78
2014-10-29 REQUEST FOR TENDER WILDLIFE HEALTH CENTRE RFT # 47 (2014-09) ADDENDUM # 3 This addendum shall be incorporated into, and form part of RFT # 47 (2014-09) and take precedence over all requirements of the previously issued bid documents including plans. This addendum must be signed by the bidder (signing officer) in the appropriate space and must be attached to the Form for submission by the bidder. This Addendum consists of one (1) page and the documents listed below. 1. Attached is a copy of addendum # 3 issued by Diamond Schmitt Architects, dated 2014-10-29 2. Clarification to bidders - Opening of bids and bid submission requirements Bids received by the required deadline of Thursday, 2014-11-06 at 12:00 (noon local time), will be opened on 1230 hours (12:30 pm) on Friday 2014-11-07 at the Administrative Support Centre located at 361A Old Finch Avenue, Toronto ON M1B 5K7 Bidders who submit a bid by the required closing date Thursday 2014-11-06 1200 hours (noon) local time, will have until 12:00 (noon local time) Friday, 2014-11-07 to submit appendices II-VI as outlined in Article 7.0 of Section II Forms of the RFT. If Appendices II-VI are not submitted by 12:00 (noon local time) Friday, 2014-11-07, the respective bid will be considered incomplete. Receipt of the Addendum shall be acknowledged as part of your submission. The Board of Management of the Toronto Zoo reserves the right to reject any or all Quotations or to accept any quotation, should it deem such action to be in its interests. If you have any queries regarding this matter, please contact Mr. Peter Vasilopoulos, Supervisor, Purchasing & Supply, at 416-392-5916. Yours truly, Peter Vasilopoulos Supervisor, Purchasing & Supply I/we hereby acknowledge receipt of this addendum and make allowance in my bid. Signed (Must be Signing Officer of Firm) Name of Firm Date:

REQUEST FOR TENDER WILDLIFE HEALTH CENTRE … 3 WHC RFT 47.pdf · 2014-10-29 REQUEST FOR TENDER ... issued by the end of this week under Addendum No. 4. ... 1/A103 ASK-A103.1 .1 Add

Embed Size (px)

Citation preview

2014-10-29

REQUEST FOR TENDER

WILDLIFE HEALTH CENTRE

RFT # 47 (2014-09)

ADDENDUM # 3

This addendum shall be incorporated into, and form part of RFT # 47 (2014-09) and take precedence over all

requirements of the previously issued bid documents including plans. This addendum must be signed by the

bidder (signing officer) in the appropriate space and must be attached to the Form for submission by the

bidder. This Addendum consists of one (1) page and the documents listed below.

1. Attached is a copy of addendum # 3 issued by Diamond Schmitt Architects, dated 2014-10-29

2. Clarification to bidders - Opening of bids and bid submission requirements

Bids received by the required deadline of Thursday, 2014-11-06 at 12:00 (noon local time), will be

opened on 1230 hours (12:30 pm) on Friday 2014-11-07 at the Administrative Support Centre

located at 361A Old Finch Avenue, Toronto ON M1B 5K7

Bidders who submit a bid by the required closing date Thursday 2014-11-06 1200 hours (noon)

local time, will have until 12:00 (noon local time) Friday, 2014-11-07 to submit appendices II-VI as

outlined in Article 7.0 of Section II Forms of the RFT. If Appendices II-VI are not submitted by

12:00 (noon local time) Friday, 2014-11-07, the respective bid will be considered incomplete.

Receipt of the Addendum shall be acknowledged as part of your submission.

The Board of Management of the Toronto Zoo reserves the right to reject any or all Quotations or to accept

any quotation, should it deem such action to be in its interests.

If you have any queries regarding this matter, please contact Mr. Peter Vasilopoulos, Supervisor, Purchasing

& Supply, at 416-392-5916.

Yours truly,

Peter Vasilopoulos

Supervisor, Purchasing & Supply

I/we hereby acknowledge receipt of this addendum and make allowance in my bid.

Signed (Must be Signing Officer of Firm)

Name of Firm

Date:

c:\users\eric lucassen\desktop\toronto zoo wildlife health centre - addendum no. 3.docx

To: Toronto Zoo 361A Old Finch Avenue Scarborough, Ontario M1B 5K7

ADD. No: 3 Project No: 1029 File No: 6.2.2 Date: 2014-10-29 Attention: Leona Mitchell

Pages (with cover): 13 + 52 – 8.5”x11” pages,

10 – 11”x17” pages 2 – 36”x48” sheets

To Email: [email protected] Project: Toronto Zoo Wildlife Health Centre Delivery: by email

The following information supplements and/or supersedes the bid documents issued on 2014-09-30. This Addendum forms part of the contract documents and is to be read, interpreted and coordinated with all other parts. The cost of all contained herein is to be included in the contract sum. The following revisions supersede the information contained in the original drawings and specifications issued for the above-named project to the extent referenced and shall become part thereof. Acknowledge receipt of this Addendum by inserting its number and date on the Tender Form. Failure to do so may subject the bidder to disqualification. 1.0 Title 1.1 Addendum No. 3 2.0 References 2.1 Section 1 – Instruction to Bidders, RFT# 47, dated 2014-09-18 2.2 Section 2 – Forms, RFT# 47, dated 2014-09-18 2.3 Section 3 – General Conditions – RFT# 47, dated 2014-09-18 2.4 Section 4 – Volume 1 – Architectural, Structural, and Landscape Specifications and Schedules –

Issued for Bid, dated 2014-09-30 2.5 Section 4 – Volume 2 – Mechanical and Electrical Specifications – Issued for Bid, dated

2014-09-30 2.6 Section 5 – Toronto Zoo Wildlife Health Centre – Construction Drawings – Issued for Tender,

dated 2014-09-30 2.7 Section 6 – Available Project Information – Issued for Bid, dated 2014-09-30 2.8 Addendum No. 1 – dated 2014-10-07 2.9 Addendum No. 2 – dated 2014-10-14 2.10 H.H. Angus Mechanical Addendum No. 2, copy attached 2.11 PMA Landscape Architects Addendum No. 1, copy attached 3.0 Description

3.1 General 3.1.1 Bidders are to acknowledge receipt of this addendum by signing the addendum and attaching the

signed addendum to their Tender Submission.

3.1.2 Bidders are to submit the Appendix I – List of Subcontractors with their Tender submission at the stipulated closing date. Appendix I – List of Subcontractors is to include the Mechanical and Electrical Contractors and Subcontractors as added by this Addendum No. 3.

c:\users\eric lucassen\desktop\toronto zoo wildlife health centre - addendum no. 3.docx 2

3.1.3 An Electrical Addendum answering contractor questions in regards to electrical items will be

issued by the end of this week under Addendum No. 4.

3.2 Section 1 - Instruction to Bidders 3.2.1 Page 2 – Tenderer’s Checklist – Revise due date for Appendix I

.1 Revise deadline for “All pages in Appendix I from “(Due 24 hours after stipulated closing date)” to “(Due with Tender on stipulated closing date)”

3.2.2 Page 1 – Tenderer’s Check Sheet – Mailing Address: .1 Remove the following sentence under Mailing Address “The complete original tender package, including specifications completed in full, must be included.”

3.3 Section 2 - Forms 3.3.1 Form I – Appendix I – List of Subcontractors – Revised due date:

.1 Revise first sentence to “LIST OF SUBCONTRACTORS (Due with Tender on stipulated closing date) .2 Add attached List of Mechanical and Electrical Subcontractors “Appendix I Continued – List of Subcontractors”.

3.2.1 Form 4 – Agreement to Bond .1 Revise date listed halfway down page 24 for Tender Form from “2014-07-24” to “2014-09-18”.

3.4 Section 3 – General Conditions 3.5 Section 4 – Volume 1 and Volume 2 Specifications 3.5.1 Section 13 19 13 – Caging

.1 Revise contact information for Preapproved Subcontractor Spec-Dor, item .a Revise item 1.3.2.1.1.1 to “390 St-Louis St., Saint-Jean-sur-Richelieu, Quebec” .b Revise item 1.3.2.1.1.2 to “J3B 1Y4” .c Revise item 1.3.2.1.1.3 to “Phone: 450-359-1881” .d Revise item 1.3.2.1.1.4 to “Fax: 450-359-5809”

3.5.2 Section 07 54 19 – Polyvinyl-Chloride (PVC) Roofing .2 Add FM assembly number - item 1.5.4.2.3 “Assembly # 279194-0-0 – for John Manville product.” .4 Add acceptable product - item 2.2.1.6.3 – “Johns Manville PVC 60 mil / 60 Mil Min.” .6 Add acceptable product – item 2.2.2.4.3 “Johns Manville ENRG3CGF.” .7 Add acceptable product – item 2.2.3.2.2 “Johns Manville – ‘APP Base Sheet’” .8 Revise second sentence in item 2.2.5 to “Use “Sarnafil Multi-Purpose Sealant” by Sarnafil / “Carlisle Syntec- Universal Sealant” by Carlisle / “Single Ply Caulk - all purpose” by Johns Manville.”

c:\users\eric lucassen\desktop\toronto zoo wildlife health centre - addendum no. 3.docx 3

.6 Add acceptable product – item 2.2.6.1.2.1.2 “Johns Manville ‘Two Part Urethane insulation adhesive’”. .9 Add acceptable product – item 2.2.6.2.4.2 “Johns Manville ‘Two Part Urethane insulation adhesive’.”

3.5.3 Section 09 31 00 – Tiling .1 Revise item 3.7.1 to “Install waterproofing membrane in accordance with waterproofing membrane manufacturers written instructions, to wet service areas including; change room floors, vestibule floors, janitor room floors, and shower area walls and floors.”

3.5.4 Section 03 20 00 – Concrete Reinforcement .1 Delete item 2.1.6. .2 Delete item 2.1.7.

3.5.5 Section 03 30 00 – Cast-in-Place Concrete .1 Delete item 2.1.5. .2 Delete item 3.3.2.1.

3.5.6 Section 09 51 12 – Acoustical Wood Ceiling Panels – Item 2.1.1.8 – Acceptable Product: .1 Add acceptable product – “item 2.1.1.8.5 – Atkar Au.di, Groove AG19-316” .2 Add acceptable product – “item 2.1.1.8.6 – Norton Industries - Acoustiline Plank – 5/8” Ribs”

3.5.7 Section 05 50 00 – Metal Fabrications .1 Delete “item 1.2.1.13 – Vertical wood guard supports, primed.” .2 Delete “item 1.2.1.8 – Maintenance platforms and catwalks, hot dip galvanized.” .3 Add “item 1.2.1.16 – Stainless steel angle frames, frame types 29, 30, and 31. Refer to Door and Screen Schedule 1/A1004.”

3.5.8 Section 07 46 67 – Zinc Cladding and Flashing .1 Add acceptable Zinc Manufacturer “item 2.1.1.4 – Jarden Zinc Products.”

3.5.9 Section 07 46 67 – Zinc Cladding and Flashing – Item 2.2.7 – Fabric Underlayment and Slip Sheet .1 Add acceptable Product “item 2.2.7.4.3 – VaproShield, WrapShield.”

3.5.10 Section 07 27 00 – Air Barrier Systems – Item 2.3 .1 Add acceptable Product “item 2.3.5 – Acceptable Products: Henry ‘Blueskin VP 160’, and SRP AirOutshield SA 280’.”

3.5.6 Section 12 31 00 – Stainless Steel Casework – Item 2.1.1 – Acceptable manufacturers .1 Add acceptable manufacture – “item 2.1.1.5 – Bedcolab Ltd.”

3.5.7 Section 12 35 50 – Painted Steel Casework – Item 2.1.1 – Acceptable manufacturers .1 Add acceptable manufacture – “item 2.1.1.5 – Bedcolab Ltd.”

3.5.8 Section 12 35 26 – Modular Laboratory Casework System

c:\users\eric lucassen\desktop\toronto zoo wildlife health centre - addendum no. 3.docx 4

.1 Add acceptable manufacture – “item 2.1.4 – Bedcolab Ltd. ‘Symphony system.”

3.5.9 Section 01 21 00 – Allowances .1 Add missing dollar amount for radiation protection cash allowance under item 1.1.8.1.1 of “$65,500.00”.

3.5.10 Section 07 33 63 – Vegetated Roof Growing Medium and Planting .1 Revise item 2.4.1 to “Root barrier membrane: to prevent root growth to membrane level, minimum 0.8mm (40 mil) thick black high density polyethylene sheet specifically formulated and electronically tested, chemically neutral. Sheets of roof barrier membrane to overlap a minimum of 1500 mm and joints sealed with manufacturers recommended tape. .2 Revise item 2.4.1.1.1 to “Hydrotech Membrane Corporation ‘ROOT STOP HD 1.0mm’.”

3.6 Section 5 – Construction Drawings

Reference

Drawing (copy attached)

Comment

GR-1 Revise scale of drawing from “1:200” to “1:300”.

ER-1 Revise scale of drawing from “1:200” to “1:300”.

