37
Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] 1.1.1* The AHJ is permitted to accept lesser or partial requirements of this standard. Statement of Problem and Substantiation for Public Input This is proposed because not all sections of this standard are intended to apply to every construction or alteration project. For example it may not be reasonable to expect a complete Fire Safety Program, including an on-site fire brigade or a pre-fire plan with the local fire department for a minor project, such as adding a light fixture. However, some sections would be applicable to all projects, such as a first aid kit (7.7.6) or good housekeeping (7.1.2-1). This proposed exception allows the AHJ to make the determination on the applicability of the provisions of this standard. Note that this Public Input is related to the addition of A.1.1.1. Related Public Inputs for This Document Related Input Relationship Public Input No. 32-NFPA 241-2015 [New Section after A.1.1] Submitter Information Verification Submitter Full Name: Jim Muir Organization: Building Safety Division, Clark County, WA Affilliation: NFPAs Building Code Development Committee (BCDC) Street Address: City: State: Zip: Submittal Date: Tue Nov 24 20:04:53 EST 2015 Committee Statement Resolution: FR-2-NFPA 241-2016 Statement: The committee agrees with the concept but changed some wording for consistent style and structure and moved the insertion. National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 37 4/26/2016 9:21 AM

Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ]

1.1.1*

The AHJ is permitted to accept lesser or partial requirements of this standard.

Statement of Problem and Substantiation for Public Input

This is proposed because not all sections of this standard are intended to apply to every construction or alteration project. For example it may not be reasonable to expect a complete Fire Safety Program, including an on-site fire brigade or a pre-fire plan with the local fire department for a minor project, such as adding a light fixture. However, some sections would be applicable to all projects, such as a first aid kit (7.7.6) or good housekeeping (7.1.2-1). This proposed exception allows the AHJ to make the determination on the applicability of the provisions of this standard. Note that this Public Input is related to the addition of A.1.1.1.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 32-NFPA 241-2015 [New Section after A.1.1]

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 24 20:04:53 EST 2015

Committee Statement

Resolution: FR-2-NFPA 241-2016

Statement: The committee agrees with the concept but changed some wording for consistent style and structureand moved the insertion.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 37 4/26/2016 9:21 AM

Page 2: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 9-NFPA 241-2015 [ Section No. 5.1.3.2 ]

5.1.3.2

A fire watch in accordance with NFPA 1 shall be posted for the duration of the work and for 2 hoursthereafter for torch-applied roofing operations (see 9.3.9).

Statement of Problem and Substantiation for Public Input

This suggested revision will provide requirements for a fire watch to follow the provisions for a fire watch as set forth in NFPA 1, section 41.2.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:04:18 EST 2015

Committee Statement

Resolution: NFPA 1 extracts from NFPA 241 and therefore this creates a circular reference and provides noadded information or clarity.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 37 4/26/2016 9:21 AM

Page 3: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 10-NFPA 241-2015 [ Section No. 5.2.5 ]

5.2.5

Temporary heating equipment shall be situated placed and used in such a manner so that it is securedagainst overturning or displacement so as to create a hazard .

Statement of Problem and Substantiation for Public Input

The new wording more directly addresses the two principal concerns of such heating equipment whether at rest or in use.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:07:38 EST 2015

Committee Statement

Resolution: FR-3-NFPA 241-2016

Statement: The committee agrees with the concept that the new wording more directly addresses the twoprincipal concerns of such heating equipment whether at rest or in use, however it removed the lastsix words of the public input as being unnecessary.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 37 4/26/2016 9:21 AM

Page 4: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 11-NFPA 241-2015 [ Section No. 5.5.2.3 ]

5.5.2.3

Means shall be provided to contain and dispose of leakage and spills promptly and safely.

Statement of Problem and Substantiation for Public Input

This Public Input will help ensure the spill or leak is contained first and then disposed.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:10:29 EST 2015

Committee Statement

Resolution: FR-4-NFPA 241-2016

Statement: This change will help ensure the spill or leak is contained first and then disposed.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 37 4/26/2016 9:21 AM

Page 5: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ]

Disconnecting Means

6.1.1.4 During construction or demolition activities, all temporary and permanent service equipmentdisconnecting means shall be readily accessible to emergency service personnel and shall be labeled as toequipment controlled by such disconnects.

Statement of Problem and Substantiation for Public Input

NFPA 70, nor the current language in NFPA 241 addresses the accessibility or labeling of service disconnecting means during construction or demolition activities. During construction or demolition activities, the ability for emergency responders to quickly identify and disconnect power to a building is critical life safety, property preservation and firefighter safety. The NFPA 70 panel has previously indicated that issues such as accessibility for FD access are beyond the scope of NFPA 70. Therefore, the issue rests with the NFPA 241 TC.

Submitter Information Verification

Submitter Full Name: ANTHONY APFELBECK

Organization: ALTAMONTE SPRINGS BUILDING/FIRE SAFETY DIVISION

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 03 10:49:37 EDT 2015

Committee Statement

Resolution: FR-5-NFPA 241-2016

Statement: Neither NFPA 70, nor the current language in NFPA 241 addresses the accessibility or labeling ofservice disconnecting means during construction or demolition activities. During construction ordemolition activities, the ability for emergency responders to quickly identify and disconnect power toa building is critical life safety, property preservation and firefighter safety. The NFPA 70 panel haspreviously indicated that issues such as accessibility for FD access are beyond the scope of NFPA70. Therefore, the issue rests with the NFPA 241 TC.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 37 4/26/2016 9:21 AM

Page 6: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 2-NFPA 241-2015 [ Section No. 6.1.3.6 ]

6.1.3.6

Temporary wiring and lights shall be removed immediately upon the completion of the construction orpurpose for which the wiring was and lights were installed.

Statement of Problem and Substantiation for Public Input

Lighting should be included with the removal (of wiring) process to, aid in the prevention of live circuits being left behind. adding to the prevention of (possible) structural damage or personnel injury.

