QH Circuitbreakers DataSheet

Embed Size (px)

Citation preview

  • 8/10/2019 QH Circuitbreakers DataSheet

    1/20

    QH 10kA Miniature CircuitBreaker & RCBO Range

    Innovative, Robust, Reliable & Efficient Protection.

    NEW

  • 8/10/2019 QH Circuitbreakers DataSheet

    2/20

  • 8/10/2019 QH Circuitbreakers DataSheet

    3/20

    01 - 0418mm Range QH Miniature Circuit Breakers

    01Features, Accessories, Technical Characteristics

    02Time Delay Characteristics, Connection Diagrams, Dimensions

    03Ambient Temperature Chart, Load Capacity,

    04Effect of Power Frequency, Let-Through Energy Data

    05 - 0727mm Range QH Miniature Circuit Breakers

    05Features, Accessories, Technical Characteristics

    06Time Delay Characteristics, Connection Diagrams, Dimensions

    07Load Capacity, Let-Through Energy Data

    08 - 09Electronic Combined RCD/MCB Devices

    08Features, Accessories, Technical Characteristics

    09Technical Characteristics, Tripping Characteristics, Connection Diagrams, Dimensions

    10QH Isolating Switches

    10Features

    11QH 10kA Retrofit Kits for ADVD & HPRD Distribution Boards

    11Upgrade & installation

    12Advantage ADVDH Distribution Switchboards

    12Features, Dimensions & Part Numbers

    12HPRDH Distribution Switchboards

    12Features, Dimensions & Part Numbers

    13QH 10kA Retrofit Kits & Accessories

    13Description, Detail & Part Numbers

    14Selection Data

    14DIN Miniature Circuit Breakers, Isolating Switches, Miniature RCBOs, Miniature RCDs

    CONTENTS

    QH 10kA Miniature Circuit Breaker & RCBO Range

  • 8/10/2019 QH Circuitbreakers DataSheet

    4/20

    01FREE CALL1800 770 870 www.cbi-electric.com.au

    Electrical Mechanical

    Compliance: AS/NZS 60898.1 Frame size: 45mm(Approval No NSW25003)

    Rated voltage: 230/400V AC Device size: 80mm (height), 17.5mm (width)

    48V DC (per pole) Mounting: DIN rail (EN 50022)

    Rated frequency: 50/60Hz Degree of protection: IP20 (when installed)

    Breaking capacity (Ics=Icu): 10kA Terminals: Open mouthed lift terminals

    Time delay characteristic: Curves: 1, 2 Terminal protection: Touch safe, VBG 4, VE-EN 6

    Back up fuse: Max. 125A gL Terminal capacity: 1 25mm

    Selectivity class: 3 Fastening torque: 2 2.4Nm Endurance: > 8000 operating cycles Busbar thickness: 0.8 2mm

    Line voltage connection: Optional (above/below) Mounting position: Any

    Technical Characteristics

    QH 10kA Range

    QH Miniature Circuit Breakers & RCBOsThe new QH Range of MCBs & RCBOs provide safe and reliable solutions for low voltage electricalprotection against overload and short circuit, delivering reliability, strength and efficient protectionfor commercial, industrial and mining applications.

    DIN mounting18mm Module widthHigh selectivity between MCB and back-up fuse due to low let-through energyCompatible with standard busbarTwin-purpose terminal (lift/open-mouthed) above & belowBusbar positioning optionally above or belowMeets the requirements of insulation co-ordination, distance between contacts

    4 mm, for secure isolation.

