60
Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April 2003 4

Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

Model 4081 T

Remote Controlled FOUNDATION FieldbusTwo-Wire Conductivity Transmitter

Instruction ManualPN 51-4081T/rev.DApril 2003

4

Page 2: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

ESSENTIAL INSTRUCTIONSREAD THIS PAGE BEFORE PROCEEDING!

Rosemount Analytical designs, manufactures, and tests its products to meetmany national and international standards. Because these instruments aresophisticated technical products, you must properly install, use, and maintainthem to ensure they continue to operate within their normal specifications. Thefollowing instructions must be adhered to and integrated into your safetyprogram when installing, using, and maintaining Rosemount Analyticalproducts. Failure to follow the proper instructions may cause any one of thefollowing situations to occur: Loss of life; personal injury; property damage;damage to this instrument; and warranty invalidation.

• Read all instructions prior to installing, operating, and servicing the product.If this Instruction Manual is not the correct manual, telephone 1-800-654-7768 and the requested manual will be provided. Save this InstructionManual for future reference.

• If you do not understand any of the instructions, contact your Rosemountrepresentative for clarification.

• Follow all warnings, cautions, and instructions marked on and supplied withthe product.

• Inform and educate your personnel in the proper installation, operation, andmaintenance of the product.

• Install your equipment as specified in the Installation Instructions of theappropriate Instruction Manual and per applicable local and national codes.Connect all products to the proper electrical and pressure sources.

• To ensure proper performance, use qualified personnel to install, operate,update, program, and maintain the product.

• When replacement parts are required, ensure that qualified people usereplacement parts specified by Rosemount. Unauthorized parts andprocedures can affect the product’s performance and place the safeoperation of your process at risk. Look alike substitutions may result in fire,electrical hazards, or improper operation.

• Ensure that all equipment doors are closed and protective covers are inplace, except when maintenance is being performed by qualified persons, toprevent electrical shock and personal injury.

Emerson Process Management

Rosemount Analytical Inc.2400 Barranca ParkwayIrvine, CA 92606 USATel: (949) 757-8500Fax: (949) 474-7250

http://www.RAuniloc.com

© Rosemount Analytical Inc. 2001

Page 3: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

TABLE OF CONTENTSSection Title Page

1.0 INSTALLATION ................................................................................................................. 1-11.1 Overview .................................................................................................................. 1-11.2 Mechanical Installation............................................................................................. 1-21.3 Electrical Installation ................................................................................................ 1-41.4 Installation Verification ............................................................................................. 1-4

2.0 OPERATION OVERVIEW ................................................................................................. 2-12.1 General .................................................................................................................... 2-12.2 Display ..................................................................................................................... 2-12.3 Infrared Remote Control (IRC)................................................................................. 2-22.4 Diagnostic Messages............................................................................................... 2-22.5 Menu Program Tree ................................................................................................. 2-3

3.0 FACTORY PROGRAMMED SETTINGS ........................................................................... 3-13.1 General .................................................................................................................... 3-1

4.0 TRANSMITTER PROGRAM SET-UP ............................................................................... 4-14.1 Program Menu ......................................................................................................... 4-14.2 Temperature Parameters ......................................................................................... 4-24.3 Display Units ............................................................................................................ 4-3

5.0 START-UP AND CALIBRATION....................................................................................... 5-15.1 Accessing The Calibrate Menu ................................................................................ 5-15.2 Calibrate Menu (Toroidal)......................................................................................... 5-25.3 Calibrate Menu (% Concentration)........................................................................... 5-35.4 On-line Calibration ................................................................................................... 5-4

6.0 DIAGNOSIS AND TROUBLESHOOTING ........................................................................ 6-16.1 Overview .................................................................................................................. 6-16.2 Fault Conditions ....................................................................................................... 6-36.3 Diagnostic Messages............................................................................................... 6-46.4 Quick Troubleshooting Guide................................................................................... 6-56.5 Systematic Troubleshooting..................................................................................... 6-66.6 RTD Resistance Values ........................................................................................... 6-7

7.0 MAINTENANCE ................................................................................................................ 7-17.1 Overview .................................................................................................................. 7-17.2 Preventative Maintenance ....................................................................................... 7-17.3 Corrective Maintenance ........................................................................................... 7-1

8.0 PRODUCT DATA............................................................................................................... 8-1

9.0 OPERATION WITH REMOTE CONTROLLER ................................................................. 9-1

10.0 RETURN OF MATERIALS ................................................................................................ 10-1

Appendix Title Page

A GLOSSARY....................................................................................................................... A-1

B 4081T RESOURCE AND TRANSDUCER BLOCK PARAMETERS ................................ B-1

i

MODELS 4081T TABLE OF CONTENTS

MODEL 4081TMICROPROCESSOR ANALYZERS

Page 4: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

ii

LIST OF FIGURES

Figure No. Title Page1-1 Exploded Drawing of Circuit Board Stack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11-2 Dimensional Information - Model 4081T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-21-3 Mounting Information - Model 4081T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-31-4 Function Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-61-5 Model 4081T Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-71-6 Model 4081T Wiring with Junction Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-81-7 Model 4081T Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-91-8 Typical Fieldbus Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-91-9 Wiring For Explosion Proof Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-101-10 Wiring For CSA Intrinsically Safe Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-111-11 Wiring For FMRC Intrinsically Safe Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-132-1 Process Display Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12-2 Program Mode Display Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12-3 Infrared Remote Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22-4 Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-34-1 Program Menu and Menu Segments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14-2 RTD Sensor Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24-3 Security Code Prompt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-45-1 Calibration Menu Segments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15-2 Calibration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26-1 Diagnose Menu Segments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16-2 Diagnose Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-26-3 Disabling Fault Annunciation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-36-4 Warning Annunciation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-36-5 Troubleshooting Flow Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-67-1 Hold Annunciation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17-2 Exploded View - 4081T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-28-1 Transmitter Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-38-2 Infrared Remote Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-38-3 Function Block Diagram with FOUNDATION Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . 8-39-1 Function Block Diagram with FOUNDATION Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1

LIST OF TABLESTable No. Title Page

1-1 Hardware/Software Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-41-2 Transmitter Range Limits (Conductivity) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-51-3 Transmitter Range Limits (Concentration) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-53-1 Program Variables with Factory Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14-1 Program Menu Mnemonics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-65-1 Nominal Cell Constants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-35-2 Calibrate Menu Mnemonics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-46-1 Diagnostics Variables Mnemonics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-26-2 Diagnostic Fault Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-46-3 Quick Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-56-4 RTD Resistance Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-76-5 Conductivity Determination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-77-1 4081 T Replacement Parts and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2

MODELS 4081T TABLE OF CONTENTS

Page 5: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T SECTION 1.0INSTALLATION

SECTION 1.0 INSTALLATION

FIGURE 1-1. Model 4081T Transmitter - Exploded Drawing of Circuit Board Stack

1.1 OVERVIEW This inductive conductivity transmitter has beendesigned for easy installation and shipment. The pur-pose of this section is to provide information on the elec-trical configurations and the physical mountingsavailable. Prior to discarding the packing case:

If it is damaged, the transmitter may have also sustained damage. Contact the carrier at once.

Remove all items shown on the packing list and note any exceptions.

1-1

The Model 4081T conductivity transmitter is designed tomake accurate measurements while the sensor is sub-mersed in the process stream. Measurements can alsobe tailored to high temperature and/or high pressurestreams. The specific ranges covered are controlled byboth hardware and software.

Page 6: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

1-2

FIGURE 1-2. Dimensional Information – Model 4081 T

DWG. NO. REV.

44081C01 A

MILLIMETERINCH

MODELS 4081T SECTION 1.0INSTALLATION

1.2 MECHANICAL INSTALLATIONThe Model 4081 T Transmitter is suitable for installation inharsh environments.

• For best operation, locate in an area where tempera-ture extremes, vibrations, electromagnetic, and radiofrequency interferences are minimized or absent.

The transmitter is equipped with two 3/4 in. FNPT conduitopenings, one on each side of the transmitter housing.

• Remove the terminal end cap. • With the transmitter positioned with the wiring terminal

side of the enclosure opened (as seen in Figure 1-2),use the left conduit opening to bring in the sensorwiring, and the right side conduit opening for powersupply/current loop wiring.

• To prevent moisture from entering the transmitterhousing, use weathertight cable glands supplied byothers.

NOTEMoisture accumulation in the transmitterhousing can affect transmitter performanceand may void its warranty.

• If conduit is used, connections on the transmitter hous-ing should be plugged and sealed (with tape, pipe com-pound, or sealant) to prevent moisture accumulation inthe terminal side of the housing.

• The transmitter must be installed so that the conduitopenings are not on the top, because moisture canaccumulate in that position.

• The transmitter should be easily accessed by operatingand maintenance personnel.

1.2.1 Flat Surface Mounting. The transmitter may bemounted on a flat surface (see Figure 1-2) using the thread-ed mounting holes on the bottom of the transmitter. 1.2.2 Pipe Mounting Bracket. An optional pipe mountingbracket is available. See Figure 1-3 for mounting information.

Page 7: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

1-3

MODELS 4081T SECTION 1.0INSTALLATION

FIGURE 1-3. Mounting Information - Model 4081 T

DWG. NO. REV.

40408103 B

DWG. NO. REV.

40408104 F

MILLIMETERINCH

Page 8: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

1-4

MODELS 4081T SECTION 1.0INSTALLATION

1.3 ELECTRICAL INSTALLATION

1.3.1 Conductivity Sensors

Rosemount Analytical Inc.’s inductive conductivity sensorswith PT100 are compatible with the Model 4081T transmit-ter. Please refer to Figures 1-4 thru 1-6 for appropriatesensor to transmitter wiring. The sensor cable should berouted through the conduit opening closest to the Pin 2connection.

