AN028-Quick-GuideThySetter-ThyVisor-04-2017 QUICK-GUIDE CONNECTION TO THYTRONIC RELAYS Thisapplicationnotedescribeprocedureforsetting: CommunicationEthernetparameters(IPaddress) Relayreferencename ThisapplicationnotemakeuseofsoftwareThysetterandThyvisor,freelydownloadablefromthe websitewww.thytronic.com. Forproperinstallationbesurealsotodownloadandexecutethefile“ThytronicTemplates”availa- blein2versions(ITandENorIT,EN,RU,ESandTR)

Quick-guide connection to thytronic relays

  • Upload
    others

  • View
    15

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Quick-guide connection to thytronic relays

�AN028-Quick-Guide�ThySetter-ThyVisor-04-2017

Quick-guide connection to

thytronic relays

This�application�note�describe�procedure�for�setting:Communication�Ethernet�parameters�(IP�address)Relay�reference�name

This�application�note�make�use�of�software�Thysetter�and�Thyvisor,�freely�downloadable�from�the�website�www.thytronic.com�.For�proper�installation�be�sure�also�to�download�and�execute�the�file�“ThytronicTemplates”�availa-ble�in�2�versions�(IT�and�EN�or�IT,�EN,�RU,�ES�and�TR)

••

Page 2: Quick-guide connection to thytronic relays

2�

AN028-Quick-Guide�ThySetter-ThyVisor-04-2017

t h y s e t t e rSince�fw�version�3.40�on�device�of�family�Pro-N�and�since�version�1.50�for�device�of�the�family�Pro-NX�settings�of�Ethernet�communication�parameters�(IP�address)�and�the�relay�reference�namecan�be�changed�only�inside�menu�commands \ set Params \ set no resettable parameters.For�earlier�versions�relay�reference�name�could�be�changed�from�menu�set \ Base while�Ethernet�communication�parameters�could�be�changed�from�the�menu�communication \ ethernet.

relay reference nameRelay�reference�name�can�be�changed�from�menu�commands \ set Params \ set no resettable pa-rameters.

After�inserting�the�name�and�press�the�OK�button�you�need�to�place�the�mouse�cursor�on�the�menu�set no resettable parameters�and�send�the�command�(right�click�on�it)�to�store�the�configuration�in�the�relay�memory.

communication parameters

ETHERNETInside�of�menu�is�possible�to�read�and�change�settings�regarding�Ethernet�parameters:IP host address � � Relay�IP�addressIP net mask � � � Relay�netmask�addressIP gateway� � � � Relay� gateway� adress� (usefull� for� connection� to� external�� � � � network�or�between�2�or�more�network).

With�the�same�procedure�just�now�described�to�change�the�relay�reference�name,�after�inserting�data�and�confirming�with�OK�button�you�need�to�place�the�mouse�curso�on�the�menu�set no resetta-ble parameters�and�send�the�command�(right�click�on�it)�to�store�the�changed�configuration�in�relay�memory.

•••

Page 3: Quick-guide connection to thytronic relays

�3AN028-Quick-Guide�ThySetter-ThyVisor-04-2017

Checking IP-address

To�check�an�IP�address�is�possible�to�execute�these�commands:Start�a�DOS�session:�“Start�->�Programs�->�Prompt�MS-Dos”�or�“Start�->�Run�->�CMD”Type�the�command�“ping�-n�10�200.1.1.225”�->�Enter[1]

The�communication�is�working�properly�if�you�get�the�message�“Reply�from...”;�otherwise,�if�you�get�a�message�as�“Request�time�out”,�you�need�to�change�configuration.

Close�the�DOS�session�typing�the�command�“exit”.

setting the serial numberThe�serial�number�of�relay�is�changable�from�the�menu�command \ set Params \ set serial number.

After�changing�the�serial�number�and�confirm�with�“Enter”�key,�you�need�to�put�the�cursor�on�the�menu�set serial number�and�send�the�command�(right�mouse�click)�to�save�the�modificed�configu-ration�in�the�relay�memory.

Note � In the example you are checking the transmission of pocket with a device with IP adress 200.�.2.24�.

••

Page 4: Quick-guide connection to thytronic relays

4�

AN028-Quick-Guide�ThySetter-ThyVisor-04-2017

t h y V i s o rsetting up iP address over ethernet using thyVisor software

Starting configuration:Relay�IP�address:�127.0.0.1�(default�setting)Relay�directly�linked�to�PC�using�cross�network�cable�or�è�collegato�al�PC�direttamente�tramite�cavo�incrociato�o�indirectly�through�network�switch.

Desired IP address:200.1.2.186

The�sequence�of�actions�to�be�made�is:Take�note�of�the�relay�serial�number,�in�this�example:�183247Take�note�of�the�model�and�of�the�software�version,�in�this�example:“PRON-NV10P-E00-s”;�infor-mation�are�available�on�display�in�menu�read / infoRun� Thyvisor� (properly� installad� together� with� corrisponding� or� most� recent� version� of� Thytro-nicTemplates.exe)

Click�on�the�button�“Manage”�in�the�group�“Network”

Click� on� the� button� “Add� Device”� and� select� the� relays� family� and� the� software� version�(as�per�point�2);�in�this�example:�“PRON”�and�device�“NV10P-EXO-s”.[1]

Note � In case of relay with code E00 select EX0, in case of relay with code E02, select EX2, in case of relay with code M00 or C00 select CX0, in case of relay with code M02 or C02 select CX2, in case of relay with code D00 select DX0,

in case of relay with code D02, select DX2

••

1)2)

3)

4)

5)

Page 5: Quick-guide connection to thytronic relays

�5AN028-Quick-Guide�ThySetter-ThyVisor-04-2017

Click�on�the�button�“Add”

Keep�default�name�and�press�the�button�“Ok”

Select�the�relay�just�now�added�and�press�the�button�“Modify”

After�inserting�the�desired�IP�address�(200.1.2.186)�and�serial�number�(183247)�confirm�data�pres-sing�the�“OK”�button

6)

7)

8)

9)

Page 6: Quick-guide connection to thytronic relays

sede: 20139�Milano�-�Piazza�Mistral,�7�-�Tel.�+39�02�574�957�01�ra�-�Fax�+39�02�574�037�63stabilimento: 35127�Padova�-�Z.I.�Sud�-�Via�dell’Artigianato,�48�-�Tel.�+39�049�894�770�1�ra�-�Fax�+39�049�870�139�0

www.thytronic.it [email protected] www.thytronic.com

��Click�on�“Update�Ip”

��The�error�message�is�not�importand�and�can�be�ignored.

10)

11)