Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
Project Addendum
D a t e : A p r i l 3 0 , 2 0 2 1
PROJECT: Layton Fire Station #54
ADDENDUM #: 03
PROJECT ADDRESS: 1100 North Valley View Drive
Layton City, Utah
84040
BID DATE: Tuesday, May 4, 2021
BID TIME: 3:00pm ( local time )
BID LOCATION: Layton City Fire Department Headquarters 51, 530 North
2200 West, Layton City, Utah 84041
THE FOLLOWING ITEMS SHALL BE INCLUDED WITHIN THE CONTRACT DOCUMENTS.
THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE TO INCORPORATE THESE
CHANGES INTO THE CONTRACT DOCUMENTS AND SHALL ALSO BE RESPONSIBLE TO
NOTIFY ALL SUB-CONTRACTORS OF THIS ADDENDUM.
DESCRIPTION OF ADDENDUM INFORMATION:
1.GENERAL COMMENTS N/A
2.ARCHITECTURAL
SPECIFICATIONS: N/A
DRAWINGS: N/A
3. STRUCTURAL
Specifications: N/A
Drawings: N/A
4. PLUMBING
Specifications: N/A
Drawings: N/A
5. MECHANICAL
Specification: N/A
Drawings: N/A
6. ELECTRICAL
Specifications: Reference attached Electrical Addendum-03
Drawings: Reference attached Electrical Addendum-03
7. Civil
Specifications: N/A
Drawings: N/A
8. Landscaping
Specifications: N/A
Drawings: N/A
Electrical Addendum
This Addendum shall be considered part of the Contract Documents and Project Manual for the
above-mentioned project as though it had been issued at the same time and shall be
incorporated integrally therewith. Where provisions of the following supplementary data differ
from those of the original Contract Documents and Project Manual, the Addendum shall govern
and take precedence.
Electrical Addendum
Drawings
1. EE001 – SHEET INDEX UPDATED, DIFFERD SUBMITTALS UPDATED.
2. ES101 – SITE TELECOM ROUTING TO BUILDING ADDED WITH HANDHOLE, KEYNOTES
UPDATED, ROHN G45 TOWER SYSTEM SPECIFIED (SEE ATTACHED DOCUMENTS AND
UPDATED SHEET).
3. ES503 – UNDERGROUND JUNCTION BOX SCHEDULE UPDATED.
4. ET 101 – ET 601 – MULTIPLE UPDATES TREAT AS NEW SHEET.
Specifications
REMOVED:
271100, 271300,271500
NEW:
271100 - TELECOMMUNICATIONS PATHWAY AND SPACES
271500 - COMMUNICATIONS HORIZONTAL CABLING
To: JIM POLONCIC phone:
Company: THINK ARCHITECTURE email:
copied:
Job: LAYTON FIRE STATION #54
Job No. 200371
Re: ADDENDUM 3
From: SPENCER LITTLE, PE phone: (801) 401-8495
Date: 04/28/2021 email: [email protected]
Distributed Via: Email page: 1 of 2 W/ATTACHMENT
END OF ADDENDUM
Attachments <ES101,ET101-601, SECTION 271100, SECTION 271300 >
Sincerely
By:
Spencer C. Little, P.E. Associate Principal Electrical Engineer
GENERAL LABELING SCHEMEFIRST DIGIT - BUILDING LEVEL (1 OR 2)
SECOND DIGIT - PANEL TYPE
M - MECHANICAL (120/208/277/380/480V)L or LCP - LIGHTING (120/208/277/480V)P - PLUG LOADS (120/208V)G - GENERAL LOADS (120/280V)E - EMERGENCY (277/480V)S - STANDBY (SPECIFIED ON PANEL)U - UPS (SPECIFIED ON PANEL)
THIRD DIGIT - BUILDING AREA (A, B, C, D, ECT.)
FOURTH DIGIT - SQUENCE # (1,2,3...)
ELECTRICAL SHEET INDEXEE001 SHEET INDEX, ABREVS. AND GEN. NOTES
EE002 SYMBOLS LEGEND
EE501 ELECTRICAL DETAILS - MOUNTING/POWER
EE502 ELECTRICAL DETAILS - POWER/LIGHTING
EE701 TYPICAL MOUNTING HEIGHT DETAILS
ES101 ELECTRICAL SITE PLAN
ES102 SITE LIGHTING CALCULATIONS
ES201 ELECTRICAL SITE LIGHTING DETAILS
ES501 SITE ELECTRICAL DETAILS
ES502 SITE ELECTRICAL DETAILS
ES503 UNDERGROUND JUNCTION BOX SPECIFICATIONS
ES504 PULL BOX DETAILS
EP101 LEVEL 1 POWER PLAN
EP104 ENLARGED POWER PLAN
EP600 ELECTRICAL SCHEDULES
EP601 ONE-LINE DIAGRAM
EP602 EQUIPMENT SCHEDULE
EP603 PANEL SCHEDULES
EL101 LEVEL 1 LIGHTING PLAN
EL601 INTERIOR LIGHTING FIXTURE SCHEDULE
EL602 EXTERIOR LIGHTING FIXTURE SCHEDULE
EL701 LIGHTING CONTROL RISER
ET001 TELECOM SCHEDULES AND NOTES
ET101 LEVEL 1 TELECOM FLOOR PLAN
ET501 TELECOM EQUIPMENT RACK ELEVATIONS
ET502 TELECOM DETAILS
ET503 TELECOM DETAILS
ET504 TELECOM DETAILS
ET505 TELECOM EQUIPMENT RACK GROUNDING DETAIL
ET601 TELECOM RISER DIAGRAMS
EY101 LEVEL 1 AUXILIARY PLAN
EY601 AUXILIARY DOOR DIAGRAMS
FA101 LEVEL 1 FIRE ALARM PLAN
FA601 FIRE ALARM RISER
GENERAL ELECTRICAL NOTES
3. EXPOSED STRUCTURE AREAS (EXCLUDING MECHANICAL, ELECTRICAL, ANDCOMMUNICATION SPACES): INSTALL RACEWAYS BETWEEN DECK ANDSTRUCTURE WHEREVER POSSIBLE IN EXPOSED STRUCTURE CEILING AREAS.ROUTE RACEWAYS IN CONCEALED AREAS WHEREVER POSSIBLE. REFER ALLCONDITIONS WHERE RACEWAYS MUST BE INSTALLED WHICH CANNOT COMPLYWITH THESE REQUIREMENTS TO THE ARCHITECT.
4. SUBMITTALS: PROVIDE ORIGINAL ELECTRONIC PDF FORMAT, BOUND,BOOKMARKED (EACH SECTION AND PRODUCT), AND HIGHLIGHTED. JOB NAMEAND SUBCONTRACTOR SHALL BE ON THE FRONT COVER. PREPARE INDEX OFEQUIPMENT SUBMITTED IN EACH TAB.
5. REFLECTED CEILING PLANS: COORDINATE THE LOCATION OF LIGHT FIXTURESWITH THE ARCHITECTURAL REFLECTED CEILING PLANS. REFER ALLDISCREPANCIES TO THE ARCHITECT AND ENGINEER.
6. ALL WORK SHALL BE DONE ACCORDING TO THE CURRENT NATIONAL ELECTRICCODE (NEC), IBC, NFPA, AND IFC. COMPLIANCE AND FINAL APPROVAL IS SUBJECTTO THE ON SITE FIELD INSPECTION OF THE AHJ.
7 TAKE OFF QUANTITIES SHOWN IN SCHEDULE(S) ARE FOR REFERENCE ONLY. THECONTRACTOR IS RESPONSIBLE TO PROVIDE ALL OF THE DEVICES, FIXTURES,EQUIPMENT, RACEWAYS, CONDUCTORS, CABLING, ETC. SHOWN AND SPECIFIEDIN THE CONTRACT DOCUMENTS INCLUDING THE EXTRA MATERIAL SPECIFIED.
1. CLARIFICATION METHODS: AT THE TIME OF BIDDING, BIDDERS SHALL FAMILIARIZETHEMSELVES WITH THE DRAWINGS AND SPECIFICATIONS. ANY QUESTIONS,MISUNDERSTANDINGS, CONFLICTS, DELETIONS, DISCONTINUED PRODUCTS,CATALOG NUMBER DISCREPANCIES, DISCREPANCIES BETWEEN THE EQUIPMENTSUPPLIED AND THE INTENT OR FUNCTION OF THE EQUIPMENT, ETC, SHALL BESUBMITTED TO THE ARCHITECT/ENGINEER IN WRITING FOR CLARIFICATION PRIORTO ISSUANCE OF THE FINAL ADDENDUM AND BIDDING OF THE PROJECT. WHEREDISCREPANCIES OR MULTIPLE INTERPRETATIONS OCCUR, THE MOST STRINGENT(WHICH IS GENERALLY RECOGNIZED AS THE MOST COSTLY) THAT MEETS THEINTENT OF THE DOCUMENTS SHALL BE ENFORCED.
2. OWNER FURNISHED ITEMS: THE OWNER WILL FURNISH MATERIAL ANDEQUIPMENT AS INDICATED IN THE CONTRACT DOCUMENTS TO BE INCORPORATEDINTO THE WORK. THESE ITEMS ARE ASSIGNED TO THE INSTALLER AND COSTSFOR RECEIVING, HANDLING, STORAGE, IF REQUIRED, AND INSTALLATION AREINCLUDED IN THE CONTRACT SUM.
A. THE INSTALLER'S RESPONSIBILITIES ARE THE SAME AS IF THE INSTALLERFURNISHED THE MATERIALS OR EQUIPMENT.
B. THE OWNER WILL ARRANGE AND PAY FOR DELIVERY OF OWNERFURNISHED ITEMS FREIGHT ON BOARD JOB SITE AND THE INSTALLER WILLINSPECT DELIVERIES FOR DAMAGE. IF OWNER FURNISHED ITEMS AREDAMAGED, DEFECTIVE OR MISSING, DOCUMENT DAMAGED ITEMS WITHTHE TRANSPORT COMPANY AND THE OWNER WILL ARRANGEFOR REPLACEMENT. THE OWNER WILL ALSO ARRANGE FORMANUFACTURER'S FIELD SERVICES, AND THE DELIVERY OFMANUFACTURER'S WARRANTIES AND BONDS TO THE INSTALLER.
C. THE INSTALLER IS RESPONSIBLE FOR DESIGNATING THE DELIVERY DATESOF OWNER FURNISHED ITEMS AND FOR RECEIVING, UNLOADING ANDHANDLING OWNER FURNISHED ITEMS AT THE SITE.THE INSTALLER ISRESPONSIBLE FOR PROTECTING OWNER FURNISHED ITEMS FROMDAMAGE, INCLUDING DAMAGE FROM EXPOSURE TO THE ELEMENTS, ANDTO REPAIR OR REPLACE ITEMS DAMAGED AS A RESULT OF HISOPERATIONS.
DEFINITIONSNOTE: ALL DEFINITIONS MAY NOT BE USED.
INDICATED: THE TERM "INDICATED" REFERS TO GRAPHIC REPRESENTATIONS, NOTES, OR SCHEDULES ON THE DRAWINGS, OTHER PARAGRAPHS OR SCHEDULES IN THE SPECIFICATIONS, AND SIMILAR REQUIREMENTS IN THE CONTRACT DOCUMENTS. WHERE TERMS SUCH AS "SHOWN", "NOTED", "SCHEDULED", AND "SPECIFIED" ARE USED, IT IS TO HELP THE READER LOCATE THE REFERENCE, NO LIMITATION ON LOCATION IS INTENDED.
DIRECTED: TERMS SUCH AS "DIRECTED", "REQUESTED", AUTHORIZED", "SELECTED", "APPROVED", "REQUIRED", AND "PERMITTED" MEAN "DIRECTED BY THE ENGINEER", "REQUESTED BY THE ENGINEER", AND SIMILAR PHRASES.
APPROVED: THE TERM "APPROVED", WHERE USED IN CONJUNCTION WITH THE ENGINEER'S ACTION ON THE CONTRACTOR'S SUBMITTALS, APPLICATIONS, AND REQUESTS, IS LIMITED TO THE ENGINEER'S DUTIES AND RESPONSIBILITIES AS STATED IN GENERAL AND SUPPLEMENTARY CONDITIONS.
FURNISH: THE TERM "FURNISH" IS USED TO MEAN "SUPPLY AND DELIVER TO THE PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION, AND SIMILAR OPERATIONS."
INSTALL: THE TERM "INSTALL" IS USED TO DESCRIBE OPERATIONS AT PROJECT SITE INCLUDING THE ACTUAL "UNLOADING, UNPACKING, ASSEMBLY, ERECTION, PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING, PROTECTING, CLEANING, AND SIMILAR OPERATIONS."
PROVIDE: THE TERM "PROVIDE" MEANS "TO FURNISH AND INSTALL, COMPLETE AND READY FOR THE INTENDED USE."
INSTALLER: AN "INSTALLER" IS THE CONTRACTOR OR AN ENTITY ENGAGED BY THE CONTRACTOR, EITHER AS AN EMPLOYEE, SUBCONTRACTOR, OR SUB-SUBCONTRACTOR, FOR PERFORMANCE OF A PARTICULAR CONSTRUCTION ACTIVITY, INCLUDING INSTALLATION, ERECTION, APPLICATION, AND SIMILAR OPERATIONS. INSTALLERS ARE REQUIRED TO BE EXPERIENCED IN THE OPERATIONS THEY ARE ENGAGED TO PERFORM.
TECHNOLOGY SYSTEMS: THE TERM "TECHNOLOGY SYSTEMS" IS USED TO DESCRIBE ALL LOW VOLTAGE SYSTEMS GENERALLY REFERRED TO AS "SPECIAL SYSTEMS". THESE SYSTEMS INCLUDE BUT ARE NOT NECESSARILY LIMITED TO ALL SYSTEMS WHICH UTILIZE VOLTAGES OF LESS THAN 71 VOLTS SUCH AS SOUND SYSTEMS, VIDEO SYSTEMS, TV SYSTEMS, SECURITY SYSTEMS, VOICE AND DATA CABLING SYSTEMS, ETC...
ABBREVIATIONSNOTE: ALL ABBREVIATIONS MAY NOT BE USED.
kV KILOVOLT
kVA KILOVOLT AMPERE
kVAR KILOVOLT AMPERE REACTIVE
kW KILOWATT
kWh KILOWATT HOUR
LED LIGHT EMITTING DIODE
LFMC LIQUID TIGHT FLEXIBLEMETAL CONDUIT
LFNC LIQUID TIGHT FLEXIBLENONMETALLIC CONDUIT
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTG LIGHTING
LV LOW VOLTAGE
MATV MASTER ANTENNATELEVISION SYSTEM
MAX MAXIMUM
MC METAL CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTION
MDP MAIN DISTRIBUTION PANEL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENTPROTECTION
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIOANL ELECTRICALMANUFACTURERSASSOCIATION
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTIONASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OCP OVER CURRENT PROTECTION
OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED
OF/OI OWNER FURNISHED/ OWNERINSTALLED
OFP OBTAIN FROM PLANS
OH DR OVERHEAD (COILING) DOOR
OL OVERLOAD
PB PUSHBUTTON
PF POWER FACTOR
PH PHASE
PNL PANEL
PT POTENTIAL TRANSFORMER
PTZ PAN/TILT/ZOOM
QTY QUANTITY
R REMOVE
RCP REFLECTED CEILING PLAN
RMC RIGID METAL CONDUIT
RNC RIGID NONMETAL CONDUIT
RPM REVOLUTIONS PER MINUTE
RR REMOVE AND RELOCATE
S/S START/STOP
SCA SHORT CIRCUIT AMPS
SCBA STANDARD COLOR ASSELECTED BY ARCHITECT
SF SQUARE FOOT (FEET)
SFBA STANDARD FINISH ASSELECTED BY ARCHITECT
SPDT SINGLE POLE, DOUBLETHROW
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
ST SINGLE THROW
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TL TWIST LOCK
TP TELEPHONE POLE
TP TWISTED PAIR
TTB TELEPHONE TERMINALBOARD
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGESUPPRESSER
TYP TYPICAL
UF UNDERFLOOR
UGND UNDERGROUND
UPS UNINTERRUPTIBLE POWERSUPPLY
V VOLTS
VA VOLT AMPERE
VFC/VFD
VARIABLE FREQUENCYMOTOR CONTROLLER
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
1P SINGLE POLE
1PH SINGLE-PHASE
1WAY ONE-WAY
2/C TWO-CONDUCTOR
2WAY TWO-WAY
3/C THREE-CONDUCTOR
3WAY THREE-WAY
4OUT QUADRUPLE RECEPTACLEOUTLET
4PDT FOUR-POLE DOUBLE THROW
4PST FOUR-POLE SINGLE THROW
4W FOUR-WIRE
4WAY FOUR-WAY
A ABOVE COUNTER
AC ARMORED CABLE
ADA AMERICANS WITHDISABILITIES ACT
ADJ ADJACENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTINGCAPACITY
ALUM ALUMINUM
AMP AMPERE
ANN ANNUNCIATOR
AP ACCESS POINT (WIRELESSDATA)
AR AS REQUIRED
ASC AMPS SHORT CIRCUIT
ATS AUTOMATIC TRANSFERSWITCH
AV AUDIO VISUAL
AWG AMERICAN WIRE GAGE
BBXFMR
BUCK-BOOST TRANSFORMER
C CEILING MOUNTED
CATV COMMUNITY ANTENNATELEVISION
CB CIRCUIT BREAKER
CCBA CUSTOM COLOR ASSELECTED BY ARCHITECT
CCTV CLOSED CIRCUIT TELEVISION
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFBA CUSTOM FINISH ASSELECTED BY ARCHITECT
CKT CIRCUIT
CM CONSTRUCTION MANAGER
CND CONDUIT
CO CONVENIENCE OUTLET
COR CONTRACTING OFFICER'SREPRESENTATIVE
CP CONTROL PANEL
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
dBA UNIT OF SOUND LEVEL
DPDT DOUBLE POLE, DOUBLETHROW
DS DISCONNECT SWITCH
EA EACH
EM EMERGENCY
EMT ELECTRICAL METALLICTUBING
ENT ELECTRIC NONMETALLICTUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
EX EXISTING
F FURNITURE MOUNTED
FA FIRE ALARM
FCP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPS
FMC FLEXIBLE METAL CONDUIT
FOB FREIGHT ON BOARD
FVNR FULL VOLTAGENON-REVERSING
FVR FULL VOLTAGE REVERSING
G GROUND
GEN GENERATOR
GFCI GROUND FAULTINTERRUPTER
GFP GROUND FAULT PROTECTION
HD HEAVY DUTY
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSE POWER
HPF HIGH POWER FACTOR
HPS HIGH PRESSURE SODIUM
HV HIGH VOLTAGE
HZ HERTZ
I/O INPUT/ OUTPUT
IG ISOLATED GROUND
IMC INTERMEDIATE METALCONDUIT
IN/IS INSULATED/ ISOLATED
IR INFRARED
J-BOX JUNCTION BOX
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
PROJECT NO.
SHEET TITLE:
Plo
t Da
te:
ArchitectureInterior DesignLandscape ArchitectureLand PlanningConstruction Management
7927 So. Highpoint Parkway, Suite 300
Sandy, Utah 84094
ph. 801.269.0055
fax 801.269.1425
www.thinkaec.com
The designs shown and described herein
including all technical drawings, graphic
representation & models thereof, are proprietary
& can not be copied, duplicated, or
commercially exploited in whole or in part
without the sole and express written permission
from THINK Architecture, inc.
