Upload
a
View
212
Download
0
Embed Size (px)
Citation preview
A. ELEKASSOCIATE MEMBER AlEE
Proving the Adequacy of StationGrounds
1. No shielding or correction winding,131llV
2. With correction winding but noshielding, 2 mv
3. With correction winding and shielding, <0.005 mv
ReFerences
1. CURRENT TRANSFORMER RATIO AND PHASEERROR BY TEST RING METHOD, H. S. Baker.AlEE Proceedings, vol. XXXVI, 1917, PP. 1173-83.
2. A METHOD OF TESTING CURRENT TRANSFORMERS, W. E. Bruges. Journal, Institution ofElectrical Engineers, London, England, vol. 68,1930, pp. 305-07.
3. TESTING OF CURRENT TRANSFORMERS WITH ACURRENT COMPARATOR AND AN AUXILIARY ELECTRICAL SYSTEM (in German), I. Obradovic, P.Mi1janic, S. Spiridonovic. Elektrotechnische Zeitschrift, Wuppertal-Elberfeld, Germany, pt. A, vol.78,1957,pp.699-701.
4. THE CURRENT COMPARATOR AND ITS ApPLICATION TO THE ABSOLUTE CALIBRATION OF CURRENTTRANSFORMERS, N. L. Kusters, W. t. M. Moore.AIEE Transactions, pt. III (Power Apparatus andSystems), vol. 80, Apr. 1961, pp. 94-104.
5. DIELECTRIC ADMITTANCES IN CURRENT TRANSFORMERS, A. H. M. Arnold. Proceedings, Institution of Electrical Engineers, vol. 97, pt. 2, 1950, pp.727-34.
6. THE EFFECT OF CAPACITANCE ON THE DESIGNOF TOROIDAL CURRENT-TRANSFORMERS, A. H. M.Arnold. Ibid., pp. 797-808.
7. THE EFFECT OF WINDING POTENTIALS ONCURRENT TRANSFORMER ERRORS, N. L. Kusters,W. s. M. Moore. AlEE Transactions, pt. I(Communication and Electronics), vol. 81, July 1962,pp.186-91.
8. EFFECTS OF MAGNETIC LEAKAGE IN CURRENTTRANSFORMERS, H. W. Price, C. K. Duff. Bulletin,University of Toronto, Toronto, Ont., Canada,vol. 2, 1921, p. 167.
9. LEAKAGE PHENOMENAIN RING-TYPE CURRENTTRANSFORMERS, A. H. M. Arnold. Journal, Institution of Electrical Engineers, vol. 74, 1934, PP.413-23.
Summary: The definition of ground resistance and ground impedance in the case ofalternating currents is discussed. Groundresistance measurements with earth testersare compared with power frequency methods and the errors associated with the location of auxiliary grounds are described.It is emphasized that the ultimate purposeof testing station grounds is to determinetouch voltages and potentials arising oncommunication circuits. Methods are presented to evaluate the adequacy of stationgrounds, including very large stations.
TH E GROUNDING of a station isadequate if unwanted ground po
tentials in the station area do not exceed a specified limit during power systemfaults. In order to decide whether or not
DiscussionA. F. Dunn (Division of Applied Physics,National Research Council, Ottawa, Ont.,Canada): The current comparator as apassive magnetic current-ratio device of highstability and accuracy, which was previouslydescribed by two of the three authors, hasnow been extended in range to the pointwhere measurements of 2,000:5 amp arereadily available for 60-cps power-linefrequencies. The authors are to be congratulated on the extension they have made,particularly since they have also improvedthe accuracy of their current ratio comparators to the point where it looks asthough the phrase "parts in 1OS" is theconvenient phrase to eliminate use of smallfractions of a part in a million.
I t may be suggested that accuracy of thisdegree is not needed, and it may not be ifuse of the comparator is restricted to calibration of current transformers as we knowthem now. However, it is now possibleto examine current transformers in greaterdetail and with greater reliability and, ifnecessary, improvements in design may beachieved.
The current comparator is not restrictedto this single use; in fact, its greatest valueprobably will be realized as a current-ratiodevice for comparing other types of impedances. Ratios which are accurate to afew' parts in lOS are not easy to come by inthis day of increasing demands for accuracy and reliability, and the current comparator may be one of the devices for whichthe precision electrical measurements fieldis waiting.
I would hope that these extended ratiocomparators will prove as successful as theirpredecessors when the operating frequencyis increased.
Have the authors any information on
a station ground is adequate, it is necessary to predict first the magnitude of thehighest potential differences which mayoccur, and then to compare these with thetolerable maximum values determined bysafety rules or by other requirements.
The following potential differenceshave to be determined:
1. The expected highest touch voltagewithin or outside the station.2. The expected highest voltage arisingbetween communication and other lowvoltage circuits and the station ground.
For most stations both values can bederived from a single quantity: the groundresistance of the station. The groundresistance can be measured using one of
available high er, or lower, frequency use ofthese comparators?
P. N. Miljanic, N. L. Kusters, and W. ]. M.Moore: Dr. Dunn's comment regardingthe use of the current comparator for impedance ratio measurement is most important, and we are grateful to him formentioning it here. The current comparator possesses many features which we feelare of advantage in this type of measurement. It has good long-term stability, isrelatively independent of its operating environment, and its errors are usually smallenough to be negligible in most measurements.
The current comparators described inthis and the previous paper were designedfor use with fairly large currents. Theratings of the windings were of the order of400 to 2,000 amp-turns and sensitivity wasno problem. In impedance ratio measurements, however, somewhat lower values ofcurrent are usually employed, and the realization of adequate sensitivity in the presenceof proportionally higher external magneticfields is more difficult. Fortunately, withproper magnetic shielding, this difficulty canbe overcome to an appreciable extent, andcurrent comparators rated at 0.040 ampturns and having errors less than 1 part inlQ6 have been built.
The extension of the current comparatortechnique to higher and lower frequencies ispresently being investigated in our laboratory. The sensitivity is, of course, proportional to frequency, and the existingarrangement for detecting flux in the corebecomes more and more unsuitable as thefrequency is decreased. Other methods,such as those used in magnetometers, maybe used, however, and a d-e comparatorwhich employs a second-harmonic type ofdetector has been operated successfully.
the following methods, all of which aredescribed in this paper.