1.3.2 Power Supply/Current Loop Wiring.

The Model 4081T operates within a range of 9-32 VDCpower. The power supply wiring routes through the conduitopening closest to pin number 16. Connect as illustrated inFigure 1-7. For shielded power supply cable, the shieldshould be connected to the earth ground connection.

The Model 4081T sensor connection requires connectingthe white toroid wire (see Figure 1-5) to either TB-1 pin 11(indicated on the inside of the terminal end cap) for highrange, or TB-1 pin 12 for low range. To access the terminalblock, unscrew the terminal end cap.

1.3.3 Hazardous Area Installation

In order to maintain the hazardous area rating for installedtransmitter, the following drawings must be used:

Figure 1-9. Wiring for FM Explosion-Proof Installation forModel 4081T (Drawing Number 1400175)

Figure 1-10. Wiring for CSA Intrinsic Safety for Model 4081T(Drawing Number 1400190). See also label (right).

Figure 1-11. Wiring for FMRC Intrinsic Safety for Model4081T (Drawing Number 1400185).

1.4 INSTALLATION VERIFICATION

1.4.1 Overview. Verification of installation includes ensur-ing that the proper precautions have been observed duringthe installation process and recognizing whether theinstrument is operating properly upon power up.

1.4.2 Precautionary Checklist. Before applying powerverify the following:

1. Sensor wiring and power supply/loop wiring are not inthe same conduit.

2. Sensor or power supply/loop wiring are at least 12inches from any high current lines.

3. Sensor chosen is compatible with the 4081TTransmitter.

4. Terminal end cap has been replaced.

1.4.3 Power Up. Activate power supply. Upon poweringup, with the sensor in solution, the transmitter:1. Should display a live conductivity reading in large, dark

numerals on a gray background.

2. Should display the present temperature in smaller numer-als on the lower line of the display screen.

3. Should NOT have the word FAULT or HOLD appearing onthe left edge of the display. The display should not be flash-ing.

TABLE 1-1. Hardware/Software Compatibility(Measurement Range [µS/cm]*)

MANUAL RANGE 1 2 3

Low Range 80 to 800 to 7,500 to

(accuracy: ± 1.0%) 800 7,500 80,000

High Range 1,100 to 11,000 to 100,000 to

(accuracy: ± 1.0%) 11,000 100,000 1,100,000Wir

e Te

rmin

al

11

or

12

*NOTE: Values shown are for uncompensated conductivity usinga cell constant of 1.0. The conductivity values autoranges from 0 to 2,000,000 µS/cm with an accuracy of5 to 10% ±150 µS/cm depending on the process con-ditions, installation, and the sensor used. For greateraccuracy and repeatability, manual range selection isrecommended.

LABEL, I.S. N.I. & EX CSA approved for Model 4081T

Page 9: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T SECTION 1.0INSTALLATION

TABLE 1-2. Transmitter Range Limits (Conductivity)

TABLE 1-3. Transmitter Range Limits (Concentration)

PV_HIGH_LOW_RANGE MANUAL_AUTO_RANGE RANGE_VALUE CELL_CONSTANT (0% FS) (100% FS) Manrng (1/cm) EU0% µµS/cm EU100% µµS/cm

Low Auto N/A N/A 0 400,000

High Auto N/A N/A 0 1,200,000

Low Manual 1 1.0 0 800

Low Manual 1 3.0 0 2,400

Low Manual 2 1.0 0 8,000

Low Manual 2 3.0 0 24,000

Low Manual 3 1.0 0 80,000

Low Manual 3 3.0 0 240,000

Low Manual 4 1.0 0 400,000

Low Manual 4 3.0 0 1,200,000

High Manual 1 1.0 0 11,000

High Manual 1 3.0 0 33,000

High Manual 2 1.0 0 110,000

High Manual 2 3.0 0 330,000

High Manual 3 1.0 0 1,200,000

High Manual 3 3.0 0 3,600,000

PV_HIGH_LOW_RANGE (0% FS) (100% FS)EU0% µµS/cm EU100% µµS/cm

NaOH 0% 12.00%

HCl 0% 15.00%

low H2SO4 0% 25.00%

high H2SO4 96.00% 99.00%

1-5

Page 10: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

1-6

MODELS 4081T SECTION 1.0INSTALLATION

FIGURE 1-4. Wiring Schematic Showing Signal Function On Each Connection

MILLIMETERINCH

Page 11: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

1-7

MODELS 4081T SECTION 1.0INSTALLATION

FIGURE 1-5. Model 4081T Sensor Wiring Schematic by Sensor Model

MILLIMETERINCH

Page 12: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

1-8

FIGURE 1-6. Model 4081T Sensor Wiring with Junction Box

MODELS 4081T SECTION 1.0INSTALLATION

MILLIMETERINCH

Page 13: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

1-9

MODELS 4081T SECTION 1.0INSTALLATION

FIGURE 1-7. MODEL 4081T TERMINAL BLOCKS

FIGURE 1-8. TYPICAL FIELDBUS NETWORK ELECTRICAL WIRING CONFIGURATION

Page 14: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T SECTION 1.0INSTALLATION

FIGURE 1-9. EXPLOSION-PROOF INSTALLATION

1-10

Page 15: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T SECTION 1.0INSTALLATION

FIGURE 1-10. CSA INTRINSICALLY SAFE INSTALLATION (1 of 2)

1-11

Page 16: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T SECTION 1.0INSTALLATION

FIGURE 1-10. CSA INTRINSICALLY SAFE INSTALLATION (2 of 2)

1-12

Page 17: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T SECTION 1.0INSTALLATION

FIGURE 1-11. FMRC INTRINSICALLY SAFE INSTALLATION (1 of 2)

1-13

Page 18: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

1-14

MODELS 4081T SECTION 1.0INSTALLATION

FIGURE 1-11. FMRC INTRINSICALLY SAFE INSTALLATION (2 of 2)

Page 19: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

2-1

2.1 GENERALThe Model 4081T transmitter operates in either theProcess or Program modes. The process mode screenis illustrated in Figure 2-1 and the program mode screenis illustrated in Figure 2-2.

2.2 DISPLAY 2.2.1 Process Mode (normal operating mode). Whenoperating in this mode:

• The primary process variable (the conductivity) iscontinuously displayed (see 1 in Figure 2-1)

• Engineering units are determined by the processdisplay mode

• Temperature output is in °F or °C (see 2 in Figure 2-1)

2.2.2 Program Mode (programming or calibratingmode — step-by-step instructions for programmingand calibrating the transmitter are given in Sections4.0 and 5.0, respectively). When operating in this modethe following information is provided on the instrumentdisplay:

• Continuous display of the primary process variableis still available.

• Menus are displayed below the process variable.The active subset title is in bold print (see 1 inFigure 2-2).

CALIBRATE PROGRAM DIAGNOSE

� � � � � � � � �

E X I T N E X T E N T E R

mS/cm

FAULT

HOLD

5

4

1

3

MODELS 4081T SECTION 2.0 OPERATION OVERVIEW

SECTION 2.0OPERATION OVERVIEW

2

FIGURE 2-1. Process Display Screen

mS/cm

25.0C

FIGURE 2-2. Program Mode Display Areas

• Security ID (see Section 4.4, step 10) and promptsare displayed below the segments (see 2 and 3 inFigure 2-2).

• FAULT is displayed (see 4 in Figure 2-2) when atransmitter disabling condition occurs. When in thefault mode, the fault indicator lights up and theprocess variable flashes. The program mode mustbe entered to see the descriptive fault message.

• HOLD (see 5 in Figure 2-2) becomes visible when-ever the transmitter is placed in the hold or testfunction. Hold is most often used whenservicing/cleaning the sensor. It initiates the simu-late mode.

21

Page 20: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

2-2

2.3 INFRARED REMOTE CONTROL (IRC)The IRC is the most convenient way to calibrate, pro-gram, or access the diagnostics in the transmitter. Itoperates the same as other remote controllers.

For best operation, the IRC should be within six feet ofthe transmitter and aimed directly at the infrared sensorwindow (small square window at top of display) at anangle of no more than fifteen degrees. The amount ofambient light may also affect IRC communication.

2.3.1. The overall menu structure is shown in Figure 2-4.The top level functions available to the IRC (CAL,PROG, and DIAG) are shown on the display with theactive menu segment highlighted as described inSection 2.2.

2.3.2. Menu Keys. The three primary menu structuresare Calibrate (CAL), Program (PROG), and Diagnose(DIAG). They are shown horizontally on the screen andhave separate keys on the IRC (see 1, 2, and 3 in Figure2-3). Pressing the labeled key will provide access to thatmenu.

2.3.3. Program Command Keys. The three programcommand keys are labeled ENTER, NEXT, and EXIT(see 4, 5, and 6 in Figure 2-3). These keys are used asfollows:

ENTER: This advances down through the sub-menus to the prompts, will save the new value, and activate NEXT.

NEXT: This advances the program to the next sub-menu.

EXIT: This key is used to abort the current sub- menu operation and return to the previous menu segment.

2.3.4. Editing Keys. These keys are used to edit inputvariables (see Figure 2-3). The left/right arrows changethe location of the prompt and causes the integer toflash. These also allow access to the measurement unitand decimal place location. When a flashing mnemonicappears on the display, the UP and DOWN arrow keysscroll up or down through the list. When numbers areshown, the UP and DOWN keys change the value ofthe digit.