These drawings are available for limited review
and evaluation by clients, consultants,
contractors, government agencies, vendors,
and office personnel only in accordance with
this notice.
SHEET NUMBER:
REVISIONS:
DATE:
4/2
9/2
02
1 3
:57
:12
PM
LAYT
ON
FIR
E ST
ATI
ON
#54
885
EAST
PO
NTI
AC
DRI
VE
LAYT
ON
, UTA
H 8
4041
Mar. 4, 2021
200371
SHEET INDEX, ABREVS.
AND GEN. NOTES
EE001
DEFERRED SUBMITTALS
Delegated Deferred Design Submittals to be provided by Contractor
FIRE ALARM SYSTEM
Provide complete digital addressable fire alarm system in compliance with current NFPA and all local building and fire alarm codes specific to this project. The systems shall be designed by a NICET-certified, fire alarm technician, Level III minimum.
The Fire Alarm drawings, risers, and specifications are shown as a basis of design to show intent for bidding, final documents with calculations specifying all required devices, cabling, equipment, and programing are to be provided by the contractor. The contractors bid shall include the full fire alarm system required and not limited to the devices and typical riser diagram shown.
See basis of design drawings and specifications for intended design. Comply with the Code Analysis and building construction types of this project, see Architectural drawings and specifications for building type, occupancy, fire wall separations, and other requirements that will have an effect on the fire alarm system design.
OVERCURRENT PROTECTIVE DEVICE STUDY AND ARC-FLASH STUDY REPORT & LABELING.
Provide the following items listed below and comply with additional requirements as provided. See specifications.
1. Coordination-study input data, including completed computer program input data sheets.2. Study and equipment evaluation reports.3. Overcurrent protective device coordination study report; signed, dated, and sealed by a qualified professional engineer. Overcurrent protection shall coordinate to 0.3 seconds on normal power and to 0.1 seconds on emergency power. 4. Arc-flash study input data, including completed computer program input data sheets.5. Arc-flash study report; signed, dated, and sealed by a qualified professional engineer.
a. Submit study report for action prior to receiving final approval of the distribution equipment submittals. If formal completion of studies will cause delay in
equipment manufacturing, obtain approval from Architect for preliminary submittal of sufficient study data to ensure that the selection of devices and associated characteristics is satisfactory.
SEISMIC CONTROL FOR ELECTRICAL SYSTEMS
Provide the following items listed below and comply with additional requirements as provided. See specifications.A. Product Data: For each type of product.1. Illustrate and indicate style, material, strength, fastening provision, and finish for each type and
size of seismic-restraint component used.a. Tabulate types and sizes of seismic restraints, complete with report numbers and rated
strength in tension and shear as evaluated by an agency acceptable to authorities having jurisdiction.
b. Annotate to indicate application of each product submitted and compliance with requirements.
B. Delegated-Design Submittal: For each seismic-restraint device.1. Include design calculations and details for selecting seismic restraints complying with
performance requirements, design criteria, and analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
2. Design Calculations: Calculate static and dynamic loading caused by equipment weight, operation, and seismic and wind forces required to select seismic and wind restraints and for designing vibration isolation bases.a. Coordinate design calculations with wind load calculations required for equipment
mounted outdoors. Comply with requirements in other Sections for equipment mounted outdoors.
3. Seismic-Restraint Details:a. Design Analysis: To support selection and arrangement of seismic restraints. Include
calculations of combined tensile and shear loads.b. Details: Indicate fabrication and arrangement. Detail attachments of restraints to the
restrained items and to the structure. Show attachment locations, methods, and spacings. Identify components, list their strengths, and indicate directions and values of forces transmitted to the structure during seismic events. Indicate association with vibration isolation devices.
c. Coordinate seismic-restraint and vibration isolation details with wind-restraint details required for equipment mounted outdoors. Comply with requirements in other Sections for equipment mounted outdoors.
d. Preapproval and Evaluation Documentation: By an agency acceptable to authorities having jurisdiction, showing maximum ratings of restraint items and the basis for approval (tests or calculations).
C. Deferred Submittals for the Authority Having Jurisdiction (AHJ) shall be as required by IBC 106.3.4.2.
1. Deferred submittals of seismic restraint of nonstructural components must be submitted to the AHJ a minimum of two weeks prior to the planned installation in order to allow for plan review and forwarding to inspectors. In the event that the submittal is deficient additional time may become necessary.
2. No deferred submittal element shall be installed until AHJ approval has been received.
3. If seismic restraints of nonstructural components are installed prior to receiving AHJ approval they shall not be covered or concealed until plan review and inspection approval. Further, installers are proceeding at their own risk until plan review and inspection approval occurs.
4. Deferred Submittals are required for:a. Electrical distribution equipment (switchboards, panelboards, transformers, ATS, MCC's
etc.).b. Generators, batteries, UPS.c. Conduit racks.d. Cable trays.e. Lighting fixtures.f. Control Panelsg. Self Supporting Towersh. Pole/Tower Bases
NOTE TO CONTRACTORS: THIS SHEET SET IS CONTRACTUALLY REQUIRED TO BE PRINTED IN COLOR. THERE ARE DIFFERENTIATING FEATURES THAT ARE DESIGNATED THROUGHOUT BY THEIR COLOR. FAILURE TO PRINT THIS SHEET SET IN COLOR MAY RESULT IN A MISINTERPRETATION OF THE DRAWINGS.
3 4/28/2021 ADDENDUM #3
3
3
04-29-2021
HC
ST
ST
STST
J
AA
EE
DD
BB
CC
4
4
3
3
1
1
5
5
6
6
2
2
(PG-12)
(PG-12)
1
"MDP"
"DP"
"LCP XFMR"
L1C-36,38
L1C-39,41
L1C-40
(ZX1)(ZX1)(ZX1)
(ZX1)
(RTH-2)L1A-8
(RTH-2)L1A-35
(RTH-1)L1A-49
(RTH-1)L1A-45
"GENERATOR"
WP WP WP
WP
WP WP WP
WPWP
WP
WP
WP
WPWPWPWP
WP
22
8
88
(PG-12)3
(PG-12T)(PG-12)
4"CND
4"CND
4"CND
4"CND
(PG-12T)
4
5
6
6
5
(ZX1)
8
8
8
8
FIXTURES SL-2: THE FEE OF $12,169.00 (TOTAL) FOR THE LIGHTS AND INSTALLATION SHALL BE ADDED TO THE BUILDING PERMIT FEE PAID BY THE GENERAL CONTRACTOR. HOWEVER, LIGHT FIXTURES SL-2 SHALL BE INSTALLED BY THE CITY'S STREET LIGHT CONTRACTOR. THE GENERAL CONTRACTOR, IN ADDITION, SHALL PROVIDE AND INSTALL THE POWER AND PEDISTALS FOR THE (2)-SL-2 LIGHT FIXTURES SHOWN ON SHEET ES101.
L1C-42
(ZX1)
(ZX1)
7
(ZX1)
FIXTURES SL-2: THE FEE OF $12,169.00 (TOTAL) FOR THE LIGHTS AND INSTALLATION SHALL BE ADDED TO THE BUILDING PERMIT FEE PAID BY THE GENERAL CONTRACTOR. HOWEVER, LIGHT FIXTURES SL-2 SHALL BE INSTALLED BY THE CITY'S STREET LIGHT CONTRACTOR. THE GENERAL CONTRACTOR, IN ADDITION, SHALL PROVIDE AND INSTALL THE POWER AND PEDISTALS FOR THE (2)-SL-2 LIGHT FIXTURES SHOWN ON SHEET ES101.
SL-2
SL-2
4
4
3
3
1
1
AA
5
5
6
6
EE
DD
BB
CC
2
2
(2)EA4"CND
8
9
3
3
(HH-1)
GENERAL SHEET NOTES
SHEET KEYNOTES1 PROVIDE ELECTRICAL CONNECTION TO MOTORIZED DOORS WITH ALL POWER AND
CONTROL WIRING PER MANUFACTURER'S WRITTEN INSTRUCTIONS. COORDINATEWITH DOOR SHOP DRAWINGS AND ARCHITECTURAL DETAILS. PROVIDE 1 INCHCONDUIT FOR CONTROLS TO CONTROLLER LOCATIONS AS DIRECTED BYARCHITECT/ENGINEER.
2 COORDINATE UGJ LOCATION PER ARCHITECTURAL AND SITE DRAWINGS.COORDINATE UGJ WITH SPRINKLER SHUTOFF AND CONTROL STATIONS.
3 PROVIDE STRUCTURAL CONCRETE BASE AND SELF SUPPORTING TOWER SYSTEMPER MANUFACTURERS SPCIFICATIONS (ROHN G45) WITH 4" CONDUIT STUBBED UPFOR SYMULCAST SYSTEM. COORDINATE EXACT LOCATION WITH OWNER PRIOR TOTRENCHING AND ROUGH-IN.
4 PROVIDE AND INSTALL 4" CONDUIT FROM ELECTRICAL ROOM TO CORRESPONDINGLOCATION WITHIN THE STATE FUEL/INFORMATION SYSTEM. COORDINATE EXACTLOCATION AND ROUTING WITH OWNER PRIOR TO TRENCHING AND ROUGH-IN.
5 PROVIDE AND INSTALL 4" CONDUIT FROM IT ROOM TO CORRESPONDING LOCATION.COORDINATE EXACT LOCATION AND ROUTING WITH OWNER PRIOR TO TRENCHINGAND ROUGH-IN.
6 PROVIDE AND INSTALL 4" CONDUIT FROM ELECTRICAL ROOM TO CORRESPONDINGLOCATION. COORDINATE EXACT LOCATION AND ROUTING WITH OWNER PRIOR TOTRENCHING AND ROUGH-IN.
7 STUB UP CONDUITS INTO TELECOM ROOM.
8 THE ELECTRICAL CONTRACTOR SHALL MEET WITH AND COORDINATE WITHTELECOMMUNICATION SERVICE PROVIDERS TO THE FACILITY ON SITE PRIOR TO ANYWORK BEING PERFORMED. CONFIRM WITH SERVICE PROVIDER EXACT LOCATIONSEQUIPMENT AND CONDUIT ROUTING. COMPLY WITH ALL SERVICE PROVIDER'SCURRENT STANDARDS AND REQUIREMENTS. PROVIDE THE REQUIRED EQUIPMENT,RACEWAYS, BOXES, CABLE, ETC. AS REQUIRED BY THE SERVICE PROVIDERWEATHER SHOWN ON THE DRAWINGS OR NOT. UTILITY PROVIDERS TO BUILDING(UTOPIA & CENTURYLINK).
9 PROVIDE (2) 4” CONDUIT WITH (3) 1.25” INNERDUCT IN EACH PIPE.
1 THE ELECTRICAL CONTRACTOR SHALL MEET WITH AND COORDINATE WITH ALLSERVICE PROVIDERS (POWER, COMMUNICATION, CABLE/SATELLITE, ETC.)TO THEFACILITY ON SITE PRIOR TO ANY WORK BEING PREFORMED. CONFIRM WITH EACHSERVICE PROVIDER EXACT LOCATIONS EQUIPMENT AND ROUTING. COMPLY WITHALL SERVICE PROVIDER’S CURRENT STANDARDS AND REQUIREMENTS. PROVIDETHE REQUIRED EQUIPMENT, RACEWAYS, BOXES, CABLE, ETC. AS REQUIRED BYTHE SERVICE PROVIDER WEATHER SHOWN ON THE DRAWINGS OR NOT.
2 FOR ALL LIGHT FIXTURES, POLE LIGHTS, AND ALL OTHER ELECTRICAL DEVICESTHE CONTRACTOR SHALL COORDINATE EXACT LOCATION AND MOUNTINGHEIGHTS WITH ARCHITECT, OWNER, ENGINEER, AND ALL OF THE CONTRACTDOCUMENTS PRIOR TO ROUGH IN AND TRENCHING.
3 CONTRACTOR IS RESPONSIBLE FOR ALL TRENCHING, BACKFILL, AND COMPACTIONASSOCIATED TO ALL ELECTRICAL UNDERGROUND RACEWAYS AND CABLES.COORDINATE WITH ARCHITECTURAL AND CIVIL DRAWINGS. SEE UNDERGROUNDRACEWAY DETAILS FOR REQUIREMENTS FOR EACH TRENCH.
4 CONTRACTOR SHALL INSTALL POLE MOUNTED LIGHTS IN STRAIGHT LINES,SQUARE, AND PLUMB. COORDINATE WITH ARCHITECT AND CIVIL DRAWINGS.CONTRACTOR SHALL INSTALL POLE MOUNTED LIGHTS IN STRAIGHT LINES,SQUARE, AND PLUMB. COORDINATE WITH ARCHITECT AND CIVIL DRAWINGS.
5 THE ELECTRICAL CONTRACTOR SHALL HAVE ANY AND ALL CONCRETE POLEBASES AND SLABS REVIEWED BY A STRUCTURAL ENGINEER AND SHALL MODIFYDESIGN PER STRUCTURAL ENGINEER’S AND OR AHJ’S RECOMMENDATIONS.
6 PROVIDE BATTERY PACKS IN ALL EXTERIOR FIXTURES ADJACENT TO EGRESSDOORS.
7 PROVIDE PHOTOCELL ON NORTH SIDE OF FACILITY TO CONTROL EXTERIORLIGHTS.
8 ALL EXTERIOR RECEPTACLES SHOWN SHALL BE NEMA 5-20R GFCI “WEATHERRESISTANT” RECEPTACLE WITH “WEATHER PROOF IN-USE COVER.”
9 THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CONCRETE/ASPHALTCUTTING AND REPLACEMENT OF CONCRETE/ASPHALT TO MATCH EXISTINGASSOCIATED WITH UNDERGROUND RACEWAYS PROVIDED AS PART OF THISPROJECT.
10 REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND CLEARANCEREQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS THAT FALLWITHIN THE CONSTRAINTS OF EACH SPECIFIC LOCATION.
11 PROVIDE SERVICE RATED EQUIPMENT AT EACH SERVICE ENTRANCE.
12 SERVICE EQUIPMENT SHALL BE LEGIBLY MARKED IN THE FIELD WITH THEMAXIMUM AVAILABLE FAULT CURRENT. VERIFY OR RE-CALCULATE THE AVAILABLEFAULT CURRENT AT THE SERVICE WHERE MODIFICATIONS TO THE ELECTRICALINSTALLATION OCCUR. PLEASE INCLUDE NOTES IN THE ELECTRICAL DRAWINGSOR SUPPLY CALCULATIONS WHERE APPLICABLE. SEE NEC 110.24. (B)
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
PROJECT NO.
SHEET TITLE:
Plo
t Da
te:
ArchitectureInterior DesignLandscape ArchitectureLand PlanningConstruction Management
7927 So. Highpoint Parkway, Suite 300
Sandy, Utah 84094
ph. 801.269.0055
fax 801.269.1425
www.thinkaec.com
The designs shown and described herein
including all technical drawings, graphic
representation & models thereof, are proprietary
& can not be copied, duplicated, or
commercially exploited in whole or in part
without the sole and express written permission
from THINK Architecture, inc.
These drawings are available for limited review
and evaluation by clients, consultants,
contractors, government agencies, vendors,
and office personnel only in accordance with
this notice.
SHEET NUMBER:
REVISIONS:
DATE:
4/2
9/2
02
1 2
:54
:42
PM
LAYT
ON
FIR
E ST
ATI
ON
#54
885
EAST
PO
NTI
AC
DRI
VE
LAYT
ON
, UTA
H 8
4041
Mar. 4, 2021
200371
ELECTRICAL SITE PLAN
ES101SCALE: 1" = 20'-0"A1ELECTRICAL SITE PLAN
3 4/28/2021 ADDENDUM #3
3
3
04-29-2021
PG-12
PG-22PG-34 PG-23 PG-22
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
PROJECT NO.
SHEET TITLE:
Plo
t Da
te:
ArchitectureInterior DesignLandscape ArchitectureLand PlanningConstruction Management
7927 So. Highpoint Parkway, Suite 300
Sandy, Utah 84094
ph. 801.269.0055
fax 801.269.1425
www.thinkaec.com
The designs shown and described herein
including all technical drawings, graphic
representation & models thereof, are proprietary
& can not be copied, duplicated, or
commercially exploited in whole or in part
without the sole and express written permission
from THINK Architecture, inc.
These drawings are available for limited review
and evaluation by clients, consultants,
contractors, government agencies, vendors,
and office personnel only in accordance with
this notice.
SHEET NUMBER:
REVISIONS:
DATE:
4/2
9/2
02
1 1
:37
:09
PM
LAYT
ON
FIR
E ST
ATI
ON
#54
885
EAST
PO
NTI
AC
DRI
VE
LAYT
ON
, UTA
H 8
4041
Mar. 4, 2021
200371
UNDERGROUND
JUNCTION BOX
SPECIFICATIONS
ES503
ID IMAGE BOX DESCRIPTION LENGTH WIDTH DEPTH
ABOVE GRADE
HEIGHT
BASIS OF DESIGN
MANUFACTURE PART NO. BOX OPTIONS COVER LOGO COVER OPTIONS STYLE TRAFFIC TIER NO.
(PG-12) UNDERGROUND ENCLOSURE; PRECASTPOLYMER CONCRETE WITH REINFORCED WITHFIBER GLASS. PROVIDE WITH BOLT ON COVER.
0' - 11" 1' - 6" 1' - 6" INSTALL FLUSHWITH GRADE
QUAZITE (PG1324-18) BA - BOX WITH OPEN BOTTOM "ELECTRICAL" WITH TWO BOLTSAND A SINGLE LOGO
PG TIER 15
(PG-12) UNDERGROUND ENCLOSURE; PRECASTPOLYMER CONCRETE WITH REINFORCED WITHFIBER GLASS. PROVIDE WITH BOLT ON COVER.
0' - 11" 1' - 6" 1' - 6" INSTALL FLUSHWITH GRADE
QUAZITE (PG1324-18) BA - BOX WITH OPEN BOTTOM "ELECTRICAL" WITH TWO BOLTSAND A SINGLE LOGO
PG TIER 15
(PG-12T) UNDERGROUND ENCLOSURE; PRECASTPOLYMER CONCRETE WITH REINFORCED WITHFIBER GLASS. PROVIDE WITH BOLT ON COVER.
0' - 11" 1' - 6" 1' - 6" INSTALL FLUSHWITH GRADE
QUAZITE (PG1324-18) BA - BOX WITH OPEN BOTTOM "TELECOM" WITH TWO BOLTSAND A SINGLE LOGO
PG TIER 15
(PG-12) UNDERGROUND ENCLOSURE; PRECASTPOLYMER CONCRETE WITH REINFORCED WITHFIBER GLASS. PROVIDE WITH BOLT ON COVER.
0' - 11" 1' - 6" 1' - 6" INSTALL FLUSHWITH GRADE
QUAZITE (PG1324-18) BA - BOX WITH OPEN BOTTOM "ELECTRICAL" WITH TWO BOLTSAND A SINGLE LOGO
PG TIER 15
(PG-12) UNDERGROUND ENCLOSURE; PRECASTPOLYMER CONCRETE WITH REINFORCED WITHFIBER GLASS. PROVIDE WITH BOLT ON COVER.
0' - 11" 1' - 6" 1' - 6" INSTALL FLUSHWITH GRADE
QUAZITE (PG1324-18) BA - BOX WITH OPEN BOTTOM "ELECTRICAL" WITH TWO BOLTSAND A SINGLE LOGO
PG TIER 15
(PG-12T) UNDERGROUND ENCLOSURE; PRECASTPOLYMER CONCRETE WITH REINFORCED WITHFIBER GLASS. PROVIDE WITH BOLT ON COVER.