1. Measurement with a portable groundtester. Ground testers generate their owntest current, the frequency of which differsfrom that of the system.2. The voltmeter-ammeter method. Thismethod uses a test current of system frequency.3. The wattmeter-ammeter method. Thisreplaces the voltmeter-ammeter methodwhere mutual induction exists between thetest leads, but cannot be used to measuregrounds with reactance.
I t is convenient to use earth testerswherever this is possible. I t will beshown that earth testers cannot be usedin the following cases:
1. For very large 'stations where the im-
Paper 62-206, recommended by the AI EE SpecialInstruments and Auxiliary Apparatus Committeeand approved by the AlEE Technical OperationsDepartment for presentation at the AlEE WinterGeneral Meeting, New York, N. Y., January 28February 2, 1962. Manuscript submitted November 24, 1961; made available for printing June 1,1962.
A. ELEK is with the Hydro-Electric Power Commission of Ontario, Toronto, Ont., Canada.
368 Elek-Proving the Adequacy of Station Grounds NOVEMBER 1962
pedance of the station ground contains aconsiderable reactive component.2. Where stray power frequency voltagescause excessive vibration of the movementin the indicating instrument of the earthtester.3. Where the ground resistance to bemeasured does not exceed 10% of the lowestrange of the available ground tester.4. Where probe distances are large andthe ground resistance to be measured is low,so that the resistance of the ground pathremote from the field of the station forms asignificant part of the measured resistance.
In order to obtain the total potentialrise of the station ground with respect toa remote ground during faults, the measured ground resistance must be multipliedby the magnitude of the fault currentflowing through the station ground. Asexplained later, this value of current is,in most cases, considerably smaller thanthe total fault current obtained fromconventional calculations or networkanalyzer studies.
In stations with uniform soil the highesttouch voltage can be expected to be bebetween 20 and 30% of the calculatedtotal potential rise of the station ground.The highest voltage between communication circuits and the station ground canbe obtained by adding vectorially the voltage caused by induction from parallel linesto the total potential rise of the stationground.
In the company the author is associatedwith, the highest touch voltage normallypermitted is between 1,000 and 1,500volts. Hence) the total potential rise ofthe station ground will, in most cases,be less than 5,000 volts. (A limit of 3,000volts is recommended wherever it iseconomically feasible.) The reasons forchoosing these values will be explainedlater in the paper. There is no fixed limitto the voltage permitted between communication circuits and the stationground; it is, however, usually necessaryto know the magnitude of this voltage because the protection of the communication circuits will depend on its value.
There are certain cases in which it iseither not possible or not worthwhile tomeasure the ground resistance of thestation. Such cases are the following:
1. Where the station ground is connectedto an extensive underground network ofconductors, such as waterpipes, cablesheaths, counterpoise wires, etc., whichcannot be separated from the station ground(for example, stations in the built-up areasof cities).
2. Where the station ground is very largeand is interconnected with other stationgrounds in the vicinity (for example, largegenerating stations and adjacent transformeror switching stations).
3. Stations built on nonuniform soil.
In cases 1 and 2 proper ground resistance measurements are either impossibleor costly. Furthermore, the value of theconclusions which could be drawn fromthe results is doubtful, since for verylarge ground grids the assumption that thehighest touch voltage will be between 20and 30% of the total ground potentialrise, may not be valid. This is certainlytrue in case 3, where a general relationbetween the highest touch voltage and thestation ground resistance does not exist.
In the cases mentioned, it is more practical either to measure touch voltagesdirectly at all locations where they aresuspected to be high, or to omit measurements altogether and rely on conservativeestimates. Also, the voltage appearingon communication circuits can be eithermeasured directly in such cases or simplyestimated; a highly conservative rating ofthe protection may often be cheaper thana test.
Some extraneous conductors, such asskywires or neutral conductors, can beeasily separated from the station ground,in which case the measurement can becarried out on the station grid alone andthe effect of the extraneous conductorscan be taken into account by calculation.
In addition to the aspects just discussed, two further requirements of station grounds should be mentioned. First,in a system with effectively groundedneutral, where a reduced insulation levelis used, the zero-sequence resistance mustbe smaller than the positive-sequencereactance. It will be shown that if theground resistance of the major stations ina system does not exceed 2 ohms, which ispractically always the case, this requirement is satisfied. Second, adequacy ofthe station ground must be insured fromthe point of view of lightning. Exceptfor very small stations or for special research studies, the adequacy with respectto lightning is never checked by measurements and is assumed to be satisfactory.
Definition of Ground Resistance andGround Impedance
The AlEE Proposed Guide for Measuring Ground Resistance defines theground resistance of a ground electrodeas the ohmic resistance between it and aremote grounding electrode of zero resistance. In this case, "remote" is meant"at a distance such that the mutual resistance of the two electrodes is essentially zero."1
This definition needs some amplificationin the case of large stations and alternating
currents. The voltage rise of very largeground grids (such as the ground of largegenerating stations interconnected withthe grounds of adjacent stations, or stations in urban areas connected to citywater mains) is not in phase with thealternating current causing the voltagerise. I t is more accurate, therefore, toreplace the term "ground resistance"in such cases with the more precise term"ground iinpedance," which includes areactive component in addition to theresistance. Since the impedance determines the adequacy of the station ground,this quantity should be specified andmeasured. The ground impedance depends, of course, on frequency, and, therefore, station grounds with a considerablereactance can only be tested at power frequency.
In the case of alternating currents thedistance of the remote ground electrodewill also affect the value of ground resistance or ground impedance, as definedearlier. The impedance between thestation ground and 'a remote electrodewill be composed of two parts: the groundresistance or impedance of the stationground itself and the impedance of thecurrent path between the two electrodes,outside the field of the station, as expressed by Carson's formula. 2 This impedance has a resistive and a reactive component, which are both functions of frequency and distance They are bothequal to zero at direct current.
