REPUBLIC ACT Revised Fire Code of the Philippines

9514

Page 2: RA 9514 - Pedrosantosjr

DISCLAIMER:

Always double-check the values given in this document with the actual laws. For corrections or clarifications, email

[email protected].

Page 3: RA 9514 - Pedrosantosjr

Repealing clause • RA 9514 repeals PD 1185 (the old Fire Code).

Page 4: RA 9514 - Pedrosantosjr

Outline of RA 9514 1. Interpretation

2. Coverage

3. Definition of terms

4. Authority of the BFP

5. Reorganization of the BFP

6. Fire brigades, safety practitioners

7. Assistance to the BFP

Page 5: RA 9514 - Pedrosantosjr

Outline of RA 9514 8. Fire safety enforcers

9. Enforcement and administration

10. Fire safety measures

11. Prohibited acts

12. Fire code taxes

13. Administrative courses of action

14. Miscellaneous provisions

Page 6: RA 9514 - Pedrosantosjr

Focus on three rules only • Rule 3: Definition of terms

• Rule 9: Enforcement/admin, because: – Inspections and evaluations

– FALAR

– FSIC

• Rule 10: Fire safety measures, because:

– Various design requirements

Page 7: RA 9514 - Pedrosantosjr

RULE 3 Definition of termsDefinition of termsDefinition of termsDefinition of terms

Page 8: RA 9514 - Pedrosantosjr

Abatement Any act that would remove or neutralize a fire hazard

Page 9: RA 9514 - Pedrosantosjr

suppression system An integrated piping system connected to a source of extinguishing agent which suppressed fires when actuated by its automatic detecting device

Automatic fire

Page 10: RA 9514 - Pedrosantosjr

Fire marshall The head of the City or the Municipal Fire Station

Page 11: RA 9514 - Pedrosantosjr

Standpipe system A system of vertical pipes in a building to which fire hoses can be attached on each floor,

Page 12: RA 9514 - Pedrosantosjr

Combination standpipe A pipeline system filled with water and connected to a constant water supply

Page 13: RA 9514 - Pedrosantosjr

Dry standpipe A standpipe system in which pipes are normally not filled with water. Water is introduced into the system through fire service connections when needed.

Page 14: RA 9514 - Pedrosantosjr

Fire alarm Any visual or audible signal produced by a device or system to warn a building’s occupants of the presence of fire

Page 15: RA 9514 - Pedrosantosjr

Fire alerting system A fire alarm system activated by the the presence of fire where the signal is transmitted to designated locations instead of sounding a general alarm

Page 16: RA 9514 - Pedrosantosjr

Fire wall A wall designed to prevent the spread of fire, having a fire resistance rating of not less than 4 hours with sufficient structural stability to remain standing even if construction on either side collapses under fire conditions

Page 17: RA 9514 - Pedrosantosjr

Flame retardant Any compound which when applied improves the resistivity or fire resistance quality of a material

Page 18: RA 9514 - Pedrosantosjr

High-rise building Buildings 15 meters or more in height

Page 19: RA 9514 - Pedrosantosjr

Horizontal exit A passageway from one building to another, through or around a wall, on approximately the same floor level

Page 20: RA 9514 - Pedrosantosjr

Means of egress A continuous and unobstructed route of exit from one point in a building to a public way

Page 21: RA 9514 - Pedrosantosjr

Occupancy The purpose for which a building or space is used

Page 22: RA 9514 - Pedrosantosjr

Occupant load The maximum number of persons that may be allowed to occupy a particular building or space

Page 23: RA 9514 - Pedrosantosjr

Overloading The use of electrical appliances which draw or consume electrical current beyond the designed capacity of the existing electrical system

Page 24: RA 9514 - Pedrosantosjr

Sprinkler system A piping system integrated in a building with outlets arranged in a systematic pattern which automatically discharges water when activated by heat or fire combustion products

Page 25: RA 9514 - Pedrosantosjr

Fire hazard Any condition or act which increases the probability of the occurrence of fire, or which may hinder or interfere with fire-fighting operations

Page 26: RA 9514 - Pedrosantosjr

Fire trap A building unsafe in case of fire because it will burn easily or because it lacks adequate exits

Page 27: RA 9514 - Pedrosantosjr

Fire lane The portion of a roadway that should be kept unobstructed at all times for the expedient operations of fire-fighting units

Page 28: RA 9514 - Pedrosantosjr

Flame spread rating Time in which flame will spread over the surface of a burning material

