Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
Reducing cooling energy by system innovation
Yi Jiang
Operating agency of EBC Annex 59
Building energy Research center
Tsinghua University
IEA Annex 59 Low temperature heating & high temperature cooling
Where is the energy lost through cooling?
Indoor→ chilled water → chiller → cooling water → cooling tower → outdoor
2
0
5
10
15
20
25
30
35
40
-0.25 0 0.25 0.5 0.75 1 1.25 1.5
Tem
pera
ture
/o C
Heat q /W
Evaporation Temperature
Indoor temperature
Outdoor wet bulb temperature
Air in FCU
Chilled water
Condensing Temperature
Cooling water
ΔT1
ΔT2
ΔT3
ΔT7
ΔT5
ΔT
ΔT6
Q0.5Q
ΔT4
Tin, ωin Outdoor air
AHU
Evap
Cond
Com Thro
Te
Tc Cooling tower
Where is the energy lost through cooling?
The real demand for space cooling is just raising the heat Q for 3K from 25℃ indoor to 28 ℃ outdoor, the required work is 3Q [WK]
However the chiller does lift up the heat Q from 5 ℃ at the evaporator to 40 ℃ at the condenser, the actual work is 35Q [WK], as many as 11 times!
The additional 32Q have been paid for completing the heat transfer process as well as heat flux mixed with different temperature during the heat transportation process from indoor to outdoor
The other reason is that dehumidification required. To make moisture condensation, low temperature below dew point as the cooling source is needed
3
An Innovation of space cooling system Separate humidity control from temperature control: THIC
An independent air system added to remove latent heat for humidity control
Temperature can then be controlled by a high temperature cooling source (eg. 15℃ to 20℃) to remove sensible heat only
As sensible heat normally takes more than 70% of the total heat load, high efficiency cooling source can be used to remove sensible heat Underground water or underground heat exchanger if ground temperature is
below 15℃ Evaporate cooling can also provide cooling source if the dew point outdoor is
below 15℃ COP for compression chiller can be achieved at 9 ~ 10 comparing with 5~6 at
normal state
Reduce the temperature difference between indoor space and cooling source so to raise required cooling source temperatures as high as possible
Reduce the power of fans and pumps by improvement of the heat delivering system
4
Separate humidity control from temperature control (THIC) • Humidity control as well as indoor air quality: Dried
outdoor air • Temperature control: High temperature cooling source (or
low temperature heating source in winter)
5
Outdoor air processor
Summer: Cooling source Winter: Heat resource
Displacement vent
Personalized vent.
Radiant panel
Dry FCU
Air-conditioning devices Terminal
Control indoor humidity and CO2
……
Control indoor temperature
Dry air
……
Humidity control subsystem
Temperature control subsystem
Indoor environment
16~19°C
Operating principle of the THIC air-conditioning system
* Liu XH, Jiang Y, et al. Temperature and Humidity independent Control (THIC) of Air-conditioning System. Berlin: Springer Press, 2014
16℃
An Innovation of space cooling system
Sensible heat removal for Temp. control
In more than 40% of cooling applications in the world the outdoor dew point is below 15℃. Moisture can be removed by air exchange with outdoor. Space cooling is just to remove sensible heat
To raise the cooling source temperature for high efficiency cooling, the key approach is to reduce the Δt during heat delivering process Avoid the mixing loss of heat collection process at
indoor terminals Avoid Δt loss of heat exchange process Avoid the mixing loss of heat fluxes with different
temperature
6
Terminal handling process
Task: collecting heat and moisture from sources
7
Avoid mixing loss of heat collection process at indoor terminals!
