Ref: 112177 -BCA-r1 879 Richmond Road, Marsden Park To: Skylife Properties Pty Ltd Project: 879 Richmond Road, Marsden Park Report: BCA Capability Statement Reference No: 112177-BCA-r1-Marsden Park Date: 11 June 2020 Client Contact: Sam Yasseen Email: [email protected] From: Christopher Ward Direct: (02) 8484-4071 Email: [email protected]

Ref: 112177 -BCA-r1 879 Richmond Road, Marsden Park

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Ref: 112177 -BCA-r1 879 Richmond Road, Marsden Park

To: Skylife Properties Pty Ltd

Project: 879 Richmond Road, Marsden Park

Report: BCA Capability Statement

Reference No: 112177-BCA-r1-Marsden Park

Date: 11 June 2020

Client Contact: Sam Yasseen

Email: [email protected]

From: Christopher Ward

Direct: (02) 8484-4071

Email: [email protected]

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 2 of 16

Document Control

Revision Date Description

112177-BCA-r1 5 June 2020 BCA Capability Statement

112177-BCA-r2 11 June 2020 BCA Capability Statement (updated Type of Construction required)

Prepared by Verified by

Christopher Ward Matthew McNamara

Accredited Certifier

Grade A1, BPB 2789

Building Regulations Consultant

Accredited Certifier

Grade A1, BPB 0263

Manager of Building

Regulations

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 3 of 16

Table of Contents

BCA CAPABILITY STATEMENT ................................................................................................................. 4

1 BASIS OF ASSESSMENT .................................................................................................................... 5

1.1. Location and Description ........................................................................................................... 5

1.2. Purpose ..................................................................................................................................... 5

1.3. Limitations ................................................................................................................................. 5

1.4. Design Documentation .............................................................................................................. 6

2 BUILDING DESCRIPTION .................................................................................................................... 7

2.1. Rise in Storeys (Clause C1.2) ................................................................................................... 7

2.2. Classification (Clause A6.0) ...................................................................................................... 7

2.3. Effective Height (Clause A1.0) .................................................................................................. 7

2.4. Type of Construction Required (Table C1.1) ............................................................................ 7

2.5. Floor Area and Volume Limitations (Table C2.2) ...................................................................... 7

2.6. Fire Compartments ................................................................................................................... 7

2.7. Exits ........................................................................................................................................... 7

2.8. Climate Zone (Clause A1.0) ...................................................................................................... 7

2.9. Location of Fire-source features ............................................................................................... 8

3 ESSENTIAL FIRE SAFETY MEASURES ............................................................................................. 9

4 FIRE RESISTANCE LEVELS ............................................................................................................. 11

5 BUILDING CODE OF AUSTRALIA ASSESSMENT .......................................................................... 13

5.1. Section C – Fire Resistance .................................................................................................... 13

5.2. Section D – Occupant Access and Egress ............................................................................. 13

5.3. Section E – Services and Equipment ...................................................................................... 13

5.4. Section F – Health and Amenity.............................................................................................. 14

ANNEXURE A DESIGN DOCUMENTATION .......................................................................................... 15

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 4 of 16

BCA CAPABILITY STATEMENT

The architectural design documentation as referred to in Annexure A has formed a high-level review of the

development against the Building Code of Australia, (BCA) and it is considered that such documentation is

capable of complying with BCA.

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 5 of 16

1 BASIS OF ASSESSMENT

1.1. Location and Description

The building development, the subject of this report, is located at 879 Richmond Road, Marsden Park.

The building consists of proposed retail tenancies and external carparking areas.

Figure 1. Site Location (Sixmaps).

1.2. Purpose

Reference is made to our high-level assessment of the Development Application architectural design

development drawings for the proposed development against the BCA 2019 and to provide a BCA

Capability Statement.

1.3. Limitations

This statement does not include nor imply any detailed assessment for design, compliance or upgrading

for:

(a) the structural adequacy or design of the building;

(b) the inherent derived fire-resistance ratings of any proposed structural elements of the building (unless

specifically referred to); and

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 6 of 16

(c) the design basis and/or operating capabilities of any proposed electrical, mechanical or hydraulic fire

protection services.

This report does not include, or imply compliance with:

(a) the National Construction Code – Plumbing Code of Australia Volume 3

(b) the Disability Discrimination Act 1992 including the Disability ((Access to Premises – Buildings)

Standards 2010 – unless specifically referred to), (Note: The provision of disabled access to the

subject development has been assessed against the deemed to satisfy provision of Part D3 and F2.4

of BCA2019 only);

(c) Demolition Standards not referred to by the BCA;

(d) Work Health and Safety Act 2011;

(e) Requirements of Australian Standards unless specifically referred to;

(f) Requirements of other Regulatory Authorities including, but not limited to, Telstra,

Telecommunications Supply Authority, Water Supply Authority, Electricity Supply Authority, Work

Cover, Roads and Maritime Services (RMS), Local Council, ARTC, Department of Planning and the

like.

