Upload
others
View
4
Download
0
Embed Size (px)
Citation preview
1
© NAFED 2015. All Rights Reserved.
© NAFED 2015. All Rights Reserved.
Recharge of Portable Fire Extinguishers
A Service Guide
© NAFED 2015. All Rights Reserved.
The National Association of Fire Equipment Distributors (NAFED) Online Fire Extinguisher Service Training Program is a practical training program that must be supplemented with actual hands-on training provided by the service company, NAFED University, and other sources.
This program was written by NAFED members utilizing their own experiences to provide proper procedures for the servicing and maintenance of portable fire extinguishers.
NAFED strongly suggests that all service personnel procure a copy of NFPA-10, Portable Fire Extinguishers, current edition. This standard is available from the National Fire Protection Association at www.nfpa.org. This is the internationally recognized standard for the selection, maintenance, and testing of portable fire extinguisher equipment. Its content should be familiar to all service personnel in the fire protection equipment industry.
2
© NAFED 2015. All Rights Reserved.
These programs are intended to be a general guide to the servicing of portable fire extinguishers. All service personnel should secure manufacturers’ service manuals for specific types of extinguishers and be familiar with state and local ordinances regarding extinguishers.
It is important that all service personnel follow the manufacturers’ recommended procedures when servicing any type of portable fire equipment. The information and servicing procedures presented in this program have been compiled from educated sources and currently available information.
However, the suggested practices explained in this program generally reflect the minimum maintenance requirements expressed in NFPA-10. Please review the specific requirements of your local jurisdiction because various jurisdictions may require different procedures.
© NAFED 2015. All Rights Reserved.
NAFED assumes no liability or responsibility in connection with the information, procedures, and recommendations contained herein and expressly disclaims any liability for damages, compensatory, consequential or other, in contract or in tort, arising out of or related to the use of any information in this program. The information herein is general, and not specific to any manufacturers’ products. It should not be assumed that every acceptable safety procedure or method, precaution, equipment, or device is contained within, or that unusual circumstances may not require further procedures or requirements.
Photographs used in this program are included strictly to illustrate specific training points. Use of these photographs does not constitute an endorsement by NAFED of any product or equipment shown.
© NAFED 2015. All Rights Reserved.
Throughout this presentation the term “UL” also refers to CAN/ULC.
The terms “state” or “local” can also refer to Canadian provinces or provincial regulations.
Notes
3
© NAFED 2015. All Rights Reserved.
Standards NFPA-10, currently published edition, is the standard for maintaining and servicing fire extinguishers. Local regulations, as well as those of the State Fire Marshal, provincial regulations, and other authorities having jurisdiction shall also be followed.
© NAFED 2015. All Rights Reserved.
Always read, understand, and follow the manufacturer’s service manual for the specific unit you are servicing.
Different manufacturers may have slightly different procedures on certain units.
Always use only those parts and materials specified in the manufacturer’s manuals.
© NAFED 2015. All Rights Reserved.
Safety Safety cannot be overemphasized. NAFED will always instruct that safety glasses are a requirement of the job because of the environment you will be training and eventually working in.
4
© NAFED 2015. All Rights Reserved.
Obsolete Extinguishers
© NAFED 2015. All Rights Reserved.
Extinguishers that shall not be maintained and must be permanently removed from service:
1. Soda acid 2. Chemical foam (excluding film-forming agents) 3. Vaporizing liquid (e.g., carbon tetrachloride) 4. Cartridge-operated water 5. Cartridge-operated loaded stream 6. Copper or brass shell (excluding pump tanks) joined by soft
solder or rivets 7. Carbon dioxide extinguishers with metal horns 8. Solid charge-type AFFF extinguishers (paper cartridge) 9. Pressurized water fire extinguishers manufactured prior to
1971
© NAFED 2015. All Rights Reserved.
10. Any extinguisher that needs to be inverted to operate 11. Any stored pressure extinguisher manufactured prior to
1955 12. Any extinguishers with 4B, 6B, 8B, 12B, and 16B fire
ratings 13. Stored-pressure water extinguishers with fiberglass shells
(pre-1976)
Extinguisher removal, continued
5
© NAFED 2015. All Rights Reserved.
