Pressure Instrument Trainer

Embed Size (px)

Citation preview

  • 8/16/2019 Pressure Instrument Trainer

    1/45

    Pressure Instrument Trainer 1

    ForewordForewordForewordForeword

    Welcome to value-conscious company. We are proud of the advanced engineering andquality construction of each equipment we manufacture.

    This manual explains the working of equipment. Please read it thoroughly and have allthe occupants follow the instructions carefully. Doing so will help you enjoy many yearsof safe and trouble free operation.

    When it comes to service remember that K.C. Engineers knows your equipment bestand is interested in your complete satisfaction. We will provide the quality maintenanceand any other assistance you may require.

    All the information and specifications in this manual are current at the time of printing.However, Because of K.C. Engineers policy of continual product improvement wereserve the right to make changes at any time without notice.

    Please note that this manual explains all about the equipment including options.

    Therefore you may find some explanations for options not installed on your equipment.

    You must follow the instructions and maintenance instructions given in the manualcarefully to avoid possible injury or damage. Proper maintenance will help ensuremaximum performance, greater reliability and longer life for the product.

    K.C. Engineers

  • 8/16/2019 Pressure Instrument Trainer

    2/45

    Pressure Instrument Trainer 2

    PRESSURE INSTRUMENT TRAINER

    INTRODUCTION:

    Currently, the PID algorithm is the most common control algorithm used in industry.

    Often, people use PID control processes that include heating and cooling systems, fluid flow

    monitoring, flow control and temperature control. In PID control, you must specify a process

    variable and a set point. The process variable is the system parameter you want to control

    such as temperature, pressure and flow rate and the set point is the desired value for the

     parameter you are controlling. A PID controller determines a controller output value, such as

    the heater power or valve position. The controller applies the controller output value to thesystem, which in turn drives the process variable towards the set point value.

    CONTROL SYSTEM:

    The control system is that means by which any quantity of interest in a machine,

    mechanism or equipment is maintained or altered in accordance with a desired manner.

    Control system is of two types: -

    1. OPEN LOOP CONTROL SYSTEM:

    It is shown in figure1. Any physical system, which doesn’t automatically correct forvariation in its output, is called open loop system. In these systems, the output remains

    constant for a constant input signal provided the external; conditions remain unaltered. The

    output may be changed to any desired value by appropriately changing the input signal but

    variations in external or internal parameters of the system may cause the output to vary from

    the desired value in an uncontrolled fashion. The open loop control is, therefore, satisfactory

    only if such fluctuations can be tolerated or system components are designed and constructed

    so as to limit parameter variations and environmental conditions as well controlled.

    It is important to note that the fundamental difference between an open and closed

    loop control system is that of a feedback action. Consider, for example, traffic control system

    for regulating the flow of traffic at the crossing of two roads. The system will be termed open

    loop if red and green lights are put on by a timer mechanism set for predetermined fixed

    Controller PlantInput Output

    Fig. 1: Open Loop

  • 8/16/2019 Pressure Instrument Trainer

    3/45

    Pressure Instrument Trainer 3

    intervals of time. It is obvious that such an arrangement takes no account of varying rates of

    traffic flowing to the road crossing from the two directions. If on the other hand a scheme is

    introduced in which the rate of traffic flow along both directions are measured and are

    compared and the difference is used to control the timings of the red and green lights, a

    closed-loop system results. Thus, the concept of feedback can be usefully employed to traffic

    control.

    Unfortunately, the feedback, which is the underlying principle of most control

    systems, introduces the possibility of undesirable system oscillations.

    2. CLOSED LOOP CONTROL SYSTEM:

    A closed loop control system consists of a process and a controller that automatically

    adjusts one of the inputs to the process in response to a signal feedback from the process

    output. The performance of the system can be judged by the transient response of the output

    to specific changes in the input. The change in the input may be a change in set point or a

    change in any one of the several load variables. If the purpose of the control system is to

    make the process follow changes in set point as closely as possible, the operation is called

    “servo-operation”. The term “regulator operation” is used when the main problem is to keep

    the output almost constant in spite of changes in load. The designer must be aware of the

     purpose of the control system, since the system that gives optimum servo-operation will

    generally not be the best for regulator operation.

    DEFINITIONS:

    (Referred from Modern control Engineering By Katsuhiko Ogata, 4th

     edition, page no.

    2 and Control system engineering By I.J Nagrath and M.Gopal, 3rd

     edition, page no. 195)

    CONTROLLED VARIABLE & MANIPULATED VARIABLE:

    The controlled variable is the quantity or condition that is measured and controlled.

    The-manipulated variable is the quantity or condition that is varied by the controller so as to

    affect the value of the controlled variable. Normally, the controlled variable is the output of

    the system. Control means measuring the value of the controlled variable of the system and

    applying the manipulated variable to the system to correct or limit deviation of the measured

    value from a desired value.

  • 8/16/2019 Pressure Instrument Trainer

    4/45

    Pressure Instrument Trainer 4

    PLANTS:

    A plant may be a piece of equipment, perhaps just a set of machine parts functioning

    together, the purpose of which is to perform a particular operation.

    PROCESSES:

    A process may be defined as natural, progressively continuing operation or

    development marked by a series of gradual changes that succeed one another in relatively

    fixed way and leads toward a particular result or end; or an artificial or voluntary,

     progressively continuing operation that consists of a series of controlled actions or

    movements systematically directed towards a particular result.

    SYSTEMS:

    A system is a combination of components that act together and perform a certain

    objective. A system is not limited to physical ones. The concept of system can be applied to

    abstract, dynamic phenomena such as those encountered in economics. The word system

    should therefore, be interpreted to imply physical, biological, economic and the like systems.

    DISTURBANCES:

    A disturbance is a signal that tends to adversely affect the value of the output of a

    system. If a disturbance is generated within the system, it is called internal, while the external

    disturbance is generated outside the system and is an input.

    FEEDBACK CONTROL:

    Feedback control refers to an operation that, in the presence of disturbance tends to

    reduce the difference between the output of a system and some reference input and does so on

    the basis of this difference. Here only the unpredictable or known disturbances can always be

    compensated for within the system.

    DELAY TIME:

    It is the time required for the response to reach 50% of the final value in first attempt.

    It is represented by td. It is shown in figure 2.

  • 8/16/2019 Pressure Instrument Trainer

    5/45

    Pressure Instrument Trainer 5

    R ISE TIME:

    It is the time required for the response to rise from 10% to 90% of the final value for

    over damped systems and 0 to 100% of the final value for under damped systems. It is shown

    in figure 2.

    PEAK TIME:

    It is the time required for the response to reach the peak of time response or the peak

    overshoot. It is represented by ts. It is shown in figure 2.

    PEAK OVERSHOOT MP:

    It indicates the normalized difference between the time response peak and the steady

    output and is defined as:

    Peak percent overshoot = [Ctp – C∞/C∞ ] x 100%

    The M p is represented in figure 2.

    SETTING TIME:

    It is the time required for the response to reach and stay within a specified tolerance

     band (Usually 2% to 5%) of its final value. It is represented by ts in figure 2

    Figure : 2

    0.5

    1.0

    Mp

    Ttd

    Ttp

    Tt

    Tc(t)

    Ttr 

       A   l   l  o  w  a   b   l  e   T  o   l  e

      r  a  n  c  e

  • 8/16/2019 Pressure Instrument Trainer

    6/45

    Pressure Instrument Trainer 6

    INTRODUCTION TO PID CONTROL EQUATIONS:

    This section will show you the characteristics of the each of proportional (P), the

    integral (I), and the derivative (D) controls, and how to use them to obtain a desired response.In this section, we will consider the following feedback system:

    PLANT:

    System to be controlled.

