RJ3iB Controller for Europe

Embed Size (px)

Citation preview

  • 7/21/2019 RJ3iB Controller for Europe

    1/565

    FANUCRobotics

    R-J3iB CONTROLLER

    FOR EUROPE

    MAINTENANCE MANUAL

    PROJECT DOCUMENTATION

    B-81465EN-1/05

    FANUC, 2003

  • 7/21/2019 RJ3iB Controller for Europe

    2/565

  • 7/21/2019 RJ3iB Controller for Europe

    3/565

    -3-

    FANUC Robotics

    R-J3iB CONTROLLERfor Europe

    Maintenance ManualB-81465EN-1/05

    This publication contains proprietary information of FANUC Robotics Europe S.A. furnished forcustomer use only. No other uses are authorized without the express written permission ofFANUC Robotics Europe S.A.

    FANUC Robotics Europe S.A.

    Zone Industrielle

    6466 Echternach

    Luxemburg

    Phone: +(352) 72 7777-1

    Fax: +(352) 72 7777-403

    website: www.fanucrobotics.lu

  • 7/21/2019 RJ3iB Controller for Europe

    4/565

    -4-

    The descriptions and specifications contained in this manual were in effect at the time this manual wasapproved for printing. FANUC Robotics Europe S.A., hereinafter referred to as FANUC Robotics,

    reserves the right to discontinue models at any time or to change specifications or design withoutnotice and without incurring obligations.

    Copyright 2003 by FANUC Robotics Europe S.A.All Rights Reserved

    The information illustrated or contained herein is not to be reproduced, copied, translated into anotherlanguage, or transmitted in whole or in part in any way without the prior written consent of FANUCRobotics.

    Conventions Used in this Manual

    This manual includes information essential to the safety of personnel, equipment, software, and data.This information is indicated by headings and boxes in the text.

    WARNING

    Information appearing under WARNING concerns the protection of personnel. It is boxed to set itapart from other text.

    CAUTION

    Information appearing under CAUTION concerns the protection of equipment, software, and data.It is boxed to set it apart from other text.

    NOTE

    Information appearing next to NOTE concerns related information or useful hints.

  • 7/21/2019 RJ3iB Controller for Europe

    5/565

    TABLE OF CONTENTS B-81465EN-1/05

    -5-

    PREFACE .............................................................................................................. 13

    1 SAFETY PRECAUTIONS ................................................................................ 151.1 OPERATOR SAFETY .................................................................................................151.1.1 Operator Safety ...................................................................................................................17

    1.1.2 Safety of the Teach Pendant Operator ................................................................................181.1.3 Safety During Maintenance ................................................................................................20

    1.2 SAFETY OF THE TOOLS AND PERIPHERAL DEVICES ...................................... 21

    1.2.1 Precautions in Programming ..............................................................................................211.2.2 Precautions for Mechanism ................................................................................................21

    1.3 SAFETY OF THE ROBOT MECHANISM ................................................................221.3.1 Precautions in Operation ....................................................................................................22

    1.3.2 Precautions in Programming ..............................................................................................22

    1.3.3 Precautions for Mechanisms ...............................................................................................221.4 SAFETY OF THE END EFFECTOR .......................................................................... 231.4.1 Precautions in Programming ..............................................................................................23

    1.5 SAFETY IN MAINTENANCE .................................................................................... 24

    1.6 WARNING LABEL .....................................................................................................25

    I. MAINTENANCE

    1 OVERVIEW ....................................................................................................... 27

    2 CONFIGURATION ........................................................................................... 292.1 EXTERNAL VIEW OF THE CONTROLLER ...........................................................29

    2.2 COMPONENT FUNCTIONS ......................................................................................38

    2.3 PREVENTIVE MAINTENANCE ...............................................................................40

    3 TROUBLESHOOTING ..................................................................................... 413.1 POWER CANNOT BE TURNED ON ........................................................................41

    3.2 ALARM OCCURRENCE SCREEN ............................................................................ 45

    3.3 SAFETY SIGNALS .....................................................................................................48

    3.4 MASTERING ...............................................................................................................503.5 TROUBLESHOOTING USING THE ERROR CODE ............................................... 53

    3.5.1 SRVO-001 Operator panel E-stop ......................................................................................533.5.2 SRVO-002 Teach pendant E-stop ......................................................................................563.5.3 SRVO-003 Deadman switch released ................................................................................57

    3.5.4 SRVO-004 Fence open .......................................................................................................58

    3.5.5 SRVO-005 Robot overtravel ..............................................................................................613.5.6 SRVO-006 Hand broken ....................................................................................................63

    3.5.7 SRVO-007 External E-stop ................................................................................................653.5.8 SRVO-009 Pneumatic pressure alarm ................................................................................693.5.9 SRVO-014 Fan motor abnormal ........................................................................................70

    3.5.10 SRVO-015 SYSTEM OVER HEAT (Group : i Axis : j) ................................................71

    3.5.11 SRVO-018 Brake abnormal .............................................................................................73

    3.5.12 SRVO-021 SRDY off (Group : i Axis : j) .......................................................................743.5.13 SRVO-022 SRDY on (Group : i Axis : j) ........................................................................76

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 7/21/2019 RJ3iB Controller for Europe

    6/565

    B-81465EN-1/05 TABLE OF CONTENTS

    -6-

    3.5.14 SRVO-023 Stop error excess (Group : i Axis : j) ........................................................... 773.5.15 SRVO-024 Move error excess (Group : i Axis : j) ......................................................... 793.5.16 SRVO-027 Robot not mastered (Group : i) ..................................................................... 79

    3.5.17 SRVO-033 Robot not calibrated (Group : i) .................................................................... 793.5.18 SRVO-034 Ref pos not set (Group : i) ............................................................................ 793.5.19 SRVO-035 WARN2 Joint speed limit (Group : i Axis : j) ............................................. 79

    3.5.20 SRVO-036 Inpos time over (Group : i Axis : j) ............................................................. 793.5.21 SRVO-037 Imstp input (Group : i) .................................................................................. 803.5.22 SRVO-038 Pulse mismatch (Group : i Axis : j) ............................................................. 80

    3.5.23 SRVO-042 MCAL alarm (Group : i Axis : j) ................................................................ 813.5.24 SRVO-043 DCAL alarm (Group : i Axis : j) ................................................................. 823.5.25 SRVO-044 HVAL alarm (Group : i Axis : j) ................................................................. 85

    3.5.26 SRVO-045 HCAL alarm (Group : i Axis : j) ................................................................. 863.5.27 SRVO-046 OVC alarm (Group : i Axis : j) .................................................................... 87

    3.5.28 SRVO-047 LVAL alarm (Group : i Axis : j) .................................................................. 913.5.29 SRVO-049 OHAL1 alarm (Group : i Axis : j) ............................................................... 923.5.30 SRVO-050 CLALM alarm (Group : i Axis : j) .............................................................. 943.5.31 SRVO-051 CUER alarm (Group : i Axis : j) .................................................................. 95

    3.5.32 SRVO-054 DSM Memory Error ..................................................................................... 96

    3.5.33 SRVO-055 FSSB com error 1 (Group : i Axis : j) .......................................................... 973.5.34 SRVO-056 FSSB com error 2 (Group : i Axis : j) .......................................................... 98

    3.5.35 SRVO-057 FSSB disconnect (Group : i Axis : j) ............................................................ 983.5.36 SRVO-058 FSSB init error (Group : i Axis : j) ............................................................. 1003.5.37 SRVO-059 Servo amp init error .................................................................................... 102

    3.5.38 SRVO-060 FATL FSSN init error ................................................................................. 1033.5.39 SRVO-062 BZAL alarm (Group : i Axis : j) ................................................................ 103

    3.5.40 SRVO-064 PHAL alarm (Group : i Axis : j) ................................................................ 1033.5.41 SRVO-065 BLAL alarm (Group : i Axis : j) ................................................................ 1043.5.42 SRVO-067 OHAL2 alarm (Group : i Axis : j) ............................................................. 104

    3.5.43 SRVO-068 DTERR alarm (Group : i Axis : j) ............................................................. 104

    3.5.44 SRVO-069 CRCERR alarm (Group : i Axis : j) ........................................................... 1043.5.45 SRVO-070 STBERR alarm (Group : i Axis : j) ........................................................... 1053.5.46 SRVO-071 SPHAL alarm (Group : i Axis : j) .............................................................. 106

    3.5.47 SRVO-072 PMAL alarm (Group : i Axis : j) ............................................................... 106

    3.5.48 SRVO-073 CMAL alarm (Group : i Axis : j) ............................................................... 1063.5.49 SRVO-074 LDAL alarm (Group : i Axis : j) ................................................................ 106

