13
QIS 330 400/230 V | 50HZ | 1 / 8 Diesel Generator Set QIS 330 Voltage: 400/230 V Frequency: 50HZ Technical specifications Genset Image for illustration purposes only 330 264 kW kVA Standby Power (ESP) TECHNICAL INFORMATION g 300 240 kW kVA Prime Power (PRP) Soundproofed Mechanical structure DOOSAN P126 TI-II Engine MECC ALTE ECO38-2L/4A Alternator DEEP SEA 7320 MKII Control card 3.840 x 1.470 x 1.785 mm Measures (L x W x H) 2.256 kg Empty weight 489 L Fuel tank 72 dB(A) a 7 m Acoustic pressure, LpA 97 dB(A) Acoustic power LwA (kVA) (kW) (kVA) Voltages Prime Power (PRP) Standby Power (ESP) (kW) 380/220 300 240 330 264 400/230 300 240 330 264 415/240 300 240 330 264 Notes: PRIME POWER: Electrical power data available at a variable load without limits of hours per year. An overload of 10 % is allowed for 1 hour of every 12. In accordance with ISO 8528/1 (2005) – PRP STANDBY POWER: Electrical power data at variable load in an emergency in accordance with standard ISO 8528/1 (2005) – ESP. Overloads of emergency power are not allowed. The standard reference conditions are: 25 ºC, 100 kPa and 30% relative humidity. Gasoil density: 0.85 g/cm3. Gasoline density: 0.68 g/cm3. www.atlascopco.com/industrial-generator

QIS 330 - GeneratorIn accordance with ISO 8528/1 (2005) PRP STANDBY POWER: Electrical power data at variable load in an emergency in accordance with standard ISO 8528/1 (2005) ESP

  • Upload
    others

  • View
    12

  • Download
    0

Embed Size (px)

Citation preview

  • QIS 330 | 400/230 V | 50HZ |

    1 / 8

    Diesel Generator Set

    QIS 330

    Voltage: 400/230 V

    Frequency: 50HZ

    Technical specifications

    Genset Image for illustration purposes only

    330

    264kW

    kVAStandby Power (ESP)

    TECHNICAL INFORMATIONg

    300

    240kW

    kVAPrime Power (PRP)

    SoundproofedMechanical structure

    DOOSAN P126 TI-IIEngine

    MECC ALTE ECO38-2L/4AAlternator

    DEEP SEA 7320 MKIIControl card

    3.840 x 1.470 x 1.785mmMeasures (L x W x H)

    2.256kgEmpty weight

    489LFuel tank

    72dB(A) a 7

    m

    Acoustic pressure, LpA

    97dB(A)Acoustic power LwA

    (kVA) (kW)(kVA)

    VoltagesPrime Power (PRP) Standby Power (ESP)

    (kW)

    380/220 300 240 330 264

    400/230 300 240 330 264

    415/240 300 240 330 264

    Notes:

    PRIME POWER: Electrical power data available at a variable load without limits of hours per year. An overload of

    10 % is allowed for 1 hour of every 12. In accordance with ISO 8528/1 (2005) – PRP

    STANDBY POWER: Electrical power data at variable load in an emergency in accordance with standard ISO

    8528/1 (2005) – ESP. Overloads of emergency power are not allowed.

    The standard reference conditions are: 25 ºC, 100 kPa and 30% relative humidity. Gasoil density: 0.85 g/cm3.

    Gasoline density: 0.68 g/cm3.

    www.atlascopco.com/industrial-generator

  • QIS 330 | 400/230 V | 50HZ |

    2 / 8

    g

    General description

    Engine

    Alternator

    Bedplate

    Soundproofed canopy

    Electric Panel

    ATS

    Dimensions and Weight

    Performance class

    Regulation

    Annex: Drawings

    Grupos Electrógenos Europa, S.A. is a certified company with ISO 9001, ISO 14001, OHSAS 18001 and PECAL

    We reserves the right to modify any characteristic of their equipment without prior warning.

    Photographs representing the product range, while able to include options.

    Weight and dimensions of a standard generator set.