0' - 11" 1' - 6" 1' - 6" INSTALL FLUSHWITH GRADE
QUAZITE (PG1324-18) BA - BOX WITH OPEN BOTTOM "TELECOM" WITH TWO BOLTSAND A SINGLE LOGO
PG TIER 15
(HH-1) UNDERGROUND ENCLOSURE; PRECASTPOLYMER CONCRETE WITH REINFORCED WITHFIBER GLASS. PROVIDE WITH BOLT ON COVER.
3' - 0" 3' - 0" 2' - 9" INSTALL FLUSHWITH GRADE (0'-0")
QUAZITE (PG3636-18) BA - BOX WITH OPEN BOTTOM "TELECOM" 2 PIECE WITH TWOBOLTS AND LOGOS
PG TIER 15
UNDER GROUND ENCLOSURE SCHEDULE
APPLICATION TIERS DESCRIPTION
VERTICAL
VERTICAL
LATERAL
VERTICAL
LATERAL
VERTICAL
LATERAL
LIGHT DUTY
TIER 5
TIER 8
TIER 15
TIER 22VERTICAL
LATERAL
TYPE
PEDESTRIAN TRAFFIC ONLY.
SIDEWALK APPLICATIONS WITH A SAFTEY FACTOR FOR OCCCASIONAL ACCIDENTALVEHICULAR TRAFFIC.
SIDEWALK APPLICATIONS WITH A SAFTEY FACTOR FOR OCCCASIONAL ACCIDENTALVEHICULAR TRAFFIC.
DRIEVEWAY, PARKING LOT, AND OFF ROADAPPLICATIONS SUBJECT TO OCCASIONAL NON-DELIBERATE VEHICULAR TRAFFIC.
DRIVEWAY, PARKING LOT, AND OFF ROADAPPLICATIONS SUBJECT TO NON-DELIBERATE HEAVY VEHICULAR TRAFFIC.
BOX OPTIONS DESCRIPTION
BA
BB
BC
BG
DA
DG
JA
EA
RA
BOX WITH OPEN BOTTOM
BOX WITH MOUSE HOLES
DIVIDED BOX
GASKETED BOX WITH OPEN BOTTOM
BOX WITH SOLID BOTTOM
GASKETED BOX WITH SOLID BOTTOM
FOOTED BOX
EXTENSION
SOLID BASE EXTENSION
NOTES:
1. CONTRACTOR SHALL PROVIDE A SUBMITTAL ON ALL UNDERGROUND ENCLOSURES FOR THIS PROJECT. 2. ALL ENCLOSURES SHALL BE UL LISTED3. CONTRACTOR SHALL COORDINATE THE TIER RATING WITH CIVIL ENGINEER AND ARCHITECT IN THE SUBMITTAL PROCESS.4. CONTRACTOR SHALL ADJUST THE SIZE OF THE ENCLOSURE AS REQUIRED FOR INSTALLATION. SUBMIT AN RFI OR PROVIDE SOME OTHER DOCUMENTATION SO THAT THE DESIGN TEAM AND OWNER UNDERSTAND THIS MODIFICATION PRIOR TO MOVING FORWARD WITH ADJUSTED SIZE OF ENCLOSURE. 5. PROVIDE BASIS OF DESIGN (BOD) ENCLOSURE OR PRE-APPROVED EQUAL.
COVER OPTIONS DESCRIPTION
CA
WA
LR
LP
LQ
LK
LL
LS
O2
BOLT DOWN COVER
STANDARD WITH NO BOLTS
CAST IRON 6 4-1/2" X 7-1/2" LID
CAST IRON 6"X12" LID
CAST IRON 9"X12" LID
POLYMER CONCRETE 6"X9" DROP-IN LID
POLYMER CONCRETE 7" X 13" DROP-IN LID
THROUGH SLOT (NO METER LID)
OPENS UNDER 90O
OO USED WITH DROP-IN LID
SYMBOLS LEGEND
GENERAL SHEET NOTES1 THE ELECTRICAL CONTRACTOR SHALL MEET WITH AND COORDINATE WITH ALL
SERVICE PROVIDERS (POWER, COMMUNICATION, CABLE/SATELLITE, ETC.)TO THEFACILITY ON SITE PRIOR TO ANY WORK BEING PREFORMED. CONFIRM WITH EACHSERVICE PROVIDER EXACT LOCATIONS EQUIPMENT AND ROUTING. COMPLY WITHALL SERVICE PROVIDER’S CURRENT STANDARDS AND REQUIREMENTS. PROVIDETHE REQUIRED EQUIPMENT, RACEWAYS, BOXES, CABLE, ETC. AS REQUIRED BYTHE SERVICE PROVIDER WEATHER SHOWN ON THE DRAWINGS OR NOT.
2 FOR ALL LIGHT FIXTURES, POLE LIGHTS, AND ALL OTHER ELECTRICAL DEVICESTHE CONTRACTOR SHALL COORDINATE EXACT LOCATION AND MOUNTINGHEIGHTS WITH ARCHITECT, OWNER, ENGINEER, AND ALL OF THE CONTRACTDOCUMENTS PRIOR TO ROUGH IN AND TRENCHING.
3 CONTRACTOR IS RESPONSIBLE FOR ALL TRENCHING, BACKFILL, AND COMPACTIONASSOCIATED TO ALL ELECTRICAL UNDERGROUND RACEWAYS AND CABLES.COORDINATE WITH ARCHITECTURAL AND CIVIL DRAWINGS. SEE UNDERGROUNDRACEWAY DETAILS FOR REQUIREMENTS FOR EACH TRENCH.
4 CONTRACTOR SHALL INSTALL POLE MOUNTED LIGHTS IN STRAIGHT LINES,SQUARE, AND PLUMB. COORDINATE WITH ARCHITECT AND CIVIL DRAWINGS.CONTRACTOR SHALL INSTALL POLE MOUNTED LIGHTS IN STRAIGHT LINES,SQUARE, AND PLUMB. COORDINATE WITH ARCHITECT AND CIVIL DRAWINGS.
5 THE ELECTRICAL CONTRACTOR SHALL HAVE ANY AND ALL CONCRETE POLEBASES AND SLABS REVIEWED BY A STRUCTURAL ENGINEER AND SHALL MODIFYDESIGN PER STRUCTURAL ENGINEER’S AND OR AHJ’S RECOMMENDATIONS.
6 PROVIDE BATTERY PACKS IN ALL EXTERIOR FIXTURES ADJACENT TO EGRESSDOORS.
7 PROVIDE PHOTOCELL ON NORTH SIDE OF FACILITY TO CONTROL EXTERIORLIGHTS.
8 ALL EXTERIOR RECEPTACLES SHOWN SHALL BE NEMA 5-20R GFCI “WEATHERRESISTANT” RECEPTACLE WITH “WEATHER PROOF IN-USE COVER.”
9 THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CONCRETE/ASPHALTCUTTING AND REPLACEMENT OF CONCRETE/ASPHALT TO MATCH EXISTINGASSOCIATED WITH UNDERGROUND RACEWAYS PROVIDED AS PART OF THISPROJECT.
10 REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND CLEARANCEREQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS THAT FALLWITHIN THE CONSTRAINTS OF EACH SPECIFIC LOCATION.
11 PROVIDE SERVICE RATED EQUIPMENT AT EACH SERVICE ENTRANCE.
12 SERVICE EQUIPMENT SHALL BE LEGIBLY MARKED IN THE FIELD WITH THEMAXIMUM AVAILABLE FAULT CURRENT. VERIFY OR RE-CALCULATE THE AVAILABLEFAULT CURRENT AT THE SERVICE WHERE MODIFICATIONS TO THE ELECTRICALINSTALLATION OCCUR. PLEASE INCLUDE NOTES IN THE ELECTRICAL DRAWINGSOR SUPPLY CALCULATIONS WHERE APPLICABLE. SEE NEC 110.24. (B)
3 4/28/2021 ADDENDUM #3
3
04-29-2021
GENERAL PROJECT NOTES
SYMBOL
EQUIPMENT/CABLE LIST
ITEM DESCRIPTION ACCEPTABLE TYPES
PANDUIT, GEN CABLE, COMMSCOPE, BERK-TEKSTATION CABLE, DATA - CATEGORY 6, UTP, PLENUM, BLUE
THE ITEMS INDICATED BELOW SHALL NOT BE CONSTRUED AS A "BILL OF MATERIALS". THIS LIST IDENTIFIES ITEMS OF SIGNIFICANCE USED DURING THE DESIGN OF THECABLING INSTALLATION. WHERE THE ITEMS INDICATED ARE ONE PORTION OF AN ASSEMBLY, THE ENTIRE ASSEMBLY SHALL BE PROVIDED UNLESS SPECIFIED OTHERWISE.PROVIDE ALL MISCELLANEOUS HARDWARE AND SUPPORTS WHICH MAY NOT BE LISTED HERE, FOR A COMPLETE INSTALLATION. COMPARE CATALOG NUMBERS WITHDESCRIPTIONS AND NOTIFY ENGINEER OF DISCREPANCIES PRIOR TO BID. IF CATALOG NUMBERS DO NOT MATCH DESCRIPTIONS, THE DESCRIPTIONS TAKE PRECEDENCE.PROVIDE COMPLETE SUBMITTAL FOR APPROVAL PRIOR TO PURCHASING ANY EQUIPMENT OR CABLE. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
NOTE: ALL RACKS, LADDER, PATCH PANELS AND ACCESSORIES SHALL BE BLACK IN COLOR.
DATA OUTLET, SINGLE GANG FACEPLATE, WHITE, 2 POSITION
CATEGORY 6 JACK - DATA, BLUE
DATA OUTLET, SURFACE MOUNT BOX, WHITE, 2 POSITION
CATEGORY 6 JACK - WIRELESS, BLUE
STATION PATCH PANEL, MODULAR, 48 PORT, BLACK, 2RU
SPP1
TELECOMMUNICATIONS MAIN GROUNDING BUS BAR
TELECOMMUNICATIONS GROUNDING BUS BAR
DATA OUTLET, SURFACE MOUNT BOX, WHITE, 1 POSITION
CATEGORY 6 JACK - SECURITY, BLUE
HORIZONTAL WIRE MANAGER, BLACK, 2RU, FRONT ONLYHWM
END CLOSING KIT, CABLE RUNWAY, BLACK
CABLE RUNWAY - 12", BLACK WITH ALL REQUIRED MOUNTING ACCESSORIES
BUTT SPLICE KIT, BLACK
JUNCTION SPLICE KIT, BLACK
ADJ JUNCTION SPLICE KIT, BLACK
FOOT KIT, BLACK
3" CHANNEL RACK TO RUNWAY, BLACK
TRIANGLE BRACKETS 12", BLACK
CHATSWORTH, RXL
END CLOSING KIT, CABLE RUNWAY, BLACK
RUNWAY WALL BRACKETS, BLACK
SWIVEL SPLICE KIT, BLACK
CABLE RUNWAY ELEVATION KIT, 6" CHATSWORTH, RXL
CATEGORY 6 JACK - DATA, BLUE
DATA OUTLET, SINGLE GANG FACEPLATE, WHITE, 2 POSITION
CATEGORY 6 JACK - DATA, BLUE
BLANK INSERT, WHITE
BLANK INSERT, BLACK
CHATSWORTH, RXL
CHATSWORTH, RXL
CHATSWORTH, RXL
CHATSWORTH, RXL
CHATSWORTH, RXL
CHATSWORTH, RXL
CHATSWORTH, RXL
CHATSWORTH, RXL
CHATSWORTH, RXL
CHATSWORTH, RXL
STATION CABLE, WIRELESS - CATEGORY 6A, UTP, PLENUM, BLUE
CATEGORY 6 JACK - WIRELESS, BLUE
COMMSCOPE, PANDUIT, LEVITON
COMMSCOPE, PANDUIT, LEVITON
COMMSCOPE, PANDUIT, LEVITON
COMMSCOPE, PANDUIT, LEVITON
COMMSCOPE, PANDUIT, LEVITON
COMMSCOPE, PANDUIT, LEVITON
COMMSCOPE, PANDUIT, LEVITON
COMMSCOPE, PANDUIT, LEVITON
COMMSCOPE, PANDUIT, LEVITON
COMMSCOPE, PANDUIT, LEVITON
COMMSCOPE, PANDUIT, LEVITON
COMMSCOPE, PANDUIT, LEVITON
COMMSCOPE, PANDUIT, LEVITON
PANDUIT, CHATSWORTH, COMMSCOPE
BLUE
BLUE
DATA
WIRELESS
COLOR TYPE
PANDUIT, GEN CABLE, COMMSCOPE, BERK-TEK
PS1 POWER DISTRIBUTION UNIT, SINGLE PHASE, 208/30 INPUT, NON-METERED,1RU, BLACK PANDUIT,CHATSWORTH, APC, RARITAN
EQUIPMENT RACK 19" x 7', 45 RU, BLACK CHATSWORTH 55053-703
VERTICAL WIRE MANAGER, BLACK 10", FRONT AND REARVWM PANDUIT, CHATSWORTH, COMMSCOPE
C
BLUE SECURITY
DATA OUTLET, SURFACE MOUNT BOX, WHITE, 2 POSITION
CATEGORY 6 JACK - DATA, BLUE COMMSCOPE, PANDUIT, LEVITON
COMMSCOPE, PANDUIT, LEVITON2C
COMMSCOPE, PANDUIT, LEVITONVOICE OUTLET, SINGLE GANG FACEPLATE, WHITE W/ WALL HUNG PHONEMOUNTING STUDS, ONE POSITION W/ CATEGORY 6 INSERT
NOTE: ALL ABBREVIATIONS MAY NOT BE USED.
ABBREVIATIONS
A - AUGMENTED
ER - EQUIPMENT ROOM
CAT - CATEGORY
E - ENHANCED
EA - EACH
FPP - FIBER PATCH PANEL
GIG - GIGA HERTZ
HWM - HORIZONTAL WIRE MANAGEMENT
TC - TELECOMMUNICATIONS ROOM
NIC - NOT IN CONTRACT
OE - OWNER ELECTRONICS
OFCI - OWNER FURNISHED CONTRACTOR INSTALLED
PNM - PLENUM
PR - PAIR
PS - POWER SUPPLY
RPP - RISER PATCH PANEL
SPP - TYPE S PATCH PANEL
TYP - TYPICAL
VWM - VERTICLE WIRE MANAGEMENT
NOTE: ALL DEFINITIONS MAY NOT BE USED.
DEFINITIONS
INDICATED: THE TERM "INDICATED" REFERS TO GRAPHIC REPRESENTATIONS,
NOTES, OR SCHEDULES ON THE DRAWINGS, OTHER PARAGRAPHS OR
SCHEDULES IN THE SPECIFICATIONS, AND SIMILAR REQUIREMENTS IN THE
CONTRACT DOCUMENTS. WHERE TERMS SUCH AS "SHOWN", "NOTED",
"SCHEDULED", AND "SPECIFIED" ARE USED, IT IS TO HELP THE READER LOCATE
THE REFERENCE, NO LIMITATION ON LOCATION IS INTENDED.
DIRECTED: TERMS SUCH AS "DIRECTED", "REQUESTED", AUTHORIZED",
"SELECTED", "APPROVED", "REQUIRED", AND "PERMITTED" MEAN "DIRECTED BY
THE ENGINEER", "REQUESTED BY THE ENGINEER", AND SIMILAR PHRASES.
APPROVE: THE TERM "APPROVED", WHERE USED IN CONJUNCTION WITH THE
ENGINEER'S ACTION ON THE CONTRACTOR'S SUBMITTALS, APPLICATIONS, AND
REQUESTS, IS LIMITED TO THE ENGINEER'S DUTIES AND RESPONSIBILITIES AS
STATED IN GENERAL AND SUPPLEMENTARY CONDITIONS.
FURNISH: THE TERM "FURNISH" IS USED TO MEAN "SUPPLY AND DELIVER TO THE
PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION,
AND SIMILAR OPERATIONS."
INSTALL: THE TERM "INSTALL" IS USED TO DESCRIBE OPERATIONS AT PROJECT
SITE INCLUDING THE ACTUAL "UNLOADING, UNPACKING, ASSEMBLY, ERECTION,
PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING,
PROTECTING, CLEANING, AND SIMILAR OPERATIONS."
PROVIDE: THE TERM "PROVIDE" MEANS "TO FURNISH AND INSTALL, COMPLETE
AND READY FOR THE INTENDED USE."
INSTALLER: AN "INSTALLER" IS THE CONTRACTOR OR AN ENTITY ENGAGED BY
THE CONTRACTOR, EITHER AS AN EMPLOYEE, SUBCONTRACTOR, OR
SUB-SUBCONTRACTOR, FOR PERFORMANCE OF A PARTICULAR CONSTRUCTION
ACTIVITY, INCLUDING INSTALLATION, ERECTION, APPLICATION, AND SIMILAR
OPERATIONS. INSTALLERS ARE REQUIRED TO BE EXPERIENCED IN THE
OPERATIONS THEY ARE ENGAGED TO PERFORM.
ELECTRONIC SYSTEMS: THE TERM "ELECTRONIC SYSTEMS" IS USED TO
DESCRIBE ALL LOW VOLTAGE SYSTEMS GENERALLY REFERRED TO AS "SPECIAL
SYSTEMS". THESE SYSTEMS INCLUDE BUT ARE NOT NECESSARILY LIMITED TO
ALL SYSTEMS WHICH UTILIZE VOLTAGES OF LESS THAN 71 VOLTS SUCH AS
SOUND SYSTEMS, VIDEO SYSTEMS, TV SYSTEMS, SECURITY SYSTEMS, VOICE
AND DATA CABLING SYSTEMS, ETC...
1. UNLESS OTHERWISE NOTED, INSTALL ALL CABLE INSIDE RACEWAY SYSTEMS.
WHERE RACEWAY SYSTEMS HAVE NOT BEEN PROVIDED OR SPECIFIED,
INSTALL CABLE THROUGH THE SPECIFIED "CADDY" CLIPS AT THE MINIMUM
INTERVALS IDENTIFIED IN THE SPECIFICATIONS. SUPPORT "CADDY" CLIPS
DIRECTLY FROM THE BUILDING STRUCTURE, NOT FROM OTHER BUILDING
SYSTEM SUPPORT WIRES OR CABLE.
2. PROVIDE PLENUM RATED CABLE FOR ALL PLENUM SPACES. VERIFY THAT ANY
PATHWAYS INSTALLED IN "WET OR DAMP" LOCATIONS AS DETERMINED BY THE
AHJ; SUCH AS PATHWAYS UNDER THE SLAB, ARE SUITABLE FOR THOSE
LOCATIONS AND THAT THE SPECIFIED CABLING SYSTEMS ARE ALSO SUITABLE
FOR THOSE LOCATIONS.
3. LABEL ALL CABLE INSTALLED UNDER THIS CONTRACT REGARDLESS OF
LENGTH. ACCORDING TO WRITTEN SPECIFICATION.
4. THE EQUIPMENT LABELING IDENTIFIED ON DETAILS IN THESE DRAWINGS ARE
EXAMPLES ONLY OF THE ACTUAL LABELING WHICH IS REQUIRED AS PART OF
THIS CONTRACT. PRIOR TO FABRICATION, SUBMIT THE NOMENCLATURE FOR
ALL LABELS TO THE OWNER FOR REVIEW. THIS REQUIREMENT INCLUDES BUT
IS NOT LIMITED TO ALL CABLE LABELING, AND ALL EQUIPMENT LABELING.