    CONTROLLER:

    Provides the excitation for the plant; Designed to control the overall system behavior.

    THE THREE-TERM CONTROLLER

    The transfer function of the PID controller looks like the following:

     s

    Ti KcsTdsTds

     s

    Ti Kc

      ++=++

    2

     

    K c  = Proportional gain

    Ti  = Integral gain

    Td = Derivative gain

    First, let's take a look at how the PID controller works in a closed-loop system using

    the schematic shown above. The variable (e) represents the tracking error, the difference

     between the desired input value (R) and the actual output (Y). This error signal (e) will be

    sent to the PID controller, and the controller computes both the derivative and the integral of

    this error signal. The signal (u) just past the controller is now equal to the proportional gain

    (Kc) times the magnitude of the error plus the integral gain (Ti) times the integral of the error

     plus the derivative gain (Td) times the derivative of the error.

    dt 

    deTd edt Tie Kcu   +∫+×=  

    This signal (u) will be sent to the plant, and the new output (Y) will be obtained. This

    new output (Y) will be sent back to the sensor again to find the new error signal (e). The

    controller takes this new error signal and computes its derivative and its integral again. This

     process goes on until the error becomes equal to zero.

    R e u YController Plant

    + _

  • 8/16/2019 Pressure Instrument Trainer

    7/45

    Pressure Instrument Trainer 7

    THE CHARACTERISTICS OF P, I, AND D CONTROLLERS:

    A proportional controller (Kc) will have the effect of reducing the rise time and will

    reduce, but never eliminate, the steady state. An integral control (K i) will have the effect of

    eliminating the steady-state error, but it may make the transient response worse. A derivativecontrol (K d) will have the effect of increasing the stability of the system, reducing the

    overshoot, and improving the transient response. Effects of each of controllers Kc, Ti, and Td

    on a closed-loop system are summarized in the table shown below.

    Controller Response Rise Time Overshoot Settling Time Steady-State Error

    K c  Decrease Increase Small Change Decrease

    Ti  Decrease Increase Increase Eliminate

    Td Small Change Decrease Decrease Small Change

     Note that these correlations may not be exactly accurate, because Kc, Ti, and Td are

    dependent of each other. In fact, changing one of these variables can change the effect of the

    other two. For this reason, the table should only be used as a reference when you are

    determining the values for K c, Ti and Td.

    GENERAL TIPS FOR DESIGNING A PID CONTROLLER:

    When you are designing a PID controller for a given system, follow

    the steps shown below to obtain a desired response.

    1.  Obtain an open-loop response and determine what needs to be improved.2.  Add a proportional control to improve the rise time.

    3.  Add an integral control to eliminate the steady-state error.

    4.  Add a derivative control to improve the overshoot.

    5.  Adjust each of Kc, Ti, and Td until you obtain a desired overall response.

    Lastly, please keep in mind that you do not need to implement all three controllers

    (proportional, derivative, and integral) into a single system, if not necessary. For example, if

    a PI controller gives a good enough response, then you don't need to implement derivative

    controller to the system. Keep the controller as simple as possible to obtain the system with

    no overshoot, fast rise time, and no steady-state error.

  • 8/16/2019 Pressure Instrument Trainer

    8/45

    Pressure Instrument Trainer 8

    VARIOUS TYPES OF CONTROLS:

    (Referred from Process control By Peter Harriott, page no. 6)

    1. PROPORTIONAL CONTROL:

    The cycling inherent with the on-off control would be objectionable for most

     processes. To get steady operation when the disturbances are absent, the controlled variable

    must be a continuous function of error. With proportional control, the most widely used type;

    the controller output is a linear function of the error signal. The controller gain is the

    fractional change in output divided by the fractional change in input.

    P = Kc* e -------------------------(1)

    Where:P = fractional change in controller output,

    e = fractional change in the error.

    Kc = controller gain.

    The control action can also be expressed by the proportional bandwidth B. The

     bandwidth is the error needed to cause a 100% change in the controller output, and it is

    usually expressed as a percentage of the chart width. A bandwidth of 50% means that

    controller output would go from 0 to 1 for an error equal to 50% of the chart width or from,

    say, 0.5 to 0.6 for an error of 5%.

    B = 1/Kc * 100 ------------------(2)

    Some pneumatic controllers are calibrated in sensitivity units, or pounds per square

    inch per inch of the pen travel. For a standard controller with a 3 to 15 psi range and a 4-inch

    chart, the gain and sensitivity are related by equation:

    S = 3Kc psi/inch ------------------------(3)

    2. PROPORTIONAL + INTEGRAL CONTROL:

    This mode of control is described by the relationship:

    )4(−−−−−−−−−−−+∫+×=   Psedt Ti

     Kce Kc P   

    Where:

    Kc = gain

    Ti = integral time, seconds

    Ps = constant

  • 8/16/2019 Pressure Instrument Trainer

    9/45

    Pressure Instrument Trainer 9

    P = output

    In this case, we have added to the proportional action term, Kc * e, another term that

    is proportional to the integral of the error.

    There is no offset with the integral control, since the output keeps changing as long as

    any error persists. However, the initial response to an error is slow and proportional control is

    ordinarily used with integral control. The integral action corrects for the offset that usually

    occurs with proportional control only, and the effect is similar to manual adjustment or

    resetting of the set point after each load change. The terms “ reset action” and “reset time” are

    widely used to characterize the integral action of a proportional – integral controller.

    )5()1

    (   −−−−−−−−−−−−−−∫+=   dt Ti

    e Kc P   

    Where:

    Ti = reset time

    Kc = gain

    P = output

    3. PROPORTIONAL + DERIVATIVE (PD) CONTROL:

    This mode of control may be represented by:

    )6(−−−−−−−−−−−−+×=dt 

    de KcTd e Kc P   

    Where: Kc = gain

    Td = derivative time, seconds

    P = output

    In this case, we have added to the proportional term another term, KcTd (de/dt) that is

     proportional to the derivative of the error. Other terms that are used to describe the derivative

    action are rate control and anticipatory control.

    Derivative action is often added to proportional control to improve the response of

    slow systems. By increasing the output when the error is changing rapidly, derivative action

    anticipates the effect of large load changes and reduces the maximum error.

  • 8/16/2019 Pressure Instrument Trainer

    10/45

    Pressure Instrument Trainer 10

    DESCRIPTION:

    FOR PRESSURE CONTROL TRAINER:

    The basic objective of this flow controller is to control the pressure in the process tank.

    This set up consists of the following components:

    SETUP ASSEMBLY:

    This assembly is used for supporting the various components on the front panel of the

    equipment i.e. pressure gauges which is used to measure the pressure, Current to pressure

    converter having a range in between 3 to 15 psi i.e. 3 psi for a current of 4mA and 15 psi for

    current of 20mA which is given to the I/P converter by DIGITAL INDICATING

    CONTROLLER. The setup also contains a pneumatic actuator.

    SHEMATIC DIAGRAM OF PRESSURE CONTROL TRAINER

    PRESSURE TRANSMITTER:

    The pressure in the process tank is sensed by the pressure transmitter with the help of

     pressure sensor fitted in the line and after that is transmitted by the transmitter to the

    computer through interfacing unit which shows the value of the process variable. This

    transmitter converts that accordingly into 4-20mA i.e. 4mA for 0% pressure and 20mA for

    100 % pressure.