Additionally, dry chemical stored-pressure extinguishers with an indicated manufacturing date of 1984 or prior shall be removed from service.
© NAFED 2015. All Rights Reserved.
4
3 2 1
5
Obsolete Units
6
© NAFED 2015. All Rights Reserved.
It must be removed from service.
You may not hydrotest.
You may not recharge.
You may not service in any way. When disposing of these types of obsolete fire extinguishers follow all local, state, and provincial regulations in an environmentally responsible manner.
If you find an obsolete fire extinguisher:
6
© NAFED 2015. All Rights Reserved.
Additionally, NFPA-10 mandates that an extinguisher that may no longer be serviced in accordance with its listing is “obsolete.”
An example would be an extinguisher made by a company no longer in business.
This would also include extinguishers for which parts are no longer available.
© NAFED 2015. All Rights Reserved.
This presentation is designed to cover the following type of fire extinguishers: • Stored Pressure Dry Chemical
• Clean Agent • Carbon Dioxide (CO2) • Stored Pressure Water
Each will be covered in a separate section.
© NAFED 2015. All Rights Reserved.
All service procedures are shown in a service facility setting.
Servicing in a mobile facility or vehicle will follow the same general procedures.
Equipment shown is for illustration only and NAFED does not endorse any specific equipment or manufacturer.
7
© NAFED 2015. All Rights Reserved.
Stored Pressure Dry Chemical Recharge Procedures
This section will cover stored pressure dry chemical extinguishers and the related equipment necessary to recharge them.
© NAFED 2015. All Rights Reserved.
Equipment and Tools
© NAFED 2015. All Rights Reserved.
Certain tools and equipment are needed for proper recharging.
Examples of such equipment are presented here, although other options may be available.
A clean, ordered, well-lit work area is essential.
8
© NAFED 2015. All Rights Reserved.
Equipment and Tools All dry chemical extinguishers are filled by weight using a suitable scale (legal for trade)
© NAFED 2015. All Rights Reserved.
A suitable work area is required.
Note the anti-fatigue mats on the floor.
Equipment and Tools
© NAFED 2015. All Rights Reserved.
Dust masks and ventilation to the outside should be required for a safe recharging environment.
Equipment and Tools
9
© NAFED 2015. All Rights Reserved.
An NFPA-10 compliant source of pressuring gas must be provided.
Equipment and Tools
© NAFED 2015. All Rights Reserved.
Hand tools, as needed, include wrenches, pliers, rags, brushes etc.
A non-serrated wrench is also required.
Equipment and Tools
© NAFED 2015. All Rights Reserved.
Dry chemical may be introduced into the cylinder by scoop and funnel, vacu-fill type machines, or other approved methods. If using fixed machines, it is essential to keep different types of dry chemical separated to prevent contamination.
Equipment and Tools
10
© NAFED 2015. All Rights Reserved.
Example of a service shop
© NAFED 2015. All Rights Reserved.
Each facility may be different. Facility shown in this presentation is an example.
Mobile shops will contain similar equipment.
Make certain to read, understand, and follow the various equipment manufacturer's manuals and observe all safety precautions.
© NAFED 2015. All Rights Reserved.
Caution This training shows a typical dry chemical extinguisher recharge.
NFPA-10 requires that the procedures and instructions in the manufacturer’s manual be followed.
Please ensure that you have a current manual and follow the manufacturer’s specific model instructions.
11
© NAFED 2015. All Rights Reserved.
The procedures involved include:
• Safety and checking for pressure
• Removal and disassembly of the valve and components
• Reassembly of valve and components & clean
• Internal inspection of cylinder
• Filling the unit safely and correctly
• Reassembly procedures
• Pressurizing
• Leak checks
Each of these will be covered separately
Basic Procedures
© NAFED 2015. All Rights Reserved.
Warning:
Prior to recharging an extinguisher, personnel should be thoroughly familiar with the contents of the manufacture manual to recognize any equipment conditions or discrepancies that might prohibit the recharge of the extinguisher or direct further equipment maintenance or repair.
© NAFED 2015. All Rights Reserved.
Extinguishers may contain pressure even if the gauge shows empty. The first step is to determine if there is pressure.
Caution
Pressure both visually via the pressure gauge and mechanically via the proper recharge procedures you will learn during this training.
