RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, 575 V EDUS341819-D 201806 Engineering Data Heat Pump 60 Hz

RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

RXLQ-TATJU, 208 / 230 VRXLQ-TAYDU, 460 VRXLQ-TAYCU, 575 V

EDUS341819-D201806

Engineering Data

Heat Pump 60 Hz

Page 2: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU
Page 3: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

1

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ-TATJU (208 / 230 V, 60 Hz) RXLQ-TAYDU (460 V, 60 Hz) RXLQ-TAYCU (575 V, 60 Hz)

1. FeaturesandBenefits ................................................................................32. Nomenclature .............................................................................................43. Model Names of Indoor Unit and Outdoor Unit ..........................................7

3.1 Outdoor Units ....................................................................................73.2 Indoor Units .......................................................................................83.3 Air Treatment Equipment ..................................................................9

4. External Appearance ................................................................................104.1 Outdoor Units ..................................................................................104.2 Indoor Units .....................................................................................114.3 Air Treatment Equipment ................................................................12

5. Outdoor Unit Combination ........................................................................136. Capacity Range ........................................................................................14

6.1 Connection Ratio ............................................................................146.2 Indoor Unit Connection Capacity ....................................................15

7. Specifications ...........................................................................................167.1 RXLQ - TATJU ................................................................................167.2 RXLQ - TAYDU ...............................................................................187.3 RXLQ - TAYCU ...............................................................................20

8. Dimensions ...............................................................................................229. Service Space ..........................................................................................2410. Center of Gravity ......................................................................................2611. Foundation Drawing .................................................................................2812. Piping Diagrams .......................................................................................2913. Wiring Diagrams .......................................................................................3114. Field Wiring ..............................................................................................4115. Electrical Characteristics ..........................................................................4316. Operation Limits .......................................................................................4617. Sound Levels (Reference Data) ...............................................................4718. Accessories ..............................................................................................50

18.1 Optional Accessories ......................................................................5019. Selection Procedure .................................................................................51

19.1 Selection Procedure ........................................................................5120. Caution Label ...........................................................................................57

20.1 RXLQ72 - 120TATJU / TAYDU / TAYCU .......................................57

Page 4: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

2

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

21. Caution for Refrigerant Leaks ..................................................................6621.1 Introduction .....................................................................................6621.2 Procedure for Checking Maximum Concentration ..........................67

22. Safety Devices Setting .............................................................................6922.1 FXFQ-T ...........................................................................................6922.2 FXZQ-TA .........................................................................................6922.3 FXUQ-P ..........................................................................................6922.4 FXEQ-P ...........................................................................................6922.5 FXDQ-M ..........................................................................................7022.6 FXSQ-TA ........................................................................................7022.7 FXMQ-PB ........................................................................................7022.8 FXMQ-M .........................................................................................7022.9 FXHQ-M ..........................................................................................7122.10 FXAQ-P ...........................................................................................7122.11 FXLQ-M, FXNQ-M ..........................................................................7122.12 FXTQ-TA .........................................................................................71

Appendix........................................................................................................731. Introduction ...............................................................................................74

1.1 ED Book List ...................................................................................741.2 Publication List of Engineering Data for VRV Products ..................75

2. GuideSpecifications .................................................................................772.1 GuideSpecifications .......................................................................77

Page 5: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

3

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

1. Features and Benefits

Engineered for optimized life cycle cost, Daikin’s new VRV AURORATM Heat Pump Series completes the VRV AURORATM family. VRV AURORA Heat Pumps demonstrate Daikin’s technologicalleadershipbyofferinghighseasonalefficiencyandcapacitiesacrosstheentireoperational range.

• Available in 6, 8, 10 ton single modules and 12, 16, 20 ton multi-module systems•VRFIndustry’sfirstaircooledsystemthatdeliversheatingdownto-22°F(-30°C)asstandard• Daikin’s inverter based vapor injection compressor is designed to deliver heating capacity of up to100%ofnominalat0°F(-18°C),upto85%ofnominalat-13°F(-25°C)andupto60%ofnominalat-22°F(-30°C)

•Refrigerant-cooledefficientandstableinverterboardoperation,independentofambientconditions

• Hot gas base pan circuit allows installation without an additional drain pan heater• Added peace of mind with Auto Changeover ability to back up (auxiliary) heat•YearroundcomfortandenergyefficiencydeliveredbycombiningVRV and VRT technologies• Designed and optimized for Total Cost of Construction (TCC) and reduced Life Cycle Cost (LCC)•Corrosionresistant,1000hourssaltspraytestedDaikinPEbluefinheatexchanger• Ships factory standard with coil guards• Seamless connection to all VRV M, P and T series indoor units•Easecommissioningwithabilitytoprogramsettingsoffsiteusingnewconfiguratortool•3-digit7-segmentdigitaldisplayontheunitforimprovedandfasterconfiguration,commissioning,

and troubleshooting• Backed by 10 year parts limited warranty and 10 years replacement compressor limited warranty*

* Complete warranty details available from local distributor or manufacturer’s representative or at www.daikincomfort.com

Page 6: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

4

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

2. Nomenclature

Outdoor Unit

240QR X L T A UYD

Standard SymbolU: United States of America

Power Supply SymbolTJ: 3 phase, 208/230 V, 60 HzYD: 3 phase, 460 V, 60 HzYC: 3 phase, 575 V, 60 Hz

Indicates Minor Change Category

Indicates Major Design Category

RefrigerantQ: R410A

TypeL:

Series categoryX: Heat pumpE: Heat recovery

Unit categoryR: Outdoor unit for air cooled type

Capacity Indication in cooling 72: 72,000 Btu/h 96: 96,000 Btu/h

144: 144,000 Btu/h192: 192,000 Btu/h240: 240,000 Btu/h120: 120,000 Btu/h

Page 7: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

5

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

Indoor Unit

M 54 VJPB UX QF

Standard symbolU: United States of America

Power supply symbolVJ: 1 phase, 208/230 V, 60 Hz

Indicates major design category

Capacity indication in cooling05: 5,800 Btu/h 18: 18,000 Btu/h 48: 48,000 Btu/h07: 7,500 Btu/h 24: 24,000 Btu/h 54: 54,000 Btu/h09: 9,500 Btu/h 30: 30,000 Btu/h 60: 60,000 Btu/h12: 12,000 Btu/h 36: 36,000 Btu/h 72: 72,000 Btu/h15: 15,000 Btu/h 42: 42,000 Btu/h 96: 96,000 Btu/h

RefrigerantQ: R410A

ShapeF: Ceiling Mounted Cassette (Round Flow with Sensing)Z: VISTA™ 2 × 2 Cassette UnitU: 4-Way Blow Ceiling-SuspendedE: One Way Blow CassetteD: Slim Ceiling Mounted DuctS: MSP Concealed Ducted UnitM: Ceiling Mounted DuctH: Ceiling SuspendedA: Wall MountedL: Floor StandingN: Concealed Floor StandingT: Air Handling Unit

Series categoryX: Inverter

Unit categoryF: Indoor Unit for Air Cooled Type

Page 8: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

6

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

Air Treatment Equipment

M 48 VJ UM FX QF

Standard symbolU: United States of America

Power supply symbolVJ: 1 phase, 208/230 V, 60 Hz

Outdoor air processing unit

Indicates major design category

Capacity indication in cooling48: 48,000 Btu/h72: 72,000 Btu/h96: 96,000 Btu/h

RefrigerantQ: R410A

ShapeM: Ceiling Mounted Duct

Series categoryX: Inverter

Unit categoryF: Indoor Unit for Air Cooled Type

Outdoor Air Processing Unit

UG300V A M VJ

Standard symbolU: United States of America

Power supply symbolVJ: 1 phase, 208/230 V, 60 Hz

Indicates major design category

Airflow rate (H)300: 300 cfm 600: 600 cfm470: 470 cfm 1200: 1,200 cfm

Mounted type

Air

Ventilation

Energy Recovery Ventilator (VAM series)

Page 9: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

7

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

3. Model Names of Indoor Unit and Outdoor Unit3.1 Outdoor Units

Capacity Range 6 ton 8 ton 10 ton 12 ton 16 ton 20 ton Power Supply, StandardCapacity Index 72 96 120 144 192 240

Heat Pump208/230 V RXLQ- 72TA 96TA 120TA 144TA 192TA 240TA TJU460 V RXLQ- 72TA 96TA 120TA 144TA 192TA 240TA YDU575 V RXLQ- 72TA 96TA 120TA 144TA 192TA 240TA YCU

TJ : 3 phase, 208/230 V, 60 HzYD : 3 phase, 460 V, 60 HzYC : 3 phase, 575 V, 60 HzU(TJU) : Standard Symbol

Heat Pump 208/230 V

Model name RXLQ72TATJU RXLQ96TATJU RXLQ120TATJUOutdoor unit 1 RXLQ72TATJU RXLQ96TATJU RXLQ120TATJU

Model name RXLQ144TATJU RXLQ192TATJU RXLQ240TATJUOutdoor unit 1 RXLQ72TATJU RXLQ96TATJU RXLQ120TATJUOutdoor unit 2 RXLQ72TATJU RXLQ96TATJU RXLQ120TATJU

Heat Pump 460 V

Model name RXLQ72TAYDU RXLQ96TAYDU RXLQ120TAYDUOutdoor unit 1 RXLQ72TAYDU RXLQ96TAYDU RXLQ120TAYDU

Model name RXLQ144TAYDU RXLQ192TAYDU RXLQ240TAYDUOutdoor unit 1 RXLQ72TAYDU RXLQ96TAYDU RXLQ120TAYDUOutdoor unit 2 RXLQ72TAYDU RXLQ96TAYDU RXLQ120TAYDU

Heat Pump 575 V

Model name RXLQ72TAYCU RXLQ96TAYCU RXLQ120TAYCUOutdoor unit 1 RXLQ72TAYCU RXLQ96TAYCU RXLQ120TAYCU

Model name RXLQ144TAYCU RXLQ192TAYCU RXLQ240TAYCUOutdoor unit 1 RXLQ72TAYCU RXLQ96TAYCU RXLQ120TAYCUOutdoor unit 2 RXLQ72TAYCU RXLQ96TAYCU RXLQ120TAYCU

Page 10: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

8

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

3.2 Indoor Units

Capacity Range 0.5 ton 0.6 ton 0.8 ton 1 ton 1.25 ton 1.5 ton 2 ton 2.5 ton 3 ton 3.5 ton 4 ton 4.5 ton 5 ton 6 ton 8 ton Power Supply, StandardCapacity Index 5.8 7.5 9.5 12 15 18 20 24 30 36 42 48 54 60 72 96

Ceiling Mounted Cassette (Round Flow with Sensing) Type

FXFQ — 07T 09T 12T 15T 18T — 24T 30T 36T — 48T — — — —

VJU

VISTA™ 2 × 2 Cassette Unit FXZQ 05TA 07TA 09TA 12TA 15TA 18TA — — — — — — — — — —4-Way Blow Ceiling-Suspended Type FXUQ — — — — — — 18P 24P 30P 36P — — — — — —

One Way Blow Cassette Type FXEQ — 07P 09P 12P 15P 18P — 24P — — — — — — — —

Slim Ceiling Mounted Duct Type FXDQ — 07M 09M 12M — 18M — 24M — — — — — — — —

MSP Concealed Ducted Unit FXSQ 05TA 07TA 09TA 12TA 15TA 18TA — 24TA 30TA 36TA — 48TA 54TA — — —Ceiling Mounted Duct Type (Middle and High Static Pressure)

FXMQ — 07PB 09PB 12PB 15PB 18PB — 24PB 30PB 36PB — 48PB 54PB — — —

Ceiling Mounted Duct Type FXMQ — — — — — — — — — — — — — — 72M 96MCeiling Suspended Type FXHQ — — — 12M — — — 24M — 36M — — — — — —Wall Mounted Type FXAQ — 07P 09P 12P — 18P — 24P — — — — — — — —Floor Standing Type FXLQ — 07M 09M 12M — 18M — 24M — — — — — — — —Concealed Floor Standing Type FXNQ — 07M 09M 12M — 18M — 24M — — — — — — — —

Air Handling Unit FXTQ— — 09TA 12TA — 18TA — 24TA 30TA 36TA 42TA 48TA 54TA 60TA — — VJUA— — 09TA 12TA — 18TA — 24TA 30TA 36TA 42TA 48TA 54TA 60TA — — VJUD

VJ : 1 phase, 208/230 V, 60 HzU(VJU) : Standard Symbol

Page 11: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

9

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

3.3 Air Treatment EquipmentOutdoor Air Processing Unit

Series Model Name Power Supply, StandardFXMQ 48MF 72MF 96MF VJU

VJ : 1 phase, 208/230 V, 60 HzU(VJU) : Standard Symbol

Energy Recovery Ventilator (VAM series)

Series Model Name Power Supply, StandardVAM 300G 470G 600G 1200G VJU

VJ : 1 phase, 208/230 V, 60 HzU(VJU) : Standard Symbol

Page 12: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

10

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

4. External Appearance4.1 Outdoor UnitsSingle Outdoor Unit

RXLQ72TATJURXLQ96TATJU

RXLQ120TATJU

RXLQ72TAYDURXLQ96TAYDU

RXLQ120TAYDU

RXLQ72TAYCURXLQ96TAYCU

RXLQ120TAYCU

6, 8, 10 ton

Double Outdoor Units

RXLQ144TATJURXLQ192TATJURXLQ240TATJU

RXLQ144TAYDURXLQ192TAYDURXLQ240TAYDU

RXLQ144TAYCURXLQ192TAYCURXLQ240TAYCU

12, 16, 20 ton

Page 13: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

11

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

4.2 Indoor Units

Ceilingmountedcassette(Roundflowwithsensing)type

FXFQ-T

Shown with BYCQ125B-W1

Ceiling mounted duct type

FXMQ-M

VISTA™ 2 × 2 Cassette Unit

FXZQ-TA

Shown with BYFQ60C3W1W Shown with BYFQ60C3W1S

Ceiling suspended type

FXHQ-M

4-way blow ceiling-suspended type

FXUQ-P

Wall mounted type

FXAQ-P

One way blow cassette type

FXEQ-P

Floor standing type

FXLQ-M

Slim ceiling mounted duct type

FXDQ-M

Concealedfloorstandingtype

FXNQ-M

MSP Concealed Ducted Unit

FXSQ-TA

Air handling unit

FXTQ-TA

Ceiling mounted duct type (Middle and high static pressure)

FXMQ-PB

Page 14: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

12

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

4.3 Air Treatment Equipment

Outdoor air processing unit

FXMQ-MF

Energy recovery ventilator (VAM series)

VAM-G

Page 15: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

13

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

5. Outdoor Unit Combination

Model nameSystem capacity Number of

unitsModule Outdoor Unit Multi Connection Piping Kit

1Ton HP kW 72 96 120RXLQ72TATJURXLQ72TAYDURXLQ72TAYCU

6 7.5 21.1 1 l

—RXLQ96TATJURXLQ96TAYDURXLQ96TAYCU

8 10.0 28.1 1 l

RXLQ120TATJURXLQ120TAYDURXLQ120TAYCU

10 12.5 35.2 1 l

RXLQ144TATJURXLQ144TAYDURXLQ144TAYCU

12 15.0 42.2 2 ll

BHFP22P100URXLQ192TATJURXLQ192TAYDURXLQ192TAYCU

16 20.0 56.3 2 ll

RXLQ240TATJURXLQ240TAYDURXLQ240TAYCU

20 25.0 70.3 2 ll

Note:1. For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.