Page 29: RA 9514 - Pedrosantosjr

RULE 9 Enforcement of fire safety Enforcement of fire safety Enforcement of fire safety Enforcement of fire safety

measuresmeasuresmeasuresmeasures

Page 30: RA 9514 - Pedrosantosjr

General enforcement

Page 31: RA 9514 - Pedrosantosjr

General enforcement • Inspection of all buildings shall be done by

the Fire Marshall

• Fire Safety Inspection Cetrtificate (FSIC) shall be a prerequisite for permits/licenses, including: – Occupancy permit

– Business permit

Page 32: RA 9514 - Pedrosantosjr

General enforcement • The Fire Marshall and the Building Official

shall review designs/drawings and issue the Fire Safety Evaluation Clearance (FSEC) if the design is determined to be in accordance with the Fire Code

Page 33: RA 9514 - Pedrosantosjr

Evaluation and inspection

Page 34: RA 9514 - Pedrosantosjr

Building plan review • Six sets of plans are sent from the Building

Official to the Fire Marshall for review

• A plan evaluator review the drawings

• Based on findings, the FSEC will either be released or denied

• Note: FALAR 1 is required before plan review

Page 35: RA 9514 - Pedrosantosjr

Construction inspection • The Fire Marshall shall conduct inspections

during construction to ensure that plans are being followed

Page 36: RA 9514 - Pedrosantosjr

Inspection after completion • The Fire Marshall needs to conduct another

inspection before the Building Official can issue an occupancy permit

• When the Building Official receives an application for occupancy permit, the Fire Marshall shall be notified

Page 37: RA 9514 - Pedrosantosjr

Inspection after completion • Fire Marshall conducts inspection

• If OK, the Fire Marshall issues the FSIC and notifies the Building Official

• Note: FALAR 2 is required for issuance of FSIC

Page 38: RA 9514 - Pedrosantosjr

Routine inspection • Routine inspection

Page 39: RA 9514 - Pedrosantosjr

FALAR

Page 40: RA 9514 - Pedrosantosjr

What is the FALAR? • Fire and Life Safety Assessment Report

• Three kinds: – FALAR 1

– FALAR 2

– FALAR 3

Page 41: RA 9514 - Pedrosantosjr

The three FALARs • FALAR 1: Documentation on safety features

of the facility

• FALAR 2: Documentation submitted by contractor/CM certifying that construction was in accordance with FALAR 1

• FALAR 3: Documentation of periodic maintenance

Page 42: RA 9514 - Pedrosantosjr

FALAR applicability • For all buildings: – FALAR 1

– FALAR 2

• For buildings with occupant load of at least 50:

– FALAR 3 (annually)

Page 43: RA 9514 - Pedrosantosjr

FALAR 1 • Documentation on fire and life safety

features of the facility

• A written report prepared by the Architect and his Fire Protection Consultant

• A compilation of plans and specs and design analysis

Page 44: RA 9514 - Pedrosantosjr

FALAR 2 • Documentation submitted by

contractor/CM certifying that construction was in accordance with FALAR 1

• A compilation report of all approved submittals, test forms, acceptance forms

• Shall be included in the as-built documents given by contractor to owner

Page 45: RA 9514 - Pedrosantosjr

FALAR 3 • Documentation of required periodic

maintenance and upkeep of facility

• Written report prepared by the building owner, his fire safety officer

• A compilation of the maintenance and testing records

Page 46: RA 9514 - Pedrosantosjr

FSEC

Page 47: RA 9514 - Pedrosantosjr

FSEC • Fire Safety Evaluation Clearance

• Released once building plans and specs are found to be in accordance with the Fire Code

• Required for building permits

Page 48: RA 9514 - Pedrosantosjr

FSIC

Page 49: RA 9514 - Pedrosantosjr

FSIC • Fire Safety Inspection Certificate

• Certifies that the building was inspected and was found to be OK

• Required for occupancy permits, business permits, permits to operate, PHILHEALTH accreditation for hospitals, DOH License to Operate

Page 50: RA 9514 - Pedrosantosjr

Making sense of everything

Page 51: RA 9514 - Pedrosantosjr

Scenario 1: Building permit • You need a building permit, so you need an

FSEC.

• You need an FSEC, so you need a building plan review.

• You need a building plan review so you prepare FALAR 1 along with other requirements (6 sets of drawings, etc.).