SS-1 Revise scale of drawing from “1:200” to “1:300”.

1/A010 ASK-A010.2 .1 Remove five (5) existing trees to be removed. These trees have already been relocated by the Toronto Zoo.

1/A100 ASK-A100.1 .1 Relocate elevator pit ladder as shown .2 Revise note “ELEVATOR PIT ACCESS LADDER” to “elevator pit access ladder, refer to detail 10/A605”

1/A102 ASK-A102.2 .1 Add one (1) additional overflow scupper and text “OVERFLOW SCUPPER, REFER TO DETAIL 11/A605”.

1/A102 ASK-A102.3 .1 Add five (5) additional overflow scuppers and text “OVERFLOW SCUPPER, REFER TO DETAIL 11/A605”.

1/A103 ASK-A103.1 .1 Add two (2) additional overflow scuppers and text “OVERFLOW SCUPPER, REFER TO DETAIL 11/A605”.

1/A103 ASK-A103.2 .1 Add one (1) additional overflow scuppers and text “OVERFLOW SCUPPER, REFER TO DETAIL 5/A605”.

c:\users\eric lucassen\desktop\toronto zoo wildlife health centre - addendum no. 3.docx 5

1/A103 ASK-A103.3 .1 Add one (1) additional overflow scuppers and text “OVERFLOW SCUPPER, REFER TO DETAIL 11/A605”. .2 Add one (1) additional overflow scuppers and text “OVERFLOW SCUPPER, REFER TO DETAIL 5/A605”.

1/A103 ASK-A103.4 .1 Add one (1) additional overflow scuppers and text “OVERFLOW SCUPPER, REFER TO DETAIL 5/A605”.

1/A103 ASK-A103.5 .1 Add two (2) additional overflow scuppers and text “OVERFLOW SCUPPER, REFER TO DETAIL 5/A605”.

3/A502 ASK-503.1 Revise note from: “GYPSUM BOARD BULKHEAD - 16MM GYPSUM BOARD - 92MM STEEL STUDS @ 400MM O.C.” to “GYPSUM OR CEMENT BOARD BULKHEAD - 16MM GYPSUM OR CEMENT BOARD, REFER TO ROOM FINISH SCHEDULE - 92MM STEEL STUDS @ 400MM O.C.”

A605 ASK-A605.1 Add pit ladder plan detail 10/A605.

A605 ASK-A605.2 Add pit ladder section detail 13/A605.

2/A853 ASK-A853.1 .1 Add one (1) caging food dish system to each room WH- 0301 Isolation Holding C, WH-0303 Isolation Holding A, WH-0401 Strong Holding C, and WH-0403 Strong Holding A for a total of four (4) caging food dish systems. .2 Add note “CAGING FOOD DISH SYSTEM, REFER TO DETAIL 6/A856”

A856 ASK-A856.1 ASK-A856.2 ASK-A856.3

Add plan and section details 6/A856 for Caging Food Dish System.

A903 ASK-A903.1 Add millwork detail of typical MDF wall base 51/A903.

A1000 ASK-A1000.1 Revise ULC Design Numbers for Wall Types “P2” and P7” .1 Revise UCL Design Number for Wall Type “P2” from “ULC DESIGN U419” to “ULC DESIGN W453” .2 Revise UCL Design Number for Wall Type “P7” from “ULC DESIGN U419” to “ULC DESIGN W453”

A1003 CU-1041 – VESTIBULE .1 Revise BASE from “MDF” to “PFT”

c:\users\eric lucassen\desktop\toronto zoo wildlife health centre - addendum no. 3.docx 6

WH-1005 – RADIOLOGY .1 Revise CEILING from “ACT / EXP / CB” to “ACT / EXP / GB” WH-1019 – NIGHT ROOM .1 Revise CEILING from “ACT / EXP / CB” to “ACT / EXP / GB” WH-2002 – GAMETE LAB .1 Revise CEILING from “ACT / EXP / CB” to “ACT / EXP / GB” WH-2004 – STERILE ROOM .1 Revise CEILING from “ACT / EXP / CB” to “ACT / EXP / GB” WH-2007 – ENDO 2 ASSAY LAB .1 Revise CEILING from “ACT / EXP / CB” to “ACT / EXP / GB” WH-2013 – PATHOLOGIST LAB OFFICE .1 Revise CEILING from “ACT / EXP / CB” to “ACT / EXP / GB” WH-2014 – PARTNER OFFICE .1 Revise CEILING from “ACT / EXP / CB” to “ACT / EXP / GB” WH-2015 – RESEARCH/ EXTERN OFFICE .1 Revise CEILING from “ACT / EXP / CB” to “ACT / EXP / GB” WH-2017 – PATHOLOGIST LAB OFFICE .1 Revise CEILING from “ACT / EXP / CB” to “ACT / EXP / GB” WH-2018 – REPRODUCTIVE BIOLOGIST OFFICE .1 Revise CEILING from “ACT / EXP / CB” to “ACT / EXP / GB”

3.7 Section 6 – Available Project Information

c:\users\eric lucassen\desktop\toronto zoo wildlife health centre - addendum no. 3.docx 7

3.8 Response to Bidders’ Questions – Bid Document and Architectural 3.8.1 Question: Spec Section 01 21 00; indicates a Cash Allowance for radiation protection, but

with no value, please provide allowance amount. Answer: Please allow the amount of $65,500.00 + HST. This number has been added to the specification section 01 21 00 by this Addendum No. 3.

3.8.2 Question: The room finish schedule indicates MDF base for several rooms. Specifications do not indicate the height and type of the base. Could you please clarify? Answer: A millwork section detail of the MDF base has been added by this Addendum No. 3. Please refer to attached sketch ASK-A903.1

3.8.3 Question: For the showers in rooms WH-1022, WH-1023 & WH-1045A on drawing A800, is there a shower curb? Answer: No, these are to be accessible showers and therefore don’t have a curb at the entrance. The floor is sloped to the drain as per the slab edge drawing.

3.8.4 Question: Tiling section 09 31 00, item 2.4.1 Waterproofing membrane. Could you please clarify if waterproofing membrane is to be install under porcelain tiles floors and walls in room WH-1022, WH-1023 & WH-1045A? Answer: Install waterproofing membrane to wet service areas including; change room floors, vestibule floors, janitor room floors, and shower area walls and floors. Refer to item 3.5.3 above.

3.8.5 Question: Roller Shades (12 24 13) are to be installed in the upper glazing sections of the Conference Room 1032 and Surgery 1003, Treatment 1004 and Radiology 1005. The Specification notes two different types, a blackout and a sunscreen shade, but the drawings only mention roller shades not which type or if it is a dual shade required. Could you please clarify? Answer: Refer to the Room Finish Schedule on A1003. Rooms SURGERY WH-1003, TREATMENT WH-1004, and CONFERENCE WH-1032 are to have interior roller window sun shades. Room RADIOLOGY WH-1005 is to have the interior roller window room darkening (black-out) shades.

3.8.6 Question: Certain rooms (they are WH - 1002, -1005, -1019, -1029, -1030, -1031, -1032, - 1033, -1034, -1035, -1036, -1037, -1038, -2002, -2004, -2007, -2013, -2014, - 2015, -2017, -2018, and -2019) have bulkheads, that accordingly must be built with cement board, according to the room finish schedule; however, detail 3/A502 that is typical for all the bulkheads, indicates that they must be built with 16 mm gypsum board. Could you please clarify which product is to be used? Answer: The scheduled CEILING Cement Board (CB) for rooms; WH-1005, WH-1019, WH-2002, WH-2004, WH-2007, WH-2013, WH-2014, WH-2015, WH-2017, and WH-2018 have been changed to Gypsum Board (GB) by this Addendum No. 3. The note on detail 3/A502 calling out “16mm gypsum board” has been revised to call out “16mm gypsum board or cement board, refer to room finish schedule” by this Addendum No. 3.

c:\users\eric lucassen\desktop\toronto zoo wildlife health centre - addendum no. 3.docx 8

3.8.7 Question: Please provide the location on the drawings and detail for the maintenance platform and catwalk as indicated in section 05 50 00 paragraph 1.2.8. Section 02/A505 indicate a sloped structural composite deck. Please clarify. Answer: The floor structure for CATWALK WH-2016 is covered under the structural drawings, therefore item 1.2.8 – Maintenance platforms and caltwalks is not required for this building. Item 1.2.8 – Maintenance Platforms and Caltwalks has been deleted from specification section 05 50 00 by this Addendum No. 3.

3.8.8 Question: Please provide the location on the drawings of the Unistrut channels (UC) complete with stainless steel bird screen as indicated in section 05 50 00 paragraph 1.2.9. Answer: Rooms PLAIN WH-0500 and ICU WH-1021 have ‘UC’ unistrut channels and ‘BS’ bird screen ceilings. Please refer to the Room Finish Schedule on A1003 and drawing 1/A201 - Level 1 – Ground Floor – Reflected Ceiling Plan.

3.8.9 Question: Please provide the location on the drawings of the Vertical wood guards supports as indicated in section 05 50 00 paragraph 1.2.13. Answer: There are no vertical wood guard supports required on this project. Item 1.2.13 – Vertical wood guard supports has been deleted from specification section 05 50 00 by this Addendum No. 3.

3.8.10 Question: Please provide a detail for the Pit ladder, complete with slip resistant step surfaces as indicated in section 05 50 00 paragraph 1.2.15.2. Answer: Plan and section details for the pit ladder have been added to the construction set by this Addendum No. 3. Refer to attached sketches ASK-A605.1 and ASK-A605.2.

3.8.11 Question: Spec section 096700, 2.2 mentions HPEF paint. In same paragraph in subsection .1 Epoxy Paint (EPOXY PT) is mentioned. The room finish schedule in drawing A1003 has some walls as HPEF and others as EPOXY PT. Please advise whether these two terms mean the same thing or are they different. Answer: The two terms refer to two different products / systems. High performance epoxy finish for walls (HPEF) is specified under section 09 67 00. Epoxy Paint finish for walls in specified under section 09 67 00, as noted under specification section 09 67 00, item 1.3.1.1.

3.8.12 Questions: Section II – Forms, item 1.3. To our knowledge, Plumbers and Electricians are the only trades that require licensing by City of Toronto. We are not aware of license requirements for General Contractors. Please clarify and/or revise. Answer: The General Contractor is not required to provide a license from the City of Toronto.

3.8.13 Question: As per ITB 20.2, Contractor shall arrange and pay consultant for As Build CAD files. Please provide consultant cost. Answer: Section I, item 20.2 states that the “Contractor shall arrange and pay for the Consultant to transfer the marked up prints to CADD media.” Since it is not

c:\users\eric lucassen\desktop\toronto zoo wildlife health centre - addendum no. 3.docx 9

possible to know the extent of the contractors marked up prints or required modification to the original drawings, we will not be issuing a dollar amount for this item. The work involved by the consultant transferring the marked up prints to CADD will be billed on an hourly basis. Contractor should carry an appropriate amount for this in there tender submission.

3.8.14 Question: There are different dates on Tender Form and Agreement to Bond. About half way down the page it says the following, “the Tenderer to you by Tender Form dated 2014-07-24” is this date correct? The date on the top right corner of the form is 2014-09-18 and the issue date on the request for tender is 2014-09-30. Please clarify. Answer: The date listed half way down page 24 in Section II – Forms should be revised to 2014-09-18. This date has been corrected by this Addendum No. 3.

3.8.15 Question: Please clarify if we have to submit signed page of addenda only or entire documents? Answer: Signed page of addenda only is required and acknowledgement on Section II - Forms, article 4.0.

3.8.16 Question: Due to request from our sub-trades, please consider one week extension to the closing date. With this extension we will have a better coverage from our trades and ultimately better price which will be beneficial to the owner. Answer: Closing date will not be extended.

3.8.17 Question: Sheet A1003 – Please provide specifications regarding 3 Stainless Steel Frames listed on the doors schedule. (1003-3-sc, 1004-2-sc, 1005-2-sc). Please confirm Stainless Steel type and finish. Answer: Refer to specification section 05 50 00 - Metal Fabrications for the stainless steel requirements. Note that these stainless steel frames (frame types 29, 30, and 31) have been added to specification section 05 50 00 – Metal Fabrications by this Addendum No. 3.

3.8.18 Question: Is it possible to receive all the Tender Form and all other forms needed for the deposit in Word or Excel format? Answer: No, documents cannot be provided in Word or Excel format.

3.8.19 Question: RFT document, Section I - INSTRUCTIONS TO BIDDERS, page 1 of 21, last paragraph, "The complete original tender package, including specifications completed in full, must be included." Do you mean that we have to put a full copy of the specs in our Tender document? If so, it would be a very large document and we don't see the point of sending the specifications back to you and including them in our Tender package. Could you please clarify? Answer: Delete – sentence under Mailing Adress, page 1 of 21 of Instruction to Bidders "The complete original tender package, including specifications completed in full, must be included." Bidders are to review the Instruction to Bidders including Tender checklist, page

c:\users\eric lucassen\desktop\toronto zoo wildlife health centre - addendum no. 3.docx 10

2 of 21 and govern themselves accordingly for submission requirements.