12
© NAFED 2015. All Rights Reserved.
Check to make certain there is no pressure by inverting the unit (so any remaining agent falls toward the valve). Then wait 10 seconds, control the end of the hose, and slowly open the valve.
A “puff” is normal.
CLIP 3 STORED PRESSURE
© NAFED 2015. All Rights Reserved.
NOTE: Make sure to point the hose up and away from you.
An alternative is to connect the unit to an approved discharge hopper or device or to a “blow out” bag.
Several equipment manufacturers make these pieces of equipment.
PHOTOS ©BROOKS EQUIPMENT
© NAFED 2015. All Rights Reserved.
Read, use, and follow the manufacturer’s service manual.
13
© NAFED 2015. All Rights Reserved.
The date of manufacture may be located in different places on different units.
Check the date of manufacture. Always verify every cylinders hydrostatic testing date before recharging.
© NAFED 2015. All Rights Reserved.
Visually examine the extinguisher for any signs of damage, wear, dents, corrosion, missing labels or other conditions which might prohibit the unit from being recharged. If necessary remove extinguisher from service.
© NAFED 2015. All Rights Reserved.
Removal of Valve Assembly Unscrew and remove the discharge hose from the valve assembly.
Slowly unscrew the discharge valve assembly from the agent cylinder.
Note: When disassembling many fire extinguishers at the same time, they should always be tagged or referenced so they remain matched to the specific cylinder that they were removed from. This will keep the orientation of the gauge facing the front of the fire extinguisher when screwed back on.
14
© NAFED 2015. All Rights Reserved.
Check the agent type discoloration or contaminants – NFPA 10 7.8.3.4 Dry Chemical Agent Re-Use. 7.8.3.4.1 The dry chemical agent shall be permitted to be reused, provided a closed recovery system is used and the agent is stored in a sealed container to prevent contamination. 7.8.3.4.2 Prior to re-use, the dry chemical shall be thoroughly checked for the proper type, contamination, and condition. 7.8.3.4.3 Where doubt exists with respect to the type, contamination, or condition of the dry chemical, the dry chemical shall be discarded
© NAFED 2015. All Rights Reserved.
Dry Chemical Agent – Caking Vs Packing
“Take a piece of the suspected dry chemical. Hold it 6 inches over a hard surface (a concrete floor for example) and drop it. If it shatters into powder - then the chemical was packed (compressed). If not, it is caked and must be discarded”
© NAFED 2015. All Rights Reserved.
Disassembly of Valve Assembly Remove the discharge valve assembly from the agent cylinder. Disassemble the siphon tube and remove the spring and discharge valve stem. Ensure siphon tube is unobstructed.
15
© NAFED 2015. All Rights Reserved.
Cleaning of Valve Assembly Closely examine all components to ensure they are not damaged, cracked or worn. Remove the O-ring and examine it to ensure it is not cut, cracked or deformed (Replace if necessary) Use rags and/or brushes for cleaning
© NAFED 2015. All Rights Reserved.
Lubrication of Valve Stem Examine the valve stem to ensure it is not bent or corroded. Ensure the rubber seat is not cut, damaged or deformed (Replace as necessary)
Lubricate O-ring with a light coat of silicone grease.
© NAFED 2015. All Rights Reserved.
Reassemble the Valve Stem Properly reassemble the valve assembly. Ensure the valve stem, spring and siphon tube are correctly installed and securely tightened.
16
© NAFED 2015. All Rights Reserved.
Filling the Cylinder
© NAFED 2015. All Rights Reserved.
Filling the Cylinder Add the proper type and quantity of dry chemical agent specified on the extinguisher nameplate recharge instructions.
© NAFED 2015. All Rights Reserved.
Filling the Cylinder Complete the required information on the verification of service collar, and place over the neck of the cylinder.
17
© NAFED 2015. All Rights Reserved.
Filling the Cylinder Reinstall the discharge valve assembly into the agent cylinder.
Ensure the valve is properly snugged down.
Pressure gauge facing the front of the cylinder. Weigh the extinguisher to verify the total extinguisher weight falls within the tolerance limitations indicated on the nameplate.
© NAFED 2015. All Rights Reserved.
Pressurizing the Cylinder
© NAFED 2015. All Rights Reserved.