Q Q
Tin
Heat sources
Mixing process
Transfer
T
Supply air
Supply water
Indoor stateTin, ωin
Indoor heat sources and moisture sources
Solar radiation
Indoor terminal
Terminal handling process
Heat sources with different temperatures
8
Heat sources’ temp. varying in the range of 26~40ºC, or even higher
平板电视flat-panel tv
message sign
Significant mixing loss from heat sources to indoor air
9
Direct solar radiation
9
Radiant floor surface (Tr)
QsTr Inner surface (Ts) QsTs
Indoor air (Ta)
5
10
15
20
25
30
35
0 10 20 30 40 50 60 70 80 90 100
Tem
pera
ture
/oC
Heat flux W/m2
QsTr
QsTs
Indoor air
Supply air
Chilled water Chilled water
Floor surface
10
5
10
15
20
25
30
35
0 10 20 30 40 50 60 70 80 90 100
Tem
pera
ture
/oC
Heat flux W/m2
Radiant floor Jet ventilation
①
②
①
②
③
Terminal handling process
> Simplify heat transfer process from heat sources to chilled water
10
Heat sources Radiant floor surface Chilled water
Heat sources Indoor air Chilled water Supply air
① ②
① ② ③
11 11
Terminal handling process
> Reducing indoor mixing loss > Decrease temperature gradient in space > Avoid fluid mixture of high temperature with low temperature
0 1000 2000 3000 4000
SystemII
SystemI
Floor radiantion
Floor convection
Floor heat conduction
Envelope convection
Mixture
Air-water convection
Entransy dissipation EnΦ (WoC/m2)
12 12
Terminal handling process
Jet supply air ~20m
~5m
Radiant floor
Displacement supply air
~20m
~2m
5
10
15
20
25
30
35
0 20 40 60 80 100 120 140 160
Tem
pera
ture
/oC
Heat flux W/m2
EnvelopeIndoor air
Supply airChilled water
Convective Entransy Dissipation
Mixture Entransy Dissipation
Convective Entransy Dissipation
Jet ventilation Radiant floor
5
10
15
20
25
30
35
0 20 40 60 80 100 120 140 160
Tem
pera
ture
/oC
Heat flux W/m2
Envelope
Indoor airDisplacement airRadiant floorChilled water
Radiant floor Displacement ventilation
Radiant Entransy
Dissipation
Convective Entransy Dissipation
Convective Entransy Dissipation
Mixture Entransy Dissipation
ConductiveEntransy Dissipation
13
Terminal handling process
13
0 1000 2000 3000 4000
SystemII
SystemI
Floor radiantion
Floor convection
Floor heat conduction
Envelope convection
Mixture
Air-water convection
Entransy dissipation EnΦ (WoC/m2)
> Total entransy dissipation of System II (2411 (W·ºC)/m2)) is less than
that of System I (3413 (W·ºC)/m2))
> Reduced entransy dissipation (1002 (W·ºC)/m2)) by system II equals to
rising 6.3ºC of chilled water temperature.
Entransy dissipation comparison
Terminals with low mixing loss Radiant panels, radiant floor, TABs
14
高さ:3000200間隔で計測
床面
放射パネル
空調室内機
2800Ceiling height:2.8mMeasuring Point:1.5m above floor
Radiant Panel
Indoor Unit
Floor Embedded radiant systems: a) Floor, b) Ceiling, c) Wall, d) TABS
Application
15
Terminal 3 of Xi’an airport Area: 258,000m2, with a maximum height of 36.5m Coming into service since May 2012
The first terminal adopting radiant cooling/heating in China Radiant cooling, displacement ventilation, liquid desiccant …
15
AC system (summer)
Large space area Stratified air conditioning in summer
16
辐射地板
分布式送风末端
渗风
建筑开口
顶部排风(排出高温高湿空气)
2 m
~ 20m
Radiant floor with high temp water
Dry air
Natural ventilation zone
Conditioned temp., low hum. zone Infiltration
Entrance
Displacement ventilation
17
Terminal handling process
1.1m
2.8m
12m
7.4m
1.7m
21.6m
17m
23.9℃
27.6℃
30.3℃
29.0℃
24.8℃
31.4℃
31.1℃
121m
1.1m
2.8m
12m
7.4m
1.7m
17m
1.1m
2.8m
12m
7.4m
1.7m
17m
West Wall
East Wall
Air
Displacement vent. 22.5℃
Displacement vent. 22.5℃
2m
Measured temperatures
Application
18
Radiant floor for cooling (without solar)
14
16
18
20
22
24
10:00
11:00
12:00
13:00
14:00
15:00
16:00
Time
Tem
pera
ture
℃) floor surface (no seat)
floor surface (under seat)
dew point
0
10
20
30
40
50
10:00
11:00
12:00
13:00
14:00
15:00
16:00
Time
Coo
ling
capa
city
(W/m
2 )
Temperatures Cooling capacity
(20~40W/m2)
Application Radiant floor for cooling (with solar) Solar radiation on floor: High intensity, transient process
19
0
40
80
120
160
200
Sola
r rad
iatio
n de
nsity
(W
/m2 )
Time (p.m.)
