CUSTOM PROCESS EQUIPMENT4727 NW Evangeline Thrwy
Carencro, La 70520Phone: 337.896.3815 / Fax: 337.896.3816
PSV DATA SHEETS
Customer Name: McMORAN/AUDUBON ENGINEERING
Project Title: AMINE PLANT
CPE JOB #: 11043
DOCUMENT # 11043-DS-1304
Issue Record
A 2-Aug-11 FOR APPROVAL MJH
Rev Date Issue By Checked Approved
DOC. TYPE YEAR JOB I.D. # Revision Revision Date
Data Sheet - 2011 - 11043 - 1304 A 2-Aug-11
Document Title: PSV DATA SHEET
VENDOR DOCUMENT REVIEW
F A R I
SIGNATURE:
DATE:
CODE F - Final (Accepted). Work may proceed.
CODE A -
CODE R - Rejected. Fully incorporate comments and resubmit documents as required. Work may not proceed.
CODE I - Accepted for information only.
IMPORTANT
Purchaser’s review of Vendor’s documents does not relieve Vendor of the responsibility for correctness under the Purchase Order. Permission to proceed does not constitute acceptance of design, detail and calculations, test methods or materials developed or selected by the Vendor and does not relieve the Vendor from full compliance with the Purchase Order or any other obligations, nor detract from any of the Purchaser’s rights.
Qualified Release. Revise and re-submit, but work may proceed subject to the incorporation of Purchaser comments.
Should the Vendor consider that any comments made by the Purchaser change the Scope of Supply, the Vendor shall advise the price and delivery implications of such changes within five working days of receipt. The Vendor must not incorporate such changes without prior approval of the Purchaser of the revised price and/or delivery period. RETROSPECTIVE CLAIMS WILL NOT BE CONSIDERED.
PRESSURE RELIEF Sht: 1 of 5
VALVES DOCUMENT:
REV BY APPR DATE REVISION 1304
A MJH 8/2/2011 FOR APPROVAL PROJECT:
11043
P.R.:
P.O.:
1
GE
NE
RA
L
Tag Number PSV - 0041 PSV-0061
2 ServiceAMINE CONTATOR
3 Line No./ Vessel No. MAK-1004 MAF-1006
4 Full Nozzle/ Semi Nozzle Semi Semi
5 Safety or Relief Safety Relief Safety Relief
6 Conv., Bellows, Pilot Op. Conventional Conventional
7 Bonnet Type Closed Closed
8
CO
NN
. Size: Inlet Outlet 4" 6" 2" 3"
