Relay Connection For
1. 4G Reader
2. 4G Lite Reader
3. Sigma Reader
4. Sigma Lite Reader
1.
4G Relay Connection
4G’s has 170 Ma ability
Relay needs to be turn on via Software (Single door Access Control in Secure Admin)
***If you don’t have a door connect then tie 20( Blue/Brown) and 25(White/Green) together**
1.
4G with a External Relay
4G’s has 170 Ma ability
Relay needs to be turn on via Software (Single door Access Control in Secure Admin)
***If you don’t have a door connect then tie 20(Blue/Brown) and 25(White/Green) together***
***The External relay and 4G device needs to be on separate power supply***
1.
4G Relay Connection with Motion Detector or Push Button
***If you don’t have a door connect then tie 20(Blue/Brown) and 25(White/Green) together***
18(yellow\Blue) and 21(yellow\Black) for your Motion Detector or Push button
Relay needs to be turn on via Software (Single door Access Control in Secure Admin)
2.
4G Lite Relay Connection
4G Lite has 1 amp ability
Relay needs to be turn on via Software (Single door Access Control in Secure Admin or Access Control in Secure Admin Lite)
***If you don’t have a door connect then tie 13( Yellow/Blue) and 9(White/Red) together***
2.
4G Lite with a External Relay
4G Lite has 1 amp ability
Relay needs to be turn on via Software (Single door Access Control in Secure Admin or Access Control in Secure Admin Lite)
***If you don’t have a door connect then tie 13( Yellow/Blue) and 9(White/Red) together***
***The External relay and 4G Lite device needs to be on separate power supply***
2.
4G Lite with Motion Detector or Push Button
4G Lite has 1 amp ability
Relay needs to be turn on via Software (Single door Access Control in Secure Admin or Access Control in Secure Admin Lite)
Wire 15, Blue/Brown and Wire 9, White/Red for Push button or Motion dectector
3.
Sigma Reader Relay
Please use an External power supply for your deadbolt or Door strike
Internal Relay not active from Factory and would need to be turn on via LCD screen or software (Biometric Device Profile in Morpho Manager)
Internal relay is rated for 2 Amps
Relay_1 and Relay_2 for Door strike
If no door contact being used GPI1 and GPO1 needs to connected together
3.
Sigma Reader Sigma with Push Button and Door Contact
Relay_1 and Relay_2 for Door strike
GPO0 and GPI0 for push Button
Internal Relay not active from Factory and would need to be turn on via LCD screen or software for any control (Biometric Device Profile in Morpho Manager)
If no door contact being used GPI1 and GPO1 needs to connected together
4.
Sigma Lite Relay
Please use an External power supply for your deadbolt or Door strike
Internal Relay not active from Factory and would need to be turn on via software (Biometric Device Profile in Morpho Manager)
Internal relay is rated for 1 Amps
19-Relay_NO Yellow
21-Relay_NC Orange
22-Relay_Comm Grey
If no door contact being used GPI_2(Orange/Red) and GPO_2 (Yellow/Red) needs to be connected together
4.
Sigma Lite Relay (with Push Button)
Relay_1 and Relay_2 for Door strike
GPI_0 (yellow)and GPO_0 (yellow)for push Button
Internal Relay not active from Factory and would need to be turn on via software (Biometric Device Profile in Morpho Manager)
Label and documenation are incorrect for push button and door contact
If no door contact being used wire 10(Orange/Red) and wire 12 (Yellow/Red) needs to be connected together
Wire 9 (Orange) and Wire 11 (Yellow) are for the push button