3.9 Response to Bidders’ Questions – Structural 3.9.1 Question: Sheet S001. Could you please clarify what areas should be considered as

animal accessible in order to allow for the proper quantity of each concrete mix? Answer: Animal accessible areas are those areas accessible by animals as shown on the Architectural Drawings. Note that concrete floor slabs to receive protective finish (refer S001, Table 1 for concrete exposure class) also refer to Architectural Documents. These areas are; all Small Holding and Keeper Areas (indoor and outdoor, Pool Holding and Keeper Areas, Plain Area, All Strong Holding and Keeper Areas, all Isolation Holding and Keeper Areas, all Hoofstock Holding and Keeper Areas (indoor and outdoor), and Corridors WH-1059, WH-1043, WH- 1060, and WH-1053.

3.9.2 Question: On sheet S01, should slab on grade mix #4 comments read wiremesh reinforced slabs instead of unreinforced slab? We did not find unreinforced slabs on grade. Answer: Yes should read WIREMESH REINFORCED. Note slab on grade schedule on S200, slab type SG1 should be mesh reinforced 152x152 MW18.7 x MW18.7 WWF as SG3.

3.9.3 Question: Where should steel fibers described in section 03 20 00 2.1.6 and 2.1.7 be used?Answer: No locations require steel fibers. Delete specification section 03 20 00, item 2.1.6 and 2.1.7

3.9.4 Question: Which concrete mixes are to use Shrinkage Control Fibres specified in section 03 30 00 2.1.5? Answer: No requirement for use of shrink control fibers on this project. Delete specification section 03 30 00, item 2.1.5.

3.9.5 Question: Section 03 30 00 3.3.2.1 specifies wet cure for C-XL concrete but there is no C- XL concrete specified in Table 1 on S001. Could you please clarify? Answer: There is no C-XL concrete on this project. Delete specification section 03 30 00, item 3.3.2.1.

3.9.6 Question: On A1000, the vertical reinforcements for the foundation masonry walls are indicated as “Reinforced as per structural drawings”. If we cross-reference this with the drawings and schedule on S200, when there are two withes, only the inner one appears to be reinforced. Is this correct? Answer: Correct, inner wythe only reinforced. All cells below grade to be fully grouted. Outer wythe to be solid block. Refer details eg drawing 1, 2, 6, 8, etc… on S401 that typically shows reinforcement to inner wythe only.

3.9.7 Question: Drawing S012, Detail PC30. Please specify dimensions and locations for both angle on each side of the steel beam to support hollow core slab. Answer: We understand you are referring to details PC28, PC29, PC30. These are

c:\users\eric lucassen\desktop\toronto zoo wildlife health centre - addendum no. 3.docx 11

typical details should the need apply but are not used. The lintel schedule on S300 does not specify the lintel types shown in PC28 and PC29. PC30 is not used. Refer to S210 and S420 etc… for requirement generally.

3.9.8 Question: Drawing S401 – Could you please provide the missing reinforcement details for combined footing on grid C-8 and C-8b as well as footing at grid C1-2? Answer: For conbined footing C-8 and C-8b provide the following: 15-25 T&B longitudinal, 15@100 ties. For column foundation at grid C1-2 provide: 7-15HH (same as E1-6).

3.9.9 Question: What is the extent of the mesh reinforcing for the concrete topping required on detail 17/S420? Other nearby details such as 10, 11, and 12 on S420 do not show any mesh. Could you please clarify? Answer: For all concrete topping on pre-cast concrete slabs provide mesh reinforcing as shown on plan. If none shown on plan then none required. (applies to detail 17/S420 and all other related / similar details on S420, S421, S011 and A012)

3.9.10 Question: Should I used the block wall reif. For all the walls based on thickness of wall? Because it is very inconclusive. Answer: Vertical reinforcement for block masonry walls shall be as per Masonry Wall Schedule on S200. Requirements sometimes vary for the same wall thickness depending on the function and requirement of the particular wall. Please refer to the schedule on S200.

3.9.11 Question: Is there any reinf. For parapet or should it match the same reinf. As wall? (please refer to section 15/S420). Answer: For reinforcement to the parapet wall in 15/S420 continue the same reinforcement from the wall below, i.e. as per 15/S420 refers follow the S200 Masonry Wall Schedule or min of 15@200V with cells fully grouted. For all parapet masonry walls all cells shall be fully grouted and reinforcement shall be the minimum of that required in the S200 Masonry Wall Schedule or as otherwise noted. Also refer to S011 and S012 for typical details.

3.9.12 Question: Pier reinforcement is missing on S300. I see reinf. For Piers on drawing S401 on Section 20/S401 & 10/S401. Answer: For vertical and tie reinforcement for footing caps (i.e. for the cap schedule provided in S300) refer to typical detail CF3/S010.

3.9.13 Question: Should I follow the details for bond beam given on S402 of it is only applicable to the walls shown on that drawing. Answer: The bond beam shown on S402 is only applicable to the walls shown on that drawing.

3.10 Response to Bidders’ Questions – Civil

c:\users\eric lucassen\desktop\toronto zoo wildlife health centre - addendum no. 3.docx 12

3.10.1 Question: Reference drawings - GR-1, ER-1, SS-1; The scale on the civil drawings appears to be incorrect, when scaled at 1:200, they do not line up with drawings from other disciplines, and the service conduits shown on sheet SS-1 are much shorter than the length indicated next to each one. Please confirm which drawings are at the correct scale and which should be scaled differently. Answer: Please revise the scale for drawings GR-1, ER-1, and SS-1 from “1:200” to “1:300”. This has been revised in this Addendum No. 3.

3.10.2 Question: Drawing SS-1. Please provide specifications, details and top or bottom elevation of the 20 m³ storm water retention tank shown on the Site Servicing Plan. Answer: 3mx5mx1.3m 20m3 STORAGE TANK 200mm N INV. 139.61 200mm OVERSPILL S INV. 140.56 Reg-U-Flo 8.5 SH VORTEX VALVE ORIFICE S INV. 139.56 This is your invert of the tank. +1.3m = 140.86m That’s the inside of the top of the tank.

3.11 Response to Bidders’ Questions – Mechanical 3.11.1 Question: On Mechanical drawing M310, outlets were shown to connect to a structural

beam. I did not see any spec for articulating arms or ceiling columns on the architectural so we are not quite sure how they will install these. They do mention if they are ceiling outlets so the ones below are questionable to me. We also looked at the architectural plans and they did not show anything. Please advise.Answer: Refer to architectural reflected ceiling plan drawing 1/A201 and section detail 2/A501 for the identified beam.

3.11.2 Question: The ductwork shown on dwg. M420, grid 8 to 10, G to j appears to be in a 12 ft. high ceiling space without access. Is this duct in an exposed or concealed area?Answer: Rooms WH-1003 Surgery and WH-1004 Treatment are tall spaces with clerestory windows. The ductwork in these rooms are located at the ceiling level. Please refer to the architectural reflected ceiling plans and building sections to understand these spaces.

3.11.3 Question: In Optional Price No.1 document OP-SK-1.8 under heading "Mechanical Revisions" it states that "buried plumbing services are to be installed as per plans (except for lines serving deleted areas). On drawing M200 near gridline N between gridlines 3 - 5 a 12" storm sewer is indicated. If the Optional Price No.1 is selected, the 12" storm sewer will not be able to be installed in the location indicated due to the existing Invertebrate building not being demolished. Please indicate optional location of 12" Storm sewer so that it will be able to pick up all items between gridlines A-K and 2-9. Answer: Route the proposed 12” dia. storm line around the “to remain Invertebrate House” and connect to civil service in same location.

c:\users\eric lucassen\desktop\toronto zoo wildlife health centre - addendum no. 3.docx 13

3.11.4 Question: Please provide specifications for ME-10, RO System. Answer: Refer to attached H.H. Angus Mechanical Addendum No. 2.

3.11.5 Question: Please provide specifications for in-room Humidifiers ME-11A to ME-11G Answer: Refer to attached H.H. Angus Mechanical Addendum No. 2.

3.11.6 Question: Please provide pump schedule and specification. Answer: Refer to attached H.H. Angus Mechanical Addendum No. 2.

3.11.7 Question: They are using 09 code but code is only for healthcare facilities. Please advise. (Section 22 63 13, Clause 1.3.2.1) Answer: Refer to attached H.H. Angus Mechanical Addendum No. 2.

3.11.8 Question: On page 7 of the ductwork specification, Execution 3.1.1.1,.2 and .3 indicate that all the ductwork needs to be insulated. Since the 1st floor has a large area that is exposed without a ceiling the cost of insulating this duct is extensive. Please confirm that all this duct requires insulation. Answer: Refer to attached H.H. Angus Mechanical Addendum No. 2.

End of Addendum

Per: Eric Lucassen

Copied: Jon Soules DSAI File

2014-09-18 RFT # 47 (2014-09) - WILDLIFE HEALTH CENTRE SECTION II - FORMS Page 1 of 2 FORM 1 Appendix I - Continued LIST OF SUBCONTRACTORS (Must be provided with Tender on stipulated closing date.) The tenderer proposes to sublet the following portions of the Work to the persons firms or corporations indicated (the Contractor is responsible for all pricing with all subcontractors). The Tenderer submits that in proposing the under mentioned subcontractors, the tenderer has consulted each and have ascertained to our completed satisfaction that those names are fully acquainted with the extent and nature of the work and that they will execute their work with the requirements of the contract documents. TRADE NAME/ADDRESS TELEPHONE LICENCE #S

20/21/22/23/25 Mechanical Contractor – Prequalified

20 – Sheet Metal

20 - Insulation

20 – Mechanical Wiring

21 – Fire Protection

21 – Sprinklers

22 – Plumbing and Drainage

22 – Medical Gas

23 – Mechanical Piping

2014-09-18 RFT # 47 (2014-09) - WILDLIFE HEALTH CENTRE SECTION II - FORMS Page 2 of 2

23 – Mechanical Controls

26/27/28/ Electrical Contractor - Prequalified

28 – Addressable Fire Alarm

OTHER (LIST)**

* Insert “Own Forces” for every portion of the Work which Tenderer will be performing without

a subcontractor. See Note following clause 39 of the General Conditions regarding non-union sub-contractors.

** Tenderer must specify nature of work for each “Other” sub-contract.

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx

To: Toronto Zoo

361A Old Finch Avenue Scarborough, Ontario M1B 5K7

ADD. No: Mechanical Addendum #2

Project No: 1029

File No: 6.2.2

Date:

Attention: Leona Mitchell

Pages (with cover): 1 +

To Email: [email protected]

Project: Toronto Zoo Wildlife Health Centre Delivery: by email

The following information supplements and/or supersedes the bid documents issued on 2014-09-30. This Addendum forms part of the contract documents and is to be read, interpreted and coordinated with all other parts. The cost of

all contained herein is to be included in the contract sum. The following revisions supersede the information contained in the original

drawings and specifications issued for the above-named project to the extent referenced and shall become part thereof.

Acknowledge receipt of this Addendum by inserting its number and date on the Tender Form. Failure to do so may subject the

bidder to disqualification. Title

H.H. Angus Mechanical Addendum #2 QUESTIONS

1.0 1.03 Would a Condenser water filtration package, manufactured by ARKAL/Pep Filters be

allowed for this project? H.H. Angus has approved this product in the past.

Answer: Yes. This product is acceptable.

2.0 1.04 The Cooling Tower schedule (ME‐07) shows 56.7 l/s (900 GPM) whereas the spec

(23.65.13 p.2)shows 900 GPM per cell X 2 cells‐is it 900 GPM or 1800 GPM ?

Answer: The Tower flow is 900gpm total, 450gpm per cell.

3.0 AGSS line showing copper line (AGSS and Vac are using the same system) but on the

execution spec, they wanted to connect to a stainless steel AGSS duct. (Section 22 63 13,

Clause 3.10) Please advise. AGSS line showing copper line (AGSS and Vac are using the

same system) but on the execution spec, they wanted to connect to a stainless steel

AGSS duct. (Section 22 63 13, Clause 3.10) Please advise.

Answer: No connection to the exhaust duct is necessary. The piping will tie into the Medical VAC

unit shown on detail 14 on dwg. M-013

SPECIFICATIONS

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 2

1.0 Mechanical Specification Section 20 07 16 Ductwork Insulation

1.1 Part 2 Products, 2.4 Field applied Finishes,

a) Add .4

.4 PVC (Polyvinyl Chloride) finish jacket:

.1 minimum 20 mil thickness with permeability not more than 0.09 perms,

.2 flexible flat-sheet,

.3 pressure sensitive, colour matching vinyl tape.

Standard of Acceptance

• VentureClad 1577CW – White

1.2 Part 3 Execution, 3.1 Insulation Limits, .1 Externally insulate air handling system components:

a) Add .12

.12 Supply duct silencers.