9 Flange Rating or Screwed 600# 300# 600# 300#
10 Type of Facing RF RF RF RF
11
MA
TE
RIA
LS
Body and Bonnet NACE CARBON STEEL NACE CARBON STEEL
12 Seat and Disc VTA VTA
13 Resilient Seat Seal VTA VTA
14 Guide and Rings VTA VTA
15 Spring VTA VTA
16 Bellows VTA VTA
17
18
OP
TIO
NS
Cap: Screwed or Bolted VTA VTA
19 Lever: Plain or Packed None None
20 Test Gag No No
21
22
23
24
BA
SIS
Code ASME VIII ASME VIII
25 Fire NO YES
26
27
28
FL
UID
DA
TA
Fluid and State GAS/VAPOR GAS/VAPOR
29 Required Capacity 150 MMSCFD 582.201 Ibs/hr
30 Mol. Wt. Oper. sp. gr. 19.363 32.073
31 Oper Press Set Press. 1200 1350 1200 1350
32 Oper. Temp. Rel. Temp. 200 160 200
33 Constant PSIG 0 psi-g 0 psi-g
34 Variable PSIG 0 psi-g 0 psi-g
35 Total PSIG 150 psi-g 150 psi-g
36 % Allowable Overpressure 21 21
37 Overpressure Factor 1.0 1.0
38 Compressibility Factor .872 .0855
39 Latent Heat of Vaporization btu IT/ib btu IT/ib
40 Ratio of Specific Heats
41 Operating Viscosity
42 Barometric Pressure 14.696 psia 14.696 psia
43
44
45 Calc. Area sq. in. 3.4541 sq. in.
46 Selected Area 4.340 sq. in.
47 Orifice Designation N D
48 Manufacturer Anderson Greenwood Anderson Greenwood
49 Model No. 44312P46/S 44312J23X/SPL
NO
TE
S
1 ALL VALVES TO BE IN ACCORDANCE WIT H NACE MR-0175
2
3
4
5
6
7 * Information supplied by manufacturer unless already specified
FORM: V04 Rev C
TAG: PSV
HP GAS COALESCING FILTER SEPERATOR
120 oF
Back Pressure
0.0015 in2
.110 in2
Revisions shown in RED BOLD.
PRESSURE RELIEF Sht: 2 of 5
VALVES DOCUMENT:
REV BY APPR DATE REVISION 1304
A MJH 8/2/2011 FOR APPROVAL PROJECT:
11043
P.R.:
P.O.:
1
GE
NE
RA
L
Tag Number PSV-0101 PSV-0111 PSV-0112 PSV-0081
2 ServiceHOLD
3 Line No./ Vessel No. MAJ-1010 MAJ-1011 MAJ-1012 MBD-1008
4 Full Nozzle/ Semi Nozzle Semi Semi Semi Semi
5 Safety or Relief Safety Relief Safety Relief Safety Relief Safety Relief
6 Conv., Bellows, Pilot Op. Conventional Conventional Conventional Conventional
7 Bonnet Type Closed Closed Closed Closed
8
CO
NN
. Size: Inlet Outlet 1" 1" 1" 1" 1" 1"
9 Flange Rating or Screwed 150# 150# 150# 150# 150# 150#
10 Type of Facing RF RF RF RF RF RF
11
MA
TE
RIA
LS
Body and Bonnet Nace Carbon Steel Nace Carbon Steel Nace Carbon Steel Nace Carbon Steel
12 Seat and Disc VTA VTA VTA VTA
13 Resilient Seat Seal VTA VTA VTA VTA
14 Guide and Rings VTA VTA VTA VTA
15 Spring VTA VTA VTA VTA
16 Bellows VTA VTA VTA VTA
17
18
OP
TIO
NS
Cap: Screwed or Bolted VTA VTA VTA VTA
19 Lever: Plain or Packed None None None None
20 Test Gag No No No No
21
22
23
24
BA
SIS
Code ASME VIII ASME VIII ASME VIII ASME VIII
25 Fire
26
27
28
FL
UID
DA
TA
Fluid and State Gas/Vapor Gas/Vapor Gas/Vapor
29 Required Capacity lb/hr 30.485 70.978 9.681
30 Mol. Wt. Oper. sp. gr. 31.411 31.411 31.41
31 Oper Press Set Press. 60 PSIG 150 PSIG 60 PSIG 150 PSIG 60 PSIG 150 PSIG PSIG PSIG
32 Oper. Temp. Rel. Temp. 177 250 177 220 170 200
33 Constant PSIG 0 psi-g 0 psi-g 0 psi-g 0 psi-g
34 Variable PSIG 0 psi-g 0 psi-g 0 psi-g 0 psi-g
35 Total PSIG 15 psi-g 15 psi-g 15 psi-g psi-g
36 % Allowable Overpressure 21 21 21 21
37 Overpressure Factor 1.0 1.0 1.0 1.0
38 Compressibility Factor .0055 .00545 .0055
39 Latent Heat of Vaporization btu IT/ib btu IT/ib btu IT/ib btu IT/ib
40 Ratio of Specific Heats
41 Operating Viscosity
42 Barometric Pressure 14.696 psia 14.696 psia 14.696 psia 14.696 psia
43
44
45 Calc. Area sq. in. .0004
46 Selected Area .110
47 Orifice Designation D D D
48 Manufacturer Anderson Greenwood Anderson Greenwood Anderson Greenwood Anderson Greenwood
49 Model No. 45305D12/S1 45305D12/S1 45305D12/S1
NO
TE
S
1 ALL VALVES TO BE IN ACCORDANCE WIT H NACE MR-0175
2
3
4
5
6
7 * Information supplied by manufacturer unless already specified
FORM: V04 Rev C
TAG: PSV
LEAN AMINE PRE-FITLER
LEAN AMINE CARBON FILTER
LEAN AMINE POLISH FILTER
AMINE FLASH VESSEL
°F 656.8 oF
Back Pressure
.0002 in2 .0001 in2 in2
..110 in2 .110 in2 in2
Revisions shown in RED BOLD.