SAFETY GLASSES SHALL BE WORN FOR ALL INSPECTION,
MAINTENANCE AND RECHARGE PROCEDURES AT ALL TIMES.
A SAFETY NOTE
18
NFPA 10 Standard for Portable Fire Extinguishers 2018 Edition
7.1.2.1* Persons performing maintenance and recharging of extinguishers shall be certified. 7.1.2.2 Persons performing maintenance and recharging of extinguishers shall be trained and shall have available the appropriate manufacturer’s servicing manual(s), the correct tools, recharge materials, lubricants, and manufacturer’s replacement parts or parts specifically listed for use in the fire extinguisher.
FROM NFPA-10
7.8.4.1 Only standard industrial-grade nitrogen with a maximum dew point of −60°F (−51°C), in accordance with CGA G-10.1, Commodity Specification for Nitrogen, shall be used to pressurize stored-pressure dry chemical and halogenated-type fire extinguishers that use nitrogen as a propellant.
FROM NFPA-10
19
7.8.4.2 Halogenated-type fire extinguishers that require argon shall be pressurized with argon with a dew point of −65°F (−54°C) or lower. 7.8.4.3 Compressed air shall be permitted to be used from special compressor systems capable of delivering air with a dew point of −60°F (−51°C) or lower. (See Annex J.) 7.8.4.5 A rechargeable stored-pressure-type fire extinguisher shall be pressurized only to the charging pressure specified on the fire extinguisher nameplate.
FROM NFPA-10
7.8.1.2* When recharging is performed, the manufacturer’s service manual shall be followed. (For recharge agents, see 7.8.3.) From one manufacturer’s manual
From a Manufacturer’s Manual
Connect a regulated nitrogen source, pre-set to 25 P.S.I. over intended charging pressure stated on the extinguisher nameplate, and pressurize the unit by opening the pressure valve and depressing the extinguisher operating lever. Refer to the calibrated charging pressure gauge to determine the charge pressure. Do not rely on the extinguisher gauge for charging pressure. Close the pressurization valve and release the extinguisher operating lever once the proper charge pressure has been reached. Bleed off the charging line pressure by opening the bleed valve.
From another Manufacturer’s Manual Install the proper manufacturer’s pressurization charge adapter into the discharge valve outlet port. Using a regulated source of dry nitrogen containing a calibrated pressure gauge, depress operating leverand slowly pressurize the extinguisher to pressure indicated on the nameplate. Reference the calibrated pressurization gauge for proper charge.
20
OTHER MANUFACTURES’ MANUALS HAVE SIMILAR WORDING. YOU SHOULD NEVER USE THE EXTINGUISHER GAUGE AS THE MEANS FOR DETERMINING CORRECT PRESSURIZATION.
IT’S NOT A “GAUGE” BUT AN INDICATOR IT INDICATES ONLY A RANGE – NOT A NUMERIC
VALUE
MANUFACTURER’S MANUALS STATE “DO NOT RELY ON THE GAUGE FOR DETERMINING CORRECT CHARGING PRESSURE.”
DETERMINE RECHARGE PRESSURE
NOTE: DIFFERENT EXTINGUISHERS MAY HAVE DIFFERENT CHARGING PRESSURES EVEN FROM THE SAME MANUFACTURER.
TO DETERMINE THE CHARGING PRESSURE NEEDED FOR THE EXTINGUISHER (SEE NAMEPLATE)
7.8.4.5.2 A regulated source of pressure, set no higher than 25 psi (172 kPa) above the operating (service) pressure, shall be used to pressurize fire extinguishers. 7.8.4.5.3 The gauge used to set the regulated source of pressure shall be calibrated at least annually. 7.8.4.6* An unregulated source of pressure, such as a nitrogen cylinder without a pressure regulator, shall not be used.
21
N2 CYLINDER
REGULATOR ASSY.
SAFETY RELIEF
CHARGING LINE
RECHARGE ADAPTER
CALIBRATED GAUGE
CHARGING VALVE
BLEED OFF VALVE
CHECK VALVE
CORRECT PRESSURIZATION
© NAFED 2015. All Rights Reserved.
