25
ABSTRACT The purpose of this report is to document the Air Resources Board=s (ARB=s) evaluation and verification of the air quality performance claims made by the Curtiss-Wright Flow Control Corporation (CWFC) concerning its Model 100 and 120 flow-control valves. Upon successful completion of the requirements associated with the ARB=s Equipment and Process Precertification Program (Equipment Precertification Program), a report is issued with two companion documents: 1) a certificate; and 2) an Executive Order. These companion documents serve as official records that the ARB has independently verified the performance claims presented in this report. Certificates earned under the ARB=s Equipment Precertification Program are valid for three years from the date issued, presuming the holder of the certificate complies with: 1) the terms and conditions identified in this report; and 2) the general requirements discussed in the Equipment Precertification Program Guidelines and Criteria. In addition, Executive Orders issued under the Equipment Precertification Program identify requirements necessary to retain a valid certificate. The CWFC has been producing flow-control valves for nuclear power generation facilities since the early 1970's. The flow-control valves, which do not employ a stem, packing, or bellows, were designed to meet the requirements of the Nuclear Regulatory Commission. The CWFC plans to further expand the use of its valves into other industries and believes that becoming certified under the ARB=s Equipment Precertification Program will assist with meeting this objective. As part of its Equipment Precertification application package, the CWFC requested that the ARB evaluate three proposed performance claims with respect to the ability of the subject flow-control valves (Models 100 and 120) to control fugitive emissions of volatile organic compounds. As part of the precertification evaluation, the ARB assisted the CWFC in designing a test protocol to verify the proposed claims. Radian International Limited Liability Company (Radian) was chosen by the CWFC to conduct the testing after the ARB approved the test protocol. During the test, a minor modification to the Model 120 flow-control valve was requested by the CWFC. The ARB approved the change and testing continued as originally planned. After review of the final test results, in conjunction with the other documents discussed throughout this report, the ARB recommends that precertification certificates be issued to the CWFC for flow-control valve Models 100 and 120. Applicant: Curtiss-Wright Flow Application Number: 980601 Control Corporation Executive Order: 698-016-93109-12 1966E Broadhollow Road Date: June 7, 2001 East Farmingdale, NY 11735-1768 Equipment: Flow-Control Valve Model 100 Flow-Control Valve Model 120 Contact: Mr. Steven R. Pauly Title: Technical Support Manager Phone: (516) 293-3800, extension 647 Fax: (516) 293-4949 E-Mail: [email protected] Website: www.trc.thomasregister.com ARB Staff Contact: Todd Sterling ARB Website: www.arbis.arb.ca.gov/eqpr/eqpr.com

Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Embed Size (px)

Citation preview

Page 1: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

ABSTRACT

The purpose of this report is to document the Air Resources Board=s (ARB=s) evaluation and verification of the air quality performance claims made by the Curtiss-Wright Flow ControlCorporation (CWFC) concerning its Model 100 and 120 flow-control valves. Upon successfulcompletion of the requirements associated with the ARB=s Equipment and Process PrecertificationProgram (Equipment Precertification Program), a report is issued with two companion documents: 1)a certificate; and 2) an Executive Order. These companion documents serve as official records that theARB has independently verified the performance claims presented in this report.

Certificates earned under the ARB=s Equipment Precertification Program are valid for threeyears from the date issued, presuming the holder of the certificate complies with: 1) the terms andconditions identified in this report; and 2) the general requirements discussed in the EquipmentPrecertification Program Guidelines and Criteria. In addition, Executive Orders issued under theEquipment Precertification Program identify requirements necessary to retain a valid certificate.

The CWFC has been producing flow-control valves for nuclear power generation facilitiessince the early 1970's. The flow-control valves, which do not employ a stem, packing, or bellows, weredesigned to meet the requirements of the Nuclear Regulatory Commission. The CWFC plans tofurther expand the use of its valves into other industries and believes that becoming certified under theARB=s Equipment Precertification Program will assist with meeting this objective.

As part of its Equipment Precertification application package, the CWFC requested that theARB evaluate three proposed performance claims with respect to the ability of the subject flow-controlvalves (Models 100 and 120) to control fugitive emissions of volatile organic compounds. As part ofthe precertification evaluation, the ARB assisted the CWFC in designing a test protocol to verify theproposed claims. Radian International Limited Liability Company (Radian) was chosen by the CWFCto conduct the testing after the ARB approved the test protocol. During the test, a minor modificationto the Model 120 flow-control valve was requested by the CWFC. The ARB approved the change andtesting continued as originally planned. After review of the final test results, in conjunction with theother documents discussed throughout this report, the ARB recommends that precertificationcertificates be issued to the CWFC for flow-control valve Models 100 and 120.

