17
PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17 PW-Series Panels with S-Net Readers for Pro-Watch ® 3.81 Rev. D Document Date: 01/09/2011

PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

Embed Size (px)

Citation preview

Page 1: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17

PW-Series Panels with S-Net Readers

for Pro-Watch® 3.81 Rev. D

Document Date: 01/09/2011

Page 2: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 2 of 17

Table of Contents Chapter Page Scope of this document 3 Installation Pre-requisites 3 Integration Overview 3 Additions to Pro-Watch® 3.81 4 Updating the PW6000 IC Panel 4 Creating a new card format 6 PW6000 IC S-Net Port Setup. 7 PW6KR2 Reader board S-Net Setup 9 S-Net Reader Configuration Settings 10 Reader Programming per type 11 Connection diagrams 12 Appendix A: Supported reader types 13 Appendix B: PW6000 S-Net Architecture 14 Appendix C: DR420X LED behavior 17

Page 3: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 3 of 17

Scope of this document This document describes the steps needed to successfully configure the Pro-Watch® Access management system to support PW6000 Series controllers with S-Net DKR and MSR series readers. This document is intended for qualified Pro-Watch engineers, with in-depth knowledge of PW-Series controllers and legacy S-Net wiring and configuration. Installation Pre-requisites The following components are required to support S-Net on PW6000 series panels.

Pro-Watch® 3.81 build 3.81.0.8475 or higher PW6KIC and PW6K1R2 panels PW6KIC firmware pw6k_2_5_4_0279.crc or higher PW6K1R2 firmware pw6k1r2_appl_1_5_8.aax or higher S-Net capable readers. 12.5 Volt ~ 24Volt DC Powersupply New 32 bit PW5K Wiegand card format for use with DKR readers New 40 bit PW5K Magnetic Stripe card format for MSR readers

Supported Readers:

DKR Readers (DR4201 / DR4203 / DR4205 / DR4205K / DR4208S / DR4208K / DR4220 / DR4238) MSR Readers (DR4201SC / DR4205SC / DR4205SCK / MSR5 /MSRK5)

Integration Overview The S-Net readers can be integrated into the PW6000 series architecture in 2 ways or a mix of both.

The first method allows one RS485 port on the PW6000 IC board to be used for up to 8 S-Net readers, another RS485 port is used to connect the PW6K series downstream devices. These can be I/O modules or additional reader boards.

The second method allows for 2 S-Net readers to be configured via a PW6KR2 board.

The 2 S-Net readers are to be connected to the board using the RS485 S-Net protocol, instead of Wiegand. Each Wiegand port on the PW6KR2 allows the connection of 1 S-Net reader on the fixed address 1.

Both methods can also be combined, having a maximum of 8 readers controlled by the PW6000 IC and up to 56 DR420X readers using additional 28 PW6K1R2 reader boards with the absolute maximum of 64 readers per PW6000 IC. See Appendix B for detailed schematics.

Page 4: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 4 of 17

Additions to Pro-Watch 3.81 Adding Firmware to Pro-Watch firmware folder The Pro-Watch software needs to be at a minimum of build 3.1.8.0.8475 or higher to support the PW6000 IC’s with S-Net. The PW6000 IC panel itself requires firmware PW6K_2_5_4_0279 or higher. If the Pro-Watch system does not come with this firmware, please contact technical support. In order to be able to upgrade the firmware, the firmware files need to be placed in the C:\Program Files\ProWatch\Firmware folder.

1. Place the pw6k_2_5_4_0279.crc file in PW_6K folder. 2. Place the pw6k1r2_appl_1_5_8.aax file in PW_SUBPANEL folder

Updating the PW6000 IC Panel firmware Downloading new Firmware to the PW6000 panel Do the following to determine if the PW6000 panel requires a firmware update, Open Hardware Configuration. Expand the appropriate Site on which the panel is located and then go to Panels. Right click on the appropriate panel and select Status. The lower right corner will show firmware version that is currently loaded in the panel.

Page 5: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 5 of 17

Downloading new Firmware to the PW6000 panel - continued When the PW6000 panel requires a firmware update, execute the following procedure:

Go to Hardware Configuration-Site-Panels’ folder and click on the PW6K series panel and select download.

Uncheck Download System in the Download options Check download firmware Select pw6k_2_5_4_0279.crc file from the drop down list. Click the download button. Once the panel comes back online, the PW6KR2 firmware can be updated.