5. GROUND ALL EQUIPMENT RACKS LADDER RACK, AND EQUIPMENT INSTALLED
UNDER THIS CONTRACT IN COMPLIANCE WITH THE CONTRACT DOCUMENTS
AND WRITTEN SPECIFICATION.
6. COORDINATE WITH OWNER I.T. PERSONNEL ON RACK PATCH PANEL DENSITY
PRIOR TO ANY CABLE TERMINATION.
7. FACEPLATE COLOR WILL BE DETERMINED BY THE ARCHITECT AND OWNER.
FACEPLATE COLOR SHOULD MATCH ELECTRICAL FACEPLATE COLOR, UNLESS
OTHERWISE SPECIFIED.
8. FOR EVERY CABLE PULL SPECIFIED, COIL 10" OF EXCESS CABLE AT THE
STATION END FOR FUTURE USE.
9. COORDINATE WITH ALL SUBS TO ENSURE THAT ALL CABLE SHALL BE
PROTECTED FROM ANY DIRECT PAINT OR INCIDENTAL OVERSPRAY.
OUTLET COLOR SCHEDULE
2
W
3
3
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
PROJECT NO.
SHEET TITLE:
Plo
t Da
te:
ArchitectureInterior DesignLandscape ArchitectureLand PlanningConstruction Management
7927 So. Highpoint Parkway, Suite 300
Sandy, Utah 84094
ph. 801.269.0055
fax 801.269.1425
www.thinkaec.com
The designs shown and described herein
including all technical drawings, graphic
representation & models thereof, are proprietary
& can not be copied, duplicated, or
commercially exploited in whole or in part
without the sole and express written permission
from THINK Architecture, inc.
These drawings are available for limited review
and evaluation by clients, consultants,
contractors, government agencies, vendors,
and office personnel only in accordance with
this notice.
SHEET NUMBER:
REVISIONS:
DATE:
4/2
9/2
02
1 2
:54
:36
PM
LAYT
ON
FIR
E ST
ATI
ON
#54
885
EAST
PO
NTI
AC
DRI
VE
LAYT
ON
, UTA
H 8
4041
Mar. 4, 2021
200371
TELECOM SCHEDULES
AND NOTES
ET001
3 4/28/2021 ADDENDUM #3
SHEET INTENDED TO BE PRINTED IN COLOR FOR CLARITY. DO NOT PRINT IN BLACK AND WHITE.
04-29-2021
DW
C
C
C
C
DB
C
C
ELECTRICAL
101
LAUN.
103
MECH
104
FIRE RISER
106
MECH.
130
SHIFT
OFFICE
129
PANTRY
110
LOBBY
128
TURN OUT
102 HALL
117
UTILITY
112
SLEEPING 7
127 SLEEPING 6
126
SLEEPING 5
125
SLEEPING 4
124
APPARATUS
BAY
107BATH
115
BATH
114
BATH
113
HALL
122
BATH
105
OFFICE
123
DAY ROOM
108
IT
111 SLEEPING 3
120
SLEEPING 2
119
SLEEPING 1
118
BATH
121
WORK OUT
116
KITCHEN
109
2
2
+86"
+86"
2
2+86"
+86"
+86"2
A A
A
A
2
22
2
W
2
W
2+86"
+86"
+48"+48"
4
4
3
3
1
1
AA
5
5
6
6
EE
DD
BB
CC
2
2
ET101
2
ET101
3
+18'-0"AFF
+18'-0"AFF
+120"
2C
1
+120"
2C
2
4"x4"
+168" AFF
4"x4"
+168" AFF
4"x4"
+168" AFF
4"x4"
+168" AFF
+120"
2C
2
4"x4"
+156" AFF
4"x4"
+156" AFF
4"x4"
+156" AFF
3
3
4
4
IT
111
A-1
"FACP"
GROUND BUS BARMOUNTED AT+8'-0" AFF
2 EA., 4" CND TO"HH-1" AT SITEFOR SERVICEPROVIDER
4
4
IT
111
12"x1" LADDER RACKMOUNTED AT+7'-6" AFF
4"x4" CABLE TRAYMOUNTED AT+13'-0" AFF
12"x1" VERTICAL LADDERRACK FROM FLOOR UP TO DECK ABOVE FORCABLE PATHWAY
GENERAL SHEET NOTES
SHEET KEYNOTES1 COORDINATE EXACT TERMINATION LOCATION OF DATA DEVICE IN OPEN CEILING
WITH ELECTRICAL INSTALLER.
2 COORDINATE EXACT TERMINATION LOCATION OF DATA DEVICE IN OPEN CEILINGWITH MECHANICAL INSTALLER.
3 MOUNT WIRELESS ACCESS POINT DEVICE IN OPEN CEILING ACCORDING TO DETAIL8/ET502.
1 PLANS IN GENERAL SHOW CABLE TRAYS IN PLAN AND DO NOT DETAIL CHANGES INELEVATION. COORDINATE LAYOUT AND INSTALLATION OF CABLE TRAYS ANDSUSPENSION SYSTEM WITH OTHER CONSTRUCTION ELECEMENTS. INCLUDETRANSITIONS, OFFSETS AND CHANGES IN ELEVATION. COORDINATE ITEMS THATPENETRATE CEILINGS OR ARE SUPPORTED BY THEM, INCLUDING LIGHT FIXTURES,HVAC EQUIPMENT, FIRE SUPRESSION SYSTEMS AND PARTITION ASSEMBLIES.
2 PROVIDE 18” WIDE, LADDER STYLE CABLE TRAY UNLESS OTHERWISE NOTED.
3 LOCATE CABLE TRAY ABOVE ACCESSIBLE CEILING TILE AND BELOW PIPING ANDDUCT WORK SUCH THAT CEILING TILE CAN BE REMOVED AND TOP OF TRAY ISACCESSIBLE.
4 COORDINATE ACTUAL CABLE TRAY ROUTIN WITH MECHANICAL AND OTHERTRADES SO THAT CABLE TRAY IS ACCESSIBLE AND THE CABLE TRAY DOES NOTBLOCK ACCESS TO OTHER EQUIPMENT.
5 COORDINATE LAYOUT OF CABLE TRAY IN IDF ROOMS WITH THE I.T. CABLINGINSTALLER.
6 DO NOT SUPPORT ELECTRICAL CABLES AND RACEWAYS FROM CABLE TRAY.MAINTAIN AT LEAST 12’’ SEPARATION FROM CABLE TRAY TO POWER RACEWAYSOR CABLES AND LIGHT FIXTURES.
7 WHER CABLE TRAY PASSES THROUGH FIRE-RATED WALLS. PROVIDE (4) 4’’CONDUIT SLEEVES THROUGH WALLS AND FIRE STOP AFTER CABLES AREINSTALLED.
8 ROUTE CONDUIT STUBS TO CABLE TRAY SUCH THAT A MAXIMUM CABE DISTANCEOF 275’ IS NOT EXCEEDED BETWEEN THE OUTLET AND NEAREST IDF ROOM.
9 COORDINATE MOUNTING LOCATIONS OF ALL EQUIPMENT IN IDF AND MDF ROOMSWITH UVU IT PERSONEL.
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
PROJECT NO.
SHEET TITLE:
Plo
t Da
te:
ArchitectureInterior DesignLandscape ArchitectureLand PlanningConstruction Management
7927 So. Highpoint Parkway, Suite 300
Sandy, Utah 84094
ph. 801.269.0055
fax 801.269.1425
www.thinkaec.com
The designs shown and described herein
including all technical drawings, graphic
representation & models thereof, are proprietary
& can not be copied, duplicated, or
commercially exploited in whole or in part
without the sole and express written permission
from THINK Architecture, inc.
These drawings are available for limited review
and evaluation by clients, consultants,
contractors, government agencies, vendors,
and office personnel only in accordance with
this notice.
SHEET NUMBER:
REVISIONS:
DATE:
4/2
9/2
02
1 2
:54
:35
PM
LAYT
ON
FIR
E ST
ATI
ON
#54
885
EAST
PO
NTI
AC
DRI
VE
LAYT
ON
, UTA
H 8
4041
Mar. 4, 2021
200371
LEVEL 1 TELECOM
FLOOR PLAN
ET101
3 4/28/2021 ADDENDUM #3
SCALE: 1/8" = 1'-0"1LEVEL 1 TELECOM PLAN
SCALE: 1/4" = 1'-0"
ENLARGED IT 111 EQUIPMENT RACKPLAN
2SCALE: 1/4" = 1'-0"
ENLARGED IT 111 LADDER RACKPLAN
3SCALE:
ENLARGED IT 111 ISOMETRIC PLAN4
SHEET INTENDED TO BE PRINTED IN COLOR FOR CLARITY. DO NOT PRINT IN BLACK AND WHITE.
3
3
3
04-29-2021
1TELECOM EQUIPMENT RACK ELEVATION, LEVEL 1, IT 111NO SCALE
A-1
HWM (2RU)
SPP1 (2RU)
HWM (2RU)
SPP1 (2RU)
PS1 (1RU)
PS1 (1RU)
HWM (2RU)
45RU EQUIPMENT RACK,7'-0" (HIGH) x 19" (W),TYPICAL
VERTICAL WIREMANAGEMENT,7'-0" (HIGH) x 10" (W),TYPICAL
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
PROJECT NO.
SHEET TITLE:
Plo
t Da
te:
ArchitectureInterior DesignLandscape ArchitectureLand PlanningConstruction Management
7927 So. Highpoint Parkway, Suite 300
Sandy, Utah 84094
ph. 801.269.0055
fax 801.269.1425
www.thinkaec.com
The designs shown and described herein
including all technical drawings, graphic
representation & models thereof, are proprietary
& can not be copied, duplicated, or
commercially exploited in whole or in part
without the sole and express written permission
from THINK Architecture, inc.
These drawings are available for limited review
and evaluation by clients, consultants,
contractors, government agencies, vendors,
and office personnel only in accordance with
this notice.
SHEET NUMBER:
REVISIONS:
DATE:
4/2
9/2
02
1 2
:54
:23
PM
LAYT
ON
FIR
E ST
ATI
ON
#54
885
EAST
PO
NTI
AC
DRI
VE
LAYT
ON
, UTA
H 8
4041
Mar. 4, 2021
200371
TELECOM EQUIPMENT
RACK ELEVATIONS
ET501
3 4/28/2021 ADDENDUM #3
DATA DEVICE DROP SCHEDULE - IT 111
DATA DEVICE TYPEDETAIL
LOCATIONCOMM ROOM
LOCATIONTOTAL BY
FLOOR Num of DropsLEVEL 1
CEILING DATA (2-DROP) SEE DETAIL 6/ET502 IT 111 3 6
CEILING DATA - CAMERA (1-DROP) SEE DETAIL 2/ET502 IT 111 1 1
CEILING WIRELESS ACCESS POINT (2-DROP) SEE DETAIL 1/ET502 IT 111 6 8
WALL DATA (2-DROP) SEE DETAIL 7/ET502 IT 111 7 14
WALL DATA - ABOVE COUNTER (2-DROP) SEE DETAIL 7/ET502 IT 111 4 8
WALL DATA - CAMERA (1-DROP) SEE DETAIL 2/ET502 IT 111 5 5
WALL DATA - PHONE (1-DROP) SEE DETAIL 4/ET502 IT 111 2 2
Grand total 28 44
SHEET INTENDED TO BE PRINTED IN COLOR FOR CLARITY. DO NOT PRINT IN BLACK AND WHITE.
3
3
04-29-2021
VERTICAL WIRE
MANAGEMENT
FRONT
REAR
24"LADDER
RACK
EQUIPMENT RACK
SIDE VIEW
VERTICAL WIRE
MANAGEMENT
EQUIPMENT RACK
22
C
A
2C15EQUIPMENT RACK/RACEWAY MOUNTING DETAIL
8
CEILING WIRELESS APMOUNTING DETAIL
10
EQUIPMENT RACK/ENCLOSEDCABINET ANCHOR DETAIL
11
FOOT/WALLATTACHMENT DETAIL
12
CABLE RUNWAY ENDCLOSING SPLICE DETAIL
14
TRIANGLE BRACKETDETAIL
9
CABLE INDENTIFICATIONEXAMPLE DETAIL
5
VOICE-DATA OUTLETPINNING DETAIL
3
TYPICAL 1-DROP WALLDATA OUTLET
1
TYPICAL 2-DROP WAPDATA OUTLET
7
TYPICAL 2-DROPWALL DATA OUTLET
136" CHANNEL RACK-TO-RUNWAY MOUNTING PLATE
6
TYPICAL 2-DROPCEILING DATA OUTLET
2
TYPICAL 1-DROPCAMERA DATA OUTLET
4
TYPICAL 1-DROP WALLPHONE DATA OUTLET
111
1 2 43 5 6 87
2 R2-O/W
6 R3-GR/W
3 T3-W/GR
8 R4-BR/W
7 T4-W/BR
5 T1-W/BL
1 T2-W/O
4 R1-BL/W
PINNING (T568B)
# COLOR
PIN RP/RP1
RP3
RP2 RP4
TR NUMBER
CAT 6A, RJ-45INSERT, WIRELESS,
BLUE, TYPICAL
SCALE: 2" = 1'-0"
CONCRETE SLAB
RACK BASE ANGLE
HILTI .5" HIT HY 150INJECTION ADHESIVEANCHOR 2.125"EMBEDMENTLENGTH. TYPICAL OFALL FOUR CORNERS.
FLOOR ATTACHMENT WALL ATTACHMENT
A 01
PATCH PANEL NUMBER
PORT NUMBER
111-A-01 111-A-02
TYPICAL LABEL,STATION NUMBER(EXAMPLE ONLY) 111-A-01 111-A-02
FACE PLATE
CAT 6, RJ-45INSERT, DATA,BLUE, TYPICAL
TYPICAL LABEL,STATION NUMBER(EXAMPLE ONLY)
FACE PLATE
CAT 6, RJ-45INSERT, DATA,
BLUE
SURFACE MOUNTED 2POSITION BOX WITH 2 CAT 6AJACKS, TYP.
(2) CAT 6A PATCH CORDS, TYP.
CEILING MOUNT
T-BAR MOUNT
SURFACE MOUNTED 2POSITION BOX WITH 2 CAT 6AJACKS, TYP.
(2) CAT 6A PATCH CORDS, TYP.
SURFACE MOUNTED 2POSITION BOX WITH 2 CAT 6AJACKS, TYP.
OPEN CEILING MOUNT
1" CONDUIT, TYP.
J-HOOK, TYP
1" CONDUIT, TYP.
(2) CAT 6A CABLES, TYP.
(2) CAT 6A CABLES, TYP.
(2) CAT 6A CABLES, TYP.
4" SQUARE BOX
4" SQUARE BOX
MOUNTING PLATE
MOUNTING PLATE
GRID CEILING T-BARSUPPORT
ADAPTER CLIP TOMOUNT DEVICE TO
T-BAR SUPPORT
(2) CAT 6A PATCH CORDS, TYP.
CABLE COIL, TYP.
ROOF/DECK
111-A-01
TYPICAL LABEL,STATION NUMBER(EXAMPLE ONLY)
SURFACE MOUNT BOX
NO SCALE
NO SCALE
BLANK INSERT,WHITE
PERPENDICULAR MOUNTING PARALLEL MOUNTING
NO SCALE
CAT 6, RJ-45INSERT, DATA,BLUE, TYPICAL
111-A-01 111-A-02
TYPICAL LABEL,STATION NUMBER(EXAMPLE ONLY)
SURFACE MOUNT BOX
LABEL, STATIONNUMBER(EXAMPLE ONLY)
SINGLE GANGFACEPLATE
CAT 6A, RJ-45INSERT, BLUE
METALMOUNTING LUGS,TYP
111-A-01
CAT 6, RJ-45INSERT,
SECURITY, BLUE
111-A-01
TYPICAL LABEL,STATION NUMBER(EXAMPLE ONLY)
SURFACE MOUNT BOX
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
PROJECT NO.
SHEET TITLE:
Plo
t Da
te:
ArchitectureInterior DesignLandscape ArchitectureLand PlanningConstruction Management
7927 So. Highpoint Parkway, Suite 300
Sandy, Utah 84094
ph. 801.269.0055
fax 801.269.1425
www.thinkaec.com
The designs shown and described herein
including all technical drawings, graphic
representation & models thereof, are proprietary
& can not be copied, duplicated, or
commercially exploited in whole or in part
without the sole and express written permission
from THINK Architecture, inc.
These drawings are available for limited review
and evaluation by clients, consultants,
contractors, government agencies, vendors,
and office personnel only in accordance with
this notice.
SHEET NUMBER:
REVISIONS:
DATE:
4/2
9/2
02
1 2
:54
:21
PM
LAYT
ON
FIR
E ST
ATI
ON
#54
885
EAST
PO
NTI
AC
DRI
VE
LAYT
ON
, UTA
H 8
4041
Mar. 4, 2021
200371
TELECOM DETAILS
ET502
3 4/28/2021 ADDENDUM #3
SHEET INTENDED TO BE PRINTED IN COLOR FOR CLARITY. DO NOT PRINT IN BLACK AND WHITE.
3
04-29-2021
1STATION PATCH PANEL, SPP1, TYPICAL
CAT 6, RJ-45 INSERT, DATA,BLUE, TYP.
NO SCALE
CAT 6A, RJ-45 INSERT,WIRELESS, BLUE, TYP.
CAT 6A, RJ-45 INSERT,SECURITY, BLUE, TYP.
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
PROJECT NO.
SHEET TITLE:
Plo
t Da
te:
ArchitectureInterior DesignLandscape ArchitectureLand PlanningConstruction Management
7927 So. Highpoint Parkway, Suite 300
Sandy, Utah 84094
ph. 801.269.0055
fax 801.269.1425
www.thinkaec.com
The designs shown and described herein
including all technical drawings, graphic
representation & models thereof, are proprietary
& can not be copied, duplicated, or
commercially exploited in whole or in part
without the sole and express written permission
from THINK Architecture, inc.
These drawings are available for limited review
and evaluation by clients, consultants,
contractors, government agencies, vendors,
and office personnel only in accordance with
this notice.
SHEET NUMBER:
REVISIONS:
DATE:
4/2
9/2
02
1 2
:54
:20
PM
LAYT
ON
FIR
E ST
ATI
ON
#54
885
EAST
PO
NTI
AC
DRI
VE
LAYT
ON
, UTA
H 8
4041
Mar. 4, 2021
200371
TELECOM DETAILS
ET503
3 4/28/2021 ADDENDUM #3
SHEET INTENDED TO BE PRINTED IN COLOR FOR CLARITY. DO NOT PRINT IN BLACK AND WHITE.
3
04-29-2021
3"
6"
12"
6"
3"
12" 6"
6CABLE TRAY WITH SEISMIC SUPPORTS DETAIL
4CABLE TRAY WITH SUPPORT AT SPLICE POINT DETAIL
110'-0" CABLE TRAY WITH SUPPORT AT ENDS DETAIL
7CABLE TRAY INTERSECTION WITH SUPPORTS DETAIL
5CABLE TRAY WITH PARALLEL OBSTRUCTION DETAIL
2CABLE TRAY WITH PERPENDICULAR CROSSING DETAIL
3CABLE TRAY 90 DEGREE BEND WITH SUPPORTS DETAIL
CABLE TRAYSPLICE POINT
ISOMETRIC VIEW
SIDE VIEW
ISOMETRIC VIEW
ISOMETRIC VIEW
CABLE TRAY
UNISTRUT SUPPORT,TYPICAL
WASHER AND NUTABOVE AND BELOWUNISTRUT, TYPICAL
THREADED ROD,TYPICAL
NOTE:
INSTALL UNISTRUT
SUPPORT NO LESS
THAN 1'-0" FROM
EITHER SIDE OF
CABLE TRAY SPLICE
POINT.