     Air ReleaseValve

    ProcessTank

    SurgeTank

    ControlValve

    PressureRegulator 

    MoistureSeparator 

     Air Supply

    PressureTransmitter 

    SafetyValve

    SafetyValve

    PressureGauge

    PressureGauge

    Digital IndicatingPID Controller  I/P Convertor 

     

  • 8/16/2019 Pressure Instrument Trainer

    11/45

    Pressure Instrument Trainer 11

    CONTROL VALVE:

    A control valve basically performs the function of controlling the input of air pressure in the

     process tank. It is a diaphragm type pneumatic actuator, which varies the flow of the air

    according to the movement of the stem at a pressure range of 3 to 15 psi, which is receivedfrom I/P converter.

    INTERFACING UNIT:

    The interfacing unit is basically a medium for communicating with the equipment from the

    computer. In case of pressure controller, the pressure of the air in process tank is sensed by

    the pressure sensor in the pipe line, which is further transmitted into 4-20 mA which means

    that the current is 4mA for 0% pressure and 20mA for 100% pressure and are displayed on

    the interfacing unit in terms of 0 to 100%. These signals are further transmitted to the

    computer through this interfacing unit by using a RS-232C where the signals are displayed on

    the computer screen. The output of the interfacing unit is then transmitted to the I/P

    converter, which converts it into 3 to 15 psi that means 3 psi for 4mA and 15 psi for 20mA.

    CURRENT TO PRESSURE CONVERTER (I/P CONVERTER ):

    This converter is basically used to convert the current to pressure having a range of 3 to 15

     psi, which shows 3 psi at 4 mA and maximum 15 psi at 20 mA. This I/P converter receives

    the continuous input pressure of more than 15 psi and then converts this pressure into 3 to 15

     psi according to the 4 to 20 mA current received by it from the digital indicating controller.

    INSTALLATION R EQUIREMENTS: -

    This section gives the necessary details regarding the installation of the equipment and the

    software used for interfacing with the equipment.

    For the installation of the equipment, following components are required: -

    1)  Table for support.

    2)  Water supply.

    3)  Electricity 220V, single phase, 50Hz, 5 Amps socket.

    For the installation of the software, following components are required: -

  • 8/16/2019 Pressure Instrument Trainer

    12/45

    Pressure Instrument Trainer 12

    COMPUTER:

    A computer, which is the basic requirement for installing the software for interfacing with

    the equipment. But the computer must fulfill the following requirements:-

    1.  The Processor must be at least celeron 286 MHZ, Pentium III is recommended.

    2.  It must have at least 16 MB RAM.

    3.  It must have 30 MB hard disk space.

    4.  It must have at least Windows 95 OS or higher version of operating system.

    5.  There must be an A4 size printer, which is used to get a hard copy of the stored data

    required.

    SOFTWARE

    INSTALLATION:

    1)  Close all the programs running before inserting the Cd into CD drive.

    2)  Insert the provided CD for the software in the CD drive of computer.

    3)  It is an AUTORUN CD. Follow the instructions appeared on the computer

    screen and install the software in desired directory.

    4)  After completion of installation, reboot your computer.

    5)  Then, Open the software directory and double click the exe file of the

    software to run the program.

    6)  Follow the steps according the experimentation.

    MENUS & BASIC FUNCTIONS: -

    This section gives us the detailed information regarding the menus and the basic function of

    the control software, which is used to control the equipment. It is shown in figure 3.

    LOGIN:

    This menu enables you to start the experiment. In this option, we are given with the User

    Name i.e. name of the institute and the Password, which is “k.c.engineers”. Here we have

    also the option of the entering the “Professors Name” under whose supervision test is going

    to be performed, “Student’s name” and the  “Roll Number” of the student who is

     performing the experiment, which can be used during the report generation. It is compulsory

    to select this option first and to fill the correct user name and password to continue the

  • 8/16/2019 Pressure Instrument Trainer

    13/45

    Pressure Instrument Trainer 13

    experiment. Without enabling this option and trying to continue the process or to select any

    other option in the front panel shows the display box indicating that the user must login first

    for selecting any other option. In this option, password is compulsory for running the

    software. In case of wrong password the software will not run and a dialogue box will appear

    with the software. All other options can be skipped off if not desired.

    VIEW DIAGRAM: -

    After LOGIN, we have to select VIEW DIAGRAM.  This option, which shows us the

    complete block diagram of the equipment and tells us how the equipment functions and also

    helps in preparing the equipment connection. After that we have to choose the BACK  option

    and then decide to choose either the SIMULATION to access data from the simulation logic

    in order to start the experiment or INTERFACE to access with the real time data.

    SIMULATION:

    Selecting this option accesses data from the PID simulation logic. This option doesn’t use any

    real time data. In this case, the process values and set point are to be entered by the user and

    then observes the change in the controller output. In this we have the option to put some

    value of disturbance. Now as the value of the load or the disturbance increases in a process,

    then the corresponding error between the SP and PV increases. Hence as a result, the output

    response also increases and vice-versa. Also in case of manual mode in the Simulation, when

    the controller output is made equal to zero, then the value of PV decreases and finally reaches

    to zero.

    SIMULATION MODE:

  • 8/16/2019 Pressure Instrument Trainer

    14/45

    Pressure Instrument Trainer 14

    INTERFACE:

    Selecting this option, accesses real time data from using interfacing unit. In order to make the

    system stable, we have to change the values of P, I, D.

    START:

    By enabling this option, the equipment will be ready to perform the experiment.

    LOG:

    On clicking the LOG button ON  or selecting this option enables the data to be logged in

    some particular file, which can be used later for continuing the experiment. In order to view

    this saved data-logging file, click VIEW DATA FILE.

    OFF:

    Selecting this option disables the data logging. 

    FUNCTION GENERATOR:

    The function generator is basically used to apply the dynamic waveform of some particular

     period and amplitude to the process. The waveform is applied to the set point in case of the

    close loop operation and is applied to the output in case of the open loop function.

    ON:

    This option enables the function generator selection and also enables the waveform to be

    applied to the process.

    OFF:

    Selecting this option disables the function generator so that it stops functioning.

  • 8/16/2019 Pressure Instrument Trainer

    15/45

    Pressure Instrument Trainer 15

    FUNCTION GENERATOR PARAMETERS:

    SIGNAL TYPE:

    This function enables you to select one waveform out of the sine, triangular, square

    and saw tooth waveform to be applied to the process.

    R EFERENCE POINT:

    This function is used to set the reference point equal to set point which helps in

    making PV equal to the set point.

    PERIOD:

    This function is basically used to provide some time period to a waveform so that the

    waveform completes its one complete cycle in some particular interval of time.

    AMPLITUDE:

    This function is used to set the amplitude of the waveform, which is selected to be

    applied to the process.

    PROCESS: -

    This function is responsible for either increasing or decreasing the value of PV in the

    SIMULATION mode.

    LAG (MIN): -

    It is also known as delay time and is measured in minutes. It is the amount of time

    required for the response to reach 50% of the final value in first attempt. As the value of the

    lag time increases, the change in the value of PV also increases.

    DISTURBANCE (%):

    A disturbance is a signal that tends to adversely affect the value of the output of a

    system. If a disturbance is generated with in the system, it is called internal, while an external

    disturbance is generated outside the system and is an input.

    INITIAL:

    This is the value of the PV when we continue the process without allowing the

     process variable to reach its initial state i.e. equal to zero or its ambient temperature.

  • 8/16/2019 Pressure Instrument Trainer

    16/45

    Pressure Instrument Trainer 16

    AMBIENT TEMPERATURE: -

    This is the initial value of PV, or due to the room temperature of the place where the

    experiment is to be performed.

    OUTPUT R ANGE: -

    This corresponds to the maximum and the minimum range of the controller output,

    which is to be set by the user.

    OUTPUT HIGH

    It corresponds to the maximum limit of the controller output means that the output of

    the controller never exceeds this limit. This value is set by the user in order to obtain the

    accurate result.