Point A11min
Point B24min
Point C31min
ABC
0
40
80
120
160
200
Coo
ling
capa
city
(W/m
2 )
Time
Point A Point BPoint C Point D (under chair)
18
20
22
24
26
28
Floo
r sur
face
tem
pera
ture
(°C
)
Time
Point A Point BPoint C Point D (under chair)
Cooling capacity could be higher than 100W/m2 with direct solar radiation
Application
20
T2:
Power consumption Significant energy conservation benefits
T2
T3
Application Radiant terminal in a solar house (Denmark)
21
Embedded pipes
Application Radiant terminal in a solar house (Denmark)
22
Operative temperature and external air temperature during the cooling season
0
5
10
15
20
25
30
35
Hea
t fl
ux
[W/m
2]
Floor cooling
Cooling capacity
Avoid Δt loss of heat exchange process
Direct connection of the cooling source with indoor terminals
Enlarge the heat transfer ability and adjust the flow rates at both sides so to ensure the Δt uniformed along the heat exchange process
23
Tc,out Tc,in
Th,in Th,out
Th,out
Tc,in
Th,in
Tc,out
T
Tc,in
Tc,out
Th,out
Th,in
x
T
Q
Th,in
Th,out
Tc,in
Tc,out
Unmatched flow rates
Avoid Δt loss of heat exchange process
4~5 K temperature difference for water circulation On-off control for each indoor terminal (radiative)
to obtain near linear control performance Careful design of the water piping system to avoid
large pump power consumed Remove most of control valves and other resistance device
in water loops except on-off control valve Pressure drop: 10~15 m H2O for total water loop circulation
24
× × On-off control
Case study
Evaporative cooling as cooling source Outlet water temperature 15~19℃ to remove sensible heat
25
M
Inlet air O
User heat exchanger 3
1
2
4
1
Exhaust air C
A
Cold water
Inlet air O
A
Tsp
T
• Key parts: countercurrent air cooler/packing tower • Design idea: matched flow rates and parameters
Case study
Evaporative cooling as cooling source
26
Installed in Shihezi Kai Rui Building, now four years well-running.
Shihezi outdoor design air state: dry bulb 32.8℃, wet bulb 21.5 ℃. Designed water out temperature 18.5 ℃, cooling Energy output 120kW.
Case study
Evaporative cooling as cooling source
27
0
5
10
15
20
25
30
35
4019:40
19:40
12:50
18:40
12:10
20:10
13:00
17:40
12:20
17:00
21:40
19:00
23:40
16:50
22:00
22:40
15:20
10:10
14:50
9:50
14:30
19:10
10:40
15:20
20:00
10:10
14:50
19:30
13:00
20:40
15:20
20:00
10:30
15:10
19:50
14:10
18:50
23:30
Tem
pera
ture
(℃)
Inlet dry bulb tempeature(℃)Inlet wet bulb temperautre(℃)Out water temperature (℃)Inlet dew point temperature(℃)
Out water Temperature lower than inlet Wet Bulb Temperature.
Tested COP (sensible heat removed/power of fan and pump) higher than 10.