Applicant: Curtiss-Wright Flow Application Number: 980601

Control Corporation Executive Order: 698-016-93109-12 1966E Broadhollow Road Date: June 7, 2001 East Farmingdale, NY 11735-1768

Equipment: Flow-Control Valve Model 100 Flow-Control Valve Model 120

Contact: Mr. Steven R. Pauly Title: Technical Support ManagerPhone: (516) 293-3800, extension 647 Fax: (516) 293-4949E-Mail: [email protected] Website: www.trc.thomasregister.com

ARB Staff Contact: Todd Sterling ARB Website: www.arbis.arb.ca.gov/eqpr/eqpr.com

Page 2: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

CALIFORNIA ENVIRONMENTAL PROTECTION AGENCYAIR RESOURCES BOARD

EQUIPMENT PRECERTIFICATION PROGRAM

Evaluation of the Air Quality Performance Claims for Curtiss-Wright Flow-Control Valves:

Models 100 and 120

June 1998

Page 3: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Table of Contents

Contents Page

I. Introduction 1

A. Fugitive Emissions of Volatile Organic Compounds 1 B. Organization of Evaluation Report 1

II. General Information 1

A. Equipment Precertification Program Background 2B. Relationship to Air Quality 2C. Health and Environmental Impacts 3D. Manufacture / Ownership Rights 3

III. Summary of Scope 3

IV. Statement of Claims 4

V. Materials Available for Evaluation 4

VI. Technology Description 6

VII. Technical Evaluation 11

A. Design Review 11B. Description of Test Protocol 11

VIII. Evaluation of Claims 12

IX. Test Results 14

X. Quality Management 17

XI. Environmental and Economic Benefits 17

XII. Recommendations 17

XIII. Suggested Operating Conditions 18

XIV. Precertification Conditions 19

XV. Figures

1. Curtiss-Wright Flow Control Valve Model 100 8

Page 4: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

2. Curtiss-Wright Flow Control Valve Model 120 83. Curtiss-Wright Flow Control Valve Model 120 Cutaway 94. Curtiss-Wright Flow Control Valve Cutaway 105. Curtiss-Wright Flow Control Valve Cycle Test Loop 13

XVI. Appendices

Appendix A - Test Results for Curtiss-Wright Flow-Control Valve Model 120Appendix B - ATesting to the Fugitive Emission Standards,@ Valve Magazine, fall,

1997.

Page 5: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

I. INTRODUCTION

This report discusses the technology usedby the Curtiss-Wright Flow ControlCorporation (CWFC) in the design of itsflow-control valves, the performance claimsto be verified by the Air Resources Board(ARB), the test procedures used, the testresults, and the findings andrecommendations of ARB staff concerningthe flow-control valves evaluated.

A. Fugitive Emissions of Volatile Organic Compounds

The control of fugitive volatile organiccompounds (VOC) emissions from flow-control valves is part of the overall strategy toachieve and maintain healthy air quality inCalifornia. Through a series of complexatmospheric reactions, VOCs contribute to theformation of ground-level ozone. As such,federal, state and local air quality programsinclude strategies to reduce fugitive emissionsof VOCs into the atmosphere. These controlstrategies rely heavily on promoting thedevelopment and use of continuallyimproving technologies, as well as periodicinspection and maintenance procedures toensure that performance is maintained.

The CWFC believes that its flow-controlvalve Models 100 and 120 are effective atreducing fugitive VOC emissions from avariety of industrial applications. As such,the CWFC submitted an application under theARB=s Equipment Precertification Program. As part of its application package, the CWFCrequested verification of the claims that itsflow-control valve Models 100 and 120reliably reduce VOC fugitive emissions.

B. Organization of this Report

This report is organized into several

sections. The first section, GeneralInformation, provides backgroundinformation on the ARB=s precertificationprogram, as well as the CWFC flow-controlvalves being evaluated. The next foursections: Summary of Scope; Statement ofClaims; Materials Available for Evaluation;and Description of Technology discuss thebreadth of our evaluation, the performanceclaims for the flow-control valves, theinformation that we relied on to conduct ourevaluation, and a detailed description of the CWFC=s flow-control valves (Models 100 and120).

The following three sections: TechnicalEvaluation; Evaluation of Claims; and TestResults; present detailed information on ourtechnical review and assessment of theperformance of the flow-control valves. Thesections entitled: Quality Management andEnvironmental and Economic Benefitsprovide supporting information on the TheCWFC=s procedures to produce values whichmeet the company=s claims. These sectionsalso provide a brief assessment of thepotential environmental and economicimpacts of the technology.

Finally, the remaining sections:Recommendations; Suggested OperatingConditions; and Precertification Conditionsdiscuss the ARB staff=s determination of theperformance of the valves relative to thecompany=s claims. These sections alsoprovide some general guidance with respectto air quality permitting considerations aswell as specific conditions that must be metfor the certificate to remain valid for threeyears. The Appendices contain additionalinformation supporting the evaluationdocumented in this report.

II. GENERAL INFORMATION

Page 6: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 2

Under the regulations established by theprogram, equipment or processes eligible forthe Equipment Precertification Program must:1) have an air quality benefit; 2) becommonly-used or have the potential to becommonly-used in the near future (marketready); and, 3) not pose a significant potentialhazard to public health and safety and theenvironment. Furthermore, to be eligible forthe program, applicants for the program mustdemonstrate that they have sufficient controlover the manufacture of the equipment orprocess to ensure that they can consistentlyand reliably produce equipment whichperforms at least as well as that considered aspart of this evaluation.