    OUTPUT LOW:

    It corresponds to the lowest limit of the controller output means that the output of the

    controller can never be less than this value.

    PID GAINS:

    This corresponds to the various values of the Kc, Ti and Td, which are to be selected

     by the user in order to make the system stable. In other words, these values are selected in

    order to make PV equal to SP.

    MODE STATUS: -

    This option tells you that in which mode the system is operating i.e. whether the

    system is operating in P, PI or PID.

    P:

    This option tells you that the system is operating in proportional controller mode. P 

    represents the proportional gain. In order to get the steady operation when the disturbances

    are absent, the controlled variable must be a continuous function of error. With proportional

    control, the controller output is a linear function of the error signal.

    PD:

    This option indicates that the system is operating in Proportional + Derivative

    controller mode.

  • 8/16/2019 Pressure Instrument Trainer

    17/45

    Pressure Instrument Trainer 17

    PID:

    This option indicates that the system is operating in proportional + Integral +

    Derivative controller  

    BIAS:

    Bias is the value of the normal output of the controller at zero error. This is added to the

     proportional controller.

    Thus, when a process is under P only control and the SP equals the measurement (when error

    equals zero), some bias value of the controller output must exist or the measured PV will drift

    from the set point. This bias value of the controller output is determined from the design flow

    of operation of the process to be controlled. Specifically, bias is the value of the controller

    output, which in open loop causes the measured PV to maintain steady state at the design

    flow of the operation when the process disturbances are at their design.

    ACTION:

    There are mainly two actions for controlling the process variable and controller output.

    These actions are:

    1)  INC-INC

    2)  INC-DEC

    Using INC-INC action will cause increase in output with the corresponding increase in

     process variable. Using INC-DEC action will cause decrease in controller output with

    increase in process variable. This action should be observed by the user, which will further

    depend on the final control element functioning.

    For example: Consider a case of pneumatic actuator, which is open for air and otherwise

    closed which means that the actuator valve is open for 15 psi pressure and close for 3 psi pressure. So, the final control element sets INC-INC action or INC-DEC action.

    SWITCHING BETWEEN AUTO AND MANUAL:

    Auto and Manual:

    There’re two different modes option in this software i.e. Auto and Manual. In case of auto

    mode, the software automatically controls the output of the process. In this case, user doesn’t

  • 8/16/2019 Pressure Instrument Trainer

    18/45

    Pressure Instrument Trainer 18

    do anything to control the output of the process. So, if the output is increasing with increase

    in the value of the Kc, the controller automatically decreases its output in order to make it

    stable. But in case of manual control, the user controls the output of the process. Click AUTO

    to select the AUTO mode and Click again to change the system to manual mode.

    EXIT:

    This option enables you to logout of the simulation or interfacing mode.

    VIEW DATA FILE:

    This option accesses data from the data stored in the stored file using LOG button.

    Results and data of the experiment conducted are observed .The user can see the data stored

    in the file in the form of tables as well as graphs. After enabling this option, user enters into a

    window where user has to open the file in which he has stored his/her data while performing

    the experiment using the LOG button and this shows the data in the form of table which

    indicates date and time i.e. which indicates when the experiment was performed and at what

    time, PV, set point, output, upper and lower range and the limit of the upper and lower

    hysteresis. This window also indicates the User  i.e. the name of the institute which is

     performing the experiment and also the Professor name  i.e. under whose supervision the

    experiment is going to be performed, Student Name and Roll Number  i.e. name and roll

    number of the student who is performing the experiment.

    STOP:

    This option enables you to logout out of this window.

    R UN/PAUSE:

    This option enables the graph to run or pause to show the waveform according to the

    data shown the table in that window.

    PRINT GRAPH:

    Use print graph option for printing graphs according to the data that is saved in the

    data log file.

    Enabling this option enables you to enter into the print window, which shows the

    User i.e. the name of the institute, Professor’s Name i.e. under whose supervision test is to

     be performed, Student’s Name and Roll number i.e. the name and the roll number of the

    student who is performing the experiment and the File path i.e. the path of the file which was

  • 8/16/2019 Pressure Instrument Trainer

    19/45

    Pressure Instrument Trainer 19

    saved using the LOG button. In this window the user has two options at the top of the

    window i.e. one option of Print Window, which is used to take out the printout of the

    window, and the second option is of Stop, which enables the user to come out of the window.

    PRINT

    TABLE:

    Use print table option to print table from data file that are saved in the data log file.

    This option opens all the data stored using the log button in the excel file where the user has

    an option to set the left, right margins of the page.

    BODE PLOT:

    To view this, switch off the start button so as to return back to the front panel and

    click bode plot.

    COMPARE DATA:

    This option enables you to compare the data between to two experiments having

    different values of P, I, D. This option also enables you to compare data between the

    SIMULATION mode and INTERFACING mode.

    EXIT:

    Selecting this option allows you to return back to the desktop or logout you from the

    software.

    VARIOUS PID CONTROL METHODS:

    1. COHEN AND COON R ULES (C-C): 

    (Referred from Process systems Analysis and Control By Donald R.Coughanowr, 2nd

     edition,

     page no.288)

  • 8/16/2019 Pressure Instrument Trainer

    20/45

    Pressure Instrument Trainer 20

     

    The open loop method of tuning in which the control action is removed from the

    controller by placing it in manual mode and an open loop transient is induced by a step

    change in the signal. This method was proposed by COHEN and COON in 1953 and is often

    used as an alternative to the Z-N method. Fig shows a typical control loop in which the

    control action is removed and the loop opened for the purpose of introducing a step change

    (M/S). The step response is recorded at the output of the measuring element. The step change

    to the valve is conveniently provided by the output from the controller, which is in manualmode. The response of the system is called the process reaction curve; a typical process

    reaction curve exhibits an s-shape as shown in the fig. 5

    It is represented by equation:

    1)(

    +

    ×=

    Ts

    e Kc sGp

    Tds

      ------------------(7)

    The C-C method is summarized in the following steps: -

    Typical process Reaction Curve showing graphical construction to determine first order with Transport lag Model

    Figure : 5

    Block Diagram of a Control loop for measurement of the Process reaction Curve

    COHEN-COON METHOD

    To Recorder 

    Loop Opened

    H

    B

    CGc

    M/S

    Gv   GpR=0

    Uu=0

    +

    -

    +

    +

    Tangent Line;Slope S = Bu/T

    Time

    Td0

    Tt

    M

    0

     

  • 8/16/2019 Pressure Instrument Trainer

    21/45

    Pressure Instrument Trainer 21

    1)  After the process reaches steady state at the normal temperature of operation, switch

    the controller to manual. In modern controller, the controller output will remain at the

    same value after switching as it had before switching.

    2)  With the controller in manual, introduce a small step change in the controller output

    and record the transient, which is the process reaction curve.

    3)  Draw a straight line tangent to the curve at the point of inflection, as shown in fig .the

    intersection of the tangent line with the time axis is the apparent transport lag (Td);

    the apparent first order time constant (T) is obtained from the

    T=Bu/S ------------------------------(8)

    Where Bu is the ultimate value of B at large t and S is the slope of the tangent line.