Case study
Evaporative cooling as cooling source Applications in the dry region (Xinjiang province, China)
28
Shihezi Kai Rui Building
Aksu People’s Hospital Xinjiang Chinese Medicine Hospital
Xinjiang Medical University Hospital
Xinjiang air force hospital
Office building of Xinjiang medicine hospital
Changji medicine hospital
Xinjiang international exhibition center
Suitable region for evaporative cooling
Climate condition: dew point ≤15℃ System requirement: Low Δt loss terminals with on-off control Large water circulation with minimal pressure drop
29
Division: Outdoor Humidity
Ratio: 12g/kg
West China West U.S.
Suitable region for evaporative cooling
Climate condition: dew point ≤15℃
30 Outdoor Humidity Ratio (g/kg)
North Europe
0
10
20
30
40
50
60
0 0.005 0.01 0.015 0.02 0.025
含湿量 /(kg/kg)
温度
/o C OO
RS
转轮除湿
溶液除湿
冷凝除湿
R
S
ω
T
Efficient dehumidification process
Weak point of dehumidification by condensation: Require the cooling source below dew point Reheat, or mix with higher temperature environment
31
For moist region: humidity control is part of the task in space cooling
New approaches for dehumidification are required!
Reheating
Conventional desiccant wheel
Efficient dehumidification process
New approaches for dehumidification Liquid desiccant dehumidification
32
Fresh air Supply air
Return air Exhaust air
Throttle
Condenser
Evaporator
Compressor
Two-stage total heat recovery
Multi-stage process for dehumidification, matched parameters
Efficient dehumidification process
New approaches for dehumidification Liquid desiccant dehumidification
33
Close to the iso-relative humidity line instead of isenthalpic line
Efficient dehumidification process
New approaches for dehumidification Liquid desiccant dehumidification
34
Cooling Dehumidify
Deep Dehumidify Total Heat Recovery
Humidify
Fresh air t (°C) 36.0 22.8 22.8 35.9 6.4 4.3
Fresh air d (g/kg) 24.6 8.6 8.6 26.7 2.1 1.6
Supply air t (°C) 17.3 16.1 11.9 30.4 22.5 25.6
Supply air d (g/kg) 8.6 5.1 3.4 19.5 7.2 10.7
Return air t (°C) 26.0 33.2 26.3 26.1 20.5 22.1
Return air d (g/kg) 12.2 18.3 16.3 12.1 4.0 5.1
Exhaust air t (°C) 39.1 43.9 42.2 32.6 7.0 6.6
Exhaust air d (g/kg) 37.3 23.4 24.1 20.3 2.7 2.9
COP 5.00 2.32 1.74 62.5% 6.2 4.6
Efficient dehumidification process
New approaches for dehumidification Solid desiccant dehumidification (DESICA, Japan)
35
压缩机
排风
回风
新风
送风
compressor SA
RA
FA EA
Heat pump utilized for internal cooling in dehumidification
Efficient dehumidification process
New approaches for dehumidification Solid desiccant dehumidification (DESICA, Japan)
36
fresh air
return air
exhausted air
supplied air
Freshair
return air
exhausted air
Suppliedair
heat exchangers glued with silica-gel
heat exchangers glued with silica-gel
after a period:• Four-way valve changes direction• Air valves change direction
Return air
Supply air
Exhaust air
Supply air
Outdoor air
Return air
Outdoor air
Return air
FA
RA
SA
EA
100%
60%
20%
40%
80%
15
20
25
30
35
40
45
5 10 15 20 25ω(g/kg)
T (℃
)
A typical process
Close to the iso-relative humidity line instead of isenthalpic line
COP is as high as 4.0
37
Application——Liquid desiccant
37
