RECon Line Converters for Renewable Energies

1With continuous investments in research and development, FRIEM is leader in Diode, Thyristor or IGBT type High Power Converters, applying the most advanced technologies and electronics.

Founded in 1950 to design and manufacture High Power Converters, FRIEM continued to develop its know-how in energy conversion for industrial and traction applications.

In 1956 FRIEM produced and installed its first 50kA Rectifier Unit for application in Chlor- Alkali industry. At the absolute forefront in technology, in the early 60’s FRIEM was able to manufacture units rated up to 110kA and to design the first high current Thyristor Rectifier.

Service continuity required by the Electrochemical Industry oriented FRIEM’s design towards absolute reliability: quality, safety, latest international standards have always been the base for the design and development of our Equipments.

This experience and know-how were applied in the early 70’s when FRIEM started the production of Rectifier Units for traction application. With the support of it’s Partners, FRIEM provides complete Substations Systems with all the main equipment and services.

In 1984 FRIEM was able to design and start-up its first Power Supply for a PolySilicon CVD Reactor. Nowadays FRIEM has hundreds of units in service all over the World supplying all the different types of CVD Reactors.

In 2009 FRIEM started the production of the ReCon Line, a complete line of Inverters for the renewable energies (Photovoltaic Plants and Wind Turbines), becoming one of the main manufacturer in Italy and in the World.

2 3

IndexGeneral Characteristics . . . . . . . . . . . . . . . . . . . . . . . . 05MPPT Maximum Power Point Tracking . . . . . . . . . . . . 07Output Efficiency Curve . . . . . . . . . . . . . . . . . . . . . . . . 09RECon 30 and RECon 30-US Standards . . . . . . . . . . 11Models Available . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

RECon S LineRECon S1-2.5, 3.0, 4.0, 5.0 . . . . . . . . . . . . . . . . . . . . 14RECon S3-10, 12, 15, 20 . . . . . . . . . . . . . . . . . . . . . . 16

RECon 10L LineRECon 10L-33 / 33-T . . . . . . . . . . . . . . . . . . . . . . . . . 18 RECon 10L-66 / 66-T . . . . . . . . . . . . . . . . . . . . . . . . . 20RECon 10L-99 / 99-T . . . . . . . . . . . . . . . . . . . . . . . . . 22RECon 10L-132 / 132-T . . . . . . . . . . . . . . . . . . . . . . . 24RECon 10L-165 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26RECon 10L-198 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

RECon 10H LineRECon 10H-50 / 50-T . . . . . . . . . . . . . . . . . . . . . . . . . 30RECon 10H-100 / 100-T . . . . . . . . . . . . . . . . . . . . . . . 32RECon 10H-150 / 150-T . . . . . . . . . . . . . . . . . . . . . . . 34RECon 10H-200 / 200-T . . . . . . . . . . . . . . . . . . . . . . . 36RECon 10H-250 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38RECon 10H-300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

RECon 30L LineRECon 30L-100 / 100-T . . . . . . . . . . . . . . . . . . . . . . . 42 RECon 30L-200 / 200-T . . . . . . . . . . . . . . . . . . . . . . . 44RECon 30L-300 / 300-T . . . . . . . . . . . . . . . . . . . . . . . 46RECon 30L-400 / 400-T . . . . . . . . . . . . . . . . . . . . . . . 48 RECon 30L-500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 RECon 30L-600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

RECon 30H LineRECon 30H-150 / 150-T . . . . . . . . . . . . . . . . . . . . . . . 54RECon 30H-300 / 300-T . . . . . . . . . . . . . . . . . . . . . . . 56RECon 30H-450 / 450-T . . . . . . . . . . . . . . . . . . . . . . . 58RECon 30H-600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60RECon 30H-750 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 RECon 30H-900 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

RECon 65H LineRECon 65H-340 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66RECon 65H-680 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68RECon 65H-1020 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70RECon 65H-1360 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72RECon 65H-1700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 RECon 65H-2040 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

RECon Station RST LineGeneral Characteristics . . . . . . . . . . . . . . . . . . . . . . . . 78Models Available . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78RST-50 - 33 - 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 RST-100 - 83 - 66 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82RST-130 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

AccessoriesAccessories Available . . . . . . . . . . . . . . . . . . . . . . . . . . 86QI: Interface Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . 86STR: String Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88RMS: RECon Monitoring System . . . . . . . . . . . . . . . . . 90

In order to serve our customers with a wider range of products and solutions, FRIEM has started partnerships and investments with expert Electrotechnical Companies. This strategy gives FRIEM an even stronger Local presence, with offices or representatives in more than 20 Countries all over the World.

In its 11000m2 facilities nowadays FRIEM designs, manufactures and delivers all over the World:• AC/DC High Power Rectifiers• DC/DC High Power Converters• DC/AC High Power Inverters• AC/AC High Power Converters

For all the Main Applications• Renewable Energies Inverters for Photovoltaic plants and Wind turbines • PolySilicon Production Power Supply for CVD Reactors and TET Converters • Chemicals Production Rectifiers and Power Converters for Chlorine, Caustic soda, Hypocloride, Hypochlorine• Metal refining Rectifiers for Aluminium and Zinc smelters, Copper, Nickel, Lead, Iridium, Indium refineries • DC Arc furnaces Rectifiers for Steel DC Arc furnaces for stainless steel and alloys • Graphite refining Rectifiers for Graphite refining furnaces and heating processes• Traction Application Rectifiers and Power converters for main DC line substations

4 5General Characteristics

FRIEM has developed a complete line of High Power Solar and Wind Inverters. The RECon Line concept is derived from the long experience FRIEM has achieved in Power Conversion and in the use of all kind of semiconductors.

The Line has been developed following FRIEM’s traditional concept of reliability, efficiency and modularity devoted to high flexibility and easy maintenance.

The different models of RECon Line Inverters are available in three main versions:

RECon S: Single Phase and Three Phase String Inverters.

RECon-xxx: Three-phase Inverter for LV/MV applications with external transformer.

RECon-xxx-T: Three-phase Inverter grid connected with LV/LV integrated transformer.

All the different models of the RECon Line can be either used as single units or combined in parallel to reach the requested power.

The RECon Line Inverters offer:

• Modular draw-out and Compact Design for configuration flexibility, space saving and fast installation.

• Parallel Modules or Independent Modules Configurations.

• Easy Maintenance thanks to the completely withdrawable Power Section.

• The Digital Regulator FRIEM DRP-6Ph Type allows the fully automated Control and Protection of the Inverter itself and offers the availability of: - Single or Multiple MPPT management. - Real Time and Recorded Measurements. - Event Recording, Load Profile and Oscyllography. - Internal Canbus Communication Protocol for I/O management (temperature, irradiation and wind speed sensors). - Programmable Output Relays, Digital Inputs and Outputs. - Comprehensive self diagnostic - not just memory checksums - periodically tests the entire regulator.

• A Touch Screen Operator Panel for easy access to Measurements and Setting Parameters of one or more Inverters and of the PV Field, equipped with: - Front Face USB Serial Comm. Port for Local Interface. - Second Serial RS485 Comm. Port. - RS232/Modem Comm. Port. - Ethernet Serial Comm. Port.

• Standard Modbus-RTU or Profibus-DP communication protocols.

• Conformance to IEC Standards and CE Directive; UL-CSA listed.

• ISO 9001: 2008 Certified Quality System

4

6 7

The MPPT controls the voltage, current and power of the photovoltaic field and generates the Reference Current for the Current Regulator of the Inverter to achieve the greatest possible power harvest.The MPPT algorithm sample the output of the photovoltaic panel, to obtain the Maximum Power for any given environmental condition.The calculated voltage at which the photovoltaic panel should work is based on the voltage measurement of the panel and from the supplied Power.

The two most common methods to execute the MPPT algorithm are: - Incremental Conductance (IncCon).- Perturb and Observe (P&O).

The RECon Line Inverters use both algorithms.

The characteristics of photovoltaic panels are not stable, in fact they variate in function of weather conditions and solar irradiation.

The purpose of the MPPT System is to follow the maximum power point for any photovoltaic module.Analyzing the V-P solar panel characteristic, it can be noticed that, when environmental conditions change (partial shading of the panels), there exists different absolute and relative maximum power points.

MPPT Maximum Power Point Tracking

T = 25 degC, Irr. (rated %) = 25.0, 50.0, 75.0, 100

43.5

3

2.52

1.5

10.5

0

Cur

rent

(A)

0 5 10 15 20 25Voltage (V)

2000

1800

1600

1400

1200

1000

800

600

400

200

0

Pow

er (W

)

0 50 100 150 200 250 300 350

Tension (V)

Initial FV CharacteristicFinal FV CharacteristicMPPT FV Characteristic

MaximumMaximum

6

8 9Output Efficiency Curve

Rated Output Efficiency 99,7%Maximum Output Efficiency 99,7%EURO Output Efficiency 98,7%

No-load loss 35WStand-by loss 50W

When an efficiency value has been guaranteed, the tolerance of this value shall be within the value at rated conditions indicated below:-0,2 x (1-h) x h (%)(h=guaranteed efficiency)

Output Efficiency at Operating Voltage

110,0%

100,0%

90,0%

80,0%

70,0%

60,0%

50,0%

Out

put E

ffici

ency

0,0 20,0 40,0 60,0 80,0 100,0 120,0

Rated Load %

The graph here below shows the efficiency load curve of the RECon-line Inverters.The efficiency reaches not only very high absolute values (hmax 99,7% @ 0,9 Pn), but also stays above the 98%, starting from the 20% of the load, granting an high EURO efficiency.