Page 16: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

14

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

6. Capacity Range6.1 Connection Ratio

Connection ratio =Total capacity index of the indoor units

Capacity index of the outdoor units

TypeMin.

connection ratio

Max. connection ratio

Types of connected indoor units Type of connected air treatment equipments

When using only FXDQ, FXMQ-PB, FXAQ, FXSQ07-

54T

When using at least one FXFQ07/09,

FXZQ05TFXSQ05T

Other indoor unit models

FXMQ-MF

When FXMQ-MF is only connected

When FXMQ-MF and indoor units are

connectedSingle outdoor unit

70% 200% *1180% *1 200% *1

100% 100% *2Double outdoor units 160% *1 160% *1

Notes:*1. Iftheoperationalcapacityofindoorunitsismorethan130%,lowairflowoperationisenforcedinalltheindoorunits.Fieldsettingnowexiststo

configurethissituation.Forcoolingandheatingmode–seebelow.*2. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total connection capacity of the outdoor-air

processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%.

Indoor unit fan tap settingIndoor units fan speed limitation related to connection capacity and outdoor air temperature for energy saving.Default value = 0

Value Indoor unit fan tap setting0 FanspeedislimitedtoLtapwhenindoorunitscapacity≥130%.1 Inheatingmode,fanspeedislimitedtoLtapwhenindoorunitscapacity≥130%.2 Fan speed follows the setting of the remote controllers (not limited by indoor units connection capacity).

3FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow85.1°F(29.5°C)andindoorairtemperature is in condition A (*1). It returns to remote controller setting when outdoor air temperature goes up to over 90.5°F(32.5°C)orindoorairtemperatureisinconditionB(*2).

4FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow74.3°F(23.5°C)andindoorairtemperature is in condition A (*1). It returns to remote controller setting when outdoor air temperature goes up to over 79.7°F(26.5°C)orindoorairtemperatureisinconditionB(*2).

5FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow66.7°F(19.3°C)andindoorairtemperature is in condition A (*1). It returns to remote controller setting when outdoor air temperature goes up to over 72.1°F(22.3°C)orindoorairtemperatureisinconditionB(*2).

6 FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow85.1°F(29.5°C).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover90.5°F(32.5°C).

7 FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow74.3°F(23.5°C).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover79.7°F(26.5°C).

8 FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow66.7°F(19.3°C).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover72.1°F(22.3°C).

*1. IndoorconditionA:Temperaturedifference(indoorairtemperature–settemperature)ismorethan–2.7°F(–1.5°C)andlessthan5.4°F(3°C).*2. IndoorconditionB:Temperaturedifference(indoorairtemperature–settemperature)is–2.7°F(–1.5°C)orless,or5.4°F(3°C)ormore.

Page 17: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

15

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

6.2 Indoor Unit Connection Capacity

Type Ton Capacity index Model name CombinationOutdoor unit multi

connection piping kit *1

Total capacity index of connectable indoor

units *2

Maximum number of connectable indoor

units

Single outdoor unit

6 72 RXLQ72TA RXLQ72TA—

51 to 93 (144) 128 96 RXLQ96TA RXLQ96TA 68 to 124 (192) 1610 120 RXLQ120TA RXLQ120TA 84 to 156 (240) 20

Double outdoor units

12 144 RXLQ144TA RXLQ72TA+ RXLQ72TA

BHFP22P100U

101 to 187 (230) 25

16 192 RXLQ192TA RXLQ96TA+ RXLQ96TA 135 to 249 (307) 33

20 240 RXLQ240TA RXLQ120TA+ RXLQ120TA 168 to 312 (384) 41

Note:*1. For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.*2. Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single outdoor unit, 160% for double

outdoor units.

Page 18: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

16

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

7. Specifications7.1 RXLQ - TATJU

Model name RXLQ72TATJU RXLQ96TATJU RXLQ120TATJUPower supply 3 phase, 208/230 V, 60 Hz 3 phase, 208/230 V, 60 Hz 3 phase, 208/230 V, 60 Hz

Cooling capacity

Nominal Btu/h (kW)

1 72,000 (21.1) 1 96,000 (28.1) 3 120,000 (35.2)Rated 1 69,000 (20.2) 1 92,000 (27.0) 3 114,000 (33.4)

Heating capacity

Nominal Btu/h (kW)

2 81,000 (23.7) 2 108,000 (31.7) 4 135,000 (39.6)Rated 2 77,000 (22.6) 2 103,000 (30.2) 4 129,000 (37.8)

Casing color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)

Dimensions: (H × W × D) in. (mm)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

Heat exchanger Crossfincoil Crossfincoil Crossfincoil

Compressor

Type Hermetically sealed scroll type Hermetically sealed scroll type Hermetically sealed scroll typeDisplacement m3/h 12.7 17.5 23.1Number of revolutions r/min 3,738 3,294 4,350Motor output × Number of units kW 3.9 × 1 5.0 × 1 6.6 × 1

Starting method Soft start Soft start Soft start

Fan

Type Propeller fan Propeller fan Propeller fanMotor output kW 0.80 × 2 0.80 × 2 0.80 × 2

Airflowrate cfm (m3/min) 7,283 (206) 7,989 (226) 8,806 (249)

Drive Direct drive Direct drive Direct drive

Connecting pipes

Liquid pipe in. (mm)

f3/8 (9.5) C1220T (Brazing connection)

f3/8 (9.5) C1220T (Brazing connection)

f1/2 (12.7) C1220T (Brazing connection)

Gas pipe in. (mm)

f3/4 (19.1) C1220T (Brazing connection)

f7/8 (22.2) C1220T (Brazing connection)

f1-1/8 (28.6) C1220T (Brazing connection)

Weight lbs (kg) 727 (330) 793 (360) 793 (360)Sound pressure level (Reference data) dB(A) 60 (65 5) 61 (67 5) 63.5 (67 5)

Sound power level (Reference data) dB 79 80.5 84.5

Safety devices

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting device

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting device

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting deviceDefrost method Deicer Deicer DeicerCapacity control % 10.7-100 12.8-100 11.7-100

RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 (11.7) 25.8 (11.7) 25.8 (11.7)Control Electronic expansion valve Electronic expansion valve Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual,

Connection pipes, Clamps

Installation manual, Operation manual,

Connection pipes, Clamps

Installation manual, Operation manual,

Connection pipes, Clamps

Drawing No.Specification C: 4D112564A C: 4D112565A C: 4D112566ASound level C: 4D107376A C: 4D107377A C: 4D107378A

Notes:1. Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)

Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,50ft.(15.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).2. Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)

Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,50ft.(15.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).3. Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)

Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,75ft.(23m)fornon-ductedindoorunits,leveldifference:0ft.(0m).4. Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)

Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,75ft.(23m)fornon-ductedindoorunits,leveldifference:0ft.(0m).5. Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound

pressure at those conditions.

Page 19: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

17

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

Model name (Combination Unit) RXLQ144TATJU RXLQ192TATJU RXLQ240TATJU

Model name (Independent Unit) RXLQ72TATJURXLQ72TATJU

RXLQ96TATJURXLQ96TATJU

RXLQ120TATJURXLQ120TATJU

Power supply 3 phase, 208/230 V, 60 Hz 3 phase, 208/230 V, 60 Hz 3 phase, 208/230 V, 60 Hz

Cooling capacity

Nominal Btu/h (kW)

1 144,000 (42.2) 1 192,000 (56.3) 1 240,000 (70.3)Rated 1 138,000 (40.4) 1 184,000 (53.9) 1 228,000 (66.8)

Heating capacity

Nominal Btu/h (kW)

2 162,000 (47.5) 2 216,000 (63.3) 2 270,000 (79.1)Rated 2 154,000 (45.1) 2 206,000 (60.4) 2 256,000 (75.0)

Casing color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)

Dimensions: (H × W × D) in. (mm)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

Heat exchanger Crossfincoil Crossfincoil Crossfincoil

Compressor

Type Hermetically sealed scroll type Hermetically sealed scroll type Hermetically sealed scroll typeDisplacement m3/h 12.9 + 12.9 17.7 + 17.7 22.4 + 22.4Number of revolutions r/min 3,804 + 3,804 3,342 + 3,342 4,230 + 4,230Motor output × Number of units kW 4.0 × 1 + 4.0 × 1 5.1 × 1 + 5.1 × 1 6.5 × 1 + 6.5 × 1

Starting method Soft start Soft start Soft start

Fan

Type Propeller fan Propeller fan Propeller fanMotor output kW (0.80 × 2) × 2 (0.80 × 2) × 2 (0.80 × 2) × 2

Airflowrate cfm (m3/min) 7,283 + 7,283 (206 + 206) 7,989 + 7,989 (226 + 226) 8,806 + 8,806 (249 + 249)

Drive Direct drive Direct drive Direct drive

Connecting pipes

Liquid pipe in. (mm)

f1/2 (12.7) C1220T (Brazing connection)

f5/8 (15.9) C1220T (Brazing connection)

f5/8 (15.9) C1220T (Brazing connection)

Gas pipe in. (mm)

f1-1/8 (28.6) C1220T (Brazing connection)

f1-1/8 (28.6) C1220T (Brazing connection)

f1-3/8 (34.9) C1220T (Brazing connection)

Weight lbs (kg) 727 + 727 (330 + 330) 793 + 793 (360 + 360) 793 + 793 (360 + 360) Sound pressure level (Reference data) dB(A) 63 (68 3) 64 (70 3) 67 (70 3)

Sound power level (Reference data) dB 82 83.5 87.5

Safety devices

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting device

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting device

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting deviceDefrost method Deicer Deicer DeicerCapacity control % 5.4-100 6.4-100 5.9-100

RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7)Control Electronic expansion valve Electronic expansion valve Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual,

Connection pipes, Clamps

Installation manual, Operation manual,

Connection pipes, Clamps

Installation manual, Operation manual,

Connection pipes, Clamps

Drawing No.Specification C: 4D112567A C: 4D112568A C: 4D112569ASound level — — —

Notes:1. Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)

Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).2. Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)

Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).3. Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound

pressure at those conditions.

Page 20: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

18

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

7.2 RXLQ - TAYDU

Model name RXLQ72TAYDU RXLQ96TAYDU RXLQ120TAYDUPower supply 3 phase, 460 V, 60 Hz 3 phase, 460 V, 60 Hz 3 phase, 460 V, 60 Hz

Cooling capacity

Nominal Btu/h (kW)

1 72,000 (21.1) 1 96,000 (28.1) 3 120,000 (35.2)Rated 1 69,000 (20.2) 1 92,000 (27.0) 3 114,000 (33.4)

Heating capacity

Nominal Btu/h (kW)

2 81,000 (23.7) 2 108,000 (31.7) 4 135,000 (39.6)Rated 2 77,000 (22.6) 2 103,000 (30.2) 4 129,000 (37.8)

Casing color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)

Dimensions: (H × W × D) in. (mm)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

Heat exchanger Crossfincoil Crossfincoil Crossfincoil

Compressor

Type Hermetically sealed scroll type Hermetically sealed scroll type Hermetically sealed scroll typeDisplacement m3/h 12.7 17.5 23.1Number of revolutions r/min 3,738 3,294 4,350Motor output × Number of units kW 3.9 × 1 5.0 × 1 6.6 × 1

Starting method Soft start Soft start Soft start

Fan

Type Propeller fan Propeller fan Propeller fanMotor output kW 0.60 × 2 0.60 × 2 0.60 × 2

Airflowrate cfm (m3/min) 7,283 (206) 7,989 (226) 8,806 (249)

Drive Direct drive Direct drive Direct drive

Connecting pipes

Liquid pipe in. (mm)

f3/8 (9.5) C1220T (Brazing connection)

f3/8 (9.5) C1220T (Brazing connection)

f1/2 (12.7) C1220T (Brazing connection)

Gas pipe in. (mm)

f3/4 (19.1) C1220T (Brazing connection)

f7/8 (22.2) C1220T (Brazing connection)

f1-1/8 (28.6) C1220T (Brazing connection)

Weight lbs (kg) 727 (330) 793 (360) 793 (360)Sound pressure level (Reference data) dB(A) 60 (65 5) 61 (67 5) 63.5 (67 5)

Sound power level (Reference data) dB 79 80.5 84.5

Safety devices

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting device

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting device

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting deviceDefrost method Deicer Deicer DeicerCapacity control % 10.7-100 12.8-100 11.7-100

RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 (11.7) 25.8 (11.7) 25.8 (11.7)Control Electronic expansion valve Electronic expansion valve Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual,

Connection pipes, Clamps

Installation manual, Operation manual,

Connection pipes, Clamps

Installation manual, Operation manual,

Connection pipes, Clamps

Drawing No.Specification C: 4D112570A C: 4D112571A C: 4D112572ASound level C: 4D107376A C: 4D107377A C: 4D107378A

Notes:1. Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)

Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,50ft.(15.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).2. Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)

Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,50ft.(15.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).3. Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)

Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,75ft.(23m)fornon-ductedindoorunits,leveldifference:0ft.(0m).4. Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)

Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,75ft.(23m)fornon-ductedindoorunits,leveldifference:0ft.(0m).5. Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound

pressure at those conditions.

Page 21: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

19

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

Model name (Combination Unit) RXLQ144TAYDU RXLQ192TAYDU RXLQ240TAYDU

Model name (Independent Unit) RXLQ72TAYDURXLQ72TAYDU

RXLQ96TAYDURXLQ96TAYDU

RXLQ120TAYDURXLQ120TAYDU

Power supply 3 phase, 460 V, 60 Hz 3 phase, 460 V, 60 Hz 3 phase, 460 V, 60 Hz

Cooling capacity

Nominal Btu/h (kW)

1 144,000 (42.2) 1 192,000 (56.3) 1 240,000 (70.3)Rated 1 138,000 (40.4) 1 184,000 (53.9) 1 228,000 (66.8)

Heating capacity

Nominal Btu/h (kW)

2 162,000 (47.5) 2 216,000 (63.3) 2 270,000 (79.1)Rated 2 154,000 (45.1) 2 206,000 (60.4) 2 256,000 (75.0)

Casing color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)

Dimensions: (H × W × D) in. (mm)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

Heat exchanger Crossfincoil Crossfincoil Crossfincoil

Compressor

Type Hermetically sealed scroll type Hermetically sealed scroll type Hermetically sealed scroll typeDisplacement m3/h 12.9 + 12.9 17.7 + 17.7 22.4 + 22.4Number of revolutions r/min 3,804 + 3,804 3,342 + 3,342 4,230 + 4,230Motor output × Number of units kW 4.0 × 1 + 4.0 × 1 5.1 × 1 + 5.1 × 1 6.5 × 1 + 6.5 × 1

Starting method Soft start Soft start Soft start

Fan

Type Propeller fan Propeller fan Propeller fanMotor output kW (0.60 × 2) × 2 (0.60 × 2) × 2 (0.60 × 2) × 2

Airflowrate cfm (m3/min) 7,283 + 7,283 (206 + 206) 7,989 + 7,989 (226 + 226) 8,806 + 8,806 (249 + 249)

Drive Direct drive Direct drive Direct drive

Connecting pipes

Liquid pipe in. (mm)

f1/2 (12.7) C1220T (Brazing connection)

f5/8 (15.9) C1220T (Brazing connection)

f5/8 (15.9) C1220T (Brazing connection)

Gas pipe in. (mm)

f1-1/8 (28.6) C1220T (Brazing connection)

f1-1/8 (28.6) C1220T (Brazing connection)

f1-3/8 (34.9) C1220T (Brazing connection)

Weight lbs (kg) 727 + 727 (330 + 330) 793 + 793 (360 + 360) 793 + 793 (360 + 360)Sound pressure level (Reference data) dB(A) 63 (68 3) 64 (70 3) 67 (70 3)

Sound power level (Reference data) dB 82 83.5 87.5

Safety devices

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting device

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting device

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting deviceDefrost method Deicer Deicer DeicerCapacity control % 5.4-100 6.4-100 5.9-100

RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7)Control Electronic expansion valve Electronic expansion valve Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual,

Connection pipes, Clamps

Installation manual, Operation manual,

Connection pipes, Clamps

Installation manual, Operation manual,

Connection pipes, Clamps

Drawing No.Specification C: 4D112573A C: 4D112574A C: 4D112575ASound level — — —

Notes:1. Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)

Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).2. Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)

Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).3. Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound

pressure at those conditions.