    3.5.50 SRVO-075 Pulse not established (Group : i Axis : j) ................................................... 106

    3.5.51 SRVO-076 Tip Stick Detection (Group : i Axis : j) ..................................................... 1073.8.52 SRVO-081 EROFL alarm (Track enc : i) ...................................................................... 108

    3.5.53 SRVO-082 DAL alarm (Track ebc : i) .......................................................................... 1093.5.54 SRVO-084 BZAL alarm (Track enc : i) ........................................................................ 1093.5.55 SRVO-087 BLAL alarm (Track enc : i) ........................................................................ 109

    3.5.56 SRVO-089 OHAL2 alarm (Track enc : i) ..................................................................... 1093.5.57 SRVO-091 CRCERR alarm (Track enc : i) ................................................................... 110

    3.5.58 SRVO-092 STBERR alarm (Track enc : i) ................................................................... 110

    3.5.59 SRVO-093 SPMAL alarm (Track enc : i) ..................................................................... 1103.5.60 SRVO-094 PMAL alarm (Track enc : i) ....................................................................... 1113.5.61 SRVO-095 CMAL alarm (Track enc : i)....................................................................... 111

    3.5.62 SRVO-096 LDAL alarm (Track enc : i) ........................................................................ 111

    3.5.63 SRVO-097 Pulse not established (enc : i) ..................................................................... 111

    3.5.64 SRVO-105 Door open or E-stop .................................................................................... 1123.5.65 SRVO-136 DCLVAL alarm (Group : i Axis : j) .......................................................... 114

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 7/21/2019 RJ3iB Controller for Europe

    7/565

    TABLE OF CONTENTS B-81465EN-1/05

    -7-

    3.5.66 SRVO-138 SDAL alarm (Group : i Axis : j) .................................................................1163.5.67 SRVO-153 CHGAL(CNV) alarm (Group : i Axis : j) ..................................................1163.5.68 SRVO-156 IPMAL alarm (Group : i Axis : j) ...............................................................117

    3.5.69 SRVO-194 Servo disconnect ..........................................................................................1183.5.70 SRVO-199 Control Stop .................................................................................................1203.5.71 SRVO-201 Panel E-stop or SVEMG abnormal .............................................................121

    3.5.72 SRVO-202 TP E-stop or SVEMG abnormal ..................................................................1233.5.73 SRVO-204 External (SVEMG abnormal) E-STOP .......................................................1253.5.74 SRVO-205 SVAL1 Fence open (SVEMG abnormal) ....................................................128

    3.5.75 SRVO-206 Deadman switch (SVEMG abnormal) .........................................................1313.5.76 SRVO-213 Fuse blown (Panel PCB) .............................................................................1333.5.77 SRVO-214 Fuse blown (Amp)....................................................................................... 137

    3.5.78 SRVO-216 OVC (total) (Robot : i) ................................................................................1383.5.79 SRVO-221 Lack of DSP (Group : i Axis : j) .................................................................138

    3.5.80 SRVO-230 SVAL1 Chain 1 (+24V) abnormalSRVO-231 SVAL1 Chain 2 (0V) abnormal .................................................................. 139

    3.5.81 SRVO-230 Chain 1 (+24V) abnormal withSRVO-001 Operator s panel E-stop

    SRVO-231 Chain 2 (0V) abnormal with

    SRVO-001 Operators panel E-stop ...............................................................................1413.5.82 SRVO-230 Chain 1 (+24V) abnormal with

    SRVO-002 Teach pendant E-stopSRVO-231 Chain 2 (0V) abnormal withSRVO-002 Teach pendant E-stop ..................................................................................143

    3.5.83 SRVO-230 Chain 1 (+24V) abnormal withSRVO-003 Deadman switch released

    SRVO-231 Chain 2 (0V) abnormal withSRVO-003 Deadman switch released ............................................................................ 145

    3.5.84 SRVO-240 Chain1 (FENCE) abnormal with

    SRVO-230 Chain1 (+24V) abnormal and

    SRVO-004 Fence open SRVO-241 Chain2 (FENCE) abnormal with SRVO-231 Chain2 (0V) abnormal and

    SRVO-004 Fence open ...................................................................................................147

    3.5.85 SRVO-242 Chain1 (EXEMG) abnormal withSRVO-230 Chain 1 (+24V) abnormal and

    SRVO-007 External emergency stops

    SRVO-243 Chain 2 (EXEMG) abnormal withSRVO-231 Chain 2 (0V) abnormal and

    SRVO-007 External emergency stops............................................................................ 1503.5.86 SRVO-230 Chain 1 (+24V) abnormal with SRVO-232 NTED input

    SRVO-231 Chain 2 (0V) abnormal with SRVO-232 NTED input .................................................................................................153

    3.5.87 SRVO-230 Chain 1 (+24V) abnormal with

    SRVO-233 TP disabled in T1, T2/Door open SRVO-231 Chain 2 (0V) abnormal with SRVO-233 TP disabled in T1, T2/Door open ................................................................157

    3.5.88 SRVO-232 NTED input .................................................................................................160

    3.5.89 SRVO-233 TP disabled in T1, T2/Door open .................................................................162

    3.5.90 SRVO-235 Short term Chain abnormal .........................................................................1643.5.91 SRVO-236 Chain failure is repaired ..............................................................................165

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 7/21/2019 RJ3iB Controller for Europe

    8/565

    B-81465EN-1/05 TABLE OF CONTENTS

    -8-

    3.5.92 SRVO-237 Not reset chain failure ................................................................................. 1653.5.93 SRVO-240 Chain 1 (FENCE) abnormal ....................................................................... 1653.5.94 SRVO-241 Chain 2 (FENCE) abnormal ....................................................................... 165

    3.5.95 SRVO-242 Chain 1 (EXEMG) abnormal SRVO-243 Chain 2 (EXEMG) abnormal ..................................................................... 1693.5.96 SRVO-260 Chain 1 (NTED) abnormal

    SRVO-261 Chain 2 (NTED) abnormal ......................................................................... 1723.5.97 SRVO-262 Chain 1 (SVDCT) abnormal SRVO-263 Chain 2 (SVDCT) abnormal ....................................................................... 175

    3.5.98 SRVO-264 "E.STOP circuit abnormal 1" ...................................................................... 1783.5.99 SRVO-265 E.STOP circuit abnormal 2 ......................................................................... 1803.5.100 SRVO-266 FENCE1 status abnormal

    SRVO-267 FENCE2 status abnormal ......................................................................... 1823.5.101 SRVO-268 SVOFF1 status abnormal

    SRVO-269 SVOFF2 status abnormal .......................................................................... 1823.5.102 SRVO-270 EXEMG1 status abnormal SRVO-271 EXEMG2 status abnormal ........................................................................ 1833.5.103 SRVO-272 SVDISC1 status abnormal

    SRVO-273 SVDISC2 status abnormal ........................................................................ 183

    3.5.104 SRVO-274 NTED1 status abnormalSRVO-275 NTED2 status abnormal ........................................................................... 184

    3.5.105 SRVO-280 SVOFF input ............................................................................................. 1843.5.106 SRVO-281 SVOFF input (SVEMG abnormal) ........................................................... 1873.5.107 SRVO-282 Chain1 (SVOFF) abnormal

    SRVO-283 Chain2 (SVOFF) abnormal ....................................................................... 1903.5.108 SRVO-282 Chain1 (SVOFF) abnormal with

    SRVO-230 Chain 1 (+24V) abnormal and SRVO-280 SVOFF input SRVO-283 Chain2 (SVOFF) abnormal with

    SRVO-231 Chain 2 (0V) abnormal and

    SRVO-280 SVOFF input ............................................................................................. 1933.5.109 SRVO-291 "IPM over heat (Group : i Axis : j)" ........................................................ 1963.5.110 SRVO-292 EXT FAN alarm (Group : i A : j) ............................................................ 196

    3.5.111 SRVO-293 DClink (PSM) HCAL (Group : i Axis : j) ............................................... 196

    3.5.112 SRVO-294 EXT FAN (PSM) alarm (Group : i Axis : j) ............................................ 1963.5.113 SRVO-295 PSM COM alarm (Group : i Axis : j) ...................................................... 196

    3.5.114 SRVO-296 PSM DISCHG alarm (Group : i Axis : j) ................................................ 197

    3.5.115 SRVO-297 PSM Low Volt alarm (Group : i Axis : j) ................................................ 1973.5.116 SRVO-300 Hand broken/HBK disabled

    SRVO-302 Set Hand broken to ENABLE ................................................................... 197

    3.6 FUSED-BASED TROUBLESHOOTING ..................................................................199

    3.7 TROUBLESHOOTING BASED ON LED INDICATIONS .....................................211

    3.8 POSITION DEVIATION FOUND IN RETURN TO THE

    REFERENCE POSITION (POSITIONING) ............................................................226

    3.9 VIBRATION OBSERVED DURING MOVEMENT................................................ 226

    3.10 MANUAL OPERATION IMPOSSIBLE .................................................................227

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 7/21/2019 RJ3iB Controller for Europe