    The steady state gain that relates B to M in fig is given by

    K  p=Bu/M -----------------------------(9)

    4)  Using the values of K  p, T and Td from step 3, he controller settings are found from the

    relations as given below:

    TYPE OF CONTROL PARAMETER SETTING

    Proportional (P) )3

    1(T 

    Td 

     KpTd 

    T  Kc   +=  

    Proportional – Integral (PI) )1210

    9(

    Td 

     KpTd 

    T  Kc   +=  

    )

    209

    330(

    Td T Td 

    Td Ti

    +

    +=  

    Proportional- Derivative (PD) )64

    5(

    1

    Td 

     KpTd  Kc   +=  

    )

    322

    26

    (

    Td T 

    Td 

    Td td 

    +

    −=  

    Proportional – integral-derivative (PID) )43

    4(

    Td 

    TdKp

    T  Kc   +=  

    )

    813

    632

    (

    Td T 

    Td 

    Td Ti

    +

    +=  

  • 8/16/2019 Pressure Instrument Trainer

    22/45

    Pressure Instrument Trainer 22

    )

    211

    4(

    Td Td td 

    +

    =  

    2. ZIEGLER’S NICHOL’S METHOD:

    (Referred from Modern Control Engineering By Katsuhiko Ogata)

    According to Zeigler – Nichol, PID controllers can be classified into two categories: -

    1)  A controller in which the dynamic model of the plant is not known.

    2)  A controller in which the dynamic model of the plant is known.

    FIRST METHOD:

    In this method, we obtain experimentally the response of the plant to a unit step input.

    If the plant involves neither integrator nor dominant complex conjugate poles, then such a

    S Shaped Response Curve

    Figure : 6

    Tangent Line atInflection point

    TimeL   T

    0

    K

    C(t)

    Unit Step Response of a Plant

    Zigler-Nichol’s Method

    PLANT

    C(t)Uu(t)

    1

     

  • 8/16/2019 Pressure Instrument Trainer

    23/45

    Pressure Instrument Trainer 23

    unit step response curve may look S-shaped. This method applies if the response to a step

    input exhibits an S-shaped curve. Such step response curves may be generated experimentally

    or from a dynamic simulation of the plant.

    The S-shaped curve may be characterized by two constants, delay time L and time

    constant T, which is shown in fig. 6 constant are determined by drawing a tangent line at the

    inflection point of the S-shaped curve and determining the intersections of the tangent line

    with the time axis and line C (t)=K, as shown in the figure.

    The transfer function C(s)/U(s) may then be approximated by first order system with a

    transport lag as follows: -

    1)(

    )(

    +

    ×=

    Ts

    e K 

     sU 

     sC  Ls

      ----------------------(10)

    Zeigler and Nichols suggested setting the values of Kp, Ti and Td according to theformula shown in below table.

    Type of controller K c  Ti  Td 

    P T/L ∞ 0

    PI 0.9T/L L/0.3 0

    PID 1.2T/L 2L 0.5L

     Notice that the PID controller tuned by the first order method of Zeigler- Nichols

    rules gives: )5.02

    11(2.1

    11()(   Ls

     Ls L

    T Tds

    Tis KcS Gc   ++=++=  

    Thus the PID controller has the pole at the origin and double zeros at S=-1/L.

    SECOND METHOD:

    It is shown in fig. 7. In the second method, we first set Ti=infinity and Td=0. Using

    the proportional control action only, increase Kc from 0 to critical value Kcr at which the

    output first exhibits sustained oscillations, (If the output doesn’t exhibit sustained oscillations

    for whatever value Kp may take, then this method doesn’t apply). Thus, the critical gain Kcr

    and the corresponding period Pcr are experimentally determined. Zeigler and Nichols

    suggested that we set the values of the parameters Kc, Ti and Td according to the formula

    shown in the table

     Notice that the PID controller tuned by the second method of Zeigler-Nichols rules

    gives:

  • 8/16/2019 Pressure Instrument Trainer

    24/45

    Pressure Instrument Trainer 24

     

     s Pcr  s KcrPcr 

     Pcrs Pcrs

     Kcr 

    TdsTis

     Kc sGc

    2

    )/4(075.0

    )125.05.0

    11(6.0

    )1

    1()(

    +=

    ++=

    ++=

     

    Thus the PID controller has the pole at the origin and double zeros at S=-4/Pcr.

    Type of controller K c  Ti  Td 

    P 0.5K cr   ∞ 0

    PI 0.45K cr   Pcr /1.2 0

    PID 0.6K cr   0.5Pcr   1.25Pcr  

     Note that if the system has a known mathematical model (such as transfer function),

    then we can use the root locus method to find the critical gain Kcr and the frequency of the

    sustained oscillations Wcr, where 2*pi/Wcr=Pcr. These values can be found from the

    crossing points of the root locus branches with the jw axis. (Obviously, if the root locus

     branches do not cross the jW axis, this method doesn’t apply).

    COMMENTS:

    Zeigler-Nichols tuning rules (other tuning rules presented in the literature) have been

    widely used to tune PID controllers in process control system where the plant dynamics are

    not precisely known. Over many tears, such tuning rules proved to be very useful. Zeigler-

    Shaped Response Curve

    Figure : 7

    Tangent Line atInflection point

    TimeL   T

    0

    K

    C(t)

     

  • 8/16/2019 Pressure Instrument Trainer

    25/45

    Pressure Instrument Trainer 25

     Nichols tuning rules can, of course, be applied to plants whose dynamics are known. (If the

     plant dynamics are known, many analytical and graphical approaches to the design of the PID

    controllers are available, in addition to the Zeigler-Nichols tuning rules).

    3. 

    QUARTER

    DECAY

    R ATIO

    METHOD:

    The following controller tuning procedures are based on the work of Zeigler and

     Nichols, the developers of the Quarter Decay ratio-tuning techniques derived derived from a

    combination of theory and empirical observations.

    CLOSED LOOP (ULTIMATE TUNING) TUNING PROCEDURE:

    Although the closed loop tuning procedure is very accurate, you must put your

     process in steady state oscillation and observe the PV on a strip chart. Complete the following

    steps to perform the closed loop tuning procedure.

    1)  Set both the derivative time and integral time on your PID controller to zero.

    2)  With the controller in automatic mode, carefully increase the proportional gain (Kc)

    in small increments. Make a small change in SP to disturb the loop after each

    increment. As you increase Kc, the value of the PV should begin to oscillate. Keep

    making changes until the oscillation is sustained, neither growing nor decaying

    overtime.

    3)  Record the controller proportional band (PBu) as a percent, where PBu=100/Kc.

    4)  Record the period of oscillation (Tu) in minutes.

    5)  Multiply the measured values by the factors shown in the below table and enter the

    new tuning parameters into your controller. This table provides the proper values for a

    quarter decay ratio.

    If you want less overshoot, increase the gain Kc.

    Controller PB (%) Reset (min.) Rate (min.)

    P 2PBu --------- --------

    PI 2.22PBu 0.83Tu -------

    PID 1.67PBu 0.50TTu 0.125Tu

  • 8/16/2019 Pressure Instrument Trainer

    26/45

    Pressure Instrument Trainer 26

     

    OPEN LOOP (STEP TESTING) TUNING PROCEDURE:

    The open loop tuning procedure assumes that you can model any process as a first

    order lag and a pure dead time. This method requires more analysis than the closed loop

    tuning procedure, but your process doesn’t need to reach sustained oscillation. Therefore, the

    open loop tuning procedure might be quicker and the PV on a strip chart that shows time on

    the X-axis. Complete the following steps to perform the open loop tuning procedure.

    1. Put the controller in manual mode, set the output to a nominal operating value and

    allow the PV to settle completely. Record the PV and output values.

    2. Make a step change in the output. Record the new output values.3. Wait for the PV to settle. From the chart, determine the values as derived from the

    sample displayed in the given figure.

    4. Multiply the measured values by the factors shown in fig (a) and enter the new tuning

     parameters into your controller. The table provides the proper values for a quarter

    decay ratio. If you want less overshoot, reduce the gain, Kc.