PRESSURE RELIEF Sht: 3 of 5
VALVES DOCUMENT:
REV BY APPR DATE REVISION 1304
A MJH 8/2/2011 FOR APPROVAL PROJECT:
11043
P.R.:
P.O.:
1
GE
NE
RA
L
Tag Number PSV-7055 PSV-7053 PSV-0113 PSV-7052
2 ServiceLean Amine Cooler
3 Line No./ Vessel No. HAL-0705 HAL-0706 HAL-0704 HAL-0706
4 Full Nozzle/ Semi Nozzle Semi Semi Semi Semi
5 Safety or Relief Safety Relief Safety Relief Safety Relief Safety Relief
6 Conv., Bellows, Pilot Op. Conventional Conventional Conventional Conventional
7 Bonnet Type Closed Closed Closed Closed
8
CO
NN
. Size: Inlet Outlet
9 Flange Rating or Screwed
10 Type of Facing
11
MA
TE
RIA
LS
Body and Bonnet Nace Carbon Steel Nace Carbon Steel Nace Carbon Steel Nace Carbon Steel
12 Seat and Disc VTA VTA VTA VTA
13 Resilient Seat Seal VTA VTA VTA VTA
14 Guide and Rings VTA VTA VTA VTA
15 Spring VTA VTA VTA VTA
16 Bellows VTA VTA VTA VTA
17
18
OP
TIO
NS
Cap: Screwed or Bolted VTA VTA VTA VTA
19 Lever: Plain or Packed None None None None
20 Test Gag No No No No
21
22
23
24
BA
SIS
Code ASME VIII ASME VIII ASME VIII ASME VIII
25 Fire
26
27
28
FL
UID
DA
TA
Fluid and State Gas/Vapor Gas/Vapor Gas/Vapor Gas/Vapor
29 Required Capacity Ib/hr 23402.83 23402.83 47321.392 23402.83
30 Mol. Wt. Oper. sp. gr. 31.779 31.779 31.312 31.779
31 Oper Press Set Press. 51 150 51 150 45 150 51 150
32 Oper. Temp. Rel. Temp. 210 300 210 300 177 200 210 300
33 Constant PSIG 0 psi-g 0 psi-g 0 psi-g 0 psi-g
34 Variable PSIG 0 psi-g 0 psi-g 0 psi-g 0 psi-g
35 Total PSIG 15 psi-g 15 psi-g 15 psi-g 15 psi-g
36 % Allowable Overpressure 21 21 21 21
37 Overpressure Factor 1.0 1.0 1.0 1.0
38 Compressibility Factor .0045 .0045 .0044 .0045
39 Latent Heat of Vaporization btu IT/ib btu IT/ib btu IT/ib btu IT/ib
40 Ratio of Specific Heats
41 Operating Viscosity
42 Barometric Pressure 14.696 psia 14.696 psia 14.696 psia 14.696
43
44
45 Calc. Area sq. in. .1221 .1221 .2281 .1221
46 Selected Area .196 .196 .307 .196
47 Orifice Designation E E F E
48 Manufacturer Anderson Greenwood Anderson Greenwood Anderson Greenwood Anderson Greenwood
49 Model No.
NO
TE
S
1 ALL VALVES TO BE IN ACCORDANCE WIT H NACE MR-0175
2
3
4
5
6
7 * Information supplied by manufacturer unless already specified
FORM: V04 Rev C
TAG: PSV
Amine/Amine Exchangers
Amine/Amine Exchangers
Amine/Amine Exchanger
Back Pressure
Revisions shown in RED BOLD.