    9/565

    TABLE OF CONTENTS B-81465EN-1/05

    -9-

    4 PRINTED CIRCUIT BOARDS ....................................................................... 2294.1 MAIN BOARD (A16B-3200-0412, -0413) ............................................................... 230

    4.2 EMERGENCY STOP CONTROL BOARD (A20B-1007-0800) ..............................2354.3 BACKPLANE BOARD ............................................................................................. 236

    4.4 PANEL BOARD (A20B-2100-0770) ........................................................................ 238

    4.5 PANEL BOARD (A20B-2100-0771) ........................................................................ 240

    4.6 PROCESS I/O BOARD CA (A16B-2201-0470) .......................................................241

    4.7 PROCESS I/O BOARD CB (A16B-2201-0472) .......................................................245

    4.8 PROCESS I/O BOARD DA (A16B-2201-0480) .......................................................247

    4.9 PROCESS I/O BOARD EA (A16B-3200-0230) .......................................................250

    4.10 PROCESS I/O BOARD EB (A16B-3200-0231)...................................................... 255

    4.11 PROCESS I/O BOARD FA (A16B-2203-0420)...................................................... 257

    4.12 PROCESS I/O BOARD GA (A16B-2203-0520)..................................................... 2604.13 PROCESS I/O BOARD HA (A16B-2203-0760)..................................................... 263

    4.14 PANEL SWITCH BOARD (A20B-1007-0850)...................................................... 266

    5 SERVO AMPLIFIERS .................................................................................... 2675.1 LED OF SERVO AMPLIFIER ..................................................................................269

    5.2 SETTING OF SERVO AMPLIFIER ......................................................................... 271

    5.3 DRIVER IC FOR ROBOT DI/DO 272

    6 SETTING THE POWER SUPPLY .................................................................. 273

    6.1 BLOCK DIAGRAM OF THE MAIN POWER INCLUDING POWER SUPPLY..................................................................................................... 273

    6.2 SELECTING TRANSFORMER TAPS ...................................................................... 276

    6.3 CHECKING THE POWER SUPPLY UNIT (A16B-2203-0370) .............................281

    7 REPLACING A UNIT ..................................................................................... 2857.1 A-CABINET ...............................................................................................................285

    7.1.1 Replacing the A-cabinet Top Panel ..................................................................................2857.1.2 Replacing the A-cabinet Rear Panel .................................................................................2867.1.3 Replacing the A-cabinet Louver .......................................................................................287

    7.1.4 Replacing the A-cabinet Door ..........................................................................................288

    7.2 REPLACING THE PRINTED-CIRCUIT BOARDS ................................................. 2887.2.1 Replacing the Backplane Board (Unit) .............................................................................289

    7.2.2 Replacing the Power Unit and Printed-Circuit Boards on the

    Backplane Unit .................................................................................................................2907.2.3 Replacing the Process I/O Board EA, EB, FA,GA (A-cabinet) .......................................2927.2.4 Replacing the Panel Board ...............................................................................................293

    7.3 REPLACING CARDS AND MODULES ON THE MAIN BOARD ....................... 295

    7.4 REPLACING THE TRANSFORMER ...................................................................... 301

    7.5 REPLACING THE REGENERATIVE RESISTOR UNIT .......................................308

    7.6 REPLACING THE E-STOP UNIT ............................................................................311

    7.7 REPLACING THE POWER DISTRIBUTING UNIT .............................................. 3137.8 REPLACING SERVO AMPLIFIERS ....................................................................... 314

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 7/21/2019 RJ3iB Controller for Europe

    10/565

    B-81465EN-1/05 TABLE OF CONTENTS

    -10-

    7.9 REPLACING I/O UNIT MODEL A ..........................................................................323

    7.9.1 Replacing the Base Unit of I/O Unit Model A ................................................................ 323

    7.9.2 Replacing a Module ......................................................................................................... 324

    7.10 REPLACING THE TEACH PENDANT ..................................................................325

    7.11 REPLACING THE CONTROL SECTION FAN MOTOR .....................................327

    7.12 REPLACING THE AC FAN MOTOR .....................................................................3287.12.1 Replacing the Heat Exchanger and Door Fan Unit (A-cabinet) .................................... 328

    7.12.2 Replacing the Rear Fan Unit (A-cabinet) ...................................................................... 3307.12.3 Replacing External Air Fan Unit and Door Fan (B-cabinet) ......................................... 331

    7.13 REPLACING THE OPERATORS PANEL AND PANEL SWITCH BOARD .....333

    7.14 REPLACE THE MODE SWITCH ...........................................................................336

    7.15 REPLACING FUSES ...............................................................................................337

    7.15.1 Replacing Fuses in the Servo Amplifier ........................................................................ 337

    7.15.2 Replacing Fuses in the Power Unit ................................................................................ 3387.15.3 Replacing the Fuse on the Process I/O Boards .............................................................. 3397.15.4 Replacing the Fuse on the Panel Board ......................................................................... 343

    7.15.5 Replacing the Fuses of the Power Distributing Unit ..................................................... 344

    7.16 REPLACING RELAYS ..............................................................................................457.16.1 Replacing Relays on the Panel Board ............................................................................ 345

    7.17 REPLACING BATTERY .........................................................................................3467.17.1 Battery for Memory Backup (3 VDC) ........................................................................... 346

    II. CONNECTION

    1 GENERAL ........................................................................................................ 349

    2 BLOCK DIAGRAM ......................................................................................... 351

    3 ELECTRICAL CONNECTIONS ..................................................................... 3553.1 CONNECTION DIAGRAM BETWEEN MECHANICAL UNITS ..........................355

    3.2 EXTERNAL CABLE WIRING DIAGRAM ..............................................................358

    3.2.1 Robot Connection Cables ................................................................................................ 3583.2.2 Teach Pendant Cable ....................................................................................................... 3653.2.3 Connecting the Input Power ............................................................................................ 366

    3.2.4 Connecting the External Power Supply ON/OFF Switch ................................................ 3683.2.5 Connecting the External Emergency Stop ....................................................................... 371

    3.2.6 Connecting the Operation Box ........................................................................................ 383

    3.2.7 Connecting the NTED Signal (CRM65) .......................................................................... 3863.2.8 Connecting the Auxiliary Axis Brake (CRR65 A/B) ...................................................... 3873.2.9 Connecting the Auxiliary Axis Over Travel (CRM68) ................................................... 388

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 7/21/2019 RJ3iB Controller for Europe

    11/565

    TABLE OF CONTENTS B-81465EN-1/05

    -11-

    4 PERIPHERAL DEVICE, ARC WELDING, ANDEND EFFECTOR INTERFACES .................................................................. 389

    4.1 PERIPHERAL DEVICE INTERFACE BLOCK DIAGRAM ...................................3924.1.1 When Process I/O Board EA/EB/GA is used (A-cabinet) ...............................................3924.1.2 When Process I/O Board FA is Used (A-cabinet) ............................................................3944.1.3 When Process I/O Board CA/CB/HA is Used (B-cabinet) ..............................................395

    4.1.4 When Process I/O Board DA is Used (B-cabinet) ...........................................................397

    4.1.5 When I/O Unit-MODEL A is Used ..................................................................................3994.1.5.1 In case of B-cabinet ................................................................................................................ 399

    4.1.6 When Two or more Process I/O Boards and I/O Unit-Model A are Used .......................400

    4.2 PERIPHERAL DEVICE INTERFACE COMBINATION ........................................ 401

    4.2.1 In Case of A-cabinet .........................................................................................................4014.2.2 In Case of B-cabinet .........................................................................................................401

    4.3 PROCESS I/O BOARD SIGNALS ............................................................................403

    4.4 INTERFACE FOR PERIPHERAL DEVICES,

    END EFFECTORS, AND WELDERS ..................................................................... 4094.4.1 Peripheral Device and Control Unit Connection ..............................................................409

    4.4.2 Connection Between the Mechanical Unit and End Effector ...........................................429

    4.4.3 Connection Between the Control Unit and Welder ..........................................................432

    4.5 DIGITAL I/O SIGNAL SPECIFICATIONS .............................................................443

    4.5.1 Peripheral Device Interface ..............................................................................................443

    4.5.2 End Effector Control Interface .........................................................................................4464.5.3 I/O Signal Specifications for ARC-Welding Interface .....................................................448

    4.6 SPECIFICATIONS OF THE CABLES USED FOR

    PERIPHERAL DEVICES AND WELDERS ...........................................................4534.6.1 Peripheral Device Interface A Cable (CRM2: Honda Tsushin, 50 pins) ........................4534.6.2 Peripheral Device Interface B Cable (CRM4: Honda Tsushin, 20 pins) ........................4544.6.3 ARC Weld Connection Cable (CRW1, CRW7: Honda Tsushin, 34 pins) ......................454