Page 52: RA 9514 - Pedrosantosjr

Scenario 2: Occupancy permit • You’re done with construction so you need

an occupancy permit.

• You need an occupancy permit so you need an FSIC.

• You need an FSIC so you need an inspection.

• You want them to release FSIC after inspection so you prepare FALAR 2.

Page 53: RA 9514 - Pedrosantosjr

Scenario 3: Business permit • You need to get/renew a business permit so

you need an FSIC.

• You need an FSIC so you need an inspection.

• You want them to release the FSIC after inspection, so you prepare FALAR 3.

Page 54: RA 9514 - Pedrosantosjr

RULE 10 Fire safety measuresFire safety measuresFire safety measuresFire safety measures

Page 55: RA 9514 - Pedrosantosjr

Means of egress

Page 56: RA 9514 - Pedrosantosjr

Means of egress • A continuous, unobstructed route of exit

from any point in the building to a public way

• Shall be integral or permanently affixed to a building

• Minimum width: 915mm

Page 57: RA 9514 - Pedrosantosjr

Number of exits • For any storey, mezzanine, balcony, etc: –0-499 occupant load: 2 exits

– 500-1000 occupant load: 3 exits

– 1000 or more: 4 exits

Page 58: RA 9514 - Pedrosantosjr

Travel distance to exits • Depends on occupancy

• For individual rooms with max. O.L of 6: – 15 meters from any point in the room

Page 59: RA 9514 - Pedrosantosjr

Discharge from exits • Exits should terminate directly at a public

way or an exit discharge

–Exit discharge: Yards, courts, open spaces, etc.

• Exits that continue beyond the floor of discharge: provide an interruption

Page 60: RA 9514 - Pedrosantosjr

Headroom • Minimum of 2.00m

Page 61: RA 9514 - Pedrosantosjr

Doors • Provide a self-closing mechanism for exit

doors

• Clear opening: 710mm-1220mm

• Maximum threshold height: 13mm

Page 62: RA 9514 - Pedrosantosjr

Panic hardware • A mechanical device which when pushed

from the inside will cause the door to open

• Maximum required force: 7kg-f

• 2/3 the width of the door

• 760-112mm above the floor

Page 63: RA 9514 - Pedrosantosjr

Panic hardware • A mechanical device which when pushed

from the inside will cause the door to open

• Maximum required force: 7kg-f

• 2/3 the width of the door

• 760-112mm above the floor

Page 64: RA 9514 - Pedrosantosjr

Stairs • All stairways designated as a means of

egress should be continuous from the uppermost floor level to the ground floor

• Two sets of requirements – New stairs

– Existing stairs

Page 65: RA 9514 - Pedrosantosjr
Page 66: RA 9514 - Pedrosantosjr
Page 67: RA 9514 - Pedrosantosjr
Page 68: RA 9514 - Pedrosantosjr

Handrails • 760mm-865mm from upper surface of tread

Page 69: RA 9514 - Pedrosantosjr

Ramps

Page 70: RA 9514 - Pedrosantosjr

Fire escape stairs • Allowed as means of egress only in existing

buildings

• Should not constitute more than 50% of required exit capacity

Page 71: RA 9514 - Pedrosantosjr

Ladders • Not allowed as fire escape or means of

egress

Page 72: RA 9514 - Pedrosantosjr

Exit marking • Label all exits as “EXIT”

• Provide directional signs for locations where the direction of travel to exit is not obvious

• The word “EXIT” should be in letters at least 15cm high with strokes of letters at least 19mm wide

Page 73: RA 9514 - Pedrosantosjr

Emergency evacuation plan • Minimum dimension: letter size

• Posted in strategic and conspicuous locations

• Photoluminescent background

Page 74: RA 9514 - Pedrosantosjr

Features of fire protection

Page 75: RA 9514 - Pedrosantosjr

Protection of vertical openings

• Stairways, elevator shafts, chutes and other vertical openings shall be enclosed or protected to prevent the spread of fire, except if protected by automatic fire suppression systems

Page 76: RA 9514 - Pedrosantosjr

Sprinkler vent method

• A combination of an automatic detection system, automatic exhaust system, and an automatic water curtain

• Recommended for escalators

Page 77: RA 9514 - Pedrosantosjr

Spray nozzle method

• A combination of an automatic fire or smoke detection system and a system of high-velocity water spray nozzle

Page 78: RA 9514 - Pedrosantosjr

Partial enclosure method

• Enclose the opening (for example, escalator) with partitions. Provide door to access escalator/opening.

