34
PROPER CONTROL VALVE SELECTION - AN ENGINEER’S PERSPECTIVE DOUG SHOWERS, PE NOVEMBER 12, 2018 MADISON ASHRAE CHAPTER MEETING

PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

  • Upload
    others

  • View
    8

  • Download
    4

Embed Size (px)

Citation preview

Page 1: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

PROPER CONTROL VALVE SELECTION -

AN ENGINEER’S PERSPECTIVEDOUG SHOWERS, PE

NOVEMBER 12, 2018

MADISON ASHRAE CHAPTER MEETING

Page 2: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

LEARNING OBJECTIVES

• BETTER UNDERSTANDING OF CONTROL VALVE FUNCTION

• REVIEW OF CONTROL VALVE OPTIONS

• SELECTING THE RIGHT VALVE

• SIZING CONTROL VALVES

• WHEN TO USE PRESSURE INDEPENDENT CONTROL (PIC) VALVES

Page 3: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

BETTER UNDERSTANDING OF CONTROL VALVE FUNCTION

• FLOW CONTROL (2-POSITION – OPEN/CLOSED)

• TEMPERATURE CONTROL (MODULATION OF FLOW TO AFFECT ENERGY TRANSFER)

• PRESSURE CONTROL (MODULATION OF FLOW TO AFFECT PRESSURE OR PRESSURE

DIFFERENTIAL AT A GIVEN POINT)

• COMBINATION TEMPERATURE/PRESSURE CONTROL

• CONTROL VALVES CAN CHANGE THE FLOW RESISTANCE OF THE SUB-CIRCUIT ONLY!

• INDIRECTLY AFFECTS FLOW IN OTHER PARTS OF THE SYSTEM.

Page 4: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

SupplyReturn

A BCoil / Heat

Exchanger

Best location

Sub-circuit A-B

TEMPERATURE CONTROL VALVE FUNCTION

Page 5: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

SupplyReturn

A B

Sub-circuit A-B

PRESSURE CONTROL VALVE FUNCTION

PDT

Page 6: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

SupplyReturn

A BCoil / Heat

Exchanger

Sub-circuit A-B

TEMPERATURE/PRESSURE CONTROL VALVE

FUNCTION

PIC

Page 7: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

Pressure

Flow

ControlValve Pressure Drop

Coil and Sub-Circuit PipingPressureDrop

Cons

tant

Pre

ssur

eTEMPERATURE CONTROL VALVE FUNCTION

Page 8: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

VALVE CHARACTERISTICS

FROM 2016 ASHRAE SYSTEM HANDBOOKCH. 47

Page 9: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

VALVE CHARACTERISTICS

Combined with Heating Coil PerformanceFROM 2016 ASHRAE SYSTEM HANDBOOKCH. 47

Page 10: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

REVIEW OF CONTROL VALVE OPTIONS

• VALVE BODY STYLES AND MATERIALS

• PORT SHAPES/CHARACTERISTICS

• ACTUATOR TYPES/FAIL POSITIONS

Page 11: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

½” TO 2” BRONZE BALL VALVES• USED FOR MODULATING OR SHUTOFF SERVICE

• BODIES:

• AVAILABLE IN 2 PORT, 3-PORT MIXING, AND 3-PORT DIVERTING CONFIGURATIONS

• NPT OR SWEAT END CONNECTIONS

• CLASS 125 TO 250 PSIG WORKING PRESSURE (FUNCTION OF FLUID TEMPERATURE)

• AVAILABLE IN STAINLESS STEEL FOR CERTAIN APPLICATIONS

• BALL/PORT CHARACTERISTICS

• NORMAL, FULL, EQUAL PERCENTAGE

• BALL MATERIALS – BRASS, CHROME-PLATED BRASS, STAINLESS STEEL

• SEALS

• EPDM, VITON

• TEMPERATURE RANGES (0OF TO 250OF)