MODELS 4081T SECTION 2.0OPERATION OVERVIEW

98

6

5

43

2

1

Editingkeys

FIGURE 2-3. Infrared Remote Control

2.3.5. Special Entry Keys. These keys provide systemlevel operations.

RESET: Aborts the current operation and returns to the process display screen (see 8 in Figure 2-3).

HOLD: Accesses prompt to toggle between enable and disabling of this function (see 9 in Figure 2-3).

2.4 DIAGNOSTIC MESSAGESWhenever a warning or fault has been triggered, diag-nostic messages are displayed to aid in problem solv-ing. These messages flash alternately with thetemperature reading.

If more than one message has been generated, thewarning or fault messages will alternate with the regularreadings.

See Section 6.0 Diagnosis and Troubleshooting formessage meaning and possible causes.

Page 21: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

2-3

MODELS 4081T SECTION 2.0OPERATION OVERVIEW

CALIBRATION

��� ��������� ����� ��� � ���� ���t�� ��� �� ������ ����� ���

25.0C

Model 4081TProcess Display

ScreenmS/cm

��������� ���� ����� ������ ���� ���

���� �������

PROGRAM

Process Display

FIGURE 2-4. Menu Tree

DIAGNOSTICS

2.5 MENU PROGRAM TREE The software has been designed with the user in mind. It uses a simple three layer setup to calibrate and program (configure)the instrument and display instrument diagnostic conditions (see Figure 2-4).

NOTE: In Calibration or Program mode, the Fieldbus parameter — MODE_BLK (INDEX 405) — of the Transducer Blockswitches to the out-of-service mode.

Page 22: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

2-4

Page 23: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

3-1

MODELS 4081T SECTION 3.0FACTORY PROGRAMMED SETTINGS

SECTION 3.0FACTORY PROGRAMMED SETTINGS

3.1 GENERALThe Models 4081 T transmitter is shipped with factory programmed settings.

This table is useful in several ways:

1. It gives an overview of variables that can be changed, the mnemonics, and the factory settings.

2. It identifies more detailed sections for each menu.

3. It shows the factory settings.

4. It provides space to input specific values.

VARIABLE NAME MNEMONIC FACTORY SETTINGS CUSTOMER SETTINGS

Temperature (Section 4.2) ��������

Auto temperature compensation ����� on

Manual temperature ���� 25.0° C (overridden by auto)

Temperature sensor type �� 100-3

Display (Section 4.3) ��������������

Measurement type �� ���� ���� ���� ��� t

Range ����� Hi

Auto range ������ on

Manual range �!��� 1, 2, 3, 4 (selectable only with

Autorng “off”) or see Table 4-1

Temperature ���� C

Code ���� 000

Table 3-1. Program Variables with Factory Settings*

Table 3-1 continues on page 3-2.

*Press ENTER after each command to get entry field.

Page 24: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

3-2

MODELS 4081T SECTION 3.0START-UP AND CALIBRATION

Table 3-1 (continued) Calibrate Menu (Section 5.0)/Diagnose Menu (Section 6.0)

VARIABLE NAME MNEMONIC FACTORY SETTINGS CUSTOMER SETTINGS

Calibrate (Section 5.0)

Cell constant ���� ���"� (sensor specific)

Sensor 0 �#�"�� � 0

Temperature setting �#$% ��& 025.0

Temperature slope (Two Point temperature) �#$% "'�%# t1 =

t2 =

Temperature slope (if already known) !�& "'�%# 2.000

Diagnose (Section 6.1)

(Each segment displays the current value in the transmitter.)

Absolute conductivity ��" � 1000 µS/cm

Cell constant �#'' 1.00

Temperature slope �"'�%# 2.000

Software version

Show fault warnings ���(& �'� (enter) none

NOTE: Software version is on the serial tag and should match what is in the diagnose segment.

Page 25: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

4-1

4.1 PROGRAM MENUThe program menu allows configuration of the transmit-ter values for the display shown on the LCD.

Changes to the operating parameters are made throughthe Program menu.

Press the Program menu key, while pointing the InfraredRemote Control (IRC) at the transmitter to initiate com-munication. To avoid communicating with more than onetransmitter at a time, each one must have a unique 3digit code. Entering the “Id” CODE (see Section 4.3,step 9) of a transmitter wil l permit access toprogramming menus of only that transmitter. For thesequence to enter this code, press the PROG key andgo to the last (display) element of the sub-menu.

MODELS 4081T SECTION 4.0TRANSMITTER PROGRAM SET-UP

SECTION 4.0PROGRAM SET-UP

Calibrate MenuSegments/Commands

Program MenuSegments/Commands

DIAGNOSE MENUSegments/Commands

CURRENT OPERATING MENU

������

EXIT NEXT ENTER

����

EXIT NEXT ENTER

����

EXIT NEXT ENTER

FIGURE 4-1. Program Menu and Menu Segments

������

EXIT NEXT ENTER

���������

EXIT NEXT ENTER

���� �����

EXIT NEXT ENTER

������ EXIT

NEXT ENTER

��� ��

EXIT NEXT ENTER

KEYPRESS COMMANDS

Calibrate Program Diagnose����

Exit EnterMenu Segment/Prompt

Area

The sub-menus are shown in the message display area.These define which prompts are shown (See Figure 2-2). The prompts have fields that are used to edit theparameters of the menu currently active. Editing isaccomplished by scrolling through a predetermined listof responses. See Figure 4-1 for the sub-menus avail-able under the program menu.

See Table 4-1 for Program Menu sequence/commandsand mnemonics.

�������

EXIT NEXT ENTER

����

EXIT NEXT ENTER

��� �����

EXIT NEXT ENTER

���� ���

EXIT NEXT ENTER

���� �����

EXIT NEXT ENTER

���)& ���

EXIT NEXT ENTER

Page 26: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

4-2

MODELS 4081T SECTION 4.0TRANSMITTER PROGRAM SET-UP

4.2 TEMPERATURE PARAMETERS

1. Press the Program key (PROG) on the IRC, enter the security code ifnecessary, and press NEXT.

While tEMP is displayed, press ENTER to get the first prompt of thetEMP menu segment.

2. The tAUtO prompt is used to enable (ON) or disable (OFF) auto tem-perature compensation for all conductivity process measurements. IfOn is selected, an equation is used to temperature compensate allprocess measurements to 25 °C and will be the reported temperatureon the process display. The default value is On. Press ENTER.

3. The tMAn prompt is used to enter a temperature value that the com-pensation equation will use (overrides auto). The actual process tem-perature, however, will be shown on the main screen. The temperaturedisplay mode determines the units used. Absolute conductivity is meas-ured using the default value of 025.0 °C. Use the IRC editing keys tochange the value only if some determination other than absolute con-ductivity is required. Press ENTER.

4. The tC prompt matches the instrument to the type of temperature sen-sor being used. Listed type available is 100-3 (3-wire Pt100 RTD). TheIRC editing keys scroll through the listing. The default value is 100-3.Press ENTER.

NOTE4-wire Pt100 is displayed but is not available intoroidal sensors.

5. Press EXIT to return to normal operation or NEXT to go to the displaysub-menu.

����

EXIT NEXT ENTER

Returnto MainScreen

To displaymenu segment.

RTD

3 Wire RTD - Connected to an instrument designed to accept three wireinput. Compensation is achieved for lead resistance (cable wire resistanceis affected by cable length and temperature change). This is the most com-monly used configuration.

+

-

The following procedures are used to select between automatic temperature compensation, absolute conductivity, manualtemperature compensation, and RTD sensor type. To access the temperature parameters, do the following:

� ���� ��

EXIT ENTER

�� *+

EXIT ENTER

���� ,-.

EXIT ENTER

Sense

FIGURE 4-2. RTD Sensor Connections

Page 27: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

4-3

MODELS 4081T SECTION 4.0TRANSMITTER PROGRAM SET-UP

4.3 DISPLAY UNITSThe following procedures are used to select the display menus, calculation formulas, process variable and temperaturedisplay units. The factory settings are shown with each variable. To access the display sub-menu, do the following:

��� �EXIT NEXT ENTER

�������

EXIT NEXT ENTER

���� “”EXIT ENTER

���� “�”EXIT ENTER

��� � “�”/EXIT ENTER

�!��� “”/EXIT ENTER

������ “��”/EXIT ENTER

��� � “��”EXIT ENTER

1. Press PROG key on remote control.

2. Enter ID Code number (if necessary). See step 9.

Press NEXT twice to scroll through the tEMP menusegment to the dISPLAY menu segment.

3. When the dISPLAY menu is displayed, press ENTERto access the first prompt in the display sequence.

4. The tYPE prompt determines which conductivitymeasurement with measurement units is to be dis-played: "t" = toroidal, “HSH” (95-99% Sulfuric Acid),“HSO” (0-25% Sulfur ic Acid),“HCl” (0-15%Hydrochloric Acid), and “NOH” (0-12% SodiumHydroxide). The IRC editing keys are used to scrollthrough the list. Other mnemonics will appear, buthave been deactivated. Choose the desired one andpress ENTER.

5. The rAnGE prompt is used to determine the meas-urement range limit (High or Low). The IRC editingkeys are used to scroll between these. The default isHI. The selection must agree with the terminal con-nection at pin 11 or 12 (refer to Figures 1-4 through1-6). Choose between these and press ENTER.

NOTE

This transmitter has the option of autoranging over the conductivity range of 0 -1,200,000 µs/cm or being restricted tothe specific manual ranges.

6. The Autorng (auto range) is a toggle (or incrementbetween On and Off) which enables or disables theauto range function. Press the up or down arrow toselect On or Off as desired. The On setting turns onthe auto range function and preempts Manrng (manualrange). Press ENTER.