NOTE DIRECTION OF CHECK VALVE
VERIFY “ZERO” - OPEN N2 CYLINDER
22
OPEN CHARGING VALVE
ADJUST REGULATOR AS NEEDED
© NAFED 2015. All Rights Reserved.
Set regulator to no more than
25 PSI over extinguisher's
service pressure. (Do not rely the gauge on the fire
extinguisher) A GOOD RULE
IS 10-15 PSI MAX.
23
© NAFED 2015. All Rights Reserved.
NOTE: GAUGE USED TO SET THE
REGULATED SOURCE MUST BE
CALIBRATED AT LEAST ANNUALLY
CALIBRATED GAUGE
© NAFED 2015. All Rights Reserved.
CLOSE CHARGING VALVE
© NAFED 2015. All Rights Reserved.
VENT DISCHARGE LINE PRESSURE
24
© NAFED 2015. All Rights Reserved.
CLOSE VENT LINE
© NAFED 2015. All Rights Reserved.
CONNECT EXTINGUISHER TO CHARGING LINE 7.8.4.5.1 The manufacturer’s pressurizing adapter shall be connected to the valve assembly before the fire extinguisher is pressurized.
© NAFED 2015. All Rights Reserved.
DEPRESS EXTINGUISHER HANDLE FULLY
25
© NAFED 2015. All Rights Reserved.
SLOWLY OPEN CHARGING VALVE
© NAFED 2015. All Rights Reserved.
SAFETY ALERT
NOTE: Charge pressure should be applied slowly.
IT IS NORMAL TO EXPECT A HOP OR NOISE AS PRESSURE LIFTS THE DRY CHEMICAL OFF THE
BOTTOM OF THE EXTINGUISHER
During recharge, dry chemical agent can accumulate and pack within the siphon tube. If
extinguisher pressurization is obtained too quickly it may indicate a plugged siphon tube.
© NAFED 2015. All Rights Reserved.
RELEASE EXTINGUISHER VALVE AT CORRECT PRESSURE
26
© NAFED 2015. All Rights Reserved.
INSERT RING PIN IN EXTINGUISHER
© NAFED 2015. All Rights Reserved.
OPEN VENT VALVE SLOWLY
© NAFED 2015. All Rights Reserved.
DISCONNECT CHARGING LINE
27
© NAFED 2015. All Rights Reserved.
VERIFY GAUGE IN CORRECT RANGE
© NAFED 2015. All Rights Reserved.
Each cylinder must be checked for leaks using either a hot water bath or leak check fluid.
Failure to properly check for leaks may result in loss of pressure for the extinguisher.
LEAK TESTING THE CYLINDER
© NAFED 2015. All Rights Reserved.
Attach the required service tag and complete the other documentation as required.
28
© NAFED 2015. All Rights Reserved.
Complete and attach the six-year maintenance label, if applicable.
The label is installed normally on the back or side of the fire extinguisher, but never over the top of a manufacturer’s label, and NEVER on the front of the extinguisher.
Remember to:
© NAFED 2015. All Rights Reserved.
Recheck the unit to ensure there are no leaks.
Return unit to service.
© NAFED 2015. All Rights Reserved.
Safety points to remember
29
© NAFED 2015. All Rights Reserved.
Never try to remove the valve to release pressure!
This is extremely dangerous.
The valve can suddenly and violently “blast off” from the cylinder, causing serious injury.
SAFETY WARNING
© NAFED 2015. All Rights Reserved.
Gauges may show “no pressure” even if the cylinder is fully charged.
Always check for pressure.
SAFETY WARNING
© NAFED 2015. All Rights Reserved.
Always wear your safety glasses.
SAFETY WARNING
30
© NAFED 2015. All Rights Reserved.
Stored Pressure Clean Agent Recharge Procedures
This section will cover stored pressure Clean Agent extinguishers and the related equipment necessary to recharge them.
© NAFED 2015. All Rights Reserved.
Equipment and Tools In Addition to the tools while working on Dry
Chemical extinguishers you will need…
© NAFED 2015. All Rights Reserved.
Clean Agent recovery machines, or other approved methods shall be used.
Equipment and Tools
31
© NAFED 2015. All Rights Reserved.
The process of charging fire extinguishers with clean agent involves working with a pressurized liquid and high pressure gas, so it should only be undertaken by trained personnel.