NOTE:
INSTALL UNISTRUT
SUPPORT NO LESS
THAN 1'-0" FROM
EITHER END OF
CABLE TRAY ON 10'-0"
SECTION.
UNISTRUT SUPPORT,TYPICAL
CABLE TRAY
THREADED ROD,TYPICAL
CABLE TRAY
UNISTRUT SUPPORT
THREADED ROD,TYPICAL
DUCT WORK
FINISHEDCEILING
ISOMETRIC VIEW
SIDE VIEW
CABLE TRAY
UNISTRUT SUPPORT
THREADED ROD,TYPICAL
DUCT WORK
FINISHEDCEILING
USE MANUFACTURERS JOINTSPLICE SPECIFICATIONS TOENSURE PROPER BONDING
WASHER AND NUTABOVE AND BELOWUNISTRUT, TYPICAL
WASHER AND NUTABOVE AND BELOWUNISTRUT, TYPICAL
WASHER AND NUTABOVE AND BELOWUNISTRUT, TYPICAL
NOTE:
MAXIMUM WIDTH OF
PERPENDICULAR
CROSSING IS 6 FEET
WIDE.
ISOMETRIC VIEW
NOTE:
INSTALL UNISTRUT
SUPPORT NO LESS
THAN 1'-0" FROM
CABLE TRAY SPLICE
POINT, TYPICAL.
UNISTRUT SUPPORT,TYPICAL
THREADED ROD,TYPICAL
CABLE TRAY
ISOMETRIC VIEW
CABLE TRAY
THREADED ROD,TYPICAL
UNISTRUT SUPPORT
SEISMIC SUPPORT,TYPICAL
SEISMICSUPPORT,
TYPICAL
ISOMETRIC VIEW
NOTE:
INSTALL UNISTRUT
SUPPORT NO LESS
THAN 1'-0" FROM
CABLE TRAY SPLICE
POINT, TYPICAL.
UNISTRUT SUPPORT,TYPICAL
THREADED ROD,TYPICAL
CABLE TRAY
NOTE:
SEISMIC ENGINEERING TO BE DONE
BY OTHERS.
WASHER AND NUTABOVE AND BELOWUNISTRUT, TYPICAL
WASHER AND NUTABOVE AND BELOWUNISTRUT, TYPICAL
WASHER AND NUTABOVE AND BELOWUNISTRUT, TYPICAL
NO SCALE NO SCALE NO SCALE
NO SCALE NO SCALE NO SCALE
NO SCALE
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
PROJECT NO.
SHEET TITLE:
Plo
t Da
te:
ArchitectureInterior DesignLandscape ArchitectureLand PlanningConstruction Management
7927 So. Highpoint Parkway, Suite 300
Sandy, Utah 84094
ph. 801.269.0055
fax 801.269.1425
www.thinkaec.com
The designs shown and described herein
including all technical drawings, graphic
representation & models thereof, are proprietary
& can not be copied, duplicated, or
commercially exploited in whole or in part
without the sole and express written permission
from THINK Architecture, inc.
These drawings are available for limited review
and evaluation by clients, consultants,
contractors, government agencies, vendors,
and office personnel only in accordance with
this notice.
SHEET NUMBER:
REVISIONS:
DATE:
4/2
9/2
02
1 2
:54
:18
PM
LAYT
ON
FIR
E ST
ATI
ON
#54
885
EAST
PO
NTI
AC
DRI
VE
LAYT
ON
, UTA
H 8
4041
Mar. 4, 2021
200371
TELECOM DETAILS
ET504
3 4/28/2021 ADDENDUM #3
SHEET INTENDED TO BE PRINTED IN COLOR FOR CLARITY. DO NOT PRINT IN BLACK AND WHITE.3
04-29-2021
1TELECOM EQUIPMENT RACK GROUNDING DETAIL
OSP COPPER
FUSE PROTECTION
BASKET TRAY, FOLLOWMANUFACTURER'SGROUNDING INSTRUCTIONS
GROUNDING ELECTRODE TOBUILDING ELECTRODE SYSTEM
(OVERHEAD OR UNDERGROUND)
1 EA., #6GREEN
1 EA., #6GREEN
ENTRANCE CONDUITSOR METALLIC SLEEVES
LADDER RACK JUNCTIONSPLICE
1 EA., #6 GROUNDING STRAP
LADDER RACK,TYPICAL
1 EA., #6 GROUNDING STRAP
GENERAL NOTES:
1. ALL LOW VOLTAGE COMMUNICATIONS CONDUIT SHALL BE GROUNDED TO
BASKET TRAY OR TELECOMMUNICATIONS GROUNDING BUS BAR.
2. "TMGB" SHOULD BE 1/4"x4"x24".
3. "TGB" SHOULD BE 1/4"x2"x24".
4. EMT CONDUIT GROUNDING CLAMP SHOULD BE ELECTROLYTIC CAST BRONZE.
PANDUIT PART NUMBER GPL-"X"-"X", OR EQUAL.
5. RIGID CONDUIT GROUND CLAMP SHOULD BE O-Z/GEDNEY BLG-XXXX, OR
HBLG-XXXX, OR EQUAL.
6. GROUNDING LUGS SHOULD BE TWO HOLE LONG BARREL LUGS. PANDUIT
PART NUMBER LCC6, OR EQUAL.
COMMUNICATIONOUTLET
COMMUNICATIONOUTLET
COMMUNICATIONOUTLET
CND, TYP.
BEAM CLAMP,TYPICAL
TO ELECTRICALPANEL
TMGB/TGB,TYP.
1 EA., #6GREEN
NO SCALE
FB/PT
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
PROJECT NO.
SHEET TITLE:
Plo
t Da
te:
ArchitectureInterior DesignLandscape ArchitectureLand PlanningConstruction Management
7927 So. Highpoint Parkway, Suite 300
Sandy, Utah 84094
ph. 801.269.0055
fax 801.269.1425
www.thinkaec.com
The designs shown and described herein
including all technical drawings, graphic
representation & models thereof, are proprietary
& can not be copied, duplicated, or
commercially exploited in whole or in part
without the sole and express written permission
from THINK Architecture, inc.
These drawings are available for limited review
and evaluation by clients, consultants,
contractors, government agencies, vendors,
and office personnel only in accordance with
this notice.
SHEET NUMBER:
REVISIONS:
DATE:
4/2
9/2
02
1 2
:54
:17
PM
LAYT
ON
FIR
E ST
ATI
ON
#54
885
EAST
PO
NTI
AC
DRI
VE
LAYT
ON
, UTA
H 8
4041
Mar. 4, 2021
200371
TELECOM EQUIPMENT
RACK GROUNDING
DETAIL
ET505
3 4/28/2021 ADDENDUM #3
SHEET INTENDED TO BE PRINTED IN COLOR FOR CLARITY. DO NOT PRINT IN BLACK AND WHITE.
3
04-29-2021
C
STATION
PATCH
PANEL,
(SPP1)
OWNEREQUIPMENT
(NIC)
1TELECOM CONDUIT RISER DIAGRAM
2TELECOM CABLE RISER DIAGRAM
A
2C
4-11/16" SQUARE
BOX SINGLE GANG
MUD RING
2C
TO "HH-1" AT SITE FORSERVICE PROVIDERS
NO SCALE
1 #6 CU TOGROUNDINGELECTRODE
CABLE TRAY, TYP.
1" CND, TYP.
1" CND, TYP.
NO SCALE
1 EA., CAT 6PATCH CORD
WALLMOUNTED
2 EA, CAT 6 CABLE, BLUE
1 EA, CAT 6 CABLE, BLUE
2 EA, CAT 6 CABLE, BLUE
1 EA, CAT 6 CABLE, BLUE
2 EA, CAT 6 CABLE, BLUE
2 EA, CAT 6A CABLE, BLUE
1 EA, CAT 6 CABLE, BLUE
2 EA., 4" CND W/3 EA., 1.25" INNERDUCT
(IN EACH CONDUIT)
LADDERRACK
LEVEL 1, IT 111
ACCESSIBLE CEILING
C
LEVEL 1
ROOF
LEVEL 1, IT 111
ROOF
A
2 2
2
W
2
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
PROJECT NO.
SHEET TITLE:
Plo
t Da
te:
ArchitectureInterior DesignLandscape ArchitectureLand PlanningConstruction Management
7927 So. Highpoint Parkway, Suite 300
Sandy, Utah 84094
ph. 801.269.0055
fax 801.269.1425
www.thinkaec.com
The designs shown and described herein
including all technical drawings, graphic
representation & models thereof, are proprietary
& can not be copied, duplicated, or
commercially exploited in whole or in part
without the sole and express written permission
from THINK Architecture, inc.
These drawings are available for limited review
and evaluation by clients, consultants,
contractors, government agencies, vendors,
and office personnel only in accordance with
this notice.
SHEET NUMBER:
REVISIONS:
DATE:
4/2
9/2
02
1 2
:54
:16
PM
LAYT
ON
FIR
E ST
ATI
ON
#54
885
EAST
PO
NTI
AC
DRI
VE
LAYT
ON
, UTA
H 8
4041
Mar. 4, 2021
200371
TELECOM RISER
DIAGRAMS
ET601
3 4/28/2021 ADDENDUM #3
SHEET INTENDED TO BE PRINTED IN COLOR FOR CLARITY. DO NOT PRINT IN BLACK AND WHITE.
3
04-29-2021
LAYTON UTAH
FIRE STATION 54
Table of Contents: Division 26, 27, & 28 COVER PAGE DIVISION 26: ELECTRICAL SECTION 260500 COMMON WORK RESULTS FOR ELECTRICAL 260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260529 HANGERS & SUPPORTS FOR ELECTRICAL SYSTEMS 260533 RACEWAYS & BOXES FOR ELECTRICAL SYSTEMS 260536 CABLE TRAYS FOR ELECTRICAL SYSTEMS
260548 VIBRATION & SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS 260553 IDENTIFICATION OF ELECTRICAL SYSTEMS 260572 OVERCURRENT PROTECTIVE DEVICE SHORT-CIRCUIT STUDY 260573 OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY 260574 OVERCURRENT PROTECTIVE DEVICE ARC-FLASH STUDY
260923 LIGHTING CONTROL DEVICES 260943 NETWORK LIGHTING CONTROLS
262413 SWITCHBOARDS 262416 PANELBOARDS 262726 WIRING DEVICES 262726.1 WIRING DEVICE SCHEDULE 262813 FUSES 262816 ENCLOSED SWITCHES AND CIRCUIT BREAKERS 262913 ENCLOSED CONTROLLERS 263213 ENGINE GENERATORS 263600 TRANSFER SWITCHES 264313 SURGE PROTECTION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS 265100 INTERIOR LIGHTING 265600 EXTERIOR LIGHTING DIVISION 27: COMMUNICAITONS SECTION 271100 TELECOMMUNICATIONS PATHWAYS AND SPACES 271300 COMMUNICATION BACKBONE CABLING 271500 COMMUNICATIONS HORIZONTAL CABLING 271100 - TELECOMMUNICATIONS PATHWAY AND SPACES 271500 - COMMUNICATIONS HORIZONTAL CABLING DIVISION 28: ELECTRONIC SAFETY AND SECURITY SECTION 281300 ACCESS CONTROLS 281316 SECURITY AND DATABASE MANAGEMENT SYSTEM 283111 DIGITAL ADDRESSABLE FIRE ALARM SYSTEM 283000 CCTV 284000 INTRUSION DETECTION END OF TABLE OF CONTENTS
TELECOMMUNICATIONS PATHWAY AND SPACES 271100
SECTION 271100 - TELECOMMUNICATIONS PATHWAYS AND SPACES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:1. Telecommunications vertical and horizontal pathways.2. Backboards and mounting elements.3. Telecommunications equipment racks and cabinets.4. Telecommunications service entrance pathways.5. Grounding.
B. Related Sections:1. Division 271300 Section "Communications Backbone Cabling" for voice and data
cabling associated with system panels and devices.2. Division 271500 Section "Communications Horizontal Cabling" for voice and data
cabling associated with system panels and devices.
1.3 DEFINITIONS
A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.
B. BICSI: Building Industry Consulting Service International.
C. EIA: Electronic Industries Alliance.
D. TIA: Telecommunications Industry Association
E. ANSI: American National Standard Institute
F. RCDD: Registered Communications Distribution Designer.
1.4 REFERENCES
A. ANSI/TIA-568-D Telecommunications Pathways and Spaces, 2015
B. ANSI/TIA-568-D.0 Generic Telecommunications Cabling for Customer Premises, 2015
C. ANSI/TIA – 568-D.1 Commercial Building Telecommunications Cabling Standard, 2015.
D. ANSI/NECA/BICSI 568-2006 – Standard for Installing Commercial Building Telecommunication Cabling
E. ANSI/TIA-942-A Telecommunications Infrastructure Standard for Data Centers, 2014.
TELECOMMUNICATIONS PATHWAY AND SPACES 271100
F. ANSI/TIA – 606-B Administration Standard for Telecommunications Infrastructure, 2012.
G. ANSI/TIA – 607-C Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises, 2015.
H. NFPA 70 – National Electric Code, 2008, 2014, 2017
1.5 PERFORMANCE REQUIREMENTS
A. Seismic Performance: Floor-mounted cabinets, racks and cable pathways shall withstand the effects of earthquake motions determined according to SEI/ASCE 7, (Zone 4).
1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified and the unit will be fully operational after the seismic event.
1.6 SUBMITTALS
A. Product Data: For each type of product indicated. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for equipment racks and cabinets. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories.
B. Shop Drawings: For communications equipment room fittings. Include plans, elevations, sections, details, and attachments to other work.
1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.
2. Equipment Racks and Cabinets: Include workspace requirements and access for cable connections.
3. Grounding: Indicate location of grounding bus bar and its mounting detail showing standoff insulators and wall mounting brackets.
C. Qualification Data: For each qualified layout technician, installation supervisor, and field inspector.
D. Seismic Qualification Certificates: For floor-mounted cabinets, accessories, and components, from manufacturer.
1. Basis for Certification: Indicate whether withstand certification is based on actual test of assembled components or on calculation.
2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions. Base certification on the maximum number of components capable of being mounted in each rack type. Identify components on which certification is based.
3. Detailed description of equipment anchorage devices on which the certification is based and their installation requirements.
1.7 QUALITY ASSURANCE
A. Installer Qualifications: Cabling Installer must have personnel certified by BICSI on staff.
TELECOMMUNICATIONS PATHWAY AND SPACES 271100
1. Layout Responsibility: Preparation of Shop Drawings shall be under the direct supervision of an RCDD.
2. Installation Supervision: Installation shall be under the direct supervision of a Registered Technician (BICSI), who shall be present at all times when Work of this Section is performed at Project site.
3. Field Inspector: Currently registered by BICSI as an RCDD to perform the on-site inspection.
4. Contractor must be certified prior to time of bid with the manufacturer, and must be able to provide a complete system warranty for products installed by the listed manufacturers.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
C. Telecommunications Pathways and Spaces: Comply with ANSI/TIA/EIA-569-B.
D. Grounding: Comply with ANSI-J-STD-607-A.
1.8 PROJECT CONDITIONS
A. Environmental Limitations: Do not deliver or install equipment frames and cable trays until spaces are enclosed and weathertight, wet work in spaces is complete and dry, and associated construction work on the subfloor and raised floor supports is substantially complete.
PART 2 - PRODUCTS
2.1 PATHWAYS
A. General Requirements: Comply with ANSI/TIA/EIA-569-B.
B. Cable Support (J-Hook): Cable installation that does not require basket cable tray management, but shall require support of cables with J-Hooks. J-Hook pathway support will be spaced no more than 60” between supports.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:a. Erico Caddyb. B-Linec. CTSd. Stiffye. Panduit
2. Cable Support Materials (J-Hook) shall meet or exceed the below characteristics of construction and features.a. Provide broad based support for cabling to aid in maintaining overall system
performance.b. Be available in 50.8mm (2”) and 101.6mm (4”) optionsc. Come equipped with a cable retention clipd. Offers a full line of mounting accessories.
C. Cable Trays:
TELECOMMUNICATIONS PATHWAY AND SPACES 271100
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:a. Cablofil Inc.b. Cooper B-Line, Inc.c. WBT Wire Basket Tray
2. Cable Tray Materials: Metal, suitable for indoors and protected against corrosion by electroplated zinc galvanizing, complying with ASTM B 633, Type 1, not less than 0.000472 inch (0.012 mm) thick.a. Basket Cable Trays: Provide tray widths as noted – 4 – 24 inches - wide and
minimum 2 inch deep. Wire mesh spacing shall not exceed 2 by 4 inches.
D. Ladder Rack:1. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:a. Chatsworthb. RXL
2. Description: a. Size: 1.5 inches high by 0.4 inches wide high tubular steel with 0.065 inch wall
thickness.b. Stringers: 9 feet 11-1/2 inches long.c. Cross Members: Welded in between stringers on 12 inch intervals/centers
beginning 5-3/4 inches with 10 cross members per ladder rack. Open space of 10-1/2 inches between each cross member.
d. Finish and Color: Powder coat paint in black.e. Provide cable tray widths as noted, 12” – 24” wide.
E. Conduit and Boxes: Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical Systems".
F. Conduit Sleeves: Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical Systems".
G. Conduit and Boxes (Wireless Access Points): Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical Systems". Provide a 1” conduit and two gang box, coordinated with the finished height of a hard lid ceiling for outlet mounting, and extend the conduit to the nearest cable tray.
2.2 BACKBOARDS
A. Backboards: Provide plywood, fire-retardant treated, 3/4 by 48 by 96 inches, on at least two of the full non-door walls of each telecommunications room, or as noted. Comply with requirements for plywood backing panels specified in Division 06 Section "Rough Carpentry."
2.3 EQUIPMENT FRAMES TWO POST
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
TELECOMMUNICATIONS PATHWAY AND SPACES 271100
1. Chatsworth2. RXL
B. General Frame Requirements:1. Mounting Channels: 3 inches (76 mm) deep and punched on the front and rear flange
with the EIA-310-D Universal hole pattern.2. Capacaity: 1,000 lb3. UL and cUL Listed as a Communications Circuit Accessory, DUXR and DUXR7 category,
file number 140851.4. Size:
7 feet (2.1 m) high by 20.3 inches (515.9 mm) wide by 15 inches (381.0 mm) deep, 45U by 19 inch EIA in black.
2.4 CABLE MANAGEMENT
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Commscope2. Panduit3. Chatsworth
B. Vertical Cable Management for Equipment Frames:
1. Shall consist of a metal backbone, with cable fingers that align with EIA rack spacing.2. Baked-polyester powder coat finish.3. Fingers will be molded plastic, and shall provide integral bend radius control.4. Vertical cable management panels shall have front and rear channels, with covers.5. Width: 10 inches (254 mm)6. Depth: 22 inches (558 mm).7. Height: 84 inches (2.1 m)
C. Horizontal Cable Management for Equipment Frames:
1. Horizontal cable management panels shall have front channels with covers, and shall be a minimum height of two rack units each.
