    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 1 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    User ManualProfiHub A5/B5

    5 Channel DP Spur and Repeater component

    5 Isolated Channels.Transparent for all PROFIBUS DP protocols. RS 485 specifications for each Channel.Max. 12 Mbps .Max. 31 devices per Channel.Max. 1.200 m spur line length .

    No limit in serial placement.No Address is required.

    Integrated termination facilities.Configurable grounding system.

    IP 65 classification (ProfiHub A5).IP 20 classification (ProfiHub B5).

    distributed by:

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    2/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 2 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    Safety GuidelinesThis manual contains notices which you should observe to ensure your own personal safety, as wellas to protect the product and connected equipment. These notices are highlighted in the manual by a

    warning sign and are marked as follows according to the level of danger:

    Draws your attention to important information on handling the product, a particular part of thedocumentation or the correct functioning of the product.

    WarningThis device and its components may only be used for the applications described in this manual andonly in connection with devices or components that comply with PROFIBUS and RS 485 interface.This product can only function correctly and safely if it is transported, stored, set up, installed,operated and maintained as recommended.

    Qualified TechniciansOnly qualified technicians should be allowed to install and work with this equipment. Qualifiedtechnicians are defined as persons who are authorized to commission, to ground, and to tag circuits,equipment, and systems in accordance with established safety practices and standards. It isrecommended that the technicians carry a Certified PROFIBUS Installer or Certified PROFIBUSEngineer certificate.

    Disclaimer of LiabilityWe have checked the contents of this manual as much as possible. Since deviations cannot beprecluded entirely, we cannot guarantee full agreement. However, the content in this manual isreviewed regularly and any necessary corrections included in subsequent editions. Suggestions forimprovement are welcomed.

    Copyright October 2006 PROCENTEC All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, ortransmitted, in any form or by any means, electronic, mechanical, photocopying, recording orotherwise, without the prior written permission of the publisher.

    PROCENTECTurfschipper 412292 JC WATERINGENThe Netherlands

    Tel.: +31-(0)174-671800Fax: +31-(0)174-671801Email: [email protected]: www.procentec.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    3/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 3 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    Important Information

    Purpose of the ManualThis manual explains how to put the ProfiHub A5 and ProfiHub B5 into operation.

    Recycling and DisposalThe parts of the ProfiHub can be recycled. For further information about environment-friendly recyclingand the procedure for disposing of your old equipment, please contact:

    PROCENTECTurfschipper 412292 JC WATERINGENThe Netherlands

    Tel.: +31-(0)174-671800Fax: +31-(0)174-671801Email: [email protected]

    Document UpdatesYou can obtain constantly updated information on PROCENTEC products on the Internet athttp://www.procentec.com You can also contact PROCENTEC Customer Support:- by phone at +31-(0)174-671800 or- by fax at +31-(0)174-671801 or- by email at [email protected]

    1630 W Diehl Rd Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    4/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 4 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    Contents

    1 Product Description...................................................................................................................... 5 1.1 Product Features.................................................................................................................... 6 1.2 Application areas.................................................................................................................... 7 1.3 Additional Benefits ................................................................................................................. 7 1.4 Channel Structure .................................................................................................................. 8 1.5 Grounding System ................................................................................................................. 8 1.6 Cable lengths for PROFIBUS DP .......................................................................................... 9 1.7 Cable types for PROFIBUS DP............................................................................................ 10 1.8 Status Display ...................................................................................................................... 11 1.9 Comparison table ................................................................................................................. 12

    2 Installation Instructions ProfiHub A5 ....................................................................................... 13 2.1 Location................................................................................................................................ 13 2.2 Position................................................................................................................................. 13 2.3 Mounting............................................................................................................................... 13 2.4 Power Supply ....................................................................................................................... 14 2.5 Backbone ............................................................................................................................. 15 2.6 Spur Segments .................................................................................................................... 16 2.7 Termination .......................................................................................................................... 17 2.8 Baudrate switch.................................................................................................................... 18