1.3 Part 3 Execution, 3.1 Insulation Limits, .2 Externally insulate ductwork located outdoors:

a) Add .6

.6 Supply, return and exhaust duct silencers.

1.4 Part 3 Execution, 3.9 Insulating and finishes Tables, Table 1: Ductwork and Plenum Insulation

Type and Thickness mm(in.), Under Equipment description, Rectangular – Outdoor –Supply:

a) Revise Insulation thickness to read:

Two layers each 38mm(1-1/2in.)

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 3

1.5 Part 3 Execution, 3.9 Insulating and finishes Tables, Table 1: Ductwork and Plenum Insulation

Type and Thickness mm(in.), Under Equipment description, Rectangular – Outdoor – Return, and Rectangular – Outdoor – Exhaust:

a) Revise Insulation thickness to read:

Two layers each 38mm(1-1/2in.)

1.6 Part 3 Execution, 3.9 Insulating and finishes Tables, Table 1: Ductwork and Plenum Insulation

Type and Thickness mm(in.), Under Equipment description, Round – Outdoor:

a) Revise Insulation thickness to read:

Two layers each 38mm(1-1/2in.)

1.7 Part 3 Execution, 3.9 Insulating and finishes Tables, Table 1: Ductwork Insulation Protective

Finishes, Under Location: Exposed, Weather Exposure: Indoors, System/Space: Services rooms and Publics spaces:

a) Revise finishes to read:

PVC finish - VentureClad – 1577CW White

Mechanical Specification Section 20 07 16 Ductwork Insulation

2.0 Mechanical Specification Section 20 05 23 Valves

2.1 Part 1, General, 1.3 Quality and Equivalence, under .2.2 for gate, globe, angle, and check valves,

under Standard of Acceptance, add the following: (a) Beric

2.2 Part 1 General, 1.3 Quality and Equivalence, under .2.5 for butterfly valves, under Standard of

Acceptance, add the following:

(a) MAS (b) WKM

3.0 Mechanical Specification Section 20 07 19 Piping Insulation

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 4

3.1 Part 3 Execution, 3.17 Insulating and finishes Tables, Table 4: Piping Insulation Protective

Finishes, Under Location: Exposed, Weather Exposure: Indoors, Piping System: All except steam over 860 kPa (125 psig).

a) Revise finish to read:

PVC - White

3.2 Part 3 Execution, 3.17 Insulating and finishes Tables, Table 4: Piping Insulation Protective

Finishes, Under Location: Exposed, Weather Exposure: Indoors – Painted piping, Piping System: All

a) Revise finish to read:

PVC – Colour to match painted colour

4.0 Mechanical Specification Section 22 42 13 Plumbing Fixtures and Trim

4.1 Remove item 2.9 – Laundry Sink Type “S-6”

5.0 Mechanical Specification Section 23 21 23 – Pumps – Heating and Cooling

5.1 This specification section is added.

6.0 Mechanical Specification Section 23 33 14 Dampers Operating

6.1 Part 2 Products, 2.1 Multi-leaf dampers, Under .4 Construction add:

Standard of Acceptance

● For Fresh Air and Exhaust dampers – Tamco Series 9000 BF ● For Recirculation Dampers - Tamco series 1000

7.0 Mechanical Specification Section 23 33 63 Louvres

7.1 Part 2 Products, 2.1 Louvres: Under Standard of Acceptance add:

(a) Ruskin

8.0 Mechanical Specification Section 23 37 13 Grilles, Register, and Diffusers

8.1 Part 2 Products, 2.2 Type designations: Under Standard of Acceptance add:

(b) Titus

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 5

8.2 Part 2 Products, 2.3 Supply Registers:

(a) Delete .3 - opposed blade dampers (OPD) with concealed manual operator, Note: opposed blade dampers are required for each duct branch and for each diffuser/register at the diffuser branch take-off. They are not to be installed in the diffuser/register neck

8.3 Part 2 Products, 2.4 Return and exhaust grilles:

(a) Delete .3 - opposed blade dampers (OPD) with concealed manual operator, Note: opposed blade dampers are required for each duct branch and for each grille at the grille branch take-off. They are not to be installed in the grille neck.

8.4 Part 3 Execution, 3.3 Installation of grilles and registers, 3.4 Installation of diffusers.

(b) Delete .2 - (Note: this deletes the requirement for equalizing grids in diffuser necks) Delete .3 - (Note: this deletes the requirement for volume extractors - opposed blade dampers are required for each duct branch and for each diffuser at the diffuser branch take-off. They are not to be installed in the diffuser neck.

9.0 Mechanical Specification Section 23 41 13 Packaged Hot Water Boilers – Condensing

(incorrectly numbered the same as the filter section) 9.1 Renumber this spec section from 21 41 13 to 23 52 16.

9.2 Part 2 Products, 2.1 General, under .1 Standard of Acceptance, add the following

Standard of Acceptance ° Cleaverbrooks ° Aerco ° Fulton - Endura

9.3 Part 2 Products, 2.2 Boiler Requirements,

(a) under .1 Design conditions, revise the following to read: .2 Leaving water temperature: 71.1C

.3 Return water temperature: 41°C

.4 Capacity Output (each boiler): 400kW

(b) under .2 Fuel: Natural gas with gas supply pressure: 14 kPa (2 psig), add the following: .1 Provide pressure reducing valve to provide 14” gas inlet pressure.

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 6

9.4 Part 2 Products, 2.3 Boiler, under .2 Boiler Trim, Add the following: .1 Condensate neutralizing treatment kit

10.0 Mechanical Specification Section 23 51 23 Gas Vents

10.1 This specification section is added.

11.0 Mechanical Specification Section 23 57 13 Heat Exchangers

11.1 Part 2 Products, 2.1 Plate and Heat Exchangers, .1 Construction, add the following to Standard of

Acceptance:

Standard of Acceptance ° FlowFab FF Series

12.0 Mechanical Specification Section 23 64 16 Packaged Chiller – Centrifugal

12.1 Part 2 Products, 2.1 General, .2 Packaged electric drive centrifugal machine with dual

frictionless magnetic drive compressors, evaporator, water cooled condenser, motor, disconnect switch, adjustable frequency drive (AFD) rated-motor and AFD drive, harmonic filter unit, controls, piping, wiring, and refrigerant,

(a) Revise .2 to read:

.2 Packaged electric drive centrifugal machine with Two or More frictionless Danfoss-Turbocor magnetic drive compressors, evaporator, water cooled condenser, motor, disconnect switch, adjustable frequency drive (AFD) rated-motor and AFD drive, harmonic filter unit, controls, piping, wiring, and refrigerant.

(b) add to Standard of Acceptance,

Standard of Acceptance ° Artic Cool – EFI ° SMARDT – Applied Energy

12.2 Part 2 Products, 2.2 Design Criteria, add .2,

.2 NPLV: 0.357 kW/Ton

12.3 Part 2 Products, 2.3 Compressors, .1 Compressor

(a) revise .1 to read:

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 7

.1 Danfoss-Turbocor electric frictionless magnetic bearing motor driven centrifugal type, with two stages of Compression.

(b) Add ..4 and .5

.4 Each Compressor shall be installed with Individual Suction, Discharge and Motor

Cooling Refrigerant line isolation valves. Chillers without discharge line isolation valves that rely on non-return valves in discharge line for compressor removal shall not be accepted.

.5 Each Compressor shall have mechanical and Electrical Isolation to allow the chiller to operate when a compressor is removed from the machine. Each Compressor shall have an individual disconnect switch.

12.4 Part 2 Products, 4.1 Condenser and Evaporator

(a) Add.4, .5, .6, and .7

.4 Shall be designed, constructed, tested and stamped in accordance with the requirements of the ASME Code, Section VIII Code Case 1518-5. The refrigerant side of each vessel shall bear the ASME Code Stamp

.5 Water Circuit shall be designed for a minimum of 1000kPa (145psig) or as specified.

.6 The Evaporator shall be provided with Spring loaded Re-seating type pressure relief Valves according to ASHRAE-15. Condenser shall be provided with Dual relief Valves equipped with a transfer valve so one valve can be removed for testing or replacement without loss of refrigerant.

.7 Liquid Level Controls

.1 Control of refrigerant flow shall utilize a single or Multiple 6000 Step Electronic Expansion Valve (EXV) top operate within the full range from full load to the lowest loading capacity of the chiller. The EXV liquid line shall have a sight glass with moisture indicator and temperature sensor connected to the control system for validating sub-cooling

.2 Condenser shall be provided with a capacitive type liquid level transducer with a resolution of not less than 1024 discrete steps. Condenser liquid level measurement shall be used in EXV control algorithm .Chillers without direct level measurement are prohibited due to possible over heating damage.

12.5 Part 2 Products, 4.2 Chiller control panel, .5 Key Pad Operation

(a) Add (l)

(l) Chiller documentation shall be viewable in pdf format

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 8

12.6 Part 2 Products, 4.2 Chiller control panel, add .9 Chiller Control panels shall have the following

features:

.9 Chiller Control panels shall have the following features .1 Built in stepper motor controls for EXV’s

.2 Chiller control software shall employ an active fault avoidance algorithm to reduce chiller capacity and / or power level in the case of the chiller approaching within 10% of any trip limit value such as suction pressure, discharge pressure , chiller amp limit, leaving chilled water temp etc.

.3 Multiple compressor staging algorithm shall operate at the optimized power curve of each compressor simultaneously, and shall reset automatically every second during operation. Compressor staging methods that operate using simple incremental percent of demand shall not be accepted.

.4 Alarm Screens shall be capable of filtering faults into specific categories such as compressor, chiller and system faults in order to provide rapid diagnosis and separation of failure modes.

.5 Chiller control panel user interface shall be capable of remote control via an internet connection, without the use of any third party gateway device or an additional hardware or software.

.6 Real time chiller control processor shall be capable of e-mailing a pre-defined list of recipients, should a fault occur. Emails shall include details of fault, possible reason for fault, attachment of monthly data logof 195 or more compressor and chiller variables at a minimum of 30 second intervals and indication of fault severity.

.7 Continuous data logging for operational trending and bin analysis shall be exportable to CSV format.

13.0 Mechanical Specification Section 23 65 13 Cooling Towers

13.1 Part 2 Products, 2.1 General, .1 Provide a factory assembled cooling tower located outdoors for

summer/winter operation, add the following to Standard of Acceptance:

Standard of Acceptance ° The Cooling Tower Company/ Abbotts air

13.2 Part 2 Products, 2.3 Induced draft, crossflow or counterflow, steel tower, .1 Construction,

(a) revise .2 to read:

.2 manufactured from 304L Stainless Steel frames, angles, channels, and metal panels,

(b) revise .8 and .9 to read:

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 9

.8 304L Stainless Steel exterior surfaces, and

.9 PVC or 304L Stainless Steel louvers with stainless steel wire mesh inlets.

13.3 Part 2 Products, 2.3 Induced draft, crossflow or counterflow, steel tower, .3 Fan Motor, add .3:

.3 Fan motors to be IP56 construction, VFD rated, Nema MG1 Part 31 nameplated (motor

winding insulation suitable to withstand 2000v spikes (3 ph/575v motors), c/w shaft grounding.

13.4 Part 2 Products, add 2.8 Adjustable frequency drives (AFDs)(related Section 20 05 14)

2.8 Adjustable frequency drives (AFDs)(related Section 20 05 14)

.1 Adjustable frequency drives shall be by same supplier as AFDs for the rest of the

project. .2 Provide one AFD per cooling tower cell (min. two). .3 AFDs larger than 15 Hp. to be c/w input Harmonic filter .4 AFD to be c/w output dVdT filter. .5 AFD to be c/w 3 contactor across the line bypass. .6 Wiring from AFD to motor :

.1 liquid tight, flexible metal conduit and cable to be specifically manufactured for this duty,

.2 voltage rating: nominal 1000 V, and voltage spikes to 2000 V,

.3 each motor wiring to be in separate conduit. Do not combine control wiring with motor wiring.

.4 3 phase and 3 ground conductors. Standard of Acceptance

NEXANS - Drive Rx - Variable speed drive cable LAPP USA - OLFLEX® VFD SLIM; Severe duty power cable for AFD drives ShawCor - Shawflex VFD cable Rockbestos-Suprenant Cable - EXANE - VFD sheathed armoured power

cable.

13.5 Part 2 Products, add 2.9 TowerTech Cooling Tower Option.

2.9 TowerTech Cooling Tower Option

.1 TowerTech Cooling Tower to be factory-assembled, forced draft, counter-flow, modular cooling tower. Unit shall be a Tower Tech Inc. Model TTXL-i31975. The tower’s principal construction shall be of pultruded Fiberglass Reinforced Polyester (FRP) and must have a flame spread rating less than 25 or a flammability coefficient of 94-V0.

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 10

.2 Design Loading

.1 Tower shell and substructure (support legs) shall be designed to withstand a wind load equivalent to 150 MPH and be able to resist seismic forces classified under Zones 1-4. Spring isolation shall not be required.