8

10 11RECon 30 and RECon 30-US Standards10

RECon 30 L/H for MV

2004/108/EC EMC - Electromagnetic Compatibility2006/95/EC Low Voltage Directive

SafetyEN-62109-1 : 2010-12 Safety for Power Converter for Use in Photovoltaic Power Systems-General Requirements EN-62109-2 : 2012-04 Safety of Power Converter for Use in Photovoltaic Power Systems-Particular Requirements for Inverters

Semiconductor ConvertorIEC 60146 - 1 - 1: 2009 - 06 Semiconductor convertorsGeneral requirements and line commutated convertors - Part 1.1Specifications of basic requirementsEN 60146-1-3:1997: 1997 - 09 Semiconductor convertorsGeneral requirements and line commutated convertors - Part 1.3Specifications of basic requirementsTransformers and Reactors

Electrical Energy Production SystemCEI 11-20: 2000 + V1: 2004 Electrical energy production system and uninterruptable power systems connected to I and II class network

Distribution HV - MV NetworkCEI 0-16: 2012-12 Reference technical rules for the connection of active and passive consumers to the HV and MV electrical networks of distribution Company

EMCImmunityEN 61000 - 6 - 2: 2005 Electromagnetic compatibility (EMC) - Part 6-2 Generic standards - Immunity for industrial environments

EmissionEN 61000 - 6 - 4: 2007 Electromagnetic compatibility (EMC) - Part 6-4 Generic standards - Emission standard for industrialenvironments

ImmunityEN 61000 - 3 - 12: 2005 Electromagnetic compatibility (EMC) Part 3.12Limits - Limits for harmonic currents produced by equipment connected to public low-voltage systems with input current > 16 A and ≤ 75 A per phase

EUROPEAN EFFICENCY EVALUATIONIEC 61683: 1999-11 Photovoltaic Systems - Power Conditioner - Procedure for measuring efficiency

RECon 30 L/H - T-R for BT

The same as RECon 30 L/H except CEI 0-16 and Emission EN 61000-6-4

Distribution LV NetworkCEI 0-21: 2012-12 + V1 2012-12 Reference technical rules for the connection of active and passive users to the LV electrical Utilities

EmissionEN 61000 - 6 - 3: 2007-11 Electromagnetic compatibility (EMC) - Part 6-3 Generic standards - Emission standard for residential, commercial and light-industrial enviroments

RECon 30 L/H - US

UL1741Inverter, Converter, Controllers and Interconnection System Equipment for use with Distributed Energy ResourcesUL1998Software in Programmable ComponentsIEEE 1547 Standard for Interconnecting Distributed Resource with Electrical Power SystemCSA C.22.2 No. 107.1-01General Use Power SupplyANSI.C84.1-1995 (R2005)Electrical Power System and Equipment-Voltage Rating (60 Hertz)NEMA 250Enclosures for Electrical Equipment (1000V Maximum)NFPA 70 National Electrical Code 2011

RECon 30 L/H for German LV

VDE 0126-1-1 (2006)Automatic Disconnection Device Between Generator and the public low voltage grid

12 13

Line “S1”: Low Voltage PV - Vin = (200-480) Vdc - Vout = 180/280 Vca - Iout = 12,5-25 A ac S1-2.5 Monophase Inverter: PIN = (2700)kWp - POUT = 2500 kWca S1-3 Monophase Inverter: PIN = (3200)kWp - POUT = 3200 kWca S1-4 Monophase Inverter: PIN = (4300)kWp - POUT = 4200 kWca S1-5 Monophase Inverter: PIN = (5200)kWp - POUT = 5000 kWca Line “S3”: High Voltage PV - Vin = (250-800) Vdc - Vout = 230/400 Vca - Iout = 15,5-29 A ac S3-10 Threephase Inverter: PIN = (10,35)kWp - POUT = 10 kWca S3-12 Threephase Inverter: PIN = (12,45)kWp - POUT = 12 kWca S3-15 Threephase Inverter: PIN = (15,55)kWp - POUT = 15 kWca S3-20 Threephase Inverter: PIN = (20,60)kWp - POUT = 20 kWca Line “10L-”: Low Voltage PV - Vin = (325÷665) Vdc - Vout = 200 Vca - Iout = 97 A ac/mod. 10L- 33 Threephase Inverter: PIN = (20÷37)kWp - POUT = 33 kWac 10L- 66 Threephase Inverter: PIN = (45÷74)kWp - POUT = 66 kWac 10L- 99 Threephase Inverter: PIN = (70÷110)kWp - POUT = 100 kWac 10L- 132 Threephase Inverter: PIN = (90÷147)kWp - POUT = 132 kWac 10L- 165 Threephase Inverter: PIN = (115÷185)kWp - POUT = 165 kWac 10L- 198 Threephase Inverter: PIN = (139÷220)kWp - POUT = 198 kWac 10L- 33-T Threephase Inverter: PIN = (20÷37)kWp - POUT = 33 kWac with LV/LV Integrated Trasfo 10L- 66-T Threephase Inverter: PIN = (45÷74)kWp - POUT = 66 kWac with LV/LV Integrated Trasfo 10L- 99-T Threephase Inverter: PIN = (70÷110)kWp - POUT = 99 kWac with LV/LV Integrated Trasfo 10L- 132-T Threephase Inverter: PIN = (90÷147)kWp - POUT = 132 kWac with LV/LV Integrated Trasfo Line “10H-”: High Voltage PV - Vin = (470÷850) Vdc - Vout = 300 Vca - Iout = 97 A ac/mod. 10H-50 Threephase Inverter: PIN = (33÷55)kWp - POUT = 50 kWac 10H-100 Threephase Inverter: PIN = (70÷110)kWp - POUT = 100 kWac 10H-150 Threephase Inverter: PIN = (100÷170)kWp - POUT = 150 kWac 10H-200 Threephase Inverter: PIN = (140÷220)kWp - POUT = 200 kWac 10H-250 Threephase Inverter: PIN = (175÷278)kWp - POUT = 250 kWac 10H-300 Threephase Inverter: PIN = (200÷335)kWp - POUT = 300 kWac 10H-50-T Threephase Inverter: PIN = (33÷55)kWp - POUT = 50 kWac with LV/LV Integrated Trasfo 10H-100-T Threephase Inverter: PIN = (70÷110)kWp - POUT = 100 kWac with LV/LV Integrated Trasfo 10H-150-T Threephase Inverter: PIN = (100÷170)kWp - POUT = 150 kWac with LV/LV Integrated Trasfo 10H-200-T Threephase Inverter: PIN = (140÷220)kWp - POUT = 200 kWac with LV/LV Integrated Trasfo Line “30L-”: Low Voltage PV - Vin = (325÷665) Vdc - Vout = 200 Vca - Iout = 290 A ac/mod. 30L-100 Threephase Inverter: PIN = (70÷110)kWp - POUT = 100 kWac 30L-200 Threephase Inverter: PIN = (140÷225)kWp - POUT = 200 kWac 30L-300 Threephase Inverter: PIN = (200÷335)kWp - POUT = 300 kWac 30L-400 Threephase Inverter: PIN = (280÷450)kWp - POUT = 400 kWac 30L-500 Threephase Inverter: PIN = (350÷560)kWp - POUT = 500 kWac 30L-600 Threephase Inverter: PIN = (400÷670)kWp - POUT = 600 kWac 30L-100-T Threephase Inverter: PIN = (70÷110)kWp - POUT = 100 kWac with LV/LV Integrated Trasfo 30L-200-T Threephase Inverter: PIN = (140÷225)kWp - POUT = 200 kWac with LV/LV Integrated Trasfo 30L-300-T Threephase Inverter: PIN = (200÷335)kWp - POUT = 300 kWac with LV/LV Integrated Trasfo 30L-400-T Threephase Inverter: PIN = (280÷450)kWp - POUT = 400 kWac with LV/LV Integrated Trasfo Line “30H-”: High Voltage PV - Vin = (470÷850) Vdc - Vout = 300 Vca - Iout = 290 A ac/mod. 30H-150 Threephase Inverter: PIN = (100÷170)kWp - POUT = 150 kWac 30H-300 Threephase Inverter: PIN = (200÷335)kWp - POUT = 300 kWac 30H-450 Threephase Inverter: PIN = (300÷500)kWp - POUT = 450 kWac 30H-600 Threephase Inverter: PIN = (400÷670)kWp - POUT = 600 kWac 30H-750 Threephase Inverter: PIN = (500÷835)kWp - POUT = 750 kWac 30H-900 Threephase Inverter: PIN = (600÷1000)kWp - POUT = 900 kWac 30H-150-T Threephase Inverter: PIN = (100÷170)kWp - POUT = 150 kWac with LV/LV Integrated Trasfo 30H-300-T Threephase Inverter: PIN = (200÷335)kWp - POUT = 300 kWac with LV/LV Integrated Trasfo 30H-450-T Threephase Inverter: PIN = (300÷500)kWp - POUT = 450 kWac with LV/LV Integrated Trasfo Line “65H-”: High Voltage PV - Vin = (470÷930) Vdc - Vout = 300 Vca - Iout = 655 A ac/mod. 65H-340 Threephase Inverter: PIN = (224-÷378)kWp - POUT = 340 kWac 65H-680 Threephase Inverter: PIN = (448÷756)kWp - POUT = 680 kWac 65H-1020 Threephase Inverter: PIN = (672÷1134)kWp - POUT = 1020 kWac 65H-1360 Threephase Inverter: PIN = (896÷1512)kWp - POUT = 1360 kWac 65H-1700 Threephase Inverter: PIN = (1120÷1890)kWp - POUT = 1700 kWac 65H-2040 Threephase Inverter: PIN = (1344-÷2268)kWp - POUT = 2040 kWac