    3 Installation Instructions ProfiHub B5 ....................................................................................... 19 3.1 Location................................................................................................................................ 19 3.2 Position................................................................................................................................. 19 3.3 Mounting............................................................................................................................... 19 3.4 Power Supply ....................................................................................................................... 19 3.5 Backbone ............................................................................................................................. 20 3.6 Spur Segments .................................................................................................................... 21 3.7 Termination .......................................................................................................................... 22 3.8 Baudrate switch.................................................................................................................... 23

    4 Technical Data ProfiHub A5....................................................................................................... 24

    5 Technical Data ProfiHub B5....................................................................................................... 26

    6 Order codes................................................................................................................................. 28

    7 Glossary....................................................................................................................................... 30

    8 Revision History.......................................................................................................................... 33

    9 Next version ................................................................................................................................ 34

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    5/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 5 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    1 Product Description

    ProfiHub A5 and B5 are advanced, flexibleand robust network components forPROFIBUS DP installations, which makes itpossible to implement long multi-device spurlines and backbone structures with star/treesegments.

    PROFIBUS DP is a high speed communicationbus that has to comply with strict rulesconcerning spur lines, because of possiblereflections that could lead to communicationdisturbances. If spur lines or star segments arerequired, costly investments in repeaters have tobe done.

    Innovative components for such applications arethe ProfiHub A5 and B5. These are perfecteconomic solutions to implement reliable spurlines in high speed DP networks. They have thefunctionality of 5 galvanic isolated transparentrepeaters . This allows network structures withextended spur lines that individually can handle amaximum of 31 devices and a length equal to themain bus. The ProfiHub A5 and B5 refresh areceived message on one Channel andtransfer it to all the other Channels (chickenfoot topology).

    Because the ProfiHub A5 and B5 create isolatedsegments, the devices can now be removed andadded during operation. Also electrical busproblems and EMC disturbances in a spur do notspread to the other segments. The intelligent logicand isolation circuits of the ProfiHubs do notchange the bit width. This means the ProfiHubsdo not have limitations in serial placement. Thelogic also detects the transmission speedautomatically.

    To assist the installation work, termination isintegrated and can be switched on/off. Thegrounding concept is also selectable: direct orcapacitive grounding. The ProfiHubs are powered by a 10 to 32 DC Voltage (110/230V AC versionsare also available). For troubleshooting, maintenance and commissioning the ProfiHubs are equippedwith a display on the outside, which indicate the status of each Channel (Data and Error).

    Fig. 1 - ProfiHub A5

    Fig. 2 - ProfiHub B5

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    6/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 6 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    1.1 Product Features

    5 Galvanic isolated Channels (repeatersegments).

    Transparent for all PROFIBUS DPprotocols.

    DP - RS 485 specifications for eachChannel.

    9,6 Kbps to 12 Mbps .

    31 devices per Channel. 1.200 m spur line length (depends ontransmission speed).

    No limit in serial placement or cascading of ProfiHubs.

    No Address is required.

    Integrated termination facilities (switches).

    Configurable grounding system (direct or capacitive).

    IP 65 classification (ProfiHub A5).

    IP 20 classification (ProfiHub B5).

    Fig. 3 - Long spur lines to instruments and the possibility to remove/insert them duringoperation. Short circuit protection on each spur line is automatically provided.

    DP backbone

    Each spur linecan be 200 mat 1,5 Mbps.

    Wiring problemsdo not spread tothe other spurlines.

    Channel 1 to 5Channel 1 to 5

    Power supplyPower supply

    Intelligent Internal Backbone

    C5C4C3C2C1Main

    Bus

    Intelligent Internal Backbone

    C5C4C3C2C1Main

    Bus

    Main bus InMain bus InMain bus OutMain bus Out

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    7/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 7 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    1.2 Application areas

    Dynamic spur lines to actuators, flow meters and pH analyzers. Removable drives and motors. Pull/Plug motor control centers (drawers). Roof mounted devices in Tank Parks. Dirty and Humid environments. Barrier for non galvanic isolated equipment. Large star/tree structured networks. Outdoor applications with device and cable stress (ProfiHub A5).