1.4. Design Documentation

This report has been based on the Design plans and Specifications listed in Annexure A of this Report.

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 7 of 16

2 BUILDING DESCRIPTION

For the purposes of the Building Code of Australia (BCA) the development may be described as follows.

2.1. Rise in Storeys (Clause C1.2)

The building has been assessed as having a rise in storeys of one (1).

2.2. Classification (Clause A6.0)

The building has been classified as follows.

Table 1. Building Classification

Class Level Description

Class 6 Ground Level Retail tenancie(s)

2.3. Effective Height (Clause A1.0)

The building has an effective height of less than 12 metres.

2.4. Type of Construction Required (Table C1.1)

The building is required to be constructed as Type A Construction based on the floor area and volume

limitations in Table C2.2 of the BCA.

2.5. Floor Area and Volume Limitations (Table C2.2)

The building is subject to maximum floor area and volume limits of a building of Type A construction:-

Class 6 Maximum Floor Area 5,000 m2

Maximum Volume 30,000 m3

2.6. Fire Compartments

The building has been considered as one large fire compartment and tenancies are not separated by fire

walls.

2.7. Exits

The following points in the building have been assumed as the exits:

The western elevation front entry doorways to each Retail Tenancy;

The eastern rear elevation double doorways from each Retail Tenancy; and

Additional exit doorway(s) located approximately midway along the northern and southern

elevations of the building are required.

The exits will be required to be reviewed as part of the tenancy fit-outs.

2.8. Climate Zone (Clause A1.0)

The building is located within Climate Zone 6.

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 8 of 16

2.9. Location of Fire-source features

The fire source features for the subject development are:

North: The side allotment boundary (1.2 m)

South: The side allotment boundary (~16.8 m)

East: The rear allotment boundary (~16.5 m)

West: The far side of Richmond Road (>6 m)

In accordance with Clause 2.1 of Specification C1.1, a part of a building element is exposed to a fire-source

feature if any of the horizontal straight lines between that part and the fire-source feature, or vertical

projection of the feature, is not obstructed by another part of the building that–

(a) has an FRL of not less than 30/–/–; and

(b) is neither transparent nor translucent.

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 9 of 16

3 ESSENTIAL FIRE SAFETY MEASURES

The following fire safety measures are required to be installed in the building. The following table may be

required to be updated as the design develops and options for compliance are confirmed.

Table 2. Essential Fire Safety Measures

Item Essential Fire and Other Safety Measures Standard of Performance

1.

Construction Joints BCA2019 C1.1, Spec C1.1

BCA2019 C3.16

AS 1530.4:2014 & AS 4072.1:2005

2.

Fire seals protecting openings in fire resisting components of the building

BCA2019 C3.15 (Openings for service installations)

BCA2019 C3.16 (Construction joints)

BCA2019 Spec C3.15

AS1530.4:2014 & AS4072.1-2005

3.

Lightweight construction

BCA2019 C1.1, Spec. C1.1

BCA2019 C1.8, Spec C1.8

BCA2019 C2.7 (Fire Walls)

4.

Warning & operational signs BCA2019 D2.23 (Signs on Fire Doors)

BCA2019 D3.6 (Braille Exit Signs) (Note: E4.5 (Exit Signs))

5. Emergency lighting BCA2019 E4.2, E4.4

AS/NZS 2293.1:2018

6.

Exit signs BCA2019 E4.5 (Exit Signs)

BCA2019 E4.6 (Direction Signs)

BCA2019 E4.8 (Design and Operation - Exits)

AS/NZS 2293.1:2018

Hydraulic Services

7.

Fire hydrant systems

NSW Storz Couplings

BCA2019 E1.3

BCA2019 C2.12 (Separation of Equipment)

AS 2419.1:2005

FRNSW Technical Sheet D15/45534.V9 issued 10.01.19, ‘Compatible Hose Connections’

8. Hose reel systems BCA2019 E1.4

AS 2441:2005

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 10 of 16

Item Essential Fire and Other Safety Measures Standard of Performance

9.

Smoke Hazard Management

a. An automatic smoke exhaust system complying with specification E2.2b; or

b. Automatic smoke-and-heat vents complying with Specification E2.2c, if the building is single store, or

c. If the floor area of the fire compartment is not more than 3,500 m2 and the building –

i. Is single storey, an automatic smoke detection and alarm system complying with Specification E2.2a; or

ii. Has a rise in storeys of not more than 2, a sprinklers system (other than a FPAA101D or FPAA101H system) complying with Specification E1.5.