Temperature and Humidity Independent control system
Cooling water pump
Outdoor air
Outdoor air processor
Supplied air
Return air Exhaust air
Cooling tower
Chiller Chilled water pump
FCU & radiant panel
1st floor
4th floor
2nd floor
3rd floor
Outdoor air processor 17ºC
37
38
Application——Liquid desiccant
Outdoor air process Chilled water process
Entire system
OAHU Fan Chiller Chilled water pump
Cooling water pump
Cooling tower
Fan Coil Unit
Cooling capacity
/kW 773.0 446.1 1219.1
Energy consump
/kW 166.9 20.0 52.5 30.6 14.6 3.7 19.4 307.7
COP 4.3
(OAHU=4.6) 3.7
(Chiller=8.5) 4.0
39
Application——Liquid desiccant
0
15,000
30,000
45,000
60,000
75,000
90,000
105,000
Apr May Jun Jul Aug Sep Oct
Annual power consumption: 32kWh/(m2 AC area) Common building in Shenzhen: ~50kWh/(m2 AC area) Energy saving: ~30%
Pow
er c
onsu
mpt
ion
/kW
h
40
Application——DESICA
Office building in Japan DESICA for humidity control and VRF for temp. control
41
Application——DESICA
Office building in Japan DESICA for humidity control and VRF for temp. control
42
Application——DESICA
DESICA for humidity control and VRF for temp. control
0.00 0.05 0.10 0.15 0.20 0.25
THICSystem
ConventionalSystem
Average Daily Energy Consumption(kWh/m2・day)
Ventilation Fan
HP Desiccant Compressor
Ventilation Standby PowerRequirement
Inner Unit of VRF
Outer Unit of VRF
VRF Standby PowerRequirement
-46.5%
0.00 0.05 0.10 0.15 0.20 0.25
THICSystem
ConventionalSystem
Average Dayly Energy Consumption(kWh/m2・day)
Ventilation Fan
HP Desiccant Compressor
Ventilation Standby PowerRequirement
Inner Unit of VRF
Outer Unit of VRF
VRF Standby PowerRequirement
-47.4%
Set temperature is 28℃
Set temperature is 26℃
THIC applications in China
43
Dry area: Indirect evap. cooling
Wet area: Dehumidification solution
THIC applications in China: Over 10 million m2 buildings
since 2006
How much energy can be saved? Office building in dry climate Conventional system for cooling: electricity used 50 kWh/㎡,
Total cooling: 100 kWh/㎡, COP=2, fans: 17kWh/㎡, pumps: 11kWh/㎡, chiller:22kWh/㎡
Evaporate cooling with the innovative system: electricity used 23kWh/㎡, 54% saved
Total cooling 100 kWh/㎡, COP=5, fans:8kWh/㎡, pumps: 15kWh/㎡
Office building in moist region Conventional HVAC system for cooling: electricity used 65kWh/㎡
Total cooling:130 kWh/㎡,COP=2, fans:22kWh/㎡, pumps:14kWh/㎡, chiller:29kWh/㎡
THIC system: electricity used 44kWh/㎡, 32% saved Total cooling:130kWh/㎡, dehumidifier with fan: 14kWh/㎡,
pumps:15kWh/㎡, chiller:15kWh/㎡ Latent heat:35kWh/㎡,COPL=2.5, sensible heat:95kWh/㎡,COPs=3.2
44
Conclusion Huge potential saving in space cooling technology! Dry regions, ~40% of current cooling applications
Direct/indirect evaporative cooling instead of mechanical chillers System should be well designed both for indoor terminal and heat
delivering to adapt “high temperature cooling” More than 50% energy can be saved!
Moist regions: east China and US, Japan, south India Humidity should be treated independently with temperature Desiccant humidity control techniques should be applied for
dehumidification Sensible heat should be removed with high temperature cooling
source About 30% saving can be achieved!