Models Available12

14 15

RECon S1-2.5, S1-3.0, S1-4.0, S1-5.0

Inverter RECon S1-2.5, 3.0, 4.0, 5.0

S1-2.5-3.0-4.0-5.0

EMCFilter

DC-DCBoost

Converter

EMCFilter

PV Array

PV Array

DC-DCBoost

Converter

DC-ACInverter

EMCFilter

Transformerless

ACGrid

Relay

+

+

_

_

OptionalDC Switch

RECon S1-2.5 RECon S1-3.0 RECon S1-4.0 RECon S1-5.0Input (DC) Field Power Range [kW DC] 2,7 3,2 4,3 5,2DC Voltage Range MPPT [V] 180-400 200-480 200-480 200-480Maximum DC voltage [V] 500 550 550 550Maximum DC current [A] 2x13,5 2x15 2x15 2x15Number of protected DC inputs 2 2 2 2Voltage ripple < 5% < 5% < 5% < 5% Standard DC devicesDC fuses on both terminals No No No No DC on-load isolator Yes Yes Yes YesInsulating monitoring system Yes Yes Yes YesSurge arrestor No No No No Output (AC)Rated AC output power [kW] 2,3 3 4 4,9Max AC output power [kW] 2,5 3,2 4,2 5Rated AC current [A] 12.5 16 21 25Operating grid voltage [V] 180/280 180/280 180/280 180/280Operating grid frequency [Hz] 50/60 50/60 50/60 50/60Harmonic distortion of grid current (THD) < 3% < 3% < 3% < 3%Power factor (cos j) -0,8 + 0,8 -0,8 + 0,8 -0,8 + 0,8 -0,8 + 0,8Number of Feed-in Phases Single-Phase Single-Phase Single-Phase Single-PhaseEfficiencyMaximum efficiency 96,7% 97,0% 97,5% 97,5%EURO Efficiency 95,5% 96 ,0% 97,0% 97,0%Weight and DimensionApproximate weight [kg] 15 23,5 23,5 23,5Width [mm] 380 485 485 485Height [mm] 498 398 398 398Depth [mm] 145 187 187 187General DataNight consumption [W] < 0,2W < 0,2W < 0,2W < 0,2WStandby 4W 4W 4W 4WType of cooling Free Convection Free Convection Free Convection Free ConvectionTopological Structure Transformerless Transformerless Transformerless TransformerlessAC Connection / DC Connection Plug connector / MC4 Plug connector / MC4 Plug connector / MC4 Plug connector / MC4Standard Warranty 7 years 7 years 7 years 7 yearsDegree of IP Protection IP65 IP65 IP65 IP65Operating temperature range [°C] -25° to +60°C -25° to +60°C -25° to +60°C -25° to +60°C Ambient Humidity (not condensing) 4 - 100% 4 - 100% 4 - 100% 4 - 100% Maximum altitude without derating (a.s.l.) [m] < 3000 m < 3000 m < 3000 m < 3000 mMaximum noise level [dBA @ 1m] < 30 dB < 30 dB < 30 dB < 30 dBUser interface and communicationLocal user interface Graphic Display Graphic Display Graphic Display Graphic DisplayStandard Communication Interface RS485 RS485 RS485 RS485Remote communication port (optional) Bluetooth Bluetooth Bluetooth Bluetooth Standard complianceEMC Yes Yes Yes YesCE Compliance Yes Yes Yes YesOther Standard VDE/AS/CEI/G83 VDE/AS/CEI/G83 VDE/AS/CEI/G83 VDE/AS/CEI/G83

16 17

S3-10-12-15-20

RECon S3-10, S3-12, S3-15, S3-20

Inverter RECon S3-10, 12, 15, 20

EMCFilter

DC-DCBoost

Converter

EMCFilter

PV Array

PV Array

DC-DCBoost

Converter

DC-ACInverter

EMCFilter

Transformerless

ACGrid

Relay

+

+

_

_

OptionalDC Switch

RECon S3-10 RECon S3-12 RECon S3-15 RECon S3-20Input (DC) Field Power Range [kW DC] 10,35 12,45 15,55 20,60DC Voltage Range MPPT [V] 250-800 330-800 380-800 450-800Maximum DC voltage [V] 1000 1000 1000 1000Maximum DC current [A] 2x20 2x20 2x20 2x25Rated MPPT voltage [V] 650V 650V 650V 650VNumber of MPPT Trackers 2 2 2 2Strings of each MPPT A:3, B:3 A:3, B:3 A:3, B:3 A:3, B:3 Standard DC devicesDC fuses on both terminals No No No No DC on load switch Yes Yes Yes YesInsulating monitoring system Yes Yes Yes YesSurge arrestor No No No No Output (AC)Rated AC output power [kW] 10 12 15 20Rated AC current [A] 15 18 22 30 Operating grid voltage [V] 230/400 (3/N/PE) 230/400 (3/N/PE) 230/400 (3/N/PE) 230/400 (3/N/PE)Operating grid frequency [Hz] 50/60 50/60 50/60 50/60Harmonic distortion of grid current (THD) < 3% < 3% < 3% < 3%Power factor (cos j) 0.9 to +0.9 adjustable 0.9 to +0.9 adjustable 0.9 to +0.9 adjustable 0.9 to +0.9 adjustableEfficiencyMaximum efficiency 98,0% 98,0% 98,0% 98,2%EURO Efficiency 97,3% 97,3% 97,4% 97,5%Weight and DimensionApproximate weight [kg] 45 45 50 55Width [mm] 550 550 550 550Height [mm] 650 650 650 650Depth [mm] 250 250 250 250General DataNight consumption [W] < 1W < 1W < 1W < 1WType of cooling Forced air cooling Forced air cooling Forced air cooling Forced air coolingTopological Structure Transformerless Transformerless Transformerless TransformerlessAC Connection / DC Connection Plug connector / MC4 Plug connector / MC4 Plug connector / MC4 Plug connector / MC4Standard Warranty 10 years 10 years 10 years 10 yearsDegree of IP Protection IP65 IP65 IP65 IP65Operating temperature range [°C] -25° to +60°C -25° to +60°C -25° to +60°C -25° to +60°C Cooling Air Flow [m3/h] Forced air cooling Forced air cooling Forced air cooling Forced air coolingAmbient Humidity (not condensing) 4 - 100% 4 - 100% 4 - 100% 4 - 100% Maximum altitude without derating (a.s.l.) [m] up to 2000 up to 2000 up to 2000 up to 2000Maximum noise level [dBA @ 1m] < 55 dB < 55 dB < 55 dB < 55dbUser interface and communicationLocal user interface LCD LCD LCD LCDStandard Communication Interface RS485/RS232 RS485/RS232 RS485/RS232 RS485/RS232Remote communication port (optional) Bluetooth Bluetooth Bluetooth Bluetooth Standard complianceEMC Yes Yes Yes YesCE Compliance Yes Yes Yes YesOther Standard VDE/AS/CEI/G83 VDE/AS/CEI/G83 VDE/AS/CEI/G83 VDE/AS/CEI/G83

18 19

10L-33

RECon 10L-33, 10L-33-T RECon 10L-33 RECon 10L-33-TInput (DC) Field Power Range [kW DC] 20-37 20-37DC Voltage Range MPPT [V] 325-680 325-680Maximum DC voltage [V] 700 700Maximum DC current [A] 110 110Number of protected DC inputs 2 2Number of independent MPPT 1 1Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 33 33Max AC output power [kW] 37 37Rated AC current [A] 97 48Operating grid voltage [V] 200 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99 96,9EURO Efficiency 98,1 95,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 70 < 100Weight and DimensionApproximate weight [kg] 250 700Width [mm] 400 800Height [mm] 1.800 1.800Depth [mm] 800 800Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 800 1.600Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16

Inverter RECon 10L-33

Inverter RECon 10L-33-T

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io>I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

REPEATERRELAY

I>

PV

=1

2

BT / BT

TRANSFORMER CABINET

STATUS

ENERGYMETER

INTERFACEBREAKER

GENERATOR CONTACTOR

MAIN BREAKER

AUXILIARYSUPPLYFROM UPS

REPEATERRELAY

TEMPERATURATRASFORMATORE

GRID

PTSYNCHRON.

EMCFILTER

230/400

EMCFILTER

OPTION

OPEN

STATUS

CLOSE

DC INPUT SECTION

STRING BOXSTR16

POWER CONVERTION SECTION

INVERTER CABINET

INSULATION MONITOR

GRID PROTECTIONRELAYV> F>V< F<

AUX. SUPPLYDISTRIBUT.