BCA2019 E2.2, Table E2.2b

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 11 of 16

4 FIRE RESISTANCE LEVELS

The following fire resistance levels (FRL’s) are required for the various building elements, with a fire source

feature being the far boundary of a road adjoining the allotment, a side or rear boundary or an external wall

of another building on the allotment except a Class 10 structure.

Type A Construction

Table 3. Type A Construction

Item Class 6

Loadbearing External Walls (including columns and other building elements incorporated therein)

- Less than 1.5m to a fire- source feature

- 1.5 – less than 3m from a fire-source feature

- 3m or more from a fire source feature

180/180/180

180/180/120

180/120/90

Non-Loadbearing External Walls - Less than 1.5m to a fire-source feature

- 1.5 – less than 3m from a fire-source feature

- 3m or more from a fire-source feature

-/180/180

-/180/120

-/-/-

External Columns - Loadbearing

- Non-loadbearing

180/-/-

-/-/-

Common Walls & Fire Walls 180/180/180

Stair and Lift Shafts required to be fire-resisting - Loadbearing

- Non-loadbearing

180/120/120

-/120/120

Internal walls bounding sole occupancy units - Loadbearing

- Non-loadbearing

180/-/-

-/-/-

Internal walls bounding public corridors, public lobbies and the like:

- Loadbearing

- Non-loadbearing

180/-/-

-/-/-

Ventilating, pipe, garbage and like shafts: - Loadbearing

- Non-loadbearing

180/120/120

-/120/120

Other loadbearing internal walls, beams trusses and columns

180/-/-

Floors 180/180/180

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 12 of 16

Item Class 6

Roofs1 180/60/30

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 13 of 16

5 BUILDING CODE OF AUSTRALIA ASSESSMENT

Reference is made to our high-level assessment of the Development Application architectural plans for the

proposed development against the Deemed-to-Satisfy Provisions of the BCA2019.

5.1. Section C – Fire Resistance

The building is required to maintain the fire-resistance levels for Type A Construction (see Part 2.4 of

Report) and will be required to be constructed in accordance with Table 3 of Specification C1.1 of the

BCA.

The external walls must be of non-combustible construction in accordance with BCA Clause C1.9.

5.2. Section D – Occupant Access and Egress

The assumed exits from each tenancy is via:

The western elevation doorway from each Retail Tenancy;

The eastern elevation double doorways from each Retail Tenancy; and

Additional exit doorway(s) located approximately midway along the northern and southern

elevations of the building are required to be provided.

The above exits are considered to provide appropriate travel distances to exits based on an empty floor

plate with two tenancies. Any internal fit-out of the building will have to re-consider the egress travel

distances. Further doors provided to the northern and southern elevations will provide greater flexibility in

the fit-outs with regard to the 20m/ 40m/ 60m travel distance requirements of BCA Clause D1.4 and D1.5.

The exit travel distances will be required to be reviewed as part of the tenancy fitouts.

5.3. Section E – Services and Equipment

Refer to Part 3 ‘Essential Fire Safety Measures’ of the report for the required essential fire safety

measures. This table may be required to be updated as the design develops and options for compliance

are confirmed.

It is noted that BCA Table E2.2b requires a building where the floor area of a Class 6 part of a fire

compartment is more than 2000 m2 must be provided with-

(i) An automatic smoke exhaust system complying with specification E2.2b; or

(ii) Automatic smoke-and-heat vents complying with Specification E2.2c, if the building is single

store, or

(iii) If the floor area of the fire compartment is not more than 3,500 m2 and the building –

(A) Is single storey, an automatic smoke detection and alarm system complying with

Specification E2.2a; or

(B) Has a rise in storeys of not more than 2, a sprinklers system (other than a FPAA101D or

FPAA101H system) complying with Specification E1.5.

The provisions above do not apply to a Class 6 sole-occupancy unit that –

(A) Has a floor area of not more than 2000 m2; and

(B) Is a single storey with a main public entrance opening to a road or open space; and

(C) Is separated for other parts of the fire compartment by construction, including openings,

penetrations and junctions with other building elements, that prevents the free passage of

smoke.

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 14 of 16

5.4. Section F – Health and Amenity

The building does not include details of the sanitary facilities. Sanitary facilities will be required to be

provided as part of the retail tenancy fit-outs as part of a separate application and specific to the building

use.

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 15 of 16

ANNEXURE A DESIGN DOCUMENTATION

Ref: 112177 -BCA-r2 879 Richmond Road, Marsden Park

Page 16 of 16

Annexure A – Design Documentation

This report has been based on the following design documentation.

Table 4. Architectural Plans

Architectural Plans Prepared by bokor architecture + interiors

Drawing Number Revision Date Title

A-110 D Mar 2020 Proposed Ground Floor Plan