PRESSURE RELIEF Sht: 4 of 5
VALVES DOCUMENT:
REV BY APPR DATE REVISION 1304
A MJH 8/2/2011 FOR APPROVAL PROJECT:
11043
P.R.:
P.O.:
1
GE
NE
RA
L
Tag Number PSV-7051 PSV-7052
2 Service
3 Line No./ Vessel No. MBA-1013 HAL-0706
4 Full Nozzle/ Semi Nozzle Semi Semi
5 Safety or Relief Safety Relief Safety Relief
6 Conv., Bellows, Pilot Op. Conventional Conventional
7 Bonnet Type Closed Closed
8
CO
NN
. Size: Inlet Outlet 1" 2"
9 Flange Rating or Screwed 150# 150#
10 Type of Facing RF RF
11
MA
TE
RIA
LS
Body and Bonnet Nace Carbon Steel Nace Carbon Steel
12 Seat and Disc VTA VTA
13 Resilient Seat Seal VTA VTA
14 Guide and Rings VTA VTA
15 Spring VTA VTA
16 Bellows VTA VTA
17
18
OP
TIO
NS
Cap: Screwed or Bolted VTA VTA
19 Lever: Plain or Packed None None
20 Test Gag No No
21
22
23
24
BA
SIS
Code ASME VIII ASME VIII
25 Fire No
26
27
28
FL
UID
DA
TA
Fluid and State Gas/Vapor Gas/Vapor
29 Required Capacity lb/hr 291.921 23402.83
30 Mol. Wt. Oper. sp. gr. 29.480 31.779
31 Oper Press Set Press. 16 PSIG 150 PSIG 51 150
32 Oper. Temp. Rel. Temp. 260 300 210 300
33 Constant PSIG 0 psi-g 0 psi-g
34 Variable PSIG 0 psi-g 0 psi-g
35 Total PSIG 15 psi-g 15 psi-g
36 % Allowable Overpressure 21 21
37 Overpressure Factor 1.0 1.0
38 Compressibility Factor .0019 .0045
39 Latent Heat of Vaporization btu IT/ib btu IT/ib
40 Ratio of Specific Heats
41 Operating Viscosity
42 Barometric Pressure 14.696 psia 14.696
43
44
45 Calc. Area sq. in. .0010 .1221
46 Selected Area .110 .196
47 Orifice Designation D E
48 Manufacturer Anderson Greenwood Anderson Greenwood
49 Model No. 453_D____/NACE
NO
TE
S
1 ALL VALVES TO BE IN ACCORDANCE WIT H NACE MR-0175
2
3
4
5
6
7 * Information supplied by manufacturer unless already specified
FORM: V04 Rev C
TAG: PSV
AMINE STILL COLUMN
Amine/Amine Exchanger
Back Pressure
Revisions shown in RED BOLD.
