RESIDENTIAL CONSTRUCTION GUIDE
FOR DETACHED SINGLE STORY BUILDINGS AND ADDITIONS
LESS THAN 800 SQ. FT
APPLICANT MUST PROVIDE 2 COPIES OF Application submittals with floor
plan and elevation.
(Additions must show existing rooms adjoining new construction)
DESCRIBE USE OF BUILDING OR ADDITION
FLOOR PLANS MUST BE DRAWN TO ¼” = 1’ – SCALE
If adding on to an existing home, please show existing rooms adjoining the addition. Label
use of each room and show all doors, windows etc.
SELECT CONSTRUCTION DETAILS USED FROM PAGES 3 THROUGH 10 AND FILL IN
INFORMATION ON SHEET 2.
SHEETS 11, 12 & 13 ARE DRAWING SAMPLES ONLY.
ADDITIONAL INFORMATION AND / OR REQUIREMENTS MAY APPLY – please contact a Permit
Technician.
THIS GUIDE DESCRIBES THE PRESCRIPTIVE CONSTRUCTION REQUIREMENTS OF THE IRC
AND IS NOT INTENDED TO RELIEVE OTHER REQUIREMENTS OF THE CODE.
ADDITIONAL INFORMATION MAY BE REQUIRED.
The State of Washington adopted the 2015 International Building and Residential Code on
July 1St
, 2016. Please note below additional requirements based on the 2015 IRC:
Winds Speed: 135 MPH, 3 second gust Ultimate
Exposure: B
Seismic: Zone D1
Snow: Minimum roof snow load 25 psf… NO Reduction permitted, 30 psf Ground
Allowable bearing pressure: 1500 psf without a geotechnical report.
Revised 1-2-18
RESIDENTIAL CONSTRUCTION GUIDE
BUILDING DESCRIPTION
Owners Name:
Permit number:
Address:
Phone: Business Phone:
1) Please describe building use(s)
2) Check one:
Detached attached Total Sq. Ft. of project
3) Footing Type: (see sheet 3)
Check one:
Monolithic Slab Other: foundation
(If other, please provide detail)
4) Floor Type: (see sheet 4 & 5) Check one:
Slab Post & beam Floor Joist
(If other, Please provide detail – see example on sheet 11)
5) Wall Type: (See sheet 6) Check one:
Detail 1 – 2 x 6 insulated with exterior sheathing (wall)
Detail 2 – 2 x 6 insulated with siding and sheathing (double wall)
Detail 3 – 2 x 4 or 2 x 6 unheated garage or shop
6) Roof Type (see sheets 7, 8,9 & 10) Check one:
Conventional Roof framing (see detail 3, sheet 7 & 13)
Vaulted ceiling (see sheet 8)
Engineered trusses (see page 9)
Shed roof (see page 10)
Revised 1-2-18
CHAPTER
3 of 13 Residential Construction Guide* Lap rebar min. 20" for #4's & 25" for #5 at splices-secure with tie wire *2500 p.s.i.-3000 p.s.i. for stem walls.
NOTE: * Footings over 4'-0" high are required to be designed as retaining walls. Min. concrete strength for footings- 33
32
31
Footing at door openingFooting with stem wall
Monolithic slab/footing
8" m
in.
12
" min
.
4'-0
" max
.
6"
6"
1'-0"6" min.
3" clear
2x wall (see details on page 6)
sill seal - if heated
# 4 rebar horizontalcontinous top andbottom
# 4 vert. @ max. 48" o.cw/min. 14" extensioninto stem wall with 6"hook-detail R403.1.3.1
see note above foranchor bolt spacing
1'-0"
6"
note: 2'-0" wide shear walls and portal framewill require larger continous footings atgarage opening
garage jambw/wall beyond
# 4 horizontal rebar
driveway slabor paving
4" concrete slab 3000 psisee page 4 for wood floor
granular fill
foundation vents - 1 sffor every 300 s.f. of floor area.place within 3'-0" of corners-provide cross ventilation
2% slope
3" m
in.