Submitter Information Verification

Submitter Full Name: ROBERT TRIBBIE

Organization: WEST VIRGINIA STATE FIRE MAR

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 20 18:46:11 EDT 2015

Committee Statement

Resolution: FR-6-NFPA 241-2016

Statement: Lighting should be included with the removal (of wiring) process to, aid in assuring that live circuitsare not left behind.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 37 4/26/2016 9:21 AM

Page 7: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 34-NFPA 241-2015 [ Section No. 7.2.5.1 ]

7.2.5.1*

Guard service shall be provided where required by the authority having jurisdiction. Residential buildingswith combustible construction more than 40 feet above grade plane shall be provided with 24 hour, 7-dayper week guard service.

Statement of Problem and Substantiation for Public Input

This proposal will address a gap in this standard that has arisen because of more permissible building codes that allow combustible construction as high as 7 stories. With the introduction of increased allowable heights and stories in building codes based on the installation of sprinklers and horizontal building separation allowances (podium construction), more and more buildings above the traditional 3 story limit for combustible construction are being built. These buildings pose a threat to adjacent properties and buildings on the same lot during construction that is not addressed in the codes or in this standard. In the past few years, a series of high profile buildings around North America have burned during construction. Many of the fires occurred after normal construction hours at unattended sites. In several of the major fires, adjacent buildings and other property have been damaged, and in almost all cases, the building under construction has been a total loss. Examples of documented fires include:

Project Name / Location: Lindell Avenue Apartments, St. Louis, MODate of Incidents: June 13, 2007 and July 18, 2012Project Description: 4 story, 197-unit, wood framed apartment building.Building Status: Completed and occupied.This same wood framed building was also the scene of a 2007 fire that caused $12 million in damage while construction was underway.

Project Name / Location: 21828 South Avalon Boulevard, Carson, CaliforniaDate of Incident: October 27, 2011Project Description: Three-story wood framed apartment building Building Status: Under constructionThe three-story apartment building caught fire on October 27, 2011 and quickly spread to a nearby mobile home park. More than 139 mobile homes were evacuated. At least 10 homes in the park were damaged by flames. The total damage estimate was $3.1 million, with $2.5 million for the senior living center and $600,000 for the mobile home park.

Project Name / Location: Monroe Apartments, Portland, ORDate of Incident: August 8, 2013Project Description: 46-unit, wood frame apartment buildingBuilding Status: Under constructionThe Monroe Apartments is one of a surge in mid-sized projects across the Portland area. Portland Fire & Rescue put the damage at $4 million.

Project Name / Location: Student Apartments, Kingston, Ontario, CANDate of Incident: December 17, 2013Project Description: The 144-unit student wood-framed apartment complex in Kingston, Ont., was 4,559 square metres (49,072 square feet). Building Status: Under constructionIn all, 10 stations and 113 Kingston firefighters were on scene with 27 apparatuses; 11 Kingston fire personnel helped in communications; 11 mutual-aid departments were called and brought 160 firefighters and 19 trucks.

Project Name / Location: 550 East and 500 South, Salt Lake City, UTDate of Incident: February 9, 2014Project Description: Four story, wood frame apartment complexBuilding Status: Under constructionThe building is a four-story apartment complex. The fire caused $2.5 million in damage.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 37 4/26/2016 9:21 AM

Page 8: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Project Name / Location: Mission Bay Project, San Francisco, CADate of Incident: March 11, 2014Project Description: The projects, supported by piles, consist of 4 and 5-story wood framed residential buildings over 2 levels of parking. The levels above the podium slabs are Type III and V. The 172 unit building was one half of the 360-unit Mission Bay Project.Building Status: Under constructionThe six-story, largely wood-frame building wouldn't have been permitted in California just a few years ago. Until 2008, buildings six stories or higher were required to have "noncombustible" exterior walls.

Project Name / Location: Axis Apartments, Houston, TX Date of Incident: March 25, 2014Project Description: 5 story, 396 unit wood-framed apartment building.Building Status: Under constructionThe inferno began as a 3-alarm fire at 12:30 p.m. but was upgraded to a 5-alarm in less than an hour. More than 400 HFD personnel responded.

Project Name / Location: Gables Upper Rock, Rockville, MDDate of Incident: April 1, 2014Project Description: The Type III 300 unit apartment complex was a five story project, with a two story cast in place parking structure and amenity deck, with three stories of apartment units built with wood framed walls, joists and roof. Building Status: Under constructionMore than 200 firefighters were called to the scene of a three-alarm fire. Montgomery County fire officials say the three-acre complex was 90 percent complete and expected to be finished in two to three weeks before this fire ripped through 150 units. The apartment complex is a total loss, an estimated $15-$20 million.

Project Name / Location: SE Tech Center Drive/Redwood Circle, Vancouver, WADate of Incident: June 19, 2014Project Description: A four-story apartment building, planned to include 90 units.Building Status: Under construction.About 40 firefighters from Vancouver and Klackamas responded to the fire, which was reported around 3:15 a.m. Natural gas helped fuel the flames until a utility crew shut off the line. Estimated dollar loss falls somewhere between $2.5 million and $3.5 million.

Project Name / Location: Victoria Commons, Kitchener, Ontario, CANDate of Incident: July 22, 2014Project Description: The Victoria Common development includes 958 units in a mixture of condominiums, townhomes and parkland. The complex is expected to be constructed in four phases over a decade. The fire was in the first phase of units and is three and four-story wood frame construction. Building Status: Under construction The fire started in the partially completed townhouse development, destroying two blocks of homes and damaging another. At least $5 million in damage was done by the blaze. Flames swept through the primarily wood frame structures in minutes before spreading. The block behind it was destroyed and partially collapsed.

Project Name / Location: Apollo Way, Madison, WIDate of Incident: August 8, 2014Project Description: The project is a four-story, 105-unit wood-frame apartment complex. Building Status: Under construction Authorities initially said the fire caused $3.5 million to $5 million in damage, but the insurer subsequently has estimated that damage is “upwards of $10 million.”