    1.3 Additional Benefits

    Hot slave insertion and removal during operation. Short circuit protection on each Channel. Compact and robust construction. Status and error display (per Channel). Suitable for all DP cables. Conveniently arranged networks. Easy extendable installations. Standard glands can be replaced with M12 (ProfiHub A5).

    On-board DB9 female connector for maintenance activities (ProfiHub A5). Cost Savings.

    Noisy signalNoisy signal

    Clean signalClean signal

    Fig. 4 - Because of the isolation and intelligence the ProfiHub provides, it can be used asa barrier for electrically sensitive segments. This keeps the backbone and otherChannels clean.

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    8/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 8 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    1.4 Channel Structure

    Every Channel is electrically isolated and is internally connected to the transparent intelligentbackbone. The termination is switchable and is being powered by the ProfiHub. The shielding of thePROFIBUS cable can be directly grounded or indirectly grounded (see the next paragraph).

    1.5 Grounding System

    The ProfiHubs can be grounded by 3 methods:1) Direct grounding

    2) Indirect grounding (through a capacitor)3) A combination of direct and indirect.

    In most cases it is recommended always to use Direct Grounding with the power supply and theshielding of the PROFIBUS cables. If you do not want to ground all or some cables to the commonground, the cable shielding should be connected to pin I. A capacitor with a parallel high valueresistor will separate the 2 potentials ( Fig. 5 ).If by accident on 1 channel the Direct Grounding is connected with the Indirect Grounding, the DirectGrounding wins.

    Fig. 5 - Channel structure

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    9/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 9 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    1.6 Cable lengths for PROFIBUS DP

    The cables on the Channels and the Main-Channel should comply with the PROFIBUS DP cablespecifications for RS 485 ( Fig. 6 ).

    Baudrate (kbit/s)

    Segment length(m)

    9.6

    1200 1200

    19.2 1500 6000 120003000500187.593.7545.45

    100100100200400100012001200

    Segment length(feet)

    3940 3940 3283283286561310328039403940

    Baudrate (kbit/s)

    Segment length(m)

    9.6

    1200 1200

    19.2 1500 6000 120003000500187.593.7545.45

    100100100200400100012001200

    Segment length(feet)

    3940 3940 3283283286561310328039403940

    Baudrate (kbit/s)

    Segment length(m)

    9.6

    1200 1200

    19.2 1500 6000 120003000500187.593.7545.45

    100100100200400100012001200

    Segment length(feet)

    3940 3940 3283283286561310328039403940

    DeviceDevice Device Device Device Device

    Maximum 31 devices

    Example: 1000 m cable per channel at 187,5 kbps

    Other channelsWith the sameCable length

    Fig. 6 - Cable lengths for PROFIBUS DP

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    10/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 10 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    1.7 Cable types for PROFIBUS DP

    The cable type should comply with the PROFIBUS DP cable specifications for RS 485 ( Fig. 7 ).

    The ProfiHub A5 can handle cables based on multiple protection sheaths with a diameter between 6 to

    12 mm ( Fig. 8 ).

    Parameter Value

    Wires 2 (twisted)

    Impedance 135 .. 165 Ohm at 3 to 20 MHz

    Capacity < 30 pF/m

    Loop resistance < 110 Ohm/km

    Wire diameter > 0.64 mm

    Wire area > 0.32 mm 2

    FRNC cable

    Shipboard cable

    Festoon cable

    Flexible cable

    Food cable

    Robust cable

    Trailing cable

    Hybrid cable

    Fig. 8 - Cables with different protection sheaths.

    Fig. 7 - PROFIBUS DP cable specifications

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    11/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 11 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    1.8 Status Display

    The Status Display on the ProfiHubs is very useful for diagnostics.

    OFF Blinking ON

    POWER Power is notswitched on or aninternal failure.

    Power supply notstable or an internalfailure.

    Power supply OK.

    Main READY Power is notswitched on or aninternal failure.

    Trying to detect thetransmission speed, buthas not locked it yet.

    The transmissionspeed has beendetected.

    Main RX-OK No communicationdetected on the Main-Channel.

    1 or more devicescommunicating on theMain-Channel.