Page 79: RA 9514 - Pedrosantosjr

Firestopping concealed space

• Concealed space: areas in which materials have a flame-spread rating greater than Class A are exposed

• KATAMAD.

Page 80: RA 9514 - Pedrosantosjr

Fire alarms • Notifies occupants of the building and, when

required, emergency forces

• Automatic fire department notification is required for: – High rise buildings

– Hospitals

– -Schools, hotels, apartments 4 storeys or taller

– Malls

Page 81: RA 9514 - Pedrosantosjr

Wet standpipes

• Wet standpipes required for the following: – Aseembly occupancies with at least 1,000 occupant load

– Schools, hospitals, businesses, hotels, etc. 4 storeys or taller

– Hazardous occupancies exceeding 1,860 sqm per floor

• Exceptions:

– Buildings with an approved sprinkler system

Page 82: RA 9514 - Pedrosantosjr

Wet standpipes

• All portions of the building must be within 6 meters of a nozzle attached to a 22.00m long hose

• Minimum of 64mm diameter

Page 83: RA 9514 - Pedrosantosjr

Places of assembly

Page 84: RA 9514 - Pedrosantosjr

Occupant load

• Concentrated use without fixed seats, such as auditoriums, places of worship, dance floors: 0.65 sqm/person

• Less concentrated use such as conference rooms, dining rooms, gyms: 1.40sqm/person

• Standing rooms/waiting space: 0.28sqm/person

Page 85: RA 9514 - Pedrosantosjr

Mininum corridor width

• If serving 50 or more persons: 1120mm

Page 86: RA 9514 - Pedrosantosjr

Travel distance to exits

• 46 meters if with sprinkler system

• 61 meters if without sprinkler system

Page 87: RA 9514 - Pedrosantosjr

Seating

• Rows of seats back to back: 830mm

• At least 300mm from back of one seat to front of the next seat

• Seats between aisles: 14 maximum

• Seats between wall and aisle: 7

• Seats without arms: Allot 600mm/person

Page 88: RA 9514 - Pedrosantosjr

Minimum width of aisles

• If 60 seats or less, 760mm

• If more than 60 seats: –Single-loaded aisle: 915mm

–Double-loaded isle: 1220mm

• Measured farthest from exit

• Widens 25mm for each meter towards exit

Page 89: RA 9514 - Pedrosantosjr

Educational occupancies

Page 90: RA 9514 - Pedrosantosjr

Occupant loads

• Classroom: 1.80sqm/person

• Shops, laboratories: 4.60sqm/person

• Dry nurseries with sleeping facilities: 3.30sqm/person

• Rooms with greater than 50 occupants shall be treated as a place of assembly

Page 91: RA 9514 - Pedrosantosjr

Number of exits

• At least two exits from any room with capacity of 50 or more persons, or area of more than 93 sqm.

Page 92: RA 9514 - Pedrosantosjr

Travel distance to exits

• 46 meters if with sprinkler system

• 61 meters if without sprinkler system

Page 93: RA 9514 - Pedrosantosjr

Mininum corridor width

• 1.83 m

Page 94: RA 9514 - Pedrosantosjr

Special provisions for preschools

• Rooms used for preschoolers, first grade and second grade pupils shall not be located below or above the floor of exit discharge

Page 95: RA 9514 - Pedrosantosjr

Healthcare

Page 96: RA 9514 - Pedrosantosjr

Occupant loads

• Sleeping departments: 11.1sqm/person

• In-patient treatment departments: 22.3sqm/perosn

Page 97: RA 9514 - Pedrosantosjr

Door widths

• 1120mm: sleeping rooms, diagnostic and treatment rooms (surgery. X-Ray, PT, etc.)