• CLOSE OFF PRESSURE – APPROX. 200 PSI

• FAIL OPEN, FAIL CLOSED, FAIL LAST POSITION

• COMMERCIAL VALVES VS. INDUSTRIAL GRADE VALVES

• STEAM AND CRYO SERVICE OPTION MAYBE AVAILABLE FOR INDUSTRIAL VALVES

Page 12: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

2-1/2” TO 6” IRON/STEEL BODY BALL VALVES• USED FOR MODULATING OR SHUTOFF SERVICE

• BODIES:

• AVAILABLE IN 2 PORT, 3-PORT MIXING, AND 3-PORT DIVERTING CONFIGURATIONS

• NPT OR CLASS 150/300 ASME FLANGED END CONNECTIONS

• CLASS 150 TO 275 PSIG WORKING PRESSURE (FUNCTION OF FLUID TEMPERATURE)

• AVAILABLE IN CAST IRON, CAST STEEL OR CAST STAINLESS STEEL

• BALL/PORT CHARACTERISTICS

• NORMAL, FULL, EQUAL PERCENTAGE

• BALL MATERIALS – BRASS, CHROME-PLATED BRASS, STAINLESS STEEL

• SEALS

• EPDM, VITON

• TEMPERATURE RANGES (0OF TO 250OF)

• CLOSE OFF PRESSURE – APPROX. 200 PSI

• NORMALLY FAIL IN LAST POSITION UNLESS SPRING LOADED OR BATTERY OPERATED ACTUATOR IS USED

• COMMERCIAL VALVES VS. INDUSTRIAL GRADE VALVES

Page 13: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

½” TO 2” BRONZE GLOBE VALVES• USED FOR MODULATING OR SHUTOFF SERVICE

• BODIES:

• AVAILABLE IN 2 PORT, 3-PORT MIXING, AND 3-PORT DIVERTING CONFIGURATIONS

• NPT OR SWEAT END CONNECTIONS

• CLASS 125 TO 250 PSIG WORKING PRESSURE (FUNCTION OF FLUID TEMP)

• AVAILABLE IN CAST STEEL OR CAST STAINLESS STEEL FOR INDUSTRIAL VAVLES

• PORT CHARACTERISTICS

• EQUAL PERCENTAGE, LINEAR, QUICK OPENING

• CAGE-GUIDED VALVES

• SEALS

• EPDM, VITON

• TEMPERATURE RANGES (0OF TO 250OF)

• CLOSE OFF PRESSURE – APPROX. 4 TO 365 PSI (FUNCTION OF VALVE SIZE AND ACTUATOR TYPE)

• COMMERCIAL VALVES VS. INDUSTRIAL GRADE VALVES

• STEAM AND CRYO SERVICE OPTION MAYBE AVAILABLE FOR INDUSTRIAL VALVES

Page 14: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

2-1/2” TO 6” IRON/STEEL BODY GLOBE VALVES• USED FOR MODULATING OR SHUTOFF SERVICE

• BODIES:

• AVAILABLE IN 2 PORT, 3-PORT MIXING, AND 3-PORT DIVERTING CONFIGURATIONS

• CLASS 125 ASME FLANGED END CONNECTIONS

• CLASS 125 TO 250 PSI WORKING PRESSURE FOR CAST IRON (FUNCTION OF FLUID TEMPERATURE)

• CLASS 150 TO 275 PSI WORKING PRESSURE FOR CAST STEEL (FUNCTION OF FLUID TEMPERATURE)

• PORT CHARACTERISTICS

• EQUAL PERCENTAGE, LINEAR, QUICK OPENING

• CAGE-GUIDED VALVES

• SEALS

• EPDM, VITON

• TEMPERATURE RANGES (0OF TO 250OF NORMAL, UP TO 400OF WITH SEAL SEATS AND TRIM)

• CLOSE OFF PRESSURE – APPROX. 20 TO 80 PSI (FUNCTION OF VALVE SIZE AND ACTUATOR TYPE)

• COMMERCIAL VALVES VS. INDUSTRIAL GRADE VALVES

• STEAM AND CRYO SERVICE OPTION MAYBE AVAILABLE FOR INDUSTRIAL VALVES

Page 15: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

GENERAL PURPOSE BUTTERFLY VALVES (2” TO 60”)• USED FOR SHUTOFF SERVICE (NOT RECOMMENDED FOR MODULATING SERVICE)