    1 or more devicescommunicating on theMain-Channel.

    Main ERROR No problem hasbeen detected.

    Problem in thecabling has beendetected (MainChannel).

    Problem in thecabling has beendetected (MainChannel).

    Channel RX-OK There is no

    communicationdetected (on thisChannel).

    1 or more devices

    communicating (on thisChannel).

    1 or more devices

    communicating (on thisChannel).

    Channel ERROR No problem hasbeen detected.

    Problem in thecabling has beendetected (on thisChannel).

    Problem in thecabling has beendetected (on thisChannel).

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    12/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 12 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    1.9 Comparison table

    ProfiHub A5 ProfiHub B5

    Area IP 65 IP 20

    Housing Plastic Metal

    Mounting Corner screws DIN-rail

    Weight 800 g 650 g

    Dimensions 213 x 210 x 95 mm 167 x 111 x 32 mm

    PROFIBUS connectors Screw terminals (inside)Glands (outside)

    Screw terminals and DB9 connectors

    Alternative connectors Glands can be replaced withM12 connectors (see chapter6 Order codes)

    No

    Termination LEDs No Yes

    Ground rail Optional (see chapter 6 Ordercodes)

    Yes

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    13/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 13 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    2 Installation Instructions ProfiHub A5

    2.1 Location

    The ProfiHub A5 can be installed everywhere in a non-hazardous area that complies with IP 65 (DIN40 050) and the specified temperature range of -40 to +75 o Celsius.

    2.2 Position

    The ProfiHub A5 can be installed in every position, but it is recommended to install it with the cableglands pointing down to create a more reliable protection against moist and dust (water compartment

    and glands). In this position it is also easier to read the status display.

    2.3 Mounting

    The ProfiHub A5 has 4 mounting holes for 4..5 mm screws ( Fig. 9 ). To reach the holes on position 1and 2, the top lid has to be removed.

    1) It is recommended to mount the ProfiHub A5 with at least 4 suitable screws/bolts in position

    1, 2, 3 and 4. 2) Be careful with the flat cable that connects the lid with the PCB.

    1 2

    3 4

    Fig. 9 - Positions of the mounting holes.

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    14/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 14 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    2.4 Power Supply

    The 4-pin screw type power connector is located on the bottom left of the PCB ( Fig. 10 ).

    The power supply has to comply with the following specifications:- Voltage: 10 to 32 Vdc

    - Current: Min. 130 mA- Wire diameter: < 2,5 mm 2 - Cable thickness: 5 to 10 mm

    ProcedureTo connect the 24V supply to the 4-pin screw-type terminal, proceed as follows:- Strip the insulation from the cable or the conductors for the 24V power supply.- Secure the conductors in the screw-type terminal.Note: There is a grounding point that can be used.

    To connect the power supply, you need a 3 mm screwdriver.

    TestingIf the power is switched on it can be diagnosed by the following indicators on the PCB:- All the LEDs should be shortly blinking.- The READY LED is ON or Blinking.- The voltage LEDs are ON (5V, 3V3 and 1V8).

    It is recommended to use a power supply with a ground lead (3-wire).

    Power Connector

    Power LEDs

    Fig. 10 - Power connector and LEDs

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    15/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 15 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    2.5 Backbone

    Connect the DP backbone cable to the bottom connector of the Main-Channel ( Fig. 11 ). If the ProfiHubis not the last device on the bus segment, connect the Bus-Out cable to the top connector of the Main-Channel ( Fig. 11 ).

    Pin Layout of the screw terminalsPin A: Green wirePin B: Red wirePin I: Cable shielding OR Pin : Cable shielding

    Testing- If the Main-Channel recognizes valid PROFIBUS messages from 1 or more connected devices, theRX-OK LED of this Channel should be blinking.

    Bus-InConnector

    Communication statusLEDs

    Bus-OutConnector

    Fig. 11 - PROFIBUS DP backbone connection

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    16/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 16 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    2.6 Spur Segments

    Connect the spur segments to the connectors of Channel 1 to 5 ( Fig. 12 ).