20 21

10L-66

RECon 10L-66, 10L-66-T RECon 10L-66 RECon 10L-66-TInput (DC) Field Power Range [kW DC] 45-74 45-74DC Voltage Range MPPT [V] 325-680 325-680Maximum DC voltage [V] 700 700Maximum DC current [A] 220 220Number of protected DC inputs 4 4Number of independent MPPT 2 2Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 66 66Max AC output power [kW] 74 74Rated AC current [A] 194 96Operating grid voltage [V] 200 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99 96,9EURO Efficiency 98,1 95,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 140 < 170Weight and DimensionApproximate weight [kg] 500 1.200Width [mm] 800 1.500Height [mm] 1.800 1.800Depth [mm] 800 800Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 1.600 2.400Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16

Inverter RECon 10L-66

Inverter RECon 10L-66-T

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io>I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

EMC FILTER

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

n

1

2

PVSTRING BOX

STR16

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

GENERATOR CONTACTOR

PV

=1

2

BT / BT

TRANSFORMER CABINET

STATUS

ENERGYMETER

INTERFACEBREAKER

GENERATOR CONTACTOR

MAIN BREAKER

PV

=1

2

AUXILIARYSUPPLYFROM UPS

REPEATERRELAY

TEMPERATURATRASFORMATORE

GRID

PTSYNCHRON.

EMCFILTER

230/400

230/400

EMCFILTER

ENERGY ANALYZER

OPTION

1

n.

OPEN

STATUS

CLOSE

DC INPUT SECTION

STRING BOXSTR16

POWER CONVERTION SECT. AC OUTPUT SECTION

INVERTER CABINET

INSULATION MONITOR

GRID PROTECTIONRELAYV> F>V< F<

AUX. SUPPLYDISTRIBUT.

STRING BOXSTR16

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMCFILTER

INSULATION MONITOR

GENERATOR CONTACTOR

PTSYNCHRON.

22 23

10L-99

RECon 10L-99, 10L-99-T RECon 10L-99 RECon 10L-99-TInput (DC) Field Power Range [kW DC] 70-110 70-110DC Voltage Range MPPT [V] 325-680 325-680Maximum DC voltage [V] 700 700Maximum DC current [A] 325 325Number of protected DC inputs 6 6Number of independent MPPT 3 3Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 99 99Max AC output power [kW] 110 110Rated AC current [A] 291 144Operating grid voltage [V] 200 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99 96,9EURO Efficiency 98,1 95,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 210 < 240Weight and DimensionApproximate weight [kg] 750 1.500Width [mm] 1.200 1.900Height [mm] 1.800 1.800Depth [mm] 800 800Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 2.400 3.200Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16

Inverter RECon 10L-99

Inverter RECon 10L-99-T

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io>I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

EMC FILTER

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

n

1

2

PVSTRING BOX

STR16

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

GENERATOR CONTACTOR

PV

=1

2

BT / BT

TRANSFORMER CABINET

STATUS

ENERGYMETER

INTERFACEBREAKER

GENERATOR CONTACTOR

MAIN BREAKER

PV

=1

2

AUXILIARYSUPPLYFROM UPS

REPEATERRELAY

TEMPERATURATRASFORMATORE

GRID

PTSYNCHRON.

EMCFILTER

230/400

230/400

EMCFILTER

ENERGY ANALYZER

OPTION

1

n.

OPEN

STATUS

CLOSE

DC INPUT SECTION

STRING BOXSTR16

POWER CONVERTION SECT. AC OUTPUT SECTION

INVERTER CABINET

INSULATION MONITOR

GRID PROTECTIONRELAYV> F>V< F<

AUX. SUPPLYDISTRIBUT.

STRING BOXSTR16

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMCFILTER

INSULATION MONITOR

GENERATOR CONTACTOR

PTSYNCHRON.

24 25

10L-132

RECon 10L-132, 10L-132-T RECon 10L-132 RECon 10L-132-TInput (DC) Field Power Range [kW DC] 90-147 90-147DC Voltage Range MPPT [V] 325-680 325-680Maximum DC voltage [V] 700 700Maximum DC current [A] 435 435Number of protected DC inputs 8 8Number of independent MPPT 4 4Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 132 132Max AC output power [kW] 147 147Rated AC current [A] 388 192Operating grid voltage [V] 200 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99 96,9EURO Efficiency 98,1 95,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 280 < 310Weight and DimensionApproximate weight [kg] 1.000 2.100Width [mm] 1.600 2.800Height [mm] 1.800 1.800Depth [mm] 800 800Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 3.200 4.000Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16

Inverter RECon 10L-132

Inverter RECon 10L-132-T

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io>I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

EMC FILTER

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

n

1

2

PVSTRING BOX

STR16

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

GENERATOR CONTACTOR

PV

=1

2

BT / BT

TRANSFORMER CABINET

STATUS

ENERGYMETER

INTERFACEBREAKER

GENERATOR CONTACTOR

MAIN BREAKER

PV

=1

2

AUXILIARYSUPPLYFROM UPS

REPEATERRELAY

TEMPERATURATRASFORMATORE

GRID

PTSYNCHRON.

EMCFILTER

230/400

230/400

EMCFILTER

ENERGY ANALYZER

OPTION

1

n.

OPEN

STATUS

CLOSE

DC INPUT SECTION

STRING BOXSTR16

POWER CONVERTION SECT. AC OUTPUT SECTION

INVERTER CABINET

INSULATION MONITOR

GRID PROTECTIONRELAYV> F>V< F<

AUX. SUPPLYDISTRIBUT.

STRING BOXSTR16

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMCFILTER

INSULATION MONITOR

GENERATOR CONTACTOR

PTSYNCHRON.

26 27

10L-165

RECon 10L-165Input (DC) Field Power Range [kW DC] 115-185DC Voltage Range MPPT [V] 325-680Maximum DC voltage [V] 700Maximum DC current [A] 550Number of protected DC inputs 10Number of independent MPPT 5Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 165Max AC output power [kW] 185Rated AC current [A] 485Operating grid voltage [V] 200Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99EURO Efficiency 98,1Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 350Weight and DimensionApproximate weight [kg] 1.250Width [mm] 2.000Height [mm] 1.800Depth [mm] 800Environmental DataProtection Degree IP20Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 4.000Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

RECon 10L-165

Inverter RECon 10L-165INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io>I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

EMC FILTER

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

n

1

2

PVSTRING BOX

STR16

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

28 29

10L-198

RECon 10L-198 RECon 10L-198Input (DC) Field Power Range [kW DC] 139-220DC Voltage Range MPPT [V] 325-680Maximum DC voltage [V] 700Maximum DC current [A] 660Number of protected DC inputs 12Number of independent MPPT 6Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 198Max AC output power [kW] 220Rated AC current [A] 582Operating grid voltage [V] 200Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99EURO Efficiency 98,1Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 420Weight and DimensionApproximate weight [kg] 1.500Width [mm] 2.400Height [mm] 1.800Depth [mm] 800Environmental DataProtection Degree IP20Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 4.800Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

Inverter RECon 10L-198INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io>I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

EMC FILTER

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

n

1

2

PVSTRING BOX

STR16

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

30 31

10H-50

RECon 10H-50, 10H-50-T RECon 10H-50 RECon 10H-50-TInput (DC) Field Power Range [kW DC] 35-55 35-55DC Voltage Range MPPT [V] 470-885 470-885Maximum DC voltage [V] 900 900Maximum DC current [A] 110 110Number of protected DC inputs 2 2Number of independent MPPT 1 1Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 50 50Max AC output power [kW] 55 55Rated AC current [A] 97 73Operating grid voltage [V] 300 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99,3 97,5EURO Efficiency 98,7 96,6Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 70 < 100Weight and DimensionApproximate weight [kg] 250 700Width [mm] 400 800Height [mm] 1.800 1.800Depth [mm] 800 800Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 800 1.600Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16

Inverter RECon 10H-50

Inverter RECon 10H-50-T

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io>I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

REPEATERRELAY

I>

PV

=1

2

BT / BT

TRANSFORMER CABINET

STATUS

ENERGYMETER

INTERFACEBREAKER

GENERATOR CONTACTOR

MAIN BREAKER

AUXILIARYSUPPLYFROM UPS

REPEATERRELAY

TEMPERATURATRASFORMATORE

GRID

PTSYNCHRON.

EMCFILTER

230/400

EMCFILTER

OPTION

OPEN

STATUS

CLOSE

DC INPUT SECTION

STRING BOXSTR16

POWER CONVERTION SECTION

INVERTER CABINET

INSULATION MONITOR

GRID PROTECTIONRELAYV> F>V< F<

AUX. SUPPLYDISTRIBUT.

32 33

10H-100

RECon 10H-100, 10H-100-T RECon 10H-100 RECon 10H-100-TInput (DC) Field Power Range [kW DC] 70-110 70-110DC Voltage Range MPPT [V] 470-885 470-885Maximum DC voltage [V] 900 900Maximum DC current [A] 220 220Number of protected DC inputs 4 4Number of independent MPPT 2 2Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 100 100Max AC output power [kW] 110 110Rated AC current [A] 194 146Operating grid voltage [V] 300 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99,3 97,5EURO Efficiency 98,7 96,6Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 140 < 170Weight and DimensionApproximate weight [kg] 500 1.200Width [mm] 800 1.500Height [mm] 1.800 1.800Depth [mm] 800 800Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 1.600 2.500Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16

Inverter RECon 10H-100

Inverter RECon 10H-100-T

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io>I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

EMC FILTER

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

n

1

2

PVSTRING BOX

STR16

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

GENERATOR CONTACTOR

PV

=1

2

BT / BT

TRANSFORMER CABINET

STATUS

ENERGYMETER

INTERFACEBREAKER

GENERATOR CONTACTOR

MAIN BREAKER

PV

=1

2

AUXILIARYSUPPLYFROM UPS

REPEATERRELAY

TEMPERATURATRASFORMATORE

GRID

PTSYNCHRON.