• BODIES:

• CAST IRON, DUCTILE IRON, CAST STEEL, ALUMINUM

• AVAILABLE IN 2 PORT AND 3-PORT (2-VALVES LINKED TOGETHER) CONFIGURATIONS

• CLASS 125 OR 250 ASME FLANGED END CONNECTIONS FOR CAST IRON

• CLASS 150 OR 300 ASME FLANGED END CONNECTIONS FOR CAST STEEL

• PORT CHARACTERISTICS

• QUASI-EQUAL PERCENTAGE, QUICK OPENING

• SEALS

• EPDM, VITON

• TEMPERATURE RANGES (0OF TO 250OF)

• CLOSE OFF PRESSURE – UP TO 175 PSI (FUNCTION OF VALVE SIZE AND ACTUATOR TYPE)

• COMMERCIAL VALVES VS. INDUSTRIAL GRADE VALVES

• STEAM AND CRYO SERVICE OPTION MAYBE AVAILABLE FOR INDUSTRIAL VALVES

Page 16: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

HIGH PERFORMANCE BUTTERFLY VALVES (2” – 54”)

• USED FOR MODULATING OR SHUTOFF SERVICE

• RELATIVELY HIGH CV VALUES

• BODIES:

• AVAILABLE IN 2 PORT AND 3-PORT (2-VALVES LINKED TOGETHER) CONFIGURATIONS

• CLASS 150 OR HIGHER ASME FLANGED END CONNECTIONS (FUNCTION OF FLUID TEMPERATURE)

• AVAILABLE HIGHER PRESSURE CLASSES USING CAST STEEL OR CAST STAINLESS STEEL FOR INDUSTRIAL VAVLES

• PORT CHARACTERISTICS

• QUASI-EQUAL PERCENTAGE, QUICK OPENING

• SEALS

• METAL, BUTYL, EPDM, VITON

• TEMPERATURE RANGES (0OF TO 500OF)

• CLOSE OFF PRESSURE – UP TO 1480 PSI (FUNCTION OF VALVE SIZE, PRESSURE CLASS AND ACTUATOR TYPE)

• STEAM AND CRYO SERVICE OPTION MAYBE AVAILABLE FOR CERTAIN VALVES

Page 17: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

PRESSURE INDEPENDENT CONTROL (PIC) VALVES(1/2” – 16”)

• USED FOR MODULATING

• BODIES:

• SAME AS BALL OR GLOVE VALVE OPTIONS

• CAN BE TWO VALVES IN SERIES WITH PRESSURE CONTROL VALVE/DEVICE UPSTREAM OF CONTROL VALVE

• PORT CHARACTERISTICS

• EQUAL PERCENTAGE

• SEALS

• EPDM

• TEMPERATURE RANGES (0OF TO 250OF)

• PRESSURE CONTROL DEVICE

• SPRING LOADED PRESSURE DIAPHRAGM

• ACTIVE CONTROL VALVE

• CLOSE OFF PRESSURE – APPROX. 200 PSI (FUNCTION OF VALVE SIZE AND ACTUATOR TYPE)

Page 18: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

ACTUATORS• MOVEMENT TYPE (LINEAR VS ROTARY)

• LINKAGES TO ACHIEVE MOVEMENT OF EITHER TYPE

• ENERGY SOURCE

• COMPRESSED AIR (15 TO 100 PSIG)

• LOW VOLTAGE (24 VAC)

• FLOATING POINT VS ANALOG

• WITH OR WITHOUT FEEDBACK

• LINE VOLTAGE (120 OR 240 VAC)

• MOVEMENT ACTION – 2-POSITION OR MODULATING

• FAIL POSITION

• SPEED OF ACTUATORS

• TIME DELAYS

• FEEDBACK OPTIONS

• OPEN/CLOSED POSITION SWITCHES FOR 2-POSITION VALVES

• ANALOG FOR MODULATING VALVES

Page 19: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

SELECTING THE RIGHT VALVE

• SERVICE – MODULATING, SHUTOFF

• DESIRED PORT CHARACTERISTICS

• EQUAL PERCENTAGE

• LINEAR

• QUICK OPENING

• PRESSURE/TEMPERATURE CLASS

• SHUTOFF PRESSURE

• DIFFERENTIAL VS DEAD-END

Page 20: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

ASME/ANSI PRESSURE CLASS

Page 21: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

SELECTING THE RIGHT VALVE

• CHARACTERIZED BALL VALVE

• ROTARY VALVE (90 DEGREE ROTATION)