.3 Construction

.1 The cold water basin and the tower casing shall be constructed of pultruded Fiberglass Reinforced Polyester (FRP) with UV inhibitors. FRP shall have a minimum thickness of ¼” and a minimum density of 0.07 lb/cu.in. Specially placed reinforcement and a UV veil layer will ensure the structural strength and longevity. If a metal tower is provided, basin shall be constructed of 304 Stainless Steel. Cold water basin and tower casing shall be covered by a fifteen (15) year warranty.

.4 Fill and Drift Eliminators (Internal Component)

.1 Fill shall be Polyvinyl Chloride (PVC) of cross-fluted design, 10 mil (after forming), impervious to decay, fungus and biological attack. Fill sheets shall be self-spacing, supported on maximum spans of 12". Each fill sheet shall have a microstructure to improve heat transfer. Fill sheets shall be bonded together to give a cross-corrugated pattern by application of glue only to dedicated glue joints. Fill packs made from random application of glue shall not be acceptable. Fill packs or blocks shall be placed in the tower so as to provide the tightest fit possible without damage to the fill.

2. Drift eliminators shall be minimum three-pass Polyvinyl Chloride (PVC) material of cellular design impervious to decay, fungus and biological attack. Drift losses shall not exceed 0.0004% of the design circulating flow rate. Fill and drift eliminators shall be covered by a five (5) year warranty

.5 Fans

.1 Fan motors to be IP56 construction, VFD rated, Nema MG1 Part 31 nameplated (motor winding insulation suitable to withstand 2000v spikes (3 ph/575v motors), c/w shaft grounding. Motor to be c/w (5) Year warranty.7

.6 Basin make-up (water level) control

.1 Provide Utrasonic Liquid Level sensor c/w controller and control Panel , c/w Tower Tech Level controller Stilling well with 6” overflow

.2 Contractor to provide make-up water meter and on-off DDC solenoid make-up water valve.

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 11

.6 AFDs for TowerTech option.

.1 Provide one of the following:

(a) Two AFDs c/w automatic switchover panel (upon AFD failure –i.e. critical fault fault – Panel shall switch AFDs – BAS shall alternate AFDs as lead/lag on a weekly basis(adj.))(manual AFD bypass is not required.)

● Provide one input harmonic filter and one output dVdT

● This option requires one power feeder from the AFD to a weatherproof splitter provided by TowerTech at the cooling tower

or

(a) One AFD and TowerTech T1229 fan sequencing Panel c/w integral automatic switchover upon AFD failure.

● Provide one input harmonic filter and one output dVdT filter

● This option requires 3 feeders (one for each fan) installed in cable tray (cable tray as per division 26)

.2 Wiring from AFD to motor :

.1 liquid tight, flexible metal conduit and cable to be specifically manufactured for this duty,

.2 voltage rating: nominal 1000 V, and voltage spikes to 2000 V,

.3 each motor wiring to be in separate conduit. Do not combine control wiring with motor wiring.

.4 3 phase and 3 ground conductors.

Standard of Acceptance

● NEXANS - Drive Rx - Variable speed drive cable

● LAPP USA - OLFLEX® VFD SLIM; Severe duty power cable for AFD drives

● ShawCor - Shawflex VFD cable

● Rockbestos-Suprenant Cable - EXANE - VFD sheathed armoured power cable.

14.0 Mechanical Specification Section 23 73 23 Custom Air Handling Units

14.1 Part 2 Products, 2.1 General, (a) Under Standard of Acceptance, revise Mafna (Applied Energy) to MAFNA (519 624 6422)

14.2 Part 2 Products, add 2.14 AHU Sound Data,

2.14 AHU Sound Data

.1 AHU Fan sound pressure and sound power levels (dB) shall not exceed those listed in the following table

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 12

15.0 Mechanical Specification Section 23 81 26 Ductless Split air Conditioners

15.1 Part 2 Products, 2.1 General,

(a) Add .3:

.3 System is based on Daikin. Contractor is to include all additional electrical and piping

costs required for to provide complete and operation system for alternate equipment. (b) Add the following to Standard of Acceptance:

Standard of Acceptance

LG

16.0 Mechanical Specification Section 23 82 36 Convectors and Wall Fin

FREQ 63 125 250 500 1000 2000 4000 8000

AHU•1 SA DISCH 86 82 82 85 78 74 71 68

AHU•1 OA 80 77 86 90 81 80 77 74

AHU•2 SA DISCH 97 97 95 86 83 80 75 70

AHU•2 RA INLET 87 92 88 78 75 71 64 59

AHU•3 SA DISCH 83 78 79 78 73 69 66 63

AHU•3 RA INLET 80 86 88 80 76 73 66 60

EXU•1 EA 81 76 83 83 79 76 68 60

EXU•1 EA INLET 69 65 61 55 55 55 55

55

EXU•2 EA 90 88 90 88 84 79 72 65

EXU•2 EA INLET 87 89 92 85 81 76 68 63

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 13

16.1 Part 2 Products, 2.3 Flat Tube Radiators, .1 Heating Elements, Add the following:

.6 all low level mounted radiators shall an integral heavy gauge (0.09” minimum) all-

welded perforated top grille. .7 all high level mounted radiators shall have the top grille relocated to the bottom

providing a finished appearance when looking up. 17.0 Mechanical Specification Section 23 83 16 Radiant Ceiling Panels

17.1 Part 2 Products, 2.3 Linear ceiling panels, .1 Construction, add .2

.2 surface mounted panels to include 90° extrusions full length of the panels with the same profile as the face of the panel. Where the panels do not extend wall to wall, they are to include closed ends. 18.0 Mechanical Specification Section 23 83 43 Radiant Floor Heating systems

18.1 Part 2 Products, 2.1 Manufacturers, Add to Standard of Acceptance.

(c) WattsRadiant

18.2 Part 2 Products, 2.4 Manifolds, Revise .3 to read:

.3 all manifolds shall be supplied factory assembled and pre-wired and shall include

manifold with balance valve on return, flow meters on supply side of manifold mounted in a white powder-coated steel enclosure with latched door. The enclosure Shall be for a recessed application exposed trim and front panel to be stainless steel. Manifold assembly shall be complete with pre-installed and wired 24 Volt actuators on each manifold circuit and pre-wired for with individual circuit control. The assembly includes a zone relay control, 40-VA transformer, trunk isolation valves, temperature gauges, vent and purge assemblies. Field-wire thermostats and floor sensors (not included) to zone control module and dry contact switch to distribution panel

19.0 Mechanical Specification Section 23 84 13 Humidifiers

19.1 Part 2 Products, Add part 2.3 Ultrasonic Humidifiers and RO Water system:

2.3 Ultrasonic Humidifiers and RO Water system

.1 Humidfiers ME-11a, 11B, 11C, 11D, 11E, 11F, and 11G to be MistPac 25 Ultrasonic Module, c/w stainless steel mounting shelf, booster fan, Microprocessor HC301

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 14

Proportional Master control panel. (1 panel per four Humidifiers). Humidifier to be 25lbs/hr, 1ph/ 120v., 700VA per module. Humidifer c/w BAS interface.

.2 Humidification system to be c/w ME-10 RO system @ 240 lbs per hour, RODI1900,

1035USG per day, 1 ph/120v, ¾ Hp. .1 ME-10 RO system to be c/w BAS interface, c/w water quality conductivity controller.

System to be skid mounted.

Standard of Acceptance

○ Humidifier – by Humidifirst ○ RO System by CTM Inc.

Drawings

1.0 Mechanical Drawing M009 – Mechanical Schedules 1 1.1 In Miscellaneous Equipment Schedule, for Tags ME-01, ME-02, ME-03, ME-04, Hot Water

Heating Boilers, revise the following:

a) Under Performance, Revise notes to read: 3.06 L/s, EWT 41°C, LWT 71.1°C, Operating Pressure 203kpa

b) Under Construction Data , Type, Revise notes to read: Based on Cleaver Brooks CFC 1500.

1.2 In Miscellaneous Equipment Schedule, for Tag ME-07, Cooling Tower, revise the following:

c) Under Construction Data, Revise notes to read: Steel, Induced Draft c/w 2 @ 3PH/575v/60Hz Electric 9.0 Kw Basin Heaters.

1.3 Add Pump Schedule

a) Add pump schedule as per attached sketch SKM-M009-1

1.4 Revise Heat Exchanger HE-1 and HE-2 in Heat Exchanger Schedule as per attached sketch SKM-M009-2.

2.0 Mechanical Drawing M010 – Mechanical Schedules 22

2.1 In Hot water and electric Reheat Terminal Unit Schedule, under Remarks add note 5.:

5. Electric Reheat coils to be c/w SCR controllers capable of accepting a BAS 4-20ma analogue input signal.

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 15

3.0 Mechanical Drawing M012 – Mechanical Details #2, HVAC

3.1 Add detail 15/M-012 Radiant Ceiling panels for Exposed ceilings as shown on attached sketch SKM-M012-1

4.0 Mechanical Drawing M016 – Mechanical Detail #5 Exhaust Systems 4.1 On Detail #2/M016 – Hepa Filter Units, Under Standard of Acceptance add the following

manufacturers: (a) Camfil Farr (b) Tri-Dim

(c) EB Air Control Inc.(P&G)

5.0 Mechanical Drawing M200 – Plumbing Underground

5.1 Revise plumbing and drainage as per sketch drawing SKM-M200-1 5.2 Revise plumbing and drainage as per sketch drawing SKM-M200-2 5.3 Revise plumbing and drainage as per sketch drawing SKM-M200-3 5.4 Revise plumbing and drainage as per sketch drawing SKM-M200-4 5.5 In the event that Optional Price No.1 is selected, relocate 12” buried storm line to exit building at

approximate location of grids K/5 to allow for clearance from existing Invertebrate Building not being demolished.

6.0 Mechanical Drawing M210 – Plumbing Level 1

6.1 Revise plumbing and drainage as per sketch drawing SKM-M210-1 6.2 Revise plumbing and drainage as per sketch drawing SKM-M210-2 6.3 Revise plumbing and drainage as per sketch drawing SKM-M210-3

q:\projects\tor\210\1215 - toronto zoo\spec\addenda\addendum #3\toronto zoo wildlife health centre - addendum 2.docx 16

End of Addendum

Per:

Copied:

Toronto Zoo Wildlife Health Centre HH Angus & Associates Ltd. Project No.: 1029

Section 23 21 23Pumps - Heating and Cooling

Page 1 of 5

Issued for Review

PUMPS - HEATING AND COOLING 23 21 23

1 GENERAL

1.1 Scope

.1 Provide pumps as shown.

1.2 Shop Drawings

.1 Submit shop drawings or manufacturers' product data sheets and pump curves. Indicate connection points, weights, loading points and electrical characteristics.

1.3 Applicable Codes and Standards

.1 C820 - Energy Efficiency Test Methods for Small Pumps.

.2 Equipment with design pressure greater than 1,100 kPa or operating temperature greater than 121 ºC to have Canadian registration number.

2 PRODUCTS

2.1 General

.1 Selected operating point for each pump to be in range between 30% below and 10% above flow at best efficiency point for chosen impeller diameter.

.2 Determine head, power and efficiency test data for small pumps in accordance with C820.

.3 Performance curve, showing head vs flow, to rise continuously from run out to shut-off.

.4 Actual impeller size to be equal to or less than 90% of maximum impeller diameter catalogued for chosen casing size.

.5 Select motors for continuous operation without motor overload at runout condition, for impeller size and rotational speed chosen.

.6 Pump motors: to Section 20 05 13 Motors, Starters and Wiring, unless otherwise specified.

2.2 Pump seals

.1 Pumps with suction pressures less than 700 kPa (100 psi) to be fitted with mechanical seals.

.2 Pumps with suction pressures greater than 700 kPa (100 psi) may be fitted with mechanical seals or packing glands.

.3 Fit pumps with packing gland with;

.1 stainless steel shaft, or

.2 stainless steel shaft sleeve for full length of stuffing box.

2.3 In-line commercial duty circulating pumps (high flow in-line circulators)

.1 Pump:

Section 23 21 23 Pumps - Heating and Cooling Page 2 of 5

Toronto Zoo Wildlife Health CentreHH Angus & Associates Ltd.

HHA #[Comments]

Issued for Review

.1 volute of cast iron or bronze, with screwed or flanged suction and discharge connections and tapped openings for venting, draining, pressure gauges,

.2 impeller of cast bronze, stamped brass, alloy steel or cast iron,

.3 shaft of alloy steel or stainless steel with bronze sleeve bearing and integral thrust collar,

.4 mechanical seal assembly,

.5 flexible self-aligning coupling,

.2 Motor:

.1 resilient mounted, drip proof, sleeve bearing motor.

