REScheck TM Basics 1 PNNL-SA-116714 2016 Department of Energy National Energy Codes Conference Building Energy Codes Program DALE HORTON, NCAT

REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

REScheckTM Basics

1 PNNL-SA-116714

2016 Department of Energy National Energy Codes Conference

Building Energy Codes Program

DALE HORTON, NCAT

Page 2: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Building Energy Codes Program

2

Energy Code Compliance Tools

Prescriptive UA Tradeoff Simulated

Performance

None REScheck REM/Rate REM/Design Energy Gauge

REScheck?

So

ftw

ar

e

Page 3: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

www.energycodes.gov

3

Building Energy Codes Program

Page 4: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

REScheck Page

4

Building Energy Codes Program

https://www.energycodes.gov/rescheck

Page 5: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

5

REScheck

Building Energy Codes Program

Page 6: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Can exchange files between desktop and web

Log in to web

My Projects

6

Data Exchange

Building Energy Codes Program

Page 7: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Walkthrough REScheck Steps

7

Building Energy Codes Program

2. Select

Code

3. Select

Compliance

Path

4. Enter

Project Info

1. Select

Preferences

5. Enter Building

Components

6. Enter

Mechanical

Equipment

7. Complete

Requirements

Tab

Optional

Save and Print Report

Page 8: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Preferences

8

Building Energy Codes Program

Page 9: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Select the Appropriate Code

Applicable to your state/ jurisdiction (Code menu)

9

Page 10: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Project Information

Project Location

City/County

Project Type

Single Family/Duplex

Multi Family

Building Characteristics

New Construction

Addition

Alteration

Project Details

Optional

Get printed on reports

10

Building Energy Codes Program

Page 11: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Project Information – Helpful Hints

Multifamily if

All multifamily buildings three stories

or less in height above grade and

Contain three or more attached

dwelling units

Examples Apartments

Condominiums

Townhouses

Dormitories

Rowhouses

11

Building Energy Codes Program

Page 12: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Project Information – Helpful Hints

Select New Construction, Addition or Alteration

Additions

Addition only

Addition plus existing home

Alterations

Exemptions may apply

12

Building Energy Codes Program

Alteration - would enter only portions of thermal envelop that you are touching For example – only enter windows that you are changing, not other existing windows.

Page 13: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

What is the Building Thermal Envelope?

13

Building Energy Codes Program

Page 14: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Entering Building Components

14

Building Energy Codes Program

Page 15: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Envelope Helpful Hints

Don’t have to use every button

Can group “like” components

Gross area (except slab-on-grade)

Gross wall area to include peripheral edges of floors

(area of band joist and subfloor between floors)

Use “Other” assembly as needed

15

Building Energy Codes Program

Page 16: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Envelope Helpful Hints, con’t

Fenestration ratings – U-factor and SHGC

Cavity R-value – used for insulation placed

between structural members

Continuous R-value – used for insulation that is

continuous across the structure (e.g., rigid

insulation)

After you’ve entered all building thermal envelope

components, hit Check Compliance

Look for fields with red text

If no compliance results, look for missing data

and make sure you’ve made an entry for

Building Use type

16

Building Energy Codes Program

Page 17: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

SHGCs and U-Factors

17

Building Energy Codes Program

Page 18: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Cavity vs. Continuous

18

Building Energy Codes Program

Page 19: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Foundations – what button to use

19

Building Energy Codes Program

• Basement is conditioned Basement

• Separates conditioned from unconditioned space Floor

• Crawl space is not vented to the outside and floor above is NOT insulated

Crawl Wall

Page 20: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

What’s a Basement Wall?