Page 22: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

20

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

7.3 RXLQ - TAYCU

Model name RXLQ72TAYCU RXLQ96TAYCU RXLQ120TAYCUPower supply 3 phase, 575 V, 60 Hz 3 phase, 575 V, 60 Hz 3 phase, 575 V, 60 Hz

Cooling capacity

Nominal Btu/h (kW)

1 72,000 (21.1) 1 96,000 (28.1) 3 120,000 (35.2)Rated 1 69,000 (20.2) 1 92,000 (27.0) 3 114,000 (33.4)

Heating capacity

Nominal Btu/h (kW)

2 81,000 (23.7) 2 108,000 (31.7) 4 135,000 (39.6)Rated 2 77,000 (22.6) 2 103,000 (30.2) 4 129,000 (37.8)

Casing color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)

Dimensions: (H × W × D) in. (mm)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

Heat exchanger Crossfincoil Crossfincoil Crossfincoil

Compressor

Type Hermetically sealed scroll type Hermetically sealed scroll type Hermetically sealed scroll typeDisplacement m3/h 12.7 17.5 23.1Number of revolutions r/min 3,738 3,294 4,350Motor output × Number of units kW 3.9 × 1 5.0 × 1 6.6 × 1

Starting method Soft start Soft start Soft start

Fan

Type Propeller fan Propeller fan Propeller fanMotor output kW 0.7 × 2 0.7 × 2 0.7 × 2

Airflowrate cfm (m3/min) 7,283 (206) 7,989 (226) 8,806 (249)

Drive Direct drive Direct drive Direct drive

Connecting pipes

Liquid pipe in. (mm)

f3/8 (9.5) C1220T (Brazing connection)

f3/8 (9.5) C1220T (Brazing connection)

f1/2 (12.7) C1220T (Brazing connection)

Gas pipe in. (mm)

f3/4 (19.1) C1220T (Brazing connection)

f7/8 (22.2) C1220T (Brazing connection)

f1-1/8 (28.6) C1220T (Brazing connection)

Weight lbs (kg) 727 (330) 793 (360) 793 (360) Sound pressure level (Reference data) dB(A) 60 (65 5) 61 (67 5) 63.5 (67 5)

Sound power level (Reference data) dB 79 80.5 84.5

Safety devices

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting device

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting device

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting deviceDefrost method Deicer Deicer DeicerCapacity control % 10.7-100 12.8-100 11.7-100

RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 (11.7) 25.8 (11.7) 25.8 (11.7)Control Electronic expansion valve Electronic expansion valve Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual,

Connection pipes, Clamps

Installation manual, Operation manual,

Connection pipes, Clamps

Installation manual, Operation manual,

Connection pipes, Clamps

Drawing No.Specification C: 4D112544A C: 4D112545A C: 4D112546ASound level C: 4D107376A C: 4D107377A C: 4D107378A

Notes:1. Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)

Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,50ft.(15.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).2. Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)

Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,50ft.(15.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).3. Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)

Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,75ft.(23m)fornon-ductedindoorunits,leveldifference:0ft.(0m).4. Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)

Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,75ft.(23m)fornon-ductedindoorunits,leveldifference:0ft.(0m).5. Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound

pressure at those conditions.

Page 23: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

21

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

Model name (Combination Unit) RXLQ144TAYCU RXLQ192TAYCU RXLQ240TAYCU

Model name (Independent Unit) RXLQ72TAYCURXLQ72TAYCU

RXLQ96TAYCURXLQ96TAYCU

RXLQ120TAYCURXLQ120TAYCU

Power supply 3 phase, 575 V, 60 Hz 3 phase, 575 V, 60 Hz 3 phase, 575 V, 60 Hz

Cooling capacity

Nominal Btu/h (kW)

1 144,000 (42.2) 1 192,000 (56.3) 1 240,000 (70.3)Rated 1 138,000 (40.4) 1 184,000 (53.9) 1 228,000 (66.8)

Heating capacity

Nominal Btu/h (kW)

2 162,000 (47.5) 2 216,000 (63.3) 2 270,000 (79.1)Rated 2 154,000 (45.1) 2 206,000 (60.4) 2 256,000 (75.0)

Casing color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)

Dimensions: (H × W × D) in. (mm)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

Heat exchanger Crossfincoil Crossfincoil Crossfincoil

Compressor

Type Hermetically sealed scroll type Hermetically sealed scroll type Hermetically sealed scroll typeDisplacement m3/h 12.9 + 12.9 17.7 + 17.7 22.4 + 22.4Number of revolutions r/min 3,804 + 3,804 3,342 + 3,342 4,230 + 4,230Motor output × Number of units kW 4.0 × 1 + 4.0 × 1 5.1 × 1 + 5.1 × 1 6.5 × 1 + 6.5 × 1

Starting method Soft start Soft start Soft start

Fan

Type Propeller fan Propeller fan Propeller fanMotor output kW (0.7 × 2) × 2 (0.7 × 2) × 2 (0.7 × 2) × 2

Airflowrate cfm (m3/min) 7,283 + 7,283 (206 + 206) 7,989 + 7,989 (226 + 226) 8,806 + 8,806 (249 + 249)

Drive Direct drive Direct drive Direct drive

Connecting pipes

Liquid pipe in. (mm)

f1/2 (12.7) C1220T (Brazing connection)

f5/8 (15.9) C1220T (Brazing connection)

f5/8 (15.9) C1220T (Brazing connection)

Gas pipe in. (mm)

f1-1/8 (28.6) C1220T (Brazing connection)

f1-1/8 (28.6) C1220T (Brazing connection)

f1-3/8 (34.9) C1220T (Brazing connection)

Weight lbs (kg) 727 + 727 (330 + 330) 793 + 793 (360 + 360) 793 + 793 (360 + 360)Sound pressure level (Reference data) dB(A) 63 (68 3) 64 (70 3) 67 (70 3)

Sound power level (Reference data) dB 82 83.5 87.5

Safety devices

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting device

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting device

High pressure switch, Fan driver overload protector,

Overcurrent fuse, Inverter overload protector,

Leak detecting deviceDefrost method Deicer Deicer DeicerCapacity control % 5.4-100 6.4-100 5.9-100

RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7)Control Electronic expansion valve Electronic expansion valve Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual,

Connection pipes, Clamps

Installation manual, Operation manual,

Connection pipes, Clamps

Installation manual, Operation manual,

Connection pipes, Clamps

Drawing No.Specification C: 4D112547A C: 4D112548A C: 4D112549ASound level — — —

Notes:1. Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)

Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).2. Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)

Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).3. Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound

pressure at those conditions.

Page 24: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

22

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

8. Dimensions

RXLQ72 - 120TATJU / TAYDU / TAYCU

C: 3

D11

2576

Uni

t : in

. (m

m)

Li

quid

pip

e

Ø1/

2 Br

azin

g co

nnec

tion

Ø1

Braz

ing

conn

ectio

1-1/

8 Br

azin

g co

nnec

tion

Not

es)

1. F

or p

ipin

g co

nnec

tion

met

hod

(fron

t and

bot

tom

si

des)

, see

the

inst

alla

tion

man

ual.

2. G

as p

ipe

RXL

Q72

TAYC

U,T

ATJU

,TAY

DU

RXY

Q72

,96,

120T

AYC

U

Pipe

rout

ing

hole

(bot

tom

)9 8 7 6 5 4 3 2 1

Pipe

rout

ing

hole

(fro

nt)

Pow

er c

ord

rout

ing

hole

Pow

er c

ord

rout

ing

hole

Pow

er c

ord

rout

ing

hole

Tran

smis

sion

wire

rout

ing

hole

Gro

undi

ng te

rmin

alIn

side

of c

ontro

l bo

x (M

8)

Gas

pip

e co

nnec

tion

port

Liqu

id p

ipe

conn

ectio

n po

rtN

o.Pa

rts n

ame

Ø7/

8 (2

2.2)

Rem

arks

See

note

1.

See

note

1.

Ø1-

3/8

(35)

Ø1-

1/8

(28.

6)Ø

7/8

(22.

2)

See

note

2.

See

note

2.

RXL

Q96

,120

TAYC

U,T

ATJU

,TAY

DU

RXY

Q14

4,16

8TAY

CU

Page 25: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

23

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ144 - 240TATJU / TAYDU / TAYCU

C: 3

D11

2577

A

Uni

t : in

. (m

m)

Not

es :

1. H

eigh

ts o

f wal

ls o

f thi

s ex

ampl

e;Fr

ont :

59

in. (

1500

mm

)Su

ctio

n si

de :

19-5

/8 in

. (50

0 m

m)

Side

: H

eigh

t unr

estri

cted

The

inst

alla

tion

spac

e sh

own

in th

is fi

gure

is b

ased

on

the

cond

ition

of c

oolin

g op

erat

ion

at th

e ou

tdoo

r air

tem

pera

ture

of 9

5°FD

B (3

5°C

DB)

.Th

e in

stal

latio

n sp

ace

of s

uctio

n si

de s

how

n ab

ove

mus

t be

expa

nded

in th

e fo

llow

ing

case

.∙

Des

ign

outd

oor t

empe

ratu

re b

ecom

es o

ver 9

5°FD

B (3

5°C

DB)

.∙

Ope

ratin

g ov

er m

ax. o

pera

ting

load

(In

case

of c

ausi

ng a

hea

vy h

eatin

g lo

ad a

t ind

oor u

nit s

ide)

2. If

the

abov

e w

all h

eigh

ts a

re e

xcee

ded

then

h2/

2 an

d h1

/2 s

houl

d be

add

ed to

the

front

and

suc

tion

side

ser

vice

sp

aces

resp

ectiv

ely

as s

how

n in

the

follo

win

g fig

ure.

3.

Whe

n in

stal

ling

the

units

the

mos

t app

ropr

iate

pat

tern

sho

uld

be s

elec

ted

from

"Ins

talla

tion

and

repa

ir sp

ace

draw

ing"

in o

rder

to o

btai

n th

e be

st fi

t in

the

spac

e av

aila

ble

alw

ays

bear

ing

in m

ind

the

need

to le

ave

enou

gh ro

om

for a

per

son

to p

ass

betw

een

units

and

wal

l and

for t

he a

ir to

circ

ulat

e fre

ely.

(If m

ore

units

are

to b

e in

stal

led

than

are

sho

wn

in "I

nsta

llatio

n an

d re

pair

spac

e dr

awin

g", y

our l

ayou

t sho

uld

take

ac

coun

t of t

he p

ossi

bilit

y of

sho

rt ci

rcui

ting.

)4.

The

uni

ts s

houl

d be

inst

alle

d to

leav

e su

ffici

ent s

pace

at t

he fr

ont f

or th

e on

site

refri

gera

nt p

ipin

g w

ork

to b

e ca

rried

ou

t com

forta

bly.

Page 26: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

24

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

9. Service Space

RXLQ72 - 240TATJU / TAYDU / TAYCU

C: 3

D08

5503

H

Uni

t : in

. (m

m)

Not

es:

1. H

eigh

ts o

f wal

ls in

cas

e of

Pat

tern

s 1

and

2;Fr

ont :

59

in. (

1500

mm

)Su

ctio

n si

de :

19-5

/8 in

. (50

0 m

m)

Side

: H

eigh

t unr

estri

cted

The

inst

alla

tion

spac

e sh

own

in th

is fi

gure

is b

ased

on

the

cond

ition

of c

oolin

g op

erat

ion

at th

e ou

tdoo

r air

tem

pera

ture

of 9

5°FD

B (3

5°C

DB)

. Th

e in

stal

latio

n sp

ace

of s

uctio

n si

de s

how

n ab

ove

mus

t be

expa

nded

in th

e fo

llow

ing

case

.∙D

esig

n ou

tdoo

r tem

pera

ture

bec

omes

ove

r 95°

FDB

(35°

CD

B).

∙ Ope

ratin

g ov

er m

ax. o

pera

ting

load

(In

case

of c

ausi

ng a

hea

vy h

eatin

g lo

ad a

t ind

oor u

nit s

ide)

2. If

the

abov

e w

all h

eigh

ts a

re e

xcee

ded

then

h2/

2 an

d h1

/2 s

houl

d be

add

ed to

the

front

and

suc

tion

side

ser

vice

spa

ces

resp

ectiv

ely

as s

how

n in

the

follo

win

g fig

ure.

3. W

hen

inst

allin

g th

e un

its th

e m

ost a

ppro

pria

te p

atte

rn s

houl

d be

sel

ecte

d fro

m "I

nsta

llatio

n an

d re

pair

spac

e dr

awin

g" in

ord

er to

obt

ain

the

best

fit i

n th

e sp

ace

avai

labl

e al

way

s be

arin

g in

min

d th

e ne

ed to

leav

e en

ough

room

for a

per

son

to p

ass

betw

een

units

and

wal

l and

for t

he a

ir to

circ

ulat

e fre

ely.

(If m

ore

units

are

to b

e in

stal

led

than

are

sho

wn

in "I

nsta

llatio

n an

d re

pair

spac

e dr

awin

g", y

our l

ayou

t sho

uld

take

acc

ount

of t

he p

ossi

bilit

y of

sho

rt ci

rcui

ting.

)4.

The

uni

ts s

houl

d be

inst

alle

d to

leav

e su

ffici

ent s

pace

at t

he fr

ont f

or th

e on

site

refri

gera

nt p

ipin

g w

ork

to b

e ca

rried

out

com

forta

bly.

Page 27: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

25

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ72 - 240TATJU / TAYDU / TAYCU

Not

es:

1. H

eigh

ts o

f wal

ls in

cas

e of

Pat

tern

s 1

and

2;Fr

ont :

59

in. (

1500

mm

)Su

ctio

n si

de :

19-5

/8 in

. (50

0 m

m)

Side

: H

eigh

t unr

estri

cted

The

inst

alla

tion

spac

e sh

own

in th

is fi

gure

is b

ased

on

the

cond

ition

of c

oolin

g op

erat

ion

at th

e ou

tdoo

r air

tem

pera

ture

of 9

5°FD

B (3

5°C

DB)

. Th

e in

stal

latio

n sp

ace

of s

uctio

n si

de s

how

n ab

ove

mus

t be

expa

nded

in th

e fo

llow

ing

case

.∙D

esig

n ou

tdoo

r tem

pera

ture

bec

omes

ove

r 95°

FDB

(35°

CD

B).

∙Ope

ratin

g ov

er m

ax. o

pera

ting

load

(In

case

of c

ausi

ng a

hea

vy h

eatin

g lo

ad a

t ind

oor u

nit s

ide)

2. If

the

abov

e w

all h

eigh

ts a

re e

xcee

ded

then

h2/

2 an

d h1

/2 s

houl

d be

add

ed to

the

front

and

suc

tion

side

ser

vice

spa

ces

resp

ectiv

ely

as s

how

n in

the

follo

win

g fig

ure.

3. W

hen

inst

allin

g th

e un

its th

e m

ost a

ppro

pria

te p

atte

rn s

houl

d be

sel

ecte

d fro

m "I

nsta

llatio

n an

d re

pair

spac

e dr

awin

g" in

ord

er to

obt

ain

the

best

fit i

n th

e sp

ace

avai

labl

e al

way

s be

arin

g in

min

d th

e ne

ed to

leav

e en

ough

room

for a

per

son

to p

ass

betw

een

units

and

wal

l and

for t

he a

ir to

circ

ulat

e fre

ely.