Project Name / Location: DaVinci Apartment Complex, Los Angeles, CADate of Incident: December 8, 2014Project Description: The 526-unit apartment building had 1.3 million square feet of floor space, with five stories of wood framing over two stories of concrete. Building Status: Under construction The seven-story apartment building was a complete loss after fire. More than 250 firefighters were dispatched to the scene. The collapse of scaffolding and the structure’s wooden frame forced the closure of northbound Harbor (110) Freeway to the northbound 101 Freeway until 10 a.m. Computers and cubicles melted in neighboring buildings. Hundreds of windows cracked. Intense heat damaged fiber-optic cables beneath a downtown freeway and melted one of the signs. There was $10 million in estimated losses and at least four nearby buildings were

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 37 4/26/2016 9:21 AM

Page 9: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

also damaged. The Lewis Brisbois, Bisgaard & Smith building at 221 N. Figueroa St., where the computers and cubicles melted, had significant damage on its 15 floors, with 300 windows blown out. Three floors were also damaged in the Los Angeles County Department of Health Services building at 313 N. Figueroa. LA Department of Water and Power staff identified at least 160 windows, mostly on the west side of the John Ferraro Building, that were cracked. Los Angeles Department of Building and Safety reported that windows blew out in the north tower of its department headquarters, and the heat and smoke triggered sprinklers that soaked carpets and desks.

Submitter Information Verification

Submitter FullName:

Mark Nowak

Organization: M Nowak Consulting LLC

Affilliation:I represent multiple clients who produce cold-formed steel productsincluding the Steel Framing Alliance and Steel Framing IndustryAssociation.

Street Address:

City:

State:

Zip:

Submittal Date: Tue Dec 22 21:11:40 EST 2015

Committee Statement

Resolution: FR-7-NFPA 241-2016

Statement: The committee agrees with the concept but has modified the wording. This proposal will address agap in this standard that has arisen to changes in building codes allowing combustible construction ashigh as 7 stories. These buildings pose a threat to adjacent properties and buildings on the same lotduring construction that needs to be addressed in this standard. The committee is also forming a taskgroup to look more closely at the language to see if additional changes in language are needed andreport back at the public comment stage.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 37 4/26/2016 9:21 AM

Page 10: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 12-NFPA 241-2015 [ Section No. 7.6 ]

7.6 Standpipes.

In all new buildings in which standpipes are required or where standpipes exist in buildings being altered ordemolished, such standpipes shall be maintained in conformity with the progress of building construction insuch a manner that they are always ready for use. For buildings under construction standpipes shallcomply with section 8.7.4. For buildings under demolition standpipes shall comply with section 10.8.4.

Statement of Problem and Substantiation for Public Input

This addition provides a reference to provisions for standpipes.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:13:08 EST 2015

Committee Statement

Resolution: The committee concludes that this language is redundant and does not add any clarity.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 37 4/26/2016 9:21 AM

Page 11: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 13-NFPA 241-2015 [ Section No. 7.7.4 ]

7.7.4

At least one approved fire extinguisher also shall be provided in plain sight on each floor at each usablestairway as soon as combustible material accumulates is present .

Statement of Problem and Substantiation for Public Input

As written, the use of the word “accumulates” implies it is protecting against rubbish. This is intended to include all combustible construction materials that may be present. Usually construction materials aren't considered to "accumulate."

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 19-NFPA 241-2015 [Section No. 8.7.2.1]

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:14:57 EST 2015

Committee Statement

Resolution: FR-8-NFPA 241-2016

Statement: The committee agrees with the concept but added the word "significant" to clarify that this is notintended to mean that just a discarded coffee cup would trigger this requirement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 37 4/26/2016 9:21 AM

Page 12: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 33-NFPA 241-2015 [ New Section after 7.8 ]

Protection of adjacent property and buildings.

Residential buildings with combustible construction that is 40 feet or more in height above grade plane shallbe separated a minimum of 60 feet from adjacent buildings on the same site and a minimum of 60 feet fromproperty lines to protect adjacent property.

Statement of Problem and Substantiation for Public Input

This proposal will address a gap in this standard that has arisen because of more permissible building codes that allow combustible construction as high as 7 stories. With the introduction of increased allowable heights and stories in building codes based on the installation of sprinklers and horizontal building separation allowances (podium construction), more and more buildings above the traditional 3 story limit for combustible construction are being built. These buildings pose a threat to adjacent properties and buildings on the same lot during construction that is not addressed in the codes or in this standard. In the past few years, a series of high profile buildings around North America have burned during construction. Once built, these structures have some passive protection but it is not in place until the later phases of construction. In several of the major fires, adjacent buildings and other property have been damaged, and in almost all cases, the building under construction has been a total loss.

The 60 foot distance proposed here is a minimum based on the separation distances in Table 4.2.1 of this standard. It represents the most stringent setback from the table because this condition is similar to what exists with a building that is basically completely exposed and the framing is substantially complete before any covering materials are installed. This is the exact condition that has existed during most of the recent documented fires. Following are examples of documented fires:

Project Name / Location: Lindell Avenue Apartments, St. Louis, MODate of Incidents: June 13, 2007 and July 18, 2012Project Description: 4 story, 197-unit, wood framed apartment building.Building Status: Completed and occupied.This same wood framed building was also the scene of a 2007 fire that caused $12 million in damage while construction was underway.

Project Name / Location: 21828 South Avalon Boulevard, Carson, CaliforniaDate of Incident: October 27, 2011Project Description: Three-story wood framed apartment building Building Status: Under constructionThe three-story apartment building caught fire on October 27, 2011 and quickly spread to a nearby mobile home park. More than 139 mobile homes were evacuated. At least 10 homes in the park were damaged by flames. The total damage estimate was $3.1 million, with $2.5 million for the senior living center and $600,000 for the mobile home park.

Project Name / Location: Monroe Apartments, Portland, ORDate of Incident: August 8, 2013Project Description: 46-unit, wood frame apartment buildingBuilding Status: Under constructionThe Monroe Apartments is one of a surge in mid-sized projects across the Portland area. Portland Fire & Rescue put the damage at $4 million.