Downloading new Firmware to the PW6KR2 sub panel. Downloading the PW6KR2 firmware requires another download to the PW6000 panel, instead of selecting Download Firmware, the Sub panel Firmware download checkbox need to be selected. Execute the following procedure:

Go to Hardware Configuration-Site-Panels’ folder and click on the PW6K series panel and select download.

Uncheck Download System in the Download options Check download firmware Select pw6k1r2_appl_1_5_8.aax file from the drop down list. Click the download button. When the PW6KR2 comes back online again, the upgrade process is complete

Download PW600IC Firmware Download Sub panel Firmware

Page 6: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 6 of 17

Creating a new card format The S-Net protocol used with SEEP and CHIP panel types support uniquely DKR420X and MSR readers. See Appendix "A" for a full list of supported reader types. When using these readers with the PW6000, an appropriate new card format needs to be created. Regardless how you will connect the S-Net reader(s) to the PW6000 panel, the appropriate card format will need to be created and assigned to the PW6000 panel. To create a card format for a DKR reader type, execute the following steps:

Go to Database Configuration-card formats Right click and select new card format, select

non PW2000 format. Provide a description e.g. ‘S-Net DKR Format’ Select Format Type PW5K Wiegand Set Bits to 32 Set Card number star to 0 Set Card number length to 32 Click OK to Finish

To create a card format for a MSR reader type, execute the following steps:

Go to Database Configuration-card formats Right click and select new card format, select

at’ W5K Magnetic Stripe

ngth to 10 Click OK to Finish

non PW2000 format. Provide a description e.g. ‘S-Net MSR Form Select Format Type P Set Max Digits to 40 Set Card number start to 0 Set Card number le

Assign the created card format(s) to the appropriate PW6000 IC when finished.

Page 7: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 7 of 17

PW6000 IC S-Net Port Setup. The following steps describe the configuration of S-Net readers via a RS485 connection on the PW6000 IC. A new I/O Module can be created and assigned to the PW6000 panel, beside the PW6000 2 Reader board and 16IN/16Out boards. The new Module is called PW6000-S-Net. Up to 8 S-Net Readers are supported by a PW6000 IC. It is recommended to reserve PW6000 S-Net address 1 – 8 for the use with S-Net readers as these addresses will need to match the address provided using the dip/rotary switches on the reader itself. Addresses 9 and higher can be used for I/O modules. For each DKR S-Net reader a new PW6000 S-Net must be created. To configure the PW6000 IC panel for use with S-Net, execute the following steps: Open "Hardware Configuration" Expand Site Go to Panels Double click the Panel Check the S-Net LED box Set Port 3/4 to 9600 baud Set Port 3/4 protocol to S-Net Set Port 5/6 to 38400 Set Port 5/6 to MSP1* As the PW6KIC has no I/O points one Port will need to be configured as S-Net and one port as MSP1. PW6KIC Port 3/4 baud rate field is set to 9600 and Port 4 protocol to "S-Net". When using S-Net DKR/MSR readers. This port refers to Port 2 on the PW6KIC. Port 5/6 is set to a baud rate of 384000 and Port 6 protocol is set to MSP1 for normal PW series downstream RS485 modules. Port 6 is referring to Port 3 on the PW6KIC. To add the PW6000 S-Net devices, continue with the following steps: Right click in the hardware tree Click "Add I/O Module" Select appropriate address Select type PW6000-S-Net Click OK Repeat these steps for each S-Net

device Add I/O boards as usual

Once all PW6000 S-Net devices have been created, select each device and make sure that the Port is set to the appropriate S-Net configured port.

Make sure the I/O modules are configured on the MSP1 configured port.

* Mercury Standard Protocol 1

Page 8: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 8 of 17

PW6000 IC S-Net Port Setup Continued The next step would be to create Logical Devices with the S-Net readers. The creation of the Logical Devices is no different from adding Logical Devices using the standard Wiegand configuration. It is recommended that you setup the hardware templates before adding hardware. To add a Logical device, execute the following steps:

Go to "Hardware configuration" Right click on reader’s folder Select New - Logical device. Enter name for the logical device description. Select the appropriate hardware templates (e.g. Door Typical ACR) Control panel is the panel where reader is being configured on. Select the appropriate hardware class (e.g. Readers)

The Pro-Watch Logical Device Manager appears. Select the "PW6000 S-Net" reader to be used. Please note that the number behind PW6000 S-Net in the drop down list indicates the S-Net reader address. A message pops up saying that “Not all of the default hardware was available. Please manually assign the remaining hardware”.

You will need to manually assign the other I/O hardware to the logical device. Alternatively do

ot use the Logical Device Wizard and assign all hardware manually. n.

nConfigure the Logical Device with the settings as described in the Reader Settings sectio

Make sure that you have configured your hardware templates accordingly before creating logical devices. Please refer to the section Reader Settings for configuration options.