Continued on the following page.

Return toMenu

Screen

Page 28: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

4-4

TABLE 4-1. Program Menu Mnemonics

���� Transmitter on hold����� System disability fault condition���� Temperature menu header

����� Automatic temperature compensation���� Manual temperature compensation�� Temperature sensor type

������� Display menu header���� Conductivity measurement type: t, NOH, HCl, HSO, HSH����� LO/HI measurement range������ Autorange on or off toggle�!��� Manual ranges used for narrow, higher linearity

Associated with rangeWhen range = Hi, Manrng = 1, 2, 3When range = Lo, Manrng = 1, 2, 3, 4 (see Table 1-2)

���� °C / °F toggle selection���� Security code

MODELS 4081T SECTION 4.0TRANSMITTER PROGRAM SET-UP

7. The Manrng (manual range) prompt asks for the fixedrange used by the process measurement. Autorngmust be Off to enable.

For the “Hi” range setting, Manrng is

Number1 0 - 11,000 µS/cm2 0 - 110,000 µS/cm3 0 - 1,200,000µS/cm4 N/A

For the “lo” range setting, Manrng isNumber

1 0 - 800 µS/cm2 0 - 8,000 µS/cm3 0 - 80,000 µS/cm4 0 - 400,000 µS/cm

Select the desired range using the up/down arrowkeys. Press ENTER.

NOTE

The tables above use absolute conductivi-ty values and a cell constant of 1. Multiplythe table values by your sensor’s cell con-stant to adjust range for your sensor (referto Table 5-1, page 5-3 for Nominal CellConstants).

8. The tEMP prompt is used to determine which units willbe used with the temperature reading displays. Unitsavailable are °C or °F. The IRC editing keys are used toscroll between these. The default value is °C. Choosethe appropriate units and press ENTER.

9. The COdE prompt is used to identify the security “Id”Code number of the unit (see Figure 4-3). The numberentered here determines the “Id” code number used tounlock the security feature and allow access to themenu programs and program segments. The limits arebetween 000 and 999. New transmitters are shippedwith the code set to 000 which disables the feature,(allows access to all menus). If no key is pressed fortwo minutes the code will need to be entered again.Use the IRC editing keys to set the desired securitycode. Press ENTER.

NOTEIf this code has been changed or the numbermisplaced, entering 555 at the “Id” prompt andpressing ENTER will display the current code.Access will not be granted, however, until youEXIT to the process display, select program toenter (CALIBRATE, PROGRAM, orDIAGNOSE), press ENTER again, and enterCODE # just displayed.

10. Press EXIT to return to normal operation.

FIGURE 4-3. Security Code prompt.

CALIBRATE PROGRAM DIAGNOSE

����

EXIT NEXT ENTER

Page 29: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

5-1

CURRENT OPERATING MENU

KEYPRESS COMMANDS Menu Segment/Prompt

Area

MODELS 4081T SECTION 5.0START-UP AND CALIBRATION

5.1 ACCESSING THE CALIBRATE MENU

The “Calibrate” menu allows the transmitter and sensorloop to be calibrated to known temperature and conduc-tivity values. This menu also accesses two-point tempera-ture calibration operation to establish the temperatureslope.

Calibrating the Transmitter/Sensor loop may proceedafter proper power and sensor wiring.

Figure 5-1 illustrates the relationship between theCalibrate Menu and its sub-menus. Each sub-menuleads to a series of prompts that are used to edit trans-mitter parameters.

Calibration may be successfully accomplished if the fac-tory settings identified in Table 3-1 of Section 3.0 are sat-isfactory or if the transmitter has been properly pro-grammed per Section 4.0 to match the intended processapplication requirements.

Calibrate MenuSegments/Commands

Program MenuSegments/Commands

DIAGNOSE MENUSegments/Commands

0�����

EXIT NEXT ENTER

����

EXIT NEXT ENTER

����

EXIT NEXT ENTER

FIGURE 5-1. Calibration Menu Segments

������ �

EXIT NEXT ENTER

���������

EXIT NEXT ENTER

���� �����

EXIT NEXT ENTER

������

EXIT NEXT ENTER

��� ��

EXIT NEXT ENTER

�������

EXIT NEXT ENTER

����

EXIT NEXT ENTER

��� �����

EXIT NEXT ENTER

���� ���

EXIT NEXT ENTER

���� �����

EXIT NEXT ENTER

���)& ���

EXIT NEXT ENTER

Calibrate Program Diagnose����

Exit Enter

SECTION 5.0START-UP AND CALIBRATION

Page 30: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

5-2

MODELS 4081T SECTION 5.0START-UP AND CALIBRATION

5.2 CALIBRATE MENU (Toroidal Sensors)

For initial start-up where toroidal measurements are beingmade, do the following:

Figure 5-2 illustrates the relationship between the CalibrateMenu and its menu segments (sub-menus). Each menusegment leads to a series of prompts that are used to editthe transmitter’s parameters.1. To access the CALIbrAtE menu, press the CAL key on

the Infrared Remote Control. If security has beenenabled, the secondary process display will be replaced

with a prompt asking for the “Id”. Using the IRC editingkeys, enter the “Id”. If the correct “Id” is entered, theCALIbrAtE menu will appear when ENTER is pressed.If CALIbrAtE menu does not appear when ENTER ispressed, see Section 4.3, step 9, for procedure to findcorrect code.

NOTEReset can be pressed at any step to returnto the process display and override anyvalue not previously entered.

������

EXIT NEXT ENTER

���������

EXIT NEXT ENTER

���� �����

EXIT NEXT ENTER

��� �����

EXIT NEXT ENTER

���� ���

EXIT NEXT ENTER

���� �����

EXIT NEXT ENTER

Returnto MainScreen

�� ������

EXIT ENTER

��������

EXIT NEXT ENTER

��� 1/

EXIT ENTER

���� .

EXIT NEXT ENTER

������ 1,/

EXIT ENTER

���� 1/,-.

EXIT ENTER

� 1,/

EXIT NEXT ENTER

�, 1,/

EXIT NEXT ENTER

CAL key

t,%

t,%

%

t

t

%

%

%

FIGURE 5-2. Calibrate Menu

Page 31: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

5-3

MODELS 4081T SECTION 5.0START-UP AND CALIBRATION

2. When the CALibrAtE menu segment has beenaccessed, press the NEXT and ENTER commands toaccess the CELL menu segment with the flashing cellconstant prompt.

3. Utilizing the arrow keys on the IRC, generate the cor-rect cell constant of the sensor being used.

NOTECell constants are sensor dependent.Table 5-1 below lists the nominal cell con-stants for the four sensors compatible withthe Model 4081T.

4. Press ENTER to activate selected cell constant andreturn to the CELL COnSt menu segment.

5. Press NEXT to enter the SEnSOr 0 menu segmentand press ENTER to access the do SEnSOr 0 sub-segment. With the attached sensor stabilized in dryair, press ENTER again to zero the sensor.

6. CALibrAtE will show on the display. Press ENTERand CAL will display. Immerse the sensor in a solu-tion of known conductance, and enter the value of thestandard. The horizontal arrows will highlight the digit(including µS to mS and decimal positions) to bechanged and cause it to blink. The vertical arrows willincrease or decrease the currently highlighted (andblinking) digit. The display will change from a randomnumber to the input value. It should be calibrated atmiddle of the chosen manual range for maximumaccuracy.

NOTE1. If Cal Error shows, reset Cell Const = 1.002. This will also change the value shown

for the cell constant.3. DO NOT reenter SEnSOr 0. There is no

way out except to set the current readvalue (0 in air) to zero.

Press ENTER to return to the Calibratemenu.

5.2.1 Temperature CalibrationPress NEXT three (3) times and the tEMP AdJ promptwill be displayed. Press ENTER.

1. With the sensor in a sample solution of known tem-perature, allow the temperature of the sensor to stabi-lize for ten minutes (minimum). Utilize the editingkeys of the IRC to standardize the transmitter's tem-perature reading to that of the sample solution. PressENTER to standardize the temperature reading andreturn to the tEMP AdJ menu segment.

2. Press NEXT to enter the tEMP SLOPE menu segment.

The correct temperature slope must be entered intothe transmitter to ensure an acceptable process vari-able measurement under fluctuating process temper-ature conditions. This can be done two ways:

A. At the tEMP SLOPE prompt it allows for input ofconductance values of the specific process solu-tion being measured.

Press ENTER. t1 will be displayed. Enter theconductance of the process solution atroom/process temperature.

Press ENTER. t2 will be displayed. Warm theprocess solution to an elevated stable tempera-ture of normal operation. Adjust the t2 value tothe conductance at this higher temperature.Press ENTER. The transmitter will calculate theslope and use it in all process measurements. Ifslope error occurs, the calculated slope is no dif-ferent than the currently input slope. PressRESET.

B. Alternatively, the slope can be input directly.Press NEXT. Adj SLOPE appears. PressENTER at the prompt and input the known slope.Press ENTER.

Press EXIT to return to main display.NOTE

The range of slope is in %/°C, with a maximum of5.0%.

5.3 CALIBRATE MENU (Percent Concentration).

The following steps can be used for initial set-up and stan-dardization where toroidal (t) sensors are employed forpercent concentration measurements.

NOTETo accurately measure % concentrations, theappropriate equation must be used. This requireschanging the tYPE under the dISPLAY sub-menuin the Program menu to the correct chemical andconcentration.

MODEL CELL CONSTANT

222 4.0 & 6.0

225 3.0

226 1.0

228 3.0

TABLE 5-1. NOMINAL CELL CONSTANTS*

* Check sensor labels for actual, if given.