(If m

ore

units

are

to b

e in

stal

led

than

are

sho

wn

in "I

nsta

llatio

n an

d re

pair

spac

e dr

awin

g", y

our l

ayou

t sho

uld

take

acc

ount

of t

he p

ossi

bilit

y of

sho

rt ci

rcui

ting.

)4.

The

uni

ts s

houl

d be

inst

alle

d to

leav

e su

ffici

ent s

pace

at t

he fr

ont f

or th

e on

site

refri

gera

nt p

ipin

g w

ork

to b

e ca

rried

out

com

forta

bly.

C: 3

D08

5503

H

Uni

t : in

. (m

m)

Page 28: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

26

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

10. Center of Gravity

RXLQ72TATJU / TAYDU / TAYCU

4D107384

Page 29: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

27

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ96 - 120TATJU / TAYDU / TAYCU

4D107385

Page 30: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

28

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

11. Foundation Drawing

RXLQ72 - 240TATJU / TAYDU / TAYCU

C: 3

D08

5480

D

(Not

es)

1. T

he p

ropo

rtion

s of

cem

ent :

san

d : g

rave

l for

the

conc

rete

sha

ll be

1:2

:4, a

nd th

e re

info

rcem

ent

bars

that

thei

r dia

met

er a

re 3

/8 in

. (10

mm

), (a

ppro

x. 1

1-3/

4 in

. (30

0 m

m) i

nter

vals

) sha

ll be

pl

aced

.2.

The

sur

face

sha

ll be

fini

shed

with

mor

tar.

The

corn

er e

dges

sha

ll be

cha

mfe

red.

3. W

hen

the

foun

datio

n is

bui

lt on

a c

oncr

ete

floor

, rub

ble

is n

ot n

eces

sary

. How

ever

, the

sur

face

of

the

sect

ion

on w

hich

the

foun

datio

n is

bui

lt sh

all h

ave

roug

h fin

ish.

4. A

dra

in d

itch

shal

l be

mad

e ar

ound

the

foun

datio

n to

thor

ough

ly d

rain

wat

er fr

om th

e eq

uipm

ent

inst

alla

tion

area

.5.

Whe

n in

stal

ling

the

equi

pmen

t on

a ro

of, t

he fl

oor s

treng

th s

hall

be c

heck

ed, a

nd w

ater

-pro

ofin

g m

easu

res

shal

l be

take

n.

Page 31: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

29

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

12. Piping Diagrams

RXLQ72TATJU / TAYDU / TAYCU

C: 3

D11

2615

Liquid

pipe

Stop

valve

(With

serv

ice Ø

5/16

in. (

7.9

mm

) flar

e co

nnec

tion)

Filte

rCh

eck v

alve

Chec

k valv

e

Chec

k valv

e

Chec

k valv

e

Elec

tronic

expa

nsion

valve

Capil

lary

tube

Chec

kva

lveCh

eck

valve

Elec

tronic

expa

nsion

valve

Solen

oid va

lve

Pres

sure

regu

lating

valve

Filte

r

Filte

r

Filte

r

Elec

tronic

exp

ansio

n va

lve Capil

lary

tube

Chec

k valv

e

Elec

tronic

expa

nsion

valve

Plat

e he

atex

chan

ger

Fan

Filte

r

Filte

r

Gas

pipe

Four

way

valve

Doub

le tu

behe

at e

xcha

nger

Fusib

le plu

g

Accu

mula

tor

Filte

r

Solen

oidva

lve

Four

way

valve

Four

way

valve

Filte

rEl

ectro

nic e

xpan

sion

valve

Elec

tronic

exp

ansio

nva

lve

Heat

sink

Fusib

leplu

g

Rece

iver

Elec

tronic

expa

nsion

valve

Oil s

epar

ator

Char

ge p

ort

Heat

exc

hang

er

Capil

lary t

ube

Chec

k valv

e

Filte

r

Solen

oid va

lve

High

pre

ssur

esw

itch

Muf

fler

Com

pres

sor

Capil

lary t

ube

Capil

lary t

ube

Solen

oidva

lve

Filte

r

Filte

r

High

pre

ssur

ese

nsor

INV

SVSV

SV

SV

SENP

H

HPS

Fan M

M

Low

pres

sure

sens

orSE

NPL

Page 32: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

30

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ96 - 120TATJU / TAYDU / TAYCU

C: 3

D11

2616

Liquid

pipe

Stop

valve

(With

serv

ice Ø

5/16

in.(7

.9 m

m) f

lare

conn

ectio

n)

Filte

rCh

eck v

alve

Chec

k valv

e

Chec

k valv

e

Chec

k valv

e

Elec

tronic

expa

nsion

valve

Capil

lary

tube

Chec

kva

lveCh

eck

valve

Elec

tronic

expa

nsion

valve

Solen

oid va

lve

Pres

sure

regu

lating

valve

Filte

r

Filte

r

Filte

r

Elec

tronic

exp

ansio

n va

lve Capil

lary

tube

Chec

k valv

e

Elec

tronic

expa

nsion

valve

Plat

e he

atex

chan

ger

Fan

Filte

r

Filte

r

Gas

pipe

Four

way

valve

Low

pres

sure

sens

or

Doub

le tu

behe

at e

xcha

nger

Fusib

le plu

g

Accu

mula

tor

Filte

r

Solen

oidva

lve

Four

way

valve

Four

way

valve

Filte

rEl

ectro

nic e

xpan

sion

valve

Elec

tronic

exp

ansio

nva

lve

Heat

sink

Fusib

leplu

g

Rece

iver

Elec

tronic

expa

nsion

valve

Oil s

epar

ator

Char

ge p

ort

Heat

exc

hang

er

Capil

lary t

ube

Chec

k valv

e

Filte

rSolen

oid va

lve

High

pre

ssur

esw

itch

Muf

fler

Com

pres

sor

Capil

lary t

ube

Capil

lary t

ube

Solen

oidva

lve

Filte

r

Filte

r

High

pre

ssur

ese

nsor

INV

SVSV

SV

SV

SENP

H

HPS

Fan

MM

SENP

L

Page 33: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

31

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

13. Wiring Diagrams

RXLQ72TATJU

C: 2

D11

2580

A

1. T

HIS

WIR

ING

DIA

GR

AM A

PPLI

ES O

NLY

TO

TH

E O

UTD

OO

R U

NIT

. 2

.

: FIE

LD W

IRIN

G,

:

TER

MIN

AL B

LOC

K,

: CO

NN

ECTO

R,

: T

ERM

INAL

,

: PR

OTE

CTI

VE E

ARTH

(SC

REW

),

: N

OIS

ELES

S EA

RTH

. 3

. WH

EN U

SIN

G T

HE

OPT

ION

AL A

DAP

TOR

, REF

ER T

O T

HE

INST

ALLA

TIO

N M

ANU

AL O

F TH

E O

PTIO

NAL

AD

APTO

R.

4. F

OR

CO

NN

ECTI

ON

WIR

ING

TO

IND

OO

R-O

UTD

OO

R T

RAN

SMIS

SIO

N F

1 ∙F2

, OU

TDO

OR

-OU

TDO

OR

TR

ANSM

ISSI

ON

F1∙

F2

OU

TDO

OR

-MU

LTI T

RAN

SMIS

SIO

N Q

1∙Q

2, R

EFER

TO

TH

E IN

STAL

LATI

ON

MAN

UAL

. 5

. HO

W T

O U

SE B

S1~3

SW

ITC

H, R

EFER

TO

“SER

VIC

E PR

ECAU

TIO

N L

ABEL

ON

C

ON

TRO

L BO

X C

OVE

R.

6. W

HEN

OPE

RAT

ING

, DO

N'T

SH

OR

TCIR

CU

IT T

HE

PRO

TEC

TIO

N D

EVIC

E(S1

PH).

7. C

OLO

RS

BLK

: BLA

CK

; RED

: R

ED ;

BLU

: BL

UE

; WH

T : W

HIT

E ; G

RN

: G

REE

N ;

GR

Y : G

RAY

; YL

W :

YELL

OW

. 8

. CLA

SS 2

WIR

E

NO

TES)

Page 34: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

32

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ72TATJU

A1P PRINTED CIRCUIT BOARD (MAIN) R12T THERMISTOR (COMPSUCTION)A2P PRINTED CIRCUIT BOARD (NOISE FILTER) R13T THERMISTOR (RECEIVER GAS PURGE)A3P PRINTED CIRCUIT BOARD (INV) R14T THERMISTOR (M1C BODY)A4P, A5P PRINTED CIRCUIT BOARD (FAN) R15T THERMISTOR (LEAK DETECTION)A6P PRINTED CIRCUIT BOARD (SUB) R16T THERMISTOR (EVT)A7P PRINTED CIRCUIT BOARD (ABC I/P) R21T THERMISTOR (M1C DISCHARGE)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) R71T THERMISTOR (L1R)C1 CAPACITOR (A3P) R72T THERMISTOR (L2R)DS1, DS2 DIP SWITCH (A1P) S1NPH PRESSURE SENSOR (HIGH)E1HC, E2HC CRANKCASE HEATER S1NPL PRESSURE SENSOR (LOW)F1U FUSE (A1P, A6P) S1PH PRESSURE SWITCH (HIGH)F2U FUSE (A1P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)F101U FUSE (A4P, A5P) SHT1 CURRENT SENSOR (A3P)F4U, F5U FUSE (A2P) T1A CURRENT SENSORHAP PILOTLAMP (A1P, A3P~A6P) (SERVICE MONITOR-GREEN) V1D DIODE (A3P)K3R MAGNETIC RELAY (A3P) V1R POWER MODULE (A3P)K1M MAGNETIC CONTACTOR (A4P) V3R POWER MODULE (A4P, A5P)K3R MAGNETIC RELAY (Y1S) (A1P) X1A, X2A CONNECTOR (M1F)K4R MAGNETIC RELAY (Y2S) (A1P) X3A, X4A CONNECTOR (M2F)K6R MAGNETIC RELAY (OPTION) (A1P) X6A CONNECTOR (CHECK THE RESIDUAL CHARGE)K7R MAGNETIC RELAY (E1HC, E2HC) (A1P) X13A, X14A CONNECTOR (E1HC, E2HC)K8R MAGNETIC RELAY (Y7S) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K9R MAGNETIC RELAY (Y4S) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K11R MAGNETIC RELAY (Y3S) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A7P)K12R MAGNETIC RELAY (Y5S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K13R MAGNETIC RELAY (Y6S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K84R MAGNETIC RELAY (A3P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)L1R, L2R REACTOR Y4E ELECTRIC EXPANSION VALVE (INJECTION)M1C MOTOR (COMPRESSOR) Y5E ELECTRIC EXPANSION VALVE (REFRIGERAT COOLING)M1F, M2F MOTOR (FAN) Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)PS SWITCHING POWER SUPPLY (A1P, A3P, A6P) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y1S SOLENOID VALVE (OS OIL RETURN 1)Q1RP REVERSE PHASE PROTECTOR CIRCUIT (A1P) Y2S SOLENOID VALVE (HOT GAS BYPASS)R1 RESISTOR (CURRENT LIMITING) (A3P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R2 RESISTOR (CURRENT SENSOR) (A4P, A5P) Y4S 4WAY VALVE (HP/LP GAS)R1T THERMISTOR (AIR) Y5S 4WAY VALVE (HEAT EXC. LOWER)R3T THERMISTOR (RECEIVER INLET) Y6S 4WAY VALVE (HEAT EXC. UPPER)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R5T THERMISTOR (HEAT EXC. LIQUID LOWER) Z1C~Z6C NOISE FILTER (FERRITE CORE)R6T THERMISTOR (SUBCOOL GAS) ZF NOISE FILTER (A2P) (WITH SURGE ABSORBER)R7T THERMISTOR (SUBCOOL LIQUID) CONNECTOR FOR OPTIONAL ACCESSORIESR8T THERMISTOR (HEAT EXC. GAS UPPER) X37A CONNECTOR (POWER ADAPTER) (A1P)R9T THERMISTOR (HEAT EXC. GAS LOWER) COOL/HEAT SELECTORR10T THERMISTOR (SUCTION) S1S SELECTORSWITCH(FAN/COOL∙HEAT)R11T THERMISTOR (DEICER) S2S SELECTOR SWITCH (COOL/HEAT)

C: 2D112580A

Page 35: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

33

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ96 - 120TATJU

C: 2

D11

2581

A

NO

TES)

1. T

HIS

WIR

ING

DIA

GR

AM A

PPLI

ES O

NLY

TO

TH

E O

UTD

OO

R U

NIT

. 2

.

:

FIE

LD W

IRIN

G,

:

TER

MIN

AL B

LOC

K,

: CO

NN

ECTO

R,

: TE

RM

INAL

,

: PR

OTE

CTI

VE E

ARTH

(SC

REW

),

: N

OIS

ELES

S EA

RTH

. 3

. WH

EN U

SIN

G T

HE

OPT

ION

AL A

DAP

TOR

, REF

ER T

O T

HE

INST

ALLA

TIO

N M

ANU

AL O

F TH

E O

PTIO

NAL

AD

APTO

R.

4. F

OR

CO

NN

ECTI

ON

WIR

ING

TO

IND

OO

R-O

UTD

OO

R T

RAN

SMIS

SIO

N F

1 ∙F2

, OU

TDO

OR

-OU

TDO

OR

TR

ANSM

ISSI

ON

F1∙

F2

OU

TDO

OR

-MU

LTI T

RAN

SMIS

SIO

N Q

1∙Q

2, R

EFER

TO

TH

E IN

STAL

LATI

ON

MAN

UAL

. 5

. HO

W T

O U

SE B

S1~3

SW

ITC

H, R

EFER

TO

“SER

VIC

E PR

ECAU

TIO

N L

ABEL

ON

C

ON

TRO

L BO

X C

OVE

R.

6. W

HEN

OPE

RAT

ING

, DO

N'T

SH

OR

TCIR

CU

IT T

HE

PRO

TEC

TIO

N D

EVIC

E(S1

PH).