    Suitable for DC applications up to 48V DC1 pole to 3 pole

    18mm Range QH Miniature Circuit Breakers

    Features

    Auxiliary switch (add on, field mountable)Trip alarm ( add on, field mountable)Shunt trip release (add on, field mountable)Undervoltage release (add on, field mountable)

    EnclosuresAdditional terminal 35mmAnti-tamper device (handle lock)

    Accessories

  • 8/10/2019 QH Circuitbreakers DataSheet

    5/20

    FREE CALL1800 770 870 www.cbi-electric.com.au 02

    1-pole 1+N-pole 2-pole 3-pole 3+N-pole

    Connection Diagrams

    Time Delay Characteristics

    CURVE 1Operating

    Characteristics

    Ambient Temperature 30C

    TRIPPINGTIME

    S

    ECONDS

    MINUTES

    PERCENTAGE RATED CURRENT

    CURVE 2Operating

    Characteristics

    Ambient Temperature 30C

    TRIPPINGTIME

    S

    ECONDS

    MINUTES

    PERCENTAGE RATED CURRENT

    1-pole 2p & 1pole+N 3-pole 3 pole + N

    Dimensions (mm)

  • 8/10/2019 QH Circuitbreakers DataSheet

    6/20

    Effect of the Ambient Temperature on Thermal Tripping BehaviourAdjusted rated current values according to the ambient temperature

    Ambient Temperature T [C]

    In{A} -25 -20 -10 0 10 20 30 35 40 45 50 55 60

    0.16 0.20 0.19 0.19 0.18 0.17 0.17 0.16 0.16 0.15 0.15 0.15 0.14 0.14

    0.25 0.31 0.30 0.29 0.28 0.27 0.26 0.25 0.25 0.24 0.24 0.23 0.23 0.22

    0.5 0.61 0.60 0.58 0.56 0.54 0.52 0.50 0.49 0.48 0.47 0.46 0.45 0.44

    0.75 0.92 0.90 0.87 0.84 0.81 0.78 0.75 0.74 0.73 0.71 0.69 0.68 0.66

    1 1.2 1.2 1.2 1.1 1.1 1.0 1.0 0.99 0.97 0.95 0.93 0.90 0.89

    1.5 1.8 1.8 1.7 1.7 1.6 1.6 1.5 1.5 1.5 1.4 1.4 1.4 1.3

    1.6 2.0 1.9 1.9 1.8 1.7 1.7 1.6 1.6 1.5 1.5 1.5 1.4 1.4

    2 2.4 2.4 2.3 2.2 2.2 2.1 2.0 2.0 1.9 1.9 1.9 1.8 1.8

    2.5 3.1 3.0 2.9 2.8 2.7 2.6 2.5 2.5 2.4 2.4 2.3 2.3 2.2

    3 3.7 3.6 3.5 3.4 3.3 3.1 3.0 3.0 2.9 2.8 2.8 2.7 2.7 3.5 4.3 4.2 4.1 3.9 3.8 3.7 3.5 3.4 3.4 3.3 3.2 3.2 3.1

    4 4.9 4.8 4.7 4.5 4.3 4.2 4.0 3.9 3.9 3.8 3.7 3.6 3.5

    5 6.1 6.0 5.8 5.6 5.4 5.2 5.0 4.9 4.8 4.7 4.6 4.5 4.4

    6 7.3 7.2 7.0 6.7 6.5 6.3 6.0 5.9 5.8 5.7 5.6 5.4 5.3

    8 9.8 9.6 9.3 9.0 8.7 8.4 8.0 7.9 7.7 7.6 7.4 7.2 7.1

    10 12 12 12 11 11 10 10 9.9 9.7 9.5 9.3 9.0 8.9

    12 15 14 14 13 13 13 12 12 12 11 11 11 11

    13 16 16 15 15 14 14 13 13 13 12 12 12 12

    15 18 18 17 17 16 16 15 15 15 14 14 14 13

    16 20 19 19 18 17 17 16 16 15 15 15 14 14

    20 24 24 23 22 22 21 20 20 19 19 19 18 18

    25 31 30 29 28 27 26 25 25 24 24 23 23 22 32 39 38 37 36 35 33 32 32 31 30 30 29 28

    40 49 48 47 45 43 42 40 39 39 38 37 36 35

    50 61 60 58 56 54 52 50 49 48 47 46 45 44

    63 77 76 73 71 68 66 63 62 61 60 58 57 56

    Load Capacity of Series Connected Miniature Circuit Breakers

    NUMBER OF DEVICES (n) 1-pole

    LOAD

    CAPACITYFACTOR

    KN

    03FREE CALL1800 770 870 www.cbi-electric.com.au

  • 8/10/2019 QH Circuitbreakers DataSheet

    7/20

    Effect of Power FrequencyAdjusted power frequency on the tripping behaviour I

    MAof the quick release

    Power Frequency f (Hz)