20

Building Energy Codes Program

Basement Wall 50% below grade

Above Grade Wall <50% below grade

Basement Wall 50% below grade

Above Grade Wall <50% below grade

Page 21: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Basements Helpful Hints

Wall Height

from top of wall to basement floor

If not uniform, provide an average height

Depth Below Grade

Depth that the wall extends from finished,

outside grade surface to basement floor

If sloped or uneven, provide an average

depth below grade

21

Building Energy Codes Program

Page 22: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Basements Helpful Hints, con’t

Depth of Insulation

Measure from top of wall to where insulation stops

For a fully insulated wall, depth of insulation would

be equal to height of the wall

If you enter insulation depth of 0, program assumes no

insulation, regardless of values in the insulation fields

Continuous Insulation

Software assumes it’s exterior rigid

Cavity Insulation

Software assumes you’re furring out on the interior

22

Building Energy Codes Program

Page 23: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Basement Walls

Building Energy Codes Program

23

Page 24: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Colors

Red

24

Building Energy Codes Program

Green

Blue

Page 25: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Screen Operations

25

Building Energy Codes Program

Status Bar

Compliance Bar

Page 26: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Compliance - UA

UA

U-factor x Area for each building

assembly

UA from building conforming to code

compared against your building UA

26

Building Energy Codes Program

Page 27: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Compliance – Performance Alternative

Simulated Performance alternative

Based on simulated performance of your building

compared to an equivalent code building

Requires additional inputs (over UA approach):

building orientation, minimum of four walls having

unique orientations, and a minimum of one roof and

floor

Check Compliance button

Performance alternative considers the whole building

energy performance, whereas UA trade-off method

considers only the thermal conductance of envelope

components

27

Building Energy Codes Program

Page 28: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

REScheck Performance Approach

April 5, 2016 Building Energy Codes Program

28

Limited performance approach

Does not represent the true above code performance

Not to be used for home energy ratings, energy efficiency tax credit calculations or other incentive programs

Page 29: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

REScheck Performance Approach

April 5, 2016 Building Energy Codes Program

29

Limited to building envelope No credit is provided for:

• Overhang projection factor • Air tightness of the building envelope • Sun rooms/passive solar characteristics • Mechanical ventilation effectiveness • Duct leakage • Detailed equipment performance characteristics

Page 30: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

REM/Rate Simulated Performance Report

Building Energy Codes Program

30

Page 31: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

REM/Rate Simulated Performance Report

Building Energy Codes Program

31

Page 32: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Compliance Failing – Helpful Hints

Review building plans to ensure all

components are entered correctly

Confirm takeoffs (areas) are

correct

Confirm insulation values

Double check cavity vs.

continuous entries

Look at UA column (next slide)

32

Building Energy Codes Program

Page 33: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Compliance Failing – Helpful Hints, con’t

33 March 2016

Building Energy Codes Program

Page 34: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Requirements Tab

Mandatory requirements

Air leakage

Building mechanical systems and equipment

Service water heating

Duct construction, insulation, testing

For each requirement, the user

Notes that a code requirement is

Met

Exempt

Does not apply

Notes how compliance for applicable requirements are documented

This information is shown on the report in the “Comments/ Assumptions”

column of the Inspection Checklist

34

Building Energy Codes Program

Page 35: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Reports

File View / Print Report

Choices, choose any or all

Compliance Certificate

Inspection Checklist

Panel Certificate

35

Building Energy Codes Program

Page 36: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Reports

Implement Requirements tab

Inspection checklists set up by phase of

construction

Plan Review

Footing/Foundation

Rough-in

Final

36

Building Energy Codes Program

Page 37: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Reports – Sample Compliance Certificate, con’t

37

Building Energy Codes Program

Verify energy code, location, construction type, and conditioned

floor area

Page 38: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Reports – Sample Compliance Certificate, con’t

38

Verify Values are Consistent with

Plans

Verify Compliance Statement is Signed

Page 39: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Envelope Sample Inspection Checklist

39

Page 40: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace
Page 41: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace
Page 42: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace
Page 43: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace
Page 44: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Envelope Sample Inspection Checklist, con’t

44

Code

Section #

Inspection

Type

Value from

Plans

Value from

Field

Compliance

Building Energy Codes Program

Page 45: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Panel Certificate

45

Building Energy Codes Program

Page 46: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Applying REScheck Software

Jones Residence

Page 47: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Define Building Thermal Envelope

Unexcavated

16' 0

"

24' 0

"

76' 0"

Crawlspace

Conditioned Basement

Conditioned Main Floor

Building Section

WD

BEDROOM #2DEN

LIVINGROOM

NOOK

KITCHEN

3 CAR GARAGE

DECK

MASTERBEDROOM

UTILITY

MSTRBATH

DININGROOM

FAMILYROOM

ENTRY

Page 48: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Ceiling Area (adusted for vaulted ceilings)