12
" min
.8
" min
.
pressure treated plate w/ 12" dia. x 10" anchor bolts@ 6'-0" o.c. and maximum 12" from ends andsplices w/nut and 3"x3"x1
4" plate washers-typicalsill seal if heated
OPTION 2: max. 2x2 p.t nailer strippermitted w/R-10 rigid insulation - 24"total length.3 12" monolithic concrete slab
grade surface water awayfrom foundation a min. 6" withinthe first 10'-0" or slope todrain or swale R401.3
2% slope
26 gauge galvanized ironflashing or approved equal
OPTION 1: R-10 perimeterinsulation for heated structuresw/flashing and protectionboard or coating
heated space
2'-0"
2x wall (see details on page 6)
One #5 or two #4's located in middle thirdof the footing. 20" min. lap splices for # 4,35" min. lap splices for #5 see TableR608.5.4(1). Grade 40 steel required inZone D-1 R403.1.3.5.1. Secure with tiewire.
12" one story15" two story18" three storySee Detail R403.1.3
CHAPTER
4 of 13Residential Construction Guide
POST & BEAM FOOTING
sill sealer
#55 felt or use
NOTES:
POST & BEAM41
2x wall (see details on page 6)
R-15 or R-21 insulation as requiredwhen heatedpressure treated plate w/ 12" dia. x 10"anchor bolts @ 6'-0" o.c. and maximum 12"from ends and splices w/nut and 3"x3"x1
4"plate washers-typicalsill seal if heated
particle board underlayment over 2x6 or2x8 T&G decking or 1 18" plywood subflooring
1. 4x6 D.F. # 2 girders - maximum 7'-0" span. 4x8 maximum 8'-0" span.2. 4x4 D.F. #2 post. 4x6 required at girder splices.3. 2x decking must be covered with 38" plywood or approved underlayment.4. 4x post over 4'-0" high must be braced.5. See page 3 for rebar requirement in footing.6. Support insulation at 24" o.c. to hold tight to underside of floor deck - do not compress -WSEC
R402.2.7.7. Foundation vents required 1sf for each 300 s.f. of under-floor area-distribute approximately
equally on at least two sides. Recommend starting placement within 3' of corners. R408.8. Minimum concrete strength 2500 p.s.i. for footings, 3000 p.s.i. for concrete exposed to
weather. 20" lap for #4 rebar min. 25" lap for #5 bars at splices-secure with tie wire. See IRCTable R608.5.4(1).
9. See Detail R403.1.3 for multi-story footings.
12" plywood gusset nailto girder and post-alternate direction
18" dia. x 8" min. conc. pads -tributary loads over 3500#will require larger pads
6" mil (black) visqueenmin 12" lap
insulation baffle at foundationvents
Min. R-30 insulation
provide positiveconnection to 4x4 postand footing w/simpsonA24 or equal
floor ventsrequired seenote 7 below
4x_ girder @ max. 48" o.c
4x_ post2% slope8"m
in.
12
" min
.
6"
6"
6"
6"
3" m
in.
clea
r
Radon mitigation required for habitable spaces- min schedule 40 PVC piping "radon reduction system" labels required on piping
at all accessible locations. min 6 mil. black ploy. vapor barrier with 12" overlaps at seams. electrical junction box for future fan required at accessible
location nearest to pipe termination. radon duct shall be located within warm walls.
12" min.
P.T. post
FLOOR JOIST
5 of 13
Not to scale
F L O O R J O I S T S
NOTES:
51
2x_wall see walltypes-sheet 6
2x_rim joists orsolid blocking
caulk
floor vents requiredsee note 4 below
8"m
in.
12" m
in. 6"
6"
1'-0"
2% slope
floor joist (see tablefor spans)
2x_pressure treated plate w/ 12" dia. x 10"anchor bolts at 6'-0" o.c. maximum12" from ends and splicesw/ 3"x3"x14" plate washers
R-30 insulation-min.
maximum joist span
6" mil (black) visqueenmin 12" lap
55# felt
4x4 (4x6 at girder joist)bracing required when postis over 3' high
12" plywood gusset nailto girder and post-alternate direction
12" m
in.
provide positiveconnection to 4x4 postand footing w/simpsonA24 or equal
18" dia. x 8" min. conc. pads -tributary loads over 3500# willrequire larger pads
1. Floor joist to be minimum Douglas Fir #2. Code loading requirements- 40# live and 10# dead. Not for exteriordeck see IRC R507 and the deck detail package.
2. Minimum spans for subfloor-underlayment see subfloor span table this sheet.3. Minimum concrete strength 2500 psi for footing, 3000p.s.i. for concrete exposed to weather, lap rebar min.
20" for #5 and 25" for #5 at slices-secure with tie wire.4. Foundation vents required 1sf for each 300 s.f. of under-floor area-distribute approximately equally on at least
two sides. Recommend starting placement within 3' of corners. R408.
Table R502.3.1(2)Floor joist 12" o.c. 16" o.c. 24" o.c.