Page 32: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

��������� Calibrate menu header��� Sensor calibration��M� ����� Sub-menu header� First temperature conductivity reading for slope calculation�, Second temperature conductivity reading for slope calculation��& ����� Sub-menu header������ Slope adjustment %/°C ���� ����� Sub-menu header���� Cell constant value������ Sub-menu header������ Sensor "0" conductivity in air 2���� ��� Reset percent concentration offset to factory default of zero (0) ���� ��� Sub-menu header���� Temperature adjustment °C/°F

1. To access the CALIbrAtE menu, press the CAL keyon the Infrared Remote Control. If security has beenenabled, the secondary process display will bereplaced with a prompt asking for the “Id”. Using theIRC editing keys, enter the “Id”. If the correct “Id” isentered, the CALIbrAtE menu will appear whenENTER is pressed. If CALIbrAtE menu does notappear when ENTER is pressed, see Section 4.3,step 9, for procedure to find correct code.

NOTEReset can be pressed at any step toreturn to the process display and over-ride any value not previously entered.

2. When the calibrate menu segment has beenaccessed, press the NEXT and ENTER commandsto access the CELL menu segment with the flashingcell constant prompt.

3. Utilizing the arrow keys on the IRC, generate thecorrect cell constant of the sensor being used.

NOTECell constants are sensor dependent.Table 5-1 lists the nominal cell constantsfor the four sensors compatible with theModel 4081T.

4. Press ENTER to activate selected cell constant andreturn to the CELL COnSt menu segment.

5. Press NEXT to enter the SEnSOr 0 menu segmentand press ENTER to access the do SEnSOr 0 sub-segment. With the attached sensor stabilized in dryair, press ENTER again to zero the sensor.

The CALIbrAtE menu is reaccessed.6. Press ENTER. CAL will appear. Immerse the toroidal

sensor into a solution of known percent of the chemi-cal to be measured and input that percent. Allow thesensor to stabilize at the solution temperature (about10 min).

Enter the value of the standard solution and pressENTER. “Processing” will appear when the calibration ismade; then the menu will return to CALIbrAtE.7. Press NEXT. The CELL COnSt menu segment will

appear. The cell constant will have been changed toreflect the calibration step above. Press ENTER todisplay the new cell constant.

8. Press NEXT to enter the SEnSOr 0 menu segment.Do not press ENTER unless a new air calibration isdesired.

9. Press NEXT to enter the rESEtPct menu segment.This resets the SEnSOr 0 offset value to zero.

10. Press NEXT to access the tEMP AdJ menu segment.Pressing ENTER allows access to the cursor so auser specified temperature can be input. The currenttemperature is displayed. If this is acceptable, pressENTER.

11.Press RESET to return to the process display.

5.4 ON-LINE -TRANSMITTER / SENSOR CALIBRATIONFor maximum accuracy, calibrate the sensor in theprocess. This should be done after the initial transmittercalibration and periodically thereafter as required. On-line calibration is well-suited for most toroidal measure-ments.

NOTE

The calibration adjustment allows the process con-ductivity to be adjusted to the conductivity fromother measurements. However, it can only bechanged a maximum of 5%. Greater changes willresult in a slope error message. If greater changesare required, the cell constant used in Section 5.2needs to be changed.

MODELS 4081T SECTION 5.0START-UP AND CALIBRATION

5-4

TABLE 5-2. CALIBRATE MENU MNEMONICS

Page 33: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

6-1

6.1 OVERVIEWThe Model 4081T transmitter automatically monitors forfault conditions. The Diagnose Menu allows the currentvariable settings to be reviewed and shows fault mes-sages indicating problems detected. Figure 6-1 illus-trates the relationship between the Diagnose Menu andits sub-menus. The factory-set diagnose values are illus-trated in Figure 6-2. The mnemonics are defined inTable 6-1.

6.1.1 TROUBLESHOOTING

Step 1 Look for a diagnostic fault message on thedisplay to help pinpoint the problem. Refer toTable 6-2 for an explanation of the message anda list of the possible problems that triggered it.

Step 2 Refer to the Quick Troubleshooting Guide,Table 6-3, for common loop problems and therecommended actions to resolve them.

MODELS 4081T SECTION 6.0DIAGNOSIS AND TROUBLESHOOTING

SECTION 6.0DIAGNOSIS AND TROUBLESHOOTING

Step 3 Follow the step by step troubleshooting flowchart, offered in Figure 6-5, to diagnose lesscommon or more complex problems.

6.1.2 DISPLAYING DIAGNOSTIC VALUES

The DIAG key on the IRC is used to access theDiagnosis Menu. The menu flow is shown in Figure 6-2and the mnemonics are defined in Table 6-1.

The ShoW FLT sub-menu can be entered to show thelast three faults/warnings. The most recent is displayedfirst; NEXT scrolls through the remaining faults. PressingEXIT clears all fault/warnings and returns the SHoW FLTsegment. Disconnecting power removes all fault mes-sages from memory. The nonE is displayed when nofaults/warnings have occurred.

CURRENT OPERATING MENU

KEYPRESS COMMANDS Menu Segment/Prompt

Area

Calibrate MenuSegments/Commands

Program MenuSegments/Commands

DIAGNOSE MENUSegments/Commands

0�����

EXIT NEXT ENTER

����

EXIT NEXT ENTER

FIGURE 6-1. Diagnose Menu Segments

������

EXIT NEXT ENTER

�������

EXIT NEXT ENTER

����

EXIT NEXT ENTER

��� �����

EXIT NEXT ENTER

���� �����

EXIT NEXT ENTER

���)� ���

EXIT NEXT ENTER

������ �

EXIT NEXT ENTER

����

EXIT NEXT ENTER

��� ��

EXIT NEXT ENTER

���������

EXIT NEXT ENTER

���� �����

EXIT NEXT ENTER

���� ���

EXIT NEXT ENTER

Calibrate Program Diagnose����

Exit Enter

Page 34: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

6-2

���� Absolute conductivity (µS/cm or mS/cm)

���� Sensor cell constant used in T or % con-

centration display type

������ Calibration factor

���� No fault messages activated

���)� ��� Show fault messages

������ Temperature slope in %/ °C

��� �� Software version, CPU board

MODELS 4081T SECTION 6.0DIAGNOSIS AND TROUBLESHOOTING

Calibrate Program Diagnose

Exit Enter

Return toMain

Screen

TABLE 6-1. Diagnostic Variables Mnemonics

��� �

EXIT NEXT

��� ��

EXIT NEXT

���)� ���

EXIT NEXT ENTER

����

EXIT NEXT

������ .

EXIT NEXT

������ ,.

EXIT NEXT

���� .

EXIT NEXT

µS

FIGURE 6-2. Diagnose Values

Page 35: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

6-3

MODELS 4081T SECTION 6.0DIAGNOSIS AND TROUBLESHOOTING

6.2 FAULT CONDITIONSThree classes of error conditions/problems can bedetected and are differentiated by the diagnostic pro-gram. System disabling problems are faults caused byfailures in the loop or significant variations in theprocess. System non-disabling problems are warningsand deal with inputted signals/values or Analog toDigital conversion settings. The third class of detectedproblems are error messages and occur when the cali-bration limits are exceeded.

6.2.1 DISABLING FAULTS1. Both FAULT and HOLD annunciation fields will

become active (see Figure 6-3).

2. The process variable will flash at the rate of 1 sec-ond ON and 1 second OFF.

3. The appropriate fault message alternates with thenormal Temperature display (see Figure 6-3).

CALIBRATE PROGRAM DIAGNOSE

“ � � � � � � � � ” /

E X I T N E X T E N T E R

µS/cm

FAULT

HOLD

FIGURE 6-3. Disabling Fault Annunciation

CALIBRATE PROGRAM DIAGNOSE

“ � � � � � ) � � � � ” /

E X I T N E X T E N T E R

µS/cm

FIGURE 6-4. Non-Disabling Warning Annunciation

6.2.2 NON-DISABLING WARNINGS

When a non-system disabling condition occurs, awarning message is displayed. The Process variabledoes not flash. The appropriate message alternates withthe Temperature display (see Figure 6-4).

If more than one fault exists, the display will sequencethrough the diagnostic messages. This will continue untilthe cause of the fault has been corrected.

FAULT

HOLD

Page 36: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

6-4

MODELS 4081T SECTION 6.0DIAGNOSIS AND TROUBLESHOOTING

6.3 DIAGNOSTIC MESSAGES

The Model 4081T transmitter’s diagnostics constantly monitor the system for possible problems. If an operational prob-lem is encountered, check the display for a fault or error message. These are displayed in the Temperature segment ofthe display. Note the message and refer to Table 6-2 for a description of possible problems that may have triggeredthe diagnostic message.

Message Description Action

Faults

���� �� Low temperature limit of 0.0° C is exceeded (too low). Check wiring or sensor/process temp.

Check RTD

���� �� High temperature limit of 100.0° C is exceeded (too high). Check wiring or sensor/process temp.

Check RTD

���� ���� The RTD sense line fault limits have been exceeded Check wiring or Check Program/Temp

for the sensor. menu setting to verify the 100-3

sensor type connected.

��� ���� The CPU has failed during RAM or EEPROM Recycle the power. If persistent contact

verification. the factory.

���� ���� The transmitter has not been accurately factory calibrated. Contact factory.

��� ���� The PROM failed the check-sum test. Contact factory.

������)&� A wrong value was detected during power-up. Recycle the power.