A. Equipment Precertification Program Background

The Equipment Precertification Programis a voluntary statewide program formanufacturers of commonly-used equipmentor processes. A precondition for entry intothe program is that the equipment has an airquality benefit. On June 14, 1996, the ARBadopted section 91400 of the California Codeof Regulations which incorporates the Criteriafor Equipment and Process Precertification. The regulation and Criteria were approved bythe California Office of Administrative Lawon October 31, 1996 and became effective onNovember 30, 1996.

Under the Equipment PrecertificationProgram, manufacturers request that the ARB conduct an independent third-partyverification of performance claims whichfocus on the air quality benefits of its

equipment or process. If the claim is verified,the manufacture is free to refer to the resultsof the ARB=s evaluation in its marketingliterature. Upon successful completion of theverification process, the applicant may alsorequest that the ARB notify specific airpollution control and air quality managementdistricts (districts) in California of the ARB=sdetermination. As a result of the ARB=snotification, the district has an advancedopportunity to become familiar with theperformance of the equipment or process.

On June 3, 1996, the ARB received arequest from the CWFC that ARB determineif its flow-control valves Models 100 and 120were eligible for the EquipmentPrecertification Program. After receivingconfirmation from the ARB that the flow-control valves were eligible for the program,the CWFC submitted a precertificationapplication package to the ARB. Based onour initial review of the application package,we advised the CWFC that emissions testingwould be needed to support the proposedclaims. In response, the CWFC contractedwith Radian International to perform testingof the flow-control valves Models 100 and120. Prior to conducting the tests, the ARBstaff approved the emissions test protocol. Once the tests were completed, we evaluatedthe results along with other informationconcerning the past performance of the flow-control valves to determine whether theclaims were verifiable.

B. Relationship to Air Quality

In an effort to make progress towardsattaining healthy air quality in California,

regulations restrict fugitive emissions ofVOCs from a broad spectrum of activities. The reduction of fugitive VOC emissionsfrom flow-control valves is one part ofCalifornia=s clean air strategy. Typically,

Page 7: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 3

flow-control valves have a valve stem, severalseals and bellows. All are common locationsfor VOC emissions. As such, local air districtrules and regulations specify emission limitsand inspection schedules (see section XIV.Suggested Operating Conditions). Becausethe use of the CWFC flow-control valvesModels 100 and 120 is claimed to reducefugitive VOC emissions, the ARB evaluatedthe valves as air pollution control equipment.

C. Health and Environmental Impacts

As part of our evaluation, staff conducteda cursory review of the potentialenvironmental impacts associated with theCWFC=s flow-control valves Models 100 and120. Based on this review, we concluded thatthe valves would not likely present health orenvironmental impacts different from thoseassociated with valves currently in wide usethroughout California. Please note that theCWFC is required to meet all applicablehealth and safety standards with respect to themanufacture, installation, use, andmaintenance of its flow-control valvesModels 100 and 120.

D. Manufacture / Ownership Rights

The recommendations in this report arecontingent upon the CWFC Corporationhaving the legal rights to produce and/ormarket flow-control valve Models 100 and120. The CWFC documented its ownership ofthese rights in a letter to the ARB dated July14, 1997, which stated, ACurtiss-Wright FlowControl Corporation confirms that we retainthe ownership rights to manufacture orotherwise produce the equipment to beprecertified, both in the form ofprecertification conditions and therequirements in the Criteria for Equipmentand Process Precertification, upon the

production and marketing of the equipment.@ III. SUMMARY OF SCOPE

The CWFC claims that the use of itsflow-control valve Models 100 and 120 willcontrol fugitive VOC emissions associatedwith the handling and storage ofhydrocarbons. Most fugitive VOC emissionsresulting from the handling and storage ofhydrocarbons are leaks from processequipment and evaporation from open areas. Generally, the control of fugitive VOCemissions involves minimizing leaks andspills through the used of efficient airpollution control equipment (including state-of-the-art flow-control valves), modifyingprocesses, increasing monitoring andinspection frequency, and improvingmaintenance practices.

For purposes of this report, VOCs areconsidered to be any compound containing atleast one atom of carbon, except exemptcompounds. Exempt compounds include:

carbon monoxide carbon dioxidecarbonic acid metallic carbides or carbonates ammonium carbonate1,1,1-trichloroethane methylene chloride trichlorofluoromethane (CFC-11) dichlorodifluoromethane (CFC-12) chlorodifluoromethane (CFC-22) trifluoromethane (CFC-23) trichlorotrifluoroethane (CFC-113) dichlorotetrafluoroethane (CFC-114) chloropentafluoroethane (CFC-115) dichlorotrifluoroethane (CFC-123) 2-chloro-1,1,1,2-tetrafluoroethane(HCFC-124) pentafluoroethane (HFC-125)

Page 8: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 4

1,1,2,2-tetrafluoroethane (HFC-134) tetrafluorethane (HFC-134a) dichlorofluoroethane (HCFC-141b) chlorodifluoroethane (HCFC-142b) 1,1,1-trifluoroethane (HFC-143a) 1,1-difluoroethane (HFC-152a)

and the following four classes ofperfluorocarbon (PFC) compounds:

1. cyclic, branched, or linear, completelyfluorinated alkanes;2. cyclic, branched, or linear, completelyfluorinated ethers with unsaturations;3. cyclic, branched, or linear, completelyfluorinated tertiary amines with no unsaturations; and4. saturated perflorocarbons containing sulfurand with sulfur bonds only to carbon andfluorine atoms.