Project Name / Location: Student Apartments, Kingston, Ontario, CANDate of Incident: December 17, 2013Project Description: The 144-unit student wood-framed apartment complex in Kingston, Ont., was 4,559 square metres (49,072 square feet). Building Status: Under constructionIn all, 10 stations and 113 Kingston firefighters were on scene with 27 apparatuses; 11 Kingston fire personnel

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 37 4/26/2016 9:21 AM

Page 13: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

helped in communications; 11 mutual-aid departments were called and brought 160 firefighters and 19 trucks.

Project Name / Location: 550 East and 500 South, Salt Lake City, UTDate of Incident: February 9, 2014Project Description: Four story, wood frame apartment complexBuilding Status: Under constructionThe building is a four-story apartment complex. The fire caused $2.5 million in damage.

Project Name / Location: Mission Bay Project, San Francisco, CADate of Incident: March 11, 2014Project Description: The projects, supported by piles, consist of 4 and 5-story wood framed residential buildings over 2 levels of parking. The levels above the podium slabs are Type III and V. The 172 unit building was one half of the 360-unit Mission Bay Project.Building Status: Under constructionThe six-story, largely wood-frame building wouldn't have been permitted in California just a few years ago. Until 2008, buildings six stories or higher were required to have "noncombustible" exterior walls.

Project Name / Location: Axis Apartments, Houston, TX Date of Incident: March 25, 2014Project Description: 5 story, 396 unit wood-framed apartment building.Building Status: Under constructionThe inferno began as a 3-alarm fire at 12:30 p.m. but was upgraded to a 5-alarm in less than an hour. More than 400 HFD personnel responded.

Project Name / Location: Gables Upper Rock, Rockville, MDDate of Incident: April 1, 2014Project Description: The Type III 300 unit apartment complex was a five story project, with a two story cast in place parking structure and amenity deck, with three stories of apartment units built with wood framed walls, joists and roof. Building Status: Under constructionMore than 200 firefighters were called to the scene of a three-alarm fire. Montgomery County fire officials say the three-acre complex was 90 percent complete and expected to be finished in two to three weeks before this fire ripped through 150 units. The apartment complex is a total loss, an estimated $15-$20 million.

Project Name / Location: SE Tech Center Drive/Redwood Circle, Vancouver, WADate of Incident: June 19, 2014Project Description: A four-story apartment building, planned to include 90 units.Building Status: Under construction.About 40 firefighters from Vancouver and Klackamas responded to the fire, which was reported around 3:15 a.m. Natural gas helped fuel the flames until a utility crew shut off the line. Estimated dollar loss falls somewhere between $2.5 million and $3.5 million.

Project Name / Location: Victoria Commons, Kitchener, Ontario, CANDate of Incident: July 22, 2014Project Description: The Victoria Common development includes 958 units in a mixture of condominiums, townhomes and parkland. The complex is expected to be constructed in four phases over a decade. The fire was in the first phase of units and is three and four-story wood frame construction. Building Status: Under construction The fire started in the partially completed townhouse development, destroying two blocks of homes and damaging another. At least $5 million in damage was done by the blaze. Flames swept through the primarily wood frame structures in minutes before spreading. The block behind it was destroyed and partially collapsed.

Project Name / Location: Apollo Way, Madison, WIDate of Incident: August 8, 2014Project Description: The project is a four-story, 105-unit wood-frame apartment complex. Building Status: Under construction Authorities initially said the fire caused $3.5 million to $5 million in damage, but the insurer subsequently has estimated that damage is “upwards of $10 million.”

Project Name / Location: DaVinci Apartment Complex, Los Angeles, CADate of Incident: December 8, 2014

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 37 4/26/2016 9:21 AM

Page 14: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Project Description: The 526-unit apartment building had 1.3 million square feet of floor space, with five stories of wood framing over two stories of concrete. Building Status: Under construction The seven-story apartment building was a complete loss after fire. More than 250 firefighters were dispatched to the scene. The collapse of scaffolding and the structure’s wooden frame forced the closure of northbound Harbor (110) Freeway to the northbound 101 Freeway until 10 a.m. Computers and cubicles melted in neighboring buildings. Hundreds of windows cracked. Intense heat damaged fiber-optic cables beneath a downtown freeway and melted one of the signs. There was $10 million in estimated losses and at least four nearby buildings were also damaged. The Lewis Brisbois, Bisgaard & Smith building at 221 N. Figueroa St., where the computers and cubicles melted, had significant damage on its 15 floors, with 300 windows blown out. Three floors were also damaged in the Los Angeles County Department of Health Services building at 313 N. Figueroa. LA Department of Water and Power staff identified at least 160 windows, mostly on the west side of the John Ferraro Building, that were cracked. Los Angeles Department of Building and Safety reported that windows blew out in the north tower of its department headquarters, and the heat and smoke triggered sprinklers that soaked carpets and desks.

Submitter Information Verification

Submitter FullName:

Mark Nowak

Organization: M Nowak Consulting LLC

Affilliation:I represent several clients who produce cold formed steel including theSteel Framing Alliance and Steel Framing Industry Association

Street Address:

City:

State:

Zip:

Submittal Date: Thu Dec 17 16:33:11 EST 2015

Committee Statement

Resolution: The committee concludes that this is outside the committee's scope.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 37 4/26/2016 9:21 AM

Page 15: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 14-NFPA 241-2015 [ Section No. 8.3.1 ]

8.3.1

Temporary storage of equipment to be installed , combustible construction materials, or combustiblepacking materials shall not be permitted in unprotected structures under construction or alteration unlessauthorized by the authority having jurisdiction.

Statement of Problem and Substantiation for Public Input

Combustible construction materials, such as wood framing members, are usually staged on the floor under construction during construction. As currently written, this requirement makes it very difficult to follow normal framing procedures.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:18:16 EST 2015

Committee Statement

Resolution: FR-9-NFPA 241-2016

Statement: The committee agrees with the concept, but modified the language and added an annex note forclarity. Combustible construction materials, such as wood framing members, are usually staged onthe floor under construction during construction. As currently written, this requirement makes it verydifficult to follow normal framing procedures.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 37 4/26/2016 9:21 AM

Page 16: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 15-NFPA 241-2015 [ Section No. 8.3.2 ]

8.3.2 *

Storage In structures required to be protected, combustible storage shall not be permitted in protected structuresuntil until an approved level of protection is in service provided .

