00 Ft ODP1.30 in. Wg. 573 WR²

FAN PERFORMANCE: FAN SOUND POWER x 2 Fans (In/Out): RPM: Octave Band: (Re 10^-12 watts) BHP: 1 2 3 4 5 6 7 8 Efficiency: In/Out Velocity: Plenum Out Velocity: SOUND POWER A-Weighted: 99 / 99 dB

99011.0342.6% 95 98 103 97 95 92 89 861059/1229 FPM 95 98 103 97 95 92 89 86690 FPM

RPMBHPSYSTEMEfficiencySP SurgeCFM Min

Exhaust Fan M odel: M W4816-40 @ 990 RPM and 100% WidthDesign Condit ions: 30550 CFM @ 1.30" SP

CFM x 10004035302520151050

SP

2

1

0

BHP

26

24

22

20

18

16

14

12

10

8

6

4

2

0

60%

40%

20%

0%

R P M : 9 9 0

B H P : 1 1 . 0 3

EFFICIENCY: 42.63

4816-40 Axial Fan

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/23/2014 4:56:11 PM

Ramon
Highlight
Ramon
Highlight
Ramon
Highlight
Ramon
Highlight
Page 31: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.221 (SN: 7691904-9M8DQKJC)

1A 1B 1C 1D 2

3

4 5A 5B 5C 6A 6B 6C 7

8

9

10

11

12

13

14A

14B

15

16

17

18

19

20

21

22

23

R L - 1 9 0 - 8 - 0 - H 0 0 0 - 0 0 0 : B G D H - D D M - Q C Z - 0 0 0 - D 0 0 B 0 B 5 - E C - U B N 0 0 0 0 0 B Tag: AHU-1

Job Name: Elk Creek Unit Submittal For: Job Number: PS-14-480 Unit Submittal Date: December 15, 2014

Base Option DescriptionR Series Roof Top UnitL Generation Tenth Generation

190 Unit Size One Hundred and Ninety8 Voltage 208V/3Ø/60Hz0 Inter. Protection StandardH Cooling - Style Air Handling Unit w/ Blow-Through Supply Fans w/ Front Control Panel w/o Vestibule0 Cooling - Configuration No Cooling0 Cooling - Coating Standard0 Cooling - Staging No Cooling0 Heating - Type No Heat0 Heating - Designation No Heat0 Heating - Staging No Heat

Feature Option DescriptionB 1A. Return / Outside Air Section Power ExhaustG 1B. R/A Blower Configuration 2 Blowers (Prem eff mtr)w/ 2-motors 2-VFDsD 1C. R/A Blower Blower D (48" Dia 16 Blade)H 1D. R/A Motor 15 hp (1170 rpm)D 2. O/A Control Fully Mod Actuator w/ Enthalpy LimitD 3. Discharge Locations End Discharge - Air Handler w/o VestibuleM 4. Return Locations Bottom Return High CFMQ 5A. S/A Blower Configuration 4 Blowers w/(Prem eff mtr) w/4-VFD'sC 5B. S/A Blower Blower C (33" Diameter)Z 5C. S/A Motor 20.0 hp (1760 rpm)0 6A. Pre-Filter 2" Pleated (Std Position)0 6B. Final Filter Standard0 6C. Filter Options StandardD 7. Refrig. Control 115V Outlet Factory Wired0 8. Refrig. Options Standard0 9. Refrig Accessories StandardB 10. Power Options 400 Amps Power Switch0 11. Safety Options StandardB 12. Controls Phase & Brown Out Protection5 13. Special Controls Field Installed DDC Controls by Others + Isolation RelaysE 14A. Preheat Configuration Hot Water Coil Preheat (4ft Box)C 14B. Preheat Sizing Heat Qty CU 15. Option Boxes 6ft Box After Preheat CoilB 16. Cabinet Options Marine Service LightsN 17. Cabinet Options Perf Liner S/A & R/A0 18. Customer Code Standard0 19. Code Options Std ETL USA Listing0 20. Unit Splits Standard (One Piece Unit)0 21. Evap and Water Condenser Std (No Evap or Water Condenser)0 22. Control Vendors StandardB 23. Type Standard (Includes 'Gray Paint')