IV. STATEMENT OF CLAIMS

The following are the claims verified by ARB staff concerning the CWFC flow-controlvalve Models 100 and 120. The verificationof these claims is predicated on thepresumption that the flow-control valves areinstalled and operated in accordance with themanufacturer=s installation and operatinginstructions.

1. The Curtis Wright Flow ControlCorporation Model 100 flow-controlvalve is a closed system without thepotential for fugitive VOC emissions.

2. The Curtiss-Wright Flow ControlCorporation Model 120 flow-controlvalve has a calculated fugitive VOCemission rate that is no greater than5.0E-8 kilograms per hour (.001pounds per year).

3. The Curtiss-Wright Flow ControlCorporation Model 120 flow-controlvalve showed no performancedegradation after 112,109 cycles withrespect to fugitive VOC emissions.

22. MATERIALS AVAILABLE FOREVALUATION

The following materials were used aspart of our evaluation of the CWFC=s flow-control valve Models 100 and 120:

1. Request to Determine Eligibility forARB Precertification of Equipment orProcesses from Mr. James D. White ofthe Curtiss-Wright Flow ControlCorporation to Chairman John Dunlap ofthe ARB transmitting the Determinationof Eligibility application, June 3, 1996.

2. Application for the ARB EquipmentPrecertification Program from Mr. JamesD. White of the Curtiss-Wright FlowControl Corporation to Mr. Raymond E.Menebroker of the ARB transmitting theapplication for the ARB precertificationprogram, April 11, 1997.

3. Curtiss-Wright Flow Control Corporation, General Reference Book for Model 100 "Leakless@Control Valves and Model 120 ALeakproof@ Control Valves, September 22, 1997.

4. Target Rock Corporation, QualityAssurance Manual, Revision E,April 2, 1996.

5. Memorandum from Mr. Raymond E.Menebroker of the ARB=s StationarySource Division to Mr. George Lew ofARB=s Monitoring and Laboratory

Page 9: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 5

Division requesting assistance in theevaluation of a testing protocol for theCWFC flow-control valves models 100and 120, June 3, 1997.

6. Letter from Mr. Richard Corey of the ARB to Mr. Kurt Walderon of the Chevron Pipe Line Company, July 25, 1997, thanking Mr. Walderon for the field tour where the CWFC flow control valve Model 120 is in use.

7. Letter from Mr. Steven R. Pauly of theCurtiss-Wright Flow Control Corporationto Mr. Richard Corey of the ARBtransmitting the CWFC precertificationapplication to the ARB, July 14, 1997.

8. Letter from Mr. Steven R. Pauly of theCurtiss-Wright Flow Control Corporationto Mr. Glenn B. Simjian of the ARBproviding clarification of items in theCWFC application, July 28, 1997.

9. Letter from Mr. Richard Corey of theARB to Mr. Steve R. Pauly of theCurtiss-Wright Flow Control Corporationconfirming receipt of the applicationpackage, July 31, 1997.

10. Code of Federal Regulations, Title 40,Part 60, Appendix A, Reference TestMethod 21, Determination of VolatileOrganic Compound Leaks, U.S.Government Printing Office Washington,D.C., June 22, 1990.

11. Air Resources Board, California CleanAir Act Guidance for the Determinationof Reasonable Available ControlTechnology for The Control of FugitiveEmissions of Volatile OrganicCompounds from Oil and Gas Productionand Process Facilities, Refineries,

Chemical Plants, and Pipeline TransferStations, December 8, 1993.

12. Letter from Mr. Steven R. Pauly of theCurtiss-Wright Flow Control Corporationto Mr. Glenn B. Simjian of the ARBtransmitting the testing protocol for flow-control valve Models 100 and 120,September 12, 1997.

13. Letter from Mr. George Lew of ARB=s Monitoring and Laboratory

Division to Mr. Raymond E. Menebroker of ARB=s Stationary Source Division approving Curtiss-

Wright=s testing protocol,September 22, 1997.

14. Letter from Mr. Richard Corey of theARB to Mr. Steven R. Pauly of theCurtiss-Wright Flow Control Corporationapproving the CWFC=s testing protocolfor flow-control valve Models 100 and120, September 26, 1997.

15. Letter from Mr. Steven R. Pauly of theCurtiss-Wright Flow Control Corporationto Mr. Richard Corey ofthe ARB requesting approval to modify flow-control valve Model 120, November 14, 1997.

16. Letter from Mr. Richard Corey of theARB to Mr. Steven R. Pauly of theCurtiss-Wright Flow Control Corporationapproving the modification to flow-control valve Model 120, November 18,1997.