    16 2/3 50 60 100 200 300 400

    IMA(f) / IMA (50Hz) [%] 91 100 101 106 115 134 141

    Let-Through Energy Data

    PROSPECTIVE SHORT CIRCUIT [A]

    Let-Through Energy, Characteristic 1, 1-pole

    LET-THROUGH

    ENERG

    YI2t[A2s

    ec]

    PROSPECTIVE SHORT CIRCUIT [A]

    Let-Through Energy, Characteristic 2, 1-pole

    LET-THROUGH

    ENERG

    YI2t[A2s

    ec]

    04FREE CALL1800 770 870 www.cbi-electric.com.au

  • 8/10/2019 QH Circuitbreakers DataSheet

    8/20

    Electrical Mechanical

    Compliance: I EC/EN 60947-2 Frame size: 45mm

    Rated voltage: 230/400V AC Device size: 90mm (height), 27mm (width)

    60V DC (per pole) Mounting: DIN rail (EN 50022)

    Rated frequency: 50/60Hz Degree of protection: IP20 (when installed)

    Breaking capacity (Icu=Ics): 10kA Terminals: Open mouthed lift terminals

    Time delay characteristic: Curves: 1, 2 Terminal protection: Touch safe, VBG 4, VE-EN 6

    Back up fuse: Max. 200A gL Terminal capacity: 2.5 50mm

    Selectivity class: 3 Mounting position: Any

    Endurance: 20000 operating cycles

    Rated insulation voltage: 440V

    Peak withstand voltage: 4kV

    Technical Characteristics

    QH 10kA Range

    QH Miniature Circuit Breakers & RCBOsThe new QH Range of MCBs & RCBOs provide safe and reliable solutions for low voltage elec-trical protection against overload and short circuit, delivering reliability, strength and efficientprotection for commercial, industrial and mining applications.

    27mm Range QH Miniature Circuit Breakers

    DIN mounting27mm Module widthIndependent switching contacts80 to 125A ratingsWith isolator function, meets the requirements of insulation coordination,

    distance between contacts 4mm, for secure isolation.

    High current limit

    Features

    Auxiliary switch (add on, field mountable)Trip alarm ( add on, field mountable)Shunt trip release (add on, field mountable)

    Anti-tamper device (handle lock)Busbar

    Accessories

    05FREE CALL1800 770 870 www.cbi-electric.com.au

  • 8/10/2019 QH Circuitbreakers DataSheet

    9/20

    1-pole 1+N-pole 2-pole 3-pole 3+N-pole

    Connection Diagrams

    Time Delay Characteristics

    CURVE 1Operating

    Characteristics

    Ambient Temperature 30C

    TRIPPINGTIME

    SECONDS

    MINUTES

    PERCENTAGE RATED CURRENT

    CURVE 2Operating

    Characteristics

    Ambient Temperature 30C

    TRIPPINGTIME

    SECONDS

    MINUTES

    PERCENTAGE RATED CURRENT

    1-pole 2p & 1pole+N 3-pole 3 pole + N

    Dimensions (mm)

    06FREE CALL1800 770 870 www.cbi-electric.com.au

  • 8/10/2019 QH Circuitbreakers DataSheet

    10/20

    Let-through Energy Data

    LET-THROUGH

    ENERGYI2t[A2s

    ec]

    LET-THROUGH

    ENERGYI2t[A2s

    ec]

    PROSPECTIVE SHORT CIRCUIT [A] PROSPECTIVE SHORT CIRCUIT [A]

    Load Capacity of Series Connected Miniature Circuit Breakers

    NUMBER OF DEVICES (n) 1-pole AMBIENT TEMPERATURET [C]

    LOAD

    CAPACITYK

    T

    [I/In]

    Load Capacity in case of Block Installation Effect of Ambient Temperature

    Permitted permanent load at ambient temperature T[C] with n devices IDL

    = InK

    T(T)K

    N(N).