Ceiling Area - 2415 sf

WD

BEDROOM #2DEN

LIVINGROOM

NOOK

KITCHEN

3 CAR GARAGE

DECK

MASTERBEDROOM

UTILITY

MSTRBATH

DININGROOM

FAMILYROOM

ENTRY

Page 49: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Exterior Wall Areas

9’ Ceilings

9’ Ceilings 12’ Ceilings

9’ Exterior Walls – 2180 sf

North – 690 sf

South – 600 sf

East – 440 sf

West – 450 sf

12’ Exterior Walls – 689 sf

North – 221 sf

South – 234 sf

East – 52 sf

West – 182 sf

3’ knee walls (between 9’&12’ sections) – 153 sf

West – 69 sf

East – 84 sf

WD

BEDROOM #2DEN

LIVINGROOM

NOOK

KITCHEN

3 CAR GARAGE

DECK

MASTERBEDROOM

UTILITY

MSTRBATH

DININGROOM

FAMILYROOM

ENTRY

Page 50: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Knee Wall Insulation

50 Building Energy Codes Program

9' ceilings 9' ceilings12' ceilings

knee wallknee wall

No, No… Never cut the batts too short

Page 51: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Basement Walls – below grade

>50% below grade = below grade concrete basement wall

Page 52: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Ways to Insulate Basement Walls

52 Building Energy Codes Program

Interior Studs w/batts

Exterior Rigid Foam

Page 53: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Including Rim Joists in the Exterior Wall Area

Page 54: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Above Grade Bsmt Walls (exterior wood) = 837 sf (93’ x 9’)

(entered as wood frame wall. not a basement wall)

Below Grade Bsmt Walls = 1044 sf

Side basement walls = 360 sf

West Wall – 144 sf

East Wall – 216 sf

Back basement wall = 684 sf (76’x9’)

3/0

linen

2/0 2/0

3' x 4' SHWR

2/6

storagehot water

f ir eplace

Bat h

Crawlspace

CrawlspaceUnexcavat ed

Bedroom #4

Bedroom #3

Family Room

Mech/ St orage

16' 0

"

24' 0

"76' 0"

Concret e Pat io

Basement Wall Areas

Above Grade

Bsmt Walls (exterior wood) – 837 sf (93 ln. ft. x 9’ height)

144 sf

684 sf

216 sf

North

Page 55: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Floor Area

Crawlspace Area – 783 sf

Unexcavated

16' 0

"

24' 0

"

76' 0"

Crawlspace

Page 56: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Slab Perimeter

Slab Perimeter – 93 linear feet

Line represents the slab edge to be calculated in linear feet

Unexcavated

16

' 0"

24

' 0"

76' 0"

Crawlspace

Page 57: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Slabs in REScheck

57 Building Energy Codes Program

Page 58: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Building Energy Codes Program

58

Page 59: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Building Energy Codes Program

59

Page 60: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

60

Page 61: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Slab Input Dimensions

April 5, 2016 Building Energy Codes Program

61

Page 62: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Crawlspace Walls

April 5, 2016 Building Energy Codes Program

62

Page 63: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Basement Wall Example 1 – Wood Knee Wall

April 5, 2016 Building Energy Codes Program

63

3’

1’

4’

R13

R5

Create Two Basement Components:

Depth Depth Wall Below of Height Grade Insul Kneewall 3’ 0’ 3’ Concrete 5’ 4’ 5’

Page 64: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Walk-out Basement Wall – Example 2

April 5, 2016 Building Energy Codes Program

64

Example 2: Walk-Out Basement Assume an 8-ft. basement is to be built on a slope so that the front wall is 7 ft. below grade and the rear wall is totally above grade. The ground level along both side walls is sloped so that approximately 50% of each wall is below grade. The rear basement wall will be wood-frame construction with R-19 cavity insulation. The other three walls will be concrete walls with R-10 rigid insulation. All four walls will be fully insulated. Create one basement component for the front wall and enter the following information: Wall Height 8 ft. Depth Below Grade 7 ft. Depth of Insulation 8 ft. The two side walls are at least 50% below grade, so they are entered as a basement wall component. If they were less than 50% below grade, they would be entered as an above-grade wall component. Therefore, create a second basement wall component for the two side walls and enter the following information: Wall Height 8 ft. Depth Below Grade 4 ft. Depth of Insulation 8 ft. The rear wall is fully above grade and should be entered as an above-grade wall using the Wall button. Note that the basement floor along this wall should be considered a slab-on-grade component. Create a slab component using the Floor button and enter the length of the basement floor along this wall in the Gross Area or Slab Perimeter field.

