Copyright © Siemens Austral Andina 2009. All rights reserved. SIEMENS FUNDAMENTOS DE LOS SISTEMAS DE PROTECCION NUMERICOS Protección Diferencial de Barras Distribuida

Protección Diferencial de Barras Distribuida

Embed Size (px)

Citation preview

Page 1: Protección Diferencial de Barras Distribuida

Copyright © Siemens Austral Andina 2009. All rights reserved.

SIEMENS

FUNDAMENTOS DE LOS SISTEMAS DE PROTECCION NUMERICOS

Protección Diferencial de Barras Distribuida

Page 2: Protección Diferencial de Barras Distribuida

Page 1Copyright © Siemens Austral Andina 2009. All rights reserved.

ED SE PTI

Versions

7SS50 Centralised versionSummation transformer

7SS51 Centralised versionPhase segregated

7SS52 Distributed versionPhase segregated

B U S BA R P R O T E C T IO N 7S S 52 11- 5 CA 0 0

SIPROTEC

B US B A R P R O T E C TI ON 7S S5 21 1-5 C A00

SIPROTEC

B U S B A R P R O TE C TIO N 7S S 52 1 1-5 CA 00

SIPROTEC

B U S B A R P R O T E CT I O N 7S S5 2 11 -5C A 0 0

S IP R O T E C

1 2 48

B U S B A R P R OTE C TIO N 7 SS 52 1 1-5 C A 0 0

SIPROTEC

3

Page 3: Protección Diferencial de Barras Distribuida

Page 2Copyright © Siemens Austral Andina 2009. All rights reserved.

ED SE PTI

q Further development of the centralised busbar and breaker failureprotection 7SS50/51

q Employing the prooven low impedance principle which is already used by Siemens in conventional, analogue and numerical protection schemes

q Firmware based on experienced software 7SS50/51( about 200 systems worldwide in service )

q Tripping time 15ms ( heavy duty tripping contact )

q Current transformer saturation after 3ms tolerable

q Integrated two-stage circuit-breaker failure protection

Page 4: Protección Diferencial de Barras Distribuida

Page 3Copyright © Siemens Austral Andina 2009. All rights reserved.

ED SE PTI

q Phase segregated measurement for each bus section

q Additional, isolator independant 'checkzone'

q Transfer bus treated as separate bus section

q Fault detection within the 'dead zone' between CB and CT of buscouplers

q Bay specific O/C-interlocking of trip command

q Bay-out-of-service function for maintenance

Page 5: Protección Diferencial de Barras Distribuida

Page 4Copyright © Siemens Austral Andina 2009. All rights reserved.

ED SE PTI

Substation configurations

q Single, double or triple busbar with transfer bus

q 48 bays

q 12 busbar sections

q 4 couplers, 24 sectionalisers

Page 6: Protección Diferencial de Barras Distribuida

Page 5Copyright © Siemens Austral Andina 2009. All rights reserved.

ED SE PTI

central unit

bay units

B USB AR PROT ECTIO N 7SS5211-5CA00

SIPR OTEC

BUSBAR PROT ECTION 7SS 5211-5CA00

S IPR OTEC

BUS BA R PROT ECTION 7S S5211-5 CA00

S IPR OTEC

B U S B A R P R O T E C T I O N 7 S S 5 2 1 1 - 5 C A 0 0

S I P R O T E C

1 2 48

BUSB AR PROTECTION 7S S5211 -5CA 00

SIPR OTE C

3

central unit

bay units

Page 7: Protección Diferencial de Barras Distribuida

Page 6Copyright © Siemens Austral Andina 2009. All rights reserved.

ED SE PTI

TRIP L1/1

intertrip

device failure

trip release

TRIP L1/2TRIP L2/1TRIP L2/2TRIP L3/1TRIP L3/2

TRIP /1

BF release

==

TRIP /2

IL1

I

I

I

L2

L3

0

BFBF L1

L2BF L3

CB OFF

V+

Q1 ONQ1 OFF

bay out of

CB in service

Q2 ONQ2 OFF

CB ON

Q3 ONQ3 OFF

Q4/7 ONQ4/7 OFF

Q9 ONQ9 OFF

BF trig. puls/CB test

V-

OF

RS232

TTLcentral unit(OF, 1,2 MBit/s)

operating/diagnosis

OF

TTL

TTL

(RS232, 19,2kBd)

18 LEDs

LC-Display

membrane keyboard

bay unit

service

Page 8: Protección Diferencial de Barras Distribuida

Page 7Copyright © Siemens Austral Andina 2009. All rights reserved.

ED SE PTI

Features of the bay unit

q Sampling, processing, testing and display of measured values

q Special handling of measured values for use in couplers

q Isolator position monitoring and indication

q Data acquisition for breaker failure protection

q Serial port for communication with the central unit

q Cyclic testing, self monitoring

Page 9: Protección Diferencial de Barras Distribuida

Page 8Copyright © Siemens Austral Andina 2009. All rights reserved.