Page 9: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 9 of 17

PW6KR2 Reader board S-Net Setup. The following steps describe the configuration of S-Net readers via a PW6KR2 Reader board connected on a PW6000 IC panel. The reader board requires the latest firmware version. Please refer to the "Downloading new Firmware to the PW6KR2" section on page 5 In case the reader board is not at the latest firmware version. The PW6KR2 allows the connection of 2 S-Net readers. The advantage is that I/O hardware is already located on this board. Each S-Net reader will be connected to one reader port on the PW6KR2 and each S-Net reader must have address 1 configured using the dip/rotary switches. Multi-drop S-Net is not supported from these reader ports. The reader boards are added to the PW6000 IC as normal. To add a Logical device, execute the following steps:

Go to "Hardware configuration" Right click on reader’s folder Select New - Logical device. Enter name for the logical device description. Select the appropriate hardware templates (e.g. Door Typical ACR) Control panel is the panel where reader is being configured on. Select the appropriate hardware class (e.g. Readers)

The Pro-Watch Logical Device Manager appears. Select the appropriate reader from the Reader board that you want to use. The hardware is automatically assigned as the reader board contains I/O points. Click Finish to complete the logical device creation. Configure the Logical Device with the settings as described in the Reader Settings section.

Make sure that you have configured your hardware templates accordingly before creating logical devices. Please refer to the section Reader Settings for configuration options.

S-Net readers configured on a PW6KR2 reader board always use S-Net Address 1.

Page 10: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 10 of 17

S-Net Reader Configuration Settings Depending on the S-Net reader type that is being used, various reader settings will need to be configured. These settings can be configured at the logical device or they can be pre-configured in the hardware templates. The advantage of using the hardware template is that the configured settings are applied each time that a new logical device is created hence it saves time when these are configured with the settings that you want to use. To configure the settings in the Hardware Template, execute these steps:

Go to Hardware Configuration Select Hardware Templates Double click the appropriate template Select the tab Device types Double click on Reader Select the tab PW-5000/6000 Reader

To configure the settings on the Logical Device, execute these steps:

Go to Hardware Configuration Expand the appropriate Site Select the appropriate Class (e.g.

Readers) Double click the Logical Device Select the tab Logical Device Details Double Click on Reader Select the tab Reader Settings

Page 11: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 11 of 17

Reader programming per type This chapter describes the unique setting per reader type. Configuration options in both Hardware Template and Logical Device is indicated by "○", Logical Device configuration only is indicated by "●" DKR Reader without Keypad: When using DKR readers models without keypad (see Appendix "A" DKR readers a-f) the following settings will need to be configured in the Reader settings.

o Keypad Mode None o LED Mode S-Net o S-Net Type DKR o Default Mode Card Only Card Format S-Net DKR Format

DKR Reader with Keypad: When using DKR readers models with keypad (see Appendix "A" DKR readers g-h) the following settings will need to be configured in the Reader settings.

o Keypad Mode Hughes o LED Mode S-Net o S-Net Type DKR + VIP o Default Mode Card and PIN Card Format S-Net DKR Format

The default mode can be any of the other available options, e.g. Card or PIN, PIN only etc. MSR Reader without Keypad: When using MSR readers models without keypad (see Appendix "A" MSR readers A-C) the following settings will need to be configured in the Reader settings.

o Keypad Mode None o LED Mode S-Net o S-Net Type MSRK o Default Mode Card Only Card Format S-Net MSR Format

MSR Reader with Keypad: When using MSR readers models without keypad (see Appendix "A" MSR readers D-E) the following settings will need to be configured in the Reader settings.

o Keypad Mode Hughes o LED Mode S-Net o S-Net Type MSRK o Default Mode Card and PIN Card Format S-Net MSR Format

The default mode can also be any of the other available options, e.g. Card or PIN, PIN only etc.

Page 12: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 12 of 17

Connection diagrams Connecting S-Net Reader to PW6000 IC Using this configuration the PW6KIC board uses one of its two RS485 ports to connect S-Net readers. The other RS4-85 port is used to connect the PW series I/O Modules. When using this configuration, the following rules apply:

Allows S-Net reader to be multi dropped Up to 8 readers are supported. S-Net address 1 – 15 can be used Readers need to be powered

separately

Connecting S-Net Readers on PW6000 2-Reader board Using this configuration the PW6KR2 can connect one S-Net reader to each Wiegand port on the 2 reader board. In total 2 S-Net reader can be connected to this board.