Unit Submittal

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/23/2014 4:56:11 PM

Page 32: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.221 (SN: 7691904-9M8DQKJC)

1A 1B 1C 1D 2

3

4 5A 5B 5C 6A 6B 6C 7

8

9

10

11

12

13

14A

14B

15

16

17

18

19

20

21

22

23

R L - 1 9 0 - 8 - 0 - H 0 0 0 - 0 0 0 : B G D H - D D M - Q C Z - 0 0 0 - D 0 0 B 0 B 5 - E C - U B N 0 0 0 0 0 B Tag: AHU-1 Job Name: Elk Creek For: Job Number: PS-14-480 Date: December 15, 2014

Terminals Available/Required for Controlling the Unit

Terminal Description[R] 24VAC Control Voltage[E] Common[G] Supply Fan Enable + Isolation Relay[PE] Power Exhaust Enable + Isolation Relay

[B1-] & [B2+] Exhaust Fan 1 & 2 - w/2 VFD: Signal (0-10VDC)

VFD frequency reference signal control point must be able to handle 2 VFD's connected in parallel. Each drive is rated for 20k ohm input impedance.(SPA is required to provide separate terminals per VFD.)

[S1-] & [S2+] Supply Fan 1, 2, 3, & 4 - w/4 VFD: Signal (0-10VDC)

VFD frequency reference signal control point must be able to handle 4 VFD's connected in parallel. Each drive is rated for 20k ohm input impedance.(SPA is required to provide separate terminals per VFD.)

[PBO1] & [PBO2] Phase & Brown Out

Terminations Found On VFD(s)Exhaust Fan VFD(s) V1000: std 7.5-20HP VFD

[P1] & [PC] Run Status[AM] & [AC] Current Feedback (0-10VDC = 0-100%)[MA] & [MC] Fault

Supply Fan VFD(s) V1000: std 7.5-20HP VFD[P1] & [PC] Run Status[AM] & [AC] Current Feedback (0-10VDC = 0-100%)[MA] & [MC] Fault

Control Terminals

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/23/2014 4:56:11 PM

Page 33: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.221 (SN: 7691904-9M8DQKJC)

1A 1B 1C 1D 2

3

4 5A 5B 5C 6A 6B 6C 7

8

9

10

11

12

13

14A

14B

15

16

17

18

19

20

21

22

23

R N - 0 2 6 - 8 - 0 - 0 0 0 0 - E H J : C E H F - E 0 B - D L L - 0 0 A - 0 0 0 B 0 B 4 - 0 0 - 0 0 0 0 0 0 0 0 B Tag: AHU-2Job Information Unit Information

Job Name: Approx. Op./Ship Weights: Job Number: Supply CFM/ESP: Site Altitude: Final-Filter FV / Qty:

Return CFM/ESP/TSP: Outside CFM: Ambient Temperature: Return Temperature:

Elk Creek 3596 / 3596 lbs. (±5%)PS-14-480 14850 / 2 in. wg.7600 ft 464.06 fpm / 8

14850 / 0.50 / 0.89 in. wg.600095 ºF DB / 75 ºF WB75 ºF DB / 62 ºF WB

Static Pressure External: Economizer: Evaporator: Heating: Filters Clean: Cabinet: Dirt Allowance Total:

2.00 in. wg. 0.24 in. wg.0.00 in. wg. 0.12 in. wg.0.23 in. wg. 0.17 in. wg.0.35 in. wg. 3.11 in. wg.