If the ground impedance is defined asthe impedance between the station groundand a remote electrode, the impedance ofthe current path will obviously create uncertainty. Even where the ground impedance of a station is a pure resistanceand reactive components need not beconsidered, the resistive component ofCarson's formula would still' cause asignificant error in the case of largedistance between the electrodes,
It may be possible to find an unambiguous definition for the groundimpedance of stations in the case ofalternating currents. This is, however,not necessary since the value of theground impedance itself is not useddirectly for the evaluation of stationgrounds, but rather the magnitude of thehighest potential difference in the stationarea. The measurement of "groundresistance" or "ground impedance" maybe regarded as only an intermediate stepin the derivation of the highest potentialdifference. For this purpose, ground resistance or ground impedance measurements are sufficient in most cases. It isimportant, however, to know what exactlyis being measured.
NOVEMBER 1962 Elek-Proving the Adequacy of Station Grounds. 369
Fig. 1. Potential field of ground grid, cempesed of four concentric rings, comparedwith the field of an equivalent hemisp'herical electrode
GROUND TESTERS
Ground testers produce a test current
grid. The potential field close to thegrid is different from that around theequivalent hemisphere, but at a distancegreater than approximately five times theradius of the hemisphere the two fieldsare nearly identical; see Fig. 1.
2. The auxiliary grounds should belocated remote from any extensivegrounded conductor which may providea shunt path for the test current. Conductors in telephone cables can be usedas test leads between the auxiliarygrounds and the station ground onlyif their metallic sheaths (or shields) arenot grounded in the station area withina distance at least equal to lOr fromthe center. This sometimes requires isolation of the sheath from the stationground and from other grounds alongits route.
3. If possible, the two auxiliarygrounds should be so located that theangle between the two lines, drawn fromthe center of the station to the auxiliarygrounds, exceeds 90 degrees. If this cannot be achieved, the auxiliary groundsmav be located in the same direction, butin this case the mutual impedance between the test leads must be taken intoaccount. Ground testers are not significantly affected by the inductive component of the mutual impedance, but they areaffected by the resistive component, whichis a function of frequency. If the leadsare parallel, the wattmeter-ammeter andnot the voltmeter-ammeter method mustbe used.
4. If one circuit of a double-circuitline is used for the connection between anyone of the auxiliary grounds and thestation, circulating currents in the secondcircuit may cause errors if the secondcircuit is in service and, consequently,connected to grounded transformers atboth ends. For this reason the live circuit should be several times longer thanthe test circuit.
5. Induction from external circuitsshould be avoided, if possible, irrespectiveof the test method used. For this reasonthe direction of the potential probeshould be such that power lines carryinglarge currents do not cause excessive interference. Induction in the loop betweenthe station and the current probe does notaffect the measurement. Consequently,if the possibility of .a choice exists, thelead subject to less induction shouldalways be the potential lead and the onesubject to higher induction should be thecurrent lead.
(1)
lor9rsr
( 1 +~) - (~+~)Xab Xsa xs~
where r is the "equivalent radius" of thestation, X sa is the distance between thecenter of the station and the first auxiliaryground (a)'; XSb is the distance betweenthe center of the station and the secondauxiliary ground (b); Xab is the distancebetween the two auxiliary grounds. Theexplanation of these recommendations isgiven in Appendix I. It is shown thatthe ground resistance of a circular gridcomposed of a mesh of buried conductorsis very nearly equal to the ground resistance of a hemispherical electrode with aradius equal to one half of that of the
1
tion to the test result. The followingprocedure is recommended:(a). Determine the approximate area of thestation, and determine the radius of a circlehaving the same area. One half of thisradius is defined as the "equivalent radius"of the station r. The distance of the auxiliary grounds from the center of the stationand from each other should not be less than5r.(b). To correct the error caused by insufficient probe spacing, the measuredground resistance should be multiplied bythe following factor:
r ar 3 r 4 r 5 r 6 r 7 rDISTANCE FROM CENTRE OF STATION
or2r
" lJl tI I \ "It
I :<> :1--'- d= .h.: : 50I I
1[8]
I
GROUND GRID ANDEQUIVALENT HEMISPHERE
I,,' <, , I
l 1,/ ':I \
: r'< },\ zr /~, /I ' <, ---",,/ !II
I II I
I I
I II :II I
I
I' -1- -- -- - -I \1 II I[Al~~
n ~ ~ 1/\ ~ ~ POTENTIAL AROUND GROUND GRIDjAND ~t--
II~ \l\J r-, / \~\ V!\ AROUND EQUIVALENT HEMISPHERE
/ I \\, \
7 ,\ \ CURVE I,,
V- GROUND GRID, ,.>, , i\..~,.
....."'-<,~'-- CURVE 2
....~
~EQUIVALENT HEMISPHERE~
I I I I I I Ir-__~~~I='=:t:==-:.,~
I I I I I I Io
100
(fJI-.J0>~
.J 50-ci=zLLl
bQ.
LOCATION OF AUXILIARY GROUNDS
1. The auxiliary grounds should belocated at sufficiently large distancesfrom the station ground and from eachother so as not to cause excessive errorsthrough mutual coupling. In the case oflarge stations the required distances become very large, making it often morepractical to locate the auxiliary groundsat a smaller distance and apply a correc-
h =-ll.I I I __ L L_ I I I.- 300~',;;m)}}~
Measurement of Ground Impedance
The most suitable method of measuringthe ground impedance of a station incorporates the use of two auxiliarygrounds. This method consists of circulating a current between the stationground to be tested and one auxiliaryground (the current probe), and of measuring the voltage rise caused by this current, between the station ground and theother auxiliary ground (the potentialprobe). The quotient of the voltage riseand .of the ground current is then found,either directly, as in the case of earthtesters, or by calculation) as in the caseof the voltmeter-ammeter or wattmeterammeter methods. In both cases theproper location of the auxiliary groundsrequires special attention.
370 Elek-Proving the Adequacy of Station Grounds NOVEMBER 1962
60 CYCLEPOWER SUPPLY
~ 60 CYCLE= POWER SUPPLY
CURRENTPROBE
VOLTMETER
STATION GROUNDPOTENTIAL
PROBE CURRENTPROBE
VOLTMETER
POTENTIALPROBE
Fig. 2. Method of ground impedance measurement with a-voltmeter and an ammeter
Fig. 3. Method of ground resistance measurement with a wattmeterand an ammeter. (A voltmeter is convenient but not strictly necessary)
(2)
(3)
(4)
the frequency of which differs from thesystem frequency. They cannot be usedtherefore to measure the impedance of astation ground which has a significantreactive component. Also, they onlyindicate the resistive component of theimpedance, which has no significancewithout the reactive component. Theindication of ground testers having ahand-cranked generator changes withcranking speed when measuring groundswith reactance.