2x6 10'-9" 9'-9" 8'-3"2x8 14'-2" 12'-9" 10'-5"2x10 18'-0" 15'-7" 12'-9"2x12 20'-11" 18'-1" 14'-9"
for footing seedetail 2 on sheet 3
18" c
lear
solid block overbearing wall
4x6 @ 7'-0" or 4x8 @8'-0" o.c. post to post
Table R503.2.1 Subfloor spans16" o.c. 20" o.c. 24" o.c.
grade 1 1/2" 5/8" 3/4"
plywood subflooring (one perm rated)
CHAPTER
EXTERIOR WALL TYPES
36
2 x 4 or 2 x 6 W A L L - U N H E A T E Dscale- 1" = 1'-0"
16
2 X 6 W A L L W I T H E X T E R I O R S H E A T H I N G scale- 1" = 1'-0"
scale- 1" = 1'-0"
2 X 6 W A L L W I T H S I D I N G A N D S H E A T H I N G 62
Douglas Fir #2 studs at 16" o.c.2x6 maximum 10'-0" high2x4's maximum 10'-0" high
sill plates on concrete to be pressuretreatedno insulation required at unheated areasunfinished heated areas must have exposedinsulation with flame spread 25 vapor barrier
D.F. #2 studs - 2x6's @ 16" o.c. -maximum 10'-0" high w/ single bottom plateand double top platesR-21 insulation at heated areas - staple vapor barrierflange to face of studs (one perm vapor barrier)12" gypsum wall board
TI-11 panel sheathing or other approvedexterior sheathing panel
D.F. #2 studs - 2x6's @ 16" o.c. -maximum 10'-0" high w/ single bottom plateand double top plates
12" gypsum wall board
lap siding on #15 felt or other approvedweather-resistive barrier12" cdx plywood
U-.30 unlimited glazing percentageGlazing U-value at heated space
R-21 insulation at heated areas - staple vapor barrierflange to face of studs (one perm vapor barrier)
ROOF TYPES (Rafters w/Ceiling Joists)
17
C O N V E N T I O N A L F R A M I N G scale- 1" = 1'-0"
2x ridge-full depthof rafters
Ceiling joist Table R802.4(2) Dead Load 10 psfceiling joist 12" o.c. 16" o.c. 24 o.c.
2x4 9'-10" 8'-11" 7'-3"2x6 15'-0" 13'-0" 10'-8"2x8 19'-1" 16'-6" 13'-6"
2x10 23'-3" 20'-2" 16'-5"
Rafter joist Table R802.5.1(5) Dead Load 10 psfRafters (slope >
3:12) 12" o.c. 16" o.c. 24" o.c.
2x4 8'-7" 7'-10" 6'-9"2x6 13'-6" 12'-1" 9'-10"2x8 17'-8" 15'-4" 12'-6"
2x10 21'-7" 18'-9" 15'-3"2x12 25'-1" 21'-8" 17'-9"
span
ceiling joist (see span table below)
roof vents as required
rafters (see span table below)
composition roofing over 15# feltover 12" CDX plywood
when heated -insulation R-38 Adv. or R-49
insulation baffle
gutter and downspoutsto approveddrainage (see permittech)
eave ventsw/screens
for wall detailssee sheet 6
1. Ceiling joists to be Douglas Fir #2 or better. Designed for unhabitable attics with 20 PSF live load.2. Rafters to be Douglas Fir or better. Roof slopes greater than 3:12. (see sheet 10 for slopes less
than 3:12). Rafters are for light roof coverings only - 30# ground snow - 10# dead load.3. Roof vent total net area to be 1/300 of roof area if half of required vents are 3'-0" above
eave, otherwise 1/150 of roof area is required in roof vents R806.2.4. Provide a drip edge that overlaps a min. of 2" and extends a 14" below roof sheathing. Fastened to
roof deck 12" o.c. Install underlayment over the drip edge along the eaves and under the drip edgeon gables. Unless specified by manufacturer. Shingles are permitted to be flush with the edge.