7. C

OLO

RS

BLK

: BLA

CK

; RED

: R

ED ;

BLU

: BL

UE

; WH

T : W

HIT

E ; G

RN

: G

REE

N ;

GR

Y : G

RAY

; YL

W :

YELL

OW

. 8

. CLA

SS 2

WIR

E

Page 36: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

34

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ96 - 120TATJU

A1P PRINTED CIRCUIT BOARD (MAIN) R12T THERMISTOR (COMPSUCTION)A2P PRINTED CIRCUIT BOARD (NOISE FILTER) R13T THERMISTOR (RECEIVER GAS PURGE)A3P PRINTED CIRCUIT BOARD (INV) R14T THERMISTOR (M1C BODY)A4P, A5P PRINTED CIRCUIT BOARD (FAN) R15T THERMISTOR (LEAK DETECTION)A6P PRINTED CIRCUIT BOARD (SUB) R16T THERMISTOR (EVT)A7P PRINTED CIRCUIT BOARD (ABC I/P) R21T THERMISTOR (M1C DISCHARGE)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) R71T THERMISTOR (POWER MODULE) (A3P)C1 CAPACITOR (A3P) R72T THERMISTOR (DIODE) (A3P)C2 CAPACITOR (A2P) S1NPH PRESSURE SENSOR (HIGH)DS1, DS2 DIP SWITCH (A1P) S1NPL PRESSURE SENSOR (LOW)E1HC, E2HC CRANKCASE HEATER S1PH PRESSURE SWITCH (HIGH)F1U FUSE (A1P, A2P, A6P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)F2U FUSE (A1P, A2P) T1A CURRENT SENSORF3U FUSE (A2P) T2A, T3A CURRENT SENSOR (A3P)F4U, F5U FUSE (X2M) V1D DIODE (A3P)F101U FUSE (A4P,A5P) V1R DIODE BRIDGEHAP PILOTLAMP (A1P, A3P~A6P) (SERVICE MONITOR-GREEN) V2R POWER MODULE (A3P)K1M MAGNETIC CONTACTOR (A4P) V3R POWER MODULE (A4P, A5P)K3R MAGNETIC RELAY (Y1S) (A1P) X1A, X2A CONNECTOR (M1F)K4R MAGNETIC RELAY (Y2S) (A1P) X3A, X4A CONNECTOR (M2F)K5R MAGNETIC RELAY (A3P) X13A, X14A CONNECTOR (E1HC, E2HC)K6R MAGNETIC RELAY (OPTION) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K7R MAGNETIC RELAY (E1HC, E2HC) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K8R MAGNETIC RELAY (Y7S) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A7P)K9R MAGNETIC RELAY (Y4S) (A1P) X2 TERMINAL BLOCK (FUSE)K11R MAGNETIC RELAY (Y3S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K12R MAGNETIC RELAY (Y5S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K13R MAGNETIC RELAY (Y6S) (A1P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)K84R MAGNETIC RELAY (A3P) Y4E ELECTRIC EXPANSION VALVE (INJECTION)L1R REACTOR Y5E ELECTRIC EXPANSION VALVE (REFRIGERAT COOLING)M1C MOTOR (COMPRESSOR) Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)M1F, M2F MOTOR (FAN) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)PS SWITCHING POWER SUPPLY (A1P, A3P, A6P) Y1S SOLENOID VALVE (OS OIL RETURN 1)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y2S SOLENOID VALVE (HOT GAS BYPASS)Q1RP REVERSE PHASE PROTECTOR CIRCUIT (A1P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R1 RESISTOR (CURRENT LIMITING) (A3P) Y4S 4WAY VALVE (HP/LP GAS)R2 RESISTOR (CURRENT SENSOR) (A4P, A5P) Y5S 4WAY VALVE (HEAT EXC. LOWER)R1T THERMISTOR (AIR) Y6S 4WAY VALVE (HEAT EXC. UPPER)R3T THERMISTOR (RECEIVER INLET) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) Z1C~Z8C NOISE FILTER (FERRITE CORE)R5T THERMISTOR (HEAT EXC. LIQUID LOWER) Z1F NOISE FILTERR6T THERMISTOR (SUBCOOL GAS) ZF NOISE FILTER (A2P) (WITH SURGE ABSORBER)R7T THERMISTOR (SUBCOOL LIQUID) CONNECTOR FOR OPTIONAL ACCESSORIESR8T THERMISTOR (HEAT EXC. GAS UPPER) X37A CONNECTOR (POWER ADAPTER) (A1P)R9T THERMISTOR (HEAT EXC. GAS LOWER) COOL/HEAT SELECTORR10T THERMISTOR (SUCTION) S1S SELECTOR SWITCH (FAN/COOL·HEAT)R11T THERMISTOR (DEICER) S2S SELECTOR SWITCH (COOL/HEAT)

C: 2D112581A

Page 37: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

35

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ72TAYDU

C: 2

D11

2582

A

NO

TES)

1. T

HIS

WIR

ING

DIA

GR

AM A

PPLI

ES O

NLY

TO

TH

E O

UTD

OO

R U

NIT

. 2

.

: FIE

LD W

IRIN

G,

: T

ERM

INAL

BLO

CK,

: C

ON

NEC

TOR

,

:

TER

MIN

AL,

:

PRO

TEC

TIVE

EAR

TH (S

CR

EW),

:

NO

ISEL

ESS

EAR

TH.

3. W

HEN

USI

NG

TH

E O

PTIO

NAL

AD

APTO

R, R

EFER

TO

TH

E IN

STAL

LATI

ON

MAN

UAL

OF

THE

OPT

ION

AL A

DAP

TOR

. 4

. FO

R C

ON

NEC

TIO

N W

IRIN

G T

O IN

DO

OR

-OU

TDO

OR

TR

ANSM

ISSI

ON

F1 ∙

F2, O

UTD

OO

R-O

UTD

OO

R T

RAN

SMIS

SIO

N F

1∙F2

O

UTD

OO

R-M

ULT

I TR

ANSM

ISSI

ON

Q1 ∙

Q2,

REF

ER T

O T

HE

INST

ALLA

TIO

N M

ANU

AL.

5. H

OW

TO

USE

BS1

~3 S

WIT

CH

, REF

ER T

O “S

ERVI

CE

PREC

AUTI

ON

LAB

EL O

N

CO

NTR

OL

BOX

CO

VER

. 6

. WH

EN O

PER

ATIN

G, D

ON

'T S

HO

RTC

IRC

UIT

TH

E PR

OTE

CTI

ON

DEV

ICE(

S1P

H).

7. C

OLO

RS

BLK

: BLA

CK

; RED

: R

ED ;

BLU

: BL

UE

; WH

T : W

HIT

E ; G

RN

: G

REE

N ;

GR

Y :

GR

AY ;

YLW

: YE

LLO

W.

8. C

LASS

2 W

IRE

Page 38: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

36

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ72TAYDU

A1P PRINTED CIRCUIT BOARD (MAIN) R10T THERMISTOR (SUCTION)A2P PRINTED CIRCUIT BOARD (NOISE FILTER) R11T THERMISTOR (DEICER)A3P PRINTED CIRCUIT BOARD (INV) R12T THERMISTOR (COMPSUCTION)A4P, A5P PRINTED CIRCUIT BOARD (FAN) R13T THERMISTOR (RECEIVER GAS PURGE)A6P PRINTED CIRCUIT BOARD (SUB) R14T THERMISTOR (M1C BODY)A7P PRINTED CIRCUIT BOARD (ABC I/P) R15T THERMISTOR (LEAK DETECTION)A8P PRINTED CIRCUIT BOARD (CURRENT LIMITING) R16T THERMISTOR (EVT)A9P PRINTED CIRCUIT BOARD (NOISE FILTER) R21T THERMISTOR (M1C DISCHARGE)A10P PRINTED CIRCUIT BOARD (OPEN PHASE PROTECTION) S1NPH PRESSURE SENSOR (HIGH)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) S1NPL PRESSURE SENSOR (LOW)C47, C48 CAPACITOR (A3P) S1PH PRESSURE SWITCH (HIGH)DS1, DS2 DIP SWITCH (A1P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)E1HC, E2HC CRANKCASE HEATER T1A CURRENT SENSORF1U FUSE (A1P, A6P) T1R TRANSFORMER (460 V/230 V)F2U FUSE (A1P) V1R DIODE BRIDGE (A3P)F101U FUSE (A4P, A5P) V1R POWER MODULE (A4P, A5P)F401U, F403U FUSE (A2P) V2R POWER MODULE (A3P)F601U FUSE (A3P) X1A, X2A CONNECTOR (M1F)HAP PILOTLAMP (A1P, A3P~A6P) (SERVICE MONITOR-GREEN) X3A, X4A CONNECTOR (M2F)K1M MAGNETIC CONTACTOR (A3P) X5A CONNECTOR (CHECK THE RESIDUAL CHARGE)K1M MAGNETIC CONTACTOR (A8P) X7A, X8A CONNECTOR (T1R)K3R MAGNETIC RELAY (A3P) X9A, X11A CONNECTORK3R MAGNETIC RELAY (Y1S) (A1P) X13A, X14A CONNECTOR (E1HC, E2HC)K4R MAGNETIC RELAY (Y2S) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K6R MAGNETIC RELAY (OPTION) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K7R MAGNETIC RELAY (E1HC, E2HC) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A7P)K8R MAGNETIC RELAY (Y7S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K9R MAGNETIC RELAY (Y4S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K11R MAGNETIC RELAY (Y3S) (A1P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)K12R MAGNETIC RELAY (Y5S) (A1P) Y4E ELECTRIC EXPANSION VALVE (INJECTION)K13R MAGNETIC RELAY (Y6S) (A1P) Y5E ELECTRIC EXPANSION VALVE (REFRIGERAT COOLING)L1R REACTOR Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)M1C MOTOR (COMPRESSOR) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)M1F, M2F MOTOR (FAN) Y1S SOLENOID VALVE (OS OIL RETURN 1)PS SWITCHING POWER SUPPLY (A1P, A3P, A6P) Y2S SOLENOID VALVE (HOT GAS BYPASS)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R1 RESISTOR (CURRENT LIMITING) (A8P) Y4S 4WAY VALVE (HP/LP GAS)R24 RESISTOR (CURRENT SENSOR) (A4P, A5P) Y5S 4WAY VALVE (HEAT EXC. LOWER)R313 RESISTOR (CURRENT SENSOR) (A3P) Y6S 4WAY VALVE (HEAT EXC. UPPER)R865, R867 RESISTOR (A3P) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R1T THERMISTOR (AIR) Z1C, Z2C NOISE FILTER (FERRITE CORE)R3T THERMISTOR (RECEIVER INLET) ZF NOISE FILTER (A2P, A9P) (WITH SURGE ABSORBER)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) CONNECTOR FOR OPTIONAL ACCESSORIESR5T THERMISTOR (HEAT EXC. LIQUID LOWER) X37A CONNECTOR (POWER ADAPTER) (A1P)R6T THERMISTOR (SUBCOOL GAS) COOL/HEAT SELECTORR7T THERMISTOR (SUBCOOL LIQUID) S1S SELECTOR SWITCH (FAN/COOL·HEAT)R8T THERMISTOR (HEAT EXC. GAS UPPER) S2S SELECTOR SWITCH (COOL/HEAT)R9T THERMISTOR (HEAT EXC. GAS LOWER)

C: 2D112582A

Page 39: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

37

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ96 - 120TAYDU

C: 2

D11

2583

A

NO

TES)

1. T

HIS

WIR

ING

DIA

GR

AM A

PPLI

ES O

NLY

TO

TH

E O

UTD

OO

R U

NIT

. 2

.

: FIE

LD W

IRIN

G,

: T

ERM

INAL

BLO

CK,

: C

ON

NEC

TOR

,

:

TER

MIN

AL,

:

PRO

TEC

TIVE

EAR

TH (S

CR

EW),

:

NO

ISEL

ESS

EAR

TH.

3. W

HEN

USI

NG

TH

E O

PTIO

NAL

AD

APTO

R, R

EFER

TO

TH

E IN

STAL

LATI

ON

MAN

UAL

OF

THE

OPT

ION

AL A

DAP

TOR

. 4

. FO

R C

ON

NEC

TIO

N W

IRIN

G T

O IN

DO

OR

-OU

TDO

OR

TR

ANSM

ISSI

ON

F1 ∙

F2, O

UTD

OO

R-O

UTD

OO

R T

RAN

SMIS

SIO

N F

1∙F2

O

UTD

OO

R-M

ULT

I TR

ANSM

ISSI

ON

Q1∙

Q2,

REF

ER T

O T

HE

INST

ALLA

TIO

N M

ANU

AL.

5. H

OW

TO

USE

BS1

~3 S

WIT

CH

, REF

ER T

O “S

ERVI

CE

PREC

AUTI

ON

LAB

EL O

N

CO

NTR

OL

BOX

CO

VER

. 6

. WH

EN O

PER

ATIN

G, D

ON

'T S

HO

RTC

IRC

UIT

TH

E PR

OTE

CTI

ON

DEV

ICE(

S1PH

). 7

. CO

LOR

S BL

K : B

LAC

K ; R

ED :

RED

; BL

U :

BLU

E ; W

HT

: WH

ITE

; GR

N :

GR

EEN

; G

RY

: GR

AY ;

YLW

: YE

LLO

W.

8. C

LASS

2 W

IRE

Page 40: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

38

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ96 - 120TAYDU

A1P PRINTED CIRCUIT BOARD (MAIN) R12T THERMISTOR (COMPSUCTION)A2P PRINTED CIRCUIT BOARD (NOISE FILTER) R13T THERMISTOR (RECEIVER GAS PURGE)A3P PRINTED CIRCUIT BOARD (INV) R14T THERMISTOR (M1C BODY)A4P, A5P PRINTED CIRCUIT BOARD (FAN) R15T THERMISTOR (LEAK DETECTION)A6P PRINTED CIRCUIT BOARD (SUB) R16T THERMISTOR (EVT)A7P PRINTED CIRCUIT BOARD (ABC I/P) R21T THERMISTOR (M1C DISCHARGE)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) R71T THERMISTOR (POWER MODULE) (A3P)C48, C51 CAPACITOR (A3P) R72T THERMISTOR (DIODE) (A3P)C404 CAPACITOR (A2P) S1NPH PRESSURE SENSOR (HIGH)DS1, DS2 DIP SWITCH (A1P) S1NPL PRESSURE SENSOR (LOW)E1HC, E2HC CRANKCASE HEATER S1PH PRESSURE SWITCH (HIGH)F1U FUSE (A1P, A3P, A6P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)F2U FUSE (A1P) T1A CURRENT SENSORF101U FUSE (A4P, A5P) T1R TRANSFORMER (460 V/230 V)F404U FUSE (A2P) V1D DIODE (CURRENT LIMITING) (A3P)F410U, F412U FUSE (A2P) V1R DIODE BRIDGEHAP PILOTLAMP (A1P, A3P~A6P) (SERVICE MONITOR-GREEN) V1R POWER MODULE (A4P, A5P)K1M MAGNETIC CONTACTOR V2R POWER MODULE (A3P)K3R MAGNETIC RELAY (A3P) X1A, X2A CONNECTOR (M1F)K3R MAGNETIC RELAY (Y1S) (A1P) X3A, X4A CONNECTOR (M2F)K4R MAGNETIC RELAY (Y2S) (A1P) X5A CONNECTOR (CHECK THE RESIDUAL CHARGE)K6R MAGNETIC RELAY (OPTION) (A1P) X6A, X7A CONNECTOR (T1R)K7R MAGNETIC RELAY (E1HC, E2HC) (A1P) X13A, X14A CONNECTOR (E1HC, E2HC)K8R MAGNETIC RELAY (Y7S) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K9R MAGNETIC RELAY (Y4S) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K11R MAGNETIC RELAY (Y3S) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A7P)K12R MAGNETIC RELAY (Y5S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K13R MAGNETIC RELAY (Y6S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K84R MAGNETIC RELAY (A3P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)L1R REACTOR Y4E ELECTRIC EXPANSION VALVE (INJECTION)M1C MOTOR (COMPRESSOR) Y5E ELECTRIC EXPANSION VALVE (REFRIGERAT COOLING)M1F, M2F MOTOR (FAN) Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)PS SWITCHING POWER SUPPLY (A1P, A3P, A6P) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y1S SOLENOID VALVE (OS OIL RETURN 1)R1 RESISTOR (CURRENT LIMITING) (A3P) Y2S SOLENOID VALVE (HOT GAS BYPASS)R24 RESISTOR (CURRENT SENSOR) (A4P, A5P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R131, R133 RESISTOR (A3P) Y4S 4WAY VALVE (HP/LP GAS)R401 RESISTOR (CURRENT SENSOR) (A3P) Y5S 4WAY VALVE (HEAT EXC. LOWER)R1T THERMISTOR (AIR) Y6S 4WAY VALVE (HEAT EXC. UPPER)R3T THERMISTOR (RECEIVER INLET) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) Z1C~Z3C NOISE FILTER (FERRITE CORE)R5T THERMISTOR (HEAT EXC. LIQUID LOWER) ZF NOISE FILTER (A2P) (WITH SURGE ABSORBER)R6T THERMISTOR (SUBCOOL GAS) CONNECTOR FOR OPTIONAL ACCESSORIESR7T THERMISTOR (SUBCOOL LIQUID) X37A CONNECTOR (POWER ADAPTER) (A1P)R8T THERMISTOR (HEAT EXC. GAS UPPER) COOL/HEAT SELECTORR9T THERMISTOR (HEAT EXC. GAS LOWER) S1S SELECTOR SWITCH (FAN/COOL·HEAT)R10T THERMISTOR (SUCTION) S2S SELECTOR SWITCH (COOL/HEAT)R11T THERMISTOR (DEICER)

C: 2D112583A

Page 41: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

39

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ72 - 120TAYCU

C: 2

D11

2579

A

NO

TES)

1. T

HIS

WIR

ING

DIA

GR

AM A

PPLI

ES O

NLY

TO

TH

E O

UTD

OO

R U

NIT

. 2

.