    Pin Layout of the screw terminalsPin A: Green wirePin B: Red wirePin I: Cable shielding OR Pin : Cable shielding

    TestingIf a Channel recognizes valid PROFIBUS messages from 1 or more connected devices, the RX-OKLED of the specific Channel should be blinking.

    ChannelConnectors

    Communication status LEDs

    ChannelConnectorsChannelConnectorsChannelConnectorsChannelConnectors

    Fig. 12 - PROFIBUS DP spur connectors

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    17/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 17 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    2.7 Termination

    The termination of the Main-Channel has been set to OFF by default. If the ProfiHub is the last/firstdevice on the segment, the termination should be set to ON ( Fig. 13 ).

    The termination of the Channels have been set to ON by default. Because it is assumed that the newsegment is started at the ProfiHub ( Fig. 13 ).

    Dont forget to switch the termination ON at the other end of the segment and make sure it is

    powered continuously.

    Channel

    Connectors

    Termination of the MainChannel (Default set to

    OFF)

    Channel

    Connectors

    Channel

    Connectors

    Channel

    Connectors

    Termination of theChannels (Default set

    to ON)

    Fig. 13 - Termination Switches

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    18/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 18 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    2.8 Baudrate switch

    The ProfiHub recognizes the transmission speed by default. If it is required that the ProfiHub is lockedto a certain transmission speed, switch S100 should be set to the required value ( Fig. 14 ). The switchcan be reached by removing the top lid.

    To set the transmission speed, you need a 3 mm screwdriver.

    Switch values:0 = Auto detect ( default )1 = 9,6 kbps2 = 19,2 kbps3 = 45,45 kbps4 = 93,75 kbps5 = 187,5 kbps6 = 500 kbps7 = 1500 kbps8 = 3000 kbps

    9 = 6000 kbps A = 12000 kbpsB .. F = Auto detect

    Baudrate switch

    Fig. 14 Baudrate speed switch

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    19/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 19 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    3 Installation Instructions ProfiHub B5

    3.1 Location

    The ProfiHub B5 can be installed everywhere in a non-hazardous area that complies with IP 20 (DIN40 050) and the specified temperature range of -20 to +60 o Celsius.

    3.2 Position

    The ProfiHub B5 can be installed in every position, but it is recommended to install it with the cablespointing down. In this position it is also easier to read the status display.

    3.3 Mounting

    The ProfiHub B5 has to be mounted on 35 mm DIN-rail with a minimum width of 167 mm.

    3.4 Power Supply

    The 3-pin screw type power connector is located on the bottom left of the ProfiHub B5 ( Fig. 15 ).1 = + (left)2 = - (middle)3 = Indirect grounding (right)

    The power supply has to comply with the following specifications:- Voltage: 10 to 32 Vdc- Current: Min. 130 mA- Wire diameter: < 2,5 mm 2

    Fig. 15 - Power connector and LEDs

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    20/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 20 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    ProcedureTo connect the 24V supply to the 3-pin screw-type terminal, proceed as follows:

    - Strip the insulation from the cable or the conductors for the 24V power supply.- Secure the conductors in the screw-type terminal.Note: There is a grounding point that can be used.

    To connect the power supply, you need a 3 mm screwdriver.

    TestingIf the power is switched on it can be diagnosed by the following indicators:- All the LEDs should be shortly blinking.- The POWER LED is ON.- The READY LED is ON or Blinking.

    It is recommended to use a power supply with a ground lead (3-wire).

    3.5 Backbone

    Connect the DP backbone cable to the bottom-left connector of the Main-Channel ( Fig. 16 ). If theProfiHub is not the last device on the bus segment, connect the Bus-Out cable to the right connectorof the Main-Channel ( Fig. 16 ). The second method is to place a PROFIBUS standardized plug with anin/out cable on the DB9 connector.

    Pin layout of the screw terminals:Pin A: Green wirePin B: Red wirePin I: Cable shielding OR Pin : Cable shielding

    Fig. 16 - PROFIBUS DP backbone connection

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    21/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 21 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    Testing

    - If the Main-Channel recognizes valid PROFIBUS messages from 1 or more connected devices, theRX-OK LED of this Channel should be blinking.