    Controller PB (%) Reset (min) Rate (%)

    P 100KTd/T --------- ----------

    PI 110KTd/T 3.33Td  ----------

    PID 80KTd/T 2Td  0.50Td 

    Output & PV Step Change

    Figure :

    TimeTd

    T

    Output

    Max.

    Min.

    63.2%(Max.Min)PV

  • 8/16/2019 Pressure Instrument Trainer

    27/45

    Pressure Instrument Trainer 27

    VARIOUS STABILITY METHODS:

    1. BODE PLOT:

    (Referred from Process Control By Peter Harriot, Page no. 91)

    A convenient method of presenting the response data at various frequencies is to use a

    log –log plot for the amplitude ratios, accompanied by a semi log plot for the phase angles.

    Such plots are called “ Bode diagrams”, after H.W Bode, who did basic work on the theory of

    feedback amplifiers. By using wT as a parameter, a general plot for first order system is

    obtained. Since the amplitude ratio approaches 1.0 at low frequencies and 1/wT at high

    frequencies, the straight line portion of the response if extended would intersect at wT = 1.0.

    The frequency corresponding to the wT = 1 is called the “corner frequency” and the amplitude

    ratio is 0.707 at this point. The phase lag is 45 degree at the corner frequency and the phase

    curve is symmetrical about this point.

    The system shown in fig. 6 has a gain of 1, which means that the output equals the

    input as the frequency approaches zero. If the system gain K is greater than 1, the output

    amplitude is greater than the input amplitude at low frequencies and a more comprehensive

    definition of amplitude ratio is needed. The amplitude ratio is defined as the ratio of output

    amplitude to input amplitude at a given frequency, divided by the ratio of the amplitudes at

    zero frequency. This is equivalent to dividing the measured ratio by B/A by the gain K, which

    makes the amplitude ratio dimensionless and makes equation and curves applicable to the first

    order process.

    Sometimes, the amplitude ratio is defined just as B/A, or output over input, which

    leads to amplitude ratios, which may not be dimensionless. There is nothing unsound about

    this procedure but the use of different units for each process element makes it somewhat

    harder to plot the overall response of the system.

    Whenever a sinusoidal input is applied to a linear system, the output has steady state

    and transient terms. After a few cycles, the transient dies out and the output is a sine wave of

    the same frequency. This eventual response can be characterized by the amplitude ratio and

    the phase angle. Typical curves for a first order process are shown below. At low frequency,

    the output is almost equal to the input, and there is only a slight phase lag. At high frequency,

    the fluctuations in the input are severely damped because of the capacity in the system and

    the output lags the input by almost 90 degree.

  • 8/16/2019 Pressure Instrument Trainer

    28/45

    Pressure Instrument Trainer 28

     

    A.R =

    2

    1

    22 )1(

    1

    T w+

     

    The phase angle is always negative for a first order system and the negative angle iscalled “ phase lag”. The phase lag is 360(dt/p) in fig. And approaches a limit of 90 degree at

    high frequencies.

    2. R OUTH‘S ALGORITHM METHOD:

    (Referred from Problems and Systems of control systems By A.K. Jairath, 3rd

     edition, page

    no. 6.1)

    The Routh test is a purely algebraic method for determining how many roots of the

    characteristics equation have positive real parts; from this it can also be determined whether

    the system is stable, for if there are no roots with positive real parts, the system is stable. The

    test is limited to the systems that have polynomial characteristic equations.

    As per Routh’s stability criterion the necessary conditions for a system to be stable are:

    1)   None of the co-efficient of the characteristics equations should be missing or zero.

    2)  All co-efficient should be real and should have same sign.

    The sufficient condition for a system to be stable is that each and each term of the first

    column of Routh’s array should be positive and should have same sign.

    Routh’s array for the characteristic equation

    A0 s*n + A1 s*n-1 +A2 s*n-2 + ------------------An-1s + An = 0 -------------(11)

    Where n=7 is formed as given below

    A0 A2 A4 A6

    A1 A3 A5 A7

    B1 B3 B5

    C1 C3

    D1 D3

    E1

    F1

  • 8/16/2019 Pressure Instrument Trainer

    29/45

    Pressure Instrument Trainer 29

    Where

    A1A2 – A0A3

    B1 = ------------------

    A1

    A1A4 – A0A5

    B3 = -----------------

    A1

    A1A6 – A4A7

    B5 = ---------------

    A1

    B1A3 – A1B3

    C1 = ------------------

    B1

    B1A5 – A1B5

    C3 = ------------------

    B1

    C1B3 – B1C3

    D1 = -----------------

    C1

    C1B5 – B1 0

    D3 = -----------------

    C1

    If we study the array successive rows have one term fewer than the preceding row,

    and hence the array is triangular. The following are the limitations of the routh’s stability

    criterion: 

    It is valid only if the characteristic equation is algebraic.

    1)  If any co-efficient of the characteristic equation is complex or contain power of ‘e’,

    this criterion can’t be applied.2)  It gives us information as to how many roots are lying in the right hand side of the s-

     plane. Values of the roots are not available. Also, it cannot distinguish between real

    and complex roots.

  • 8/16/2019 Pressure Instrument Trainer

    30/45

    Pressure Instrument Trainer 30

    CONDUCTING EXPERIMENT:

    DESCRIPTION:

    This section gives the functional details of the product, which is used to conduct the

    experiment. Functional details and control loop description enables us to understand the

    working principle of the product.

    PRESSURE CONTROL TRAINER (TYPE SCADA):

    The SCADA is basically an interfacing unit and is a medium for communicating with the

    equipment from the computer. In case of pressure controller, the pressure of air in process

    tank is sensed by the sensor, which is further transmitted into 4-20 mA which means that the

    current is 4mA for 0% pressure and 20mA for 100% pressure and are displayed on the

    interfacing unit in terms of 0 to 100%. These signals are further transmitted to the computer

    through this interfacing unit by using a RS-232C where the signals are displayed on the

    computer screen and the error signals, which are produced by the controller, are displayed on

    the interfacing unit. The output of the interfacing unit is then transmitted to the I/P converter,

    which converts it into 3 to 15 psi that means 3 psi for 4mA and 15 psi for 20mA.

    START UP:

    1.  All the drains should be closed.

    2.  Switch on the main supply.

    3.  Check whether all the valves are properly working or not.

    4.  Switch on computer and the interfacing unit.

    5.  Select the Auto mode to perform the experiment automatically and in Manual mode to

    change the values manually.

    6.  Connect the equipment with compressed air supply.

    SHUT DOWN:

    1.  Exit from the software.

    2.  Switch off the interfacing unit.

  • 8/16/2019 Pressure Instrument Trainer

    31/45

    Pressure Instrument Trainer 31

    Following experiments can be conducted with the product.

    Experiment No. 1. To study the open loop or manual control.

    Experiment No. 2.  To study the Proportional control.

    Experiment No. 3.  To study the Two mode (P+I) control.

    Experiment No. 4.  To study the Two mode (P+D) control.

    Experiment No. 5. To study the Three mode (PID) control.

    Experiment No. 6.  To study the tuning of controller (Open loop method) using

    Zeigler-Nichols method.

    Experiment No. 7.  To study the stability of the system using the BODE PLOT.

  • 8/16/2019 Pressure Instrument Trainer

    32/45

    Pressure Instrument Trainer 32

    EXPERIMENT NO. 1: OPEN LOOP (MANUAL) CONTROL.

    OBJECTIVE:

    To study the open loop or manual control.