Where the ground impedance to bemeasured is a pure resistance, groundtesters can usually be used, but a seriouserror may be introduced in the case of lowresistance grounds associated with largeprobe distances, especially if the testleads are parallel. This error is caused bythe frequency-dependent resistance of thecurrent path in the ground remote fromthe field of the station, as expressed by thereal component of the Carson formula. 2
Where the leads are parallel this component is equal to 0.0016.f ohm per mile(where! is the frequency), or to 0.1 ohmper mile at 60 cycles, but is unknown atthe frequencies produced by groundtesters. Where the leads run in oppositedirections, the error is smaller anddifficult to calculate. The possible effectof this type of error should be consideredwhere large probe distances are used inconnection with ground testers.
In ground testers each of the two main(potential and current) circuits has twoterminals; sometimes all four are accessible, sometimes two terminals are interconnected within the instrument and thetester has only three external terminals.In the latter case, the common terminalis connected to the station ground with asingle connection and the resistance ofthis connection is measured together withthe station ground resistance. Wherethe station ground resistance is in theorder of 0.1 ohm, neglect of the resistanceof the connecting lead may result in aserious error. In 4-terminal instruments,
this error can be prevented by connectingthe potential and current circuits to thestation ground at different points.
It is sometimes impossible to use aground tester, either because the resistance to be measured is too low comparedwith the range of the instrument, or because interfering 60-cycle stray potentialscause excessive vibration, preventing anyacceptable reading.
THE VOLTMETER-AMMETER METHOD
The voltmeter-ammeter method canbe used for ground impedance measurements only if the angle between the general direction of the test leads exceeds90 degrees. The circuit diagram of thismethod is shown in Fig. 2. The principle is essentially the same as that oftests performed with a ground tester.The test current is circulated through anammeter, through the station ground, andthrough the current probe, while the voltage rise of the station is measured with avoltmeter between the station ground andthe potential probe. The ground resistance or ground impedance (R) of thestation is equal to the measured voltagerise (E t ) divided by the test current (It)and multiplied by the correction factorwhich compensates for the error causedby the insufficient distance of the auxiliary grounds (equation 1).
E tR=K1 -It
Provisions have to be made to supply thetest current from a 60-cycle low-voltagesource, either directly or through a transformer.
The measurement of ground impedancewith the voltmeter-ammeter method isaffected by external 60-cycle currentsand voltages (such as stray currentsflowing through the station ground andvoltages caused by induction from parallellines). While in the case of ground testersthese stray effects may only cause excessive vibration, they can cause serious
errors when the voltmeter-ammetermethod is used. It is, however, possibleto eliminate this error by the followingprocedure:
1. Connect the current lead to the stationground through the ammeter. Connect thepotential lead to the station ground throughthe voltmeter. Take a reading on theammeter 10 and on the voltmeter Eo beforeapplying the test current (position 0 in Fig.2).2. Insert the 60-cycle current source in thecurrent lead, as shown in Fig. 2 (position 1).Apply the test current and take a reading onthe ammeter and on the voltmeter (Ii andE 1 respectively).
3. Reverse the polarity of the test current(position 2) and take a third reading on theammeter and on the voltmeter (12 and E 2respectively).
The magnitude of the test current It canbe calculated from the following formula:
~I12+I22
1 t = ----102
2
The voltage rise E, caused by the testcurrent can be calculated from the following formula:
~E12+E22
E t = ----Eo!2
The ground resistance of the station canbe found by substituting It and E, inequation 2. The proof for equations 3and 4 is given in Appendix II.
THE WATTMETER-AMMETER METHOD
If the leads between the station and thetwo auxiliary grounds are, partly orthroughout their full lengths, runningparallel to each other, a modified versionof the voltmeter-ammeter method may beused. This consists of replacing the voltmeter with a wattmeter as shown in Fig.3. The purpose of the wattmeter is toresolve the potential rise of the stationground into two components: the one inphase with the test current and the onein quadrature with the test current. If
NOVEMBER 1962 Elek-Proving the Adequacy of Station Grounds 371
(8)
(9)
(10)
(11)
HIGH PROBE RESISTANCE
If the ground resistance of the potentialprobe is relatively high compared withthe resistance of the voltmeter (or of thepotential coil of the wattmeter or ohmmeter), all readings except current readings have to be multiplied by the followingcorrection factor:
ungrounded single-phase 60-cycle powersupply since both terminals must begrounded alternately in the station. Ifsuch power supply is not available: agrounded 3-phase power supply can beused instead. In this case instead ofthree readings, as described in the previous sections: four readings are takenand, instead of reversing the current between steps 2 and 3, the test current isdrawn in turn from the three phases.
Thus, if lo, Eo, and Po are the readingsbefore applying the test current, there willnow be three readings instead of two foreach quantity measured with the testcurrent flowing: It, 12, 13 ; EI, E2, E3 ; andPI, P2, P3• Equations 3, 4, and 7 will bemodified as follows:
~I) 2+122+13 2
I t = 102
3
HIGHER HARMONICS
The voltages and currents caused byextraneous effects (induction and straycurrents) during ground resistance tests,and measured before or after the application of the test current, very often containharmonics, especially third harmonics. inconsiderable amounts. Tests performedwith a ground tester are not affected bythese. In the case of the voltmeterammeter or wattmeter-ammeter methodit can be shown that if the source supplying the test current produces a reasonablysinusoidal 60-cycle voltage Ei, the harmonic content. of which is not higber thannormally encountered in any power system, no error of any significance will becaused. If the instruments are of theelectrodynamic type, the results w ill berigorously correct) even if Is, Eo or Po arepure higher harmonics. If the voltmeterand the ammeter is a moving-coil rectifiertype instrument, some error will be introduced where the harmonics dominate.