    3.6 Spur Segments

    Connect the spur segments to the connectors of Channel 1 to 5 ( Fig. 17 ). The second method is toplace a PROFIBUS standardized plug on the DB9 connector of the specific Channel.

    Pin layout of the screw terminals:Pin A: Green wirePin B: Red wirePin I or Ground: Cable shieldingNote: Connecting the cable shielding is not required when the ground clips are used.

    Testing- If the Main-Channel recognizes valid PROFIBUS messages from 1 or more connected devices, theRX-OK LED should be blinking.

    Fig. 17 - PROFIBUS DP spur connectors

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    22/36

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    23/36

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    24/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 24 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    4 Technical Data ProfiHub A5

    Technical Data ProfiHub A5

    Dimensions and weight

    Dimensions L x W x H (mm) with glandsWeightMounting screws

    213 x 210 x 95 mm Approximately 800 g4 to 5 mm

    Ambient conditions

    Operating temperatureIsolation class -40 to +75o

    CelsiusIP 65 (DIN 40 050)

    Protocol specifications

    Supported Protocols

    Transmission speedTransmission speed detectionTransmission speed switch

    Transmission speed detection time

    Data delay time

    Delay time jitter

    DP-V0, DP- V1, DP-V2, FDL, MPI, FMS, PROFIsafe,PROFIdrive and any other FDL based protocol.

    9,6 kbps to 12 Mbps (including 45,45 kbps) Auto detect (default) or settable with a rotary switch0 = Auto detect (default)1 = 9,6 kbps

    2 = 19,2 kbps3 = 45,45 kbps4 = 93,75 kbps5 = 187,5 kbps6 = 500 kbps7 = 1500 kbps8 = 3000 kbps9 = 6000 kbps

    A = 12000 kbpsB .. F = Auto detect

    < 10 s (if it is set to auto detect)

    1,25 TBit at 9,6 kbps to 93,75 kbps1,3 TBit at 187,5 kbps to 500 kbps1,4 TBit at 1,5 Mbps1,6 TBit at 3 Mbps2,0 TBit at 6 Mbps3,0 TBit at 12 Mbps

    Max. bit time

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    25/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 25 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    Technical Data ProfiHub A5

    PROFIBUS cable specifications

    Cable lengths

    Cable thicknessWire diameterWire type

    Number of devices

    Termination

    Cascading depthRedundancy

    1.200 m at 9,6 kbps to 93,75 kbps1.000 m at 187,5 kbps400 m at 500 kbps200 m at 1,5 Mbps100 m at 3 Mbps to 12 Mbps

    6 to 12 mm< 2,5 mm 2 Stranded or Solid core

    Maximum 31 per Channel (including ProfiHubs, OLMs,Laptops/PCs, etc)

    Integrated and switchable.Powered according to IEC 61158 (390/220/390 Ohms)- All Channels (default on)- Main-Channel (default off)

    No limitsNo

    Power supply specifications

    Nominal supply voltageCurrent consumptionPower dissipation

    Reverse polarity protectionCable thicknessWire diameter

    10 to 32 Vdc130 mA at 24 V power supply (all Channels fully loaded)Max. 4,1 W

    Yes5 to 10 mm< 2,5 mm 2

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    26/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 26 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    5 Technical Data ProfiHub B5

    Technical Data ProfiHub B5

    Dimensions and weight

    Dimensions L x W x H (mm) with screwsWeight

    167 x 111 x 32 mm Approximately 650 g

    Ambient conditions

    Operating temperature

    Isolation class

    -20 to +60 o Celsius

    IP 20 (DIN 40 050)

    Protocol specifications

    Supported Protocols

    Transmission speedTransmission speed detectionTransmission speed switch

    Transmission speed detection time

    Data delay time

    Delay time jitter

    DP-V0, DP- V1, DP-V2, FDL, MPI, FMS, PROFIsafe,PROFIdrive and any other FDL based protocol.