2. Width: 19 inches (482 mm).3. Depth: 4. RMU: 2RU5. Finishes and colors: Powder coat paint in black.
2.5 RACK MOUNT HORIZONTAL PDU 1RU
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. APC2. Chatsworth3. Panduit4. Raritan
TELECOMMUNICATIONS PATHWAY AND SPACES 271100
B. General PDU Requirements:1. Single phase input connector NEMA L6-30 plug with 10’ cord minimum.2. Output connector 10 – IEC-320-C13 outlets3. Nominal input voltage 200-240 VAC4. Input frequency 50/60 Hz5. Maximum total current draw 30 A (24 A UL derated)6. 17.5” x 1.7”x 3.03” (1RU)7. Color: Black8. Nominal input voltage 200-240 VAC9. Input frequency 50/60 Hz10. Maximum total current draw 30 A (24 A UL derated)11. 70.5” x 2.2” x 1.82”12. Color: Black
2.6 GROUNDING
A. Comply with requirements in Division 26 Section "Grounding and Bonding for Electrical Systems." for grounding conductors and connectors.
B. Telecommunications Main Ground Bus Bar:1. Connectors: Mechanical type, cast silicon bronze, solderless exothermic-type wire
terminals, and long-barrel, two-bolt connection to ground bus bar.2. Ground Bus Bar: Copper, minimum 1/4 inch thick by 4 inches wide with 9/32-inch
holes spaced 1-1/8 inches apart.3. Stand-Off Insulators: Comply with UL 891 for use in switchboards, 600 V. Lexan or
PVC, impulse tested at 5000 V.
C. Comply with ANSI-J-STD-607-A.
2.7 LABELING
A. Comply with TIA/EIA-606-A and UL 969 for a system of labeling materials, including label stocks, laminating adhesives, and inks used by label printers.
B. Contractor shall coordinate final labeling scheme with owner for final approval.
PART 3 - EXECUTION
3.1 ENTRANCE FACILITIES
A. Install underground pathways complying with recommendations in TIA/EIA-569-B, "Entrance Facilities" Article.
3.2 INSTALLATION
A. Install underground entrance pathway complying with Division 26 Section "Raceway and Boxes for Electrical Systems." Comply with NECA 1.
B. Comply with BICSI TDMM for layout and installation of communications equipment rooms.
C. Cable Trays: Provide overhead cable runway (basket tray) as noted. Comply with NEMA VE 2 and TIA/EIA-569-B.
TELECOMMUNICATIONS PATHWAY AND SPACES 271100
1. Cable tray should be installed per manufacturer’s specifications.2. Distance between supports shall not be more than 8 feet.3. Cable tray must be supported by a trapeze support. Cable tray cannot be center hung.4. Provide seismic support as required by the manufacturer.5. Cable tray cannot exceed a maximum of 40% fill ratio, and cable must not exceed 75% of
the total depth of the cable tray. If cable utilizes more than 75% of the total depth the cable tray must be upsized appropriately.
D. Bundle, wrap, and train conductors and cables to terminal points without exceeding manufacturer's limitations on bending radii. Install management bars and distribution spools.
3.3 FIRESTOPPING
A. Comply with requirements in Division 07 Section "Penetration Firestopping." Comply with TIA/EIA-569-B, "Firestopping."
B. Comply with BICSI TDMM, "Firestopping Systems" Article.
3.4 GROUNDING
A. Install grounding according to BICSI TDMM, "Grounding, Bonding, and Electrical Protection" Chapter.
B. Comply with ANSI-J-STD-607-A.
C. Locate grounding bus bar to minimize the length of bonding conductors. Fasten to wall allowing at least 2-inch (50-mm) clearance behind the grounding bus bar. Connect grounding bus bar with a minimum No. 4 AWG grounding conductor from grounding bus bar to suitable electrical building ground.
D. Bond metallic equipment to the grounding bus bar, using not smaller than No. 6 AWG equipment grounding conductor.
1. Bond the shield of shielded cable to the grounding bus bar in communications rooms and spaces.
2. Bond all racks, ladder rack, and cable tray to the grounding bus bar.
3.5 IDENTIFICATION
A. Identify system components, wiring, and cabling complying with TIA/EIA-606-A. Comply with requirements in Division 26 Section "Identification for Electrical Systems."
B. Comply with requirements in Division 09 Section "Interior Painting" for painting backboards. For fire-resistant plywood, do not paint over manufacturer's label.
C. See Section 271300 "Communications Horizontal Cabling" for additional identification requirements. See Evaluations for discussion of TIA/EIA standard as it applies to this Section.
D. Paint and label colors for equipment identification shall comply with TIA/EIA-606-A for Class 4 level of administration, including optional identification requirements of this standard.
TELECOMMUNICATIONS PATHWAY AND SPACES 271100
E. Labels shall be preprinted or computer-printed type.
COMMUNICATIONS HORIZONTAL CABLING 271500
SECTION 271500 - COMMUNICATIONS HORIZONTAL CABLING
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:1. Pathways.2. UTP cabling.3. Cable connecting hardware, patch panels, and cross-connects.4. Telecommunications outlet/connectors.5. Cabling system identification products.6. Cable management system.
B. Related Sections:1. Section 271100 "Telecommunications Pathways and Spaces" for voice and data cabling
associated with system panels and devices.
1.3 DEFINITIONS
A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.
B. BICSI: Building Industry Consulting Service International.
C. EMI: Electromagnetic interference.
D. LAN: Local area network.
E. Outlet/Connectors: A connecting device in the work area on which horizontal cable or outlet cable terminates.
F. RCDD: Registered Communications Distribution Designer.
G. UTP: Unshielded twisted pair.
1.4 HORIZONTAL CABLING DESCRIPTION
A. Horizontal cable and its connecting hardware provide the means of transporting signals between the telecommunications outlet/connector and the horizontal cross-connect located in the communications termination room (Telecom). This cabling and its connecting hardware are called "permanent link," a term that is used in the testing protocols.1. TIA/EIA-568-C.2 requires that a minimum of two telecommunications outlet/connectors
be installed for each work area, however, some locations designated by the owner shall have a single data outlet/connector.
2. Horizontal cabling shall contain no more that one transition point or consolidation point between the horizontal cross-connect and the telecommunications outlet/connector.
3. Bridged taps and splices shall not be installed in the horizontal cabling.
COMMUNICATIONS HORIZONTAL CABLING 271500
B. A work area is approximately 100 sq. ft., and includes the components that extend from the telecommunications outlet/connectors to the station equipment.
C. The maximum allowable horizontal copper cable length is 295 feet. This maximum allowable length does not include an allowance for the length of 16 feet to the workstation equipment. The maximum allowable length does not include an allowance for the length of 16 feet in the horizontal cross-connect.
1.5 PERFORMANCE REQUIREMENTS
A. General Performance: Horizontal cabling system shall comply with transmission standards in TIA/EIA-568-C.1, when tested according to test procedures of this standard.
1.6 SUBMITTALS
A. Product Data: For each type of product indicated.1. For all cable, include the following installation data for each type used:
a. Nominal OD.b. Minimum bending radius.c. Maximum pulling tension.
B. Shop Drawings:1. System Labeling Schedules: Electronic copy of labeling schedules, in software and
format selected by Owner.2. System Labeling Schedules: Electronic copy of labeling schedules that are part of the
cabling and asset identification system of the software.3. Cabling administration drawings and printouts.4. Wiring diagrams to show typical wiring schematics, including the following:
a. Cross-connects.b. Patch panels.c. Patch cords.
5. Cross-connects and patch panels. Detail mounting assemblies, and show elevations and physical relationship between the installed components.
6. Cable tray layout, showing cable tray route to scale, with relationship between the tray and adjacent structural, electrical, and mechanical elements. Include the following:a. Vertical and horizontal offsets and transitions.b. Clearances for access above and to side of cable trays.c. Vertical elevation of cable trays above the subfloor.
C. Samples: For workstation outlets, jacks, jack assemblies, in specified finish, one for each size and outlet configuration.
D. Qualification Data: For all qualified layout technicians, installation supervisors, and field inspector.
E. Source quality-control reports.
F. Field quality-control reports.
G. Maintenance Data: For splices and connectors to include in maintenance manuals.
H. Software and Firmware Operational Documentation:
COMMUNICATIONS HORIZONTAL CABLING 271500
1. Software operating and upgrade manuals.2. Program Software Backup: On magnetic media or compact disk, complete with data
files.3. Device address list.4. Printout of software application and graphic screens.
1.7 QUALITY ASSURANCE
A. Contractor shall provide upon completion a system warranty from the manufacturer to guarantee installation of end-to-end high performance cabling systems that meet all application requirements associated with the Category of cabling installed. The system warranty shall include all copper and fiber cable and connectivity components. The system warranty shall be for a period of at least 20 years.
B. Installer Qualifications: Cabling Installer must have personnel certified by BICSI on staff.1. Layout Responsibility: Preparation of Shop Drawings, Cabling Administration
Drawings, and field testing program development by an RCDD. RCDD must be employed by the contracting firm.
2. Installation Supervision: Installation shall be under the direct supervision of a Registered Technician (BICSI), who shall be present at all times when Work of this Section is performed at Project site.
3. Testing Supervisor: Currently certified by BICSI as an RCDD to supervise on-site testing.
4. Contractor must be certified prior to time of bid with the manufacturer, and must be able to provide a complete system warranty for products installed by the listed manufacturers.
C. Testing Agency Qualifications:1. Testing Agency's Field Supervisor: Currently certified by BICSI as an RCDD to
supervise on-site testing.
D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
E. Telecommunications Pathways and Spaces: Comply with TIA/EIA-569-B.
F. Grounding: Comply with ANSI-J-STD-607-A.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Test cables upon receipt at Project site.1. Test each pair of UTP cable for open and short circuits.
1.9 PROJECT CONDITIONS
A. Environmental Limitations: Do not deliver or install cables and connecting materials until wet work in spaces is complete and dry, and temporary HVAC system is operating and maintaining ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period.
COMMUNICATIONS HORIZONTAL CABLING 271500
1.10 COORDINATION
A. Coordinate layout and installation of telecommunications pathways and cabling with Owner's telecommunications and LAN equipment and service suppliers.
B. Coordinate telecommunications outlet/connector locations with location of power receptacles at each work area. This coordination will generally involve the placement of the raised floor, floor boxes and the outlet arrangements therein.
PART 2 - PRODUCTS
2.1 PATHWAYS
A. General Requirements: Comply with TIA/EIA-569-B.
B. Cable Support: NRTL labeled for support of Category 6 cabling, designed to prevent degradation of cable performance and pinch points that could damage cable.1. Underfloor basket cable tray with floor support brackets for fastening to the subfloor. 2. Lacing bars, spools, J-hooks, and D-rings.3. Straps and other devices.
C. Basket Cable Trays:1. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:a. WBTb. Cablofil Inc.c. Cooper B-Line, Inc.d. GS Metals Corp.
2. Cable Tray Materials: Metal, suitable for indoors, and protected against corrosion by electroplated zinc galvanizing, complying with ASTM B 633, Type 1, not less than 0.000472 inch thick. a. Basket Cable Trays: Width as noted – 2 - 24 inches - and 4 inch deep. Wire mesh
spacing shall not exceed 2 by 4 inches.
D. Conduit and Boxes: Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical Systems." Minimum size of conduit shall be 1 inch.1. Outlet boxes shall two gang, 4 11/16” square x 2.5” deep, with a 5/8” single gang mud
ring.
2.2 BACKBOARDS
A. Backboards: Plywood, fire-retardant treated, 3/4 by 48 by 96 inches. Comply with requirements in Division 06 Section "Rough Carpentry" for plywood backing panels.
2.3 UTP CABLE
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Panduit2. General Cable3. Commscope4. Berk Tek
COMMUNICATIONS HORIZONTAL CABLING 271500
B. Description: 100-ohm, 4-pair UTP.1. Comply with ICEA S-90-661 for mechanical properties.2. Comply with TIA/EIA-568-C.1 for performance specifications.3. Comply with TIA/EIA-568-C.2, Category 6.4. Comply with TIA/EIA-568-C.2, Category 6A.5. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying
with UL 444 and NFPA 70 for the following types:a. Communications, Plenum Rated: Type CMP, complying with NFPA 262.
C. Colors:1. Blue – Data2. Blue - Wireless
2.4 UTP CABLE HARDWARE
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:1. Panduit2. Commscope3. Leviton
B. General Requirements for Cable Connecting Hardware: Comply with TIA/EIA-568-C.2, IDC type, with modules designed for punch-down caps or tools. Cables shall be terminated with connecting hardware of same category or higher.
C. Patch Panel: Modular panels housing multiple-numbered jack units with IDC-type connectors at each jack for permanent termination of pair groups of installed cables.1. Number of Jacks per Field: One for each four-pair UTP cable indicated.
D. Jacks and Jack Assemblies: Modular, color-coded, eight-position modular receptacle units with integral IDC-type terminals.
2.5 TELECOMMUNICATIONS OUTLET/CONNECTORS
A. Jacks: 100-ohm, balanced, twisted-pair connector; four-pair, eight-position modular. Comply with TIA/EIA-568-C.1.
B. Jack Color:1. Blue – Data2. Blue – Wireless AP
C. Workstation Outlets: Provide with the number of ports as noted – 1, 2, or 4, ports - connector assemblies mounted in single faceplate.1. Floor box Faceplate: Provide adapter plates to mount in the provided floor boxes for the
appropriate cable solution being provided, ie. Panduit adapter plate for Panduit outlet connectors.
2. Legend: Machine printed, in the field, using adhesive-tape label or snap-in, clear-label covers and machine-printed paper inserts.
2.6 GROUNDING
A. Comply with requirements in Division 26 Section "Grounding and Bonding for Electrical Systems" for grounding conductors and connectors.
COMMUNICATIONS HORIZONTAL CABLING 271500
B. Comply with ANSI-J-STD-607-A.
2.7 IDENTIFICATION PRODUCTS
A. Comply with TIA/EIA-606-A and UL 969 for labeling materials, including label stocks, laminating adhesives, and inks used by label printers.
B. Comply with requirements in Division 26 Section "Identification for Electrical Systems."
2.8 SOURCE QUALITY CONTROL
A. Testing Agency: Engage a qualified testing agency to evaluate cables.
B. Factory test UTP cables on reels according to TIA/EIA-568-C.1.
C. Factory test UTP cables according to TIA/EIA-568-C.2.
D. Cable will be considered defective if it does not pass tests and inspections.
E. Prepare test and inspection reports.
PART 3 - EXECUTION
3.1 ENTRANCE FACILITIES
A. Coordinate backbone cabling with the protectors and demarcation point provided by communications service provider.
3.2 WIRING METHODS
A. Wiring Method: Install cables in raceways and cable trays except within cabinets. Conceal raceway and cables except in unfinished spaces.1. Install plenum cable in all spaces.2. Comply with requirements for raceways and boxes specified in Division 26 Section
"Raceway and Boxes for Electrical Systems."
B. Wiring within Enclosures: Bundle, lace, and train cables to terminal points with no excess and without exceeding manufacturer's limitations on bending radii. Provide and use lacing bars and distribution spools.
3.3 INSTALLATION OF PATHWAYS
A. Cable Trays: Comply with NEMA VE 2 and TIA/EIA-569-B.
B. Comply with requirements for demarcation point, pathways, cabinets, and racks specified in Section 271100 "Telecommunications Pathways and Spaces." Drawings indicate general arrangement of pathways and fittings.
C. Comply with TIA/EIA-569-B for pull-box sizing and length of conduit and number of bends between pull points.
D. Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical Systems" for installation of conduits and wire ways.
COMMUNICATIONS HORIZONTAL CABLING 271500
E. Install manufactured conduit sweeps and long-radius elbows whenever possible.
F. Pathway Installation in Termination Rooms (Telecom):1. Position conduit ends adjacent to a corner on backboard where a single piece of plywood
is installed, or in the corner of room where multiple sheets of plywood are installed around perimeter walls of room.
2. Install basket cable trays to route cables from underfloor up into the floor mounted racks. 3. Secure conduits to backboard when entering room from overhead.4. Extend conduits 3 inches above finished floor.5. Install metal conduits with grounding bushings and connect with grounding conductor to
grounding system.
G. Backboards: Install backboards with 96-inch dimension vertical. Butt adjacent sheets tightly, and form smooth gap-free corners and joints.
3.4 INSTALLATION OF CABLES
A. Comply with NECA 1.
B. General Requirements for Cabling:1. Comply with TIA/EIA-568-C.1.2. Comply with BICSI ITSIM, Ch. 6, "Cable Termination Practices.”3. Terminate all conductors; no cable shall contain unterminated elements. Make
terminations only at indicated outlets, terminals, cross-connects, and patch panels.4. Cables may not be spliced. Secure and support cables at intervals not exceeding 30
inches, not more than 6 inches from cabinets, boxes, fittings, outlets, racks, frames, and terminals.
5. Install lacing bars to restrain cables, to prevent straining connections, and to prevent bending cables to smaller radii than minimums recommended by manufacturer.
6. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI ITSIM, "Cabling Termination Practices" Chapter. Install lacing bars and distribution spools.
7. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation and replace it with new cable.
8. Cold-Weather Installation: Bring cable to room temperature before de-reeling. Heat lamps shall not be used for heating.
9. In the termination room (Telecom), leave a minimum 3 foot and no more than a 10 foot service loop on each cable.
10. For every horizontal cable pull specified, neatly coil a 10’ 0” slack loop at the station (office) end of the cable. Leave slack loop at point of conduit entrance.
11. For every horizontal cable pull specified for wireless access points, neatly coil a 10’ 0” slack loop at the point of termination, and support cable properly so it does not rest on any conduit, ducts, or other items in the ceiling space.
12. Pulling Cable: Comply with BICSI ITSIM, Ch. 4, "Pulling Cable." Monitor cable pull tensions.
13. All cable should be protected from direct paint, or incidental overspray.
C. UTP Cable Installation:1. Comply with TIA/EIA-568-C.2.2. Do not untwist UTP cables more than 1/2 inch from the point of termination to maintain
cable geometry.
COMMUNICATIONS HORIZONTAL CABLING 271500
D. Open-Cable Installation:1. Install cabling with horizontal and vertical cable guides in telecommunications spaces
with terminating hardware and interconnection equipment.2. Suspend UTP cable not in a wire way or pathway a minimum of 8 inches above ceilings
by cable supports not more than 60 inches apart.3. Cable shall not be run through structural members or in contact with pipes, ducts, or other
potentially damaging items.
E. Installation of Cable Routed Exposed under Raised Floors:1. Install plenum-rated cable only.2. Install cabling after the flooring system has been installed in raised floor areas.
F. Group connecting hardware for cables into separate logical fields.
G. Separation from EMI Sources:1. Comply with BICSI TDMM and TIA/EIA-569-B for separating unshielded copper voice
and data communication cable from potential EMI sources, including electrical power lines and equipment.
2. Separation between open communications cables or cables in nonmetallic raceways and unshielded power conductors and electrical equipment shall be as follows:a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 5 inches.b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 12 inches.c. Electrical Equipment Rating More Than 5 kVA: A minimum of 24 inches.
3. Separation between communications cables in grounded metallic raceways and unshielded power lines or electrical equipment shall be as follows:a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 2-1/2 inches.b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 6 inches.c. Electrical Equipment Rating More Than 5 kVA: A minimum of 12 inches.
4. Separation between communications cables in grounded metallic raceways and power lines and electrical equipment located in grounded metallic conduits or enclosures shall be as follows:a. Electrical Equipment Rating Less Than 2 kVA: No requirement.b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 3 inches.c. Electrical Equipment Rating More Than 5 kVA: A minimum of 6 inches.
5. Separation between Communications Cables and Electrical Motors and Transformers, 5 kVA or HP and Larger: A minimum of 48 inches.