    4.7 CABLE CONNECTION FOR THE PERIPHERAL DEVICES,

    END EFFECTORS, AND ARC WELDERS ...........................................................455

    4.7.1 Peripheral Device Connection Cable ................................................................................455

    4.7.2 Peripheral Device Cable Connector .................................................................................4564.7.3 End Effector Cable Connector ..........................................................................................4594.7.4 Recommended Cables ......................................................................................................460

    4.8 CONNECTION OF HDI ............................................................................................461

    4.8.1 Connecting HDI ................................................................................................................4614.8.2 Input Signal Rules for the High-speed Skip (HDI) ..........................................................464

    4.9 CONNECTING THE COMMUNICATION UNIT ...................................................4654.9.1 RS-232-C Interface ...........................................................................................................465

    4.9.1.1 Interface ..................................................................................................................................465

    4.9.1.2 RS-232-C Interface signals..................................................................................................... 467

    4.9.1.3 Connection between RS-232-C interface and external device ...............................................468

    4.9.2 Ethernet Interface .............................................................................................................4714.9.2.1 Connection to ethernet ............................................................................................................472

    4.9.2.2 10/100 BASE-T connector (CD38) pin assignments ..............................................................473

    4.9.2.3 Cable connection ..................................................................................................................... 473

    4.9.2.4 Lead materials .........................................................................................................................475

    4.9.2.5 Connector specification ..........................................................................................................4764.9.2.5 Cable clamp and shielding ......................................................................................................478

    4.9.2.6 Cable clamp and shielding ......................................................................................................478

    4.9.2.7 Grounding the network ...........................................................................................................478

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 7/21/2019 RJ3iB Controller for Europe

    12/565

    B-81465EN-1/05 TABLE OF CONTENTS

    -12-

    5 TRANSPORTATION AND INSTALLATION .............................................. 4815.1 TRANSPORTATION .................................................................................................481

    5.2 INSTALLATION ........................................................................................................4825.2.1 Installation Method .......................................................................................................... 4825.2.2 Assemble at Installation ................................................................................................... 487

    5.3 INSTALLATION CONDITION ................................................................................491

    5.4 ADJUSTMENT AND CHECKS AT INSTALLATION ............................................493

    5.5 RESETTING OVERTRAVEL AND EMERGENCY STOP AT INSTALLATION .4945.5.1 Peripheral Device Interface Processing ........................................................................... 494

    5.5.2 Resetting Overtravel ........................................................................................................ 494

    5.5.3 How to Disable/Enable HBK ........................................................................................... 4955.5.4 How to Disable/Enable Pneumatic Pressure Alarm (PPABN) ........................................ 496

    III. APPENDIX

    A TOTAL CONNECTION DIAGRAM ............................................................. 497

    B SPECIFICATIONS OF PERIPHERAL DEVICE INTERFACE .................... 527B.1 SIGNALS ...................................................................................................................527

    B.2 SETTING COMMON VOLTAGE ............................................................................530

    B.3 I/O SIGNALS .............................................................................................................531

    B.3.1 Input Signals ................................................................................................................... 531B.3.2 Output Signals ................................................................................................................. 537

    B.4 SPECIFICATIONS OF DIGITAL INPUT/OUTPUT ..............................................541B.4.1 Overview ......................................................................................................................... 541

    B.4.2 Input/Output Hardware Usable In the R-j3iB Controller ................................................ 541B.4.3 Software Specifications ................................................................................................... 541

    C POWER DISTRIBUTATION CIRCUIT DIAGRAM .................................... 543

    D OPTICAL FIBER CABLE .............................................................................. 551

    E CARD INTERFACE ........................................................................................ 555

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 7/21/2019 RJ3iB Controller for Europe

    13/565

    PREFACE B-81465EN-1/05

    -13-

    PREFACE

    This manual describes the following models (R-J3iB controller).

    Model Abbreviation

    FANUC Robot R- 2000iA/165F R-2000iA/165F R-2000iA

    FANUC Robot R- 2000i/200F R-2000iA/200F R-2000iA

    FANUC Robot R-2000iA/200FO R-2000iA/200FO R-2000iA

    FANUC Robot R-2000iA/165EA R-2000iA/165EA R-2000iA

    FANUC Robot R-2000iA/165EW R-2000iA/165EW R-2000iA

    FANUC Robot R- 2000i/165R R-2000iA/165R R-2000iA

    FANUC Robot R- 2000i

    /200R R-2000iA/200R R-2000iA

    FANUC Robot R- 2000i/125L R-2000iA/125L R-2000iA

    FANUC Robot R- 2000i/165CF R-2000iA/165CF R-2000iA

    FANUC Robot R-2000iA/200T R-2000iA/200T R-2000iA

    FANUC Robot M-6iB M-6iB M-6iB

    FANUC Robot M-6iB/6C M-6iB/6C M-6iB

    FANUC Robot M-16iB/20 M-16iB/20 M-16iB

    FANUC Robot M-16iB/10L M-16iB/10L M-16iB

    FANUC Robot M-16iB/20T M-16iB/20T M-16iB

    FANUC Robot M-16iB/10LT M-16iB/10LT M-16iB

    FANUC Robot ARC Mate 100iB ARC Mate 100iB ARC Mate 120iB

    FANUC Robot ARC Mate 120iB ARC Mate 120iB ARC Mate 120iB

    FANUC Robot ARC Mate 120iB/10L ARC Mate 120iB/10L ARC Mate 120iB

    FANUC Robot ARC Mate 120iB/20T ARC Mate 120iB/20T ARC Mate 120iB

    FANUC Robot ARC Mate 120iB/10LT ARC Mate 120iB/10LT ARC Mate 120iB

    FANUC Robot M-710iB/45 M-710iB/45 M-710iB

    FANUC Robot M-710iB/45E M-710iB/45E M-710iB

    FANUC Robot M-710iB/45T M-710iB/45T M-710iB

    FANUC Robot M-710iB/70 M-710iB/70 M-710iB

    FANUC Robot M-710iB/70T M-710iB/70T M-710iB

    FANUC Robot M-410iB/160 M-410iB/160 M-410iB

    FANUC Robot M-410iB/300 M-410iB/300 M-410iB

  • 7/21/2019 RJ3iB Controller for Europe

    14/565

    B-81465EN-1/05 PREFACE

    -14-

    FANUC Robot M-410iB/450 M-410iB/450 M-410iBFANUC Robot M-420iA M-420iA M-420iA

    FANUC Robot M-421iA M-421iA M-421iA

    FANUC Robot F-200iB F-200iB F-200iB

    FANUC Robot S-500iB S-500iB S-500iB

    FANUC Robot S-900iB/400 S-900iB/400 S-900iB

    FANUC Robot S-900iB/200 S-900iB/200 S-900iB

    FANUC Robot S-900iB/220L S-900iB/220L S-900iB

    FANUC Robot LR Mate 200iB LR Mate 200iB LR Mate 200iB

    FANUC Robot LR Mate 200iB/3L LR Mate 200iB/3L LR Mate 200iB

    Model Abbreviation

  • 7/21/2019 RJ3iB Controller for Europe

    15/565

    1. SAFETY PRECAUTIONS B-81465EN-1/05

    -15-

    1 SAFETY PRECAUTIONS

    For the safety of the operator and the system, follow all safety precautions when operating a robot andits peripheral devices installed in a work cell.

    1.1 OPERATOR SAFETY

    Operator safety is the primary safety consideration. Because it is very dangerous to enter the operatingspace of the robot during automatic operation, adequate safety precautions must be observed.

    The following lists the general safety precautions. Careful consideration must be made to ensureoperator safety.

    1. Have the robot system operators attend the training courses held by FANUC.

    2. Even when the robot is stationary, it is possible that the robot is still ready to move state and iswaiting for a signal. In this state, the robot is regarded as still in motion. To ensure operator safety,provide the system with an alarm to indicate visually or aurally that the robot is in motion.

    3. Install a safety fence with a gate so that no operator can enter the work area without passing throughthe gate. Equip the gate with an interlock that stops the robot when the gate is opened.

    4. Provide the peripheral devices with appropriate grounding (Class 1, Class 2, or Class 3).

    5. Try to install the peripheral devices outside the work area.

    6. Draw an outline on the floor, clearly indicating the range of the robot motion, including the toolssuch as a hand.

    7. Install a mat switch or photoelectric switch on the floor with an interlock to a visual or aural alarmthat stops the robot when an operator enters the work area.

    8. If necessary, install a safety lock so that no one except the operator in charge can turn on the powerof the robot.

    FANUC provides various training courses. Contact our sales office for details.

    The controller is designed to receive this interlock signal. When the gate is opened and this signal

    received, the controller stops the robot in an emergency. For connection, see Fig.1.1.