The procedures for recovering clean agents are similar in most respects, there are two main differences:
The type of O-rings and valve stems used (In the recovery machine, and parts used in the fire extinguisher)
Rubber used for Halon are not compatible with Halotron, if incompatible rubber are used, the result can be loss of extinguisher pressure or blockage of the valve preventing proper discharge.
Equipment and Tools
© NAFED 2015. All Rights Reserved.
Example of a service shop
© NAFED 2015. All Rights Reserved.
The process of filling extinguishers and bulk recharge cylinders with clean agents involves the use of a pressurized liquid and high pressure gas. The process should only be undertaken by personnel trained in the use of these kinds of materials. High pressure (compressed) gases can be extremely dangerous if not handled properly. Improperly installed or maintained pressure regulators or hose assemblies can cause system failures and result in possible personal injury.
A. Chemical Hazards
Measures should be taken to minimize inhalation of any vapors.
FILLING OPERATIONS SHOULD BE CONDUCTED IN A WELL VENTILATED ENVIRONMENT. B. Personal Protective Equipment
To insure proper protection, it is recommended that standard equipment for handling compressed gases and refrigerants be used for filling operations. This would include the use of rubber gloves and eye goggles.
All containers (including high pressure gas cylinders) used in filling operations should be secured to stationary objects to prevent uncontrolled movement.
NOTE: Consult the clean agent Safety Data Sheet (SDS) for more safety information.
SAFETY PRECAUTIONS
32
© NAFED 2015. All Rights Reserved.
FILLING/AGENT RECOVERY PRINICPLES It is imperative that before performing filling or agent recovery procedures, the following guidelines are followed:
1. All of the Maintenance Procedures detailed in the Service Manual be completed.
2. All extinguisher components and filling equipment components are compatible for use with the clean agent.
Extinguisher filling/agent recovery should be performed only by trained technicians. Manufacturer parts and service equipment should be used in the performance of these procedures.
All equipment should be maintained dry and free of moisture.
The general filling procedure follows three basic steps:
1. Extinguisher evacuation
2. Clean agent filling (liquid transfer)
3. Extinguisher final pressurization
SAFETY PRECAUTIONS
© NAFED 2015. All Rights Reserved.
Evacuation Principals The fire extinguisher needs emptying including the fumes/vapors 1. To remove moist air from the cylinder, which if present can cause corrosion. 2. To accelerate the filling process by removing some of the back pressure that results from entrapped air. The vacuum pump selected should be capable of pulling a minimum vacuum of 27 inches (686 mm) mercury. 3. Halon 1211 has to be recovered using a recovery machine. Per NFPA 10 (2018) 7.8.3.8.1
© NAFED 2015. All Rights Reserved.
Removal of Valve Assembly
33
© NAFED 2015. All Rights Reserved.
Cleaning Valve Assembly
© NAFED 2015. All Rights Reserved.
Complete the required information on the verification of service collar.
© NAFED 2015. All Rights Reserved.
Reinstall Valve Assembly
34
© NAFED 2015. All Rights Reserved.
Once the extinguisher valve assembly has been rebuilt, it is ready to be filled with clean agent. The filling lines and quick connect used in the filling process should be compatible with the type of clean agent being used.
One of the key differences between Halon and Halotron is that the Halotron bulk supply cylinder must be kept under pressure during the transfer of liquid from the bulk supply cylinder to an extinguisher. Halotron is a blend of two gases forced into the extinguisher by pressure. To insure that the uniformity of the Halotron stays consistent during transfer, a supply of argon must be connected to the Halotron bulk supply cylinder to maintain a minimum pressure of 95 psig (655 kPa). This is easily accomplished with a high pressure argon cylinder and a regulator.
No pumps are necessary to transfer the Halotron liquid into the extinguishers (Which is not the case with Halon) the transfer can be completed by connecting the filling hose to the extinguisher and opening the extinguisher valve. Once the extinguisher valve is opened, the pressure difference will allow the Halotron to fill the extinguisher.
The pump on your recovery machine will transfer Halon liquid/vapors into the extinguisher.
Filling (Liquid Transfer)
© NAFED 2015. All Rights Reserved.
Steps for Liquid & Pressure Recharge Step 1. Place empty cylinder onto scale and hook up to recovery machine
© NAFED 2015. All Rights Reserved.