NOTES:
drip edge (seenote 4 below)
drip edge(see note4 below)
Section @ gable or rake R905.2.8.5
ROOF TYPES (Rafters w/ridge beam)CHAPTER
alternate framing
NOTES:
composition roofing over 15# feltover 12" CDX plywood
when heated -insulation R-38 (compressed 10-1/4")
insulation bafflegutter and downspoutsto approved drainage-drip edge see page 7
eave ventsw/screens
2x12's@24" o.c.
min.1" continuousair space
roof vents orcontinuous ridgevent
blocking
ridge beam -see table for spansSimpson U210 hangers
or approved equal
vent each space - min 1"clearSimpson H2.5T or approved equal-eachrafter each sidefor wall details see sheet 6
rafter span
Beam Span
10'-0" 12'-0" 14'-0" 16'-0" 18'-0" 20'-0" 22'-0" 24'-0"
10'-0" 4 x10 6 x126 x12 #13 18 x 12 31
8 x1431
8 x1851
2 x1231
2 x2151
2 x13 1251
2 x156 34 x14
512 x18
634 x16
12'-0" 6 x104x12 6 x12
6 x143 18 x 12
318 x18
518 x117
8
318 x18
518 x 131
2
512 x14
634 x131
2
512 x16
634 x15
5 18 x19 1263
4 x18
14'-0" 4 x12 #16x12
318x11 146x14
318 x131
26x14 #1
31/2 x1651
8 x125 18 x1451
2 x 13 1251
2 x 1563
4 x1451
2 x16 126 34 x16
512 x18
6 34x16 12
16'-0" 6x12 3 18 x1114
6x1431
8 x1551
8 x11 1231
8 x1851
8 x13 125 12 x 1551
2 x146 34 x 155 18 x 16
518 x18
6 34 x1651
2 x19 126 34 x18
18'-0" 6x126 x16
3 18 x1231
8 x1851
8 x1178
312 x191
2
518 x13 12
312 x27
512 x15
6 34 x1551
2 x1651
2 x186 34x16 12
5 12 x1912
6 34 x18
Raf
ter
Spa
n
1. 318",3 12,"5 18",5 12" and
6 34" glu-lam beamsFb = 2400 1.7 EWS
2. 2x, 4x and 6xDouglas Fir #2unless otherwisenoted.
3. Ridge beam to besupported byvertical wall or postto footings.
18
R O O F F R A M I N G ( V A U L T E D )scale- 3/4" = 1'-0"
CHAPTER
roof sheathing
Roof Truss or Rafter Connector
solid blockingfor 2 x4 runner
2x4 studs at 24" o.c.or gable end assemblyw/ 2x4 backing orprovide bracingengineering by trussmanuf.
Pair of simpsonGBC or equal eachside of bracing
11
2x6 bracing@ 72" o.c.
(5) 10dmin.
2x4 blocking when thebracing is 8'-0" orgreater in length
8d @ 4" o.c.
8d on 6" o.c. min. uno
Simpson A35 orequal @ 24" o.c.
(2) 16dnails
(2) 16dnails
gutter and downspoutsto approved drainageDrip edge- see page 7
Simpson H2.5T connectoror approved equal eachtruss
light roof coveringover 15# felt
1/2" cdx plywoodor waffer board
engineered trusses orrafters
Roof trusses or rafters2x6 solid blocking
Insulation baffle
R-49 or R-38 adv.insulation
ROOF TYPES (engineered trusses)
ROOF TYPES (shed)CHAPTER
110
R O O F F R A M I N G (shed)scale- 3/4" = 1'-0"
When enclosed, venting required-each end, eachspace- w/no obstructions. 1" air space min.
rafters - see table below
gutter and downspoutsto approved drainageSee sheet 7 for drip edge
Rafter span
measured horizontally
1. 2:12 slope min. for 3 tab composition roofing - for slopes 2:12 to 3:12, two layers of 15# feltrequired, applied shingle fashion. R905.1.1. See page 7 for slopes over 3 in 12 slopes.
2. Pitches less than 2:12 are to be hot mop, metal, sheet metal, rolled roofing or other approvedmaterial, applied as directed in approved manufacture's instructions.
3. When ceiling is applied, vent each rafter space continuously through top and bottom blocking.When heated, insulate with R-38 (compressed 101/4")insulation, using 2x12 rafters to allow oneinch vent space R806.3
4. When attaching to existing building show ledger, size and method of fastening joist and ledger.Show required flashing.
5. Douglas Fir #2. For slopes 2:12 to 3:12.
NOTES:
Rafter Spansnow load = 25 psf L/ = 240, dead load = 10psf
12" o.c. 16" o.c. 24" o.c.2x4 8'-0" 7'-3" 6'-4"2x6 12'-6" 11'-4" 9'-9"2x8 16'-4" 13'-3" 12'-3"
2x10 20'-9" 18'-2" 15'-0"2x12 23'-11" 20'-11" 17'-3"
1" clear
Simpson H2.5T or equal-each end-each rafter
1. 2:12 slope min. for 3 tab composition roofing - for slopes 2:12 to 3:12, two layers of 15# feltrequired, applied shingle fashion. R905.1.1. See page 7 for slopes over 3 in 12 slopes.