    Determined according to AS/NZS 60898

    Maximum Let-Through Energy, Characteristic 1, 1-pole Maximum Let-Through Energy, Characteristic 2, 1-pole

    LOAD

    CAPACITYFACTORK

    N

    07FREE CALL1800 770 870 www.cbi-electric.com.au

  • 8/10/2019 QH Circuitbreakers DataSheet

    11/20

    Electrical

    Compliance: AS/NZS 60898 (Approval No NSW 25355)

    No of Poles: 1+N-Pole switched, N Led through (solid neutral)

    Rated voltage: 240 VAC

    Rated frequency: 50/60Hz

    Rated current: 6-32A (Curve 2), 6-20A (Curve 1)

    Rated tripping current: 10, 30mA

    Endurance electrical comp: >_ 4,000 operating cycles Endurance mechanical comp: >_ 20,000 operating cycles

    Ultimate short circuit breaking capacity: Curve 1, Curve 2 Ultimate short circuit breaking capacity: 10kA

    Rated short circuit breaking capacity: 10kA Rated fault breaking capacity: 10kA

    QH 10kA RCBO Range

    The new QH Range of RCBOs provide safe and reliable solutions for low voltage electrical protectionagainst overload and short circuit, delivering reliability, strength and efficient protection forcommercial, industrial and mining applications. Being one of the smallest 10kA RCBOs on themarket, it allows for extra wiring room in most applications.

    Electronic Combined RCD/MCB Devices

    Technical Characteristics

    DIN mounting1+N-pole, 1 module width, allows for extra wiring room in boardsElectronic residual current device /

    miniature circuit breaker combination in only 1MU

    Tripping line voltage dependentContact position indicator red greenCan be sealed with leads in the on and off positionRated currents available 632A (Curve 2), 620A (Curve 1)Permanently connected neutral conductor (1100mm long)

    Can be connected to standard busbar (at the lower side)Type A RCD

    Features

    Auxiliary switch for subsequent installationTripping signal switch for subsequent installation

    Shunt trip releaseTripping module

    Accessories

    08FREE CALL1800 770 870 www.cbi-electric.com.au

  • 8/10/2019 QH Circuitbreakers DataSheet

    12/20

    Mechanical

    Frame size: 45mm

    Device size: 102.6mm (height), 17.5mm (width) (1MU)

    Mounting: Quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715

    Upper terminals: Lift terminals

    Lower terminals: Open mouthed/lift terminals

    Terminal protection: Finger and hand touch safe, BGV A3, OVE-EN 6

    Terminal capacity: 1 25mm

    Busbar thickness below: 0.8 2mm

    Degree of protection built in: IP20 (when installed)

    Permanent ambient temperature range: -25C to + 40C

    Resistance to climatic conditions: 25 55C / 90 95% relative humidity acc. to IEC 60068-2

    Neutral conductor length: 1100mm

    Technical Characteristics

    Tripping line voltage-dependent: Instantaneous

    Peak withstand current: 250A (80/20ps)

    Rated non-tripping current: 0.5

    Voltage range for protective function: 184 264V~

    Tripping Characteristics RCD Component

    Conventional non-tripping current: 1.05

    Conventional tripping current: 1.30

    Reference temperature: 30C

    Selectivity class: 3

    Maximum back-up fuse > 6kA: 100 A gl

    Tripping Characteristics RCD Component

    Connection Diagrams Dimensions (mm)

    1+N-pole 1+N-pole

    11.5

    91

    17.7

    09FREE CALL1800 770 870 www.cbi-electric.com.au

  • 8/10/2019 QH Circuitbreakers DataSheet

    13/20

    QH 10kA Range

    QH Isolating SwitchesIntroducing the new QH Range of isolating switches. These switches are a quality solution forthe safe isolation on light and power distribution applications. Switch isolators are used as amain switch in low voltage switchgear for distribution of light and power, starting and stoppingmotors and isolating loads during any maintenance.