17. Report from Mr. Steven R. Pauly of theCurtiss-Wright Flow Control Corporationto Mr. Richard Corey of the ARBdocumenting the testing results for flow-control valve Models 100 and 120,January 13, 1998.

Page 10: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 6

18. Curtiss-Wright Flow ControlCorporation, Pre-Certification Report forModel 100 and 120 Control Valves,Fugitive Emissions Evaluation and TestProgram (Project 97X-130 TRP No.6319), January 13, 1998.

For information on how to obtain thesematerials, please contact the ARB at thenumber provided at the beginning of thisdocument.

VI. TECHNOLOGY DESCRIPTION

The CWFC flow-control valve Models100 and 120 are a departure from the standardair-or motor-operated valve design typicallyused for the storage and handling ofhydrocarbons. Specifically, the Models 100and 120 flow-control valves are solenoid-actuated; they do not use a stem, packing, orbellows. Further, flow-control valve modelsisolate all moving parts within the processpressure boundaries. The Model 100 flow-control valve is completely seal-welded,whereas the Model 120 flow-control valve isseal-welded except for one body-to-bonnetjoint sealed with an O-ring (figure 1 and 2).

The CWFC flow-control valves are usedto control the flow of liquids, steam, or gases. These valves are solenoid-actuated andemploy a pilot disc to assist actuation. Thetwo basic designs are on/off isolation valvesand modulating control valves each with hardor soft seats and in either fail open or failclosed configurations. As shown in figure 3(typical), the stainless steel bonnet assembly,

which encloses the moving parts (plunger,discs, connecting rods, and part of theposition sensor assemblies), is either threadedand seal-welded to the valve body (Model100) or bolted with an O-ring seal to the valvebody (Model 120). The solenoid assembly,electrical hardware, and other parts of theposition sensor assembly, are mounted on theoutside of the bonnet assembly. Modulatingcontrol valves use a linear variabledifferential transformer (LVDT) as a positionsensor (figure 3). On/off isolation valves usereed switch assemblies activated by a magnetassembly (figure 4) inside the bonnet forposition indication. Both the Model 100 and120 flow-control valves are designed tooperate on AC or DC voltage.

As shown in figure 4, operation of theflow-control valves occurs when the solenoidassembly is energized. It develops a magneticfield, which lifts the plunger. This pulls thepilot off its seat in the main disc opening thevent port. This changes the differentialpressure between the top and bottom surfacesof the main disc, which raises the main disc inservo motion to the pilot, and allows the fluidat the inlet to flow.

When the solenoid assembly is de-energized,eliminating the magnetic force on the plunger,the return spring seats the pilot disc in thevent port. As shown in figure 4, with thevent ports closed, the control pressure abovethe main disc increases. When the controlpressure increases sufficiently, the combinedinfluence of the differential

Page 11: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 7

Page 12: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 8

CURTISS-WRIGHT FLOW CONTROL VALVE MODEL 120 CUTAWAY

Page 13: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 9

Page 14: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 10

pressure and the return spring exerts adownward force on the main disc, seating it inthe body, thereby closing the valve.As the main disc moves, the motion istransmitted through the plunger to the position sensor element inside the pressureboundary. The internal movement is sensed by the external element of the position sensorassembly to signal the valve=s position. In theabsence of differential pressure, the solenoidcoil develops sufficient force to fully open thevalve directly.

The CWFC flow-control valve Models100 and 120 differ from standard flow-controlvalves in several respects. Specifically, theModel 100 and 120 valves do not have astem, packing, or bellows. Furthermore, theModel 100 does not have a bonnet flange. These components are eliminated becausethey are traditionally weak spots for leaks,fugitive emissions, or failure. The CWFCbelieves that by replacing these components,leaks from the following areas are eliminated:

1. Stem seal - this is a dynamic (moving) seal between the packing and the externally-actuated stem. The movement may be rotational, linear, or a combination of the two. This is the most common point where valves leak. The stem leakage rate almost always contributes the bulk of the total fugitive emissions.

2. Packing gland - this is a static seal between the packing and the valve body. This is also a common leak point, and as such can influence fugitive emissions from flow-control valves.

3. Bellows - the bellows is a flexible barrier

that provides additional protection againstfugitive emissions from typical valves. However, over time bellows can developcracks leading to leaks.

In addition to not having a stem, packinggland, or bellows, the CWFC=s Model 100flow-control valve does not have a bonnetflange. The bonnet flange is a static sealbetween the upper and lower sections of thevalve. It is typically a flanged connection, butmay sometimes be screwed or welded. Bonnet flange leaks are less common thanleaks from stem seals and packing glands.