    9,6 kbps to 12 Mbps (including 45,45 kbps) Auto detect (default) or settable with a rotary switch0 = Auto detect (default)1 = 9,6 kbps2 = 19,2 kbps

    3 = 45,45 kbps4 = 93,75 kbps5 = 187,5 kbps6 = 500 kbps7 = 1500 kbps8 = 3000 kbps9 = 6000 kbps

    A = 12000 kbpsB .. F = Auto detect

    < 10 s (if it is set to auto detect)

    1,25 TBit at 9,6 kbps to 93,75 kbps1,3 TBit at 187,5 kbps to 500 kbps1,4 TBit at 1,5 Mbps1,6 TBit at 3 Mbps2,0 TBit at 6 Mbps3,0 TBit at 12 Mbps

    Max. bit time

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    27/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 27 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    Technical Data ProfiHub B5

    PROFIBUS cable specifications

    Cable lengths

    Cable thicknessWire diameterWire type

    Number of devices

    Termination

    Cascading depthRedundancy

    1.200 m at 9,6 kbps to 93,75 kbps1.000 m at 187,5 kbps400 m at 500 kbps200 m at 1,5 Mbps100 m at 3 Mbps to 12 Mbps

    10 mm (when the ground rail is used)< 2,5 mm 2 Stranded or Solid core

    Maximum 31 per Channel (including ProfiHubs, OLMs,Laptops/PCs, etc)

    Integrated and switchable.Powered according to IEC 61158 (390/220/390 Ohms)- All Channels (default on)- Main-Channel (default off)

    No limitsNo

    Power supply specifications

    Nominal supply voltageCurrent consumptionPower dissipation

    Reverse polarity protectionCable thicknessWire diameter

    10 to 32 Vdc130 mA at 24 V power supply (all Channels fully loaded)Max. 4,1 W

    Yes10 mm (when the ground rail is used)< 2,5 mm 2

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    28/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 28 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    6 Order codes

    Component Order code Remarks

    ProfiHub A5

    16010 Includes mounting set.

    Ground rail

    16011 The ground rail has to be mounted inside the casing tosupply a common grounding area for all cableshielding. It improves the EMC behaviour and itsupplies a good construction for vibrations. Not useablefor capacitive grounding!

    M12 female flange set

    16012 Set of 5 pieces (female).

    ProfiHub B5

    17010 --

    Standard DP cable 2170220 - 1 x 2 x 0,64 mm (8 mm)- Solid conductors- PVC

    Standard DP cable FCUL/CSA

    2170820 - 1 x 2 x 0,64 mm (8 mm)- Solid conductors- PVC- Fast Connect- UL

    Flexible DP cableHalogen free

    2170222 - 1 x 2 x 0,25 mm2 (8 mm)- Stranded conductors- PUR- Halogen free

    Flexible DP cable FCUL/CSA

    2170322 - 1 x 2 x 0,67 mm (8 mm)- Stranded conductors- PUR- Fast Connect

    - UL

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    29/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 29 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    Component Order code Remarks

    DP ground cable 2170223 - 1 x 2 x 0,64 mm (10,8 mm)- Solid conductors- PVC- UV

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    30/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 30 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    7 Glossary

    Address Unique number of a station connected to a segment (participant). WithPROFIBUS this can be 0 to 126.

    Backbone The primary bus cable. Most of the time only the control systems, ProfiHubsand fiber optic couplers are connected to this cable. The field devices areconnected behind the ProfiHubs and fiber optic couplers.

    Bit Time (TBit) The bit time TBit is the time, which elapses during the transmission of onebit. It depends on the Transmission speed and is calculated as follows TBit =1 (bit) / Transmission speed (bit/s).Examples:12 Mbps --> TBit = 83 ns1,5 Mbps --> TBit = 667 ns

    Bus Analyzer Software tool to observe the protocol traffic.Other term: Bus Monitor.Example: ProfiTrace.

    C Capacitance.

    DGND Digital Ground.

    DIN German Institute for Standardization (www.din.de).