K2= Rmeter+Rprobe
Rmeter
In the case of ground testers, in whichsome means of compensation are in-
(7)
The power P e caused by the test currentand by the voltage rise can be calculatedfrom the following formula:
Pl+P2Pt=---Po2
caused by extraneous grounds and/or bymutual induction between the test circuitscannot be distinguished one from theother, parallel test leads should not beused if the ground impedance of thestation is suspected to contain a significant reactive component.
To eliminate the effects of extraneous60-cycle interference, by induction or bystray currents flowing through the station ground, the following procedure isrecommended:
1. Connect the current lead to the stationthrough the ammeter and the current coil ofthe wattmeter. Connect the potential leadto the station ground through the potentialcoil of the wattmeter. Take a reading onthe ammeter 10 and on the wattmeter Po before applying the test current (position 0 inFig. 3).
2. Insert the 60-cycle current-source in thecurrent lead as shown in Fig. 3 (position 1).Apply the test current and take a readingon the ammeter and on the wattmeter (IIand PI respectively). Note the sign of thewattmeter reading.
3. Reverse the polarity of the test current(position 2), and take a third reading on theammeter and on the wattmeter (12 and P 2respectively).
The magnitude of the test current Itcan again be calculated from the followingformula:
~I12+122
I t = ----16-2
2
GROUNDED 3-PHASE POWER SUPPLY
It is obvious from Figs. 3 and 4 that themethod of current reversal requires an
The station ground resistance can befound by substituting It and P t in equation 6.
In the procedure described, it may benecessary to change the polarity of thewattmeter between readings. In thiscase, attention must be directed to ensurethat the correct signs appear before PI,P2, and Po in equation 7. The proof forequations 6 to 8 is given in Appendix II.
Where the test leads are in parallel, 0.1ohm must be subtracted from the computed resistance for every mile between the station and the current or thepotential probe, whichever is the closer.This is derived from Carson's formula,and is the 60-cycle resistance of theground path parallel to the test leads,and is not part of the ground resistanceof the station.
(5)
(6)
REST OF THESYSTEM~
~
REST OF THE
SYSTEM-+-----
IfTOTAL FAULT
CURRENT
~ it ~ ttI gI \,,~~~~~= =--~~~===~.=.-=-~==-----.t:':~--~--~:'~)CURRENT THROUGH STATION GROUND
[AlFAULT AT THE STATION
STATIONTRANSFORM ERS
-+t--;r
STATION"TRANSFORMERS
tt Zt
.t
the test current is It and the power measured by the wattmeter is P t , the in-phasecomponent of the voltage can be foundfrom the following formula:
[B]FAULT REMOTE FROM THE STATION
Fig. 4. Distribution of fault current duringfaults inside and outside a station
~tt !! t! ~ttI' I I ~ I I I'
Ig2 \,:~=====~_::./ \,~====-~-----~-~~=':./CURRENT THROUGHSTATION GROUND
PtEd=
It
The voltage component in quadraturewith the test current is usually caused bymutual induction between the test leads,and would constitute an error if it werenot eliminated. The in-phase componentof the measured voltage Ed can then beassumed to be caused entirely by the station ground resistance. The groundresistance of the station R can be expressed from equation 5 as follows:
~ CURRENT SUPPLIED BY THE TRANSFORMERS IN THE STATION
-+----- CURRENT SUPPLIED BY THE RESTOF THE SYSTEM
K I is the correction factor compensatingfor the error caused by the proximityeffect of the auxiliary grounds (equation 1).
It was mentioned before that, if thestation ground is of large physical size (being, for instance, connected to low-resistance extraneous grounds), the measuredvoltage may contain a reactive component, even in the absence of mutualinduction between the measuring circuits.Reactive voltage components caused byextraneous groundsmust not be eliminated, since such grounds do affect thevoltage rise of the station ground duringfaults. Since the reactive components
272 Elek-Proving the Adequacy of Station Grounds NOVEMBER 1962
(12)
other transformers. In this case thecurrent flowingthrough the station groundwill be
MAGNITUDE OF TOUCH VOLTAGES
The magnitude of the highest touchvoltage can be expressed as a percentage
of the total potential rise of the station.This value has been calculated on the basisof reference 3 for some typical groundgrids. It was found that the highesttouch voltage varies between 20 and 30%of the total potential rise, the lower valuebeing valid for large stations, the higherfor small stations. These figures agreevery well with a large number of testresults.
Of course, this percentage figure is onlyvalid for touch voltages within and immediately surrounding the station. Extraneous conductors may transfer potentials to larger distances where thetouch voltage may be higher. This is trueespecially in the case of metallic conductors which are, more or less, insulatedfrom ground, such as railway tracks onrock ballast; the potential of such conductors may rise to a value considerably exceeding 20 or 30% of the station potentialrise. It is, however, not practical to basethe general specification of the highesttolerable touch voltage on such speciallocations; abnormally high touch voltagescan be eliminated by local measures,such as for instance isolation of the railway tracks, etc.
After estimating the highest touch voltage in this manner. it must be decidedwhether the value thus obtained is satisfactory or not.
The tolerable limit of touch voltage canbe calculated either on a minimum or on aprobability basis. In the first case allfactors influencing the shock hazard areassumed to be close to their worst possiblevalue. In the second approach, the probability distribution of each factor is determined separately and the probabilities arecompounded.
The company the author is associatedwith will specify a maximum telerabletouch voltage of 1,000 to 1,500 volts inits new grounding guide (otherwise exceptional safety measures would be required) . This corresponds in an averagestation to a maximum total station potential rise of 5,000 volts (3,000 volts isrecommended, however, where economically feasible). This specification is basedon a probability study assuming amean body conductance of 1.1 milliamperes/volt (equivalent to 900 ohms)with a standard deviation of 26%. Thefoot resistance on a 4-inch layer of wetcrushed stone was found from a surveyin a station to vary with equal probabilitybetween 3,000 and 12,000 ohms. Compared with this range, the body resistancebecomes almost insignificant. The probability of fault duration was computedfrom a survey of fault records on a 115and 230-kv system; it was found that
(13)
(14)
(15)
where Zext is the impedance of the extraneous grounds, as seen from the station,and Rgr id is the measured ground resistance (or ground impedance) of the grid.If the extraneous conductors are multigrounded conductors (such as skywires orneutral conductors), then
Z _ ~zscriesext-
gshunt
where Zseries is the series .impedance of theconductor in ohms per mile and gshunt is itsshunt conductance in mhos per mile. Insome cases, as for example in small distributing stations, the ground resistanceof the station grid becomes unimportantand the potential rise of the station will bealmost solely determined by the impedance of the extraneous grounds (distribution neutrals).