The CWFC=s flow-control valve Model120 has a bonnet joint-sealed with an O-ring.As this is a potential location for fugitiveemissions, the Model 120 was subjected tothe testing procedures described in SectionVII. VII. TECHNICAL EVALUATION

A. Design Review:

Radian International, as a contractor to the CWFC, performed an independent designreview of the flow-control valves Models 100and 120. Based upon the materials evaluatedas part of this report (see section V, MaterialsAvailable for Evaluation), including thedesign review conducted by RadianInternational, ARB staff has verified thefollowing:

Model 100

It was determined that it was not necessary totest the Model 100 (figure 1) flow-controlvalve for fugitive VOC emissions because itis completely seal-welded. The CWFCrequested that the Model

100 flow-control valve be verified as equivalent (from an emissions perspective) to

Page 15: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 11

four welded connections. In short, properly-welded connections do not have fugitive VOCemissions. As such, when properly installedand operated, the Model 100 flow-controlvalve would not have fugitive VOCemissions.

Model 120

The Model 120 flow-control valve isseal-welded except for one body-to-bonnetjoint (figure 2), sealed with one O-ring. Thisfeature should enable the valve to reducefugitive emissions as compared to moretypical valves. The CWFC requested that theModel 120 flow control valve be verified asequivalent (from an emission perspective) tothree welded connections and one flangedconnection. The Model 120 flow-controlvalve that was tested on October 29, 1997 hadtwo O-ring seals. One of the O-ring seals wasat the main body-to-bonnet joint as describedabove. A second (figure 3) O-ring seal waslocated at the indicator tube-to-bonnet joint.However, on November 14, 1997, the CWFCnotified the ARB that it intended to replacethe second O-ring with a seal-weld. Afterreceiving approval to modify the test planfrom the ARB, a second test reflecting themodification was performed on December 17,1997.

Figure 3 is a cut away view of the flow-control valve Model 120, showing thepressure boundary, location of the seal welds,and the O-ring. These are areas whereemissions could possibly occur. For Model120 flow-control valves, three of fourpressure boundary joints are completely seal-welded. However, the body-to-bonnet joint issealed with an elastomer O-ring (the pressureboundary is shaded in figure 3). All seals arestatic seals; there are no moving seals like

conventional stem seals. In addition, all ofthe joints are flanged seals or are welded. The flanged joints are highly engineered andcontrolled to eliminate the lateral stresses thatexist on similar flanged connectors in plantpiping systems and can contribute toconnector emissions.

B. Description of Test Protocol

Prior to conducting an emissions test offlow-control valve Model 120, we requestedthat a test protocol be prepared. We receiveda test protocol from the CWFC on September12, 1997. We approved the test protocol andnotified the CWFC of our determination onSeptember 26, 1997.

Radian International used the UnitedStates Environmental Protection Agency(U.S. EPA) Reference Test Method 21(Determination of Volatile OrganicCompound Leaks) for the testing of flow-control valve Model 120. The testing ofModel 120 consisted of two phases. The keyelements of the two phases of the tests are asfollows:

Phase I - Pre-Acceleration Wear Testing(Model 120):

1. Pressurize the valve to 300 pounds per square inch gas (psig) with methane 2. Screen the valve for any sign of leakage using U.S. EPA Reference Test Method 213. Perform a blow-through bag test tomeasure leakage 4. Screen the valve for any sign of leakage using U.S. EPA Reference Test Method 215. Depressurize the valve and return it to the manufacturer for accelerated wear testing and modifications.

Phase II - Post-Acceleration Wear Testing

Page 16: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 12

(Model 120):

1. Pressurize the valve to 300 psig with methane 2. Screen the valve for any sign of leakage using U.S. EPA Reference Method 213. Perform a blow-through bag test tomeasure leakage 4. Screen the valve for any sign of leakage using U.S. EPA Method 21.

Phase I of the testing of Model 120 wasperformed on October 29, 1997. The valvewas then sent back to the CWFC where themodifications (o-ring replaced with seal weld)were made and a 112,109 valve cycle test wasperformed (figure 5). After the cycle test wascompleted, the valve was returned to RadianInternational for Phase II of the test onDecember 17, 1997.

Phase II of the test was identical to PhaseI for the purposes of the emissions testing.The purpose of the second phase of testingwas to verify that the Model 120 flow-controlvalve had no increase in fugitive emissionsafter 112,109 total cycles. Methane was usedin this test because it is a light-endhydrocarbon and, as such, is an excellentsurrogate for detecting fugitive VOCemissions.

The accelerated wear test was initiatedonce the valve was returned to the factoryafter the first phase of testing. The valve wasinstalled in the test loop shown in figure 5. The valve was pressurized with shop air atroom temperature at approximately 100 psig. The outlet needle valve was throttled down tolimit outlet flow as necessary. The valve=sposition indicator circuit was connected to asystem that relayed the position signal to acycle counter. The valve was checked at least

three times a day to record the number ofcycles completed. An accumulator, tostabilize supply pressure, and a muffler werealso included in the testing loop. The test wasadministratively terminated when 112,109cycles were achieved.

VIII. EVALUATION OF CLAIMS:

This section presents additionalinformation relating to the claims verified byARB staff as part of its evaluation. As statedearlier, the ARB staff evaluation andrecommendations, as presented in this report,are predicated on the expectation that theflow-control valves are installed and operatedin accordance with the manufacturer=sinstructions.

To assist the reader, each of the claimsidentified on page 4 (IV. Statement ofClaims) are repeated in this section. Following each claim are supportingcomments which may be helpful ininterpreting the significance of each claim.