    Complies to IEC 60947-2Min service entrance from busbarsControl: On load circuit opening and closingSwitching and isolating motorsDirect busbar mount

    Features

    10FREE CALL1800 770 870 www.cbi-electric.com.au

  • 8/10/2019 QH Circuitbreakers DataSheet

    14/20

    QH 10kA Retrofit Kits for ADVD & HPRD Distribution BoardsExisting Heinelec ADVD & HPR distribution boards can be easily upgraded to fit our QH 10kA range of MCBs & RCBOs.

    Remove existingQF escutcheon

    Install new QH main switch

    and chassis kits. (Main switchNOT required for HPR boards)

    1

    3

    Remove existing QFchassis and main switch.(Remove main switch ONLY

    on AVDV model)

    2

    4

    Final upgraded Distribution Board allowsfor immediate use for all QH 10kA product.

    Install new QH escutcheon

    11FREE CALL1800 770 870 www.cbi-electric.com.au

  • 8/10/2019 QH Circuitbreakers DataSheet

    15/20

    Main No of Height Width Depth Part

    Switch Poles (mm) (mm) (mm) Number

    250A 24 800 580 225 ADVDH24M250 36 1000 580 225 ADVDH36M250

    48 1000 580 225 ADVDH48M250

    60 1200 580 225 ADVDH60M250

    72 1400 580 225 ADVDH72M250

    84 1600 580 225 ADVDH84M250

    96 1800 580 225 ADVDH96M250

    Advantage ADVDH Distribution Switchboards

    HPRDH Distribution Switchboards

    Spacious design affords more useable space(depth below escutcheon 150mm)

    Additional switchboard modules can be added to the top,bottom and sides for a modular solution

    Complies with AS/NZS 3439.3IP42 degree of protectionEnclosure depth: 225mm

    (including door)

    Quality 250A, 20kA, 0.25 type tested busbar system

    Top and bottom removable gland plates

    Features

    Main No of Height Width Depth Part

    Switch Poles (mm) (mm) (mm) Number

    250A 24 800 580 225 HPRDH24M250 36 1000 580 225 HPRDH36M250

    48 1000 580 225 HPRDH48M250

    60 1200 580 225 HPRDH60M250 72 1400 580 225 HPRDH72M250

    84 1600 580 225 HPRDH84M250

    96 1800 580 225 HPRDH96M250

    Complies with AS/NZS 3439.3IP66 degree of protectionQuality 250A, 20kA, 0.25 type tested busbar systemSpacious design affords more useable space

    (depth below escutcheon 140mm)

    Enclosure depth: 225mm (including door)Additional switchboard modules can be added to the top,bottom and sides for a modular solution