Zo192=-1/Zt
To calculate the highest potential rise,the type of fault which produces thelarger current through the station groundshould be considered. It is obvious fromequations 12 and 13 that if Z t>2Zo, it isthe fault in the station which producesthe larger current through the stationground and if Z t<2Zo} it is the faultoutside.
Skywires carry part of the fault currentand, therefore, I g! will actually be smallerthan calculated. This effect can, however, be considered as a safety margin.
In stations with extraneous grounds thecurrent flowing through the stationground consists of two parts: the partflowing through the station ground gridand the part flowing through the extraneous grounds. It is usually recommended that the ground impedance of theground grid be measured after disconnection of all those extraneous groundsthat can be disconnected. Hence, thestation ground current, as calculated fromequations 12 or 13, must be furtherdivided into two parts. To obtain thepotential rise of the station ground, onlythe part flowing through the ground griditself should be multiplied by the measured ground resistance. This part of thecurrent can be calculated from the following complex equation:
z.;19 r id = 19
Zext+R.grid
Evaluation of Test Results
When ground resistance measurementsare performed, it should never be £org-otten that the ultimate purpose of themeasurements is to determine potentialdifferences, such as touch voltages andovervoltages arising in the communication plant. These potentials have to becalculated, taking into account severalfactors, of which the ground resistance(or ground impedance) is only one.
corporated, their instruction manual hasto be consulted.
MAGNITUDE OF FAULT CURRENTS
The potential rise of the station groundwith respect to a remote ground (thetotal potential rise of the station) is theproduct of the ground impedance and thefault current flowing through the stationground. It is important to emphasizethat the current flowing through the station ground is very seldom equal to thefull ground fault current. In an interconnected system there are almost always several connections between transformer neutrals and the ground, all ofwhich will carry a portion of the total faultcurrent.
Fig. 4 illustrates the difference betweena fault in the station and a fault outsidethe station. In the first case, as shown inFig. 4(A), the current supplied by thegrounded transformers in the station returns to the transformer neutrals directlythrough metallic conductors withoutentering the ground. Hence, this portionof the fault current does not cause anypotential rise. In parallel with the station transformers, however, are all theother grounded transformers in the system. The portion of the fault currentflowing through these transformers hasto flow through the station ground and is,therefore, the current which has to be considered in the calculation of the potentialrise of the station ground.
If I I is the total fault current, Zo is thezero-sequence impedance of the wholesystem, as seen from the station, and Z t isthe zero-sequence impedance of the station transformers only, the current flowing through the station ground will be
lUI = (1-;:)11
If the fault occurs outside the station,as shown in Fig. 4(B), only the portionsupplied by the station transformers willflow through the station ground: theportion supplied by all the other transformers in the system will flow away fromthe fault location in the direction of these
NOVEMBER 1962 Elek-Proving the Adequacy of Station Grounds 373
PROTECTION OF COMMUNICATION
CIRCUITS
The voltage appearing between communication circuits and the station groundduring faults can be considered to beapproximately equal to the total potentialrise of the station. Of course, any additional potential caused by induction fromparallellines must be added (vectorially)to the ground potential rise. Theknowledge of the total potential rise isnecessary for the selection of the voltagerating of neutralizing and insulating transformers. It is also necessary where noprotection is applied and the insulation ofthe wires is expected to withstand thepotential rise. The value of the potential
67% of the faults last less than 12 cycles,25% between 12 cycles and 1 second, 7%between 1 and 2 seconds, and approximately 1% between 2 and 3 seconds.Compounding all probabilities, it can beshown that the probability of death is 1%in the case of a touch voltage of 1,000volts, and 2.5% in the case of 1,500 volts.This compares unfavorably with theassumption of 0.5% made by the AlEEWorking Group on Voltage Gradients. 3
However, it should be considered that during the survey the ground was found to bewet only once out of every six cases; thus,the probabilities are actually reduced toone sixth of the given values. It seemsreasonable to allow a higher probabilityin small stations than in large stationsand, hence, due to the higher gradientsin small stations, a value of 5,000 voltsis obtained for the tolerable potentialrise in every case.
I t should be noted that the ratio of thetouch voltage to the total potential riseis sometimes considerably less than 20%.This is particularly true in stratified soilswhere a shallow low-resistivity overburdencovers high-resistivity rock. The groundresistance of such stations is high because of the high-resistance subsoil.The potential gradients are, however,determined by the resistivity of thesurface. A typical case has been calculated on the basis of reference 4; thetouch voltage was determined at a distance of 1 meter outside a single buried
ring on a 2-layer soil. The results areshown as a function of the ratio of thetwo resistivities in Fig. 5. It can be seenthat while the ground resistance risessteeply with an increasing resistivity ofthe subsoil, the touch voltage remains almost constant. Hence, the percentagevalue of the touch voltage, which is 30%in the case of a uniform soil, drops to 6%for a resistivity ratio of 10, and to 1% fora ratio of 100. In nonuniform soils it istherefore often not necessary to lower theground resistance, at great expense, onlyon account of potential gradients: in suchcases, a direct measurement of the gradients may show that a total potentialrise exceeding the normal limit could bepermitted.
rise is not important where protector gapsare applied, since these will break: down inany case.
The incremental cost of the protectionof conununication circuits against higherpotentials is usually less than the costof improving the ground. It is good practice, therefore, to determine the requirements of the station ground on the basis ofprotection against touch voltages andinstall a suitable protection for the communication circuits in compliance with thestation potential rise thus obtained.
GROUNDING OF TRANSFORMER NEUTRALS
The ground resistance of the stationmust be sufficiently low to permit effective grounding of systems with operatingvoltages of 115 kv or higher, providedthat the system is designed for a reducedinsulation level, as customary in highvoltage systems.