    Non-contractual document

    Central Offices:

    Polígono Industrial Pitarco II; Parcela 20

    50450 Muel (Zaragoza) Spain

    Tel.: +34 976 14 54 32

    Fax: +34 976 14 54 31

    [email protected]

    After-sales Department:

    Customer service: +34 976 14 54 33

    Spare parts: +34 976 14 54 34

    INDEX

    www.atlascopco.com/industrial-generator

  • QIS 330 | 400/230 V | 50HZ |

    3 / 8

    GENERAL DESCRIPTION

    Specifically developed for the industrial applications, this stationary soundproof generator set is easy to use and

    straightforward to maintain. The available features & options are designed to fully meet the requirements of all

    industrial applications. The generator set will automatically start on mains failure and cool down and stop as soon as

    the mains come back. The generator set also controls the load transfer between mains (utility) and generator set. It

    can also be start-up by means of an external signal.

    It’s your solution for Predictable Power.

    g

    ENGINEg

    Doosan diesel engine, with turbo, with direct injection and Electronic regulation of the engine.

    Engine brand DOOSAN 123Bore (mm)

    Model P126 TI-II 155Stroke (mm)

    R.P.M. 1.500 17,1:1Compression ratio

    Net power (kWm) 287 ElectronicType of regulation

    Fuel Diesel ---Europe exhaust emission

    No. of cylinders 6 L ---EPA exhaust emission

    Engine Capacity (c.c.) 11.051

    Cooling System

    Cooling of the sleeves using cooling fluid comprised of water and glycol at 50% in a closed circuit driven by the engine

    pump.

    Engine driven exhaust fan, radiator and expansion tank; original from the engine manufacturer.

    The circuit is completed with the cooling purge system towards the outside of the bedplate and protections of all running

    surfaces

    Flow of air from fan (m³/min) 450 51Coolant capacity (l)

    Cooling type Water 45ºCDesign temperature radiator

    (ºC)

    Lubrication System

    Gear pump lubrication system driven by the engine and with original engine manufacturer lubricant filtering system.

    It is completed with the oil purge system towards the outside of the baseframe.

    Oil capacity (l) 23 0,4Medium oil consumption (%

    fuel consumption)

    Air intake system

    Air intake system for combustion with filtering device and filter change indicator; originals from the engine

    manufacturer. Intake air cooling after the turbo by means of an air/air exchanger.

    Intake air flow (m³/min) 22 MediumAir inlet filter type

    www.atlascopco.com/industrial-generator

  • QIS 330 | 400/230 V | 50HZ |

    4 / 8

    Exhaust System

    The exhaust system consists of pipes, bellow, interior and exterior aluminized steel exhaust silencer that is highly

    resistant to corrosion and hot part protections. Rain cap available as an option.

    Tª gas emission (ºC) 650 4Inlet diameter (")

    Gas flow (m3/min) 51 453Body diameter (mm)

    Maximum exhaust back

    pressure (kPa)

    5,9 1.340Exhaust length (mm)

    Number of exhaust 1 26Atenuattion (dB(A))

    Outlet diameter (") 5,5

    Start system

    Start system that uses an electrical motor, battery, battery disconnector and battery charge alternator that is driven

    by the engine itself. The start motor and the battery charge alternator are originals from the engine manufacturer.

    Lead acid battery with Spiralcell® recombining technology, sealed structure to prevent leaks, maintenance free, large

    start-up capacity maintaining the voltage due to its low internal resistance and small volume thanks to its rolled plates

    design that guarantees it will withstand many discharges with large temperature changes.

    Starter voltage system (V) 24 2 x 12V 44Ah - 730ABattery type

    Fuel supply system

    Fuel intake system original from engine manufacturer with filter.

    Fuel tank capacity (L) 489

    25%

    50%

    75%

    100%

    16,7

    31

    47

    62

    17,9

    34

    51

    76

    29

    15,8

    10,5

    7,8

    27

    14,3

    9,7

    6,4

    Fuel consumption panel (range according to the standard configuration)

    LoadPrime Power (PRP) Standby Power (ESP)

    (l/h) Range (h) (l/h) Range (h)

    www.atlascopco.com/industrial-generator

  • QIS 330 | 400/230 V | 50HZ |

    5 / 8

    ALTERNATORg

    Mecc Alte alternator with 4 poles, with a lifetime lasting greased bearing, H class insulation, without brushes, 2/3 coil and

    AVR (Automatic Voltage Regulator)

    Protection of all the windings by means of 2-part high quality polyester resin impregnation. The stator windings receive a

    double impregnation. Final finish with a coat of EG43 varnish.