Statement of Problem and Substantiation for Public Input

This Public Input clarifies that combustible storage is required to be provided with protection in buildings under construction. It also requires the AHJ to approve the type and level of protection provided. The annex implies this is addressing sprinkler protection, but a standpipe system or even a fire watch may be acceptable to the AHJ. This also addresses partial protection provided by staging fire sprinklers during construction.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:21:52 EST 2015

Committee Statement

Resolution: FR-10-NFPA 241-2016

Statement: This clarifies that combustible storage is required to be provided with protection in buildings underconstruction. It also requires the AHJ to approve the type and level of protection provided. This alsoaddresses partial protection provided by staging fire sprinklers during construction.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 37 4/26/2016 9:21 AM

Page 17: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 16-NFPA 241-2015 [ Section No. 8.6.1.2 ]

8.6.1.2

Fire doors with approved closing devices and hardware shall be installed as soon as is practicable andpreferably before combustible material is introduced .

Statement of Problem and Substantiation for Public Input

The deleted language has the appearance of being both advisory and permissive. Such text should appear mandatory if it is desirable to enforce. If this text is not deleted, perhaps it should be moved to the Annex.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:24:44 EST 2015

Committee Statement

Resolution: FR-11-NFPA 241-2016

Statement: The committee changed "is practicable" to simply "practical" for clarity

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 37 4/26/2016 9:21 AM

Page 18: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 17-NFPA 241-2015 [ Section No. 8.6.2 ]

8.6.2 Temporary Separation Walls.

8.6.2.1

Protection shall be provided to separate an occupied portion of the structure from a portion of the structureundergoing alteration, construction, or demolition operations when such operations are considered as bythe AHJ as having a higher level of hazard than the occupied portion of the building.

8.6.2. 2 1.1

Walls shall have at least a 1-hour fire resistance rating.

8.6.2. 3 1.2

Opening protectives shall have at least a 45-minute fire protection rating.

8.6.2. 4 2 *

Nonrated walls Walls in section 8.6.2.1.1 and opening protectives in section 8.6.2.1.2 shall be permittedwhen to be non-rated when an approved automatic sprinkler system is installed.

Statement of Problem and Substantiation for Public Input

Changing the numbering clarifies the provision and the applicability of the exception. Adding the “by the AHJ” gives the decision capability to the appropriate authority.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:28:12 EST 2015

Committee Statement

Resolution: FR-12-NFPA 241-2016

Statement: The committee agrees with the concept but added the words "and operational" to the end of the lastsentence to assure that active protection is indeed present

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 37 4/26/2016 9:21 AM

Page 19: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 18-NFPA 241-2015 [ Section No. 8.6.2.4 ]

8.6.2.4 *

Nonrated walls and opening protectives shall be permitted when an approved automatic sprinkler system isinstalled and operational .

Statement of Problem and Substantiation for Public Input

Since this standard addresses construction, the sprinkler system may be under construction. We want to make sure the sprinkler is not just present, but also operational.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:33:51 EST 2015

Committee Statement

Resolution: See FR #12

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 37 4/26/2016 9:21 AM

Page 20: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 19-NFPA 241-2015 [ Section No. 8.7.2.1 ]

8.7.2.1 *

A water supply for fire protection, either temporary or permanent, shall be made available as soon ascombustible material accumulates is present .

Statement of Problem and Substantiation for Public Input

As written, the use of the word “accumulates” implies it is protecting against rubbish. This is intended to include all combustible construction materials that may be present. Usually construction materials aren't considered to "accumulate."

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 13-NFPA 241-2015 [Section No. 7.7.4] similar

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:36:35 EST 2015

Committee Statement

Resolution: FR-13-NFPA 241-2016

Statement: As written, the use of the word “accumulates” implies it is protecting against rubbish. This is intendedto include all combustible construction materials that may be present. Usually construction materialsaren't considered to "accumulate." The committee agrees with the concept but added the word"significant" for additional clarity.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 37 4/26/2016 9:21 AM

Page 21: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 5-NFPA 241-2015 [ Section No. 8.7.4.2.5 ]

8.7.4.2.5

Valves Hose valves shall be kept closed at all times and guarded against mechanical injury.

Statement of Problem and Substantiation for Public Input

Obviously you do not want control valves closed. This section applies to the hose valves and should be specific.

Submitter Information Verification

Submitter Full Name: PETER SCHWAB

Organization: WAYNE AUTOMATIC FIRE SPRINKLER

Street Address:

City:

State:

Zip:

Submittal Date: Thu Oct 15 16:35:57 EDT 2015

Committee Statement

Resolution: FR-14-NFPA 241-2016

Statement: We do not want control valves closed. This section applies to the hose valves and should be specificto those.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 37 4/26/2016 9:21 AM

Page 22: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 20-NFPA 241-2015 [ Section No. 9.3.2.3 ]

9.3.2.3

Small torches shall be used to heat the underside of the membrane at a safe distance from these areasopenings, penetrations and flashing before securement.

Statement of Problem and Substantiation for Public Input

As written, the current provision is not clear. This Public Input clarifies the provision. Adding “safe” provides guidance to the installer to keep the risk of fire from openings, penetrations and flashing.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:38:43 EST 2015

Committee Statement

Resolution: FR-15-NFPA 241-2016

Statement: This first revision clarifies the provision. Adding “safe” provides guidance to the installer to keep therisk of fire from openings, penetrations and flashing.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 37 4/26/2016 9:21 AM

Page 23: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 21-NFPA 241-2015 [ Section No. 9.3.4.2 ]

9.3.4.2 *

Torch-applied roofing shall be exempt from the requirement in NFPA 51B, Standard for Fire PreventionDuring Welding, Cutting, and Other Hot Work, that combustibles . Combustibles shall be kept 11 m (35 ft)from hot work, commonly referred to as the “35 Foot Rule.”