• 910mm: All other rooms

Page 98: RA 9514 - Pedrosantosjr

Detention and correctional

Page 99: RA 9514 - Pedrosantosjr

Occupant load

• 11.1sqm/peron

Page 100: RA 9514 - Pedrosantosjr

Travel distance to exits

• Between any room door intended as exit access and an exit: 30.00m

• Between any point in the room: 46.00m

• Any point in a sleeping room to the door in that room: 10.00m

Page 101: RA 9514 - Pedrosantosjr

Residential

Page 102: RA 9514 - Pedrosantosjr

Occupant load

• 18.60sqm/person

• Except for single and two-family dwellings

Page 103: RA 9514 - Pedrosantosjr

Hotels • Minimum corridor width: 1120mm

• Minimum umber of exits: 2 for every floor

• Travel distance to exits: – From room door to exit: 30.00m

– From guest suite to corridor door: 23.00m (w/o sprinklers)

– From guest suite to corridor door: 38.00m (w/ sprinklers)

Page 104: RA 9514 - Pedrosantosjr

Apartment buildings • Minimum corridor width – For less than 50 persons: 910mm

– Fore more than 50 persons: 1120mm

• Travel distance to exits: –Within any unit to nearest exit: 15.50m, one storey away

max

– From apartment entrance to exit: 31.00m, or 46.50m if with sprinklers

Page 105: RA 9514 - Pedrosantosjr

Single and two-family dwellings • In dwellings with more than 2 rooms, every

habitable room shall have at least 2 means of escape, at least one which is a door/stairway

• No habitable room shall be accessible only by a ladder, folding stairs, or through a trap door

• Every sleeping room = 1 window min.

Page 106: RA 9514 - Pedrosantosjr

Single and two-family dwellings • No exit access from sleeping rooms to outside

shall be less than 900mm wide

• Doors in the path of travel should be 700mm minimum

Page 107: RA 9514 - Pedrosantosjr

Mercantile

Page 108: RA 9514 - Pedrosantosjr

Mercantile • Stores, markets, malls, supermarkets,

department stores, restaurants of less than 50 occupants – Class A: Gross area of 2,787sqm or more, 3 floors

– Class B: Gross area of 287-2,787sqm, 2 floors

– Class C: Gross area less than 287sqm, street floor only

Page 109: RA 9514 - Pedrosantosjr

Occupant load • Street floor or below street floor: 2.80sqm

• Upper floors: 5.60sqm

• Floors not open to public/offices: 9.30sqm

• Covered malls: 2.8sqm/person

Page 110: RA 9514 - Pedrosantosjr

Maximum travel distance • 30.00m if without sprinklers

• 46.00m if with sprinklers

Page 111: RA 9514 - Pedrosantosjr

Business

Page 112: RA 9514 - Pedrosantosjr

Business • Businesses other than mercantile

• Businesses that typically involve services and not the display and sale of merchandise

• Examples: Doctor/lawyer/dentist’s office, internet shops, barbershops, general offices

Page 113: RA 9514 - Pedrosantosjr

Occupant load • 9.30sqm/person

Page 114: RA 9514 - Pedrosantosjr

Travel distance to exit • 46.00m if without sprinklers

• 61.00m if with sprinklers

Page 115: RA 9514 - Pedrosantosjr

High rise buildings

Page 116: RA 9514 - Pedrosantosjr

High rise buildings • A building in which the distance between the

floor of the topmost storey and the ground level is 15.00m or more

• Building height shall be measured from the lowest level of fire department vehicle access, to the floor of the highest occupiable storey

Page 117: RA 9514 - Pedrosantosjr

Sprinkler requirements • All high rise buildings shall be provided with a

fully electrically supervised sprinkler system

Page 118: RA 9514 - Pedrosantosjr

Other occupancies

Page 119: RA 9514 - Pedrosantosjr

Industrial • Occupant load: 9.30sqm/person

• Minimum corridor width: 1120mm

• Travel distance: – 31.00m if no sprinklers

– 46.00m if with sprinklers

Page 120: RA 9514 - Pedrosantosjr
Page 121: RA 9514 - Pedrosantosjr

Exit capacity • The capacity of an exit is measured in terms

of its width –Width of level components (corridors/ramps)

–Width of non-level components (stairways)

• This width is based on how many people will need to pass (width/person)

Page 122: RA 9514 - Pedrosantosjr
Page 123: RA 9514 - Pedrosantosjr

Occupant load • Maximum number of persons allowed to

occupy a space at any time

• Floor area/occupant load factor

Page 124: RA 9514 - Pedrosantosjr

Occupant load • Maximum number of persons allowed to

occupy a space at any time

• Floor area/occupant load factor

Page 125: RA 9514 - Pedrosantosjr

Features of fire protection

Page 126: RA 9514 - Pedrosantosjr

Places of assembly

Page 127: RA 9514 - Pedrosantosjr

Educational occupancies

Page 128: RA 9514 - Pedrosantosjr

Healthcare

Page 129: RA 9514 - Pedrosantosjr

Healthcare