One-to-One configuration 2 readers can be connected to the PW6KR2 board 1 S-Net reader per Wiegand Port S-Net address 1 can be used only! Readers may be powered from the IC.

Some DKR/MSR readers work with 24VDC only. Please consult your reader's manual to see if the reader supports 12.5 VDC.

In case the reader does not support 12.5VDC, power needs to be applied separately to the readers.

Do not forget to reference the negative (0 Volts) of both powersupplies

Page 13: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 13 of 17

Appendix A: Supported reader types These are the supported reader types on PW6000IC and/or PW6KR2. Please consult the DigiReaders manual Rev F for installation and other relevant information. DKR Readers:

a) DR4201 b) DR4203 c) DR4205 d) DR4208S e) DR4220 f) DR4238 g) DR4205K - with Keypad h) DR4208K - with Keypad

MSR Readers:

A) DR4201SC - Mifare / Legic Reader B) DR4205SC - Mifare / Legic Reader C) MSR5 - Magstripe Reader D) DR4205SCK - Mifare / Legic Reader w Keypad E) MSRK5 - Magstripe Reader w Keypad

Page 14: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 14 of 17

Appendix B: PW6000 S-Net Architecture

PW6000 IC with port 4 enabled for S-Net S-Net enabled PW6000 IC

Lock

Rex Button

Door Switch

This configuration supports 8 S-Net readers only. However standard Wiegand readers can be combined. NOTE: The DR420X readers are capable to reliably function on a minimum power level of 12.5V – 24 Volts DC. The PW5KE2PS delivers a 12.0 Volts 4 amp output. A power calculation should be made to ensure proper and sufficient power for the DR420X readers. TIP: When migrating to PW6000 IC from Star X controller system the controller PI-2 powersupply can be re-used to provide 24Volts for powering the readers. Do not forget to reference the negative (0 Volt) of both powersupplies.

123 8

Maximum 8 S-Net Readers

S-Net

12.5V for DKR Readers

12.5V ~ 24V Power

Standard PW6K1IN/OUT

Page 15: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 15 of 17

Appendix B: PW6000 S-Net Architecture

PW6000 IC with PW6K1R2 S-Net enabled 2 reader boards

This configuration allows for maximum 32 downstream devices. S-Net enabled PW6K1R2 can be combined with Standard reader boards

S-Net enabled PW6K1R2

Standard PW6000 IC

S-Net enabled PW6K1R2

S-Net + 12 Volt

S-Net Reader S-Net Reader S-Net Reader S-Net Reader

Alternative 12/24 Volt Power Supply

Page 16: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 16 of 17

Appendix B: PW6000 S-Net Architecture

S-Net enabled PW6000 IC combined with PW6K1R2 S-Net enabled 2 reader boards.

This configuration allows for maximum 32 downstream devices including S-Net readers. Total number of readers remains 64.

S-Net enabled PW6K1R2

S-Net enabled PW6000 IC

Power for DKR

Maximum 8 S-Net Readers

S-Net enabled PW6K1R2

S-Net Reader S-Net Reader S-Net Reader S-Net Reader

AlternatPower S

ive 12/24 Volt upply

S-Net + 12Volt

S-Net3 8 2 1

12/24 Volts for DKR Readers needed

Page 17: PW-Series Panels with S-Net Readers for Pro-Watch 3 · PDF filePW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 1 of 17. PW-Series Panels with S-Net Readers

PW-Series Panels with S-Net Readers Date Modified: 1 November, 2011 Page 17 of 17

Appendix C: DR420X LED behavior Any DR420X series reader connected to the PW6000 IC S-Net port or PW6000 2 Reader board will only support basic LED and Buzzer controls. It is therefore essential to understand the behavioral differences before an implementation or migration is proposed. The table below delivers a comparison between the Reader control by Star 2 and PW6000 IC and 2 Reader board.

PW6000IC or 2R with S-Net Support Star 2 Controller Activity LED Behavior Buzzer LED Behavior Buzzer Online Red LED Off Red LED Off Offline Red LED blinking Off Red LED Blinking Off Access Granted Green LED Single Beep Green LED Single Beep Access Pending Amber LED Off Amber LED N/A Access Denied Red LED No change Off Red LED OFF Single Beep Unlocked Green LED N/A Green LED N/A Unlock on REX Red LED No change Green LED N/A Door Forced Red LED No change Off Red LED On Door Held Red LED No change Off Red LED Continuous Door OTL Red LED No change Off Red LED Continuous Pre Alert Red LED No change Off Red LED Intermitting