Standard of Acceptance

° S.A. Armstrong Series 1020, 1050 ° ITT Bell and Gossett Series 60

° Taco Series 1600

° Flo Fab 500, 600. 700

2.4 Single suction centrifugal pump

.1 Pump:

.1 bronze fitted type,

.2 alloy steel or stainless steel shaft with two points of support and sleeve bearings,

.3 bronze, cast iron, or stainless steel, enclosed, dynamically balanced impeller keyed to shaft and secured with locking nut or screw,

.4 cast iron, bronze or stainless steel radially split end suction volute with flanged suction and discharge, drain plug, vent cock and suction and discharge pressure gauge tappings,

.5 mechanical seal or packing gland with hardened wear rings and drip pocket piped to base gutter,

.6 common cast iron or fabricated steel base with drip rim and tapping for drain connection.

.7 positive seal flushing system with valved copper piping from pump discharge to seal or stuffing box, ball type flow indicators and

(a) cyclone separators for pump heads up to 2400 kPa (800 ft), or (b) 50 micron filters on pumps subject to dynamic heads of less than 160 kPa (55 ft),

.8 flexible self-aligning coupling.

.9 design pressure:

Class 125: 1034 kPa (at 93.3 ºC)

Class 250: 1896 kPa (at 93.3 ºC)

.2 Motor:

.1 TEFC motor, rated for AFD application where shown.

Standard of Acceptance

° S.A. Armstrong ° ITT Bell and Gossett

° Aurora

° Taco FI/CI ° Flo Fab 2196, 2300

Toronto Zoo Wildlife Health Centre HH Angus & Associates Ltd. Project No.: 1029

Section 23 21 23Pumps - Heating and Cooling

Page 3 of 5

Issued for Review

2.5 Single suction split coupled vertical-in-line centrifugal pump

.1 Pump:

.1 bronze fitted type,

.2 cast iron casing with motor mounting flange and drip rim and tapping for drain connection,

.3 alloy steel or stainless steel shaft,.

.4 bronze, cast iron, or stainless steel, enclosed, dynamically balanced impeller keyed to motor shaft and secured with locking nut or screw,.

.5 cast iron radially split end suction volute with flanged suction and discharge, drain plug, vent cock and suction and discharge pressure gauge tappings,.

.6 mechanical seal with positive seal flushing system consisting of valved copper piping from pump discharge to seal, ball type flow indicators and;

(a) cyclone separators for pump heads up to 2400 kPa (800 ft), or (b) 50 micron filters on pumps subject to dynamic heads of less than 160 kPa (55 ft).

.7 split coupled motor mount with flexible self-aligning coupling.

.8 design pressure:

Class 125: 965 kPa (at 93.3 ºC)

Class 250: 2413 kPa (at 93.3 ºC)

.2 Motor:

.1 TEFC motor, rated for AFD application

Standard of Acceptance ° S.A. Armstrong

° ITT Bell and Gossett

° Aurora ° Sulzer Paco

° Taco KS/KV

° Flo Fab 800

2.6 Double suction centrifugal pump

.1 Pump:

.1 bronze fitted type,

.2 common cast iron or fabricated steel base with drip rim and tapping for drain connection,

.3 alloy steel or stainless steel shaft with two points of support and sleeve bearings,

.4 bronze, cast iron, or stainless steel enclosed dynamically balanced impeller keyed to shaft and secured with locking nut or screw,

.5 cast iron horizontally split double suction volute with flanged suction and discharge cast in lower half, drain plug, vent cock and suction and discharge pressure gauge tappings,

.6 mechanical seal or packing gland with hardened wear rings and drip pocket piped to base gutter,

.7 positive seal flushing system with valved copper piping from pump discharge to seal or stuffing box, ball type flow indicators and

(a) cyclone separators for pump heads up to 2400 kPa (800 ft), or (b) 50 micron filters on pumps subject to dynamic heads of less than 160 kPa (55 ft),

.8 flexible self-aligning coupling.

Section 23 21 23 Pumps - Heating and Cooling Page 4 of 5

Toronto Zoo Wildlife Health CentreHH Angus & Associates Ltd.

HHA #[Comments]

Issued for Review

.9 design pressure:

Class 125: 1034 kPa (at 93.3 ºC) Class 250: 1896 kPa (at 93.3 ºC)

.2 Motor:

.1 TEFC motor, rated for AFD application.

Standard of Acceptance

° S.A. Armstrong ° ITT Bell and Gossett

° Aurora

° Sulzer Paco

° Taco TA ° Flo Fab 4800

2.7 Horizontal two stage end suction pumps

.1 Pump:

.1 bronze fitted type,

.2 common cast iron or fabricated steel base with drip rim and tapping for drain connection,

.3 alloy steel or stainless steel shaft with two points of support, 304 stainless steel shaft sleeve,

.4 bronze, enclosed dynamically balanced impellers mounted back to back, keyed to shaft and secured with locking nut,

.5 cast iron radially split first stage suction volute with flanged suction,

.6 cast iron interstage diaphragm fitted between first and second stage impellers,

.7 stuffing box casting with integral second stage volute and discharge flange, configured to accommodate mechanical seal or packing gland and drip pocket piped to base gutter,

.8 cast iron bearing housing with grease lubricated radial and thrust ball bearings,

.9 flexible self-aligning coupling and coupling guard.

.2 Motor:

.1 TEFC motor.

Standard of Acceptance

° Smart Turner ° ITT Bell and Gossett

° Aurora

° Goulds

3 EXECUTION

3.1 General

.1 Pipe drain tapping to drain.

.2 Install gauges.

.3 Check pump rotation.

Toronto Zoo Wildlife Health Centre HH Angus & Associates Ltd. Project No.: 1029

Section 23 21 23Pumps - Heating and Cooling

Page 5 of 5

Issued for Review

3.2 Installation of base mounted pumps

.1 Supply templates for anchor bolt placement, dimension layouts for pump bases and furnish anchor bolts with sleeves.

.2 Place pumps level on concrete base, dowel, shim and grout with minimum 13 mm (½ in) grout.

.3 Fill hollow portion of bases with concrete.

.4 Align couplings before and after piping connections have been made.

.5 Check oil level and lubricate.

.6 Tighten glands after run-in.

3.3 Installation of in-line circulators

.1 Install with fluid flow direction as indicated by flow arrows on pump body.

.2 Support piping and pump at flanges or near unions on connections to unit.

.3 Install with bearing lubrication points accessible.

3.4 Installation of vertical in-line pumps

.1 Support pump from pipe elbow stanchions or hangers on suction and discharge piping.

.1 Support pump on underside of pump base where required by manufacturer's instructions.

.2 Install volute venting pet cock in accessible location.

END OF SECTION Master revised: Jan. 2, 2007

Metro Zoo Wildlife Health Centre H.H.Angus and Associates Ltd. Project #1029

Section 23 51 23Gas VentsPage 1 of 3

Issued for Review

GAS VENTS 23 51 23

1 GENERAL

1.1 Scope

.1 Provide listed gas vents and vent connectors as shown for;

.1 natural gas and propane fired appliances.

1.2 Related sections

.1 23 51 13 – Insulated Sectional Chimneys

1.3 Definitions

.1 In this section the following definitions apply:

.1 Vent: (as it applies to a vent flue) has the meaning as defined in CSA B149.1

.2 Vent connector: (as it applies to a vent flue) has the meaning as defined in CSA B149.1

1.4 Manufacturer Design Services

.1 Manufacturer to provide engineering services to design vents and vent connectors for the following installation configurations:

.1 manifolded appliance vent connectors, and/or

.2 vents 300 mm (12 in) and larger

.2 Provide detailed design based on appliance layout and general routing of vent and vent connectors as shown. Include:

.1 layout and sizing drawings,

.2 bill of materials,

.3 thermal analysis including theoretical draft and available draft,

.4 wind loading restraint, seismic restraint, and structural support details.

1.5 Submittals

.1 Submit shop drawing data sheets for manufactured products and standard fittings showing dimensions and describing construction.

.2 Submit engineering shop drawings including layout and installation details.

1.6 Applicable Codes and Standards

.1 Legislation:

.1 [Ontario Regulation 212/01 Gaseous Fuels,

.2 Installation standards and codes:

.1 CSA B149.1 Natural gas and propane installation code

.3 Product standards:

Section 23 51 23 Gas Vents Page 2 of 3

Metro Zoo Wildlife Health CentreH.H.Angus and Associates Ltd.

HHA #1029

Issued for Review

.1 CAN/ULC-S605 Standard for Gas Vents

.2 CAN/ULC-S609 Standard for Low Temperature Vents Type L

.3 CAN/ULC-S636 Standard for Type BH Gas Venting Systems

2 PRODUCTS

2.1 Gas Vents – Type B/BW

.1 Catalogued, factory manufactured product:

.1 CAN/ULC-S605, Type B/BW, 245°C (473°F) rated for Category I (natural draft, non-condensing) gas appliances.

(a) size: 75 mm (3 in) to 1200 mm (48 in) diameter

.2 Clearance to combustibles: 100 mm (4 in) maximum.

.3 Sectional, prefabricated, double wall metal construction with metal fittings including roof flashings, storm collars, Belmont top, roof and wall supports, firestop spacers, wall thimbles, fittings and couplings, for both vent and vent connectors.

.4 Aluminum inner liner, galvalume outer casing with minimum 6.5 mm (1/4 in) air space.

.5 Draft hoods, hood connectors for category I appliances.

Standard of Acceptance

° Selkirk model Type B model RV or QC

° Van-Packer model B Vent ° Metal-Fab model B-1/B-2

° Cheminée Lining – Airex

2.2 Gas Vents – Type BH (Special Gas Vents) (For Condensing Boilers)

.1 Catalogued, factory manufactured product:

.1 CAN/ULC-S636, Type BH Class I appliances with flue gas temperatures between 135 and 245°C (275 and 475°F), for Category II, III and IV appliances.

.2 CAN/ULC-S636, Type BH Class IIB with flue gas temperatures of 90°C (194°F) or less for category II and IV appliances.

.2 Systems:

.1 CPVC: pipe, fittings, cement and primers and including fittings, roof flashings, storm collars, as one manufactured system for both vent and vent connectors, or

.2 Metal: sectional, prefabricated, double wall 2” mineral wool insulated T304 stainless steel liner and T304 stainless steel casing construction with metal fittings including roof flashings, storm collars, ASHRAE weatherhood, roof and wall supports, firestop spacers, wall thimbles, fittings and couplings, for both vent and vent connectors.

.3 Clearances:

.1 combustibles: 50 mm (2 in) maximum

.2 non-combustibles: 0 mm (0 in)

Metro Zoo Wildlife Health Centre H.H.Angus and Associates Ltd. Project #1029

Section 23 51 23Gas VentsPage 3 of 3

Issued for Review

Standard of Acceptance

° Selkirk ………………….model Saf-T-Vent ° Van-Packer ………………….model CS

° Metal-Fab ………………….model Corr/Guard-CG

° Schebler ………………….model eVent

° IPEX ………………….model System 636 ° Cleaverbrooks Exhaust solutions…..model CBILA

° Cheminée Lining – Airex…………….model HEPL2

3 EXECUTION

3.1 General

.1 Vents and vent connectors serving gaseous fuel appliances: installed by tradesmen certified for installation of gaseous fuel fired appliances.

3.2 Installation

.1 Select venting system in accordance with requirements of appliance listing.

.2 Install venting system and support as required in accordance with venting manufacturer and appliance manufacturer installation requirements,and applicable codes.

.3 Support vents at roof penetrations and provide roof flashing and counter-flashing.

.4 Seal double wall pressure vents and vent connectors

.5 Make vent connector connections to appliance flue gas outlet with slip type joints and mechanical fastener.

.6 Terminate vent stack c/w ASHRAE weatherhood (.i.e. Cleaverbrooks Exhaust Solutions model RSH – Rainshield.

.7 Where breeching system is designed to absorb thermal expansion make connection with flange adaptor.

END OF SECTION Master revised: January 5, 2013

Toronto Zoo Wildlife Health Centre H.H.Angus and Associates Ltd. Project No.: 1029 1029

Section 23 51 33 Insulated Sectional Chimneys

Page 1 of 4

Issued for Review

INSULATED SECTIONAL CHIMNEYS 23 51 33

1 GENERAL

1.1 Scope

.1 Provide chimneys and chimney connectors as shown for;

.1 heating oil fired appliances,

.2 natural gas fired appliances,

.3 dual-fuel gas/oil appliances.

1.2 Definitions

.1 In this section the following definitions apply:

.1 Chimney: a vertical conduit conveying flue gases to the outside atmosphere,

.2 Chimney connector: has the meaning as defined in CSA B139-09

.3 Low heat appliances: appliances with a flue gas outlet temperature of 540°C (1000°F) or less.

.4 Vent: (as it applies to a vent flue) has the meaning as defined in CSA B139-09 and CSA B149.1

.5 Vent connector: (as it applies to a vent flue) has the meaning as defined in CSA B139-09 and CSA B149.1

1.3 Manufacturer Design Services

.1 Manufacturer to provide engineering services for design of chimney and chimney connectors based on appliance layout and general routing of chimney and chimney connectors as shown. Include:

.1 layout and sizing drawings,

.2 bill of materials,

.3 thermal analysis including theoretical draft and available draft,

.4 wind loading restraint, seismic restraint, and structural support details.