    DP-V0 DP-V0 is the basic stage of the PROFIBUS DP communication protocol. DP-V0 devices (master and slaves) perform the following basic functionalities:- Cyclic exchange of I/O data between controlling and slave devices- Device, Identifier (module) and Channel related Diagnosis- Parameterization of DP-slaves- Configuration of DP-slaves

    DP-V1 DP-V1 is the first stage of extension of PROFIBUS DP after DP-V0. DP-V1devices shall comply with the following features:- Device related diagnosis is replaced by status and alarms.- The first three octets of the user parameterization data are nowstandardized- Optionally these devices may support:- Acyclic communication (MS1, MS2)- If alarms are used, MS1 shall be supported

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    31/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 31 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    DP-V2 DP-V2 is the second stage of extension of PROFIBUS DP after DP-V1. DP-V2 devices shall comply with the following features:- Data Exchange Broadcast (DxB) for slave to slave communication(publisher/subscriber principle).- Isochronous Mode (time tick synchronized operating slaves, e.g. drives)- Up- and/or download of Load Region Data (domains)- Function Invocation- Clock Control (synchronization within slaves) and Time Stamping- Redundancy

    ElectromagneticCompatibility (EMC)

    The extent to which an electric or electronic device will tolerate electricalinterference from other equipment (immunity), and will interfere with otherequipment. Within the European Community as well as in other countries it isregulated by law that electric and electronic components and equipmentcomply with basic standards such as IEC 61000-6-2 or IEC 61326 or

    corresponding individual product standards.

    FDL Fieldbus Datalink Layer. Layer 2 of PROFIBUS.

    Hub A Hub refreshes a signal and passes the information on to all nodes whichare connected to the Hub. Data frames which were received on one port aretransferred to all the other ports (chicken foot topology).

    MPI Multiple Protocol Interface. A by Siemens defined protocol which uses thelayer 1 and 2 of PROFIBUS (FDL).

    PCB Printed Circuit Board.

    PROFIBUS DP Acronym for "PROFIBUS for Decentralized Peripherals". Specification of anopen fieldbus system with the following characteristics:- Polling master-slave-system (cyclic communications, MS0)- Flying masters with robin round token passing coordination (MM)- Connection based (MS1) and connectionless (MS2, MS3) acycliccommunication between masters and slavesOptions (e.g.):- Data exchange broadcast (DXB), i.e. slave to slaves communication- Isochronous mode of slaves- Clock synchronization

    - RedundancyPROFIBUS DP is standardized within IEC 61158 and IEC 61784,communication profile families 3/1 and 3/2The term "PROFIBUS DP" also is a synonym for the RS485 baseddeployments within factory automation.

    Repeater Active physical layer device that receives and retransmits all signals over adifferent port to increase the distance and number of devices for whichsignals can be correctly transferred for a given medium.

    Spur A cable connecting a node to a bus segment. Spurs are not recommended inPROFIBUS DP and prohibited with 12 Mbps and PROFIsafe operations.

    German term is "Stichleitung".

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    32/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 32 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    Stub See Spur .

    TBit See Bit Time .

    Termination A powered resistor network at both ends of a segment to prevent reflections(for PROFIBUS DP).

    Topology In a communications network, the pattern of interconnection betweennetwork nodes; e.g. bus, ring, star configuration.

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    33/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 33 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    8 Revision History

    Version 0.3- First release.

    Version 0.4- Update of technical information.- Addition of the ProfiHub B5 (first part).

    Version 0.5- Update of technical information.- Paragraph with ProfiHub A5/B5 comparison.- Chapter with order codes.

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    34/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 34 / 36

    ProfiHub-A5B5-Manual-EN.doc PROCENTEC 2006 - Copyright - all rights reserved

    9 Next version

    - Signal amplitudes.- Capacity of a channel.- Description of the ground rail.- Adjustment of busparameters when cascading a large number of ProfiHubs.- List with world-wide distributors.- Use of the diagnostic connector.

    1841 Centre Point Circle #143Naperville, Illinois 60563 USA+1 630 245-1445, +1 630 245-1717 FAXwww.factorycomm.com

  • 8/12/2019 ProfiHub A5B5 Manual en GC

    35/36

    ProfiHub A5/B5 User Manual

    _______________________________________________Version 1.0A 31 October 2006 Page 35 / 36