6. Separation between Communications Cables and Fluorescent Fixtures: A minimum of 5 inches.
3.5 FIRESTOPPING
A. Comply with requirements in Division 07 Section "Penetration Firestopping."
B. Comply with TIA/EIA-569-B, "Firestopping."
C. Comply with BICSI TDMM, "Firestopping Systems" Article.
3.6 GROUNDING
A. Install grounding according to BICSI TDMM, "Grounding, Bonding, and Electrical Protection" Chapter.
COMMUNICATIONS HORIZONTAL CABLING 271500
B. Comply with ANSI-J-STD-607-A.
C. Locate grounding bus bar to minimize the length of bonding conductors. Fasten to wall allowing at least 2-inch clearance behind the grounding bus bar. Connect grounding bus bar with a minimum No. 4 AWG grounding electrode conductor from grounding bus bar to suitable electrical building ground.
D. Bond metallic equipment to the grounding bus bar, using not smaller than No. 6 AWG equipment grounding conductor.
3.7 IDENTIFICATION
A. Identify system components, wiring, and cabling complying with TIA/EIA-606-A. Comply with requirements for identification specified in Division 26 Section "Identification for Electrical Systems."1. Administration Class: 4.2. Color-code cross-connect fields. Apply colors to voice and data service backboards,
connections, covers, and labels.
B. Using cable management system software specified in Part 2, develop Cabling Administration Drawings for system identification, testing, and management. Use unique, alphanumeric designation for each cable and label cable, jacks, connectors, and terminals to which it connects with same designation. At completion, cable and asset management software shall reflect as-built conditions.
C. Comply with requirements in Division 09 Section "Interior Painting" for painting backboards. For fire-resistant plywood, do not paint over manufacturer's label.
D. Paint and label colors for equipment identification shall comply with TIA/EIA-606-A for Class 4 level of administration.
E. Cable Schedule: Post in prominent location in each equipment room and wiring closet. List incoming and outgoing cables and their designations, origins, and destinations. Protect with rigid frame and clear plastic cover. Furnish an electronic copy of final comprehensive schedules for Project.
F. Cabling Administration Drawings: Show building floor plans with cabling administration-point labeling. Identify labeling convention and show labels for telecommunications rooms, backbone pathways and cables, entrance pathways and cables, terminal hardware and positions, horizontal cables, work areas and workstation terminal positions, grounding buses and pathways, and equipment grounding conductors. Follow convention of TIA/EIA-606-A. Furnish electronic record of all drawings, in software and format selected by Owner.
G. Cable and Wire Identification:1. Label each cable within 4 inches of each termination and tap, where it is accessible in a
cabinet or junction or outlet box, and elsewhere as indicated.2. Each wire connected to building-mounted devices is not required to be numbered at
device if color of wire is consistent with associated wire connected and numbered within panel or cabinet.
3. Label each terminal strip and screw terminal in each cabinet, rack, or panel.a. Individually number wiring conductors connected to terminal strips, and identify
each cable or wiring group being extended from a panel or cabinet to a building-
COMMUNICATIONS HORIZONTAL CABLING 271500
mounted device shall be identified with name and number of particular device as shown.
b. Label each unit and field within distribution racks and frames.4. Identification within Connector Fields in Equipment Rooms and Wiring Closets: Label
each connector and each discrete unit of cable-terminating and connecting hardware. Where similar jacks and plugs are used for both voice and data communication cabling, use a different color for jacks and plugs of each service.
H. Labels shall be preprinted or computer-printed type with printing area and font color that contrasts with cable jacket color but still complies with requirements in TIA/EIA-606-A.1. Cables use flexible vinyl or polyester that flex as cables are bent.
3.8 FIELD QUALITY CONTROL
A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
B. Perform tests and inspections.
C. Tests and Inspections:1. Visually inspect UTP and optical fiber cable jacket materials for NRTL certification
markings. Inspect cabling terminations in communications equipment rooms for compliance with color-coding for pin assignments, and inspect cabling connections for compliance with TIA/EIA-568-C.1.
2. Visually confirm Category 6A marking of outlets, cover plates, outlet/connectors, and patch panels.
3. Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components.
4. Test UTP backbone copper cabling for DC loop resistance, shorts, opens, intermittent faults, and polarity between conductors. Test operation of shorting bars in connection blocks. Test cables after termination but not cross-connection.a. Test instruments shall meet or exceed applicable requirements in TIA/EIA-568-
C.2. Perform tests with a tester that complies with performance requirements in "Test Instruments (Normative)" Annex, complying with measurement accuracy specified in "Measurement Accuracy (Informative)" Annex. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration.
5. UTP Performance Tests:a. Test for each outlet. Perform the following tests according to TIA/EIA-568-C.1
and TIA/EIA-568-C.2:1) Wire map.2) Length (physical vs. electrical, and length requirements).3) Insertion loss.4) Near-end crosstalk (NEXT) loss.5) Power sum near-end crosstalk (PSNEXT) loss.6) Equal-level far-end crosstalk (ELFEXT).7) Power sum equal-level far-end crosstalk (PSELFEXT).8) Return loss.9) Propagation delay.10) Delay skew.
6. Final Verification Tests: Perform verification tests for UTP systems after the complete communications cabling and workstation outlet/connectors are installed.
COMMUNICATIONS HORIZONTAL CABLING 271500
a. Voice Tests: These tests assume that dial tone service has been installed. Connect to the network interface device at the demarcation point. Go off-hook and listen and receive a dial tone. If a test number is available, make and receive a local, long distance, and digital subscription line telephone call.
b. Data Tests: These tests assume the Information Technology Staff has a network installed and is available to assist with testing. Connect to the network interface device at the demarcation point. Log onto the network to ensure proper connection to the network.
D. Document data for each measurement. Data for submittals shall be printed in a summary report that is formatted similar to Table 10.1 in BICSI TDMM, or transferred from the instrument to the computer, saved as text files, and printed and submitted.
E. End-to-end cabling will be considered defective if it does not pass tests and inspections.
F. Prepare test and inspection reports.
3.9 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel in cable-plant management operations, including changing signal pathways for different workstations, rerouting signals in failed cables, and keeping records of cabling assignments and revisions when extending wiring to establish new workstation outlets. Include training in cabling administration software.
Typical Self-Supporting25G, 45G and 55G Tower
Typical Self-Supporting45GSR and 65G Tower
REV. G
includes
REV. F &
Per Rev G requirements, any structure greater than 10’ requires a climber safety device. Please see page 209 for ordering information.
GENERAL USE
The self-supporting G-Series towers o�er an easy,low-cost solution to get light weight antennas inthe air quickly. By using the G-Series tower as aself-supporting structure, you minimize landarea usage. They are functional in a wide varietyof wind speeds. See ROHN’s standard designs to help identify the right structure for your project.These are the same sturdy, robust tower sectionsthat ROHN has fabricated for years. Each largermodel allows for more loading capacity.
FEATURES
• Completely hot-dip galvanized after fabrication• Cross bracing is formed by a continuous solid rod bracing fashioned into a zig-zag pattern for strength• Pre-engineered loading charts meet varying individual specs and site conditions• Typical uses include: small dishes, broadband, security and two-way communication• All towers have ‘�xed’ bases
KITS
The kit part numbers for ROHN Self-SupportingG-Series towers include:
• Short base for embedment in concrete• Rev F ground kit• All tower sections and connection hardware• Tapered top (25G and 45G towers)• Top plate (55G towers)• Cap plate kit (65G towers)
G-SERIESSELF-SUPPORTING
www.tessco.com/go/towers 800.472.7373
W(Square)
Tower Axis & Center of Pad
CL
CL
PLAN VIEW
Tower Section orShort Base Section
#7 Bars 12”on CenterEach Way
6”
6”
4’
2” min. projection requiredfor proper drainage
Compacted Sand & GravelDrainage Bed - not requiredfor 45GSR
Grade
25G
45G
55G
45GSR65G
4’ - 0”
5’ - 3”
6’ - 0”
7’ - 9”
2.4
4.1
5.3
8.9
TowerMat
Width(W)
ConcreteVolume
(Cu. Yds.)
6”
4’
Grade6”
#7 Bars 12”on CenterEach Way,
Top & Bottom
ELEVATION VIEW25G (shown), 45G & 55G
SELF-SUPPORTING TOWER FOUNDATION
ELEVATION VIEW45GSR
SELF-SUPPORTING TOWER FOUNDATION
ELEVATION VIEW65G
SELF-SUPPORTING TOWER FOUNDATION
2” min. projection above the �nished
concrete
6” min. projection above the �nished
concrete
4’
0” to 3”2” Min.
www.tessco.com/go/towers 800.472.7373
ROHN G-Series Self-Supporting Tower Normal Soil Foundations
REV:
DWN:
ENG'R:
DRAWING NO:
DATE:CHK'D:
DESCRIPTIONREV.
FILE NO.
REVISIONS
DWN
PRODUCTS, LLC
PEORIA, IL 61601-5999
TOLL FREE 800-727-ROHN
PO BOX 5999
THIS DRAWING IS THE PROPERTY OF ROHN. IT IS NOT TO BE
REPRODUCED, COPIED OR TRACED IN WHOLE OR IN PART WITHOUT
OUR WRITTEN CONSENT.
CHK APP
SHEET #:
PRJ. ENG'R: PRJ. MANG'R:
®
JHY JDM
HA
DWG-0617
SELF-SUPPORTING G SERIES TOWERSREV. G EFFECTIVE PROJECTED AREAS
10/12/2012
3
(90-110 MPH 3-SEC GUST, NO ICE)
SSM
1 OF 1
90 MPH 3-SECOND GUST WIND SPEED
HEIGHT
(FT)
25G 45G 45GSR 55G 65G
EPA (SQ. FT)PART
NO.
EPA (SQ. FT)PART
NO.
EPA (SQ. FT)PART
NO.
EPA (SQ. FT)PART
NO.
EPA (SQ. FT)PART
NO.EXP. B EXP. C EXP. B EXP. C EXP. B EXP. C EXP. B EXP. C EXP. B EXP. C
10 26.8 21.3 25SS010 60.0 47.5 45SS010 95 84 45SR010 80 79 55SS010 95 95 65SS010
20 18.5 13.4 25SS020 31.3 22.7 45SS020 95 71 45SR020 56 42 55SS020 95 95 65SS020
30 7.9 4.1 25SS030 16.1 8.4 45SS030 87 58 45SR030 34 21 55SS030 95 71 65SS030
35 4.4 1.2 25SS035 9.8 3.8 45SS035 76 52 45SR035 25 14 55SS035 80 54 65SS035
40 1.3 - 25SS040 4.9 - 45SS040 60 40 45SR040 17 8 55SS040 62 41 65SS040
45 0.7 - 45SS045 48 31 45SR045 11 3 55SS045 48 30 65SS045
50 38 23 45SR050 5 - 55SS050 37 21 65SS050
55 29 16 45SR055 28 14 65SS055
60 22 11 45SR060 20 7 65SS060
100 MPH 3-SECOND GUST WIND SPEED
HEIGHT
(FT)
25G 45G 45GSR 55G 65G
EPA (SQ. FT)PART
NO.
EPA (SQ. FT)PART
NO.
EPA (SQ. FT)PART
NO.
EPA (SQ. FT)PART
NO.
EPA (SQ. FT)PART
NO.EXP. B EXP. C EXP. B EXP. C EXP. B EXP. C EXP. B EXP. C EXP. B EXP. C
10 20.7 16.4 25SS010 47.4 39.5 45SS010 82 66 45SR010 78 63 55SS010 95 95 65SS010
20 14.0 9.9 25SS020 23.2 16.9 45SS020 74 55 45SR020 43 32 55SS020 95 95 65SS020
30 5.3 2.2 25SS030 9.7 4.8 45SS030 66 43 45SR030 24 14 55SS030 81 55 65SS030
35 2.1 - 25SS035 5.1 0.7 45SS035 59 38 45SR035 17 8 55SS035 61 40 65SS035
40 1.2 - 45SS040 46 30 45SR040 10 3 55SS040 47 29 65SS040
45 35 22 45SR045 5 - 55SS045 35 20 65SS045
50 27 15 45SR050 26 13 65SS050
55 20 9 45SR055 17 6 65SS055
60 13 4 45SR060 11 1 65SS060
110 MPH 3-SECOND GUST WIND SPEED
HEIGHT
(FT)
25G 45G 45GSR 55G 65G
EPA (SQ. FT)PART
NO.
EPA (SQ. FT)PART
NO.
EPA (SQ. FT)PART
NO.
EPA (SQ. FT)PART
NO.
EPA (SQ. FT)PART
NO.EXP. B EXP. C EXP. B EXP. C EXP. B EXP. C EXP. B EXP. C EXP. B EXP. C
10 16.5 12.7 25SS010 39.4 31.9 45SS010 67 53 45SR010 63 51 55SS010 95 95 65SS010
20 10.6 7.2 25SS020 18.3 12.3 45SS020 59 43 45SR020 34 25 55SS020 95 81 65SS020
30 3.1 0.4 25SS030 6.5 1.9 45SS030 51 32 45SR030 17 9 55SS030 65 43 65SS030
35 1.7 - 45SS035 45 27 45SR035 11 4 55SS035 48 30 65SS035
40 35 22 45SR040 5 - 55SS040 35 21 65SS040
45 26 15 45SR045 25 13 65SS045
50 19 9 45SR050 17 7 65SS050
55 13 4 45SR055 10 - 65SS055
60 7 - 45SR060 4 - 65SS060
GENERAL NOTES:
1. TOWER DESIGNS ARE IN ACCORDANCE WITH APPROVED NATIONAL STANDARD
ANSI/TIA-222-G, STRUCTURE CLASS I, EXPOSURES B AND C, TOPOGRAPHIC CATEGORY 1.
2. ALL TOWERS MUST HAVE "FIXED" BASES. PINNED BASES MAY NOT BE USED.3. TOWER DESIGNS ASSUME TRANSMISSION LINES SYMMETRICALLY PLACED AS FOLLOWS:
25G TOWER - ONE 5/8" LINE ON EACH FACE (TOTAL = 3
45G TOWER - ONE 7/8" AND ONE 1/2" LINE ON EACH FACE (TOTAL = 3 @ 7/8"
& 3 @ 1/2")
45GSR, 55G, & 65G TOWERS - TWO 7/8" LINES ON EACH FACE (TOTAL = 6)
4. ANTENNAS AND MOUNTS ASSUMED SYMMETRICALLY PLACED AT TOWER APEX.5. THE SUITABILITY OF A ROHN STANDARD DESIGN AND STANDARD FOUNDATION FOR A
SPECIFIC APPLICATION MUST BE VERIFIED BY THE PURCHASER BASED ON SITE-SPECIFIC
DATA IN ACCORDANCE WITH ANSI/TIA-222-G.
6. THE EFFECTIVE PROJECTED AREA AND LINES TO BE INSTALLED MUST NOT EXCEED THE
DESIGN VALUES FOR THE STRUCTURE.7. DO NOT INSTALL OR DISMANTLE TOWERS WITHIN FALLING DISTANCE OF ELECTRICAL
AND/OR TELEPHONE LINES.
8. TOWER ERECTION AND DISMANTLING MUST BE DONE BY QUALIFIED AND EXPERIENCEDPERSONNEL.
9. INSTALLATION MUST BE GROUNDED IN ACCORDANCE WITH LOCAL AND NATIONAL
CODES. ANSI/TIA-222-G REQUIRES THAT THE RESISTANCE TO GROUND MUST NOT
EXCEED 10 Ohms. ADDITIONAL GROUNDING MAY BE REQUIRED IN ADDITION TO
GROUNDING KITS PROVIDED BY ROHN.
10. INSTALL WARNING PLATE (P/N ACWS) IN A HIGHLY VISIBLE LOCATION.
11. FOR FOUNDATION DETAILS AND GENERAL FOUNDATION NOTES, BASED ON
ANSI/TIA-222-G PRESUMPTIVE CLAY SOIL, SEE DRAWINGS DWG-0128 AND B090548RESPECTIVELY.
12. FOR 25G, 45G, 55G, AND 65G TOWER PROFILE DRAWINGS, REFER TO DRAWING NUMBER25GSS, 45GSS, 55GSS, AND 65GSS, RESPECTIVELY.
13. STRUCTURES SUPPORTED ON BUILDINGS OR OTHER STRUCTURES REQUIRE SPECIALCONSIDERATION. DESIGNS ASSUME STRUCTURES ARE INSTALLED ON LEVEL FLOOR.
14. DESIGN ASSUMES MAINTENANCE AND INSPECTION WILL BE PREFORMED OVER THE LIFE
OF THE STRUCTURE IN ACCORDANCE WITH ANSI/TIA-222-G. ALL TOWERS SHOULD BETHOROUGHLY INSPECTED BY QUALIFIED PERSONNEL AND RE-MARKED AS REQUIRED
WITH APPROPRIATE DANGER AND ANTI-CLIMB LABELS AT LEAST TWICE A YEAR TOENSURE SAFETY AND PROPER PERFORMANCE.
15. STANDARD DESIGNS ARE INTENDED TO BE CLIMBED BY SKILLED AND COMPETENT
CLIMBERS ONLY. A SAFETY CLIMB SYSTEM, BY OTHERS, IS REQUIRED FOR ALLSTRUCTURES TO BE ORDERED SEPARATELY.
16. THE TOLERANCE ON INSTALLED HEIGHT IS EQUAL TO PLUS 1% AND MINUS 1/2%.17. INSTALLATION MUST BE IN CONFORMANCE WITH LOCAL, STATE AND FEDERAL
REQUIREMENTS FOR OBSTRUCTION MARKING AND LIGHTING.
DATE:
3
ADDED EPA UNIT
07/20/2015
HAJDMJHY
REV:
DWN:
ENG'R:
DRAWING NO:
DATE:CHK'D:
DESCRIPTIONREV.
FILE NO.
REVISIONS
DWN
PRODUCTS
PEORIA, IL 61601-5999
TOLL FREE 800-727-ROHN
PO BOX 5999
THIS DRAWING IS THE PROPERTY OF ROHN. IT IS NOT TO BE
REPRODUCED, COPIED OR TRACED IN WHOLE OR IN PART WITHOUT
OUR WRITTEN CONSENT.
CHK APP
SHEET #:
PRJ. ENG'R: PRJ. MANG'R:
JHY JDM
HA
45GSS
Jan/9/2013
1
JPK
1 OF 1
NOTES:
1. REFER TO DRAWING NO. DWG-0617 FOR TOWER EFFECTIVE PROJECTED AREAS AND GENERAL NOTES.
2. REFER TO DRAWING NO. DWG-0128 FOR FOUNDATION DETAILS.
3. REFER TO DRAWING NO. B090548 FOR STANDARD FOUNDATION NOTES.
4. REFER TO DRAWING NO. A810214 FOR FOUNDATION AND ANCHOR TOLERANCE.
5. ROHN PRODUCTS, LLC. WILL PROVIDE A GROUNDING KIT FOR EACH TOWER ASSEMBLY.
DATE:
1
CORRECTED DESCRIPTION
8/16/2013
HAJDMJHY
W
(SQUARE)
TOWER AXIS AND
CENTER OF PAD
CL
CL
PLAN VIEW
6" MIN
4'-0"
2" MIN
6 1/2" MIN
ELEVATION VIEW
45GSR
GROUND LEVEL
#7 BARS 12" ON CENTER
EACH WAY, TOP & BOTTOM
TOWER SECTION OR
SHORT BASE SECTION
(SOLID ROD)
ELEVATION VIEW
65G
4" MIN
GROUND LEVEL
#7 BARS 12" ON CENTER
EACH WAY, TOP & BOTTOM
TOWER SECTION OR
SHORT BASE SECTION
(PIPE)
6"
COMPACTED SAND AND
GRAVEL DRAINAGE BED
6" MIN
4'-0"
2" MIN
ELEVATION VIEW
25G, 45G, & 55G
6" MIN
4'-0"
GROUND LEVEL
6" MIN#7 BARS 12" ON CENTER
EACH WAY, TOP & BOTTOM
TOWER SECTION OR
SHORT BASE SECTION
(PIPE)
2" MIN6"
COMPACTED SAND AND
GRAVEL DRAINAGE BED
REV:
DWN:
ENG'R:
DRAWING NO:
DATE:CHK'D:
DESCRIPTIONREV.
