6
www.maxfine.uk LARGE POWER UPS RELIABLE POWER FOR EVER MLT SERIES

Reliable poweR foR eveR - librasolar.comlibrasolar.com/images/brochure/maxfine_mlt.pdf · HIGH INTELLIGENcE AND RELIABLE POWER SUPPLy mlm/mlT’s capacity of maximum protection for

  • Upload
    lydat

  • View
    214

  • Download
    1

Embed Size (px)

Citation preview

w w w.maxf ine.uk

LARGE POWER UPS

Reliable poweR foR eveR

MLT SERIES

MODEL MLM - 10 ÷ 100kVA MLT - 10 ÷ 200kVATECHNOLOGY Low Frequency On - line double conversion Low Frequency On - line double conversion

INPUT

Nominal voltage 400V three phaseVoltage range ± 25% three phase ± 20% Frequency 45 ÷ 65 Hz Soft Start 0-100% in 10secPower factor >0.92 ( with input filter ) >0.9 with harmonic filter Current harmonic distortion <5% with harmonic filter

BYPASS

Nominal voltage Single phase 230V 400V three phasePermitted voltage range ±15% ( selectable from ±10% to ± 25% from front panel )Frequency 50/60 Hz Permitted Frequency range ±2% ( selectable from ±1% to ± 5% from front panel )Standard features Back feed protection split bypass line

BATTERIESType Maintenance-free lead acid VRLA AGM / GEL : NICdMaximum recharge current (A) 0.2 x c10AC ripple voltage <1%

OUT PUT

number of phase 1 3 + N Rated Voltage Single phase 230V 400VacRegulation of the output voltage 220 ÷244 Vac phase / neutral ( from control panel ) 348 ÷ 424 Vac phase / neutral ( from control panel )Crest factor ( ipeak/Irms) 3:1Static stability ±1% Dynamic stability ±5% in 5msFrequency 50/60 Hz configurable Overload 110% ,125%,150% of the rated current for 5h/10’/1’Frequency stability ±0.05% on mains failure, ±2% ( selectable from ± 1% to ± 5% ) with mains supply present

SYSTEM

Remote signaling volt free contactsRemote controls EPO and BypassCommunication Rs. 232 + romote contacts Operating temperature 0°C ÷ +40°CRelative humidity <95% non condensing Colour light grey ( RAL 7035 )Acoustic noise @ 1 metre 10-80kVA 54-62dBA at 1m,100-200kVA 54-65dBA at 1mProtection degree IP20Efficiency Online up to 93% Smart Mode up to 98%

SafetyVFI-SS-111 IEC EN62040-(1,2,3);EN62040-1-1; EN50081-2;EN50091-2;EN62040-1-2; EN60529; EN60664; EN6075; EN60950 (CEI74-2); EN61000-2-2; EN61000-4-(1,2,3,4,5,6,8,11); EN55022; EN50141; EN60269-1; IEC146 (CE122)

European Directive LV73/23/EC and 93/68/EC;89/336;EMC 2004/108/EC

MODEL POWER kVA / kW UPS DIMENSIONW x D x H mm

N.W WEIGHT kg INTERNAL BATTERIES

INPUT / OUT PUT

MLT 10k 10 / 8 555 x 720 x 1200 200 Yes III / IIIMLT 15K 15 / 12 555 x 720 x 1200 220 Yes III / IIIMLT 20K 20 / 16 555 x 720 x 1200 230 Yes III / IIIMLT 30K 30 / 24 555 x 720 x 1200 290 Yes III / IIIMLT 40K 40 / 32 555 x 720 x 1200 340 No III / IIIMLT 60K 60 / 48 800 X 740 X 1400 440 No III / IIIMLT 80K 80 / 64 800 X 740 X 1400 520 No III / III

MLT 100K 100 / 80 1070 X 740 X 1400 770 No III / IIIMLT 120K 120 / 96 1070 X 740 X 1400 855 No III / IIIMLT 160K 160 / 128 1420 X 740 X 1805 1300 No III / IIIMLT 200k 200 / 160 1420 X 740 X 1805 1350 No III / III

Technical ParameTers

mlm/mlT 10 - 200K larGe POWer UPs

Note: Product specifications are subject to change without further notice.

HIGH INTELLIGENcE AND RELIABLE POWER SUPPLy

mlm/mlT’s capacity of maximum protection for vital mission-critical networks, security applications (electro-medical) and industrial applications thanks to its outstanding mechanical and electrical design. The load is powered continuously by the inverter with a filtered, stabilized and regulated sine wave supply. The input and output emi filters considerably increase the immunity of the load to maintain disturbances and surges. The mlm/mlT uses on-line double conversion technology (VFi) with isolation transformer on the inverter output. The mlm/mlT is supplied with Watch & save 3000 software as standard and can be remotely monitored using the Power net Guard system from anywhere in the world. additional battery extension packs allow the standard battery runtime to be extended up to several hours.

APPLIcATION

l servers l local area network (lan) l Data centers l Tele communications l electro-medical equipment l industrial process and other critical equipment.