Statement of Problem and Substantiation for Public Input

This appeared to be a run-on sentence and is unclear. The revision corrects the grammatical error.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:42:06 EST 2015

Committee Statement

Resolution: FR-16-NFPA 241-2016

Statement: The committee modified the language for clarity and simplicity.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 37 4/26/2016 9:21 AM

Page 24: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 22-NFPA 241-2015 [ Section No. 9.3.8.6.2 ]

9.3.8.6.2

The If frost buildup occurs on fuel gas cylinders and the rate of vapor withdrawal is no longer adequate for operatingconditions, t he hose shall be disconnected and a cylinder with greater propane volume shall be used.

Statement of Problem and Substantiation for Public Input

The provision in this section does not make sense without the condition about frost buildup.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:44:14 EST 2015

Committee Statement

Resolution: FR-17-NFPA 241-2016

Statement: The change clarifies the requirement.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 37 4/26/2016 9:21 AM

Page 25: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 23-NFPA 241-2015 [ Section No. 9.5.5 ]

9.5.5

Where in the opinion of the authority having jurisdiction there is danger of physical damage to the fuelcontainers, protection shall be provided Fuel containers shall be protected against physical damage asapproved .

Statement of Problem and Substantiation for Public Input

It is not necessary to include wording dealing with the opinion of the authority having jurisdiction. Such an opinion is the law and that implication is well-established through a great deal of enforcement history. The wording, if left unchanged, will be open to unnecessary speculation and potential litigation. This requires protection from physical damage and that it be approved, which is defined as "approved by the AHJ."

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 21:46:32 EST 2015

Committee Statement

Resolution: FR-18-NFPA 241-2016

Statement: It is not necessary to include wording dealing with the opinion of the authority having jurisdiction. Thisrequires protection from physical damage and that it be approved, which is defined as "approved bythe AHJ."

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 37 4/26/2016 9:21 AM

Page 26: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 24-NFPA 241-2015 [ Section No. 10.5 ]

10.5 * Demolition Using Explosives.

10.5.1

If explosives are used in demolition work (implosion), hose lines [at least two of 38 mm (1.5 in.) diameter orone 64 mm (2.5 in.) diameter] shall be provided in the immediate vicinity of the demolition site during theactual detonation.

10.5.2

The required hose lines shall be of sufficient length to be capable of extinguishing any small fire anywhereon the demolition site after detonation.

Demolition of buildings using explosives shall be performed by qualified agency following approved procedures.

Statement of Problem and Substantiation for Public Input

This proposal is linked to a Public Input to the annex A10.5. The intent of the provisions in 10.5 and A10.5 should be switched. It seems the commentary in the annex, A10.5, is what the main provision should be requiring. And the existing provisions in 10.5 are to detailed for all demolitions using explosives and are more appropriate for the annex as guidance. This Public Input moves the intent of the annex into the body of the document with clarification and moves the intent of the existing text in 10.5 to the annex with clarification.

The proposed text in 10.5 now requires a “qualified agency” to conduct the explosives demolition. NFPA 241 defines “qualified agency” as “Any individual, firm, corporation, or company that, either in person or through a representative, is regularly engaged in such work, is trained and familiar with all precautions required, and has complied with all the requirements of the authority having jurisdiction.” This covers qualifications and experience as implied by the existing annex. Also, the procedures are to be “approved,” which is defined as “acceptable to the AHJ.” These procedures should involve hose lines as discussed now in the proposed commentary. The verbiage from the existing 10.5 is now proposed in the annex because it is more like commentary. Each demolition site is unique and the type of fire protection measures cannot be specified in the text. It is clear that some sites may need more hose lines than are currently required in the text of the document. As such, this language is relocated to the annex as guidance.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 25-NFPA 241-2015 [Section No. A.10.5]

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 10:56:53 EST 2015

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 37 4/26/2016 9:21 AM

Page 27: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Resolution: FR-19-NFPA 241-2016

Statement: The text now requires a “qualified agency” to conduct the explosives demolition. NFPA 241 defines“qualified agency” as “Any individual, firm, corporation, or company that, either in person or through arepresentative, is regularly engaged in such work, is trained and familiar with all precautions required,and has complied with all the requirements of the authority having jurisdiction.” This coversqualifications and experience. It also, requires that the procedures be “approved” by the AHJ. Thereis also a change to the annex A10.5 attached

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 37 4/26/2016 9:21 AM

Page 28: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 26-NFPA 241-2015 [ New Section after 10.7.2 ]

10.7.3

Demolition shall begin immediately adjacent to structure to be left standing.

Statement of Problem and Substantiation for Public Input

This Public Input is related to a Public Input to the annex. The first sentence in the annex addresses demolition of buildings adjacent to buildings that will remain. There is no provision in the text of section 10.7 that addresses this subject. So, 10.7.3 is added to relate to the first sentence in the annex, which is proposed to become A.10.7.3. The remaining text in the annex is revised to further explain the provision of 10.7.1 and this annex material is identified as A.10.7.1.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 27-NFPA 241-2015 [Section No. A.10.7]

Public Input No. 28-NFPA 241-2015 [Section No. 10.8.5]

Public Input No. 29-NFPA 241-2015 [Section No. A.10.8.5]

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 11:15:49 EST 2015

Committee Statement

Resolution: The committee concludes that this is not always the best approach and is better left to the demolitionexperts and the AHJ on a case by case basis.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 37 4/26/2016 9:21 AM

Page 29: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 28-NFPA 241-2015 [ Section No. 10.8.5 ]

10.8.5 * Fire Extinguishing Equipment Protection .

Fire extinguishing equipment Approved fire protection shall be available subject to the authority havingjurisdiction provided .