PRESSURE RELIEF Sht: 5 of 5
VALVES DOCUMENT:
REV BY APPR DATE REVISION 1304
A MJH 8/2/2011 FOR APPROVAL PROJECT:
11043
P.R.:
P.O.:
1
GE
NE
RA
L
Tag Number PSV-2441 PSV-2451 PSV-2461
2 ServiceAmine Circulation Pump
3 Line No./ Vessel No. PBA-1244 PBA-1245 PBA-1246
4 Full Nozzle/ Semi Nozzle Semi Semi Semi
5 Safety or Relief Safety Relief Safety Relief Safety Relief
6 Conv., Bellows, Pilot Op. Conventional Conventional Conventional
7 Bonnet Type Closed Closed Closed
8
CO
NN
. Size: Inlet Outlet 1.5" 2" 1.5" 2" 1.5" 2"
9 Flange Rating or Screwed 600# 300# 600# 300# 600# 300#
10 Type of Facing RF RF RF RF RF RF
11
MA
TE
RIA
LS
Body and Bonnet Nace Carbon Steel Nace Carbon Steel Nace Carbon Steel
12 Seat and Disc VTA VTA VTA
13 Resilient Seat Seal VTA VTA VTA
14 Guide and Rings VTA VTA VTA
15 Spring VTA VTA VTA
16 Bellows VTA VTA VTA
17
18
OP
TIO
NS
Cap: Screwed or Bolted Bolted Bolted Bolted
19 Lever: Plain or Packed None None None
20 Test Gag No No No
21
22
23
24
BA
SIS
Code ASME VIII ASME VIII ASME VIII
25 Fire YES YES YES
26
27
28
FL
UID
DA
TA
Fluid and State Amine Amine Amine
29 Required Capacity GPM 469.707 180360.1916 180360.1916
30 Mol. Wt. Oper. sp. gr. 1.0296 1.0296 1.0296
31 Oper Press Set Press. 1200 1350 1200 1350 1350 1485
32 Oper. Temp. Rel. Temp. 124 200
33 Constant PSIG 0 psi-g 0 psi-g 0 psi-g
34 Variable PSIG 0 psi-g 0 psi-g 0 psi-g
35 Total PSIG 20 psi-g 20 psi-g 20 psi-g
36 % Allowable Overpressure 10% 10% 10%
37 Overpressure Factor 1.0 1.0 1.0
38 Compressibility Factor
39 Latent Heat of Vaporization btu IT/ib btu IT/ib btu IT/ib
40 Ratio of Specific Heats
41 Operating Viscosity 3.1020
42 Barometric Pressure 14.696 psia 14.696 psia 14.696 psia
43
44
45 Calc. Area sq. in.
46 Selected Area
47 Orifice Designation G G G
48 Manufacturer Anderson Greenwood Anderson Greenwood Anderson Greenwood
49 Model No.
NO
TE
S
1 ALL VALVES TO BE IN ACCORDANCE WIT H NACE MR-0175
2
3
4
5
6
7 * Information supplied by manufacturer unless already specified
FORM: V04 Rev C
TAG: PSV
Amine Circulation Pump
Amine Circulation Pump
Back Pressure
.375 in² .375 in² .375 in²
.503 in2 .503 in3 .503 in4
Revisions shown in RED BOLD.
PRESSURE RELIEF Sht: 5 of 5
VALVES DOCUMENT:
REV BY APPR DATE REVISION 1304
A MJH 8/2/2011 FOR APPROVAL PROJECT:
11043
P.R.:
P.O.:
1
GE
NE
RA
L
Tag Number PSV-0071 PSV-0141 PSV-1301 PSV-0150
2 Service
3 Line No./ Vessel No. MBF-1007 MBD-1014 MBJ-0130 MBJ-0130
4 Full Nozzle/ Semi Nozzle Semi Semi Semi Semi
5 Safety or Relief Safety Relief Safety Relief Safety Relief Safety Relief
6 Conv., Bellows, Pilot Op. Conventional Conventional Conventional Conventional
7 Bonnet Type Closed Closed Closed Closed
8
CO
NN
. Size: Inlet Outlet 6" 8" 6" 8" 4" 6" 1" 1"
9 Flange Rating or Screwed 600# 300# 150# 150# 150# 150#
10 Type of Facing RF RF RF RF RF RF Threaded Threaded
11
MA
TE
RIA
LS
Body and Bonnet Nace Carbon Steel Nace Carbon Steel Nace Carbon Steel Nace Carbon Steel
12 Seat and Disc VTA VTA VTA VTA
13 Resilient Seat Seal VTA VTA VTA VTA
14 Guide and Rings VTA VTA VTA VTA
15 Spring VTA VTA VTA VTA
16 Bellows VTA VTA VTA VTA
17
18
OP
TIO
NS
Cap: Screwed or Bolted Bolted Bolted Bolted Bolted
19 Lever: Plain or Packed None None None None
20 Test Gag No No No No
21
22
23
24
BA
SIS
Code ASME VIII ASME VIII ASME VIII ASME VIII
25 Fire YES YES YES YES
26
27
28
FL
UID
DA
TA