EMCFILTER

230/400

230/400

EMCFILTER

ENERGY ANALYZER

OPTION

1

n.

OPEN

STATUS

CLOSE

DC INPUT SECTION

STRING BOXSTR16

POWER CONVERTION SECT. AC OUTPUT SECTION

INVERTER CABINET

INSULATION MONITOR

GRID PROTECTIONRELAYV> F>V< F<

AUX. SUPPLYDISTRIBUT.

STRING BOXSTR16

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMCFILTER

INSULATION MONITOR

GENERATOR CONTACTOR

PTSYNCHRON.

34 35

10H-150

RECon 10H-150, 10H-150-T RECon 10H-150 RECon 10H-150-TInput (DC) Field Power Range [kW DC] 70-110 70-110DC Voltage Range MPPT [V] 470-885 470-885Maximum DC voltage [V] 900 900Maximum DC current [A] 325 325Number of protected DC inputs 6 6Number of independent MPPT 3 3Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 150 150Max AC output power [kW] 110 110Rated AC current [A] 291 219Operating grid voltage [V] 300 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99,3 97,5EURO Efficiency 98,7 96,6Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 210 < 240Weight and DimensionApproximate weight [kg] 750 1.500Width [mm] 1.200 1.900Height [mm] 1.800 1.800Depth [mm] 800 800Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 2.400 3.200Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16

Inverter RECon 10H-150

Inverter RECon 10H-150-T

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io>I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

EMC FILTER

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

n

1

2

PVSTRING BOX

STR16

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

GENERATOR CONTACTOR

PV

=1

2

BT / BT

TRANSFORMER CABINET

STATUS

ENERGYMETER

INTERFACEBREAKER

GENERATOR CONTACTOR

MAIN BREAKER

PV

=1

2

AUXILIARYSUPPLYFROM UPS

REPEATERRELAY

TEMPERATURATRASFORMATORE

GRID

PTSYNCHRON.

EMCFILTER

230/400

230/400

EMCFILTER

ENERGY ANALYZER

OPTION

1

n.

OPEN

STATUS

CLOSE

DC INPUT SECTION

STRING BOXSTR16

POWER CONVERTION SECT. AC OUTPUT SECTION

INVERTER CABINET

INSULATION MONITOR

GRID PROTECTIONRELAYV> F>V< F<

AUX. SUPPLYDISTRIBUT.

STRING BOXSTR16

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMCFILTER

INSULATION MONITOR

GENERATOR CONTACTOR

PTSYNCHRON.

36 37

10H-200

RECon 10H-200, 10H-200-T RECon 10H-200 RECon 10H-200-TInput (DC) Field Power Range [kW DC] 140-220 140-220DC Voltage Range MPPT [V] 470-885 470-885Maximum DC voltage [V] 900 900Maximum DC current [A] 435 435Number of protected DC inputs 8 8Number of independent MPPT 4 4Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 200 200Max AC output power [kW] 220 220Rated AC current [A] 388 292Operating grid voltage [V] 300 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99,3 97,5EURO Efficiency 98,7 96,6Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 280 < 310Weight and DimensionApproximate weight [kg] 1.000 2.100Width [mm] 1.600 2.800Height [mm] 1.800 1.800Depth [mm] 800 800Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 3.200 4.000Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16

Inverter RECon 10H-200

Inverter RECon 10H-200-T

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io>I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

EMC FILTER

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

n

1

2

PVSTRING BOX

STR16

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

GENERATOR CONTACTOR

PV

=1

2

BT / BT

TRANSFORMER CABINET

STATUS

ENERGYMETER

INTERFACEBREAKER

GENERATOR CONTACTOR

MAIN BREAKER

PV

=1

2

AUXILIARYSUPPLYFROM UPS

REPEATERRELAY

TEMPERATURATRASFORMATORE

GRID

PTSYNCHRON.

EMCFILTER

230/400

230/400

EMCFILTER

ENERGY ANALYZER

OPTION

1

n.

OPEN

STATUS

CLOSE

DC INPUT SECTION

STRING BOXSTR16

POWER CONVERTION SECT. AC OUTPUT SECTION

INVERTER CABINET

INSULATION MONITOR

GRID PROTECTIONRELAYV> F>V< F<

AUX. SUPPLYDISTRIBUT.

STRING BOXSTR16

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMCFILTER

INSULATION MONITOR

GENERATOR CONTACTOR

PTSYNCHRON.

38 39

10H-250

RECon 10H-250 RECon 10H-250Input (DC) Field Power Range [kW DC] 175-278DC Voltage Range MPPT [V] 470-885Maximum DC voltage [V] 900Maximum DC current [A] 550Number of protected DC inputs 10Number of independent MPPT 5Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 250Max AC output power [kW] 278Rated AC current [A] 485Operating grid voltage [V] 300Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99,3EURO Efficiency 98,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 350Weight and DimensionApproximate weight [kg] 1.250Width [mm] 2.000Height [mm] 1.800Depth [mm] 800Environmental DataProtection Degree IP20Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 4.000Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

Inverter RECon 10H-250INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io>I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

EMC FILTER

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

n

1

2

PVSTRING BOX

STR16

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

40 41

10H-300

RECon 10H-300 RECon 10H-300Input (DC) Field Power Range [kW DC] 200-335DC Voltage Range MPPT [V] 470-885Maximum DC voltage [V] 900Maximum DC current [A] 660Number of protected DC inputs 12Number of independent MPPT 6Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 300Max AC output power [kW] 335Rated AC current [A] 582Operating grid voltage [V] 300Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99,3EURO Efficiency 98,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 420Weight and DimensionApproximate weight [kg] 1.500Width [mm] 2.400Height [mm] 1.800Depth [mm] 800Environmental DataProtection Degree IP20Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 4.800Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

Inverter RECon 10H-300INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io>I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

EMC FILTER

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

n

1

2

PVSTRING BOX

STR16

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

42 43

30L-100

RECon 30L-100, 30L-100-T RECon 30L-100 RECon 30L-100-TInput (DC) Field Power Range [kW DC] 70-110 70-110DC Voltage Range MPPT [V] 325-680 325-680Maximum DC voltage [V] 700 700Maximum DC current [A] 325 325Number of protected DC inputs 3 3Number of independent MPPT 1 1Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 100 100Max AC output power [kW] 110 110Rated AC current [A] 290 290Operating grid voltage [V] 200 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99 96,9EURO Efficiency 98,1 95,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 50 < 80Weight and DimensionApproximate weight [kg] 500 1.200Width [mm] 550 1.250Height [mm] 2.200 1.800Depth [mm] 800+200 800+200Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 1.500 2.500Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16

Inverter RECon 30L-100

Inverter RECon 30L-100-T

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

BACKUPBREAKER

OPTION

BACKUP BREAKER

AC OUTPUT SECTION

1

n

1

2

3

PVSTRING BOX

STR16

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

EMC FILTER

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

TEMPERATURETRANSFORMER

44 45

30L-200

RECon 30L-200, 30L-200-T RECon 30L-200 RECon 30L-200-TInput (DC) Field Power Range [kW DC] 140-225 140-225DC Voltage Range MPPT [V] 325-680 325-680Maximum DC voltage [V] 700 700Maximum DC current [A] 650 650Number of protected DC inputs 6 6Number of independent MPPT 2 2Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 200 200Max AC output power [kW] 225 225Rated AC current [A] 580 580Operating grid voltage [V] 200 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99 96,9EURO Efficiency 98,1 95,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 100 < 160Weight and DimensionApproximate weight [kg] 1.000 2.200Width [mm] 1.100 2.100Height [mm] 2.200 2.200Depth [mm] 800+200 800+200Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 3.000 4.000Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16

TEMPERATURETRANSFORMER

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

BACKUPBREAKER

OPTION

BACKUP BREAKER

AC OUTPUT SECTION

1

n

1

2

3

PVSTRING BOX

STR16

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

EMC FILTER

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

Inverter RECon 30L-200

Inverter RECon 30L-200-T

46 47

30L-300

RECon 30L-300, 30L-300-T RECon 30L-300 RECon 30L-300-TInput (DC) Field Power Range [kW DC] 200-335 200-335DC Voltage Range MPPT [V] 325-680 325-680Maximum DC voltage [V] 700 700Maximum DC current [A] 975 975Number of protected DC inputs 9 9Number of independent MPPT 3 3Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 300 300Max AC output power [kW] 335 325Rated AC current [A] 870 870Operating grid voltage [V] 200 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99 96,9EURO Efficiency 98,1 95,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 150 < 240Weight and DimensionApproximate weight [kg] 1.500 2.800Width [mm] 1.650 2.650Height [mm] 2.200 2.200Depth [mm] 800+200 800+200Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 4.500 5.500Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16

Inverter RECon 30L-300

Inverter RECon 30L-300-T

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

BACKUPBREAKER

OPTION

BACKUP BREAKER

AC OUTPUT SECTION

1

n

1

2

3

PVSTRING BOX

STR16

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

EMC FILTER

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

TEMPERATURETRANSFORMER

48 49

30L-400

RECon 30L-400, 30L-400-T RECon 30L-400 RECon 30L-400-TInput (DC) Field Power Range [kW DC] 280-450 280-450DC Voltage Range MPPT [V] 325-680 325-680Maximum DC voltage [V] 700 700Maximum DC current [A] 1300 1300Number of protected DC inputs 12 12Number of independent MPPT 4 4Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 400 400Max AC output power [kW] 450 450Rated AC current [A] 1160 1160Operating grid voltage [V] 200 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99 96,9EURO Efficiency 98,1 95,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 200 < 320Weight and DimensionApproximate weight [kg] 2.000 2.500*Width [mm] 2.200 2.750*Height [mm] 2.200 2.200Depth [mm] 800+200 800+200Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 6.000 7.000Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16* Transformer Excluded Beside (1200x800x1200h) mm - 1600kg