Cooling Section Heating Section No Cooling is Selected

Supply Air Fan: SA Fan RPM / Width: Return Air Fan: RA Fan RPM / Pitch:

1 x 300D @ 11.16 BHP1449 / 6.810"1 x MW3505-20 @ 3.12 BHP1665 / 20º

PreHeat Type: Std (No Preheat)

Heating Type: Heating CFM: Total Capacity: OA Temp: RA Temp: Entering Air Temp: Leaving Air Temp: Entering Glycol: Leaving Glycol: GPM / Head: Glycol % / Velocity: FA / RD / FPI / FV:

Hot Water Heat14850344.6 MBH-20.0 ºF DB / -21.0 ºF WB70.0 ºF DB / 50.0 ºF WB33.6 ºF DB / 29.2 ºF WB60.2 ºF DB / 42.0 ºF WB160.0 ºF141.9 ºF40 / 4.6 ft30 / 3.85 fps18.75 ft² / 1 / 8 / 792.0

Electrical Data Rating: Minimum Circuit Amp: Unit FLA: Maximum Overcurrent:

208/3/60 7463 110

Qty HP VAC Phase RPM FLA RLA Supply Fan: 1 15.00 208 3 1760 46.2 Return Fan: 1 5.00 208 3 1760 16.7

Cabinet Sound Power Levels*

Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW(dB): 98 98 98 100 97 93 89 82 Return LW(dB): 95 95 88 85 89 88 83 80 *Sound power levels are given for informational purposes only. The sound levels are not guaranteed.

Unit Rating

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/23/2014 4:56:11 PM

Ramon
Highlight
Ramon
Highlight
Ramon
Highlight
Ramon
Highlight
Ramon
Highlight
Page 34: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.221 (SN: 7691904-9M8DQKJC)

JOB INFORMATION: WHEEL SPECIFICATION: Job Name: Max RPM: Job Tag: Diameter x Qty: Rep Firm: CFM: Date: Tip Speed:

Inertia:

Elk Creek 1,600AHU-2 30.0 in. x 1

1485012/23/2014 11,380 FPM

35 WR²

OPERATING CONDITIONS: MOTOR SELECTION: Air Flow: Rated HP / Bypass: Static Pressure: Frame Size: Relief Dampers DP: Nominal RPM:

VAC/PH/HZ: TSP: Efficiency Site Altitude: Enclosure Type: TSP @ Sea Level: Max Inertial Load:

14,850 CFM 15 / No3.11 in. Wg. 254T0.00 in. Wg. 1760

208/3/603.11 in. Wg. Premium / 0.937600.00 Ft ODP4.13 in. Wg. 149 WR²

FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet): RPM: Octave Band: (Re 10^-12 watts) BHP: 1 2 3 4 5 6 7 8 Efficiency: In/Out Velocity: Plenum Out Velocity: SOUND POWER A-Weighted: 96 / 102 dB Max Duct SP with Blocked Airway: 1.2 in. Wg. @ 1449 rpm

144911.1665.2% 90 93 93 92 92 91 86 812500/3285 FPM 96 95 98 101 100 96 93 86168 FPM

RPMBHPSYSTEMEfficiencySP SurgeCFM Min

Supply Fan M odel: 300D @ 1449 RPM and 100% WidthDesign Condit ions: 14850 CFM @ 4.13" SP

CFM x 1000181614121086420

SP

6

5

4

3

2

1

0

BHP

26

24

22

20

18

16

14

12

10

8

6

4

2

0

50%

0%

R P M : 1 4 4 9

B H P : 1 1 . 1 6

EFFICIENCY: 65.22

30.0" STAR Plenum

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/23/2014 4:56:11 PM

Ramon
Highlight
Ramon
Highlight
Ramon
Highlight
Ramon
Highlight
Page 35: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.221 (SN: 7691904-9M8DQKJC)

JOB INFORMATION: WHEEL SPECIFICATION: Job Name: Max RPM: Job Tag: Diameter x Qty: Rep Firm: CFM: Date: Tip Speed:

Inertia:

Elk Creek 1,760AHU-2 35.5 in. x 1

1485012/23/2014 15,474 FPM

9 WR²

OPERATING CONDITIONS: MOTOR SELECTION: Air Flow: Rated HP / Bypass: Static Pressure: Frame Size: Relief Dampers DP: Nominal RPM:

VAC/PH/HZ: TSP: Efficiency Site Altitude: Enclosure Type: TSP @ Sea Level: Max Inertial Load:

14,850 CFM 5 / No0.50 in. Wg. 184T0.39 in. Wg. 1760

208/3/600.89 in. Wg. Premium / 0.8957600.00 Ft ODP1.18 in. Wg. 52 WR²

FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet): RPM: Octave Band: (Re 10^-12 watts) BHP: 1 2 3 4 5 6 7 8 Efficiency: In/Out Velocity: Plenum Out Velocity: SOUND POWER A-Weighted: 96 / 96 dB

16653.1266.7% 93 95 90 92 91 89 86 83930/1077 FPM 93 95 90 92 91 89 86 83168 FPM

RPMBHPSYSTEMEfficiencySP SurgeCFM Min

Return Fan M odel: M W3505-20 @ 1665 RPM and 100% WidthDesign Condit ions: 14850 CFM @ 1.18" SP

CFM x 100018161412108642

SP

5

4

3

2

1

0

BHP

7

6

5

4

3

2

1

0

50%

0%

R P M : 1 6 6 5B H P : 3 . 1 2

EFFICIENCY: 66.72

3505-20 Axial Fan

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/23/2014 4:56:11 PM

Ramon
Highlight
Ramon
Highlight
Ramon
Highlight
Page 36: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.221 (SN: 7691904-9M8DQKJC)

1A 1B 1C 1D 2

3

4 5A 5B 5C 6A 6B 6C 7

8

9

10

11

12

13

14A

14B

15

16

17

18

19

20

21

22

23

R N - 0 2 6 - 8 - 0 - 0 0 0 0 - E H J : C E H F - E 0 B - D L L - 0 0 A - 0 0 0 B 0 B 4 - 0 0 - 0 0 0 0 0 0 0 0 B Tag: AHU-2

Job Name: Elk Creek Unit Submittal For: Job Number: PS-14-480 Unit Submittal Date: December 15, 2014

Base Option DescriptionR Series Roof Top UnitN Generation Ninth Generation

026 Unit Size Twenty Six8 Voltage 208V/3Ø/60Hz0 Interior Protection Standard0 Refrigerant Style Air Handling Unit0 Unit Configuration No Cooling0 Coil Coating Standard0 Cooling/Heat Pump Staging No CoolingE Heating Type Hot Water Standard CoilH Heating Designation 1 Row CoilJ Heating Staging Half Serpentine 8 FPI

Feature Option DescriptionC 1A. RA/OA Section Economizer + Power ReturnE 1B. RA/EA Blower Configuration 1 Blower + Premium Efficiency Motor + 1 VFDH 1C. RA/EA Blower 35.5" Direct Drive Axial FlowF 1D. RA/EA Blower Motor 5.0 hp - 1760 rpmE 2. OA Control DDC Actuator0 3. Heat Options StandardB 4. Maintenance Options 115V Convenience Outlet - Factory WiredD 5A. SA Blower Configuration 1 Blower + Premium Efficiency Motor + 1 VFDL 5B. SA Blower 30'' Direct Drive Backward Curved Plenum - 1600 rpm Max - Aluminum WheelL 5C. SA Motor 15 hp - 1760 rpm0 6A. Pre Filter Type Standard - None0 6B. Unit Filter Type 2" Pleated - 30% EffA 6C. Filter Options Clogged Filter Switch0 7. Refrigeration Control Standard0 8. Refrigeration Options Standard0 9. Refrigeration Accessories StandardB 10. Power Options Power Switch - 150 amps0 11. Safety Options StandardB 12. Controls Phase & Brown Out Protection4 13. Special Controls Field Installed DDC Controls by Others0 14A. Preheat Configuration Standard - None0 14B. Preheat Sizing Standard - None0 15. Glycol Percent Water or No WSHP0 16. Interior Cabinet Options Standard - Double Wall + R-13 Foam Insulation0 17. Exterior Cabinet Options Standard0 18. Customer Code Standard0 19. Code Options Standard - ETL U.S.A. Listing0 20. Crating Standard0 21. Water-Cooled Cond. Standard - None0 22. Control Vendors StandardB 23. Type Standard - Includes AAON Gray Paint

Unit Submittal

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/23/2014 4:56:11 PM

Page 37: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.221 (SN: 7691904-9M8DQKJC)