    Excitation system with MAUX auxiliary winding with overload capacity 3 times the nominal current for 20 s.

    Joining of engine and alternator through flexible disc coupling.

    Regulations:

    • CEI 2-3

    • IEC 34-1

    • EN 60034-1

    • VDE 0530

    • BS 4999-5000

    • CAN/CSA-C22.2 No14-68-No100-95

    • ISO 8528:3

    Low wave distribution:

    • THC < 4%

    • THD < 4%

    • THF (IEC) < 2%

    • TIF (NEMA) < 40

    Incorporates electromagnetic emissions suppressor in accordance with standard VDE 0875, class K.

    Brand MECC ALTE ±1%Voltage Stability

    Model ECO38-2L/4A 94Performance at 75% p.f.

    0.8 (%)

    Alternator Power (kVA) 330 / Standby (SB27) 94Performance at 100% p.f.

    0.8 (%)

    Number of wires 12 8,1Direct subtransient

    reactance X"d (%)

    IP Alternator IP 23 12,5Subtransient time

    constant, T"d (ms)

    Excitation system MAUX 2,3Zero sequence reactance,

    Xo (%)

    AVR model DSR 0,4Short-circuit ratio, Kcc

    www.atlascopco.com/industrial-generator

  • QIS 330 | 400/230 V | 50HZ |

    6 / 8

    BEDPLATEg

    The engine-alternator set is coupled to the bedplate by means of anti-vibration shock mounts that absorb almost all the

    vibrations.

    The base frame is made of a phosphate, passivated steel profile with polyester dust paint that guarantees a resistance of

    up to 480 hours in a saline mist chamber in accordance with standard ASM B-117-09.

    The base frame is able to hold 100% of the liquids of the genset, reducing any potential environmental impact. It has a

    drainage plug.

    SOUNDPROOFED CANOPYg

    Soundproof generator set galvanized finish using polyester dust paint.

    It is lined inside with a noise-absorbing material made of mineral wool.

    It also has an emergency shutdown pushbutton that is accessible from the outside.

    ELECTRIC PANELg

    Electrical panel integrated in the generator set with digital control plate.

    Has an all-pole circuit breaker, manually actuated, with thermal-magnetic protection against overloads and

    short-circuits.

    Circuit Breaker rated

    current (A)

    630A 4P R DSE 9255 - 24V 5ABattery charger

    Has a DEEP SEA battery charge maintainer, designed to be permanently connected to the battery and maintains it

    charged to its maximum capacity.

    Has no moving parts. The charger switches to floating mode when the charge is complete

    www.atlascopco.com/industrial-generator

  • QIS 330 | 400/230 V | 50HZ |

    7 / 8

    Control Card

    DEEP SEA control plate, DSE 7320 with grid monitor that starts-up the generator set when it detects a failure in the

    electrical power supply from the grid and sends a signal to the switching panel to switch from the grid position to the

    group position . Once the power supply has been re-established, it sends an order to the switching panel to transfer

    the generator set power to the grid and shuts-down the generator set once it has cooled down. It also starts-up the

    generator set using an external signal.

    Also, control plate DSE 7320 checks a large number of parameters of the generator set which allows it to display

    information, statuses and alarms. If required, it will shutdown the generator set: Due to high coolant fluid

    temperature, low oil pressure, low coolant fluid level, etc.

    Includes a 132x64 pixel LCD screen with lighting, 5 navigation menubuttons, independent operational mode buttons,

    and alarms and status indicating LEDs.

    Communications via USB, RS232, RS485, as well as DSEnet® for system upgrade. Possibility of Ethernet connection

    (requires a separate module). MODBUS protocol available for client software. Completely configurable using a PC in

    Windows environment and free Scada type software in real time.