Inverter RECon 30L-400

Inverter RECon 30L-400-T

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

BACKUPBREAKER

OPTION

BACKUP BREAKER

AC OUTPUT SECTION

1

n

1

2

3

PVSTRING BOX

STR16

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

EMC FILTER

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

TEMPERATURETRANSFORMER

50 51

30L-500

RECon 30L-500 RECon 30L-500Input (DC) Field Power Range [kW DC] 350-560DC Voltage Range MPPT [V] 325-680Maximum DC voltage [V] 700Maximum DC current [A] 325Number of protected DC inputs 15Number of independent MPPT 5Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 500Max AC output power [kW] 560Rated AC current [A] 1450Operating grid voltage [V] 200Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99EURO Efficiency 98,1Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 250Weight and DimensionApproximate weight [kg] 2.500Width [mm] 2.750Height [mm] 2.200Depth [mm] 800+200Environmental DataProtection Degree IP20Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 7.500Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

Inverter RECon 30L-500INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

BACKUPBREAKER

OPTION

BACKUP BREAKER

AC OUTPUT SECTION

1

n

1

2

3

PVSTRING BOX

STR16

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

EMC FILTER

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

52 53

30L-600

RECon 30L-600 RECon 30L-600Input (DC) Field Power Range [kW DC] 400-670DC Voltage Range MPPT [V] 325-680Maximum DC voltage [V] 700Maximum DC current [A] 325Number of protected DC inputs 18Number of independent MPPT 6Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 600Max AC output power [kW] 670Rated AC current [A] 1740Operating grid voltage [V] 200Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99EURO Efficiency 98,1Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 300Weight and DimensionApproximate weight [kg] 3.000Width [mm] 3.300Height [mm] 2.200Depth [mm] 800+200Environmental DataProtection Degree IP20Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 9.000Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

Inverter RECon 30L-600INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

BACKUPBREAKER

OPTION

BACKUP BREAKER

AC OUTPUT SECTION

1

n

1

2

3

PVSTRING BOX

STR16

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

EMC FILTER

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

54 55

30H-150

RECon 30H-150, 30H-150-T RECon 30H-150 RECon 30H-150-TInput (DC) Field Power Range [kW DC] 100-170 100-170DC Voltage Range MPPT [V] 470-885 470-885Maximum DC voltage [V] 900 900Maximum DC current [A] 325 325Number of protected DC inputs 3 3Number of independent MPPT 1 1Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 150 150Max AC output power [kW] 170 170Rated AC current [A] 290 218Operating grid voltage [V] 300 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99,3 97,5EURO Efficiency 98,7 96,6Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 50 < 80Weight and DimensionApproximate weight [kg] 500 1.200Width [mm] 550 1.250Height [mm] 2.200 1.800Depth [mm] 800+200 800+200Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 1.500 2.500Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16

Inverter RECon 30H-150

Inverter RECon 30H-150-T

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

BACKUPBREAKER

OPTION

BACKUP BREAKER

AC OUTPUT SECTION

1

n

1

2

3

PVSTRING BOX

STR16

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

EMC FILTER

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

TEMPERATURETRANSFORMER

56 57

30H-300

RECon 30H-300, 30H-300-T RECon 30H-300 RECon 30H-300-TInput (DC) Field Power Range [kW DC] 200-335 200-335DC Voltage Range MPPT [V] 470-885 470-885Maximum DC voltage [V] 900 900Maximum DC current [A] 650 650Number of protected DC inputs 6 6Number of independent MPPT 2 2Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 300 300Max AC output power [kW] 335 335Rated AC current [A] 580 435Operating grid voltage [V] 300 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99,3 97,5EURO Efficiency 98,7 96,6Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 100 < 160Weight and DimensionApproximate weight [kg] 1.000 2.200Width [mm] 1.100 2.100Height [mm] 2.200 2.200Depth [mm] 800+200 800+200Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 3.000 4.000Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16

Inverter RECon 30H-300INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

BACKUPBREAKER

OPTION

BACKUP BREAKER

AC OUTPUT SECTION

1

n

1

2

3

PVSTRING BOX

STR16

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

EMC FILTER

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

TEMPERATURETRANSFORMER

Inverter RECon 30H-300-T

58 59

30H-450

RECon 30H-450, 30H-450-T RECon 30H-450 RECon 30H-450-TInput (DC) Field Power Range [kW DC] 300-500 300-500DC Voltage Range MPPT [V] 470-885 470-885Maximum DC voltage [V] 900 900Maximum DC current [A] 975 975Number of protected DC inputs 9 9Number of independent MPPT 3 3Voltage ripple < 3% @ Pn < 3% @ PnStandard DC devicesDC fuses on both terminals Yes YesDC on-load isolator Yes YesInsulating monitoring system Yes YesSurge arrestor Yes YesOutput (AC)Rated AC output power [kW] 450 450Max AC output power [kW] 500 500Rated AC current [A] 870 653Operating grid voltage [V] 300 400Operating grid frequency [Hz] 50/60 50/60Harmonic distortion of grid current (THD) ≤ 2% @ Pn ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ Pn ≥ 0,99 @ PnGrid structure IT TN-SStandard AC devicesContactor (DDG) with fuses Yes YesAutomatic Circuit breaker Yes YesGrid Interface Protection Relay No YesEfficiencyMaximum efficiency 99,3 97,5EURO Efficiency 98,7 96,6Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPS 230 Vac, 50Hz from UPSNight consumption [W] < 150 < 240Weight and DimensionApproximate weight [kg] 1.500 2.000*Width [mm] 1.650 2.200*Height [mm] 2.200 2.200Depth [mm] 800+200 800+200Environmental DataProtection Degree IP20 IP20Operating temperature range [°C] - 10 / + 40 - 10 / + 40Cooling Air Flow [m3/h] 4.500 5.500Relative Humidity (not condensing) 5% ÷ 95% 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000 1000Maximum noise level [dBA @ 1m] < 70 < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN61000-3-12CE Compliance YesOther Standard CEI 0-16* Transformer Excluded Beside (1200x800x1200h) mm - 1600kg

Inverter RECon 30H-450-T

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

BACKUPBREAKER

OPTION

BACKUP BREAKER

AC OUTPUT SECTION

1

n

1

2

3

PVSTRING BOX

STR16

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

EMC FILTER

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

TEMPERATURETRANSFORMER

Inverter RECon 30H-450

60 61

30H-600

RECon 30H-600 RECon 30H-600Input (DC) Field Power Range [kW DC] 400-670DC Voltage Range MPPT [V] 470-885Maximum DC voltage [V] 900Maximum DC current [A] 1300Number of protected DC inputs 12Number of independent MPPT 4Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 600Max AC output power [kW] 670Rated AC current [A] 1160Operating grid voltage [V] 300Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99,3EURO Efficiency 98,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 200Weight and DimensionApproximate weight [kg] 2.000Width [mm] 2.200Height [mm] 2.200Depth [mm] 800+200Environmental DataProtection Degree IP20Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 6.000Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

Inverter RECon 30H-600INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

BACKUPBREAKER

OPTION

BACKUP BREAKER

AC OUTPUT SECTION

1

n

1

2

3

PVSTRING BOX

STR16

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

EMC FILTER

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

62 63

30H-750

RECon 30H-750 RECon 30H-750Input (DC) Field Power Range [kW DC] 500-835DC Voltage Range MPPT [V] 470-885Maximum DC voltage [V] 900Maximum DC current [A] 1625Number of protected DC inputs 15Number of independent MPPT 5Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 750Max AC output power [kW] 835Rated AC current [A] 1450Operating grid voltage [V] 300Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99,3EURO Efficiency 98,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 250Weight and DimensionApproximate weight [kg] 2.500Width [mm] 2.750Height [mm] 2.200Depth [mm] 800+200Environmental DataProtection Degree IP20Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 7.500Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

Inverter RECon 30H-750INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

BACKUPBREAKER

OPTION

BACKUP BREAKER

AC OUTPUT SECTION

1

n

1

2

3

PVSTRING BOX

STR16

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

EMC FILTER

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

64 65

30H-900

RECon 30H-900 RECon 30H-900Input (DC) Field Power Range [kW DC] 600-1000DC Voltage Range MPPT [V] 470-885Maximum DC voltage [V] 900Maximum DC current [A] 1950Number of protected DC inputs 18Number of independent MPPT 6Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 900Max AC output power [kW] 1000Rated AC current [A] 1740Operating grid voltage [V] 300Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 2% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99,3EURO Efficiency 98,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 300Weight and DimensionApproximate weight [kg] 3.000Width [mm] 3.300Height [mm] 2.200Depth [mm] 800+200Environmental DataProtection Degree IP20Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 9.000Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

Inverter RECon 30H-900INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

CONNECTION KIT

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

BACKUPBREAKER

OPTION

BACKUP BREAKER

AC OUTPUT SECTION

1

n

1

2

3

PVSTRING BOX

STR16

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

INVERTER CABINET

DC INPUT SECTION POWER CONVERTION SECT. AC OUTPUT SECTION

EMC FILTER

EMC FILTER

EMC FILTER

INSULATION MONITOR

GENERATOR CONTACTOR

SYNCHRON. DISTRIBUT.