    The circuit breaker installed in the controller is designed to disable anyone from turning it on whenit is locked with a padlock.

  • 7/21/2019 RJ3iB Controller for Europe

    16/565

    B-81465EN-1/05 1. SAFETY PRECAUTIONS

    -16-

    9. When adjusting each peripheral device independently, be sure to turn off the power of the robot.

    Fig. 1.1 Safety Fence and Safety Gate

    1 Limit switch for the safety gate 2 Note:

    Terminals FENCE 1 and FENCE 2 are on the PC board

    in the operators panel.

    Fence circuit is a safety stop circuit.

  • 7/21/2019 RJ3iB Controller for Europe

    17/565

    1. SAFETY PRECAUTIONS B-81465EN-1/05

    -17-

    1.1.1 Operator Safety

    The operator is a person who operates the robot system. In this sense, a worker who operates the teachpendant is also an operator. However, this section does not apply to teach pendant operators.

    1. If it is not necessary for the robot to operate, turn off the power of the robot controller or press theEMERGENCY STOP button, and then proceed with necessary work.

    2. Operate the robot system at a location outside the work area.

    3. Install a safety fence with a safety gate to prevent any worker other than the operator from enteringthe work area unexpectedly and also to prevent the worker from entering a dangerous area.

    4. Install an EMERGENCY STOP button within the operator's reach.

    Fig. 1.1.1 Connection Diagram for External Emergency Stop Switch

    The robot controller is designed to be connected to an external EMERGENCY STOP button. Withthis connection, the controller stops the robot operation when the external EMERGENCY STOPbutton is pressed. See the diagram below for connection.

    1 External EMERGENCY STOP button 3 Note: Connect to EES1 and EES11, EES2 and EES21.

    2 Panel board

  • 7/21/2019 RJ3iB Controller for Europe

    18/565

    B-81465EN-1/05 1. SAFETY PRECAUTIONS

    -18-

    1.1.2 Safety of the Teach Pendant Operator

    While teaching the robot, it is necessary for the operator to enter the work area of the robot. It isparticularly necessary to ensure the safety of the teach pendant operator.

    1. Unless it is specifically necessary to enter the robot work area, carry out all tasks outside the area.

    2. Before teaching the robot, check that the robot and its peripheral devices are all in the normaloperating condition.

    3. When entering the robot work area and teaching the robot, be sure to check the location andcondition of the safety devices (such as the EMERGENCY STOP button and the deadman's switchon the teach pendant).

    4. The teach pendant operator should pay careful attention so that no other workers enter the robotwork area.

    NOTE

    The teach pendant supplied by FANUC is provided with a teach pendant enable switch and adeadman's switch in addition to the EMERGENCY STOP button. The functions of each switch areas follows.

    EMERGENCY STOP button:

    Pressing this button stops the robot in an emergency, irrespective to the condition of theteach pendant enable switch.

    Deadman's switch:

    The function depends on the state of the teach pendant enable switch.

    When the enable switch is on:

    Releasing the finger from the deadman switch or holding the deadman switch stronglystops the robot in an emergency.

    When the enable switch is off:

    The deadman's switch is ineffective.

    NOTE

    The deadman switch is provided so that the robot operation can be stopped simply by releasingfinger from the teach pendant or holding the deadman switch strongly in case of emergency. TheR-J3iB has adopted a 3-position deadman switch as an RIA-specification teach pendant. Pressingthe 3-position deadman switch halfway makes the robot operable. Releasing the finger from thedeadman switch or holding the deadman switch strongly causes the robot to enter the emergencystop state.

  • 7/21/2019 RJ3iB Controller for Europe

    19/565

    1. SAFETY PRECAUTIONS B-81465EN-1/05

    -19-

    5. When entering the robot work area, the teach pendant operator should enable the teach pendantwhenever he or she enters the robot work area. In particular, while the teach pendant enable switchis off, make certain that no start command is sent to the robot from any operator's panel other thanthe teach pendant.

    6. To start the system using the operator's panel/operation box, make certain that nobody is in therobot work area and that there are no abnormal conditions in the robot work area.

    7. When a program is completed, be sure to carry out a test run according to the procedure below.

    a. Run the program for at least one operation cycle in the single step mode at low speed.b. Run the program for at least one operation cycle in the continuous operation mode at low

    speed.

    c. Run the program for one operation cycle in the continuous operation mode at theintermediate speed and check that no abnormalities occur due to a delay in timing.

    d. Run the program for one operation cycle in the continuous operation mode at the normaloperating speed and check that the system operates automatically without trouble.

    e. After checking the completeness of the program through the test run above, execute it inthe automatic operation mode.

    8. While operating the system in the automatic operation mode, the teach pendant operator shouldleave the robot work area.

    NOTEIn addition to the above, the teach pendant enable switch and the deadman's switch also have thefollowing function.By pressing the deadman's switch while the enable switch is on, the emergency stop factor(normally the safety gate) connected to EAS1 and EAS11, EAS2 and EAS21 of the controller isinvalidated. In this case, it is possible for an operator to enter the fence during teach operationwithout pressing the EMERGENCY STOP button. In other words, the system understands that thecombined operations of pressing the teach pendant enable switch and pressing the deadman's switchindicates the start of teaching. The teach pendant operator should be well aware that the safety gateis not functional under this condition and bear full responsibility to ensure that no one enters thefence during teaching.

    The teach pendant, operator's panel/operation box, and peripheral device interface send each robotstart signal. However the validity of each signal changes as follows depending on the mode of theteach pendant enable switch and the remote condition.

    Teach pendant

    enable switch Remote condition Teach pendantOperators panel/

    operation box Peripheral devices

    On Independent Allowed to start Not allowed Not allowed

    Off Local Not allowed Allowed to start Not allowed

    Off Remote Not allowed Not allowed Allowed to start

  • 7/21/2019 RJ3iB Controller for Europe

    20/565

    B-81465EN-1/05 1. SAFETY PRECAUTIONS

    -20-

    1.1.3 Safety During Maintenance

    For the safety of maintenance personnel, pay utmost attention to the following.1. Except when specifically necessary, turn off the power of the controller while carrying out

    maintenance. Lock the power switch, if necessary, so that no other person can turn it on.

    2. When disconnecting the pneumatic system, be sure to reduce the supply pressure.

    3. Before the start of teaching, check that the robot and its peripheral devices are all in the normaloperating condition.

    4. If it is necessary to enter the robot work area for maintenance when the power is turned on, theworker should indicate that the machine is being serviced and make certain that no one starts therobot unexpectedly.

    5. Do not operate the robot in the automatic mode while anybody is in the robot work area.

    6. When it is necessary to maintain the robot alongside a wall or instrument, or when multiple workersare working nearby, make certain that their escape path is not obstructed.

    7. When a tool is mounted on the robot, or when any moving device other than the robot is installed,such as belt conveyor, pay careful attention to its motion.

    8. If necessary, have a worker who is familiar with the robot system stand beside the operator's paneland observe the work being performed. If any danger arises, the worker should be ready to pressthe EMERGENCY STOP button at any time.

    9. When replacing or reinstalling components, take care to prevent foreign matter from entering thesystem

    10.When handling each unit or printed circuit board in the controller during inspection, turn off thepower of the controller and also turn off the circuit breaker to protect against electric shock.

    11.When replacing parts, be sure to use those specified by FANUC. In particular, never use fuses orother parts of non-specified ratings. They may cause a fire or result in damage to the componentsin the controller.

  • 7/21/2019 RJ3iB Controller for Europe

    21/565

    1. SAFETY PRECAUTIONS B-81465EN-1/05

    -21-

    1.2 SAFETY OF THE TOOLS AND PERIPHERAL DEVICES

    1.2.1 Precautions in Programming

    1. Use a limit switch or other sensor to detect a dangerous condition and, if necessary, design theprogram to stop the robot when the sensor signal is received.

    2. Design the program to stop the robot when an abnormal condition occurs in any other robots orperipheral devices, even though the robot itself is normal.

    3. For a system in which the robot and its peripheral devices are insynchronous motion, particular caremust be taken in programming so that they donot interfere with each other.

    4. Provide a suitable interface between the robot and its peripheral devices so that the robot can detectthe states of all devices in the system and can be stopped according to the states.

    1.2.2 Precautions for Mechanism

    1. Keep the component cells of the robot system clean, and operate the robot in an environment freeof grease, water, and dust.

    2. Employ a limit switch or mechanical stopper to limit the robot motion so that the robot does notcome into contact with its peripheral devices or tools.

  • 7/21/2019 RJ3iB Controller for Europe

    22/565

    B-81465EN-1/05 1. SAFETY PRECAUTIONS

    -22-

    1.3 SAFETY OF THE ROBOT MECHANISM

    1.3.1 Precautions in Operation

    1. When operating the robot in the jog mode, set it at an appropriate speed so that the operator canmanage the robot in any eventuality.