Statement of Problem and Substantiation for Public Input

This Public Input is related to Public Inputs to the annex. As indicated in Public Input to A.10.7, hose lines should be available on site. The number and position of hose lines should be determined by the AHJ. The required hose lines shall be of sufficient length and number to be capable of extinguishing any small fire anywhere on the demolition site after detonation. This suggested revision clarifies that fire protection is required as approved. The term "approved" is defined to be as by the AHJ. Fire protection is a more general term that could include a fire watch, or other means. The revisions to the annex clarify that hose lines supplied by hydrants or riser adapters are preferred.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 27-NFPA 241-2015 [Section No. A.10.7] similar

Public Input No. 26-NFPA 241-2015 [New Section after 10.7.2] related

Public Input No. 29-NFPA 241-2015 [Section No. A.10.8.5]

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 11:28:17 EST 2015

Committee Statement

Resolution: FR-20-NFPA 241-2016

Statement: This FR is related to the annex(see attached). The number and position of hose lines should bedetermined by the AHJ. This revision clarifies that fire protection is required as approved. The term"approved" is defined to be as by the AHJ. Fire protection is a more general term that could include afire watch, or other means. The revisions to the annex clarify that hose lines supplied by hydrants orriser adapters are preferred.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 37 4/26/2016 9:21 AM

Page 30: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 30-NFPA 241-2015 [ Section No. 11.1.5 ]

11.1.5

Means of egress for existing, operating, underground structures shall be in accordance with NFPA buildingcodes or NFPA 101, Life Safety Code.

Statement of Problem and Substantiation for Public Input

This will direct the user to the locally adopted building codes, whichever it may be or NFPA 101.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 11:42:45 EST 2015

Committee Statement

Resolution: FR-21-NFPA 241-2016

Statement: This will direct the user to the locally adopted building codes, whichever it may be or NFPA 101.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 37 4/26/2016 9:21 AM

Page 31: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 32-NFPA 241-2015 [ New Section after A.1.1 ]

A.1.1.1

Not all sections of this standard are intended to apply to every construction or alteration project. Forexample it may not be reasonable to expect a complete Fire Safety Program, including an on-site firebrigade or a pre-fire plan with the local fire department for a minor project, such as adding a light fixture.However, some sections would be applicable to all projects, such as a first aid kit (7.7.6) or goodhousekeeping (7.1.2-1). This proposed exception allows the AHJ to make the determination on theapplicability of the provisions of this standard.

Statement of Problem and Substantiation for Public Input

This is proposed because not all sections of this standard are intended to apply to every construction or alteration project. For example it may not be reasonable to expect a complete Fire Safety Program, including an on-site fire brigade or a pre-fire plan with the local fire department for a minor project, such as adding a light fixture. However, some sections would be applicable to all projects, such as a first aid kit (7.7.6) or good housekeeping (7.1.2-1). This proposed exception allows the AHJ to make the determination on the applicability of the provisions of this standard. Note that this Public Input is related to the proposed addition of section 1.1.1.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 31-NFPA 241-2015 [New Section after 1.1]

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 24 20:08:11 EST 2015

Committee Statement

Resolution: See FR #2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 37 4/26/2016 9:21 AM

Page 32: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 25-NFPA 241-2015 [ Section No. A.10.5 ]

A.10.5

If buildings are demolished by explosives, work should be performed only by experienced personnelfollowing procedures approved by the authority having jurisdiction. explosives are used in demolition work(implosion), hose lines should be available on site. The number and position of hose lines should bedetermined by the AHJ. The required hose lines should be of sufficient length and number to be capableof extinguishing any small fire anywhere on the demolition site after detonation.

Statement of Problem and Substantiation for Public Input

This Public Input is related to a proposed revision to section 10.5. The intent of the provisions in 10.5 and A.10.5 should be switched. It seems the commentary in the annex, A.10.5, is what the main provision should be requiring. And the existing provisions in 10.5 are to detailed for all demolitions using explosives and are more appropriate for the annex as guidance. This Public Input moves the intent of the annex into the body of the document with clarification and moves the intent of the existing text in 10.5 to the annex with clarification.

The proposed text in 10.5 now requires a “qualified agency” to conduct the explosives demolition. NFPA 241 defines “qualified agency” as “Any individual, firm, corporation, or company that, either in person or through a representative, is regularly engaged in such work, is trained and familiar with all precautions required, and has complied with all the requirements of the authority having jurisdiction.” This covers qualifications and experience as implied by the existing annex. Also, the procedures are to be “approved,” which is defined as “acceptable to the AHJ.” These procedures should involve hose lines as discussed now in the proposed commentary. The verbiage from the existing 10.5 is now proposed in the annex because it is more like commentary. Each demolition site is unique and the type of fire protection measures cannot be specified in the text. It is clear that some sites may need more hose lines than are currently required in the text of the document. As such, this language is relocated to the annex as guidance.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 24-NFPA 241-2015 [Section No. 10.5] inter-related

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 11:10:04 EST 2015

Committee Statement

Resolution: See FR #19

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 37 4/26/2016 9:21 AM

Page 33: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 27-NFPA 241-2015 [ Section No. A.10.7 ]

A.10.7 .1

Vertical open shafts in buildings under demolition have been a major factor in the rapid spread of firethroughout such buildings. Outside shutes should be used where possible so that floor-to-floor integritycan be maintained.

A.10.7.3 When a building is being demolished in stages, the walls and shafts that assist in preventing thespread of fire should be left remaining as long as possible. In situations where adjacent structures are toremain standing, demolition should be started immediately adjacent to the structures to be left standing,thereby creating a space separation between the structures that will remain through the balance of thedemolition work.

Vertical open shafts in buildings under demolition have been a major factor in the rapid spread of firethroughout such buildings. Outside chutes should be used where possible so that floor-to-floor integrity canbe maintained.

Statement of Problem and Substantiation for Public Input

This Public Input is related to a Public Input to section 10.7. The first sentence in the Public Input to the annex (which currently is at the end of the annex section)addresses demolition of buildings adjacent to buildings that will remain. There is no provision in the text of section 10.7 that addresses this subject. So, 10.7.3 is added to relate to this sentence in the annex. To line up the proposed provision in 10.7.3, this annex commentary is proposed to become A.10.7.3. The remaining text in the annex is revised to further explain the provision of 10.7.1 and this annex material is identified as A.10.7.1.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 26-NFPA 241-2015 [New Section after 10.7.2]

Public Input No. 28-NFPA 241-2015 [Section No. 10.8.5]

Public Input No. 29-NFPA 241-2015 [Section No. A.10.8.5]

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 11:20:11 EST 2015

Committee Statement

Resolution: See FR #19.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 37 4/26/2016 9:21 AM

Page 34: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 29-NFPA 241-2015 [ Section No. A.10.8.5 ]

A.10.8.5

During demolition operations, a means of fire protection shall be provided. This is best provided bycharged hose lines supplied by hydrants or sprinkler-riser adapters should be available .