The ground resistance of the stationmust not be higher than the leakagereactance of all transformers in the station. If the station ground resistance isless than 2 ohms, this will assure propergrounding for transformer capacities upto 600 mva at 115 kv and 2,500 mva at230 kv, since the leakage reactance of atransformer bank (assuming a per-unitreactance of 0.1) is 2.2 ohms in the firstcase and 2.1 ohms in the second.
Very Large Station Grounds
Because of the reactance of largeground grids (and of ground grids connected to an extensive network of underground conductors), their ground impedance can only be measured with 60-cyclecurrents. Since large ground grids require large probe distances, 60-cyc1estraypotentials will usually be high. To overcome these, a large test current has to beused, and in order to drive that currentover the high impedance of a large probedistance a relatively large power supply isrequired. In addition, transmission lineshave usually to be taken out of service toprovide test leads of sufficient lengths....'-\11 these requirements make tests of thistype rather expensive.
Where underground pipes and cor.duetors cannot be separated from the stationground, it is not possible to specify therequired probe distance. Furthermore,even if the ground impedance could bemeasured, this value would be almost useless, since the assumption that the highesttouch voltage is approximately 20% ofthe total potential rise would probably beno longer valid for stations with verycomplex grounds and with undergroundextensions in several directions.
For these reasons. in such stations it
Fig. 5. Touch voltageand potential riseof station on nonuniform soil. Singlering with dimensionsshown in insert
i-Current densityin amperes per footpt-Resistivity of topsoil in ohm-metersps-Resistivity ofsubsoi lin ohm-meters(To obtain actualvoltages, multiplyordinates by i XPt)
3 4 5 6 8 10 20 30 40 60 100
h RATIO OF SUB-SOIL RESISTIVITY TO TOP-SOIL RESISTIVITYfT
I v,l'/
/VV
~\~v
~~er:¢~ ~ -
~'\~ 3.3' -~~~ : r-
-. X ~o~i '~.~I>< I ~"''' 053"~~"[~~ ,"""'~ ~ ~"",,',,"" ~ f-
/ Clt-~)-::"O(" _~~,~101\1 -iG~
~ -is I~~ ~I I 'v~l ~J?:Af( "~~
~/.s ~AJ
TouCH VOLTAGEe ~~
"- ...........-~ "",<,
<,r-,I ,
300
at' g 200lL -;; 4>1(1)... <J..J o l&J> en 100z ~- ..J 80(l) oC(
t= 60w Zt/) W 50
~ ~ 40
~ ~ 30Z i=LaJ oC(... t- 20~ en~ ~i= b1< C)t- ~ 10en ZC l&J 8Z 041( ffi 6
~ ~ 5UJ ~ 4
~ ~... 0..J >o ::E:> Uo a:> ...o...
374 Elek-Proving the Adequacy of Station Grounds NOVEMBER 1962
form tests at all, provided that voltagegradients are not expected to be unusuallyhigh.
(21)pI
V(x)=21rx
2IoEo*= ItE t* = P t (23)
This is the proof of equation 7. The equa-
P1+ P 2_P O
2(10+I t)( E t*+E,*) +(10
] t)(Eo*-Et*)
The quantity to be determined is
Pt=ItEt*The following equation can be written:
(Eo+ Et)(Eo*+Et*)+(EoE t)( Eo*- E t*)
Equation 4 is thus proved. The stray current can be eliminated in an analogous way,resulting in equation 3.
In the wattmeter method the power ismeasured instead of the voltage. If Po is the(complex) power measured with no testcurrent, PI is the power measured with thetest current II flowing in one direction, P 2 isthe same after current reversal, and I o is thestray current
The stray voltage Eo can be separatedfrom the voltage E, caused by the test current by performing three measurements:one with no test current and the other twowith test current, but reversing the directionof the current the second time. The voltage measured with the test current flowingis then E 1 =(Eo+Et); and after current reversal it is E 2= (Eo- E t ) . All quantities arecomplex numbers. It can therefore bewritten that
2
EoEo*=EtEt*=jEtI2 (22)
Po = loEo*
PI = (Io+It)(Eo+Et)*
P 2 = (10 - I t )( Eo- E t)*
Appendix II. Elimination ofStray Voltages and Currents
At a distance equal to 5r the differencebetween the two curves is less than 4%.Since the configuration of four rings can beregarded as a good approximation of anytypical ground grid, it can be concluded thatat a sufficient distance the field of a stationground can be represented by the field of anequivalent hemisphere, the radius of whichis equal to one half of the average radiusof the grid.
In reference 5 an equation is given tocalculate the error caused by insufficientprobe distances for a hemispherical electrode.The correction factor K 1 used in this paperwas derived from this equation.
as shown in Fig. l(A). The field of therings (curve 1) is plotted according to equation 16, whereas the field of the hemisphere (curve 2) is plotted according to thefollowing equation:
(20)
(19)
(18)
(16)P2:4 2rn (2vrnx)V(x)=- in--K--1r rn+x rn+x
n=l
pIV(J=-
3.15r4
pIVh=
21rr
Obviously, if Vg = Vh, then r ~r4/2Hence, a hemisphere with a radius equal toone half of the radius of a grid, consistingof four concentric rings, has approximatelythe same ground resistance as the grid.The two potential fields are also very similar
Appendix I. Potential Fields ofConcentric Rings and of an
Equivalent Hemisphere
Similar equations can be written for Veri)V(r2), and Vera). All four potentials mustbe equal to Vg • the potential of the groundgrid, whereas the sum of the currents, dissipated from the rings, must be equal tothe total ground fault current I.
where p is in ohm-meters and r4is in meters.On the other hand, the potential (Vh) of ahemispherical electrode with a radius equa1to r can be expressed as follows:
[2:' '. a-, (2V rnx) . 8rn. ]1-n -- K --- +1-4 In --===
rn+x rn+x Vd.hn=l
(1'7)
A. ground grid is assumed to be composedof four concentric rings, the spacing of whichis determined so as to obtain a constantdensity of conductor material. 4 The relative dimensions chosen for the example areshown in Fig. I(B). Deviations from thechosen proportions within practical limitswould, however, not affect the results appreciably.