2. Pitches less than 2:12 are to be hot mop, metal, sheet metal, rolled roofing or other approvedmaterial, applied as directed in approved manufacture's instructions.
3. When ceiling is applied, vent each rafter space continuously through top and bottom blocking.When heated, insulate with R-38 (compressed 101/4")insulation, using 2x12 rafters to allow oneinch vent space R806.3
4. When attaching to existing building show ledger, size and method of fastening joist and ledger.Show required flashing.
EXAMPLE
max.48"
U-20u-20
(unheated space)(heated space)
FTG./SLAB
G A R A G E OFFICE
133
134
122
33
31
41
12" FTG.
foundation vents
18" diam. x 8" thick concrete pad
4x6
4x6
max
imum
16
' x 7
' ove
rhea
d do
or
4040 SL.W.
30
68
DR.
3068 DR
4040 SL.W.
30
40
SL.
W.
3068 DR
30
40
SL.
W.11'-0" 24'-0"
35'-0"
4'-0
"4'-0
"16'-3
"16'-3
"
scale- 1/4" = 1'-0" (REDUCED EXAMPLE)
F L O O R P L A N2
111
F 0 U N D A T I O N / F L O O R F R A M I N G P L A Nscale- 1/4" = 1'-0" (REDUCED SCALE EXAMPLE)
11
continuous footingw/rebar
4" concrete slab
18" diameter x 8" thickconcrete pad
post &beam
note:if attaching addition to anexisting residence, show adjoiningrooms of existing home
full height studsrequired - thiswall
Wood Structural Panel (WSP) lessthan 4'-0" see alternate bracedwall details
4'-0" WSP 20'-0" requiredbetween panels
roof overhang
24'-3
"6'-
0"
11'-0" 24'-0"35'-0"
4'-0
"4'-0
"
24'-3
"
CHAPTER
4x HDRs w/2"rigid insulation(typ)
20' min. between wall lines
EXAMPLE
structural modificationsattachment to existing and allNOTE: If attaching to existing home- show
2x4 runner for bracingsee detail
floor see detailFor post and beam
8'-0
-3/4
"
2X8 facia
@ 48" o.c.2X4 outriggers
2-2X14 ridge 2X8 ridge
2-2X6 post2-2X6 king post
4X1
2
head
er
4X6 hdr 4X6 hdr4X6 hdr
4X4
hdr
4X4
hdr
4X4
hdr
2X14 #1 ceiling joists @ 24" o.c.or
2X6 rafters @ 24" o.c. with
vaulted ceiling@ 24" o.c 2X12 rafters
122
scale- 1/4" = 1'-0" (REDUCED EXAMPLE)
L O N G I T U D I N A L C R O S S S E C T I O N 122
112
R O O F F R A M I N G P L A Nscale- 1/4" = 1'-0" (REDUCED EXAMPLE)
2x14 #1 ceiling joists @24" o.c - 48" o.cwithout ceiling
flat 2x4 outriggers@8'-0" o.c.
gutter to approveddrainage
R-38 insulation w/1" air space-see detail
81
fireblocking at10'-0"
full height 2x6studs @ gableend
2x6 rafters@ 24" o.c.
2x4 runner
footing -see detail
41
134
133
33
92
134
133
CHAPTER
2X10 ceiling joists @ 12" o.c.
or 4x12 #2
scale- 1/4" = 1'-0" (REDUCED EXAMPLE)
S I D E E L E V A T I O N131
313
S E C T I O N (thru garage)scale- 1/4" = 1'-0" (REDUCED EXAMPLE)
scale- 1/4" = 1'-0" (REDUCED EXAMPLE)
F R O N T E L E V A T I O N132
413
S E C T I O N (thru shop)scale- 1/4" = 1'-0" (REDUCED EXAMPLE)
composition roofing over 15# felt
gutters anddownspouts toapproveddrainage
5/8" T1-11plywood
125
2x8 ridge
2x6 rafters @ 24" o.c.
2x14 #1 ceiling joists @24" o.c.
2-2x14 ridge2x12 rafters at 24" o.c.w/ R-38 insulation
2x6 studs w/ R-21 insulation
4x6 girders
R-30 insulation
CHAPTER
or provide engineered trusses