Fluid and State GAS/VAPOR GAS/VAPOR Gas/Vapor Gas/Vapor
29 Required Capacity lbs/hr 193.406 703.591 388.553 1441.566
30 Mol. Wt. Oper. sp. gr. 18.266 18.03 320.0 152.250
31 Oper Press Set Press. 1195 1350 13.0 150 50 150 55 150
32 Oper. Temp. Rel. Temp. 155 200 205 300 430 650 105 200
33 Constant PSIG 0 psi-g 0 psi-g 0 psi-g 0 psi-g
34 Variable PSIG 0 psi-g 0 psi-g 0 psi-g 0 psi-g
35 Total PSIG 150 psi-g 15 psi-g 15 psi-g 15 psi-g
36 % Allowable Overpressure 21% 21% 21% 21%
37 Overpressure Factor 1.0 1.0 1.0 1.0
38 Compressibility Factor .0524 .0012 .0171 .0742
39 Latent Heat of Vaporization btu IT/ib btu IT/ib btu IT/ib btu IT/ib
40 Ratio of Specific Heats
41 Operating Viscosity
42 Barometric Pressure 14.696 psia 14.696 psia 14.696 psia 14.696 psia
43
44
45 Calc. Area sq. in. .0005 .0024 .0016 .0134
46 Selected Area .110 .110 .110 .110
47 Orifice Designation D D D D
48 Manufacturer Anderson Greenwood Anderson Greenwood Anderson Greenwood Anderson Greenwood
49 Model No. 44305R68 44305R68_/NACE 44305R68 44305R69
NO
TE
S
1 ALL VALVES TO BE IN ACCORDANCE WIT H NACE MR-0175
2
3
4
5
6
7 * Information supplied by manufacturer unless already specified
FORM: V04 Rev C
TAG: PSV
AFTERCOOLER SCRUBBER
REFLUX ACCUMULATOR
Hot Oil Expansion Tank
Fired Heater Fuel Gas Scrubber
Back Pressure
Revisions shown in RED BOLD.
VENDOR DAT REQUIREMENTS
Project No:11043 Date: 8/2/2011
Bid Package:Control Valves
Instructions to Vendors:
Item Description
Quantity and Type of DocumentAfter Receipt of PO
For Review Revised For File1 Completed data sheets 1 P + E 1 P + E
2
3 Outline dimensioned drawings 1 P + E 1 P + E4 Equipment weights 1 P + E 1 P + E5 Sizing calculations 1 P + E 1 P + E6 Wiring diagrams7 Schematic piping/tubing diagrams8 Canadian Registration Number (CRN)
9 1 P + E 4 P + E10 Priced spare parts lists 1 P + E 1 P + E
11 1 P + E 1 P + E 1 P + E12 Factory calibration test results 1 P + E 1 P + E 1 P + E13 Welding procedures14 Welder qualifications and certificates15 Hydrostatic test procedures 1 P + E 1 P + E 1 P + E16 Quality Control reports 1 P + E 1 P + E 1 P + E17 Configuration details18 Control system narrative1920
Document type codes:P = Printed material, suitable for photo-copier, either 8 1/2" x 11" or 11" x 17"R = Reproducible material on Mylar, suitable for blue-print machineE = Electronic file, Adobe pdf, AutoCAD 2004; MS Office; CD-ROM etc.
1. Vendor data required with quotation must be included with the quotation and addressed to the originator of the request for quotation.
2. Vendor data required after receipt of order shall reference the P.O. number and Instrument Tag number(s) and be transmitted to: Ali Malek P.Eng. (Address above).
3. "For Review" means that PTIL reserve the right to review the design for general compliance with the specifications and other contract documents prior to acceptance. In doing so, no responsibility is assumed by PTIL for the correctness of quantities, dimensions or performance.
4. Documents required "For Review" shall be received by PTIL no later that 2 weeks after receipt of a purchase order. PTIL will return "Reviewed" documents within two weeks after their receipt.
With Quotation
Manufacturers technical specifications including all "buy-out" items.
Installation, Operation & Maintenance Manuals
Bill of materials (outside purchase items)