    THEORY: 

    In these systems, the output remains constant for a constant input signal provided the

    external; conditions remain unaltered. The output may be changed to any desired value by

    appropriately changing the input signal but variations in external or internal parameters of the

    system may cause the output to vary from the desired value in an uncontrolled fashion. The

    open loop control is, therefore, satisfactory only if such fluctuations can be tolerated or

    system components are designed and constructed so as to limit parameter variations and

    environmental conditions as well as controlled, whereas in case of closed loop system, the

    controlled variable is measured and compared with reference input and the difference is used

    to control the elements.

    EXPERIMENTAL PROCEDURE:

    1.  Start up the setup as mentioned in the starting.

    2.  Select the manual mode.

    3.  Set the controller output to 100%.

    4.  Apply a step change of 10% to the controller output and wait for the PV to reach the

    steady state.

    5.  Repeat the above steps i.e. 2 and 3 until the output of the controller reaches to 0%

    temperature

    6.  Shut down the apparatus as mentioned in the starting..

  • 8/16/2019 Pressure Instrument Trainer

    33/45

  • 8/16/2019 Pressure Instrument Trainer

    34/45

    Pressure Instrument Trainer 34

     EXPERIMENT NO. 2: PROPORTIONAL CONTROL

    OBJECTIVE: 

    To study the proportional control (P control).

    THEORY:

    In order to get steady operation when the disturbances are absent, the controlled

    variable must be a continuous function of error. With proportional control, the most widely

    used type; the controller output is a linear function of the error signal. The controller gain is

    the fractional change in output divided by the fractional change in input.

    P = Kc* e -------------------------(1)

    Where,

    P = fractional change in controller output,

    E = SP-PV = fractional change in the error.

    K c = controller gain.

    Whereas the equation of the proportional controller output is given by

    P = Kc (SP – PV) + P0 -----------------------(13)

    Where P0 = bias i.e. the value of the controller output at zero error.

    In this experiment, the measured process value (PV) and set point (SP) is compared

    And the output of the controller is proportional to the resulting error signals.

    EXPERIMENTAL PROCEDURE:

    1.  Start up the set up as mentioned previously.

    2.  Select the controller in AUTO mode.

    3.  Set the value of Kc as high as possible.

    4.  Observe the process and the output response.

    5.  If output response doesn’t shows cycling, adjust the value of Kc to half of its previous

    value.

    6.  Repeat steps 4 and 5 until cycling is observed.

    7.  Then, increase the value of Kc to twice its value and observe the Output response.

    8.  Repeat step 7 until cycling is observed.

  • 8/16/2019 Pressure Instrument Trainer

    35/45

    Pressure Instrument Trainer 35

    9.  Record the value of Kc at which you observe the oscillations and record the

    overshoot.

    10.  Now increase the value of Kc in steps and observe the corresponding overshoots.

    11. Compare the relative overshoot with the value of Kc.

    OBSERVATIONS & CALCULATIONS: 

    1.  Observe that as the value of Kc increases, then the error or the difference between the

    SP and PV increases. In other words, as the error decreases, the proportional band

    decreases.

    2.  In case of proportional controller, the control system is able to arrest the rise of the

    controlled variable and ultimately bring it to rest at a new steady state value. The

    difference between this new steady state value and the original value is called

    OFFSET. There is always some offset present in case of proportional controller.

    T

    PV

    Kc=1

    T

    PV

    Kc=10

    T

    PV

    Kc=15

    T

    PV

    Kc=20

  • 8/16/2019 Pressure Instrument Trainer

    36/45

    Pressure Instrument Trainer 36

    EXPERIMENT NO. 3: TWO MODE (P+I) CONTROL

    OBJECTIVE:

    To study the steady state and transient response to a proportional + Integral control.

    THEORY:

    This mode of control is described by the relationship:

    )14(−−−−−−−−−−−−+∫+×=   Psedt Ti

     Kce Kc P   

    Where:

    Kc = gain

    e = error = (SP-PV)

    Ti = integral time, seconds

    Ps = constant

    P = output

    In this case, we have added to the proportional action term, Kc * e, another term that

    is proportional to the integral of the error.

    There is no offset with the integral control, since the output keeps changing as long as

    any error persists. However, the initial response to an error is slow and proportional control is

    ordinarily used with integral control. The integral action corrects for the offset that usually

    occurs with proportional control only, and the effect is similar to manual adjustment or

    resetting of the set point after each load change. The terms “ reset action” and “reset time” are

    widely used to characterize the integral action of a proportional – integral controller.

    )15()1

    (   −−−−−−−−−−−−−−−−−∫+=   edt Ti

    e Kc P   

    Where:

    Ti = reset time.

    Kc = gain

    e = error = (SP-PV)

    A small reset time corresponds to an increase in the integral action. With P action the

    measured value will not necessarily become equal to the set point and a deviation will usually

     be present. The control algorithm that applies changes in output as long as deviation exits, so

  • 8/16/2019 Pressure Instrument Trainer

    37/45

    Pressure Instrument Trainer 37

    as to bring the deviation to zero is called integral action. With integral action the parameters

    that determines how fast the output will change in corresponding to some amount.

    EXPERIMENTAL PROCEDURE:

    1.  Start up the setup as mentioned previously.

    2.  Select auto mode option for control.

    3.  Select a set point.

    4.  Select some value of Kc as described in proportional controller and Ti as high as

     possible.

    5.  Observe the response of the system. If over damped oscillations are occurring, then

    increase or decrease the corresponding values of Kc or Ti so as to make PV equal to

    SP.

    6.  Then, observe the output response curve. If on decreasing the value of either Ti or Kc

    makes the PV equal to SP, then continue decreasing the value until PV becomes

    nearly equal to SP.

    7.  After experimentation, switch off the apparatus as mentioned previously.

    OBSERVATIONS & CALCULATIONS:

    1. The addition of integral action nearly eliminates the offset and the controlled variable

    Ultimately returns to the original value.

    2. It is shown the fig., that the addition of integral action introduces an oscillatory

    motion in the system and with the increase in the value of the integral time, the

    difference between the SP and PV decreases.

    Tt

    PV

    Kc=10

    Ti=10

    Tt

    PV

    Kc=10

    Ti=5

    Tt

    PV

    Kc=10

    Ti=1

     

  • 8/16/2019 Pressure Instrument Trainer

    38/45

    Pressure Instrument Trainer 38

    EXPERIMENT NO. 4: TWO MODE (P+D) CONTROL

    OBJECTIVE:

    To study steady state and transient response to a proportional + derivative control.

    THEORY:

    This mode of control may be represented by:

    P = Kc* e + Kc Td de/dt --------------(16)

    Where Kc = gain

    Td = derivative time, seconds

    In this case, we have added to the proportional term another term, KcTd (de/dt) that is

     proportional to the derivative of the error. Other terms that are used to describe the derivative

    action are rate control  and anticipatory control .

    Derivative action is often added to proportional control to improve the response of

    slow systems. By increasing the output when the error is changing rapidly, derivative action

    anticipates the effect of large load changes and reduces the maximum error.

    Larger the derivative time larger is the action. Smaller is the proportional band the larger is

    the derivative action.

    EXPERIMENTAL PROCEDURE:

    1.  Start up the setup as mentioned previously.

    2.  Select auto mode option for control.

    3.  Select a set point.

    4.  Select some value of Kc as described in the proportional controller and the value of

    Td to the minimum value.

    5.  Observe the response of the system. If over damped oscillations are occurring, then

    reduce the value of Td to half of its previous value so as to make PV equal to SP.

    6.  Then, observe the output response curve and double the value of Td in order to make

    PV equal to SP, then continue decreasing the value until PV becomes equal to SP.