    Includes reading and displaying of parameters with RMS values, real time clock, events history log up to 250 events

    and programming of alarms, events, start-ups and shutdowns.

    Operating modes: START-UP, SHUTDOWN, AUTO, MANUAL AND TEST.

    Generator

    • Generator voltage (L-N)

    • Generator voltage (L-L)

    • Generator frequency

    • Generator current

    • kW

    • kVA

    • kWh

    • kVAh

    • Power factor

    Grid

    • Grid voltage (L-N)

    • Grid voltage (L-L)

    • Grid frequency

    Engine

    • Turn speed

    • Cooling fluid temperature

    • Oil pressure

    • Hour meter

    • Battery voltage

    • No. of start-ups

    • Fuel level

    Protections

    • Start-up fault (generator set shutdown)

    • High coolant temperature (alarm and generator set

    shutdown)

    • Low oil pressure (alarm and generator set shutdown)

    • Low fuel level (alarm)

    • Low cooling fluid level (generator set shutdown)

    • Overload (alarm and generator set shutdown)

    • Battery voltage high (alarm)

    • Battery voltage low (alarm)

    • Battery charge alternator failure (alarm)

    • Generator low frequency (alarm and shutdown)

    • Generator high frequency (alarm and shutdown)

    • Generator low voltage (alarm and shutdown)

    • Generator high voltage (alarm and shutdown)

    • External emergency shutdown (shutdown)

    • Engine overspeed (shutdown)

    • Maintenance interval (alarm)

    www.atlascopco.com/industrial-generator

  • QIS 330 | 400/230 V | 50HZ |

    8 / 8

    ATSg

    Optional cabinet for switching between the grid and the generator set by means of a Socomec brand motorized switch with

    an integrated mechanical and electrical interlocking device.

    Allows for the padlock locking function. Includes a Manual / Automatic mode selector and emergency manual control.

    Safety switching for isolating the loads. High dynamic resistance against short-circuits.

    Position indicator with fully visualized cut-off. Stable positions not affected by changes in voltage and mechanical

    vibrations. External electrical control of the positions and test sequences.

    High number of operations. IP54 protection. Connections: Lower/lower.

    ATS 4P 630A 160-333V L-N CCM

    3.840

    1.470

    1.785

    2.256

    DIMENSIONS AND WEIGHT

    Lenght, L (mm)

    Width, A (mm)

    Height, H (mm)

    Weight (kg)

    g

    PERFORMANCE CLASSg

    Execution class in accordance with ISO 8528/5 (2005) taking into account the behaviour of the generator set in a

    permanent mode of operation with different load levels, as well as in a temporary mode of operation due to shocks in the

    load.

    Performance class G2

    The generator set has a CE Marking that includes the following directives:

    • 2006/42/EC Machine Safety.

    • 2014/35/EU Low Voltage.

    • 2014/30/EU Electromagnetic compatibility.

    • 2005/88/EC Noise emissions of machines outdoors in soundproof generator sets.

    Regulation (EU) 2016/1628 Gases and contaminating particles emissions only for groups within its scope of application.

    Applicable international regulations:

    • ISO 8528

    • ISO 3046

    • BS 5000

    • IEC 60034

    REGULATIONg

    www.atlascopco.com/industrial-generator

  • 24 h. FUEL TANK VERSION

    MAINTENANCE SPACE ( 1 : 40 )

    COOLING AIR FRONT OUTLET OPTION

    CoolingAir Inlet

    Cooling Air / Exhaust OUTLET

    CoolingAir Inlet

    Ed Posi-tion Modified from Date Intr./Appd.

    1 2 3 4 5 6 7 8 9

    A

    10

    B

    C

    D

    E

    F

    G

    Parent 3D model Ed . Version 3DCONF

    IDEN

    TIAL

    :Th

    is do

    cume

    nt is

    our p

    rope

    rty an

    d sha

    ll not

    witho

    ut ou

    r pur

    per

    miss

    ion be

    alter

    ed,

    copie

    d, us

    ed fo

    r man

    ufactu

    ring o

    r com

    mun

    icated

    to a

    ny ot

    her p

    erso

    n or

    comp

    any

    03 Se cambia la imagen corporativa para los QIS añadiendo la “Blue Line”19/07/2017 esfpm 02

    GC

    Fini wt.