• MORE FLOW THAN A GLOBE VALVE AT THE SAME SIZE

• LARGER CV

• BETTER SHUTOFF

• LARGE GLOBE VALVE = POOR SHUTOFF

• RECOMMEND USING MULTIPLE SMALLER CHARACTERIZED BALL VALVES INSTEAD

Page 22: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

SELECTING THE RIGHT VALVE

Page 23: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

SELECTING THE RIGHT VALVE

• COMMERCIAL VALVES

• SOME OPTIONS

• TRIM TYPE, MATERIAL

• SPRING RETURN, VOLTAGE, SIGNAL TYPE, FEEDBACK

• INDUSTRIAL VALVES

• MANY OPTIONS

• DIFFERENT TRIM TYPES TO REDUCE NOISE OR HANDLE CAVITATION, VALVE MATERIALS

• SELECTION SOFTWARE AVAILABLE FOR USE

• SMART VALVE POSITIONERS

• HART COMMUNICATION, DIAGNOSTICS

Page 24: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

SELECTING THE RIGHT VALVE

VALVE TYPE RECOMMENDED FLUIDS SIZE RANGE CV RANGE

SHUTOFF

PRESSURE

RELATIVE

COST

BRONZE BALL VALVE WATER <200oF, LPS 1/2" - 2" 1.2 - 77 200 LOW

CI/CS BALL VALVE WATER <200oF, LPS 2" - 12" 16 - 4200 200 MED-HIGH

BRONZE GLOBE VALVE WATER <200oF, LPS 1/2" - 2" 0.7 - 46 4 - 80 LOW

CI/CS GLOBE VALVE WATER <250oF, LPS, HPS 2 - 6" 51 - 347 4 - 100 MED-HIGH

PIC VALVE WATER <200oF 1/2" - 16" 3.4 - 2460 200 MED-HIGH

GP BUTTERFLY VALVE WATER <200oF, LPS 2-1/2" - 60" 300 - 190,000 175 LOW

HP BUTTERFLY VALVE WATER <400oF, LPS, HPS 2" - 60" 160 - 160,000 600 HIGH

NOTE - ALL VALUES VARY BY MANUFACTURER

VALVE COMPARISON TABLE

Page 25: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

SIZING CONTROL VALVES

• VALVE AUTHORITY

• SIZE FOR 25-50% VALVE AUTHORITY

• THIS MEANS THAT 25-50% OF THE SUBCIRCUIT PRESSURE DROP IS DUE TO THE VALVE

• OVERSIZED VALVES HAVE POOR VALVE AUTHORITY

• VALVE PRESSURE DROP △P = FUNCTION OF FLOW (Q) , SPECIFIC GRAVITY (SG), AND FLOW

COEFFICIENT CV

• CV = Q (SG/△P)0.5 OR △P = SG (Q/CV)2

• FOR WATER (SG=1), CV = FLOW (GPM) AT 1 PSI PRESSURE DROP

Page 26: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

CONTROL VALVE AUTHORITY

• CONTROL VALVE AUTHORITY (N) = RATIO OF VALVE △P/SUBCIRCUIT △P

• IDEAL AUTHORITY IS WHEN N < 0.5

• 0.25 < N < 0.5 IS USUALLY ACCEPTABLE

• UNSTABLE CONTROL RESULTS WHEN N < 0.25

• OVERSIZED VALVES RESULT IN LOW VALVE AUTHORITY

• CAN ALSO BE DESCRIBED AS TOO MUCH GAIN IN THE VALVE

Page 27: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

SIZING CONTROL VALVES

• RULES OF THUMB FOR TERMINAL DEVICES

• SUBCIRCUIT △P USUALLY < 10 FT. (4.3 PSI)