: FIE

LD W

IRIN

G,

: T

ERM

INAL

BLO

CK,

: C

ON

NEC

TOR

,

:

TER

MIN

AL,

:

PRO

TEC

TIVE

EAR

TH (S

CR

EW),

:

NO

ISEL

ESS

EAR

TH.

3. W

HEN

USI

NG

TH

E O

PTIO

NAL

AD

APTO

R, R

EFER

TO

TH

E IN

STAL

LATI

ON

MAN

UAL

OF

THE

OPT

ION

AL A

DAP

TOR

. 4

. FO

R C

ON

NEC

TIO

N W

IRIN

G T

O IN

DO

OR

-OU

TDO

OR

TR

ANSM

ISSI

ON

F1 ∙

F2, O

UTD

OO

R-O

UTD

OO

R T

RAN

SMIS

SIO

N F

1∙F2

O

UTD

OO

R-M

ULT

I TR

ANSM

ISSI

ON

Q1 ∙

Q2,

REF

ER T

O T

HE

INST

ALLA

TIO

N M

ANU

AL.

5. H

OW

TO

USE

BS1

~3 S

WIT

CH

, REF

ER T

O “S

ERVI

CE

PREC

AUTI

ON

LAB

EL O

N

CO

NTR

OL

BOX

CO

VER

. 6

. WH

EN O

PER

ATIN

G, D

ON

'T S

HO

RTC

IRC

UIT

TH

E PR

OTE

CTI

ON

DEV

ICE(

S1PH

). 7

. CO

LOR

S BL

K : B

LAC

K ; R

ED :

RED

; BL

U :

BLU

E ; W

HT

: WH

ITE

; GR

N :

GR

EEN

; G

RY

: GR

AY ;

YLW

: YE

LLO

W.

8. C

LASS

2 W

IRE

Page 42: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

40

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ72 - 120TAYCU

A1P PRINTED CIRCUIT BOARD (MAIN) R13T THERMISTOR (RECEIVER GAS PURGE)A2P, A3P PRINTED CIRCUIT BOARD (NOISE FILTER) R14T THERMISTOR (M1C BODY)A4P PRINTED CIRCUIT BOARD (INV) R15T THERMISTOR (LEAK DETECTION)A5P, A6P PRINTED CIRCUIT BOARD (FAN) R16T THERMISTOR (EVT)A7P PRINTED CIRCUIT BOARD (SUB) R21T THERMISTOR (M1C DISCHARGE)A8P PRINTED CIRCUIT BOARD (ABC I/P) S1NPH PRESSURE SENSOR (HIGH)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) S1NPL PRESSURE SENSOR (LOW)C1 CAPACITOR (A4P) S1PH PRESSURE SWITCH (HIGH)DS1, DS2 DIP SWITCH (A1P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)E1HC, E2HC CRANKCASE HEATER T1A CURRENT SENSORF1U FUSE (A1P, A4P, A7P) T1R TRANSFORMER (575 V/220 V)F2U FUSE (A1P) V1D DIODE (A4P)F101U FUSE (A2P, A5P, A6P) V1R POWER MODULE (A4P)F100U, F104U, F105U FUSE (A2P) V1R POWER MODULE (A5P, A6P)F1UT THERMAL FUSE (A4P) V1T TRANSISTOR (A4P)HAP PILOTLAMP (A1P, A4P~A7P) (SERVICE MONITOR-GREEN) X1A, X2A CONNECTOR (M1F, M2F)K1M MAGNETIC CONTACTOR (A4P) X5A CONNECTOR (CHECK THE RESIDUAL CHARGE)K3R MAGNETIC RELAY (Y1S) (A1P) X3A, X4A CONNECTOR (T1R)K4R MAGNETIC RELAY (Y2S) (A1P) X13A, X14A CONNECTOR (E1HC, E2HC)K6R MAGNETIC RELAY (OPTION) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K7R MAGNETIC RELAY (E1HC,E2HC) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K8R MAGNETIC RELAY (Y7S) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A8P)K9R MAGNETIC RELAY (Y4S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K11R MAGNETIC RELAY (Y3S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K12R MAGNETIC RELAY (Y5S) (A1P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)K13R MAGNETIC RELAY (Y6S) (A1P) Y4E ELECTRIC EXPANSION VALVE (INJECTION)L1R REACTOR Y5E ELECTRIC EXPANSION VALVE (REFRIGERAT COOLING)M1C MOTOR (COMPRESSOR) Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)M1F, M2F MOTOR (FAN) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)PS SWITCHING POWER SUPPLY (A1P, A4P, A7P) Y1S SOLENOID VALVE (OS OIL RETURN 1)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y2S SOLENOID VALVE (HOT GAS BYPASS)R1 RESISTOR (CURRENT LIMITING) (A4P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R2 RESISTOR (CURRENT SENSOR) (A4P, A5P, A6P) Y4S 4WAY VALVE (HP/LP GAS)R1T THERMISTOR (AIR) Y5S 4WAY VALVE (HEAT EXC. LOWER)R3T THERMISTOR (RECEIVER INLET) Y6S 4WAY VALVE (HEAT EXC. UPPER)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R5T THERMISTOR (HEAT EXC. LIQUID LOWER) Z1C~Z3C NOISE FILTER (FERRITE CORE)R6T THERMISTOR (SUBCOOL GAS) ZF NOISE FILTER (A2P, A3P) (WITH SURGE ABSORBER)R7T THERMISTOR (SUBCOOL LIQUID) CONNECTOR FOR OPTIONAL ACCESSORIESR8T THERMISTOR (HEAT EXC. GAS UPPER) X37A CONNECTOR (POWER ADAPTER) (A1P)R9T THERMISTOR (HEAT EXC. GAS LOWER) COOL/HEAT SELECTORR10T THERMISTOR (SUCTION) S1S SELECTOR SWITCH (FAN/COOL·HEAT)R11T THERMISTOR (DEICER) S2S SELECTOR SWITCH (COOL/HEAT)R12T THERMISTOR (COMPSUCTION)

C: 2D112579A

Page 43: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

41

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

14. Field Wiring

RXLQ72 - 120TATJU / TAYDU / TAYCU

C: 3

D08

7054

C

Not

es 1

) All

wiri

ng, c

ompo

nent

s an

d m

ater

ials

to b

e pr

ocur

edon

the

site

mus

t com

ply

with

the

appl

icab

le lo

cal a

nd n

atio

nal c

odes

.2)

Use

cop

per c

ondu

ctor

s on

ly.

3) A

s fo

r det

ails

, see

wiri

ng d

iagr

am.

4) F

ield

wiri

ng d

iagr

am is

to b

e us

ed a

s a

guid

elin

e on

ly.

Wiri

ng s

houl

d co

mpl

y w

ith a

pplic

able

loca

l and

nat

iona

l cod

es.

5) U

nit s

hall

be g

roun

ded

in c

ompl

ianc

e w

ith th

e ap

plic

able

loca

l and

nat

iona

l cod

es.

6) W

iring

sho

wn

are

gene

ral p

oint

s-of

-con

nect

ion

guid

es o

nly

and

are

not i

nten

ded

for o

r to

incl

ude

all d

etai

ls fo

r a s

peci

fic in

stal

latio

n.7)

Be

sure

to in

stal

l the

sw

itch

and

the

fuse

/bre

aker

to th

e po

wer

line

of e

ach

piec

e of

equ

ipm

ent.

8) In

stal

l the

mai

n sw

itch

that

can

inte

rrupt

all

the

pow

er s

ourc

es in

an

inte

grat

ed

man

ner b

ecau

se th

is s

yste

m c

onsi

sts

of th

e eq

uipm

ent u

tiliz

ing

the

mul

tiple

po

wer

sou

rces

.9)

If th

ere

exis

ts th

e po

ssib

ility

of re

vers

ed p

hase

, los

t pha

se, m

omen

tary

bla

ckou

t or

the

pow

er g

oes

on a

nd o

ff w

hile

the

prod

uct i

s op

erat

ing,

atta

ch a

reve

rsed

ph

ase

prot

ectio

n ci

rcui

t loc

ally

.R

unni

ng th

e pr

oduc

t in

reve

rsed

pha

se m

ay b

reak

the

com

pres

sor a

nd o

ther

pa

rts.

Page 44: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

42

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ144 - 240TATJU / TAYDU / TAYCU

C: 3

D08

7055

C

Not

es 1

) All

wiri

ng, c

ompo

nent

s an

d m

ater

ials

to b

e pr

ocur

edon

the

site

mus

t com

ply

with

the

appl

icab

le lo

cal a

nd n

atio

nal c

odes

.2)

Use

cop

per c

ondu

ctor

s on

ly.

3) A

s fo

r det

ails

, see

wiri

ng d

iagr

am.

4) F

ield

wiri

ng d

iagr

am is

to b

e us

ed a

s a

guid

elin

e on

ly.

Wiri

ng s

houl

d co

mpl

y w

ith a

pplic

able

loca

l and

nat

iona

l cod

es.

5) U

nit s

hall

be g

roun

ded

in c

ompl

ianc

e w

ith th

e ap

plic

able

loca

l and

nat

iona

l cod

es.

6) W

iring

sho

wn

are

gene

ral p

oint

s-of

-con

nect

ion

guid

es o

nly

and

are

not i

nten

ded

for o

rto

incl

ude

all d

etai

ls fo

r a s

peci

fic in

stal

latio

n.7)

Be

sure

to in

stal

l the

sw

itch

and

the

fuse

/bre

aker

to th

e po

wer

line

of e

ach

piec

e of

equi

pmen

t.8)

Inst

all t

he m

ain

switc

h th

at c

an in

terru

pt a

ll th

e po

wer

sou

rces

in a

n in

tegr

ated

man

ner

beca

use

this

sys

tem

con

sist

s of

the

equi

pmen

t util

izin

g th

e m

ultip

le p

ower

sou

rces

.9)

If th

ere

exis

ts th

e po

ssib

ility

of re

vers

ed p

hase

, los

t pha

se, m

omen

tary

bla

ckou

t or t

hepo

wer

goe

s on

and

off

whi

le th

e pr

oduc

t is

oper

atin

g, a

ttach

a re

vers

ed p

hase

pro

tect

ion

circ

uit l

ocal

ly.

Run

ning

the

prod

uct i

n re

vers

ed p

hase

may

bre

ak th

e co

mpr

esso

r and

oth

er p

arts

.

Page 45: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

43

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

15. Electrical Characteristics

RXLQ72 - 240TATJU

Model nameUnits Power supply Comp. OFM

SCCRHz Volts Min. Max. MCA MOP RLA kW FLA

RXLQ72TATJU 60 208/230 187 253 60.8 70 23.9 0.80 × 2 2.9 × 2 5 kA rms symmetrical,

230 V maximum

RXLQ96TATJU 60 208/230 187 253 76.5 80 42.2 0.80 × 2 2.9 × 2RXLQ120TATJU 60 208/230 187 253 83.4 90 41.4 0.80 × 2 2.9 × 2

RXLQ144TATJURXLQ72TATJU

60 208/230 187 253 60.8 + 60.8 70 + 70 23.9 + 23.9 (0.80 × 2) × 2 (2.9 × 2) × 2

RXLQ72TATJU

RXLQ192TATJURXLQ96TATJU

60 208/230 187 253 76.5 + 76.5 80 + 80 40.8 + 40.8 (0.80 × 2) × 2 (2.9 × 2) × 2RXLQ96TATJU

RXLQ240TATJURXLQ120TATJU

60 208/230 187 253 83.4 + 83.4 90 + 90 41.7 + 41.7 (0.80 × 2) × 2 (2.9 × 2) × 2RXLQ120TATJU

Symbols:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protector (A)RLA: Rated Load Amps. (A)OFM: Outdoor Fan MotorkW: Rated Motor Output (kW)FLA: Full Load Amps. (A)SCCR: Short-Circuit Current Rating

Notes:1. RLA is based on the following conditions. Indoortemp.80°FDB(26.7°CDB)/67°FWB(19.4°CWB) Outdoortemp.95°FDB(35.0°CDB)

2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.

3. The maximum percent unbalance of phase voltage shall be 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.

C: 4D112605A, 4D112608A

Page 46: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

44

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ72 - 240TAYDU

Model nameUnits Power supply Comp. OFM

Hz Volts Min. Max. MCA MOP RLA kW FLARXLQ72TAYDU 60 460 416 508 28.1 35 10.4 0.6 × 2 1.0 × 2RXLQ96TAYDU 60 460 416 508 39.8 45 18.3 0.6 × 2 1.0 × 2

RXLQ120TAYDU 60 460 416 508 43.4 50 18.0 0.6 × 2 1.0 × 2

RXLQ144TAYDURXLQ72TAYDU

60 460 416 508 28.1 + 28.1 35 + 35 10.4 + 10.4 (0.6 × 2) × 2 (1.0 × 2) × 2RXLQ72TAYDU

RXLQ192TAYDURXLQ96TAYDU

60 460 416 508 39.8 + 39.8 45 + 45 17.7 + 17.7 (0.6 × 2) × 2 (1.0 × 2) × 2RXLQ96TAYDU

RXLQ240TAYDURXLQ120TAYDU

60 460 416 508 43.4 + 43.4 50 + 50 18.2 + 18.2 (0.6 × 2) × 2 (1.0 × 2) × 2RXLQ120TAYDU

Symbols:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protector (A)RLA: Rated Load Amps. (A)OFM: Outdoor Fan MotorkW: Rated Motor Output (kW)FLA: Full Load Amps. (A)

Notes:1. RLA is based on the following conditions. Indoortemp.80°FDB(26.7°CDB)/67°FWB(19.4°CWB) Outdoortemp.95°FDB(35.0°CDB)

2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.

3. The maximum percent unbalance of phase voltage shall be 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.

C: 4D112606A, 4D112609A

Page 47: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

45

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ72 - 240TAYCU

Model nameUnits Power supply Comp. OFM

Hz Volts Min. Max. MCA MOP RLA kW FLARXLQ72TAYCU 60 575 518 632 21.6 25 8.3 0.7 × 2 1.0 × 2RXLQ96TAYCU 60 575 518 632 28.5 35 14.7 0.7 × 2 1.0 × 2

RXLQ120TAYCU 60 575 518 632 31.2 40 14.4 0.7 × 2 1.0 × 2

RXLQ144TAYCURXLQ72TAYCU

60 575 518 632 21.6 + 21.6 25 + 25 8.3 + 8.3 (0.7 × 2) × 2 (1.0 × 2) × 2RXLQ72TAYCU

RXLQ192TAYCURXLQ96TAYCU

60 575 518 632 28.5 + 28.5 35 + 35 14.2 + 14.2 (0.7 × 2) × 2 (1.0 × 2) × 2RXLQ96TAYCU

RXLQ240TAYCURXLQ120TAYCU

60 575 518 632 31.2 + 31.2 40 + 40 14.5 + 14.5 (0.7 × 2) × 2 (1.0 × 2) × 2RXLQ120TAYCU

Symbols:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protector (A)RLA: Rated Load Amps. (A)OFM: Outdoor Fan MotorkW: Rated Motor Output (kW)FLA: Full Load Amps. (A)

Notes:1. RLA is based on the following conditions. Indoortemp.80°FDB(26.7°CDB)/67°FWB(19.4°CWB) Outdoortemp.95°FDB(35.0°CDB)

2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.