    Removable top and bottom gland plates

    Features

    12FREE CALL1800 770 870 www.cbi-electric.com.au

  • 8/10/2019 QH Circuitbreakers DataSheet

    16/20

    QH 10kA Retrofit Kits & Accessories

    Description Pole Rating PartCapacity Number

    24 250A HQHC24

    36 250A HQHC36

    48 250A HQHC48

    60 250A HQHC60

    72 250A HQHC72

    84 250A HQHC84

    96 250A HQHC96

    250A ThreePhase BusbarAssemblies

    Type HQHCNote: All

    switchgear

    not included

    Description Pole Part

    Capacity Number

    24 453273G024

    36 453273G036

    48 - 60 453273G060

    72 - 84 453273G084

    96 453273G096

    ADVDHEscutcheon

    Description Pole Part

    Capacity Number

    24 - 36 453032G036

    48 - 60 453032G060

    72 453032G072 84 453032G084

    96 453032G096

    HPRDHEscutcheon

    Description Part

    Number

    MSHS250ADVDH250A Main SwitchKit for ADVDH,

    Description Part

    Number HS250

    250A Amp MainSwitch 3 Pole

    Description Length Part

    Number

    450mm HDINR450

    DIN Rail C/WMounting brackets

    13FREE CALL1800 770 870 www.cbi-electric.com.au

  • 8/10/2019 QH Circuitbreakers DataSheet

    17/20

    Selection Data

    DIN Miniature Circuit Breakers: 18mm Curve 2

    Rating (Amp) Rating(kA) Module Width 1 Pole 2 Pole 3 Pole

    4 10kA 18mm QHB18204 QHB28204 QHB38204

    6 10kA 18mm QHB18206 QHB28206 QHB38206

    10 10kA 18mm QHB18210 QHB28210 QHB38210

    16 10kA 18mm QHB18216 QHB28216 QHB38216

    20 10kA 18mm QHB18220 QHB28220 QHB38220

    25 10kA 18mm QHB18225 QHB28225 QHB38225

    32 10kA 18mm QHB18232 QHB28232 QHB38232

    40 10kA 18mm QHB18240 QHB28240 QHB38240

    50 10kA 18mm QHB18250 QHB28250 QHB38250

    63 10kA 18mm QHB18263 N/A QHB38263

    DIN Miniature Circuit Breakers: 27mm Curve 2

    Rating (Amp) Rating(kA) Module Width 1 Pole 3 Pole

    80 10kA 27mm QHD18280 QHD38280

    100 10kA 27mm QHD182100 QHD382100

    125 10kA 27mm QHD182125 QHD382125

    DIN Isolating Switches: Type QH

    Rating (Amp) Rating 1 Pole 2 Pole 3 Pole

    63 415V AC QHB10063 QHB20063 QHB30063

    100 415V AC QHB100100 N/A N/A

    125 415V AC QHB100125 QHB200125 QHB300125

    DIN Miniature RCBO

    Rating (Amp) Rating(kA) Module Width 1 Pole

    6 10kA 18mm QH12AD06

    10 10kA 18mm QH12AD10

    16 10kA 18mm QH12AD16

    20 10kA 18mm QH12AD20

    32 10kA 18mm QH12AD32

    DIN Miniature RCD

    Rating (Amp) Rating(kA) Module Width 1 Pole 2 Pole

    40 10kA 18mm QH16C-D-40A QH36C-D-40A

    63 10kA 18mm QH16C-D-63A QH36C-D-63A

    14FREE CALL1800 770 870 www.cbi-electric.com.au

  • 8/10/2019 QH Circuitbreakers DataSheet

    18/20

    15

    Notes

    FREE CALL1800 770 870 www.cbi-electric.com.au

  • 8/10/2019 QH Circuitbreakers DataSheet

    19/20

  • 8/10/2019 QH Circuitbreakers DataSheet

    20/20

    FREE CALL 1800 770 870 WEBSITE www cbi electric com au

    ADDRESS 90 Fairbank Road, Clayton South, Victoria 3169 | PO Box 241, Springvale, Vic 3171

    PHONE +61 3 9590 3500 | FAX +61 3 9551 1051 | EMAIL [email protected]

    MELBOURNE HEAD OFFICE

    Australia

    SALES OFFICES

    SOUTHERN REGIONVICTORIA & SOUTH AUSTRALIA

    90 Fairbank Rd, Clayton South, VIC 3169PO Box 241, Springvale, VIC 3171

    PHONE +61 3 9590 3555FAX +61 3 9551 1053FREE CALL 1800 770 870EMAIL [email protected]

    NEW SOUTH WALES

    310/33 Lexington Drive,Bella Vista, NSW, 2153

    PHONE +61 2 9836 3577FAX +61 2 9836 3588FREE CALL 1800 770 870EMAIL [email protected]

    QUEENSLAND

    Unit 2, 80 Ebbern St, Darra, QLD, 4076PO Box 3240, Darra, QLD, 4076

    PHONE +61 7 3279 1833FAX +61 7 3279 1866FREE CALL 1800 770 870EMAIL [email protected]

    WESTERN AUSTRALIA

    40 Belmont Avenue,Rivervale, WA, 6103

    PHONE +61 8 9478 3341FAX +61 8 9478 3501FREE CALL 1800 770 870EMAIL [email protected]

    DISTRIBUTORS

    TASMANIASLEGERS PRODUCTS

    WP Martin Pty Ltd85 Elizabeth St, Launceston, TAS, 7250

    PHONE +61 3 6331 5545FAX +61 3 6331 4256EMAIL [email protected]