45
IEA EBC Annex 59
High Temperature Cooling & Low Temperature Heating In Buildings (2012-2016)
46
This presentation is the summary of EBC Annex 59: High temperature cooling & low temperature heating in buildings
47
Reducing ΔEn in HV&AC system
2. Coupled Temp. & Humid. control Conventional system: coupled control of indoor Temp. & Humid. ~7ºC chilled water is required for cooling & dehumidification
49
0
5
10
15
20
25
30
35
40
-0.25 0 0.25 0.5 0.75 1 1.25 1.5Heat /W
Tem
pera
ture
/o C
Indoor temperature
Outdoor wet bulb temperature
Air in FCU
Chilled water
Evaporating temperature
Condensing temperature
Cooling water
ΔT 1
ΔT 2
ΔT 3
ΔT 4
ΔT 6
ΔT CH
ΔT 5
Q0.5Q
ΔTHP
0
5
10
15
20
25
30
35
40
-0.25 0 0.25 0.5 0.75 1 1.25 1.5Heat /W
Tem
pera
ture
/o C
Condensing temperature
ΔT CH, high T
Q0.5Q
Indoor temperature
Outdoor wet bulb temperature
Air in FCUChilled water
Evaporating temperature
Cooling water
Conventional system THIC system (for Temp. control) Adopting other approaches for Humid. control
ΔEn is significantly reduced for Temp. control in the improved system
49
50
Application in buildings——Data center
50
Conventional system 测试机架Racks
Return air
Rack
HEX
Q Q
Q
Tchip
Q Tcoldsource
Tout
Tin Treturn
Tsupply
Tex
Air flow
Outdoor Environment
Temperature
Heat
Entransy dissipation of rack cooling process
Entransy dissipation of air mixing process
Entransy dissipation of heat exchanging process
Entransy dissipation of heat
flow into outdoor environment
50
Application in buildings——Data center
Internal cooled new system
Server 1
Server 2
Server N
LHP2
LHP 1
Rack intake air(Room temperature)
Rack exhaust air(Room temperature)
Server intake air Server exhaust air
Liquid pipe 2 Steam pipe 2
Liquid pipe 1
Steam pipe 1
LHP 1LHP 2Chilledwater in
Chilledwater out
Room temp Rack temp distribution
Tem
p
℃
51
Compressor power
kW
Fan power
kW
Server power
kW
EER
Indoor air temp ℃
Evaporative temp℃
Supply/ Return air
temp℃
Rack inlet/exhaust air temp ℃
Outdoor air dry/wet bulb
temp ℃
January 2nd
16.8 4.5 58 2.7 23.5 8.7 14/24 24/33 6 / 0.2℃
May 7th 18.0 4.2 56 2.5 24.6 8.5 15/25 24/33 22 /13℃
August 10th
21.0 4.6 58 2.3 25.0 8.2 14/25
25/34
29 /19℃
Cooling tower kW
Chiller 1 power
kW
Chiller 2 power
kW
Pump power
kW
Rack fan kW
Server power
kW
EER
Indoor air temp ℃
Supply/Return water temp ℃
Rack inlet/exhaust air temp℃
January 2nd
2.2 0 0 2 2.9 58 8.2 23.5 9.5/18 23.8/24.2
May 7th 2.2 7.6 0 2 3.1 58 4.0 24.6 12.5/21 24.9/25.3
August 10th
0 6.4 6.8 2 3.1 59 3.2 23.0 9.2/19 23.2/23.8
Former CRAC
Current distributed cooling Former:rack exhaust T=indoor T +9℃ Current:rack exhaust T≈indoor T
52
Compressor power
kW
Fan power
kW
Server power
kW
EER
Indoor air temp ℃
Evaporative temp℃
Supply/ Return air
temp℃
Rack inlet/exhaust air temp ℃
Outdoor air dry/wet bulb
temp ℃
January 2nd
16.8 4.5 58 2.7 23.5 8.7 14/24 24/33 6 / 0.2℃
May 7th 18.0 4.2 56 2.5 24.6 8.5 15/25 24/33 22 /13℃
August 10th
21.0 4.6 58 2.3 25.0 8.2 14/25
25/34
29 /19℃
Cooling tower kW
Chiller 1 power
kW
Chiller 2 power
kW
Pump power
kW
Rack fan kW
Server power
kW
EER
Indoor air temp ℃
Supply/Return water temp ℃
Rack inlet/exhaust air temp℃
January 2nd
2.2 0 0 2 2.9 58 8.2 23.5 9.5/18 23.8/24.2
May 7th 2.2 7.6 0 2 3.1 58 4.0 24.6 12.5/21 24.9/25.3
August 10th
0 6.4 6.8 2 3.1 59 3.2 23.0 9.2/19 23.2/23.8
Former CRAC
Current distributed cooling EER:Increased from 2.6 to 5.7 PUE: Decreased from 1.6 to 1.35
53