3. The maximum percent unbalance of phase voltage shall be 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.

C: 4D112604A, 4D112607A

Page 48: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

46

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

16. Operation Limits

RXLQ72 - 240TATJU / TAYDU / TAYCU

3D107374

Page 49: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

47

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

17. Sound Levels (Reference Data)

RXLQ72TATJU / TAYDU / TAYCU

4D107376A

Page 50: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

48

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ96TATJU / TAYDU / TAYCU

4D107377A

Page 51: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

49

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

RXLQ120TATJU / TAYDU / TAYCU

4D107378A

Page 52: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

50

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

18. Accessories18.1 Optional AccessoriesRXLQ72 - 240TATJU / TAYDU / TAYCU

Optional accessories

RXLQ72TATJURXLQ96TATJURXLQ72TAYDURXLQ96TAYDURXLQ72TAYCURXLQ96TAYCU

RXLQ120TATJURXLQ120TAYDURXLQ120TAYCU

RXLQ144TATJURXLQ192TATJURXLQ240TATJURXLQ144TAYDURXLQ192TAYDURXLQ240TAYDURXLQ144TAYCURXLQ192TAYCURXLQ240TAYCU

Distributive piping

REFNET header KHRP26M22H9 (Max. 4 branch)KHRP26M33H9 (Max. 8 branch)

KHRP26M22H9 (Max. 4 branch)KHRP26M33H9 (Max. 8 branch)KHRP26M72H9 (Max. 8 branch)

KHRP26M22H9 (Max. 4 branch)KHRP26M33H9 (Max. 8 branch)KHRP26M72H9 (Max. 8 branch)

KHRP26M73HU9 (Max. 8 branch)

REFNET joint KHRP26A22T9KHRP26A33T9

KHRP26A22T9KHRP26A33T9

KHRP26M72TU9

KHRP26A22T9KHRP26A33T9

KHRP26M72TU9KHRP26M73TU9

Outdoor unit multi connection piping kit – BHFP22P100U

C: 3D087057D

Page 53: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

51

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

19. Selection Procedure19.1 Selection Procedure19.1.1 Flowchart

Provisionally select outdoor unit type and size based on limitation of connection ratio

Correct for cooling & heating capacity of the outdoor unit by the following items

VRV system selection is complete.

Confirm that the number of indoor units connected to the outdoor unit is within limitation.

Corrected capacity of the outdoor unit ≥ Required total heat load to the outdoor unit

2) Use the system peak load1) Use the sum of the peak load of each room

Define required total heat load to outdoor unit

Indoor unit capacity corrected for indoor air temperature (WB) ≥ Required heat load × Safety factor for the indoor units

Yes

No

-Piping length, level difference-Piping heat loss-Safety factor for the outdoor unit-Defrost (only for heating capacity)

-Outdoor air temperature-Indoor air temperature-Connection ratio

Given Conditions:· Design temperature and humidity (indoor & outdoor)· Required heat load of each room· System peak load (if necessary)· Piping length, level difference· Specifications of indoor units (type and number)

Define safety factor for the indoor units and outdoor unit

[1] Given conditions

[2] Selection of indoor units

[3] Selection of outdoor unit

Page 54: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

52

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

19.1.2 Selection ExampleThe following is a selection example based on total heat load for cooling.

Room ARoom H Room G

Room F

Room B Room ERoom C Room D

Floor plan

[1] Given conditions-Design conditionsIndoorairtemperature:67°FWB/80°FDB,Outdoorairtemperature:93°FDB

-Determine peak load of each room (and system peak load if necessary)

-Required heat load of each roomTime Room A Room B Room C Room D Room E Room F Room G Room H Total9:00 16.4 16.5 10.4 10.4 30.9 30.8 10.0 10.0 135.4

12:00 22.4 24.4 17.3 17.3 25.1 23.2 13.7 13.7 157.114:00 30.7 32.2 16.8 16.8 24.9 23.4 14.1 14.1 173.016:00 36.1 36.4 13.3 13.3 21.5 21.2 13.0 13.0 167.8

Total heat load (MBH)

From the above heat load calculation, the maximum heat load for the system (system peak load) is 173.0 MBH.

Level difference120 ft.

Select VRV indoor units FXMQ-PB series for each room.

Equivalent pipe length 200 ft.

-Safety factorIn this example, safety factor is not used. (i. e., safety factor = 1.0)

[2] Selection of indoor unitsCalculate total heat capacity of indoor units corrected for indoor air temperature.In case design temperature of the indoor air falls between temperatures listed in the table, calculate the capacity by interpolation.The corrected total heat capacity of indoor units shall satisfy the maximum heat load of each room.

Page 55: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

53

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

Capacity table of indoor unitCooling Capacity

Model Capacity indication

Indoorairtemp.°FWB(Te:43°F(6°C))61 64 67 70 72 75

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH

FXMQ07PBVJU 07 5.7 5.5 6.4 5.9 7.2 6.1 7.3 6.5 7.4 5.8 7.6 5.8 FXMQ09PBVJU 09 7.5 6.9 8.5 7.3 9.5 7.8 9.7 8.1 9.8 7.1 10.0 7.2FXMQ12PBVJU 12 9.5 8.5 10.7 9.1 12.0 9.7 12.2 10.0 12.4 9.2 12.6 9.2FXMQ15PBVJU 15 11.2 10.2 12.7 10.7 14.2 11.4 14.5 11.6 14.7 11.5 14.9 9.6 FXMQ18PBVJU 18 14.2 13.9 16.1 14.7 18.0 15.6 18.4 16.1 18.6 14.6 18.9 12.1FXMQ24PBVJU 24 19.0 16.5 21.5 17.7 24.0 18.8 24.5 19.2 24.8 17.9 25.3 20.1FXMQ30PBVJU 30 23.7 20.8 26.8 22.3 30.0 23.8 30.6 24.4 31.0 22.5 31.6 22.5FXMQ36PBVJU 36 28.4 25.0 32.2 26.9 36.0 28.8 36.7 30.0 37.2 27.7 37.9 27.7FXMQ48PBVJU 48 37.9 31.3 43.0 33.6 48.0 35.8 49.0 36.9 49.6 34.7 50.5 33.2FXMQ54PBVJU 54 42.6 35.2 48.3 37.8 54.0 40.3 55.1 41.5 55.8 39.0 56.8 37.4

TC : Total capacity: MBHSHC : Sensible heat capacity: MBH

Selection results of indoor units

Room A Room B Room C Room D Room E Room F Room G Room HMax. heat load (MBH) 36.1 36.4 17.3 17.3 30.9 30.8 14.1 14.1

Selected IDU FXMQ48PBVJU FXMQ48PBVJU FXMQ18PBVJU FXMQ18PBVJU FXMQ36PBVJU FXMQ36PBVJU FXMQ15PBVJU FXMQ15PBVJUCorrected TC (MBH) 48.0 48.0 18.0 18.0 36.0 36.0 14.2 14.2

∗In case of selection based on Total Heat Load and Sensible Heat Load, select indoor units which satisfy not only the Total Heat Load but also the Sensible Heat Load of each room. The sensible heat capacity of indoor units is to be corrected for indoor air temperature. If the design temperature of indoor air falls between temperatures listed in table, calculate sensible heat capacity by using the bypass factor calculated by interpolation for each indoor air temperature.

[3] Selection of outdoor unit[3] –1 Define the required total heat load from the indoor units to the outdoor unitDefinetherequiredtotalheatload(A)basedon(1)thesumofthepeakloadofeachroomor(2)thesystempeakload.In this example, select an outdoor unit by (2).Therefore, (A) = 173.0 MBH

Page 56: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

54

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

[3] –2 Provisionally select outdoor unit(1) Calculate CI (Capacity Index) of the selected indoor units.

CI of VRV indoor unitsCI of FXMQ15PBVJU = 15CI of FXMQ18PBVJU = 18CI of FXMQ36PBVJU = 36CI of FXMQ48PBVJU = 48

Calculate the total CI of the indoor units.Total CI = 15 × 2 + 18 × 2 + 36 × 2 + 48 × 2 = 234

The connection ratio of RXLQ-TA shall be between 70% and 130%.As the total CI of the indoor units is 234, outdoor units from 16 ton to 20 ton are connectable. Start from 16 ton which is the smallest outdoor unit.

(3) Confirm that the number of the connected indoor units is within the limitation.The number of the connected indoor units = 8The max. number of connectable indoor units of 16 ton outdoor unit = 33

(2) Provisionally select an outdoor unit based on the total CI of the indoor units

Capacity Range 0.5 ton 0.6 ton 0.8 ton 1 ton 1.25 ton 1.5 ton 2 ton 2.5 ton 3 ton 3.5 ton 4 ton 4.5 ton 5 ton 6 ton 8 ton Power Supply, StandardCapacity Index 5.8 7.5 9.5 12 15 18 20 24 30 36 42 48 54 60 72 96

Ceiling Mounted Duct Type (Middle and High Static Pressure)

FXMQ — 07PB 09PB 12PB 15PB 18PB — 24PB 30PB 36PB — 48PB 54PB — — — VJU

Type Ton Capacity index Model name CombinationOutdoor unit multi

connection piping kit *1

Total capacity index of connectable indoor

units *2

Maximum number of connectable indoor

units

Single outdoor unit

6 72 RXLQ72TA RXLQ72TA—

51 to 93 (144) 128 96 RXLQ96TA RXLQ96TA 68 to 124 (192) 1610 120 RXLQ120TA RXLQ120TA 84 to 156 (240) 20

Double outdoor units

12 144 RXLQ144TA RXLQ72TA+ RXLQ72TA

BHFP22P100U

101 to 187 (230) 25

16 192 RXLQ192TA RXLQ96TA+ RXLQ96TA 135 to 249 (307) 33

20 240 RXLQ240TA RXLQ120TA+ RXLQ120TA 168 to 312 (384) 41

Page 57: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

55

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

[3] –3 Calculate the corrected capacity of the outdoor unit.-Calculate the combination ratio of the system.Total CI = 234, CI of RXLQ192TAYCU = 192Combination ratio = 234 / 192 = 122%

- Using the capacity table of the outdoor unit, calculate the capacity (B) corrected for outdoor air temperature, indoor air temperature, and combination ratio.

120% 122% 130%

201 (B) 205

∗ In case the outdoor air temperature, the indoor air temperature, or the combination ratio falls between temperatures listed in the table, calculate the capacity by interpolation.

Connection ratio

Cooling capacity

(B) = 201 + (205 – 201) × (122 – 120) / (130 – 120) = 201.8

RXLQ192TATJU / TAYDU / TAYCU Cooling Capacity for Standard Condition (Te: 43°F)

Combi-nation

Outdoorair temp.

Indoorairtemp.(°FWB)57 61 64 67 70 72 75

TC PI TC PI TC PI TC PI TC PI TC PI TC PI% °FDB MBH kW MBH kW MBH kW MBH kW MBH kW MBH kW MBH kW

130

23 146 4.71 188 6.20 219 7.38 250 8.60 271 9.50 275 9.55 281 9.6330 146 4.86 188 6.40 219 7.63 250 8.94 265 9.63 269 9.68 275 9.7640 146 5.08 188 6.71 219 8.00 250 9.67 256 9.81 260 9.86 266 9.9550 146 5.33 188 7.05 219 8.59 242 9.91 248 10.0 251 10.1 257 10.154 146 5.44 188 7.20 219 8.88 238 9.98 244 10.1 248 10.1 254 10.258 146 5.55 188 7.36 219 9.18 235 10.1 241 10.1 245 10.2 250 10.362 146 5.66 188 7.59 219 9.50 231 10.1 237 10.2 241 10.3 247 10.466 146 5.79 188 7.85 219 9.83 228 10.2 234 10.3 238 10.4 243 10.570 146 5.91 188 8.26 219 10.4 224 10.5 230 10.6 234 10.6 240 10.772 146 6.06 188 8.58 217 10.6 223 10.7 229 10.8 232 10.9 238 11.075 146 6.41 188 9.09 214 11.0 220 11.1 226 11.2 230 11.3 236 11.479 146 6.89 188 9.79 211 11.5 217 11.7 222 11.8 226 11.8 232 12.083 146 7.40 188 10.5 207 12.1 213 12.2 219 12.3 223 12.4 229 12.587 146 7.94 188 11.3 204 12.6 210 12.7 216 12.9 219 12.9 225 13.191 146 8.51 188 12.2 200 13.1 206 13.3 212 13.4 216 13.5 219 13.693 146 8.81 188 12.6 199 13.4 205 13.5 210 13.7 214 13.8 215 13.895 146 9.12 188 13.1 197 13.7 203 13.8 209 14.0 210 14.0 210 14.099 146 9.76 188 14.0 194 14.2 199 14.4 202 14.4 202 14.4 202 14.4103 146 10.5 184 14.6 190 14.7 193 14.8 193 14.8 193 14.8 193 14.8106 146 11.1 182 15.2 187 15.3 187 15.3 187 15.3 187 15.3 187 15.3110 146 12.2 178 16.0 178 16.0 178 16.0 178 16.0 178 16.0 178 16.0115 146 13.5 154 17.0 154 17.0 155 17.0 155 17.0 155 17.1 155 17.1118 133 13.9 134 13.9 134 13.9 134 14.0 135 14.0 135 14.0 135 14.0122 107 9.83 107 9.85 107 9.87 108 9.89 108 9.91 108 9.92 108 9.94

120

23 135 4.33 173 5.66 202 6.73 230 7.84 259 8.98 271 9.50 276 9.5730 135 4.46 173 5.84 202 6.95 230 8.10 259 9.45 264 9.62 270 9.6940 135 4.66 173 6.13 202 7.29 230 8.58 252 9.75 256 9.80 261 9.8850 135 4.88 173 6.44 202 7.67 230 9.29 244 9.94 247 9.99 252 10.154 135 4.98 173 6.57 202 7.90 230 9.60 240 10.0 244 10.1 249 10.158 135 5.08 173 6.71 202 8.16 230 9.93 237 10.1 240 10.1 246 10.262 135 5.18 173 6.85 202 8.43 228 10.1 233 10.2 237 10.2 242 10.366 135 5.29 173 7.00 202 8.72 224 10.1 230 10.2 233 10.3 239 10.470 135 5.41 173 7.36 202 9.19 221 10.4 226 10.5 230 10.6 235 10.672 135 5.47 173 7.65 202 9.55 219 10.7 224 10.8 228 10.8 233 10.975 135 5.76 173 8.09 202 10.1 217 11.1 222 11.2 225 11.2 231 11.379 135 6.19 173 8.72 202 10.9 213 11.6 218 11.7 222 11.8 227 11.983 135 6.64 173 9.38 202 11.8 210 12.1 215 12.2 219 12.3 224 12.487 135 7.12 173 10.1 201 12.5 206 12.6 211 12.8 215 12.8 220 13.091 135 7.62 173 10.8 197 13.1 203 13.2 208 13.3 212 13.4 217 13.593 135 7.89 173 11.2 196 13.3 201 13.5 206 13.6 210 13.7 215 13.895 135 8.16 173 11.6 194 13.6 199 13.7 205 13.9 208 13.9 210 14.099 135 8.73 173 12.5 190 14.1 196 14.3 201 14.4 202 14.4 202 14.4103 135 9.34 173 13.4 187 14.7 192 14.8 193 14.8 193 14.8 193 14.8106 135 9.96 173 14.3 184 15.3 187 15.3 187 15.3 187 15.3 187 15.3110 135 10.9 173 15.6 178 16.0 178 16.0 178 16.0 178 16.0 178 16.0115 135 12.1 154 17.0 154 17.0 155 17.0 155 17.0 155 17.1 155 17.1118 133 13.9 134 13.9 134 13.9 134 14.0 135 14.0 135 14.0 135 14.0122 107 9.83 107 9.85 107 9.87 108 9.89 108 9.91 108 9.92 108 9.94

Page 58: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

56

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

-Confirm capacity correction factor by piping length and level difference (K1)

-Calculate capacity correction factor by piping heat loss (K2)(K2) = 1 + (heat loss factor per feet of piping × (equivalent piping length – 25 ft.)) / 100

In cooling mode, heat loss factor per feet at 93°F is calculated as below.(R) Heat loss factor per feet = 0.072*2 + (0.098*1 – 0.072*2) × (93*3 – 86*4) / (95*5 – 86*4) = 0.0922

Using “Equivalent piping length = 200 ft.” and “Heat loss factor per feet = 0.0922”,(K2) = 1 + (0.0922 × (200 – 25)) / 100 = 1.161

-Calculate the corrected capacity of RXLQ192TAYCU(C) by using (K1) and (K2).Corrected capacity of RXLQ192TAYCU (C) = (B) × (K1) / (K2) (add defrost correction factor for heating capacity) Therefore (C) = 201.8 × 0.926 / 1.161 = 161.0 MBH

If the corrected capacity (C) is the same or greater than the required total heat load (A), selection is complete.If (C) < (A), return to Procedure [3]–2 and provisionally select a larger outdoor unit.In this example, 161.0 MBH (C) < 173.0 MBH (A), so need to select a larger outdoor unit.