1. The Curtiss-Wright Flow Control Corporation Model 100 flow-control valve is a closed system without the potential for fugitive VOC emissions.

Based on our evaluation, the CWFC Model 100 flow-control valve should betreated as four welded connections from the perspective of fugitive VOC emissions. Given that properly-weldedconnections form a complete seal, nofugitive VOC emissions would be expected. As such, the valve would not be expected to require monitoring beyondthat appropriate for welded connections.

Page 17: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 13

Page 18: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 14

2.The Curtiss-Wright Flow Control Corporation Model 120 flow-control valve has a calculated fugitive VOCemission rate that is no greater than5.0E-8 kilograms per hour (.001poundsper year).

The emission rate presented in the claimis an upper-bound estimate (i.e., actualemissions are expected to be lower). Theupper-bound emission rate was calculated byconsidering the fact that the test gas(methane) used as a surrogate for fugitiveVOC emissions was not detected at the lowerlimit of detection (1 ppm) of the analyzerused in the emissions test of the CWFCCorporation Model 120 flow-control valve. As is typically the case for emission resultswhich are below the limit of detection, one-half of the detection limit was used in thecalculation of a fugitive VOC emission ratefor the Model 120 flow-control valve.

From the perspective of fugitive VOCemissions, the CWFC Model 120 flow-control valve should be treated as a seal-welded unit with one flanged 3. The Curtiss-Wright Flow Control

Corporation Model 120 flow-control valve showed no performance

degradation after 112,109 cycles with respect to fugitive VOC emissions.

This was documented by our evaluationof the emissions test results. Specifically,after 112,109 cycles, methane was notdetected in any of the tests of the O-ring sealin the bonnet-to-body joint.

IX. TEST RESULTS:

The testing protocol for the CWFC flow-control valve Model 120 employed the U.S.

EPA Reference Test Method 21 inconjunction with the procedure described inthe Protocol for Equipment Leak EmissionsEstimates (United States EnvironmentalProtection Agency, Publication Number EPA-453/R-39-026). The CWFC received theARB=s approval on September 26, 1997, touse the test protocol in the emissions testing. The summary of the test results submitted bythe CWFC are presented in Appendix A.

The bonnet-to-body joint of the CWFCModel 120 flow-control valve was tested inthe Radian Corporation laboratories beforeand after an accelerated wear test consistingof 112,109 open/close cycles. Two bag testswere performed before the accelerated weartest and three bag tests were performed afterthe accelerated wear test. One pre-acceleration bag test was conducted at anitrogen flow rate of 2 liters per minute, whilethe other was conducted at 7 liters per minute. The post-acceleration bag tests were allconducted at nitrogen flow rates ofapproximately 2 liters per minute.

The purpose of the accelerated wear testwas to demonstrate that the CWFC Model120 flow-control valve showed nodegradation, with respect to emissions, after aspecific amount of use. An article appearingin Valve Magazine, entitled ATesting to theFugitive Emission Standards@, (included inAppendix B) was the basis for selection of the number of cycles in the test. The articlereferred to the use of 100,000 cycles as anappropriate value to use to evaluateaccelerated wear in high performance controlvalves.

Page 19: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 15

A Radfisch total hydrocarbon analyzerwith a lower detection limit of 1 part permillion (ppm) was used to detect hydrocarbons. Methane was chosen as thetest gas because, as a light-end hydrocarbon,it is an excellent surrogate for detectingfugitive VOC emissions. Methane was notdetected at the lower limit of detection (1ppm) of the analyzer in any of the pre-acceleration or post-acceleration bag tests. Using the ARB=s standard approach forevaluating emissions data which are belowthe detection limit, one-half of the detectionlimit was used in the calculation of thefugitive VOC emission rate for the Model 120flow-control valve.

Test run number F3 was chosen as thebasis for the emissions calculation because itrepresented the most conservative (highest)estimated emission rate. A calculation of theemission rate for the pre-accelerated wear testis presented on the following page.

In summary, the CWFC flow-controlvalve Model 120 valve had no detectableemissions before or after the accelerated weartest. As stated in the claims section of thisreport, the resulting VOC fugitive emissionrate from the bonnet-to body joint wascalculated to be no greater than 5.0E-8kilograms per hour, which is equivalent toapproximately 0.001 pounds per year.

Page 20: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 16

Page 21: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 17

24. QUALITY MANAGEMENT

The CWFC has developed extensive qualitymanagement practices and standards for itsflow-control valve Models 100 and 120. Thestandards are described in the CWFC, TargetRock Corporation Quality Assurance Manual,Revision E, April 2 1997. This Manualincorporates the provisions of Sections I andVIII of the American Society of MechanicalEngineers (ASME) Boiler and PressureVessel Code. The Manual containsestablished quality management practices forthe following areas:

-- Design, Drawing, Specification -- Material Control and Procedure Control-- Process Control-- Inspection and Testing-- Control of Measuring--Valve Stamping and Test Equipment Sealing -- Record Retention-- Forms

The CWFC=s Quality ManagementProgram was reviewed by ARB staff as partof our evaluation of flow-control valvesModels 100 and 120. As a result of our evaluation, ARB staff has determined that thequality management program is sufficientlycomprehensive to support certifying theCWFC flow-control valve Models 100 and120. XI. ENVIRONMENTAL AND ECONOMIC BENEFITS

As part of our review, we evaluated the

potential air quality impacts of the flow-control valve Models 100 and 120. The useof the flow-control valves will likely result ina reduction of fugitive VOC emissions whencompared to traditional valves with a stem,packing, and bellows.