1A 1B 1C 1D 2

3

4 5A 5B 5C 6A 6B 6C 7

8

9

10

11

12

13

14A

14B

15

16

17

18

19

20

21

22

23

R N - 0 2 6 - 8 - 0 - 0 0 0 0 - E H J : C E H F - E 0 B - D L L - 0 0 A - 0 0 0 B 0 B 4 - 0 0 - 0 0 0 0 0 0 0 0 B Tag: AHU-2 Job Name: Elk Creek For: Job Number: PS-14-480 Date: December 15, 2014

Terminals Available/Required for Controlling the Unit

Terminal Description[R] 24VAC Control Voltage[E] Common[G] Supply Fan Enable/ Return Fan Enable

[EC1-] & [EC2+] Economizer Signal (0-10VDC)[S1-] & [S2+] Supply Fan 1 - w/ 1 VFD: Signal (0-10VDC)

VFD frequency reference signal control point must handle a rated 20k ohm input impedance.[PR1-] & [PR2+] Return Fan 1 - w/1 VFD: Signal (0-10VDC)

VFD frequency reference signal control point must handle a rated 20k ohm input impedance.[C1] & [C2] Clogged Filter Switch

[PBO1] & [PBO2] Phase & Brown Out

Terminations Found On VFD(s)Return Fan VFD(s) J1000:std 1-5HP VFD

Upgrade J1000 to V1000 by SPA for run statusSupply Fan VFD(s) V1000: std 7.5-20HP VFD

[P1] & [PC] Run Status[AM] & [AC] Current Feedback (0-10VDC = 0-100%)[MA] & [MC] Fault

Control Terminals

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/23/2014 4:56:11 PM

Page 38: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.221 (SN: 7691904-9M8DQKJC)

1A 1B 1C 1D 2

3

4 5A 5B 5C 6A 6B 6C 7

8

9

10

11

12

13

14A

14B

15

16

17

18

19

20

21

22

23

RL-190-8-0-H000-000:BGDH-DDM-QBY-000-D00B0B5-ED-UBN00000B Tag: AHU-1Job Information Unit Information Job Name: Approx. Op./Ship Weights: Job Number: Supply CFM/ESP: Site Altitude: Pre-Filter FV / Qty:

Exhaust CFM/ESP/TSP: Outside CFM: Ambient Temperature: Return Temperature:

Elk Creek 14344 / 14344 lbs. (±5%)PS-14-480 61100 / 1.5 in. wg.7600 ft 366.60 fpm / 60

61100 / 0.50 / 0.98 in. wg.1660595 ºF DB / 75 ºF WB75 ºF DB / 62 ºF WB

Static Pressure External: Economizer: Evaporator: Heating: Filters Clean: Cabinet: Dirt Allowance Total:

1.50 in. wg. 0.20 in. wg.0.00 in. wg. 0.44 in. wg.0.16 in. wg. 0.84 in. wg.0.35 in. wg. 3.49 in. wg.

Cooling Section Heating Section No Cooling is Selected

Supply Air Fan: SA Fan RPM / Width: Exhaust Air Fan: EA Fan RPM / Pitch:

BT - 4 x 300 @ 12.76 BHP Ea.1497 / 6.810"2 x MW4816-45 @ 11.67 BHP Ea.919 / 45º

PreHeat Type: Total Capacity: OA Temp: RA Temp: Entering Air Temp: Preheat Leaving Air Temp: Entering Glycol: Leaving Glycol: GPM / Head: Glycol % / Velocity: FA / RD / FPI / FV:

Hot Water Preheat1627.2 MBH-10.0 DB / -11.0ºF WB75.0 ºF DB / 62.0 ºF WB51.9 DB / 49.5 ºF WB83.5 DB / 60.0ºF WB180.0 ºF134.1 ºF75 / 0.6 ft30 / 1.08 fps58.33 ft² / 2 / 10 / 1047.4

Heating Type: No Heat

Electrical Data Rating: Minimum Circuit Amp: Unit FLA: Maximum Overcurrent:

208/3/60 290279 300

Qty HP VAC Phase RPM FLA RLA Supply Fan: 4 15.00 208 3 1760 46.2 Exhaust Fan: 2 15.00 208 3 1170 46.2 Control Circuit: 1 120 1 2.9

Cabinet Sound Power Levels* Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW(dB): 103 103 103 101 100 92 84 76 Return LW(dB): 98 96 92 88 86 84 80 77 *Sound power levels are given for informational purposes only. The sound levels are not guaranteed.