�#�"�� 0!3' Conductivity too low or open Verify the solution type setting

Simulate sensor (Figure 6.5) to check

transmitter

Replace sensor

Warnings

����� )&��� The compensated conductivity limit of 9999 mS/cm is Verify the conductivity range setting.

exceeded.

��� )&��� An analog to digital conversion error has occurred. Recycle the power.

Errors

��� ��� A calibration error has occurred between the standard Press RESET and repeat.

and process.

������ ��� The limit for t2 in a two point calibration has been Press RESET and repeat the

exceeded ( > 5%). calibrate/temp slope menu setting.

** ��� Sensor Zero limit has been exceeded. Press RESET and repeat the cali-

brate/sensor menu setting.

)&2��� ��� An attempt to write on the EEPROM has failed. The jumper JP-1 on the CPU board

has been removed.

TABLE 6-2. Diagnostic Fault Messages.

Page 37: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

6-5

MODELS 4081T SECTION 6.0DIAGNOSIS AND TROUBLESHOOTING

SYMPTOM ACTIONWrong temperature reading. Perform a temperature standardization. Verify sensor's RTD.Suspected temp. compensation problem. Resistance vs. temp.; see Table 6.4; temperature may be out of range of sensor.

Check wiring. Check jumpers and RTD configuration on displayDisplay segments missing. Display inoperable. Replace Display board. If fault continues, check CPU board.Analyzer locks up; won't respond. Replace PCB stack.

Press Reset on IRC.Check batteries in IRC.

Erratic displays. Check sensors in process. Transmitter won't respond to IRC key presses. Verify and clean ribbon cable connection on CPU board.

Check batteries in IRC

Key press gives wrong selection. Replace IRC. Check ribbon cable connection on CPU board.No display or indicators. Check power connections. Replace PCB stack.”Excess Input” Check sensor wiring.“Reverse Input” Perform sensor zero.“Check sensor zero” Analyzer will not zero; place sensor in air and perform zero routine (see Section 5.2).

Table 6-3 identifies some of the more common symptoms and suggests actions to help resolve a problem. In general,wiring is most commonly at fault.

6.4 QUICK TROUBLESHOOTING GUIDE

TABLE 6-3. Quick Troubleshooting Guide.

When it is apparent by grab sample analysis that thetransmitter is giving inaccurate readings, the following pro-cedure should be followed.

A. A quick visual inspection of the installation may identifythe problem. Check to be sure that the transmitter ismounted securely and that its internal parts are proper-ly connected.

B. Recheck to ensure the power supply is connected tothe correct pins in the transmitter and that power isbeing received.

C. Check the sensor to transmitter terminal wiring and thatall connections are tight. Most error messages are gen-erated by incorrect wiring and will indicate if the RTD orthe toroid are connected incorrectly.

D. The sensor must be immersed into the process streamto the top of the toroid.

E. Verify that the sensor is clean and the process is flow-ing through and around the toroid.

6.4.1 FIELD TROUBLESHOOTING

Page 38: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

6-6

MODELS 4081T SECTION 6.0DIAGNOSIS AND TROUBLESHOOTING

6.5 SYSTEMATIC TROUBLESHOOTINGNot all the problems encountered will be typical. If theQuick Troubleshooting Guide will not resolve the error,then try the step-by-step approach offered in this sec-tion.

Conductivity MeasurementProblem (in the process)

Remove the sensor from processand place sensor in air. Zero transmitter.

Refer to Section 5.2 and 5.3.

OK?

ConsultService Center

YES

NO

YES

YES

NO

NO

Does problemstill exist?

NOTE:Before starting this proceduremake sure that all wiring is correct.

FIGURE 6-5. Troubleshooting Flow Chart

Step 1 Follow the applicable troubleshooting flow chart below:

Step 2 Refer to the tests and instructions indicated bythe flow chart to diagnose the problem.

Place sensor in process andstandardize. Refer to Section 5.2.

OK?Restart

Transmitter

Remove sensor from process andtest in known conductivity solution

OK?

Check wiringfor short and checkjumpers for correct

configuration

Check diagnosticmessages

Refer to Table 6-2

Check for groundloops and/or

improper installation

YES NO

Page 39: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T SECTION 6.0DIAGNOSIS AND TROUBLESHOOTING

6.6 RTD RESISTANCE VALUESTable 6-4 is a ready reference of RTD resistance valuesat various temperatures. These are used for test andevaluation of the sensor.

NOTEOhmic values are read across the RTDelement and are based on the manu-facturer ’s stated values (±1%). Allowenough time for the RTD element in thesensor to stabilize to the surroundingtemperature (10 min).

Temperature Pt-100(°C) Resistance (ohms)

0 100.0010 103.9020 107.7925 109.7330 111.6740 115.5450 119.4060 123.2470 127.0780 130.8990 134.70

100 138.50

Table 6-4. RTD Resistance Values.

Table 6-5. Conductivity Determination.

6-7

FORMULA:

EXAMPLE:

cell constant value x 1,000,000desired simulated conductivity in µs/cm

.01 x 1,000,00010 µs/cm

Use the following formula to determine the appropriate resistance value to use to simulate aconductivity value:

= resistance in ohms

= use 1,000 ohm resistance

Page 40: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

6-8

Page 41: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

7-1

MODELS 4081T SECTION 7.0MAINTENANCE

SECTION 7.0MAINTENANCE

7.1 OVERVIEWMaintenance consists of "Preventative" and "Corrective"measures.

7.2 PREVENTATIVE MAINTENANCE

7.2.1 Sensor Maintenance. Sensor maintenanceconsists of periodic cleaning of the electrode. If the sen-sor is coated, the sensor must be cleaned.

A weekly cleaning is a good starting maintenanceschedule. This schedule can then be fine tuned to thesite process.

7.2.2 Transmitter Maintenance. Transmitter mainte-nance consists of periodic calibration. A monthly cali-bration is a good starting maintenance schedule. Thisschedule can then be fine tuned to the site process.

7.2.3 Initiating HOLD Function For Maintenance. Toplace the transmitter into the Hold operational mode priorto servicing the sensor, press the HOLD key on the IRC.The message field will respond with a message concern-ing the present hold condition. Press the IRC editing keyto toggle to the On condition. Press ENTER to activateHOLD output.

Hold Mode will maintain the operating parametersregardless of process changes.

The section of the LCD reserved for hold annunciation(Refer to Figure 7-1) will display HOLD when the trans-mitter is in the Hold Mode.

Always calibrate after cleaning or replacing the sensor.

To return transmitter to normal operation, press HOLDon the IRC.

Press the IRC editing key to toggle to the OFF condition.Press ENTER to disengage the HOLD output function.

µS/cm

FAULT

HOLD

FIGURE 7-1. Hold Annunciation

Hold field Illuminated

CALIBRATE PROGRAM DIAGNOSE

,,--0��

E X I T N E X T E N T E R

7.3 CORRECTIVE MAINTENANCERefer to Figure 7-2 for an exploded view of the 4081TTransmitter.

Table 7-1 lists suggested spare parts along with partnumbers. Sales and service locations are located on theback pages of this manual.

Page 42: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

7-2

FIGURE 7-2. Exploded View of Model 4081T Transmitter

MODELS 4081T SECTION 7.0MAINTENANCE

}1

2

6

13

139

7

5

812

TABLE 7-1. Replacement Parts for Model 4081T Transmitter

Location in ShippingFigure 7-1 PN Description Weight

1 23811-02 PCB stack consisting of the CPU, communication, and analog boards; 1 lb/0.5 kgdisplay board is not included; CPU, communication, and analog boards are factory-calibrated as a unit and cannot be ordered separately

2 23652-01 LCD display PCB 1 lb/0.5 kg

5 33337-02 Terminal block 1 lb/0.5 kg

6 23593-01 Enclosure cover, front with glass window 3 lb/1.5 kg

7 33360-00 Enclosure, center housing 4 lb/1.5 kg

8 33362-00 Enclosure cover, rear 3 lb/1.0 kg

9 6560135 Desiccant in bag, one each 1 lb/0.5 kg

9550187 O-ring (2-252), one, front and rear covers each require an O-ring 1 lb/0.5 kg

12 note Screw, 8-32 x 0.5 inch, for attaching terminal block to center housing *

13 note Screw, 8-32 x 1.75 inch, for attaching circuit board stack to center *housing

14 33342-00 Cover lock 1 lb/0.5 kg

33343-00 Locking bracket nut 1 lb/0.5 kg

note Screw, 10-24 x 0.38 inch, for attaching cover lock and locking bracket *nut to center housing

NOTE: For information only. Screws cannot be purchased from Rosemount Analytical.* Weights are rounded up to the nearest whole pound or 0.5 kg.

Page 43: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

8-1

MODELS 4081T SECTION 8.0PRODUCT DATA

SECTION 8.0PRODUCT DATA

• REMOTE COMMUNICATION IS SIMPLE; use the hand-held infraredremote controller, DeltaV1, or FOUNDATION2 Fieldbus host.

• LARGE TWO LINE DISPLAY shows conductivity and temperature.

• SIMPLE, INTUITIVE menus make programming and calibrating easy.

• INDUCTIVE CONDUCTIVITY AND PERCENT CONCENTRATIONMEASUREMENTS with both high accuracy and linearity.

• ROBUST NEMA 4X and NEMA 7 ENCLOSURE protects the trans-mitter from harsh plant environments.

• INTRINSICALLY SAFE DESIGN allows the transmitter to be used inhazardous environments (with appropriate safety barriers).

• NON-VOLATILE EEPROM MEMORY retains program settings and calibration data duringpower failures.