    Approved.

    Treatment

    Material

    Name

    Drawn by

    Des checked.

    Version Drwg

    Scale

    Blank wt.

    Prod checked.

    Family

    Blank nr.

    Kg Designation Sheet

    INV

    Replaces

    Compare

    DateKg

    Drawing owner

    /

    Confidentiality Class

    STATUS

    Tolerances, if not indicated, according to:

    5789,005

    Confidential

    ESF

    acc. to 1102 K

    03

    DIMENSION DRWG WD (P126)

    Thickness:

    06/04/2016

    A1

    1 6

    1633032636

    daniel navarro

    Approved

    General tolerances

    1350K - mK

    TOTAL APROX. WEIGHT with empty tank = 3100 kgCapacity tank : 490 ltrs

    3840

    MODEL TABLE CD(50 HZ) KVA (60 HZ) KVA (50 HZ) KW (60 HZ) KW

    330 300 300 280

    9062

    0

    2263

    2620

    1455

    1335

    1456

    379

    295

    1320

    555

    1285

    1:12,5

    2620Data Plate

    Noise Label

    1100

    1160

    55

    1400

    9027

    0

    1913

    1100

    1224

    55

    1106

    820

    1500

    1400

    1500

    1000 1000

    17

    815370

    1184

    .5

    1184

    .585

    1.58

    1184

    .5

    700

    930 235235

    1285

    555

    1598

    927

    700

    700

  • Ed Posi-tion Modified from Date Intr./Appd.

    1 2 3 4 5 6 7 8 9 10

    A

    B

    C

    D

    E

    F

    G

    Parent 3D model Ed . Version 3DCONF

    IDEN

    TIAL

    :Th

    is do

    cum

    ent is

    our p

    rope

    rty an

    d sha

    ll not

    witho

    ut ou

    r per

    miss

    ion be

    alter

    ed,

    copie

    d, us

    ed fo

    r man

    ufactu

    ring o

    r com

    mun

    icated

    to a

    ny ot

    her p

    erso

    n or

    com

    pany

    .

    03 Se cambia la imagen corporativa para los QIS añadiendo la “Blue Line” esfpm 163303263619/07/2017 02Fini wt.

    Approved.

    Treatment

    Material

    Name

    Drawn by

    Des checked.

    Version Drwg

    Scale

    Blank wt.

    Prod checked.

    Family

    Blank nr.

    Kg Designation Sheet

    INV

    Replaces

    Compare

    DateKg

    Drawing owner

    /

    Confidentiality Class

    STATUS

    Tolerances, if not indicated, according to:

    5789,005

    Confidential

    ESF

    acc. to 1102 K

    03

    DIMENSION DRWG

    WD (P126)

    Thickness:

    06/04/2016

    A2

    2 6

    1633032636

    daniel navarro

    Approved

    1753 1

    912

    1640

    107

    960

    541.

    5

    101.6(4")

    1:12,5

    General tolerances

    1350K - mK

    90

    2620210

    865

    55

    1913

    1400

    270

    1778

    17541

    778

    135

    1400

    3020

    1151

    478.

    5

    gama WD=CEQI 330-300CP 300-280

  • G ( 1 : 25 )

    G

    Ed Posi-tion Modified from Date Intr./Appd.

    1 2 3 4 5 6 7 8 9 10

    A

    B

    C

    D

    E

    F

    G

    Parent 3D model Ed . Version 3DCONF

    IDEN

    TIAL

    :Th

    is do

    cum

    ent is

    our p

    rope

    rty an

    d sha

    ll not

    witho

    ut ou

    r per

    miss

    ion be

    alter

    ed,

    copie

    d, us

    ed fo

    r man

    ufactu

    ring o

    r com

    mun

    icated

    to a

    ny ot

    her p

    erso

    n or

    com

    pany

    .

    03 Se cambia la imagen corporativa para los QIS añadiendo la “Blue Line” esfpm 163303263619/07/2017 02Fini wt.

    Approved.

    Treatment

    Material

    Name

    Drawn by

    Des checked.

    Version Drwg

    Scale

    Blank wt.