Unit Rating

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/15/2014 3:57:33 PM

Page 39: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG
Page 40: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.221 (SN: 7691904-9M8DQKJC)

1A 1B 1C 1D 2

3

4 5A 5B 5C 6A 6B 6C 7

8

9

10

11

12

13

14A

14B

15

16

17

18

19

20

21

22

23

R N - 0 2 6 - 8 - 0 - 0 0 0 0 - E H N : C E H F - E 0 B - D L L - 0 0 A - 0 0 0 B 0 B 4 - 0 0 - 0 0 0 0 0 0 0 0 B Tag: AHU-2Job Information Unit Information Job Name: Approx. Op./Ship Weights: Job Number: Supply CFM/ESP: Site Altitude: Final-Filter FV / Qty:

Return CFM/ESP/TSP: Outside CFM: Ambient Temperature: Return Temperature:

Elk Creek 3603 / 3603 lbs. (±5%)PS-14-480 14850 / 2 in. wg.7600 ft 464.06 fpm / 8

14850 / 0.50 / 0.89 in. wg.600095 ºF DB / 75 ºF WB75 ºF DB / 62 ºF WB

Static Pressure External: Economizer: Evaporator: Heating: Filters Clean: Cabinet: Dirt Allowance Total:

2.00 in. wg. 0.24 in. wg.0.00 in. wg. 0.16 in. wg.0.23 in. wg. 0.17 in. wg.0.35 in. wg. 3.14 in. wg.

Cooling Section Heating Section No Cooling is Selected

Supply Air Fan: SA Fan RPM / Width: Return Air Fan: RA Fan RPM / Pitch:

1 x 300D @ 11.25 BHP1452 / 6.810"1 x MW3505-20 @ 3.12 BHP1665 / 20º

PreHeat Type: Std (No Preheat)

Heating Type: Heating CFM: Total Capacity: OA Temp: RA Temp: Entering Air Temp: Leaving Air Temp: Entering Glycol: Leaving Glycol: GPM / Head: Glycol % / Velocity: FA / RD / FPI / FV:

Hot Water Heat14850379.9 MBH-10.0 ºF DB / -11.0 ºF WB70.0 ºF DB / 50.0 ºF WB45.0 ºF DB / 40.0 ºF WB75.0 ºF DB / 51.9 ºF WB180.0 ºF139.9 ºF20 / 1.5 ft30 / 1.93 fps18.75 ft² / 1 / 12 / 792.0

Electrical Data Rating: Minimum Circuit Amp: Unit FLA: Maximum Overcurrent:

208/3/60 7463 110

Qty HP VAC Phase RPM FLA RLA Supply Fan: 1 15.00 208 3 1760 46.2 Return Fan: 1 5.00 208 3 1760 16.7

Cabinet Sound Power Levels* Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW(dB): 98 98 98 100 97 93 89 82 Return LW(dB): 95 95 88 85 89 88 83 80 *Sound power levels are given for informational purposes only. The sound levels are not guaranteed.

Unit Rating

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/15/2014 3:57:34 PM

Page 41: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/15/2014 3:57:34 PM

Page 42: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/15/2014 3:57:34 PM

Page 43: Pressure drop for Models VA-2 to VA-12 · The AERCO Benchmark (BMK) Water Boiler is designed for condensing ... Water Pressure Drop. 3.0 PSIG @ 100 GPM 3.0 PSIG @ 100 GPM 3.0 PSIG

Date Created/Modified: 12/15/2014 12:39:40 PM Using Ver 4.221 (OSN# 7691904) Date Printed: 12/15/2014 3:57:34 PM