    2. Before pressing the jog key, be sure you know in advance what motion the robot will perform inthe jog mode.

    1.3.2 Precautions in Programming

    1. When the work areas of robots overlap, make certain that the motions of the robots do not interfere

    with each other.2. Be sure to specify the predetermined work origin in a motion program for the robot and program

    the motion so that it starts from the origin and terminates at the origin. Make it possible for theoperator to easily distinguish at a glance that the robot motion has terminated.

    1.3.3 Precautions for Mechanisms

    1. Keep the work area of the robot clean, and operate the robot in an environment free of grease,water, and dust.

  • 7/21/2019 RJ3iB Controller for Europe

    23/565

    1. SAFETY PRECAUTIONS B-81465EN-1/05

    -23-

    1.4 SAFETY OF THE END EFFECTOR

    1.4.1 Precautions in Programming

    1. To control the pneumatic, hydraulic and electric actuators, carefully consider the necessary timedelay after issuing each control command up to actual motion and ensure safe control.

    2. Provide the end effector with a limit switch, and control the robot system by monitoring the stateof the end effector.

  • 7/21/2019 RJ3iB Controller for Europe

    24/565

    B-81465EN-1/05 1. SAFETY PRECAUTIONS

    -24-

    1.5 SAFETY IN MAINTENANCE

    1. Never enter the robot work area while the robot is operating. Turn off the power before enteringthe robot work area for inspection and maintenance.

    2. If it is necessary to enter the robot work area with the power turned on, first press theEMERGENCY STOP button on the operator's panel.

    3. When replacing or reinstalling components, take care to prevent foreign matter from entering thesystem. When replacing the parts in the pneumatic system, be sure to reduce the pressure in thepiping to zero by turning the pressure control on the air regulator.

    4. When handling each unit or printed circuit board in the controller during inspection, turn off thepower of the controller and turn off the circuit breaker to protect against electric shock.

    5. When replacing parts, be sure to use those specified by FANUC.In particular, never use fuses or other parts of non-specified ratings. They may cause a fire or result

    in damage to the components in the controller.6. Before restarting the robot, be sure to check that no one is in the robot work area and that the robot

    and its peripheral devices are all in the normal operating state.

  • 7/21/2019 RJ3iB Controller for Europe

    25/565

    1. SAFETY PRECAUTIONS B-81465EN-1/05

    -25-

    1.6 WARNING LABEL

    Description

    Do not step on or climb the robot or controller as it may adversely affect the robot or controller andyou may get hurt if you lose your footing as well.

    1. Step-on prohibitive label

    Fig. 1.6 (a) Step-on Prohibitive Label

    Description

    Be cautious about a section where this label is affixed, as the section generates heat. If you have toinevitably touch such a section when it is hot, use a protective provision such as heat-resistant gloves.

  • 7/21/2019 RJ3iB Controller for Europe

    26/565

    B-81465EN-1/05 1. SAFETY PRECAUTIONS

    -26-

    2. High-temperature warning label

    Fig. 1.6. (b) High-Temperature Warning Label

    Description

    A high voltage is applied to the places where this label is attached. Before starting maintenance, turnthe power to the control unit off, then turn the circuit breaker off to avoid electric shock hazards. Becareful with servo amplifier and other units because high-voltage places in these units may remain inthe high-voltage state for a fixed time.

    3. High-voltage warning label

    Fig. 1.6 (c) High-Voltage Warning Label

    Description

    There may be a high voltage in a place with this label. Before working on such a portion, turn off thepower to the controller and set its circuit breaker to the off position to avoid shock hazards. In addition,be careful about servo amplifiers and other electric circuits because a high voltage may remain in themfor a certain period of time after the power is turned off.

  • 7/21/2019 RJ3iB Controller for Europe

    27/565

    1. OVERVIEW MAINTENANCE B-81465EN-1/05

    -27-

    1 OVERVIEW

    This manual describes the maintenance and connection of the R-J3iB robot controller(called the R-J3iB).

    Maintenance Part :Troubleshooting, and the setting, adjustment, and replacement of units

    Connection Part :Connection of the R-J3iB controller to the robot mechanical unit and peripheral devices, andinstallation of the controller

    - For information on third party approvals, contact your FANUC representative.

    WARNING

    Before you enter the robot working area, be sure to turn off the power to the controller or press theEMERGENCY STOP button on the operators panel/operation box or teach pendant. Otherwise,you could injure personnel or damage equipment.

  • 7/21/2019 RJ3iB Controller for Europe

    28/565

    B-81465EN-1/05 MAINTENANCE 1. OVERVIEW

    -28-

  • 7/21/2019 RJ3iB Controller for Europe

    29/565

    2. CONFIGURATION MAINTENANCE B-81465EN-1/05

    -29-

    2 CONFIGURATION

    2.1 EXTERNAL VIEW OF THE CONTROLLER

    The appearance and components might slightly differ depending on the controlled robot, application,and options used.Fig. 2.1 (a), (b), (c), (d) and (e) show external and internal views of the R-J3iB A-cabinet andB-cabinet controllers.

    Fig. 2.1 (f), (g) and (h) show the MODE SELECT switch, the operator panel and the operator panelinterface.

    Fig. 2.1 (i) and (j) show the block diagram of R-J3iB.

    Fig. 2.1 (a) External View of the R-J3iB Controller (A-cabinet)

    1 Operation box 3 R-J3iB controller

    2 Teach pendant

  • 7/21/2019 RJ3iB Controller for Europe

    30/565

    B-81465EN-1/05 MAINTENANCE 2. CONFIGURATION

    -30-

    Fig. 2.1 (b) External View of the R-J3iB Controller (B-cabinet)

    1 Mode switch 3 Operators panel

    2 Teach pendant

  • 7/21/2019 RJ3iB Controller for Europe

    31/565

    2. CONFIGURATION MAINTENANCE B-81465EN-1/05

    -31-

    Fig. 2.1 (c) R-J3iB A-cabinet interior

    1 Teach pendant 5 Power supply unit

    2 E-stop unit 6 Fan unit

    3 Servo amplifier 7 Regenerative resistor

    4 Main board 8 Transformer

  • 7/21/2019 RJ3iB Controller for Europe

    32/565

    B-81465EN-1/05 MAINTENANCE 2. CONFIGURATION

    -32-

    Fig. 2.1 (d) R-J3iB B-cabinet interior (Front)

    1 Servo Amplifier 11 Backplane

    2 External air Fan Unit 12 E-Stop Unit

    3 Emergency Stop Button 13 Main Board

    4 Battery 14 Breaker

    5 DC Fan Unit 15 Power supply Unit

    6 Panel Board 16 Floor Fan Unit

    7 Operator Panel 17 Enable switch

    8 MODE Switch 18 Teach Pendant

    9 Door Fan 19 Emergency Stop Button

    10 Process I/O Board

  • 7/21/2019 RJ3iB Controller for Europe

    33/565

    2. CONFIGURATION MAINTENANCE B-81465EN-1/05

    -33-

    Fig. 2.1 (e) R-J3i B-cabinet overview (Back)

    Fig. 2.1 (f) R-J3iB mode switch overview

    1 Regenerative Resistor Unit 2 Transformer

  • 7/21/2019 RJ3iB Controller for Europe

    34/565

    B-81465EN-1/05 MAINTENANCE 2. CONFIGURATION

    -34-

    Fig. 2.1 (g) R-J3iB panel overview

    Fig. 2.1 (h) R-J3iB interface overview

  • 7/21/2019 RJ3iB Controller for Europe

    35/565

    2. CONFIGURATION MAINTENANCE B-81465EN-1/05

    -35-

    Tab. 2.1 Servo amplifier and regenerative resistor unit

    Robot models Servo amplifierRegenerative resistor

    A-CABINET

    Regenerative resistor

    B-CABINET

    R-2000iA/200T A06B-6105-H001 ----- A05B-2452-C200

    S-900iB A06B-6105-H001 A05B-2451-C204 A05B-2452-C200

    M-410iB A06B-6105-H001 A05B-2451-C204 A05B-2452-C200

    R-2000iA (except/200T) A06B-6105-H002 A05B-2451-C202 A05B-2452-C200

    S-500iB A06B-6105-H002 A05B-2451-C202 A05B-2452-C200

    M-710iB A06B-6105-H002 A05B-2451-C202 A05B-2452-C200

    M-16iB A06B-6105-H002 A05B-2451-C202 A05B-2452-C200

    ARC Mate 120iB A06B-6105-H002 A05B-2451-C202 A05B-2452-C200

    M-420iA, M-421iA A06B-6105-H002 A05B-2451-C204 A05B-2452-C200

    M-6iB A06B-6105-H003 A05B-2451-C201 A05B-2452-C201

    ARC Mate 100iB A06B-6105-H003 A05B-2451-C201 A05B-2452-C201

    F-200iB A06B-6105-H003 A05B-2451-C201 A05B-2452-C201

    LR Mate 200iB A06B-6105-H003 ----- A05B-2452-C201

  • 7/21/2019 RJ3iB Controller for Europe

    36/565

    B-81465EN-1/05 MAINTENANCE 2. CONFIGURATION

    -36-

    Fig. 2.1 (i) Block diagram of the R-J3iB (A-cabinet)

  • 7/21/2019 RJ3iB Controller for Europe

    37/565

    2. CONFIGURATION MAINTENANCE B-81465EN-1/05

    -37-

    Fig. 2.1 (j) Block diagram of the R-J3iB (B-cabinet)

  • 7/21/2019 RJ3iB Controller for Europe

    38/565

    B-81465EN-1/05 MAINTENANCE 2. CONFIGURATION

    -38-

    2.2 COMPONENT FUNCTIONS

    - Main board

    The main board contains a microprocessor, its peripheral circuits, memory, and operator's panelcontrol circuit. The main CPU controls servo mechanism positioning and servo amplifier voltages.