Steps for Liquid & Pressure Recharge Step 2. Open the liquid valve from recovery machine
35
© NAFED 2015. All Rights Reserved.
Steps for Liquid & Pressure Recharge Step 3. Fill with the correct weight of clean agent
© NAFED 2015. All Rights Reserved.
Steps for Liquid & Pressure Recharge Step 4. Fill with the correct weight of clean agent
© NAFED 2015. All Rights Reserved.
Steps for Liquid & Pressure Recharge Step 5 Close the liquid valve and open the pressure valve to pressurize the fire extinguisher, remove handle clamp, and, pull a vacuum on the fire extinguisher.
36
© NAFED 2015. All Rights Reserved.
Steps for Liquid & Pressure Recharge Step 6. Reinstall hose, seal pull pin, and tag.
© NAFED 2015. All Rights Reserved.
Safety points to remember
© NAFED 2015. All Rights Reserved.
Never try to remove the valve to release pressure!
This is extremely dangerous.
The valve can suddenly and violently “blast off” from the cylinder, causing serious injury.
SAFETY WARNING
37
© NAFED 2015. All Rights Reserved.
Gauges may show “no pressure” even if the cylinder is fully charged.
Always check for pressure.
SAFETY WARNING
© NAFED 2015. All Rights Reserved.
Always wear your safety glasses.
SAFETY WARNING
© NAFED 2015. All Rights Reserved.
Carbon Dioxide (CO2) Recharge Procedures
This section will cover stored pressure Carbon Dioxide (CO2) extinguishers and the related equipment necessary to recharge them.
38
© NAFED 2015. All Rights Reserved.
Equipment and Tools In Addition to the tools while working on Dry
Chemical extinguishers you will need…
© NAFED 2015. All Rights Reserved.
CO2 Transfer pump, or other approved methods shall be used.
Equipment and Tools
© NAFED 2015. All Rights Reserved.
The process of charging fire extinguishers with CO2 involves working with a pressurized liquid and high pressure gas, so it should only be undertaken by trained personnel.
Safety glasses and gloves shall be used.
Equipment and Tools
39
© NAFED 2015. All Rights Reserved.
Sufficient concentrations of discharged carbon dioxide will reduce oxygen and cause
unconsciousness or even death. Avoid discharging carbon dioxide agent into any
occupied small or unventilated spaces.
Note: The discharge of carbon dioxide (CO2) will be very cold and may cause
frostbite to unprotected skin. Avoid touching or holding cold areas of the discharge horn
during use.
WARNING
© NAFED 2015. All Rights Reserved.
Prior to servicing or recharging a CO2 extinguisher, personnel should be
thoroughly familiar with the contents of the manufacturer’s manual to recognize any
equipment conditions or discrepancies that might dictate or prohibit further equipment
maintenance or repair.
WARNING
© NAFED 2015. All Rights Reserved.
To avoid personal injury or death, always ensure all pressure is properly relieved from
an extinguisher prior to attempting any service, repair or recharge.
WARNING
40
© NAFED 2015. All Rights Reserved.
1. In a well ventilated area, secure the nozzle and slowly squeeze the discharge lever to discharge any remaining agent and remove pressure from the extinguisher.
2. Check the hydro-test date before refilling.
3. Visually examine the extinguisher for signs of damage, wear, corrosion, or other conditions that might prohibit the unit from being recharged.
Recharge Instructions
© NAFED 2015. All Rights Reserved.
4. Remove the hose/horn, closely examine the hose assembly, discharge horn and couplings for any damage, wear, or conditions that might affect its proper function.
5. Examine the valve assembly (including safety relief assembly) ensure it is not damaged, corroded or obstructed.
Note: If replacement of safety relief is required, the extinguisher must first be emptied.
Recharge Instructions
© NAFED 2015. All Rights Reserved.
Attaching to transfer pump
41
© NAFED 2015. All Rights Reserved.
Open valves and turn on transfer pump
© NAFED 2015. All Rights Reserved.
Once filled perform a leak check.
© NAFED 2015. All Rights Reserved.
Safety points to remember
42
© NAFED 2015. All Rights Reserved.