AUX. SUPPLYDISTRIBUT.

REPEATERRELAY

I>

66 67

RECon 65H-340

Inverter RECon 65H-340

65H-340

RECon 65H-340Input (DC) Field Power Range [kW DC] 224-378DC Voltage Range MPPT [V] 480-930Maximum DC voltage [V] 1000Maximum DC current [A] 715Number of protected DC inputs 6Number of independent MPPT 1Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 340Max AC output power [kW] 375Rated AC current [A] 655Operating grid voltage [V] 300Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 3% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99,3EURO Efficiency 98,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 70Weight and DimensionApproximate weight [kg] 750Width [mm] 800Height [mm] 2.200Depth [mm] 800+200Environmental DataProtection Degree IP40 (IP 54 Optional)Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 3.000Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

REPEATERRELAY

I>

68 69

RECon 65H-680

65H-680

RECon 65H-680Input (DC) Field Power Range [kW DC] 448-756DC Voltage Range MPPT [V] 480-930Maximum DC voltage [V] 1000Maximum DC current [A] 1430Number of protected DC inputs 12Number of independent MPPT 2Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 680Max AC output power [kW] 750Rated AC current [A] 1310Operating grid voltage [V] 300Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 3% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99,3EURO Efficiency 98,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 70Weight and DimensionApproximate weight [kg] 750Width [mm] 800Height [mm] 2.200Depth [mm] 800+200Environmental DataProtection Degree IP40Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 3.000Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 140User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

Inverter RECon 65H-680INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

REPEATERRELAY

I>

70 71

RECon 65H-1020

Inverter RECon 65H-1020

65H-1020

RECon 65H-1020Input (DC) Field Power Range [kW DC] 672-1134DC Voltage Range MPPT [V] 480-930Maximum DC voltage [V] 1000Maximum DC current [A] 2145Number of protected DC inputs 18Number of independent MPPT 3Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 1020Max AC output power [kW] 1125Rated AC current [A] 1965Operating grid voltage [V] 300Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 3% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99,3EURO Efficiency 98,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 210Weight and DimensionApproximate weight [kg] 750Width [mm] 800Height [mm] 2.200Depth [mm] 800+200Environmental DataProtection Degree IP40 (IP 54 Optional)Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 9.000Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

REPEATERRELAY

I>

72 73

RECon 65H-1360

Inverter RECon 65H-1360

65H-1360

RECon 65H-1360Input (DC) Field Power Range [kW DC] 896-1512DC Voltage Range MPPT [V] 480-930Maximum DC voltage [V] 1000Maximum DC current [A] 2860Number of protected DC inputs 24Number of independent MPPT 4Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 1360Max AC output power [kW] 1500Rated AC current [A] 2620Operating grid voltage [V] 300Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 3% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99,3EURO Efficiency 98,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 210Weight and DimensionApproximate weight [kg] 750Width [mm] 800Height [mm] 2.200Depth [mm] 800+200Environmental DataProtection Degree IP40 (IP 54 Optional)Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 12.000Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

REPEATERRELAY

I>

74 75

RECon 65H-1700

Inverter RECon 65H-1700

65H-1700

RECon 65H-1700Input (DC) Field Power Range [kW DC] 1120-1890DC Voltage Range MPPT [V] 480-930Maximum DC voltage [V] 1000Maximum DC current [A] 3575Number of protected DC inputs 30Number of independent MPPT 5Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 1700Max AC output power [kW] 1875Rated AC current [A] 3275Operating grid voltage [V] 300Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 3% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99,3EURO Efficiency 98,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 210Weight and DimensionApproximate weight [kg] 750Width [mm] 800Height [mm] 2.200Depth [mm] 800+200Environmental DataProtection Degree IP40 (IP 54 Optional)Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 15.000Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

REPEATERRELAY

I>

76 77

RECon 65H-2040

Inverter RECon 65H-2040

65H-2040

RECon 65H-2040Input (DC) Field Power Range [kW DC] 1344-2268DC Voltage Range MPPT [V] 480-930Maximum DC voltage [V] 1000Maximum DC current [A] 4290Number of protected DC inputs 36Number of independent MPPT 6Voltage ripple < 3% @ PnStandard DC devicesDC fuses on both terminals YesDC on-load isolator YesInsulating monitoring system YesSurge arrestor YesOutput (AC)Rated AC output power [kW] 2040Max AC output power [kW] 2250Rated AC current [A] 3930Operating grid voltage [V] 300Operating grid frequency [Hz] 50/60Harmonic distortion of grid current (THD) ≤ 3% @ PnPower factor (cos j) ≥ 0,99 @ PnGrid structure ITStandard AC devicesContactor (DDG) with fuses YesAutomatic Circuit breaker YesGrid Interface Protection Relay NoEfficiencyMaximum efficiency 99,3EURO Efficiency 98,7Power consumptionAuxiliary Supply 230 Vac, 50Hz from UPSNight consumption [W] < 210Weight and DimensionApproximate weight [kg] 750Width [mm] 800Height [mm] 2.200Depth [mm] 800+200Environmental DataProtection Degree IP40 (IP 54 Optional)Operating temperature range [°C] - 10 / + 40Cooling Air Flow [m3/h] 18.000Relative Humidity (not condensing) 5% ÷ 95%Maximum altitude without derating (a.s.l.) [m] 1000Maximum noise level [dBA @ 1m] < 70User interface and communicationLocal user interface Touch Screen O. P.String box communication port RS485PC communication port RS232 - RS485Remote communication port (optional) Ethernet, (GPRS)Standard complianceEMC EN 61000-6-2, EN 61000-6-4CE Compliance YesOther Standard CEI 0-16

INVERTER CABINET

SYNCHRON. DISTRIBUT. OPEN

CLOSE

STATUS

STATUS

ENERGY METER

GRID PROTECTIONRELAYV> F>V< F<

GRID BREAKER

67N Io> I>

PG

3

INTERFACE CABINET TRANSFORMER MV CABINET

INTERFACEBREAKER

GENERATOR CONTACTOR

AUX. SUPPLYDISTRIBUT.

POWER CONVERTION SECT.PV LV

=

DC INPUT SECTIONSTRING BOXSTR16

1

2

3

TRANSFORMERMONITORTEMPERATURE

ACINSULATIONRELAY

OPTION

OPTION

AC OUTPUT SECTION

1

EMC FILTER

EMC FILTER

INSULATION MONITOR

MV

TRANSFORMER PROTECTION RELAY

REPEATERRELAY

I>

78 79RST - RECon StationVibrate Reinforced Concrete Monoblock Kiosk for Photovoltaic systems

RECon Station (RST-xxx) is a monoblock kiosk made from vibrate reinforced concrete, designed to contain all the components necessary for the connection of photovoltaic systems to the Grid, from 100kWp to 1,3MWp.The RST represents a “plug & play” solution already assembled and tested in the factory. It is ready to be transported and installed on-site, connected through the string boxes to the PV panels, then connected to the grid.

This pre-assembled solution reduces the costs of engineering, transportation and on-site installation. Thanks to its reduced dimension and weight, it is not necessary to provide oversize transportation.The internal floating floor allows simplified maintenance and cabling of inverters and equipments inside the kiosk.The RST is also provided with an industrial air conditioning system which grants full capacity in each operating condition.The operating temperatures of components are preserved within the rated and optimal value therefore granting the longest life expectancy with great benefit to the production continuity and reliability.

478

Models AvailableLine 5,85 - MV: Kiosk for 140kWp/500kWp peak power for MV connection including:Inverter RECon 30H/L-xxxInterface Cabinet LV QI-xxxMV SwitchgearMV TransformerBT/BT Auxiliary TransformerAuxiliary Power PanelUPSAir Conditioner Line 7,5 - MV: Kiosk for 510kWp/1MWp peak power for MV connection including:Inverter RECon 30H/L-xxxInterface Cabinet LV QI-xxxMV SwitchgearMV TransformerBT/BT Auxiliary TransformerAuxiliary Power PanelUPSAir ConditionerLine 7,5+2,55 - MT: Kiosk for 800kWp ÷ 1,3MWp peak power for MV connection including:Inverter RECon 30H/L-xxxInterface Cabinet LV QI-xxxMV SwitchgearMV TransformerBT/BT Auxiliary TransformerAuxiliary Power PanelUPSAir Conditioner

80 81Configuration RST - 50

Line 5,85-MV: RST50 - RST33 - RST22

Model RECon Station RST50Peak Power 340 – 500kWMonoblock Kiosk external dimensions CAV 5850x2300x2950 mmInverter RECon 30H-450 (3 modules) Transformer LV/MV 500kVAQI-45 Model RECon Station RST33Peak Power 250 – 330kWMonoblock Kiosk external dimensions CAV 5850x2300x2950 mmInverter RECon 30H-300 (2 modules) Transformer LV/MV 400kVAQI-33 Model RECon Station RST22Peak Power 140 – 220kWMonoblock Kiosk external dimensions CAV 5850x2300x2950 mmInverter RECon 30L-200 (2 modules) Transformer LV/MV 400kVAQI-33

Section

Plan

82 83Configuration RST - 100

Line 7,5-MV: RST100 - RST83 - RST66

Model RECon Station RST100Peak Power 840 – 1000kWMonoblock Kiosk external dimensions CAV 7500x2300x2950 mmInverter RECon 30H-900 (6 modules) Transformer LV/MV 1000kVAQI-90 Model RECon Station RST83Peak Power 670 – 830kWMonoblock Kiosk external dimensions CAV 7500x2300x2950 mmInverter RECon 30H-750 (5 modules) Transformer LV/MV 800kVA / 1000kVAQI-70 Model RECon Station RST66Peak Power 510 – 660kWMonoblock Kiosk external dimensions CAV 7500x2300x2950 mmInverter RECon 30H-600 (4 modules) Transformer LV/MV 630kVA / 800kVAQI-60

Section

Plan

84 85Configuration RST - 130

Line MV: RST130

Model RECon Station RST130Peak Power 1000 – 1340kWMonoblock Kiosk external dimensions CAV MV 2550x2300x2950 mmMonoblock Kiosk external dimensions CAV Inverter 7500x2300x2950 mmTransformer LV/MV 1250 kVA / 1600kVAInverter 2x30H-600 QI-60 2

Section

Plan

86 87

Interface and parallel LV Cabinet for MV connected systems

FRIEM has carried out a complete series for Medium Voltage connected systems where the RECon Inverters without LV integrated transformer are installed: • LV Interface Cabinet with LV Interface Protection• LV Parallel Cabinet.