    - Battery retains main board memory when controller power is off.

    - I/O printed circuit board and FANUC I/O Unit MODEL-A

    Various types of printed circuit boards are provided for applications including process I/O. The

    FANUC I/O unit MODEL A can also be installed. When it is used, various I/O types can be selected.These are connected with FANUC I/O Link.

    - E-stop unit

    This unit controls the emergency stop system with control reliable E-stop performance criteria for bothof the magnetic contactor and the precharge of the servo amplifier.

    - Power supply unit

    The power supply unit converts the AC power to various levels of DC power.

    - Backplane printed circuit board

    The various control printed circuit boards are mounted on the backplane printed circuit board.

    - Teach pendant

    All operations including robot programming are performed with this unit. The controller status anddata are indicated on the liquid-crystal display (LCD) on the pendant.

    - Servo amplifier

    The servo amplifier controls servomotor power, pulse coder, brake control, overtravel and handbroken.

    - Operators panel/operation box

    Buttons and LEDs on the operators panel/operation box are used to start the robot and to indicate therobot status. The panel has a port for the serial interface to an external device and an interface toconnect the memory card for data backup. It also controls the emergency stop control circuit.

  • 7/21/2019 RJ3iB Controller for Europe

    39/565

    2. CONFIGURATION MAINTENANCE B-81465EN-1/05

    -39-

    - Transformer

    The supply voltage is converted to an AC voltage required for the controller by the transformer.

    - Fan unit, heat exchanger

    These components cool the inside of the control unit.

    - Circuit breaker

    If the electric system in the controller malfunctions, or if abnormal input power causes high current inthe system, the input power is connected to the circuit breaker to protect the equipment.

    - Regenerative resistor

    To discharge the counter electromotive force from the servomotor, connect a regenerative resistor tothe servo amplifier.

  • 7/21/2019 RJ3iB Controller for Europe

    40/565

    B-81465EN-1/05 MAINTENANCE 2. CONFIGURATION

    -40-

    2.3 PREVENTIVE MAINTENANCE

    Daily maintenance and periodic maintenance/inspection ensure reliable robot performance forextended periods of time.

    1. Daily maintenanceBefore operating the system each day, clean each part of the system and check the system parts forany damage or cracks. Also check the following:

    a. Before service operationCheck the cable connected to the teach pendant for excessive twisting. Check the controllerand peripheral devices for abnormalities.

    b. After service operationAt the end of service operation, return the robot to the specified position, then turn off thecontroller. Clean each part, and check for any damage or cracks. If the ventilation port of

    the controller is dusty, clean it.c. Check after one monthCheck that the fan is rotating normally. If the fan has dirt and dust built up, clean the fanaccording to step (d) described below for inspection to be performed every 6 months.

    d. Periodic inspection performed every six monthsRemove the top cover, louver, and back panel (if possible), then remove any dirt and dustfrom the inside of the transformer compartment. Wipe off dirt and dust from the fan andtransformer.

    e. Replacing batteryReplace the lithium battery on the front panel of the main board every 4 years.Please refer to the section 7.17.

    2. Maintenance toolsThe following maintenance tools are recommended:

    a. Measuring instrumentsAC/DC voltmeter (A digital voltmeter is sometimes required.)Oscilloscope with a frequency range of 5 MHz or higher, two channels

    b. ToolsPhillips screwdrivers : Large, medium, and smallStandard screwdrivers: Large, medium, and smallNut driver set (Metric)PliersNeedle-nose pliers

    Diagonal cutting pliers

  • 7/21/2019 RJ3iB Controller for Europe

    41/565

    3. TROUBLESHOOTING MAINTENANCE B-81465EN-1/05

    -41-

    3 TROUBLESHOOTING

    This chapter describes the checking method and corrective action for each error code indicated if ahardware alarm occurs. Refer to the operator's manual to release program alarms.

    3.1 POWER CANNOT BE TURNED ON

    Check and Corrective action Figure

    (Check 1)Check that the circuit breaker is on and has not tripped.

    (Corrective action)Turn on the circuit breaker.

  • 7/21/2019 RJ3iB Controller for Europe

    42/565

    B-81465EN-1/05 MAINTENANCE 3. TROUBLESHOOTING

    -42-

    (Check 2)Check whether the LED (PIL: green) on the power supply

    unit is on.

    (Corrective action)

    If the LED is not on, 200 VAC is not supplied to the

    power supply unit. It is likely that fuse F1 in the powersupply unit has blown.

    - If 200 VAC is not supplied:Find the cause by referencing the general schematicdiagram presented in the appendix.

    - If 200 VAC is supplied:

    Find the cause of the blown fuse. Fuse F1 is in the powersupply unit. Before you start troubleshooting, turn off the

    circuit breaker.

    a) If fuse F1 has blown:

    - See Corrective action (1).b) If fuse F1 has not blown: - Replace the power supply unit.

    (Corrective action(1))Causes of blown fuses F1 and corrective action

    a) Check whether the unit and printed-circuit boardconnected to the connectors CP2 and CP3 in the power

    supply unit are abnormal, by referencing the generalschematic diagram presented in the appendix.

    b) Short-circuit in the surge absorber VS1VS1 is inserted to absorb surge voltage between input

    lines.If the surge voltage is excessive or sustained,

    excessively high voltage is applied to VS1 and a failureoccurs in the short-circuit mode, causing F1 to blow. If ashort-circuit occurs in VS1, and there is not a spare part,

    the system is permitted to operate without VS1. In thiscase, however, obtain and install a new VS1 as soon aspossible. VS1 ordering number:

    A50L-2001-0122#G431k

    c) Short-circuit of diode stack DB1

    d) The secondary power supply module is faulty :If one of the causes (b) to (c) above is detected, replace

    the power supply unit with a spare unit.

    The spec. for F1 is : A60L-0001-0396#8.0A

    Check and Corrective action Figure

  • 7/21/2019 RJ3iB Controller for Europe

    43/565

    3. TROUBLESHOOTING MAINTENANCE B-81465EN-1/05

    -43-

    Check and Corrective action Figure

    (Check 3)Check whether the EXON1 and EXON2 signals, and

    the EXOFF1 and EXOFF2 signals are connected onthe terminal block on the panel board.

    (Corrective action)

    If the external ON/OFF function is not used, connectthe EXON1 and EXON2 the EXOFF1 and EXOFF2.

    If the external ON and OFF lines are already used,check the mating contacts and the cable.

  • 7/21/2019 RJ3iB Controller for Europe

    44/565

    B-81465EN-1/05 MAINTENANCE 3. TROUBLESHOOTING

    -44-

    (Check 4)Check whether the connector (JRS11) on the mainboard or the connector (JRS11) on the panel board is

    connected properly. Another probable cause is that

    the cable connected to either of these connectors is

    faulty.

    (Check 5)Check 1 to 3 above confirm that 200 VAC power issupplied to connector CP1 of the power supply unit

    and that the ON/OFF switch functions normally.Therefore check the power supply unit using the

    following procedure:If the LED (ALM: red) on the power supply unit ison

    Check if the +24 V external connection cable is

    connected to 0 V or ground.

    a) Fuse F4 blown :

    See corrective action (2).

    b) None of the above fuses blown [d) is also

    probable] :

    A printed circuit board or unit that uses a DC supplyvoltage (+3.3V, +5V, +24V, or +/-15V) is faulty.

    c) None of the above fuses blown :Check that 200 VAC is supplied to connector CP1. If

    it is supplied replace the power supply unit.

    (Corrective action)

    If the power supply unit is not faulty, replace thepanel board or operators panel.