As part of our evaluation, we also contacted current users of the CWFC flow-control valves. The users of the flow-controlvalves, which were from various industries,indicated that the flow-control valves have asignificantly longer life, with less requiredmaintenance, than conventional flow-controlvalves. The ARB staff also visited apetroleum bulk terminal where one of theflow-control valves has been usedsuccessfully for several years. It should benoted that under certain conditions, emissionreductions resulting from the installation ofthe CWFC flow-control valves may beeligible for emission reduction credits. Therefore, appropriate air districts inCalifornia should be consulted to determinethe eligibility for any emission reductioncredits.

XII. RECOMMENDATIONS

After evaluating the informationdiscussed in this report, ARB staff recommends that the CWFC flow- controlvalve Models 100 and 120 be certified underits Equipment Precertification Program. Specifically, we have independently verifiedthe claims of the CWFC concerning its flow-control valves Models 100 and 120, aspresented in the claims section of this report.

By accepting certification under theARB=s program, the CWFC assumes, for theduration of the three-year certification period,responsibility for maintaining the quality of

the manufactured equipment and materials ata level equal to or better than was provided toobtain this certification. Certification underthe ARB=s program is also contingent on the

Page 22: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 18

recipient agreeing to be subject to qualitymonitoring by the ARB as provided by law.

The ARB makes no express or impliedwarranties as to the performance of themanufacturer=s product or equipment. Nor,does the ARB warrant that the manufacturer=sproduct or equipment is free from any defectsin workmanship or material caused bynegligence, misuse, accident, or other causes. The ARB staff believes, however, that the CWFC=s flow-control valves Models 100 and120 will achieve performance levels presentedin the claims section of this report. Ourdetermination is based on our evaluation ofthe data submitted by the CWFC, as well asthe other information identified in this report. Our recommendations are predicated on theexpectation that installation and operation ofthe valves are performed in accordance withthe manufacturer=s specifications. XIII. SUGGESTED OPERATING CONDITIONS

In California, stationary sources arepermitted at the local level by districts. Eachof California=s 35 districts have rules andregulations which must be met to receive andmaintain an air quality permit. The districtrules and regulations reflect federal and stateregulatory requirements as well as anyadditional requirements that the districtboards determine to be appropriate for theregion.

Technologies which have been certifiedunder the ARB=s Equipment Precertification

Program are subject to the same federal, state,and local permitting requirements as sourceswhich have not been certified. In short,receipt of a certificate under the ARB=sEquipment Precertification Program does notin anyway limit the authority of local air districts. However, it is expected that localair districts will have an interest inconsidering the information presented in thisreport when making permitting decisions. Therefore, we have included someinformation on inspection frequency thatdistricts may consider helpful when makingpermitting decisions on the valves discussedin this report.

After it has been determined that thevalve has been properly installed, theinspection recommendations differ for theModel 100 and Model 120 flow-controlvalves. Specifically, it is recommended thatthe Model 100 be inspected on a frequencyconsistent with that which applies to weldedpipe. That is because, if properly installed,the Model 100 does not include any featureswhich would suggest that there is a potentialfor fugitive emissions.

For the Model 120, quarterly to semi-annual inspections (using a leak detectioninstrument) are suggested for the first year. Ameasurement of 10,000 parts per million orgreater should be considered a leak. If fourconsecutive readings below 100 parts permillion or less are recorded, it isrecommended that the inspections beconducted annually.

If , during any inspection, a reading of10,000 parts per million or greater isrecorded, it is recommended that the valve berepaired and that quarterly inspections beresumed. Alternatively, if any readings areover 100 parts per million but less than

10,000 it is suggested that the cause of thereading be investigated and that the valve berepaired if needed. After any repair iscompleted, it is suggested that inspectionstake place on a quarterly basis until fourconsecutive readings below 100 parts per

Page 23: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 19

million are made, then return to annualinspections.

XIV. PRECERTIFICATION CONDITIONS

The recommendations in this report are conditional on the flow-control valves being installed, inspected and maintained, in

accordance with the CWFC operator=s manual and the CWFC General Referencebook. In order for the precertification toremain valid, the CWFC must retainmanufacturing rights to the flow-controlvalves Models 100 and 120.

Page 24: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 20

Appendix A

Test Results for Curtiss-Wright Flow Valve Model 120

Page 25: Research Abstract: 2002-08-26 Curtis Wright Flow Control Valve · PDF fileconditions identified in this report; and 2) the general requirements discussed in the Equipment ... to the

Page 21

Appendix B

Article Entitled ATesting to the Fugitive Emissions Standards,@ Value Magazine