Statement of Problem and Substantiation for Public Input

This Public Input is related to other Public Inputs. As indicated in Public Input to A.10.7, hose lines should be available on site. The number and position of hose lines should be determined by the AHJ. The requires that hose lines shall be of sufficient length and number to be capable of extinguishing any small fire anywhere on the demolition site after detonation. Proposed revisions to this annex clarifies that a means of fire protection is required, but that is determined by the AHJ, but that hose lines supplied by hydrants or sprinkler riser adapters are desired.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 28-NFPA 241-2015 [Section No. 10.8.5] inter-related

Public Input No. 26-NFPA 241-2015 [New Section after 10.7.2] related

Public Input No. 27-NFPA 241-2015 [Section No. A.10.7] related

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, WA

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 11:32:44 EST 2015

Committee Statement

Resolution: Se FR #20

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 37 4/26/2016 9:21 AM

Page 35: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 1-NFPA 241-2015 [ Chapter B ]

Annex B Informational References

B.1 Referenced Publications.

The following documents or portions thereof listed in this annex are referenced within the informationalsections of this standard and are not part of the requirements of this document unless also listed inChapter 2 for other reasons.

B.1.1 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 1, Fire Code, 2012 edition.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2013 edition.

NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems,2011 edition.

NFPA 30, Flammable and Combustible Liquids Code, 2012 edition.

NFPA 37, Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines, 2010edition.

NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work, 2009 edition.

NFPA 70 ®, National Electrical Code ®, 2011 edition.

NFPA 72 ®, National Fire Alarm and Signaling Code, 2013 edition.

NFPA 101 ®, Life Safety Code ®, 2012 edition.

NFPA 120, Standard for Fire Prevention and Control in Coal Mines, 2010 edition.

NFPA 122, Standard for Fire Prevention and Control in Metal/Nonmetal Mining and Metal MineralProcessing Facilities, 2010 edition.

NFPA 170, Standard for Fire Safety and Emergency Symbols, 2012 edition.

NFPA 326, Standard for the Safeguarding of Tanks and Containers for Entry, Cleaning, or Repair, 2010edition.

NFPA 601, Standard for Security Services in Fire Loss Prevention, 2010 edition.

NFPA 5000 ®, Building Construction and Safety Code ®, 2012 edition.

Fire Protection Handbook, 20th edition, 2008.

B.1.2 Other Publications.

B.1.2.1 ACGIH Publications.

American Conference of Governmental Industrial Hygienists, 1330 Kemper Meadow Drive, Cincinnati, OH45240-1634.

2011 Threshold 2015 Threshold Limit Values and Biological Exposure Indices.

B.1.2.2 ASSE Publications.

American Society of Safety Engineers, 1800 East Oakton Street, Des Plaines, IL 60018 520 N.Northwest Highway, Park Ridge, IL 60068 .

ANSI/ASSE A10.16, Safety Requirements for Tunnels, Shafts, and Caissons,1995 (r2001) 2009 .

B.1.2.3 FM Publications.

FM Global, 1301 Atwood 270 Central Avenue , P.O. Box 7500, Johnston, RI 02919-4923 .

FM Data Sheet 1-33, Safeguarding Torch-Applied Roof Installations, 1988 (Rev. 2000).

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 37 4/26/2016 9:21 AM

Page 36: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

B.1.2.4 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

UL 647, Standard for Unvented Kerosene-Fired Room Heaters and Portable Heaters, 1993, revised 2010 .

ANSI/UL 1278, Standard for Moveable and Wall- or Ceiling-Hung Electric Room Heaters, 2000, Revised2011 2014 .

B.1.2.5 U.S. Government Publications.

U.S. Government Printing Publishing Office, 732 North Capitol Street, NW, Washington, DC20402 20401-0001 .

Title 29, Code of Federal Regulations, Part 1926, “Safety and Health Regulations for Construction,” SubpartS, “Tunnels and Shafts, Caissons, Cofferdams and Compressed Air.”

Title 30, Code of Federal Regulations, Part 57, “Safety and Health Standards — Underground Metal andNonmetal Mines.”

Title 30, Code of Federal Regulations, Part 75, “Mandatory Safety Standards — Underground Coal Mines.”

B.2 Informational References. (Reserved)

B.3 References for Extracts in Informational Sections. (Reserved)

Statement of Problem and Substantiation for Public Input

Referenced current SDO addresses, standard names, numbers, and editions.

Submitter Information Verification

Submitter Full Name: Aaron Adamczyk

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Jul 19 17:54:16 EDT 2015

Committee Statement

Resolution: FR-22-NFPA 241-2016

Statement: Referenced current SDO addresses, standard names, numbers, and editions.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 37 4/26/2016 9:21 AM

Page 37: Public Input No. 31-NFPA 241-2015 [ New Section after 1.1 ] … · 2016-04-26 · Public Input No. 3-NFPA 241-2015 [ New Section after 6.1.1.3 ] Disconnecting Means 6.1.1.4 During

Public Input No. 35-NFPA 241-2016 [ Section No. B.1.2.4 ]

B.1.2.4 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

UL 647, Standard for Unvented Kerosene-Fired Room Heaters and Portable Heaters, 1993. , Revised2010

ANSI/UL 1278, Standard for Moveable and Wall- or Ceiling-Hung Electric Room Heaters, 2000, Revised2011 2014 .

Statement of Problem and Substantiation for Public Input

Referenced UL Standards have been updated/revised to a newer edition.

Submitter Information Verification

Submitter Full Name: Ronald Farr

Organization: Ul Llc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 05 10:59:40 EST 2016

Committee Statement

Resolution: See FR #22

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 37 4/26/2016 9:21 AM