    (Corrective action (2))

    Causes of blown fuse F4 and corrective actionThe device connected to connector CP5 of the power

    supply unit may be faulty. If no device is connectedto CP5 or the connected device is normal, the +24 V

    power used in a printed circuit board connected to the

    backplane is faulty.The code of F4 is A60L-0001-0046#7.5 :

    Check and Corrective action Figure

  • 7/21/2019 RJ3iB Controller for Europe

    45/565

    3. TROUBLESHOOTING MAINTENANCE B-81465EN-1/05

    -45-

    3.2 ALARM OCCURRENCE SCREEN

    The alarm occurrence screen displays only the alarm conditions that are currently active. If an alarmreset signal is input to reset the alarm conditions, the alarm occurrence screen displays the message"PAUSE or more serious alarm has not occurred."

    The alarm occurrence screen displays only the alarm conditions (if any) that occur after the mostrecently entered alarm reset signal. To erase all alarm displays from the alarm occurrence screen.Press the CLEAR key (+ shift) on the alarm history screen.The alarm occurrence screen is intended to display PAUSE or more serious alarms. It will not displayWARN, NONE, or a reset. It is possible to disable PAUSE and some of more serious alarms frombeing displayed by setting the $ER_NOHIS system variable appropriately.If two or more alarms have occurred, the display begins with the most recent alarm.

    Up to 100 lines can be displayed.If an alarm has a cause code, it is displayed below the line indicating the alarm.

    Fig. 3.2 Alarm Occurrence Screen and Alarm History Screen Display Procedure

    1 Press the screen selection key to select [4 ALARM] 5 Press F3 [ACTIVE]

    2 Press the alarm key 6 Press F3 [HIST]

    3 Automatic alarm display upon occurrence 7 Alarm history screen display

    4 Alarm occurrence screen display

  • 7/21/2019 RJ3iB Controller for Europe

    46/565

    B-81465EN-1/05 MAINTENANCE 3. TROUBLESHOOTING

    -46-

    Displaying the alarm history/alarm detail information

    Step

    1. Press the MENUS key to display the screen menu.

    2. Select [ALARM]. You will see a screen similar to the following

    3. To display the alarm detail screen, press F5, [HELP].

    4. To return to the alarm history screen, press the PREV key.

    NOTE

    The latest alarm is assigned number 1. To view messages that are currently not on the screen, pressthe F5, HELP, then press the right arrow key.

  • 7/21/2019 RJ3iB Controller for Europe

    47/565

    3. TROUBLESHOOTING MAINTENANCE B-81465EN-1/05

    -47-

    5. To delete all the alarm histories, press and hold down the SHIFT key, then press F4, [CLEAR].

    The following map indicates teach pendant operations used to check an alarm.

    NOTE

    When system variable $ER_NOHIS = 1, NONE alarms or WARN alarms are not recorded. When$ER_NOHIS=2, resets are not recorded in the alarm history. When $ER_NOHIS=3, resets, WARN

    alarms, and NONE alarms are not recorded.

  • 7/21/2019 RJ3iB Controller for Europe

    48/565

    B-81465EN-1/05 MAINTENANCE 3. TROUBLESHOOTING

    -48-

    3.3 SAFETY SIGNALS

    The safety signal screen indicates the state of signals related to safety. To be specific, the screenindicates whether each safety signal is currently on. On this screen, it is impossible to change the stateof any safety signal.

    Tab. 3.3 Safety Signals

    Safety signal Description

    Operators panel/operation box

    emergency stop

    This item indicates the state of the emergency stop button on the

    operators panel or operation box. If the EMERGENCY STOP board ispressed, the state is indicated as "TRUE".

    Teach pendant emergency stop This item indicates the state of the emergency stop button on the teachpendant. If the EMERGENCY STOP board is pressed, the state is

    indicated as "TRUE".

    External emergency stop This item indicates the state of the external emergency stop signal. If theEMERGENCY STOP signal is input, the state is indicated as "TRUE".

    Fence open This item indicates the state of the safety fence. If the safety fence isopen, the state is indicated as "TRUE".

    Deadman switch This item indicates whether the DEADMAN switch on the teach

    pendant is grasped. If the teach pendant is operable, and theDEADMAN switch is grasped, the state is indicated as "TRUE". If the

    deadman switch is released when the teach pendant is operable, an alarmoccurs, causing the servo power to be switched off.

    Teach pendant operable This item indicates whether the teach pendant is operable. If the teachpendant is operable, the state is indicated as "TRUE".

    Hand broken This item indicates the state of the hand safety joint. If the hand

    interferes with a workpiece or anything like this, and the safety joint is

    opened, the state is indicated as "TRUE". In this case, an alarm occurs,causing the servo power to be switched off.

    Robot overtravel This item indicates whether the current position of the robot is out of theoperation range. If any robot articulation goes out of the operation range

    beyond the overtravel switch, the state is indicated as "TRUE". In thiscase, an alarm occurs, causing the servo power to be switched off.

    Abnormal air pressure This item indicates the state of the air pressure. The abnormal airpressure signal is connected to the air pressure sensor. If the air pressure

    is not higher than the specified value, the state is indicated as "TRUE".

  • 7/21/2019 RJ3iB Controller for Europe

    49/565

    3. TROUBLESHOOTING MAINTENANCE B-81465EN-1/05

    -49-

    Step

    1. Press the MENUS key to display the screen menu.

    2. Select STATUS on the next page.3. Press F1, [TYPE] to display the screen switching menu.

    4. Select Safety Signal. You will see a screen similar to the following.

  • 7/21/2019 RJ3iB Controller for Europe

    50/565

    B-81465EN-1/05 MAINTENANCE 3. TROUBLESHOOTING

    -50-

    3.4 MASTERING

    Mastering is needed if:1. The SRVO-062 BZAL or SRVO-038 pulse mismatch alarm occurs, or

    2. The pulse coder is replaced.

    Item (1) requires simplified mastering, while item (2) requires zero-degree or jig position mastering.(Zero-degree position mastering is just for quick-fix purposes. After zero-degree position mastering isused, jig position mastering should be performed later.)The mastering procedure is described below. For details, refer to an applicable maintenance manualof the mechanical unit or operator's manual of control unit.

    Condition

    System variable $MASTER_ENB must be set to 1 or 2.

    Step

    1. Press .

    2. Select SYSTEM.

    3. Press F1, TYPE.

    4. Select Master/Cal you will see a screen similar to the following.

    5. Jog the robot to the mastering position. Release the brake on the manual brake control screen ifnecessary.

    6. Select "1 FIXTURE POSITION MASTER" and press the F4 key (yes). Mastering data is set.

    NOTE

    Mastering cannot be performed until axis is rotated enough to establish a pulse.

  • 7/21/2019 RJ3iB Controller for Europe

    51/565

    3. TROUBLESHOOTING MAINTENANCE B-81465EN-1/05

    -51-

    7. Select "6 CALIBRATE" and press the F4 key (yes). Calibration is performed.

    Alternatively, to perform positioning, turn the power off, then turn it on again. Calibration isperformed whenever the power is turned on.

    8. Press F5 "DONE", after mastering.

  • 7/21/2019 RJ3iB Controller for Europe

    52/565

    B-81465EN-1/05 MAINTENANCE 3. TROUBLESHOOTING

    -52-

  • 7/21/2019 RJ3iB Controller for Europe

    53/565

    3. TROUBLESHOOTING MAINTENANCE B-81465EN-1/05

    -53-

    3.5 TROUBLESHOOTING USING THE ERROR CODE

    3.5.1 SRVO-001 Operator panel E-stop

    (Explanation)The emergency stop button on the operator's panel or operation box is pressed.If the SYST-067 (Panel HSSB disconnect) alarm is also generated, or if the LED (green) on thepanel board is turned off, communication between the main board (JRS11) and the panel board(JRS11) is abnormal. The connectors of the cable between the main board and the panel board maybe loose. Or, the cable, panel board, or main board may be faulty. (Note)

    (Action 1)Release the emergency stop button pressed on the operator's panel/operation box.

    (Action 2)

    Check the wires connecting between the emergency stop button and the connector (CRM51) onpanel switch board for continuity. If an open wire is found replace the entire harness.

    (Action 3)With the emergency stop in the released position, check for continuity across the terminals of theswitch. If continuity is not found, the emergency stop button is broken. Replace the switch unit orthe operator's panel/operation box.

    (Action 4)Replace the panel board.

    (Action 5)Replace the cable connecting between the main board (JRS11) and the panel board (JRS11).

    Before executing the (Action6), perform a complete controller back-up to save all your programs andsettings.

    (Action 6)Replace the main board.

    NOTE

    If SYST-067 Panel HSSB disconnect alarm occurs simultaneously or the RDY LED is turned off,the following alarms are also generated.

    SRVO-001 Operator's panel E-stop.SRVO-004 Fence open.SRVO-007 External emergenc