Both have to be connected to the inverters, and include the below listed dispositives:Thanks to their design, they should be placed perfectly beside the inverter cabinets, reducing the overall dimension, enabling a complete isolation of the connection bars between inverter and cabinet.

LV Interface Cabinet LV Parallel Cabinet Pn AC QI-20 QP-20 200 kW QI-25 QP-25 250 kW QI-30 QP-30 300 kW QI-35 QP-35 350 kW QI-40 QP-40 400 kW QI-45 QP-45 450 kW QI-50 QP-50 500 kW QI-60 QP-60 600 kW QI-70 QP-70 700 kW QI-75 QP-75 750 kW QI-90 QP-90 900 kWDimensions: 550 x (800+200) x 2.200mmWeight: from 300kg to 500kg

Equipment installed in the LV Interface Cabinet LV Parallel Cubicle:Description QI: LV Interface Cabinet QP: LV Parallel Cabinet LV Interface Switch (3 Phase Automatic Switch)with opening and closing coils, CEI 0-16 certified Yes NoSafety switch for the LV Interface Switch (for power over 400kW) Yes NoInterface Protective Relay CEI0-16 Certified Yes No3 Phase Automatic Switch with opening and closing coils No YesMeasurement CTs for Energy Meter Yes (Optional) Yes (Optional)Energy Meter Yes (Optional) Yes (Optional)AC side Ground fault Protective Relay Yes (Optional) Yes (Optional)LV/MV Transformer’s Temperature metering device Yes (Optional) Yes (Optional)

QI - Interface Cabinet

Models Available: QI -20 Rated Output Power = 200kW AC QI -25 Rated Output Power = 250kW AC QI -30 Rated Output Power = 300kW AC QI -35 Rated Output Power = 350kW AC QI -40 Rated Output Power = 400kW AC QI -45 Rated Output Power = 450kW AC QI -50 Rated Output Power = 500kW AC QI -60 Rated Output Power = 600kW AC QI -70 Rated Output Power = 700kW AC

QI -80 Rated Output Power = 800kW AC QI -90 Rated Output Power = 900kW AC

STR - String Box

Models Available: STR-8 String Box with 8 Current Input STR-12 String Box with 12 Current Input STR-16 String Box with 16 Current Input

STR-N String Box with n Current Input (base model) STR-n.D String Box with n Current Input + Diodes STR-n.C String Box with n Current Input + Fast-On Connectors STR-n.BI String Box with n Current Input + Shunt Release STR-n.BV String Box with n Current Input + U/V Release STR-n.A String Box with n Current Input + Selfpowered

RMS - RECon Monitoring System PV Plants centralized Supervision System for acquisition and recording of Inverters and other equipments measurements and singnals. The plant data and alarms can be sent also via GPRS/GSM connection.

RDA - 1: Wind and ambient Temperature Acquisition Module

RDP - 1: PV Module Data Acquisition

Norme ApplicateAccessories

88 89

Electrical Drawing

Electrical Characteristics Number of current inputs 8 ÷ 12 ÷ 16DC Maximum Voltage 1000VccDC Maximum Output Current 128÷192AccShort Circuit Maximum Current 192÷256AccDC fuses (positive pole) 10,3 x 38 mm 12÷15Acc - 1kVccDC fuses (negative pole) 10,3 x 38 mm 12÷15Acc – 1kVcc (optional)Withdrawable fuse holder YesAUX power supply 230 Vca ± 10%Standard DC devices1000V Surge arrestor with microswitch YesOutput (Inverter side) Disconnector Switch, 4 poles in s.c. (2NAO + 2NC aux.contacts), rated 1000V dc - 315÷400A dc Current Opening Coil OptionalLow Voltage Opening Coil OptionalReverse Current protection with diode OptionalStandard AC devicesString Current measurement 8 - 16DC Isolator status YesString Fault alarm YesSurge arrestor trip YesTemperature module 1÷2 Irradiation module 1÷2Standard AC devicesDimensions: (l x p x h)mm 760x380x230 mmWeight STR-8,-12,-16 20, 21, 22 kg

String Box

A complete device for parallel connection and monitoring of the strings for photovoltaic generator.FRIEM string box enables the parallel connection of 8 (STR-8), 12 (STR-12) or 16 (STR-16) strings, which, through a disconnecting switch, are connected to the inverter.The string box has also an overvoltage protection device.

The continuous measurement of the current for each string, of the irradiation and temperature of the panels (through dedicated sensors), allows a complete check of the operation of the solar modules.Transmission of measures and of protection’s status through serial communication with the inverters are integrated in the monitoring system.Cover of the string box is realized in strong polycarbonate, weatherproof, with IP65 protection degree suitable for indoor and protected outdoor installation.

Models AvailableModel Description STR-8 String Box with 8 Current Input (base model)STR-8 .D String Box with 8 Current Input + DiodesSTR-8 .C String Box with 8 Current Input + Fast-On Connectors STR-8 .BI String Box with 8 Current Input + Shunt Release STR-8 .BV String Box with 8 Current Input + U/V ReleaseSTR-8 .A String Box with 8 Current Input + Selfpowered STR-12 String Box with 12 Current Input (base model)STR-12 .D String Box with 12 Current Input + DiodesSTR-12 .C String Box with 12 Current Input + Fast-On Connectors STR-12 .BI String Box with 12 Current Input + Shunt Release STR-12 .BV String Box with 12 Current Input + U/V ReleaseSTR-12 .A String Box with 12 Current Input + Selfpowered STR-16 String Box with 16 Current Input (base model)STR-16 .D String Box with 16 Current Input + DiodesSTR-16 .C String Box with 16 Current Input + Fast-On Connectors STR-16 .BI String Box with 16 Current Input + Shunt Release STR-16 .BV String Box with 16 Current Input + U/V ReleaseSTR-16 .A String Box with 16 Current Input + Selfpowered

Note: All the options can be combined when ordered.

90 91Here below are listed the main services included in the annual subscription:- Possibility of collection and recording of the plant data.- Easy customizable generation of SMS and/or e-mails in case of alarms.- Alarm and measurement recording.- Display of report tables and trend of data.- Efficiency forecast.- Optimization of the plants assistance.

Other devices (energy measuring instruments, MV cabinet, surveillance and alarm systems etc.) can be connected through interface RS232/485, digital input and USB ports.

The RMS system is provided with a RJ45 communication port, that allows the connection to the LAN system or to a router connected to the web. Besides is possible to use a GSM integrated modem in the Data logger (SIM card for internet connection exluded).

The RMS system can be equipped with the following communication models: - Ethernet Interface (standard).- Modbus RS232 Interface for RECon Inverter (standard).- WI-FI Interface (optional).- GPRS Interface (optional) SIM excluded.- I/O Interface (optional).

RMS: Recon Monitoring System

FRIEM offers a complete system for the remote control and supervision of photovoltaic systems from 33kWp to multi MWp.Thanks to a web application the users have access to a dedicated web portal, where they are reported in real time, with diagrams and tables, the information on measures and data elaboration, monitoring the system performances.

An annual fee foresees the log-in to the dedicated web portal, which records the data on a server hosted into a web farm, equipped with air conditioning, UPS back up, power supply and alarm security system.The annual fee includes maintenance and updating of the software installed for the management of the data and the web pages. FRIEM’s technical staff are available in real time in case of need.

Technical Characteristics Number of current inputs 8 ÷ 12 ÷ 16Memory 1 GB DDR2 667 MHzEthernet LAN 1 x 10/100/1000 MbpsSerial Interfaces 2 x RS-232 port, 1 x RS-232/422/485 port USB Interfaces 6 x USB 2.0Storage SSD CompactFlash socket for type I/IIPower Input Votage 12 VMinimum Power Input 12 V, 1.12 APower Adapter AC to DC, DC 12 V/3.0 A, 36 W (Optional)Power Consumption 12W Construction Aluminum housingMounting Desk/wall-mountingDimensions (WxHxD) 264.5 mm x 69.2 mm x 137.25 mmWeight 2 kgOperating Temperature -20 - 60° CStorage Temperature -40 - 85° CRelative Humidity 95% @ 40° C (non-condensing)EMC CE/FCC Class A, CCC, BSMI Safety Certifications UL, CCC, BSMI

Power Supply SystemPower Electronics & Automation