ED SE PTI

==

reset of LEDs

bay unit 1(OF, 1,2 MBit/s)

operating/diagnosis(RS232, 19,2kBd)

central unit

OF

RS232

TTL

OF

TTL

TTL

release differential

time synchronisation

control master unit(OF)

OF

TTL

bay unit 48(OF, 1,2 MBit/s)

annunciation 1

annunciation 16 (32)

34 LEDs

LC-Display

membrane keyboard

current supervision

release disturbancerecord buffer

freeze disturbancerecord buffer

V+V-

device failure

Page 10: Protección Diferencial de Barras Distribuida

Page 9Copyright © Siemens Austral Andina 2009. All rights reserved.

ED SE PTI

Features of the central unit

q Phase- and sectionsegregated measurement

q Circuit-breaker failure protection

q Communication and synchronisation with bay units

q Cyclic checks of the entire system

q Administration of configuration data and parameters

q Interface to local PC ( DIGSI )

q Fault reporting and status indication

q Fault recording

Page 11: Protección Diferencial de Barras Distribuida

Page 10Copyright © Siemens Austral Andina 2009. All rights reserved.

ED SE PTI

Serial link central unit - bay unit

q Synchronous data transmission

q Full duplex communication via 2 optical fibres (62,5/125µm, 820nm, 1,5km, FSMA)

q Protocol in accordance to HDLC with additional monitoring of length of telegram (High Level Data Link Control Procedures for Data Communication)

q 1,2 MBaud

q Cycle time 1ms (50Hz), 0.83ms (60Hz)

q Hamming-distance d = 4

Page 12: Protección Diferencial de Barras Distribuida

Page 11Copyright © Siemens Austral Andina 2009. All rights reserved.

ED SE PTI

Circuit-breaker failure protection

q Two-stage for faults outside the busbar l Stage 1: repetition of tripsignal for faulty bay l Stage 2: tripping of every bay connected to the same bus sectionl Phase segregated unbalancing (reversal of current) l Limit of differential current related to nominal bay currentl Bay-specific minimum current releasel Bay-specific intertrip l Unbalancing on receive signal from the opposite protection

q Busbar faultsl Bay-specific intertrip

q Bus section specific, O/C-controlled distribution of trip commands in combination with external circuit-breaker failure protection devices

Functionality configurable independently for each bay

Page 13: Protección Diferencial de Barras Distribuida

Page 12Copyright © Siemens Austral Andina 2009. All rights reserved.

ED SE PTI

q Modular system

q Few types ofcomponents

q easy to extend

q easy to assemble

central unitZPS

(BSZ1)

DPR

ZPS(BSZ2)

DPR

ZPS(BSZ3)

DPR

ZPS(SBK)

DPR

ZPS(SK1)

DPR

ZPS(SK2)

DPR

ZPS(SK3)

DPR

ZPS(SK4)

DPR

ZPS(SK5)

DPR

ZPS(SK6)

EAZ1 EAZ2 SV

1 2 8 48

bay 1 bay 2 bay 48

ZPS: processing unitSBK: system management

BSZ: protection algorithmSK: Serial link

EAZ: I/O unitSV: power supply

bay unitA/D µC

bay unitA/D µC

bay unitA/D µC

Page 14: Protección Diferencial de Barras Distribuida

Page 13Copyright © Siemens Austral Andina 2009. All rights reserved.

ED SE PTI

central unitZPS

(BSZ1)

DPR

ZPS(BSZ2)

DPR

ZPS(BSZ3)

DPR

ZPS(SBK)

DPR

ZPS(SK1)

DPR

ZPS(SK6)

1 2 8 48

Abzweig 1 Abzweig 48

ZPS: processing unitSBK: system management

BSZ: protection algorithmSK: Serial link

EAZ: I/O unitSV: power supply

bay unitA/D µC

bay unitA/D µC

Calculationeven

samples

Interface to upto 8 bay units

Date acquisition ofbay informations,

indication, tripcommands

Calculation

checkzone

MasterSystemcontrol

Calculationodd

samples

Page 15: Protección Diferencial de Barras Distribuida

Page 14Copyright © Siemens Austral Andina 2009. All rights reserved.

ED SE PTI

Security against malfunction: 3-out-of-3 decision per bay

(BSZ 2)DPR

ZPS(BSZ 3)

DPR

ZPS

L+L -

(BSZ 1)DPR

ZPS

Short circuit in the checkzone, calculated fromall samples

Short circuit in disciminative zone x,calculated fromeven samples

Short circuit in disciminative zone x,calculated fromodd samples

Trip- relay(per bay)

3 pole tripping control per bay