PrODUcTFeaTUres

MLT 10-200K

MODEL POWERkVA / kW

UPS DIMENSIONW x D x H mm

N.W WEIGHTkg

INTERNAL BATTERIES

INPUT / OUT PUT

MLTM+ 10k 10 / 8 555 x 720 x 1200 200 Yes III / IMLTM+ 15K 15 / 12 555 x 720 x 1200 220 Yes III / IMLTM+ 20K 20 / 16 555 x 720 x 1200 230 Yes III / IMLTM+ 30K 30 / 24 555 x 720 x 1200 290 No III / IMLTM+ 40K 40 / 32 555 x 720 x 1200 340 No III / IMLTM+ 60K 60 / 48 800 x 740 x 1400 440 No III / IMLTM+ 80K 80 / 64 800 x 740 x 1400 520 No III / I

MLTM+ 100K 100 /80 1070 x 740 x 1400 770 No III / I

MINIMUM IMPAcT ON SUPPLIERS EASy SOURcE:input current distortion is less than 4% for the mlm/mlT with fil-ter with sinusoidal absorption to remove the risk of resonance with other input supply users or phase shift capacitor sets. The absorbed current distortion is independent of input supply parameters such as impedance. This enable mlm/mlT to deliver maximum perfor-mance levels regardless of the installation environment. With these input features, mlm/mlT can achieve significant savings in terms of sizing and power supply source isolation transformer and genera-tors over less sophisticated power systems.

MAXIMUM BATTERy cARE:l Battery deep discharge protection

l Temperature compensating charger

l Built-in automatic and manual battery test feature.

SIMPLE TO INSTALL:l capability to install the UPs into any distribution system (neu-

tral not required on rectifier input):

l capability to separate the rectifier / bypass power net works and to power these from two separate sources, without Galvan-ic isolation (necessary on UPs without an output transformer).

HIGH RELIABILITy:l extremely high short-circuit current to ensure compatibility

with the most difficult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output;

l Full microprocessor control with no-break static and manual bypasses;

l iGBT technology

l 0.8 power factor make mlm/mlT suitable for powering

IcT AND INDUSTRIAL LOADS;l high level diagnostics: event log with 128 messages, states,

measurements and alarms-available from the built-in lcD with several languages;

l BacK FeeD Protection: to avoid energy feeding back into the mains supply cause a fault occur.

MAXIMUM RELIABILITy AND AVAILABILITy:connect up to 8 units in parallel or n+1 redundancy, even of dif-ferent power ratings. The UPs continue to work in parallel even if one of the interconnecting communication cables is disconnected (clOseD lOOP)

LOW cONSUMPTION LEVELS:mlm/mlT cab achieve efficiency level less than 98%. Thanks to se-lectable economy mode which can be used in stable electrical en-vironments for providing power supply continuity when the mains fail.

ADVANcE cOMMUNIcATION:l compactible with TelenetGuard for remote maintenance.

l advanced, multi-platform communication for all operation systems and network environments: Watch & save 3000 monitoring and shut-down software included, with snmP agent, for Windows 2008, Vista, 2003, XP; mac Os X, linux, novell and most popular Unix operating systems;

l The UPs is supplied with a cable for direct connection to the Pc (Plug and Play);

l rs 232 double serial port; installation slot for an emergency Power Off (ePO) interface to allow the UPs to be switched off remotely in an emergency;

l Generator interface: enables desynchronisation of the UPs output from a generator supply which may be subject to phase and frequency variations. The interface also enables more economic use of the battery charge.

EXPANDABILITy:The units can be connected in parallel up to 8 units to increase power availability or redundancy. The single module or the system can be expanded anytime to suit power requirements without influencing the initial investment. Thanks to be peculiarity of the “hot system expansion” feature, the additional unit can be connected in parallel while the other units are on-line and supplying regular power to the load. The new UPs is on-line and will be set up automatically.

Technical ParameTers

mlm/mlT 10 - 200K laeGe POWer UPs

Parallel configuration of up to 8 units with distributed bypassParallel architecture which guarantees the redundancy of the power source. + Flexibility and modularity

Parallel configuration of up to 8 units with common bypass and Battrey Parallel architecture which guarantees the redundancy of the power source, with autonomous bypass management. +selectivity downstream faults in bypass mode.

Dynamic dual bus configurationsolution which redundancy until the distribution of the power supply to the loads + downstream fault discrimination

Dual bus system configurationa solution which guarantees the redundancy of the power supply even during maintenance + high levels of availability and redundancy.

COMPARISON BETWEEN SCR CHARGER & IGBT CHARGERMLTS SCR Charger UPS MHT IGBT Charger

Input Power Factor >0.98 (with flitters ) >0.99Output Power Factor 0.9 1In Put Harmonic Current Distribution <4.5% ( if harmonic flitters added ) 100% load <2.0% THDiReliability High MediumIsolation Double Isolation Single IsolationProtection for lightning/Surge/High Voltage High MediumElectro Magnetic Emission Low HighReliability of Input Switching Device 1A SCR-50A Peak 1A IGBT-2A Peak

Reliable power for ever

LIBRA INDUSTRIES36/1951, Kaloor Tower, Kochi - 682 017

Tele/Fax:+91 484 4033322 M:+91 9995554411Email: [email protected] www.librasolar.com