    Prod checked.

    Family

    Blank nr.

    Kg Designation Sheet

    INV

    Replaces

    Compare

    DateKg

    Drawing owner

    /

    Confidentiality Class

    STATUS

    Tolerances, if not indicated, according to:

    5789,005

    Confidential

    ESF

    acc. to 1102 K

    03

    DIMENSION DRWG

    WD (P126)

    Thickness:

    06/04/2016

    A2

    3 6

    1633032636

    daniel navarro

    Approved

    55

    86596

    0

    gama WD=CE 24hQI 330-300CP 300-280

    2263

    1400

    620

    9089

    0

    470 580

    1350

    2620

    18

    185 18525

    25

    3020

    1400

    478.

    5

    1151

    101.6

  • Ed Posi-tion Modified from Date Intr./Appd.

    1 2 3 4 5 6 7 8 9 10

    A

    B

    C

    D

    E

    F

    G

    Parent 3D model Ed . Version 3DCONF

    IDEN

    TIAL

    :Th

    is do

    cum

    ent is

    our p

    rope

    rty an

    d sha

    ll not

    witho

    ut ou

    r per

    miss

    ion be

    alter

    ed,

    copie

    d, us

    ed fo

    r man

    ufactu

    ring o

    r com

    mun

    icated

    to a

    ny ot

    her p

    erso

    n or

    com

    pany

    .

    03 Se cambia la imagen corporativa para los QIS añadiendo la “Blue Line” esfpm 163303263619/07/2017 02Fini wt.

    Approved.

    Treatment

    Material

    Name

    Drawn by

    Des checked.

    Version Drwg

    Scale

    Blank wt.

    Prod checked.

    Family

    Blank nr.

    Kg Designation Sheet

    INV

    Replaces

    Compare

    DateKg

    Drawing owner

    /

    Confidentiality Class

    STATUS

    Tolerances, if not indicated, according to:

    5789,005

    Confidential

    ESF

    acc. to 1102 K

    03

    DIMENSION DRWG

    WD (P126)

    Thickness:

    06/04/2016

    A2

    4 6

    1633032636

    daniel navarro

    Approved

    BATTERIESSWITCH OFF

    FUEL PUMP

    SPIRAL BATTERY12V Ah-730A

    ADDITIONAL FUEL FILTER

    General tolerances

    1350K - mK

    gama WD=CEQIS 330-300CP 300-280

  • J ( 1:10 )

    H

    J

    Ed Posi-tion Modified from Date Intr./Appd.

    1 2 3 4 5 6 7 8 9

    A

    10

    B

    C

    D

    E

    F

    G

    Parent 3D model Ed . Version 3DCONF

    IDEN

    TIAL

    :Th

    is do

    cume

    nt is

    our p

    rope

    rty an

    d sha

    ll not

    witho

    ut ou

    r pur

    per

    miss

    ion be

    alter

    ed,

    copie

    d, us

    ed fo

    r ma n

    ufactu

    ring o

    r com

    mun

    icated

    to a

    ny ot

    her p

    erso

    n or

    comp

    any

    03 Se cambia la imagen corporativa para los QIS añadiendo la “Blue Line”19/07/2017 esfpm 02 Fini wt.Approved.

    Treatment

    Material

    Name

    Drawn by

    Des checked.

    Version Drwg

    Scale

    Blank wt.

    Prod checked.

    Family

    Blank nr.

    Kg Designation Sheet

    INV

    Replaces

    Compare

    DateKg

    Drawing owner

    /

    Confidentiality Class

    STATUS

    Tolerances, if not indicated, according to:

    5789,005

    Confidential

    ESF

    acc. to 1102 K

    03

    DIMENSION DRWG

    WD (P126)

    Thickness:

    06/04/2016

    A1

    6 6

    1633032636

    daniel navarro

    Approved

    QIS (WD) salida front 24h

    700

    930

    1170

    235235

    2263

    3840

    1400

    2620

    1350

    182525

    785 435

    1320

    295

    145

    1220

    55

    2193

    373

    353 354 353

    374

    373

    1160

    1100

    20 20

    2020

    700

    930

    100

    360

    12