FEATURESREMOTE COMMUNICATIONS: Remote communica-tions with the Model 4081T transmitter is easy. Thehand-held, push button infrared remote controllerworks from as far away as six feet. The transmitteralso communicates via any FOUNDATION fieldbus host,such as the Fisher Rosemount DeltaV system.DISPLAY: The 0.8-inch high LCD main display meansconductivity values are easy to read even at a dis-tance. Temperature reading also appears in a 0.3inch high display. MENUS: Menu formats for calibration and program-ming are simple and intuitive. Prompts guide the userthrough the basic procedures. Diagnostic and errormessages appear in plain language. There are noannoying error codes to look up.

Remote Control and Digital CommunicationCapability Make Interface Convenient, Regardlessof Transmitter Location: Direct user interface isachieved via an infrared remote controller that pro-vides access to a self-prompting menu for program-ming, calibration, standardization, and interrogation.Digital communication capability through FOUNDATION

fieldbus or AMS (Asset Management Solutions) soft-ware stretches the user’s access from anywhere inthe factory to anywhere outside the factory.

1. DeltaV is a trademark of Fisher-Rosemount.

2. FOUNDATION is a registered trademark of Fieldbus Foundation.

Page 44: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T SECTION 8.0PRODUCT DATA

FUNCTIONAL SPECIFICATIONSCalibration: Calibration is easily accomplished by

immersing the sensor in a known solution and entering its value.

Power Supply and Load Requirements:A power supply voltage of 9 Vdc to 32 Vdc at 22mA is required; Intrinsically Safe installations maybe limited to a maximum of 2-3 transmitters pernode, depending on the barrier used.

Automatic Temperature Compensation: 3-wire Pt 100 RTD Conductivity: 0 to 200°C (32 to 392°F)% Concentration: 0 to 100°C (32 to 212°F)

Local Readout: LCD display may be set in one ofthree positions at 90° increments for optimum legi-bility independent of mounting. Main display is 4digits, 20 mm (0.8 in.) tall. Message display is tendigits 7 mm (0.3 in.) tall

Diagnostics: The internal diagnostics can detect: Calibration Error Zero ErrorTemperature Slope Error Low Temperature ErrorHigh Temperature Error Sensor FailureLine Failure CPU FailureROM Failure Input Warning

Once one of the above is diagnosed, the LCD will dis-play a message describing the failure/default detected. FOUNDATION Fieldbus:

3 AI Function Blocks: conductivity, temperature,and absolute conductivity

Execution time: 75 millisecondsPID Block (optional)

Execution time: 100 millisecondsAmbient Temperature: –20 to 65°C. (–4 to 149°F)Failure Mode Alarm: When a fault is detected, the

display will indicate a fault.Configuration Security: Access to the transmitter

configuration and reconfiguration modes may berestricted via user selected security codes.

Enclosure: NEMA 4X (IP65), weatherproof and corrosion resistant; NEMA 7, explosion-proof

CE: EMI/RFI CertificationEN-61326

Hazardous Area Classification:Explosion Proof:

FM: Class I, Div. 1, Groups B, C & DClass II, Div. 1, Groups E, F, & GClass III, Div. 1

CSA: Class I, Div. 1, Groups C& DClass I, Div. 2, Groups A, B, C & DClass II, Div. 2, Groups E, F & GClass III, Div. 1

Intrinsic Safety:FM: Class I, II & III, Div. 1

T4 T AMB= 40°C; T3AT AMB= 70°CCSA: Class I, Div. 1

T 3C T AMB=40°C; T3 T AMB=80°C CENELEC: EEx ia IIC

T5 Tamb=40°C; T4 Tamb=60°CNon-Incendive:

FM: Class I, Div. 2, Groups A, B, C & DCSA: Class I, Div. 2, Groups A, B, C & D T5

(Tamb=40°C)

PHYSICAL SPECIFICATIONS - GeneralHousing: Epoxy-polyester painted over low-copper

aluminum. Neoprene O-rings on cover. 160.5 mmx 175.3 mm x 161.3 mm (6.3 in. x 6.9 in. x 6.4 in.)

Diameter: 155.4 mm (6.1 in.) Electrical Conduit Openings: 2 X 3/4 in. FNPTWeight/Shipping Weight: 4.18 kg/4.27 kg (9.2/9.4 lb)

TRANSMITTER SPECIFICATIONS @ 25°CMeasured Range*: 0 to 2,000,000 µS/cmAccuracy: ± 1.0% of readingRepeatability: ± 0.25% of readingStability: 0.25% of output range/month, non-cumulativeAmbient Temperature Coefficient: ± 0.2% of FS/°CTemperature Slope Adjustment: 0-5%/° C% Concentration Ranges:

Sodium Hydroxide: 0 to 12%Hydrochloric Acid: 0 to 15%Sulfuric Acid: 0 to 25% and 96 to 99%

LOOP SPECIFICATIONS (see table below)Accuracy: ± 1.0% ± 2 least significant digit

MANUAL RANGE 1 2 3 4

Low Range 80 - 800 800 - 8,000 8,000 - 80,000 80,000 - 400,000

(accuracy: ± 1.0%)

High Range 1,100 - 11,000 11,000 - 110,000 110,000 - 1,200,000 N/A

(accuracy: ± 1.0%)

*NOTE: Values shown are for 25°C conductivity with a temperature slope of 2% per degree C. The maximum range value will be higher forsolutions with a lower temperature slope, and lower for solutions with a higher temperature slope. Values shown are for uncompensatedconductivity using a cell constant of 1.0. The conductivity values auto range from 0 to 2,000,000 µS/cm with an accuracy of 5 to 10%±150 µS/cm depending on the process conditions, installation, and the sensor used. For greater accuracy and repeatability, manualrange selection is recommended.

Measurement Range (µS/cm)*

8-2

Page 45: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T SECTION 8.0PRODUCT DATA

8-3

FIGURE 8-2. Infrared Remote Control

TRANSMITTER DISPLAY (Figure 8-1)The liquid crystal display (LCD) provides valuable userinformation clearly identified as follows:

1. Continuous process display.2. Process temperature displayed during process

operation mode.3. Options within sub-menus become visible when in

each selected menu.4. Selected menu becomes visible after the appro-

priate “Menu key” on the IRC is activated.5. “Hold” is displayed when the analyzer is in hold,

test or fault mode. Pressing the “HOLD” key onthe IRC will place the transmitter in a hold mode.

6. “Fault” is displayed should a system disablingfault occur.

INFRARED REMOTE CONTROL FUNC-TIONS (Figure 8-2)All operating functions of the Model 4081T areaccessed and activated through the hand-held InfraredRemote Control (IRC).

1. MENU KEYS: Allow access to calibrate, programand diagnose menus.

2. VARIABLE ENTRY KEYS: Allow the operator toenter data, move between sub-menus and edit.

3. EDITING KEYS: Allow navigation through thepre-programmed variables or editable digits.These arrow keys scroll across digit fields whenentering numbers.

4. SPECIAL ENTRY KEYS:“Hold” key activationdrives the reading to a preprogrammed level.“Reset” key activation aborts the current functionand exits to the on-line process display mode.

1.

4.

3.

2.

FIGURE 8-1. Transmitter Display

6

5

4

2

1

3

*.FAULTHOLD

mS

CALIBRATE PROGRAM DIAGNOSE

EXIT NEXT ENTER

��.

FIGURE 8-3. Functional Block Diagram for the Model 4081T Transmitter with FOUNDATION Fieldbus

Page 46: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T SECTION 8.0PRODUCT DATA

8-4

MODEL / PN DESCRIPTION2002577 Two Inch Pipe Mounting Kit 23572-00 Infrared Remote Controller

ORDERING INFORMATIONThe Model 4081T two-wire microprocessor transmitter is housed in a NEMA 4X and NEMA 7 case.Communication with the transmitter is through a hand-held infrared remote controller, DeltaV or FOUNDA-TION Fieldbus host. Standard features include µS, mS, and % concentration measurements, as well as auto-matic or manual temperature compensation.

MODEL4081T FOUNDATION FIELDBUS TWO-WIRE MICROPROCESSOR TRANSMITTER

Code REQUIRED SELECTION

03-20 LCD (Infrared Remote Control - included), 9.4 lb/4.3 kg

03-21 LCD (Infrared Remote Control - not included)

RECOMMENDED SENSORS:

Model 222 Flow-Through Toroidal Conductivity Sensor

Model 225 Clean-In-Place (CIP) Conductivity Sensor

Model 226 Submersion/Insertion Conductivity Sensor

Model 228 Submersion/Insertion/Retractable Toroidal Conductivity Sensor

ACCESSORIES

Code AGENCY APPROVALS (no selection required)

67 FM approved, Intrinsically Safe (when used with approved sensor and safety barrier) and Explosion Proof

69 CSA approved, Intrinsically Safe (when used with approved sensor and safety barrier) and Explosion Proof

73 CENELEC approved, Intrinsically Safe (safety barrier required)

4081T - 01 - 20 - 67 EXAMPLE

Page 47: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

9-1

MODELS 4081T SECTION 9.0OPERATION WITH REMOTE CONTROLLER

SECTION 9.0OPERATION WITH REMOTE CONTROLLER

FIGURE 9-1. Functional Block Diagram for the Model 4081T Transmitter with FOUNDATION Fieldbus

OVERVIEWThis section covers basic transmitter operation and software functionality. For detailed descriptions of the functionblocks common to all Fieldbus devices, refer to Fisher-Rosemount Fieldbus FOUNDATION Function Blocks manual,publication number 00809-4783.

Figure 9-1 illustrates how the conductivity signal is channeled through the transmitter to the control room and theFOUNDATION Fieldbus configuration device.