    7.  After experimentation, switch off the apparatus as mentioned previously.

  • 8/16/2019 Pressure Instrument Trainer

    39/45

    Pressure Instrument Trainer 39

    OBSERVATIONS & CALCULATIONS:

    1.  The derivative action is added to improve the response of the slow system.

    2.  The addition of derivative action to the PI action gives a definite improvement in theresponse. The rise of controlled variable is arrested more quickly and it is returned

    rapidly to the original value with little or no oscillations.

  • 8/16/2019 Pressure Instrument Trainer

    40/45

    Pressure Instrument Trainer 40

    EXPERIMENT NO. 5: THREE MODE (PID) CONTROL

    OBJECTIVE:

    To study the steady state and transient response to a Proportional + Integral + Derivative.

    THEORY:

    This mode of control is described by the relationship

    )17(−−−−−−−−−−−−−+×+∫+×=   Psdt 

    deeTd  Kcedt 

    Ti

     Kce Kc P   

    Where:

    e = error = (SP-PV)

    K c  = gain

    Td is derivative time, Ti is integral time and Kc=proportional gain

    EXPERIMENTAL PROCEDURE:

    1.  Start up the setup as mentioned earlier.

    2.  Select auto mode option for control.3.  Select a set point.

    4.  Select some value of Kc, Ti and Td.

    5.  Observe the response of the system. If over damped oscillations are occurring, then

    increase or decrease the corresponding values of Kc, Ti and Td so as to make PV

    equal to SP.

    6.  Then, observe the output response curve. If on decreasing the value of either Kc, Ti,

    Td makes the PV equal to SP, then continue decreasing the value until PV becomes

    equal to SP.

    7.  After experimentation, switch off the apparatus

    8.  Using trail and error, select the proportional gain and integral time, which gives a

    satisfactory response to step change in set point.

    9.  Set the derivative time to a non-zero value and carry out the above steps for different

    derivative time values.

    10. After experimentation shut down the setup as mentioned earlier.

  • 8/16/2019 Pressure Instrument Trainer

    41/45

    Pressure Instrument Trainer 41

    OBSERVATIONS & CALCULATIONS:

    The addition of derivative action to the PI action gives a definite improvement in the

    response. The rise of controlled variable is arrested more quickly and it is returned rapidly to

    the original value with little or no oscillations.

    T

    PV

    Kc=10Ti=1Td=10

    T

    PV

    Kc=10Ti=1Td=5

    T

    PV

    Kc=10Ti=1

    Td=1

  • 8/16/2019 Pressure Instrument Trainer

    42/45

    Pressure Instrument Trainer 42

    EXPERIMENT NO.6: TUNING OF CONTROLLER (OPEN LOOP

    METHOD) 

    OBJECTIVE:

    To study the tuning of PID controller by open loop method, using Zeigler- Nichols

    tuning rules.

    THEORY:

    This method is basically used to calculate the value of P, I, D using the open loop or

    manual control method. The values of P, I, D are selected in such a way that the error or the

    difference between the SP and PV should become equal to zero.

    Since we are not given with the plant equation. So the process is assumed to be of first

    order with steady state gain Kc, integral time Ti and derivative time td. The step response i.e.

     process reaction curve, allows to obtain the approximate values of each parameter. With the

    feedback loop open, a step response is applied to manipulated variable and the values of P, I

    and D are estimated.

    The delay time L and time constant T are determined by drawing a tangent line at the

    inflection point of a S-shaped curve and determining the intersections of the tangent line with

    the time axis and line c (t) = K as shown in the figure obtained by performing the experiment.

    S Shaped Response Curve

    Figure : 7

    Tangent Line atInflection point

    TimeL   T

    0

    K

    C(t)

     

  • 8/16/2019 Pressure Instrument Trainer

    43/45

    Pressure Instrument Trainer 43

    For P, PI and PID controller the parameters are calculated as follows:

    Mode Proportional Integral Derivative

    P T/L INFINITY 0

    P+I 0.9T/L L/0.3 0

    P+I+D 1.2T/L 2L 0.5L

    EXPERIMENTAL PROCEDURE:

    1.  Start up the set up as mentioned.

    2.  Select open loop option for control.

    3.  Select the value of the set point to some desired value.

    4.  Apply a 20-30% change to controller output. Record the step response. Wait for the

    steady state.

    5.  Start data logging and from the readings draw a step response curve.

    6.  Calculate the value of Td and L.

    7.  From this, calculate the values of PID controller settings from the table.

    8.  After experimentation, shut down the set up.

    OBSERVATIONS & CALCULATIONS: 

    Tabulate the data from stored file as follows:

    Observation No. Time in sec. Process Value (%)

    1.

    2.

    3.

    4.

    Calculate the value of the P, D and I from the table given in the theory part of this

    experiment.

  • 8/16/2019 Pressure Instrument Trainer

    44/45

    Pressure Instrument Trainer 44

     EXPERIMENT NO. 7: TO STUDY THE STABILITY OF A 

    SYSTEM

    OBJECTIVE:

    To study the stability of the system by plotting the bode plots. 

    THEORY:

    A convenient method of presenting the response of the data at various frequencies is

    to use a log-log plot for the amplitude ratios, accompanied by the semi log plot for the phase

    angles. Such plots are called BODE PLOT. Plotting of BODE plot is relatively easier as

    compared to other methods as the loci of (1 + sT) and K/(1 + sT) can be represented by

    straight line asymptotes.

    In case of Bode plot, multiplication is converted into addition, so if

    G(s) = K/(1 + sT)

    And putting s = jw,

    Then 20 log [G (w)] = 20 log K– 20 log [1 + jwt].

    In case of Bode plot, study of relative stability is easier as parameters of analysis of

    relative stability are gain and phase margin, which are visibly seen on the sketch.

    The transfer function for a first order system is given by

    1)(

    +=

    Tds

    ke sG

     Ls

     

    The amplitude ratio of the above equation can be written as

    2

    1

    22 )1(

    1..

    T w

     R A

    +

    =  

    The phase angle is always negative for a first order system and this negative angle is

    called “phase lag”.

    STABILITY CRITERIA:

    1.  A system is stable if the phase lag is less than 180 degree at the frequency for which

    the gain is unity.

  • 8/16/2019 Pressure Instrument Trainer

    45/45

    2.  A system is stable if the gain is less than unity at the frequency for which the phase

    lag is 180.

    EXPERIMENTAL PROCEDURE:

    1.  Rewrite the sinusoidal transfer function in the time constant form.

    2.  Identify the corner frequencies associated with each factor of the transfer function.

    3.  Knowing the corner frequency, draw the asymptotic magnitude plot. This plot

    consists of a straight line segments with the line slope changing at each corner

    frequency by +20 db/decade for a zero and –20 db/decade for a pole For a complex

    conjugate zero or pole the slope changes by +/- 40 db/decade.

    4.  Draw a smooth curve through the corrected point such that it is asymptotic to the

    straight-line segments. This gives the actual log-magnitude plot.

    5.  Draw the phase angle curve for each factor and add them algebraically to get the

     phase plot.

    6.  The ultimate gain value i.e. Wco is that value when the phase angle curve crosses the

    180 degree line and the corresponding gain value is called the ultimate gain i.e. Ku.

    7.  By using these two gains the other parameters that are the values of

    P, D and I are calculated from the table given in the theory part of the Zeigler’s closed

    loop method.

    OBSERVATIONS & CALCULATIONS:

    1.  Draw the graphs of Magnitude Vs frequency on log-log scale.

    2.  Draw the graphs of Phase angle Vs frequency on semi log co-ordinates.

    3.  Compare the values calculated from Zeigler open loop and this Bode plot.

    4.  The first order system will be stable only if the phase angle Vs frequency graph has

    negative phase lag.