• SIZE MOST VALVES FOR △P BETWEEN 1.5 AND 2.2 PSI BUT NO LOWER THAN 1.1 PSI FOR GOOD

CONTROL AUTHORITY

• SOME UH/CUH COULD HAVE SUBCIRCUIT △P AS HIGH AS 25 FT (10.8 PSI)

• SIZE UH/CUH VALVES FOR △P BETWEEN 3 AND 5 PSI BUT NO LOWER THAN 2.7 PSI FOR GOOD

CONTROL AUTHORITY

Page 28: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

SIZING CONTROL VALVES

• PRIMARY EQUIPMENT

• SUBCIRCUIT △P CAN VARY BETWEEN 10 AND 40 FT (4.3 – 17.3 PSI)

• 1-2 ROW HEATING COILS ARE AT THE LOWER RANGE

• 6-10 ROW COOLING COILS ARE AT THE HIGHER RANGE

• FOR ACCURATE SIZING, CONSIDER DETERMINING SUBCIRCUIT PRESSURE DROP AND SELECTING VALVE FOR UP TO 50% OF SUBCIRCUIT △P.

• RULE-OF-THUMB METHOD:

• SIZE HEATING VALVES FOR △P BETWEEN 3 AND 5 PSI BUT NO LOWER THAN 3 PSI FOR GOOD CONTROL AUTHORITY

• SIZE COOLING VALVES FOR △P BETWEEN 3 AND 9 PSI BUT NO LOWER THAN 3 PSI FOR GOOD CONTROL AUTHORITY

Page 29: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

SIZING CONTROL VALVES

Page 30: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

INSTALLATION

• RULE OF THUMB IS NO MORE THAN TWO SIZES SMALLER THAN PIPE

• IF MORE THAN 2 SIZES, NEED STRAIGHT PIPE UPSTREAM AND DOWNSTREAM VALVE TO AVOID

CAVITATION

• NO AGREEMENT ON STANDARDS OR RULES

• CONTROL VALVE TEST STANDS HAVE AS MUCH AS 20D UPSTREAM AND 10D DOWNSTREAM

• USUALLY NOT PRACTICAL IN THE REAL WORLD

• BEST PRACTICE IS TO HAVE 2/3 OF STRAIGHT RUN UPSTREAM OF VALVE

Page 31: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

CAVITATION, FLASHING AND CHOKED FLOW

• CAVITATION AND FLASHING

• CAVITATION AND FLASHING OCCURS

WHEN PRESSURES WITHIN THE VALVE

(@ P2 LOW - BEFORE RECOVERY)

DROPS BELOW THE VAPOR PRESSURE

OF THE FLUID AT A GIVEN

TEMPERATURE

• CHOKED FLOW FOR NON-

COMPRESSIBLE LIQUIDS OCCURS AS A

RESULT OF CAVITATION OR FLASHING

• CHOKED FLOW FOR COMPRESSIBLE

GASES OCCURS WHEN VELOCITY

THROUGH THE PORT REACHES MACH 1

Page 32: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

CAVITATION, FLASHING, AND CHOKED FLOW

Page 33: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

WHEN TO USE PRESSURE INDEPENDENT CONTROL (PIC) VALVES

• FOR LARGE UNBALANCED SYSTEMS

• FOR SYSTEMS WHERE LOAD OR △P VARIES

• PROPERLY SIZED PRESSURE DEPENDENT VALVE CAN ACCOMPLISH THE SAME THING

• RESPONSE MAY BE SLOWER

• CONSIDER WHETHER TO USE ON ENTIRE SYSTEM OR ONLY LARGE VALVES

• NECESSARY FOR TERMINAL VALVES TO BE PRESSURE INDEPENDENT?

• COST IS MORE COMPETITIVE THAN IN THE PAST

Page 34: PROPER CONTROL VALVE SELECTION - AN ENGINEER’S …...sizing control valves •primary equipment • subcircuit p can vary between 10 and 40 ft (4.3 –17.3 psi) • 1-2 row heating

QUESTIONS?

• CONTACT INFORMATION

• DOUG SHOWERS, PE

• (608) 236-1119

[email protected]