Software Functionality. The Model 4081T software is designed to permit remote testing and configuration of thetransmitter using the Fisher-Rosemount DeltaV Fieldbus Configuration Tool, or other FOUNDATION fieldbus compli-ant host.

Transducer Block. The transducer block contains the actual measurement data. It includes information about sen-sor type, engineering units, reranging, damping, temperature compensation, calibration, and diagnostics.

Resource Block. The resource Block contains physical device information, including available memory, manufac-turer identification, type of device, and features.

FOUNDATION Fieldbus Function Blocks. The Model 4081T includes three Analog Input (AI) function blocks and oneInput Selector (ISEL) function block as part of its standard offering.

Analog Input. The Analog Input (AI) block processes the measurement and makes it available to other functionblocks. It also allows filtering, alarming, and engineering unit change.

Characterizer (optional). The characterizer block changes the characteristic of the input signal. Common usesof the characterizer block include converting temperature to density or humidity, and converting millivolts to tem-perature for an IR sensor.

Page 48: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April
Page 49: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T SECTION 10.0RETURN OF MATERIALS

10-1

SECTION 10.0RETURN OF MATERIALS

GENERAL.

To expedite the repair and return of instruments,proper communication between the customer and thefactory is important. Before returning a product forrepair, call 1-949-757-8500 for a Return MaterialsAuthorization (RMA) number.

WARRANTY REPAIR.

The following is the procedure for returning instru-ments still under warranty:

1. Call Rosemount Analytical for authorization.

2. To verify warranty, supply the factory sales ordernumber or the original purchase order number.In the case of individual parts or sub-assem-blies, the serial number on the unit must be sup-plied.

3. Carefully package the materials and encloseyour “Letter of Transmittal” (see Warranty). Ifpossible, pack the materials in the same manneras they were received.

4. Send the package prepaid to:

Rosemount Analytical Inc., Uniloc DivisionUniloc Division2400 Barranca ParkwayIrvine, CA 92606

Attn: Factory Repair

RMA No. ____________

Mark the package: Returned for Repair

Model No. ____

NON-WARRANTY REPAIR.

The following is the procedure for returning for repairinstruments that are no longer under warranty:

1. Call Rosemount Analytical for authorization.

2. Supply the purchase order number, and makesure to provide the name and telephone numberof the individual to be contacted should addition-al information be needed.

3. Do Steps 3 and 4 of Warranty Repair.

NOTEConsult the factory for additional informa-tion regarding service or repair.

Page 50: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

10-2

Page 51: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

A-1

Display Timeout. The display returns to the Process display when the RESET key is pressed, orif no key has been pressed for the timeout period. The normal timeout periodis 2 minutes. During buffer calibration, the timeout period is 20 minutes. Whenin the Hold and Test Modes, the timeout feature is disabled.

Error Condition An error condition (“Std Err”, “SLOPE Err LO”, or “SLOPE Err HI”) occurredduring calibration due to a calculated value exceeding a calibration limit.

The appropriate error message is displayed in the Temperature display area.

Fault Condition A system disabling condition.

• The Fault and Hold display areas illuminate.

• The process variable flashes.

• An appropriate fault message appears in the Temperature display area.

• If not in the Test or Hold Modes, the output current goes to the non-Zero fault value.

Menu segment A term used to define submenus, within the menu programs, that are used to select the set of prompts required to set-up the transmitter during configuration

Item/Value Item refers to a parameter contained in a list of parameters. (e.g., "On" and"OFF").

Value refers to a parameter value that may be edited (e.g., CAL “1”000 µS/cm).

Main Menus Those menus available to calibrate, set up, and diagnose transmitter operation using variables other than the factory default settings.

Process Display The Main display consists of:

• the Primary process variable (conductivity, % concentration or resistivity) in large numerals (in the top half of the display), and

• the temperature measurements (shown in the lower portion of the dis-play).

Prompt A message that appears in the temperature display area requesting a response from the operator that is either a numerical value, or an item from the list associated with the parameter being edited.

Mnemonics Short descriptions that aid or help memory.

MODELS 4081T APPENDIX AGLOSSARY

APPENDIX AGLOSSARY

Page 52: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

RTD Resistive Temperature Device used to provide temperature signal to instrument.

Special Entry keys Those keys on the IRC pressed to access the DIAGNOSE, HOLD and RESETfunctions of the transmitter.

• The Diagnose function gives access to information about absolute conductivity, sensor (cell constant value, calibration constant, and cellfactor), temperature slope, transmitter software version and fault messages, to aid in interpretation of Fault and Warning conditions.

• The HOLD function is used to maintain the conductivity value to a predetermined value while enabled.

• The RESET function aborts the current operation and returns to the Process Display Screen.

Temperature Offset A value calculated by the instrument to make RTD measurement displayed match site value. Calculated during the TEMPERATURE ADJUSTMENTfunction to match the RTD reading with a known site standard.

Warning Conditions. When a non-system disabling condition occurs, an appropriate message is dis-played in the temperature display area.

Raw Conductivity Conductivity that is not factory or process calibrated, or compensated for tem-perature.

Absolute Conductivity Conductivity that is factory calibrated, but not process calibrated or compen-sated for temperature.

Conductivity Conductivity that is factory and process calibrated and compensated for tem-perature.

Resistivity A value equal to the inverse of the conductivity.

MODELS 4081T APPENDIX AGLOSSARY

GLOSSARY (Continued)

A-2

Page 53: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T APPENDIX A4081T RESOURCE AND TRANSDUCER BLOCK PARAMETERS

APPENDIX B4081T RESOURCE AND TRANSDUCER BLOCK PARAMETERS

B-1

Page 54: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T APPENDIX A4081T RESOURCE AND TRANSDUCER BLOCK PARAMETERS

B-2

Page 55: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T APPENDIX A4081T RESOURCE AND TRANSDUCER BLOCK PARAMETERS

B-3

Page 56: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T APPENDIX A4081T RESOURCE AND TRANSDUCER BLOCK PARAMETERS

B-4

Page 57: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T APPENDIX A4081T RESOURCE AND TRANSDUCER BLOCK PARAMETERS

B-5

Page 58: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

MODELS 4081T APPENDIX A4081T RESOURCE AND TRANSDUCER BLOCK PARAMETERS

B-6

Page 59: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

WARRANTY

Goods and part(s) (excluding consumables) manufactured by Seller are warranted to be free from defects in workman-ship and material under normal use and service for a period of twelve (12) months from the date of shipment by Seller.Consumables, pH electrodes, membranes, liquid junctions, electrolyte, O-rings, etc. are warranted to be free from defectsin workmanship and material under normal use and service for a period of ninety (90) days from date of shipment by Seller.Goods, part(s) and consumables proven by Seller to be defective in workmanship and / or material shall be replaced orrepaired, free of charge, F.O.B. Seller's factory provided that the goods, parts(s), or consumables are returned to Seller'sdesignated factory, transportation charges prepaid, within the twelve (12) month period of warranty in the case of goodsand part(s), and in the case of consumables, within the ninety (90) day period of warranty. This warranty shall be in effectfor replacement or repaired goods, part(s) and consumables for the remaining portion of the period of the twelve (12)month warranty in the case of goods and part(s) and the remaining portion of the ninety (90) day warranty in the case ofconsumables. A defect in goods, part(s) and consumables of the commercial unit shall not operate to condemn such com-mercial unit when such goods, parts(s) or consumables are capable of being renewed, repaired or replaced.

The Seller shall not be liable to the Buyer, or to any other person, for the loss or damage, directly or indirectly, arisingfrom the use of the equipment or goods, from breach of any warranty or from any other cause. All other warranties,expressed or implied are hereby excluded.

IN CONSIDERATION OF THE STATED PURCHASE PRICE OF THE GOODS, SELLER GRANTS ONLY THE ABOVESTATED EXPRESS WARRANTY. NO OTHER WARRANTIES ARE GRANTED INCLUDING, BUT NOT LIMITED TO,EXPRESS AND IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

RETURN OF MATERIAL

Material returned for repair, whether in or out of warranty, should be shipped prepaid to:

Rosemount Analytical Inc.Uniloc Division

2400 Barranca ParkwayIrvine, CA 92606

The shipping container should be marked:

Return for RepairModel _______________________________

The returned material should be accompanied by a letter of transmittal which should include the following information(make a copy of the "Return of Materials Request" found on the last page of the Manual and provide the following there-on):

1. Location type of service, and length of time of service of the device.2. Description of the faulty operation of the device and the circumstances of the failure.3. Name and telephone number of the person to contact if there are questions about the returned material.4. Statement as to whether warranty or non-warranty service is requested.5. Complete shipping instructions for return of the material.

Adherence to these procedures will expedite handling of the returned material and will prevent unnecessary additionalcharges for inspection and testing to determine the problem with the device.

If the material is returned for out-of-warranty repairs, a purchase order for repairs should be enclosed.

Page 60: Remote Controlled FOUNDATION Fieldbus Two-Wire ... · Model 4081 T Remote Controlled FOUNDATION Fieldbus Two-Wire Conductivity Transmitter Instruction Manual PN 51-4081T/rev.D April

Credit Cards for U.S. Purchases Only.

The right people,the right answers,right now.

ON-LINE ORDERING NOW AVAILABLE ON OUR WEB SITEhttp://www.raihome.com

Emerson Process Management

Rosemount Analytical Inc.2400 Barranca ParkwayIrvine, CA 92606 USATel: (949) 757-8500Fax: (949) 474-7250

http://www.raihome.com

© Rosemount Analytical Inc. 2002