FILE NO.
REVISIONS
DWN
PRODUCTS, LLC
PEORIA, IL 61601-5999
TOLL FREE 800-727-ROHN
PO BOX 5999
THIS DRAWING IS THE PROPERTY OF ROHN. IT IS NOT TO BE
REPRODUCED, COPIED OR TRACED IN WHOLE OR IN PART WITHOUT
OUR WRITTEN CONSENT.
CHK APP
SHEET #:
PRJ. ENG'R: PRJ. MANG'R:
®
FAD HA
HA
DWG-0128
FOUNDATIONMAT FND FOR SS G SERIES TOWERS
5/27/2010
3
1 OF 1
FOUNDATION DETAILS
TOWER
NUMBER
OVER-TURNING
MOMENT
(FT-LBS)
TOTAL SHEAR
(LBS)MAT WIDTH
"W"
CONCRETE
VOLUME
(CU. YDS.)
25G 7000 500 4'-0" 2.4
45G 12300 1000 5'-3" 4.1
55G 22100 1600 6'-0" 5.3
45GSR/65G 53100 3500 7'-9" 8.9
GENERAL NOTES:
1. FOR STANDARD FOUNDATION NOTES, SEE DRAWING NUMBER B090548.
2. FOR 25G, 45G, 55G, 65G, AND 45GSR TOWER ASSEMBLY DRAWINGS AND MAXIMUM TOWER HEIGHTS, REFER
TO DRAWING NUMBER 25GSS, 45GSS, 55GSS, 65GSS, AND 45GSRSS RESPECTIVELY.
DATE:
3
ADDED 45GSR ELEVATION VIEW
3/2/2015
HAKTLJHY
REV:
DWN:
ENG'R:
DRAWING NO:
DATE:CHK'D:
DESCRIPTIONREV.
FILE NO.
REVISIONS
DWN
PRODUCTS
PEORIA, IL 61601-5999
TOLL FREE 800-727-ROHN
PO BOX 5999
THIS DRAWING IS THE PROPERTY OF ROHN. IT IS NOT TO BE
REPRODUCED, COPIED OR TRACED IN WHOLE OR IN PART WITHOUT
OUR WRITTEN CONSENT.
CHK APP
SHEET #:
PRJ. ENG'R: PRJ. MANG'R:
FAD HA
HA
B090548
Nov/20/2009
2
1 OF 1
STANDARD FOUNDATION NOTES
ANSI/TIA-222-G
1. STANDARD FOUNDATION DESIGNS ARE IN ACCORDANCE WITH ANSI/TIA-222-G, "STRUCTURAL
STANDARDS FOR STEEL ANTENNA TOWERS AND ANTENNA SUPPORTING STRUCTURES", SECTION 9
AND ANNEX F FOR THE FOLLOWING PRESUMPTIVE CLAY SOIL PARAMETERS:
2. THE PURCHASER MUST VERIFY THAT ACTUAL SITE SOIL PARAMETERS MEET OR EXCEED
ANSI/TIA-222-G PRESUMPTIVE CLAY SOIL DESIGN PARAMETERS AND THAT THE PENETRATION
AND/OR ZONE OF SEASONAL MOISTURE VARIATION AT THE SITE. FOUNDATION DESIGN
MODIFICATIONS MAY BE REQUIRED IN THE EVENT PRESUMPTIVE CLAY SOIL PARAMETERS ARE NOT
APPLICABLE FOR THE ACTUAL SUBSURFACE CONDITIONS ENCOUNTERED.
3. A SITE-SPECIFIC INVESTIGATION IS REQUIRED FOR CLASS III STRUCTURES IN ACCORDANCE WITH
ANSI/TIA-222-G.
4. FOUNDATION DESIGNS ASSUME FIELD INSPECTIONS WILL BE PERFORMED BY THE PURCHASER'S
REPRESENTATIVE TO VERIFY THAT CONSTRUCTION MATERIALS, INSTALLATION METHODS AND
ASSUMED DESIGN PARAMETERS ARE ACCEPTABLE BASED ON THE CONDITIONS EXISTING AT THE
SITE.
5. WORK SHALL BE IN ACCORDANCE WITH LOCAL CODES, SAFETY REGULATIONS AND UNLESS
OTHERWISE NOTED, THE LATEST REVISION OF ACI 318, "BUILDING CODE REQUIREMENTS FOR
REINFORCED CONCRETE". PROCEDURES FOR THE PROTECTION OF EXCAVATIONS, EXISTING
CONSTRUCTION AND UTILITIES SHALL BE ESTABLISHED PRIOR TO FOUNDATION INSTALLATION.
6. CONCRETE MATERIALS SHALL CONFORM TO THE APPROPRIATE STATE REQUIREMENTS FOR
EXPOSED STRUCTURAL CONCRETE.
7. PROPORTIONS OF CONCRETE MATERIALS SHALL BE SUITABLE FOR THE INSTALLATION METHOD
UTILIZED AND SHALL RESULT IN DURABLE CONCRETE FOR RESISTANCE TO LOCAL ANTICIPATED
AGGRESSIVE ACTIONS. THE DURABILITY REQUIREMENT OF ACI 318 CHAPTER 4 SHALL BE SATISFIED
BASED ON THE CONDITIONS EXPECTED AT THE SITE. AS A MINIMUM, CONCRETE SHALL DEVELOP A
MINIMUM COMPRESSIVE STRENGTH OF 4500 PSI (31.0 MPa) IN 28 DAYS.
8. MAXIMUM SIZE OF AGGREGATE SHALL NOT EXCEED SIZE SUITABLE FOR INSTALLATION METHOD
UTILIZED OR 1/3 CLEAR DISTANCE BEHIND OR BETWEEN REINFORCING. MAXIMUM SIZE MAY BE
INCREASED TO 2/3 CLEAR DISTANCE PROVIDED WORKABILITY AND METHODS OF CONSOLIDATION
SUCH AS VIBRATING WILL PREVENT HONEYCOMBS OR VOIDS.
9. REINFORCEMENT SHALL BE DEFORMED AND CONFORM TO THE REQUIREMENTS OF ASTM A615
GRADE 60 UNLESS OTHERWISE NOTED. SPLICES IN REINFORCEMENT SHALL NOT BE ALLOWED
UNLESS OTHERWISE INDICATED.
10. REINFORCING CAGES SHALL BE BRACED TO RETAIN PROPER DIMENSIONS DURING HANDLING,
THROUGHOUT PLACEMENT OF CONCRETE AND DURING EXTRACTION OF TEMPORARY CASING.
11. WELDING IS PROHIBITED ON REINFORCING STEEL AND EMBEDMENTS.
N
(blows/ft)
[blows/m]
Φ
(deg)
Y
(lb/ft3)
[kN/m3]
C
(psf)
[kPa]
Ultimate Bearing
(psf)
[kPa]
Ultimate
Skin Friction
(psf)
[kPa]
k
(pci)
[kN/m3]ε50
Shallow
Fnds.
Deep
Fnds.
8 [26] 0110
[17]
1000
[48]
5000
[240]
9000
[431]
500
[24]
150
[41,000]0.01
12. MINIMUM CONCRETE COVER FOR REINFORCEMENT SHALL BE 3 INCHES (76 mm) UNLESS
OTHERWISE NOTED. APPROVED SPACERS SHALL BE USED TO INSURE A 3 INCH (76 mm) MINIMUM
COVER ON REINFORCEMENT. CONCRETE COVER FROM TOP OF FOUNDATION TO ENDS OF
VERTICAL REINFORCEMENT SHALL NOT EXCEED 3 INCHES (76 mm) NOR BE LESS THAN 2 INCHES
(51 mm).
13. SPACERS SHALL BE ATTACHED INTERMITTENTLY THROUGHOUT THE ENTIRE LENGTH OF VERTICAL
REINFORCING CAGES TO INSURE CONCENTRIC PLACEMENT OF CAGES IN EXCAVATIONS.
14. FOUNDATION DESIGNS ASSUME STRUCTURAL BACKFILL TO BE COMPACTED IN 8 INCH (200 mm)
MAXIMUM LAYERS TO 95% OF MAXIMUM DRY DENSITY AT OPTIMUM MOISTURE CONTENT IN
ACCORDANCE WITH ASTM D698. ADDITIONALLY, STRUCTURAL BACKFILL MUST HAVE A MINIMUM
COMPACTED UNIT WEIGHT OF 100 POUNDS PER CUBIC FOOT (16 kN/m3).
15. FOUNDATION DESIGNS ASSUME LEVEL GRADE AT THE SITE.
16. FOUNDATION INSTALLATION SHALL BE SUPERVISED BY PERSONNEL KNOWLEDGEABLE AND
EXPERIENCED WITH THE PROPOSED FOUNDATION TYPE. CONSTRUCTION SHALL BE IN
ACCORDANCE WITH GENERALLY ACCEPTED INSTALLATION PRACTICES.
17. FOR FOUNDATION AND ANCHOR TOLERANCES SEE DRAWING A810214.
18. LOOSE MATERIAL SHALL BE REMOVED FROM BOTTOM OF EXCAVATION PRIOR TO CONCRETE
PLACEMENT. SIDES OF EXCAVATION SHALL BE ROUGH AND FREE OF LOOSE CUTTINGS.
19. CONCRETE SHALL BE PLACED IN A MANNER THAT WILL PREVENT SEGREGATION OF CONCRETE
MATERIALS, INFILTRATION OF WATER OR SOIL AND OTHER OCCURRENCES WHICH MAY DECREASE
THE STRENGTH OR DURABILITY OF THE FOUNDATION.
20. FREE FALL CONCRETE MAY BE USED PROVIDED FALL IS VERTICAL DOWN WITHOUT HITTING
SIDES OF EXCAVATION, FORMWORK, REINFORCING BARS, FORM TIES, CAGE BRACING OR OTHER
OBSTRUCTIONS. UNDER NO CIRCUMSTANCES SHALL CONCRETE FALL THROUGH WATER.
21. CONCRETE SHALL BE PLACED AGAINST UNDISTURBED SOIL EXCEPT FOR PIERS OR PIER AND PAD
FOUNDATIONS. FORMS FOR PIERS SHALL BE REMOVED PRIOR TO PLACING STRUCTURAL BACKFILL.
22. CONSTRUCTION JOINTS, IF REQUIRED IN PIER MUST BE AT LEAST 12 INCHES (305 mm) BELOW
BOTTOM OF EMBEDMENTS AND MUST BE INTENTIONALLY ROUGHENED TO A FULL AMPLITUDE OF
1/4 INCH (6 mm). FOUNDATION DESIGN ASSUMES NO OTHER CONSTRUCTION JOINTS.
23. CASING, IF USED, SHALL NOT BE LEFT IN PLACE. EQUIPMENT, PROCEDURES, AND PROPORTIONS
OF CONCRETE MATERIALS SHALL INSURE CONCRETE WILL NOT BE ADVERSELY DISTURBED UPON
CASING REMOVAL. DRILLING FLUID, IF USED, SHALL BE FULLY DISPLACED BY CONCRETE AND
SHALL NOT BE DETRIMENTAL TO CONCRETE OR SURROUNDING SOIL. CONTAMINATED CONCRETE
SHALL BE REMOVED FROM TOP OF FOUNDATION AND REPLACED WITH FRESH CONCRETE.
24. TOP OF FOUNDATION SHALL BE SLOPED TO DRAIN WITH A FLOATED FINISHED. EXPOSED EDGES
OF CONCRETE SHALL BE CHAMFERED 3/4" X 3/4" (19 mm X 19 mm) MINIMUM.
25. FOR ANCHOR BLOCK TYPE FOUNDATIONS, FOR GUYED TOWERS, ADDITIONAL CORROSION
PROTECTION MAY BE REQUIRED FOR STEEL GUY ANCHORS IN DIRECT CONTACT WITH SOIL.
DESIGN ASSUMES PERIODIC INSPECTIONS WILL BE PERFORMED OVER THE LIFE OF THE
STRUCTURE TO DETERMINE IF ADDITIONAL ANCHOR CORROSION PROTECTION MEASURES MUST
BE IMPLEMENTED BASED ON OBSERVED SITE-SPECIFIC CONDITIONS.
DATE:
2
REVISED NOTE 7 TO 4500 PSI
2/10/2014
HAHAJHY
FOUNDATION AND ANCHOR TOLERANCES
ALL FOUNDATIONS
1. CONCRETE DIMENSIONS - PLUS OR MINUS 1" (25mm).
2. DEPTH OF FOUNDATION - PLUS 3" (76mm) OR MINUS 0".
3. DRILLED FOUNDATIONS OUT OF PLUMB - 1.0 DEGREE.
4. REINFORCING STEEL PLACEMENT - PER A.C.I. 301.
5. PROJECTION OF EMBEDMENTS - PLUS OR MINUS 1/8" (3mm).
6. VERTICAL EMBEDMENTS OUT OF PLUMB - 0.5 DEGREE.
ANCHOR BOLTS
7. MAXIMUM DISTANCE FROM CENTERLINE OF ANCHOR BOLTS TO
CENTERLINE OF FOUNDATION - 1/24 OF PIER DIAMETER UP TO A
MAXIMUM OF 2" (51mm).
8. ANCHOR BOLT SPACING - 1/16" (2mm).
9. ANCHOR BOLT CIRCLE ORIENTATION - 0.25 DEGREE.
10. ANCHOR BOLT CIRCLE DIAMETER - PLUS OR MINUS 1/16" (2mm).
SELF-SUPPORTING TOWERS
11. FACE SPREAD DIMENSION CENTER TO CENTER OF ANCHOR BOLT CIRCLES -
PLUS OR MINUS 1/16" (2mm) OR 1/16" (2mm) PER 20 FT. (6m) OF FACE
SPREAD.
12. MAXIMUM DIFFERENCE BETWEEN ANY TWO FOUNDATION ELEVATIONS -
1/2" (13mm).
GUYED TOWERS
13. GUY RADIUS - PLUS OR MINUS 5% OF DISTANCE SPECIFIED.
14. ANCHOR ELEVATION - PLUS OR MINUS 5% OF GUY RADIUS.
15. ANCHOR ALIGNMENT (PERPENDICULAR TO GUY RADIUS) - 1.0 DEGREE.
16. ANCHOR ROD SLOPE - PLUS OR MINUS 1.0 DEGREE.
17. ANCHOR ROD ALIGNMENT WITH GUY RADIUS PLUS OR MINUS 1.0 DEGREE.
18. ANCHOR HEAD OUT OF PLUMB - 1.0 DEGREE.
19. GUY INITIAL TENSION - PLUS OR MINUS 10% OF TENSION SPECIFIED.
NOTE: TOLERANCES IN NOTES 13 AND 14 CAN NOT OCCUR SIMULTANEOUSLY
WARNING!!!
AFTER ANCHOR BOLTS ARE INSTALLED IN CONCRETE HAS TAKEN ITS INITIAL
SET, ANCHOR BOLTS MUST NOT BE MOVED, BENT OR REALIGNED IN ANY
MANNER. A NUT LOCKING DEVICE MUST BE INSTALLED ON ALL ANCHOR
BOLTS.
CHK
REV:
DWN:
ENG'R:
DRAWING NO:
DATE:CHK'D:
DWG REFERENCE
DESCRIPTIONREV.
FILE NO.
REVISIONS
DWN
PRODUCTS
PEORIA, IL 61604
TOLL FREE 800-727-ROHN
6718 WEST PLANK ROAD
THIS DRAWING IS THE PROPERTY OF ROHN. IT IS NOT TO BE
REPRODUCED, COPIED OR TRACED IN WHOLE OR IN PART WITHOUT
OUR WRITTEN CONSENT.
APP
Jan/1
4/2
008 3:2
3:2
2 P
M
Sep/25/1987
\Ere
ctio
n\
8
KTLCSR
XK
A810214
Standard-SSV
8 JDA JDM H.A
GROUND LUG
(IF PROVIDED)
GROUND WIRE
ATTACHMENT LUG
ANCHOR BOLT MUST
BE STAKED IF PAL
NUT IS OMITTED
TINNED BARE
COPPER WIRE
(NO. 4 MAX)
GROUND ROD
CLAMP6.00" MIN.
(152mm)
8' (2.438M) GALV.
STEEL GROUND ROD
SELF-SUPPORTING
TOWERS AND GUYED
TOWERS WITH ANCHOR
BOLTS.
APPLICATION
ATTACH TO LEG IF CLAMP
PROVIDED: ATTACH TO JOINT BOLT
IF GROUND WIRE ATTACHMENT
LUG PROVIDED.
GROUND ROD
CLAMP
TINNED BARE
COPPER WIRE
(NO. 4 MAX)
8' (2.438M) GALV.
STEEL GROUND ROD
NO. 25, 45 & 55 TOWERS
WITH FLAT BASE
APPLICATION
6.00" MIN.
(152mm)
6.00" MIN.
(152mm)
6.00" MIN.
(152mm)GROUND ROD
CLAMP
8' (2.438M) GALV.
STEEL GROUND ROD
TINNED BARE
COPPER WIRE
(NO. 4 MAX)
GROUND WIRE
ATTACHMENT LUG
TINNED BARE
COPPER WIRE
(NO. 4 MAX)
ATTACH TO LEG IF CLAMP
PROVIDED, ATTACH TO BRACE
BOLT IF GROUND WIRE
ATTACHMENT LUG PROVIDED
GROUND ROD
CLAMP
8' (2.438M) GALV.
STEEL GROUND ROD
NO. 25, 45, 55, 36, 48,
80, 90, CC & DD TOWERS
WITH TAPERED BASE
APPLICATION
NO. 65 & JJ TOWERS
WITH TAPERED BASE
APPLICATION
BASE GROUNDING KITS (BGK)
6.00" MIN.
(152mm)GROUND ROD
CLAMP
8' (2.438M) GALV.
STEEL GROUND ROD
GUY WIRE GROUNDING
(AGK)
ANCHOR GROUNDING KITS
NOTE: REMOVE ALL SHARP BENDS
FROM GROUND WIRE
REV:
DWN:
ENG'R:
DRAWING NO:
DATE:CHK'D:
DESCRIPTIONREV.
FILE NO.
REVISIONS
DWN
PRODUCTS LLC
PEORIA, IL 61601-5999
TOLL FREE 800-727-ROHN
PO BOX 5999
THIS DRAWING IS THE PROPERTY OF ROHN. IT IS NOT TO BE
REPRODUCED, COPIED OR TRACED IN WHOLE OR IN PART WITHOUT
OUR WRITTEN CONSENT.
CHK APP
DWG REFERENCE
9
WDUAED
CW
C731105
Standard-SSV
Nov/27/1973
\Ere
ctio
n\
Jan/1
8/2
010 1:0
1:1
1 P
M
8 JDA JDM H.A
9 JDA JDM HA