1.4 Submittals

.1 Submit shop drawing data sheets for manufactured products and standard fittings showing dimensions and describing construction.

.2 Submit engineering shop drawings including layout and installation details.

1.5 Applicable Codes and Standards

.1 Legislation:

.1 Ontario Regulation 213/01 Fuel Oil,

.2 Installation standards and codes:

.1 CSA B139 Installation Code for Oil Burning Code.

.3 Product standards:

Section 23 51 33 Insulated Sectional Chimneys Page 2 of 4

Toronto Zoo Wildlife Health Centre H.H.Angus and Associates Ltd.

HHA #1029

Issued for Review

.1 CAN/ULC-S604 Standard for Factory-Built Type A Chimneys

.2 CAN/ULC-S609 Standard for Low Temperature Vents Type L

.3 CAN/ULC-S629 Standard for 650°C Factory-Built Chimneys

.4 ULC/ORD-C959 540°C and 760°C Industrial Chimneys

2 PRODUCTS

2.1 Building Heating Appliance Chimneys

.1 General:

.1 to CAN/ULC-S604 or CAN/ULC-S629 or ULC/ORD-C959

.2 maximum flue gas temperature: 540°C (1000°F)

.3 vent pressure: negative, neutral or positive pressure

.4 fuels: natural gas, propane, oil.

.5 size: 150 – 1200 (6 – 48 in) liner ID.

.6 clearance to combustibles: 100 - 250 mm (4 - 10 in) maximum depending on chimney size.

.2 Construction:

.1 double wall construction for chimney and chimney connectors,

(a) flue liner: T304 stainless steel (b) casing: T304 stainless steel (c) insulation: 25 mm (1 in) air space or mineral wool insulation

.2 prefabricated sectional lengths and fittings, and accessories including roof flashings, storm collars, Belmont top, roof and wall supports, firestop spacers, wall thimbles, for both chimney and chimney connectors.

Standard of Acceptance

Selkirk – model UltraTemp/ UltimateOne/ ICA

Van-Packer – model DW

Metal-Fab – model PIC

Schebler – model P1

2.2 Barometric draft control for non draft hood applications

.1 Construction:

.1 single acting, for natural gas,

.2 dual acting for natural gas and oil fired applications,

.3 80% of full size of breeching area,

.4 fabricated from 3.5 mm [10 ga] steel.

Standard of Acceptance

Wing DA and SA

Field M and MG2

Toronto Zoo Wildlife Health Centre H.H.Angus and Associates Ltd. Project No.: 1029 1029

Section 23 51 33 Insulated Sectional Chimneys

Page 3 of 4

Issued for Review

3 EXECUTION

3.1 General

.1 Chimneys and chimney connectors serving gaseous fuel and liquid fuel appliances: installed by tradesmen certified for installation of fuel fired appliances.

.2 Select chimney type base on flue gas temperature, and required chimney size as per the following:

Type of Appliances

Maximum Flue Gas Temperature Limit

Appliance Flue Outlet Size or Manifolded

Chimney Connector Size(1)

Chimney Type

Building Heating appliances

≤300°C (570°F)

>200 mm (8 in) Building Heating

Appliance Chimney

≤540°C (1000°F) All sizes Building Heating

Appliance Chimney

3.2 Installation

.1 Install chimney system in accordance with chimney manufacturer and appliance manufacturer installation requirements.

.2 Maintain clearance between chimney connectors and combustible materials or building insulation in accordance with product listing requirements.

.3 Position chimneys inside of enclosures to maintain minimum clearances to:

.1 combustible material in accordance with chimney listing requirements, and

.2 for non-combustible materials as follows:

(a) 50 mm (2 in) for chimney OD size less than or equal to 450 mm (18 in) (b) 100 mm (4 in) for chimney OD size larger than 450 mm (18 in).

.4 Support chimneys at roof penetrations and provide roof flashing and counter-flashing.

.5 Provide expansion joints as shown and as required by specific product engineered design.

.6 Erect chimneys true and plumb to within 1 in 1200.

.7 For multiple appliances, manifold the chimney connectors in accordance with manufacturer installation requirements.

.8 Where an offset is required, make offset with 45° elbow fittings whenever possible.

Section 23 51 33 Insulated Sectional Chimneys Page 4 of 4

Toronto Zoo Wildlife Health Centre H.H.Angus and Associates Ltd.

HHA #1029

Issued for Review

.9 Provide clean-outs at base of chimney and provide access to clean-outs.

.10 Seal double wall pressure stacks and breechings:

.1 seal inner joints bead of high temperature sealant,

.2 fill channel of vee band with high temperature sealant and install and tension vee-band,

.3 install insulation filler strips in air space between inner and outer walls, and secure outer shell with draw band,

.4 caulk upper edge of drawbands exposed to the weather with silicone sealant.

.11 Make connector connection to equipment, flue gas outlet with slip type joints and mechanically fasten with a minimum of three (3) screw fasteners.

.12 Where chimney passes through combustible floor or wall construction, provide fire-stop fitting.

.13 Where breeching system is designed to absorb thermal expansion make connection with flange adaptor.

END OF SECTION Master revised: January 5, 2013

addendum 1 Project Number: 12005 Addendum Number: 1 Date: October 29, 2014 To: Diamond Schmitt Architects 384 Adelaide Street West, Suite 300 Toronto ON. M5R 1R7 Attn: Eric Lucassen

Re: Landscape clarifications and revisions and responses to RFI’s 1. The following revisions are to be incorporated in the Work prior to the award of

Contract in accordance with the requirements of the contract documents. 2. The cost of such revisions shall be included in the Tenderer's submission.

Description of Addendum

A. RESPONSE TO BIDDERS QUESTIONS

1. Question: Could you please provide the thickness of Pervious Concrete and Granular

B. The Geotechnical report makes no mention of pervious concrete. Load-bearing and Hydrogeological requirements should be determined by the Consultants.

Answer: Refer to attached LSK-1. The Pervious Concrete should be 150mm, ontop a 150mm depth of High Performance Bedding (HPB), on of a geotextile, on 200mm depth of Granular ‘B’, on top of a geotextile on ex. compacted subgrade. Drain subbase to an infiltration trench down the centre of the parking lot. This detail shall replace detail 8 on sheet L-03, Hydromedia Permeable Concrete Paving.

2. Question: The top and bottom of wall elevations given at the end of the wall near the existing road are 142.65 and 141.35 which gives a height of 1.3m but on 9/L-03, the elevation shows that wall as being 0.3m high. Could you please clarify which is correct?

Answer: Drawing L-01 contains a typo in the spot elevations. The CIP concrete wall elevations at the east end of the wall should read: top of the wall at 141.65 and bottom of the wall at 141.35. The detail is correct showing a wall height of 30cm. See attached re-issued L-01 and revision bubble.

3. Question: On drawing L-02, the upland Beaty mix for the grass, add up to 58%. Evening Primrose, Indian grass and Greenheaded Coneflower do not have percentages. Please clarify what is the percentage missing?

Answer: Evening Primrose is 15%. Greenheaded Coneflower is 10%.

addendum 1

Indian Grass is 17%

B. LANDSCAPE DRAWINGS 1. L-01 has been revised to show limits of landscape disturbance, and notes regarding

restoration of disturbed area. See attached re-issued L-01 and revision bubbles. 2. Drawing TP-1 has been added to the landscape drawing set that shows Existing Trees

to Remain and Existing Trees to be removed. Should there be any discrepancies between trees to remain or to be removed, refer to Landscape TP-1 for the most current condition. All other special notes and instructions regarding type of hoarding to be as per Arborist Plan.

Per: Fung Lee, PMA LANDSCAPE ARCHITECTS Distribution: Authorized by:

- to Architect for distribution

PMA LANDSCAPE ARCHITECTS LTD. _____October 29, 2014_________ Date

200mm GRANULAR 'B' COMPACTED TO 98% S.P.D.

150mm HYDROMEDIA PERVIOUS CONCRETE BY LAFARGECONTACT: INNOCON; BAHEE SOORIYAKUMAR @ 647-228-9009

SLOPE TO EDGE

FINISHED GRADE

SECTION

INSTALLATION NOTES:

1. PLACEMENT TO BE CONTINUOUS AND RAPID2. USE MANUFACTURER'S RECOMMENDED PLACEMENT

METHOD.3. AVOID OVER WORKING THE CONCRETE.4. CONVENTIONAL FORMS TO BE USED5. STANDARDS SCREEDS AND ROLLER COMPACTORS CAN BE USED FOR STRIKE-OFF6. RISER STRIPS ARE NOT RECOMMENDED.7. HAND TAMP NEAR EDGES AND OTHER PLACES NOT

REACHED BY COMPACTOR.8. COMPLETE COMPACTION WITH 15 MINUTES OF PLACEMENT9. NO FLOATING OR TROWELLING10. DO NOT WALK ON SURFACE AFTER COMPACTION.11. PLACE JOINTS IMMEDIATELY AFTER COMPACTION.12. SAW CUTS ARE POSSIBLE AFTER 7 DAYS OF CURING.13. FOG MIST THE SURFACE WITHIN 20 MINUTES OF COMPACTION.14. COVER WITH PLASTIC SHEETING WITHIN 20 MINUTES AFTER PLACEMENT AND LEAVE IN PLACE FOR 7 DAYS.

SUBGRADE COMPACTED TO 90 - 95% S.P.D.PERMEABILITY DECREASES WITH INCREASED COMPACTION

150mm HPB

CLEAR STONE COMPACTED TO 98% S.P.D.

100mm Ø DRAINAGE PIPE

100m

m10

0mm

GEOTEXTILE

600mm

MIN. 1% SLOPE TO INFILTRATION TRENCH

Project

Toronto ZOO Wildlife Health Centre361A Old Finch Avenue

Toronto, ON.

Drawn ByScale Project No.

Date Drawing No.

PMA 12005

OCT. 28.2014 LSK-1

N.T.S.

Revision No.

MK

359 Keele St. Toronto, Ontario M6P 2K6t. 416.239.9818 f. 416.239.1310 www.pmalarch.ca

hydromedia permeable concrete paving

ISSUED

DateNo Issued

CONTRACTOR MUST CHECK & VERIFY ALL DIMENSIONS ON THE JOB.

DO NOT SCALE DRAWINGS.

ALL DRAWINGS, SPECIFICATIONS AND RELATED DOCUMENTS ARE THE COPYRIGHT PROPERTY OF THE ARCHITECT AND MUST BE RETURNED UPON REQUEST. REPRODUCTION OF DRAWINGS, SPECIFICATIONS AND RELATED DOCUMENTS IN PART OR IN WHOLE IS FORBIDDEN WITHOUT THE WRITTEN PERMISSION OF THE ARCHITECT.

THIS DRAWING IS NOT TO BE USED FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT.

KEYPLAN

Date:Project No:Scale:

1029

361A OLD FINCH AVENUETORONTO, ONTARIO

TORONTO ZOO WILDLIFE HEALTH CENTRE

O L D F I N C H A V E N U E

/Vo

lum

es/

File

s/ P

roje

cts/

2012

Pro

ject

s/12

005

- T

OR

ON

TO

ZO

O M

ED

ICA

L/2

Bas

e In

form

atio

n/12

0126

fro

m D

iam

ond/

Arc

hite

ctur

al D

WG

\201

2012

5 A

rchi

ve C

opy\

1029

_01-

TB

-36X

48-I

.dw

g

14

0.50

141.

00

141.00

141.00

141.

50

141.50

141.50

14

2.00

142.00

142.

00

14

2.00

142.00

142.

00

142.

00 142.00

142.00

142.00

142.00

142.50

142.50

142.50

142.50

142.

50

14

2.50

14

2.50

142.50

143.

00

143.

00

143.

00

14

3.50

143.

50

144.00

144.00

EX

EXISTING QUARANTINE FACILITY

EXISTING HORTICULTURE CENTRE

EXISTING GREENHOUSES

SET-OUT POINT

EXISTING SOD

EXISTING SOD

LOADING AREA

E X I S T I N G S E R

V I C E R

O A D

S E R V I C

E R O

A D

EXISTING SODC E

EXISTING SOD

EXISTING BH

EXTENT OF WORK;MAKE GOOD EXISTING, TRAFFIC SURFACE, SIDEWALK, CURB, AND LANDSCAPING AT JUNCTION WITH NEW WORK IN THIS CONTRACT

EXISTING BH

1200

0

MIN

. FIR

E A

CC

ES

S W

IDT

H

FIRE ACCESS ROUTE

EXISTING BH

E X

I S

T I

N G

S

E R

V I

C E

R

EXISTING BH

LINE OF CANOPY ABOVE

EXISTING BH

EXISTING BH

EXISTING BH

EXISTING BH

EXISTING BH

EXISTING TP

EXISTING TP

EXISTING TP

TRAFFIC SURFACE

EXISTING FIRE HYDRANT

EXISTING FIRE HYDRANT

EXISTING SOUTH ELECTRICAL ROOM ON GROUND FLOOR

EXISTING ELECTRICAL / COMMUNICATIONS ROOM ON GROUND FLOOR

EXISTING UNDERGROUND CONDUITS NEW CONCRETE DUCT BANK, REFER TO ELECTRICAL DRAWINGS

E X I S T I N G T R A F F I C S U R F A C E

EXISTING VEGETATION

142.310 142.310

142.310142.310

142.310

142.310

EX

142.310

142.310

142.310 142.310

142.310

142.310

142.310

142.310142.310

142.310

142.310

142.33

142.33

142.10 EX 142

.15

EX 142.21

142.33

EX 142.23

EX 142

.17

EX 142.33

142.12

EX 141.92

NEW 1

42.2

2

142.33

EX 142.13

EX 142.05

142.