To avoid personal injury or death, always ensure all pressure is properly relieved from
an extinguisher prior to attempting any service, repair or recharge.
Avoid discharging carbon dioxide agent into any occupied small or unventilated spaces.
SAFETY WARNING
© NAFED 2015. All Rights Reserved.
Always wear your safety glasses & gloves
SAFETY WARNING
© NAFED 2015. All Rights Reserved.
Stored Pressure Water Recharge Procedures
This section will cover stored pressure water extinguishers and the related equipment necessary to recharge them.
43
© NAFED 2015. All Rights Reserved.
Equipment and Tools. Use the same tools
found on the slides from the Stored Pressure Dry Chemical section of this
presentation.
© NAFED 2015. All Rights Reserved.
Caution This training shows a typical stored pressure water extinguisher recharge.
NFPA-10 requires that the procedures and instructions in the manufacturer’s manual be followed.
Please ensure that you have a current manual and follow the manufacturer’s specific model instructions.
© NAFED 2015. All Rights Reserved.
Caution Prior to recharging an extinguisher, properly trained personnel should be thoroughly familiar with the contents of the manufacture manual to recognize any equipment conditions or discrepancies that might prohibit the recharge of the extinguisher or direct further equipment maintenance or repair.
44
© NAFED 2015. All Rights Reserved.
Caution: Invert the extinguisher, then while securing and pointing the nozzle in a safe direction, squeeze the operating valve lever to remove all remaining pressure from the extinguisher.
Warning: To prevent injury or death, always ensure all pressure is properly relieved from an extinguisher prior to attempting any service, repair or recharge.
© NAFED 2015. All Rights Reserved.
Visually examine the extinguisher for any signs of damage, wear, dents, corrosion, missing labels or other conditions which might prohibit the unit from being recharged. Check that the hydro test date is still current. If necessary, remove extinguisher from service.
© NAFED 2015. All Rights Reserved.
Removal of Valve Assembly
45
© NAFED 2015. All Rights Reserved.
Cleaning Valve Assembly
© NAFED 2015. All Rights Reserved.
Filling the Cylinder NOTE: Some water extinguishers have a “Fill Tube” while others have a “Fill Mark” on the cylinders. Check manufactures manual(s)
© NAFED 2015. All Rights Reserved.
Filling the Cylinder Complete the required information on the verification of service collar, and place over the neck of the cylinder.
46
© NAFED 2015. All Rights Reserved.
Filling the Cylinder Once filled to the correct the fill mark, reinstall the valve assembly. Ensure the valve is properly snugged down. Pressure gauge facing the front of the cylinder.
© NAFED 2015. All Rights Reserved.
Pressurizing the Cylinder
© NAFED 2015. All Rights Reserved.
SAFETY GLASSES SHALL BE WORN FOR ALL INSPECTION,
MAINTENANCE AND RECHARGE PROCEDURES AT ALL TIMES.
A SAFETY NOTE
47
© NAFED 2015. All Rights Reserved.
Pressurizing the Cylinder Some extinguishers are pressurized using the refill valve in the back of the valve assembly, others are pressurized via the discharge outlet
© NAFED 2015. All Rights Reserved.
Each cylinder must be checked for leaks using either a hot water bath or leak check fluid.
Failure to properly check for leaks may result in loss of pressure for the extinguisher.
LEAK TESTING THE CYLINDER
© NAFED 2015. All Rights Reserved.
Reinstall the discharge hose
48
© NAFED 2015. All Rights Reserved.
Safety points to remember
© NAFED 2015. All Rights Reserved.
Never try to remove the valve to release pressure!
This is extremely dangerous.
The valve can suddenly and violently “blast off” from the cylinder, causing serious injury.
SAFETY WARNING
© NAFED 2015. All Rights Reserved.
Gauges may show “no pressure” even if the cylinder is fully charged.
Always check for pressure.
SAFETY WARNING
49
© NAFED 2015. All Rights Reserved.
Always wear your safety glasses.
SAFETY WARNING
© NAFED 2015. All Rights Reserved.
Produced and directed by..
George E. Seymour, CFPS, SET Technical Review and Support by..
William Johnson
Tim Krulan
Stan Oman
SPECIAL THANKS TO NAFED MEMBERS WHO CONTRIBUTED TO
THIS PRESENTATION