According to reference 4, the potentialVex) in volts at a distance x from the centerof the grid can be expressed with good approximation as
This results in five unknowns and fiveequations, from which i I .... . i4 and Vgcan be determined. After substituting thedimensions shown in Fig. I( B) the followingexpression is obtained for the potential ofthe ground grid:
where p is the soil resistivity in ohm-meters,in is the current dissipated per-unit lengthfrom ring "n' in amperes per meter, and r« isthe radius of ring "n:" K(k) is the completeelliptic integral of the first kind of a variablek.
The potential of the ground grid itselfcan be expressed, for example, by expressingthe potential V(r4) on the surface of ring4.
is more convenient either not to performtests at all, or if these are believed to benecessary, to measure touch voltagesdirectly. Locations where high touchvoltages can be suspected are the following:
1. The periphery of the station groundgrid, especially at the corners.
2. Exposed metal parts which arerelatively far from buried ground busses.
3. Isolated structures far from denselybuilt-up parts of the station, but electrically connected to the ground grid (suchas nearby transmission towers, railwaytracks, fire hydrants, etc.).
The method of potential gradient(touch voltage) measurements is essentially the same as that of ground resistance measurements with the voltmeterammeter method. A current is circulatedbetween the station ground and a remoteprobe. The touch voltage is then measured at various locations by connecting avoltmeter between a structure and a smallpotential probe at a distance of approximately 3 feet from the structure. Sincethe probe must be small, its resistance willbe high. It is expedient, therefore, to usea vacuum tube voltmeter. Measurements with an earth tester may lead tolarge errors, due both to reactive components in the ground impedance and tothe low internal resistance of the instrument as compared with the probe resistance. The requirements of the currentprobe are the same as before.
The measurements may be performedin a similar way as the ground resistancemeasurements described before. Equations 3 and 4 can be used without change,except that E t should be interpreted astouch voltage.
To find the potential difference betweenthe station ground and communicationcircuits, direct measurements can be performed in the same way as for touch voltages. The voltmeter should be connectedbetween the station ground and the telephone wire, the remote end of which isgrounded (usually in an exchange or inanother station). It is convenient to dothe measurement on the same circuit forwhich protection is required. Whereneutralizing or insulating transformers areconsidered, the voltmeter can be insertedin the circuit at the same location wherethe transformer is to be installed.
Regarding the protection of communication circuits, it is practical to estimatein advance the maximum possible savingwhich could be expected from a test.Sometimes, the incremental cost of anover-conservative design may be lesscostly than the test itself; in such cases.it may be more economical not to per-
NOVEMBER 1962 Elek-s-Prooing the Adequacy of Station Grounds 375
tions for a 3-phase power supply (equations 8, 9, and 10) can be proved in a similarmanner.
References
1. PROPOSED RECOMMENDED GUIDE FOR MEASURING GROUND RESISTANCE AND POTENTIAL GRADIENTS IN THE EARTH. AIEE Special PublicationNo. 81, July, 1960.
2. WAVE PROPAGATION IN OVERHEAD WIRES WITHGROUND RETURN, J. R. Carson. Bell System Technical Journal, vol. 5, Oct. 1926, pp. 539-55.
3. VOLTAGE GRADIENTS THROUGH THE GROUNDUNDER FAULT CONDITIONS, AlEE Committee Report. AlEE Transactions, pt. III (Power Apparatus and Systems), vol. 78, Oct. 1958, pp. 669-85.
4. EFFICIENCY OF GROUNDING GRIDS WITHNONUNIFORM SOIL, J. Zaborszky. Ibid., vol. 75,Dec. 1955, pp. 1230-33.
5. SOME OF 1 HE FUNDAMENTAL ASPECTS OFGROUND RESISTANCE MEASUREMENTS, E. B. Curdts.Ibid., pt. I (Communication and Electronics), vol.77, Nov. 1958, pp. 760-66.
-----+----
Discussion
C. A. Duke (Tennessee Valley Authority,Chattanooga, Tenn.): The author hasprovided a well-written paper on a timely
subject, which is assuming importance asground fault currents reach higher andhigher values.
We thoroughly agree with all the statements in the paper except those on instrumentation. Particularly close agreement isemphasized on the points of the ultimatepurpose of determining potentials that mayexist and of the ground impedance's havingan appreciable reactive component.
We do differ on some points of instrumentation but not on theory. We havebeen particularly interested in makingmeasurements! on large station groundswhere the author states that it is "eithernot possible or not worthwhile to measurethe ground resistance of the station."Our experience has been that there is neveran impossible case of measurement. Also,we have found that the impedance of astation ground cannot always be predictedand should be measured by a practicalmethod which gives the information whichthis author shows is of great importance.
REFERENCE
1. THE TECHNIQUE AND INSTRUMENTATION OFLow-IMPEDANCE GROUND MEASUREMENT, C. A.Duke, L. E. Smith. AlEE Transactions, pt I.(Communication and Electronics) vol. 77, Nov.1958, pp. 767-70.
A. Elek: I agree with Mr. Duke that thereis never an impossible case of measurement, provided that the quantity to bemeasured is well-defined. Thus, for ex-
ample, the current driven through thestation ground during a test and the potential difference between the station groundand a zero-potential reference point arewell-defined and can be measured. Thedifficulty arises when one attempts toderive a single figure from these, call it"ground resistance," and to use this figure todecide whether the station ground is adequate or not. Considering, for example, astation within the limits of a city, interconnected with several other stations inclose vicinity through a maze of underground cables, waterpipes, etc., the testresults will vary to a large extent with thereturn path of the test current and withthe direction of the zero-potential referencepoint, even if both auxiliary electrodes areremote. In such case no single value ofground resistance can be established.
What I really wished to emphasize inthe paper was the fact that since it is thepotential difference between the stationground and certain reference points inwhich we are normally interested, there isno reason to increase our difficulties by introducing such a vaguely defined additionalquantity as the ground resistance, whichhas to be derived from the measurementof a potential difference only to be used todetermine another potential difference.In the example mentioned, it is much simplerto measure the potential differences inquestion directly and not to attempt toattach any single value of ground resistanceto the station.
376 Elek-Proving the Adequacy of Station Grounds NOVEMBER 1962