8
Freon NU-22B Refrigerant (R-422B) 8 Basic Steps to Retrofit from R-22 to Freon™ NU-22B Refrigerant Quick Switch Pocket Retrofit Guide

Refrigerant (R-422B) - Chemours

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Refrigerant (R-422B) - Chemours

Freon™ NU-22BRefrigerant (R-422B)

8 Basic Steps to Retrofit from R-22 to Freon™ NU-22B Refrigerant

Quick Switch Pocket Retrofit Guide

Page 2: Refrigerant (R-422B) - Chemours

Freon™ NU-22B Refrigerant

2

STEP 1: Recover all of the R-22 from system following EPA regulations.

Page 3: Refrigerant (R-422B) - Chemours

Freon™ NU-22B Refrigerant

3

STEP 2: Complete all necessary system service and repairs.

Page 4: Refrigerant (R-422B) - Chemours

Freon™ NU-22B Refrigerant

4

STEP 3: Pressurize system and perform leak check.

STEP 4: Pull system into vacuum.

Page 5: Refrigerant (R-422B) - Chemours

Freon™ NU-22B Refrigerant

5

STEP 5: With system off, initially charge Freon™ NU-22B in the system to 90-95% of original R-22 charge as a liquid.Note: Charging system with NU-22B as a vapor will reduce system performance.

Page 6: Refrigerant (R-422B) - Chemours

Freon™ NU-22B Refrigerant

6

STEP 7: To maximize system performance on a fixed orifice system, check compressor superheat; on expansion valve units, check system subcooling. Adjust charge as necessary.Note: Refer to OEM’s superheat and subcooling specifications.

STEP 6: Start system and allow pressures to stabilize.

Page 7: Refrigerant (R-422B) - Chemours

Freon™ NU-22B Refrigerant

7

STEP 8: Leak check system and establish preventive maintenance schedule.

Page 8: Refrigerant (R-422B) - Chemours

Freon™ NU-22B Refrigerant

For additional Freon™ NU-22B information, visit freon.com.

For more information on Freon™, or other refrigerants from Chemours, please contact your local representative.

The Chemours Company1007 Market StreetWilmington, DE 19899Tel: 800-235-7882

freon.com

The information set forth herein is furnished free of charge and based on technical data that Chemours believes to be reliable. It is intended for use by persons having technical skill, at their own risk. Because conditions of use are outside our control, Chemours makes no warranties, expressed or implied, and assumes no liability in connection with any use of this information. Nothing herein is to be taken as a license to operate under, or a recommendation to infringe, any patents or patent applications.

© 2018 The Chemours Company FC, LLC. Freon™ and any associated logos are trademarks or copyrights of The Chemours Company FC, LLC. Chemours™ and the Chemours Logo are trademarks of The Chemours Company.

C-11740 (12/18)