Side walls 50% below grade with R-10 Insulation

8’ Concrete Basement Walls

1’

R-19 Frame Wall

Front Wall

Front Wall

Back Wall

Page 65: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Walk-out Basement Wall - Example 2

April 5, 2016 Building Energy Codes Program

65

Example 2: Walk-Out Basement Assume an 8-ft. basement is to be built on a slope so that the front wall is 7 ft. below grade and the rear wall is totally above grade. The ground level along both side walls is sloped so that approximately 50% of each wall is below grade. The rear basement wall will be wood-frame construction with R-19 cavity insulation. The other three walls will be concrete walls with R-10 rigid insulation. All four walls will be fully insulated. Create one basement component for the front wall and enter the following information: Wall Height 8 ft. Depth Below Grade 7 ft. Depth of Insulation 8 ft. The two side walls are at least 50% below grade, so they are entered as a basement wall component. If they were less than 50% below grade, they would be entered as an above-grade wall component. Therefore, create a second basement wall component for the two side walls and enter the following information: Wall Height 8 ft. Depth Below Grade 4 ft. Depth of Insulation 8 ft. The rear wall is fully above grade and should be entered as an above-grade wall using the Wall button. Note that the basement floor along this wall should be considered a slab-on-grade component. Create a slab component using the Floor button and enter the length of the basement floor along this wall in the Gross Area or Slab Perimeter field.

Create Two Basement Components:

Depth Depth Wall Below of Height Grade Insul Front Wall 8’ 7’ 8’ Side Walls 8’ 4’ 8’

Create one above grade wall for back (walk-out) wall.

Create one slab-on-grade component with length of back wall as linear feet.

Page 66: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Basement Wall Example 3

April 5, 2016 Building Energy Codes Program

66

Example 3: Below-Grade Exterior Insulation An 8-ft. high by 21-ft. wide foundation wall is 7 ft. below grade and is to be insulated using R-5 exterior rigid foam. The insulation will start at grade level and run down to the bottom of the foundation wall. There is 1 foot of uninsulated exposed above-grade wall. The wall has no openings. This wall is entered by creating two basement wall components. The first component will be used for entering the uninsulated above-grade portion of the wall. Click the Basement button and enter the following information: Wall Height 1 ft. Depth Below Grade 0 ft. Depth of Insulation 0 ft. The second component will be used for entering the insulated below-grade portion of the wall. Click the Basement button again and enter the following information: Wall Height 7 ft. Depth Below Grade 7 ft. Depth of Insulation 7 ft. After these components have been created, enter the gross area of each component and the R-value of the insulation used on the below-grade component.

Create Two Basement Components:

Depth Depth Wall Below of Height Grade Insul Uninsulated 1’ 0’ 0’ Insulated 7’ 7’ 7’ Areas and R-Values must also be entered.

Page 67: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Insulation Levels

Roof/Ceiling

Walls (above and below grade)

Floor over vented crawl space

Slab-on-grade

Page 68: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

Window/ Door Area

North

South

East

West

Glass Doors <50% glass - 40 sf; U-factor = 0.50

North – 40 sf

Opaque Doors - 40 sf; U-factor = 0.50

South – 40 sf

Window Area - 533 sf

North – 369 sf

South – 149 sf

West – 15 sf

U-factor = 0.35

U-factor = 0.27

SHGC = .25

Page 69: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace
Page 70: REScheckTM Basics...Panel Certificate 45 Building Energy Codes Program . Applying REScheck Software Jones Residence . Define Building Thermal Envelope Unexcavated " " 76' 0" Crawlspace

70