03

142.18

142.03

EX 142

.31

142.18

142.33

MATCH EX.

142.03

EX 141

.38

EX 141

.29

EX 141

.50

141.

78

141.78

142.00

141.

53

141.53

141.

81

141.

51

142.87

142.28

142.33

142.33

EX 142

.54

EX 142

.60

EX 142

.51

EX 142

.70

142.69

142.48

142.33

142.60

142.72

EX 142

.75

EX 142

.80

142.

76

MATCH EX.

MATCH EX.

142.28

142.25

MATCH EX.

142.

29

142.

27

142.

33

142.

33

EXTENT OF CONC. PAVING -TYPE C

+

142.38 TW

+144.26 HP

144.20

144.10144.00

143.50

143.00

+ 142.70 TW

+ 142.70 TW

+ 142.70 TW

+

142.72 TW

3:1

MAX

3:1 MAX

142.12 BW141.78 BW

+

141.65 TW

141.35 BW

3JVC

6CAR

5BP

1CO

1JVC

4CC

1JVC

LIMITS OF CONSTRUCTION

LIMITS OF CONSTRUCTION

LIM

ITS

OF

CONS

TRUC

TION

EXTENT OF WORK;MAKE GOOD EXISTING, TRAFFIC SURFACE, SIDEWALK, CURB, AND LANDSCAPING AT JUNCTION WITH NEW WORK IN THIS CONTRACT

GOLF CART PARKING 2700 X 3300QTY: 3

STANDARD PARKING 2700 X 5800QTY: 3

DECORATIVE CIP. CONCRETE PAVING -PATTERN 1REFER TO D1/L-03

NATURALIZED HERBACEOUS PLANTING ZONE SEED WITH UBM. SPECIES NOT TO EXCEED 1.25m HEIGHT AT MATURITYFOR SPECIES CONTENT REFER TO D6/L-02.

FOR SHRUB & HERBACEOUS PLANTING REFER TO D6/L-02 PLANTING PLAN.

EXISTING TREE TO REMAINAREA DAMAGED BY CONSTRUCTION TO BE REPAIRED & SEEDED WITH UBM MIX. FOR SPECIES CONTENT REFER TO D5/L-02

EXISTING TREE TOBE PRESERVED & PROTECTED.FOR TREE PROTECTION REFER TO D1/L-02

EXISTING TREE TOBE PRESERVED & PROTECTED.FOR TREE PROTECTION REFER TO D1/L-02

SLOPED CIP CONCRETE RETAINING WALLREFER TO D9/L-03

100mm ØSUB SURFACE DRAIN REFER TO D8/L-03

100mm ØSUB SURFACE DRAIN REFER TO D11/L-03

CIP. CONCRETE PAVING - TYPE CREFER TO SPECIFICATION 32 13 13FOR HEAVY DUTY BUILD-UPREFER TO D4/L-03

CONTINUOUS TREE PIT WITH PERMEABLE PAVING.REFER TO D6/L-02

PERMEABLE PRECAST UNIT PAVING ; REFER TO D5/L-03

1200 WIDE CIP CONCRETE ACCESS PATH - REFER TO D2/L-03TYPE C CONC - REFER TO SPECIFICATION 32 13 13LIGHT DUTY BUILD-UP - REFER TO D3/L-03

EXISTING TREE TOBE PRESERVED & PROTECTED.

FOR TREE PROTECTION REFER TOD1/L-02

AREA DAMAGED BY CONSTRUCTION TO BE REPAIRED & SEEDED WITH UBM. FOR SPECIES CONTENT REFER TO D6/L-02

AREA DAMAGED BY CONSTRUCTION TO BE REPAIRED AND SEEDED WITH UBM.

EXTENT OF DECORATIVE CONC. PAVING PATTERN 1EXTENT OF CONC. PAVING -TYPE C

100mm Ø SUB SURFACE DRAIN CONNECT TO STORMREFER TO D11/L3

ARMOUR STONE RETAINING WALLREFER TO D10/L-03

PARKING TO BE PAVED WITH HYDROMEDIA PERVIOUS CONCRETEREFER TO D8/L-03

EXTENT OF HEAVY DUTY CONC. PAVING

EXTENT OF HEAVY DUTY CONC. PAVING

CIP CONC CURB AT TREE PIT; REFER TO D7/L-03

MAKE GOOD EXISTING ROAD AT JUNCTION WITH THIS NEW WORK IN THIS CONTRACT

8.3

17.7

8.1

29.7

PROPOSED TORONTO ZOO WILDLIFE CENTRE

EXISTING CONSERVATION / BIOLOGY CENTRE

EXISTING COLD FLATS

OLDING

PATTERNED CONCRETE PAVER,REFER TO LANDSCAPE DRAWINGS

EXISTING VEGETATION TO REMAINREFER TO TP-1 PLAN FOR TREE INVENTORY AND CONDITION

ONLY TREES TO BE REMAIN OR PROTECTED ARE SHOWN ON LANDSCAPE PLANREFER TO ARBORIST REPORT FOR TREE INVENTORY AND CONDITIONFOR EXISTING TREES TO BE REMOVED OR TRANSPLANTEDREFER TO TP-1 PLAN AND ARBORIST REPORT

LIMIT OF PLANTING BED/DISTURBANCE

plant list - site trees

ID Qty Botanical Name Common Name Size

TREES:

BP 5 Betula Papyrifera Paper Birch 60mm CLUMPCAR 6 Carpinus caroliniana Blue Beech 70mmCC 4 Cercis canadensis Eastern Redbud 50mmCO 1 Celtis occidentalis Common Hackberry 70mm

JVC 5 Juniperus virginiana Eastern Red Cedar 50cm

LANDSCAPE PLAN

LEGEND

EXISTING TREE TO BE PROTECTED

PROPOSEDDECIDUOUS TREE

PROPOSEDDECIDUOUS SHRUB

SHRUB & HERBACEOUS GROUNDCOVER

STANDARDCIP CONC. PAVING

EXPANSION JOINT

L-011:150

ISSUED FOR TENDER 2014-09-3001

HYDROMEDIAPERMEABLE CONC. PAVING

LOADINGAREA

ISSUED FOR ADDENDUM No.1 2014-10-2802

ISSUED

DateNo Issued

CONTRACTOR MUST CHECK & VERIFY ALL DIMENSIONS ON THE JOB.

DO NOT SCALE DRAWINGS.

ALL DRAWINGS, SPECIFICATIONS AND RELATED DOCUMENTS ARE THE COPYRIGHT PROPERTY OF THE ARCHITECT AND MUST BE RETURNED UPON REQUEST. REPRODUCTION OF DRAWINGS, SPECIFICATIONS AND RELATED DOCUMENTS IN PART OR IN WHOLE IS FORBIDDEN WITHOUT THE WRITTEN PERMISSION OF THE ARCHITECT.

THIS DRAWING IS NOT TO BE USED FOR CONSTRUCTION UNTIL SIGNED BY THE ARCHITECT.

KEYPLAN

Date:Project No:Scale:

1029

361A OLD FINCH AVENUETORONTO, ONTARIO

TORONTO ZOO WILDLIFE HEALTH CENTRE

O L D F I N C H A V E N U E

/Vo

lum

es/

File

s/ P

roje

cts/

2012

Pro

ject

s/12

005

- T

OR

ON

TO

ZO

O M

ED

ICA

L/2

Bas

e In

form

atio

n/12

0126

fro

m D

iam

ond/

Arc

hite

ctur

al D

WG

\201

2012

5 A

rchi

ve C

opy\

1029

_01-

TB

-36X

48-I

.dw

g

14

0.50

141.

00

141.00

141.00

141.

50

141.50

141.50

14

2.00

142.00

142.

00

14

2.00

142.00

142.

00

142.

00 142.00

142.00

142.00

142.00

142.50

142.50

142.50

142.50

142.

50

14

2.50

14

2.50

142.50

143.

00

143.

00

143.

00

14

3.50

143.

50

144.00

144.00

EX

EXISTING QUARANTINE FACILITY

EXISTING HORTICULTURE CENTRE

EXISTING GREENHOUSES

SET-OUT POINT

EXISTING SOD

EXISTING SOD

LOADING AREA

E X I S T I N G S E R

V I C E R

O A D

S E R V I C

E R O

A D

EXISTING SODC E

EXISTING SOD

EXISTING BH

EXTENT OF WORK;MAKE GOOD EXISTING, TRAFFIC SURFACE, SIDEWALK, CURB, AND LANDSCAPING AT JUNCTION WITH NEW WORK IN THIS CONTRACT

EXISTING BH

1200

0

MIN

. FIR

E A

CC

ES

S W

IDT

H

FIRE ACCESS ROUTE

EXISTING BH

E X

I S

T I

N G

S

E R

V I

C E

R

EXISTING BH

LINE OF CANOPY ABOVE

EXISTING BH

EXISTING BH

EXISTING BH

EXISTING BH

EXISTING BH

EXISTING TP

EXISTING TP

EXISTING TP

TRAFFIC SURFACE

EXISTING FIRE HYDRANT

EXISTING FIRE HYDRANT

EXISTING SOUTH ELECTRICAL ROOM ON GROUND FLOOR

EXISTING ELECTRICAL / COMMUNICATIONS ROOM ON GROUND FLOOR

EXISTING UNDERGROUND CONDUITS NEW CONCRETE DUCT BANK, REFER TO ELECTRICAL DRAWINGS

E X I S T I N G T R A F F I C S U R F A C E

EXISTING VEGETATION

142.310 142.310

142.310142.310

142.310

142.310

EX

142.310

142.310

142.310 142.310

142.310

142.310

142.310

142.310142.310

142.310

142.310

142.33

142.33

142.10 EX 142

.15

EX 142.21

142.33

EX 142.23

EX 142

.17

EX 142.33

142.12

EX 141.92

NEW 1

42.2

2

142.33

EX 142.13

EX 142.05

142.

03

142.18

142.03

EX 142

.31

142.18

142.33

MATCH EX.

142.03

EX 141

.38

EX 141

.29

EX 141

.50

141.

78

141.78

142.00

141.

53

141.53

141.

81

141.

51

142.87

142.28

142.33

142.33

EX 142

.54

EX 142

.60

EX 142

.51

EX 142

.70

142.69

142.48

142.33

142.60

142.72

EX 142

.75

EX 142

.80

142.

76

MATCH EX.

MATCH EX.

142.28

142.25

MATCH EX.

142.

29

142.

27

142.

33

142.

33

LIMITS OF CONSTRUCTION

LIMITS OF CONSTRUCTION

LIM

ITS

OF

CONS

TRUC

TION

EXISTING VEGETATION TO REMAIN

EXISTING VEGETATION TO REMAIN

EXISTING TREE TO REMAIN

TREE TO BE PROTECTEDREFER TO TREE PROTECTION DETAIL

TREES TO BE PROTECTEDREFER TO TREE PROTECTION DETAIL

EXISTING VEGETATION TO REMAIN

EXISTING VEGETATION TO REMAIN

XX

X

XX X

X

XX X X X X X

EXISTING VEGETATION TO REMAIN

EXISTING VEGETATION TO REMAIN

X

XX

X

XX

EXISTING TREES TO REMAIN

XX

X XX

XX

XX

X

XX

X

TREE PROTECTION PLAN

LEGEND

EXISTING TREE TO BE PROTECTED

PROPOSEDDECIDUOUS TREE

PROPOSEDDECIDUOUS SHRUB

SHRUB & HERBACEOUS GROUNDCOVER

STANDARDCIP CONC. PAVING

EXPANSION JOINT

TP-11:150

ISSUED FOR TENDER 2014-09-3001

HYDROMEDIAPERMEABLE CONC. PAVING

ISSUED FOR ADDENDUM No.1 2014-10-2802

TREES TO BE PROTECTED

TP ZONE AS PER CITY REQUIRENMENTS

TREES TO BE REMOVED

TREES TO REMAIN

MINIMUM TREE PROTECTION HOARDING DURING THE CONSTRUCTION OF SOFT LANDSCAPE AREA ONLY THAT IS WITHIN THE CITY TPZ

LEGEND:

X

TREE PROTECTION HOARDING