The capacity of RXLQ240TAYCU at the same condition is 185.8 MBH, which is more than the heat load (A): 173.0 MBH. So the selection is complete.

Cooling Ambient temperature

Heat loss factor per feet of piping (%)

Heating Ambient temperature

Heat loss factor per feet of piping (%)

5°F 14°F 23°F 32°F 41°F 50°F 59°F 68°F0.328 0.305 0.282 0.256 0.233 0.210 0.187 0.161

(K1) = 0.926

0.926

41°F

0.000

50°F

0.000

59°F

0.013

68°F

0.030

77°F

0.046

86°F*4

0.072*2

93°F*3

(R)

95°F*5

0.098*1

104°F

0.125

Page 59: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

57

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

20. Caution Label20.1 RXLQ72 - 120TATJU / TAYDU / TAYCU

3P487082-1

Page 60: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

58

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

1P361833-1B

Page 61: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

59

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

1P361833-1B

Page 62: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

60

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

1P361833-1B

Page 63: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

61

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

1P361833-1B

Page 64: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

62

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

1P361833-1B

Page 65: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

63

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

1P361833-1B

Page 66: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

64

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

3P510840-1

Page 67: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

65

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

3P510840-1

Page 68: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

66

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

21. Caution for Refrigerant Leaks21.1 Introduction

Points to note in connection with refrigerant leaks

The installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available.

The VRV System, like other air conditioning systems, uses R410A as refrigerant. R410A itself is an entirely safe non-toxic, non-combustible refrigerant.Neverthelesscaremustbetakentoensurethatairconditioningfacilitiesareinstalledinaroomwhichissufficientlylarge.Thisassuresthat the maximum concentration level of refrigerant gas is not exceeded, in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards.

Maximum concentration levelThe maximum charge of refrigerant and the calculation of the maximum concentration of refrigerant is directly related to the humanly occupied space in to which it could leak.The unit of measurement of the concentration is lb./1000 ft.3 (the weight in Ibs. of the refrigerant gas in 1 ft.3 volume of the occupied space).Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required.

Direction of therefrigerant flow

Room where refrigerant leak has occurred(outflow of all the refrigerant from the system)

Pay special attention to places, such as basements, etc. where refrigerant can stay, since refrigerant is heavier than air.

Page 69: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

67

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

21.2 Procedure for Checking Maximum Concentration

Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply.Step1: Calculate the amount of refrigerant (lbs.) charged to each system separately.

Amount of refrigerant in a single unitsystem (amount of refrigerant withwhich the system is charged beforeleaving the factory)

+

Additional charging amount (amountof refrigerant added locally inaccordance with the length or diameterof the refrigerant piping)

= Total amount of refrigerant (lbs.)in the system

Note:Where a single refrigerant facility is divided into 2 entirely independent refrigerant systems then use the amount of refrigerant with which each separate system is charged.

Step 2: Calculate the smallest room volume (ft.3) In case like the following, calculate the volume of (a), (b) as a single room or as the smallest room. (a) Where there are no smaller room divisions.

(b)Wherethereisaroomdivisionbutthereisanopeningbetweentheroomssufficientlylargetopermitafreeflowofairbackandforth.

Opening betweenrooms

Partition

(Where there is an opening without a door or where there are openings above and below the door which are each equivalent in size to 0.15% ormoreofthefloorarea.)

(c) Where there is a gas leak detection alarm device linked to a mechanical ventilator in the smallest room then the next smallest room will become the measurement target.

Page 70: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

68

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

Step 3: Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above.

Total volume of refrigerant in therefrigerant system

≤ Maximum concentration level (lbs./ft.3)Size (ft.3) of the smallest room in whichthere is an indoor unit installed

If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so until the result falls short of the maximum concentration.

Step 4: Dealing with the situations where the result exceeds the maximum concentration level. Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise

the system. Please consult your Daikin supplier.

Page 71: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

69

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

22. Safety Devices Setting22.1 FXFQ-T

Model FXFQ07TVJU FXFQ09TVJU FXFQ12TVJU FXFQ15TVJU FXFQ18TVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AFan motor thermal fuse °F(°C) – – – – –Fan motor thermal protector °F(°C) – – – – –

Model FXFQ24TVJU FXFQ30TVJU FXFQ36TVJU FXFQ48TVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AFan motor thermal fuse °F(°C) – – – –Fan motor thermal protector °F(°C) – – – –

C: 3D086932A

22.2 FXZQ-TA

Model FXZQ05TAVJU FXZQ07TAVJU FXZQ09TAVJU FXZQ12TAVJU FXZQ15TAVJU FXZQ18TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AFan motor thermal fuse °F(°C) – – – – – –Fan motor thermal protector °F(°C) – – – – – –Drain pump fuse °F(°C) – – – – – –

C: 4D110603

22.3 FXUQ-P

Model FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F(°C) – – – –Fan motor thermal protector °F(°C) – – – –Fan motor thermal fuse °F(°C) – – – –

C: 3D090213

22.4 FXEQ-P

Model FXEQ07PVJU FXEQ09PVJU FXEQ12PVJU FXEQ15PVJU FXEQ18PVJU FXEQ24PVJUPrinted circuit board fuse A1P 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A

Fan motor thermal protector °F(°C)OFF: 223±9

(106±5)ON: 205±27

(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

OFF: 223±9 (106±5)

ON: 205±27(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

C: 4D098709

Page 72: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

70

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

22.5 FXDQ-M

Model FXDQ07MVJU FXDQ09MVJU FXDQ12MVJU FXDQ18MVJU FXDQ24MVJUPrinted circuit board fuse A1P 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A

Fan motor thermal protector °F OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

C: 3D051758

22.6 FXSQ-TA

Model FXSQ05TAVJU FXSQ07TAVJU FXSQ09TAVJU FXSQ12TAVJU FXSQ15TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) — — — — —

Model FXSQ18TAVJU FXSQ24TAVJU FXSQ30TAVJU FXSQ36TAVJU FXSQ48TAVJU FXSQ54TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) — — — — — —

C: 3D112398

22.7 FXMQ-PB

Model FXMQ07PBVJU FXMQ09PBVJU FXMQ12PBVJU FXMQ15PBVJU FXMQ18PBVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) 293 (145) 293 (145) 293 (145) 293 (145) 293 (145)

Model FXMQ24PBVJU FXMQ30PBVJU FXMQ36PBVJU FXMQ48PBVJU FXMQ54PBVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) 293 (145) 293 (145) 293 (145) 293 (145) 293 (145)

C: 3D086916B

22.8 FXMQ-M

Model FXMQ72MVJU FXMQ96MVJUPrinted circuit board fuse 250 V, 5 A 250 V, 5 AFan motor thermal fuse °F – –

Fan motor thermal protector °F OFF: 275±14(ON: 189±27)

OFF: 275±14(ON: 189±27)

Page 73: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

71

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

22.9 FXHQ-M

Model FXHQ12MVJU FXHQ24MVJU FXHQ36MVJUPrinted circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 AFan motor thermal fuse °F – – –

Fan motor thermal protector °F OFF: 266±9ON: 176±36

OFF: 266±9ON: 176±36

OFF: 266±9ON: 176±36

C: 3D049334A

22.10 FXAQ-P

Model FXAQ07PVJU FXAQ09PVJU FXAQ12PVJU FXAQ18PVJU FXAQ24PVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AFan motor thermal fuse °F – – – – –Fan motor thermal protector °F – – – – –

C: 4D047085C

22.11 FXLQ-M, FXNQ-M

Model FXLQ07MVJUFXNQ07MVJU

FXLQ09MVJUFXNQ09MVJU

FXLQ12MVJUFXNQ12MVJU

FXLQ18MVJUFXNQ18MVJU

FXLQ24MVJUFXNQ24MVJU

Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A

Fan motor thermal protector °F(°C)OFF: 275±18

(135±18)ON: 248 (120)

or less

OFF: 275±18(135±18)

ON: 248 (120)or less

OFF: 275±18(135±18)

ON: 248 (120)or less

OFF: 275±18(135±18)

ON: 248 (120)or less

OFF: 275±18(135±18)

ON: 248 (120)or less

C: 3D045646B

22.12 FXTQ-TA

Model FXTQ09TAVJUA FXTQ12TAVJUA FXTQ18TAVJUA FXTQ24TAVJUA FXTQ30TAVJUAModel (with factory disconnect) FXTQ09TAVJUD FXTQ12TAVJUD FXTQ18TAVJUD FXTQ24TAVJUD FXTQ30TAVJUD

Printed circuit board fuse (F1U) 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 APrinted circuit board fuse (F2U) 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AOthers Blower motor, Fan driver overload protector

Model FXTQ36TAVJUA FXTQ42TAVJUA FXTQ48TAVJUA FXTQ54TAVJUA FXTQ60TAVJUAModel (with factory disconnect) FXTQ36TAVJUD FXTQ42TAVJUD FXTQ48TAVJUD FXTQ54TAVJUD FXTQ60TAVJUD

Printed circuit board fuse (F1U) 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 APrinted circuit board fuse (F2U) 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AOthers Blower motor, Fan driver overload protector

Page 74: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

72

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

Page 75: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

73

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

Appendix

1. Introduction ...............................................................................................741.1 ED Book List ...................................................................................741.2 Publication List of Engineering Data for VRV Products ..................75

2. GuideSpecifications .................................................................................772.1 GuideSpecifications .......................................................................77

Page 76: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

74

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

1. Introduction1.1 ED Book List

Design Manual ..................................................... RXLQ-TA ........ EDUS341819-D (This booklet)

Indoor Units

Ceiling Mounted Cassette Type (Round Flow with Sensing) ....... FXFQ-T ..... EDUS391400A-F14

VISTA™ 2 × 2 Cassette Unit .................................. FXZQ-TA .......... EDUS391776-F9

4-Way Blow Ceiling-Suspended Type ...................... FXUQ-P ........ EDUS391437-F15

One Way Blow Cassette Type ................................ FXEQ-P ........ EDUS391533-F16

Slim Ceiling Mounted Duct Type ............................. FXDQ-M ........... EDUS39-600-F2

MSP Concealed Duct Unit ..................................... FXSQ-TA ........ EDUS391777-F17

Ceiling Mounted Duct Type .................................... FXMQ-PB ........ EDUS391503A-F4

Ceiling Mounted Duct Type .................................... FXMQ-M ....... EDUS39-900A-F11

Ceiling Suspended Type ....................................... FXHQ-M ........... EDUS39-600-F5

Wall Mounted Type .............................................. FXAQ-P .......... EDUS391100-F6

Floor Standing Type / Concealed Floor Standing Type ........ FXLQ-MFXNQ-M .......... EDUS391502-F7

Air Handling Unit .................................................. FXTQ-TA ....Engineering Data FXTQ-TA

Air Treatment Equipment

Outdoor Air Processing Unit ................................... FXMQ-MF ....... EDUS39-900A-F10

Energy Recovery Ventilator .................................... VAM-G ............. EDUS711116A

Outdoor Units Capacity Table Book

Heat Pump ......................................................... RXLQ-TA ............ EDUS341819-C

Controls ............................................................................................ EDUS391000-C

Remote Controller

Navigation Remote Controller ................................. BRC1E73 ............... EDUS721438

Page 77: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

75

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

1.2 Publication List of Engineering Data for VRV Products

Refrigerant Type Product Series Book No. Type Hz Volts Model name Area Note Published in

R410A

Air cooled

Inverter T, PC

EDUS371435-MH/RH/RH/RH/R

60 Hz60 Hz60 Hz60 Hz

460 V208/230 V460 V208/230 V

REYQ72-456TYDNREYQ72-456TTJUREYQ72-120PCYDREYQ72-144PCTJ

USA Generalinformation Aug. 2015

EDUS371435-NH/RH/RH/RH/R

60 Hz60 Hz60 Hz60 Hz

460 V208/230 V460 V208/230 V

REYQ72-456TYDNREYQ72-456TTJUREYQ72-120PCYDREYQ72-144PCTJ

USA Installation Jul. 2015

EDUS371435-R3 H/R 60 Hz 460 V REYQ72-120PCYD USA Specification Mar. 2015EDUS371435-R4 H/R 60 Hz 208/230 V REYQ72-144PCTJ USA Specification Mar. 2015

Inverter TA

EDUS341703-M H/PH/P

60 Hz60 Hz

460 V208/230 V

RXYQ72-408TAYDURXYQ72-408TATJU USA General

information Jun. 2017

EDUS341703-N H/PH/P

60 Hz60 Hz

460 V208/230 V

RXYQ72-408TAYDURXYQ72-408TATJU USA Installation Jul. 2017

EDUS341703-R1 H/P 60 Hz 460 V RXYQ72-408TAYDU USA Specification Apr. 2017EDUS341703-R2 H/P 60 Hz 208/230 V RXYQ72-408TATJU USA Specification Apr. 2017

EDUS371704-M H/RH/R

60 Hz60 Hz

460 V208/230 V

REYQ72-456TAYDUREYQ72-456TATJU USA General

information Jun. 2017

EDUS371704-N H/RH/R

60 Hz60 Hz

460 V208/230 V

REYQ72-456TAYDUREYQ72-456TATJU USA Installation Jul. 2017

EDUS371704-R1 H/R 60 Hz 460 V REYQ72-456TAYDU USA Specification May 2017EDUS371704-R2 H/R 60 Hz 208/230 V REYQ72-456TATJU USA Specification May 2017EDUS341824-D H/P 60 Hz 575 V RXYQ72-384TAYCU Canada Design manual Jun. 2018

EDUS341824-C H/P 60 Hz 575 V RXYQ72-384TAYCU Canada Capacity table book Jun. 2018

EDUS371706-M H/R 60 Hz 575 V REYQ72-384TAYCU Canada General Information Jun. 2017

EDUS371706-N H/R 60 Hz 575 V REYQ72-384TAYCU Canada Installation Jul. 2017EDUS371706-R H/R 60 Hz 575 V REYQ72-384TAYCU Canada Specification Jun. 2017

EDUS371705A-M H/R 60 Hz208/230 V460 V

RELQ72-240TATJURELQ72-240TAYDU

USACanada General

Information Oct. 2017575 V RELQ72-240TAYCU Canada

EDUS371705A-N H/R 60 Hz208/230 V460 V

RELQ72-240TATJURELQ72-240TAYDU

USACanada Installation Oct. 2017

575 V RELQ72-240TAYCU Canada

EDUS371705A-R H/R 60 Hz208/230 V460 V

RELQ72-240TATJURELQ72-240TAYDU

USACanada Specification Oct. 2017

575 V RELQ72-240TAYCU Canada

EDUS341819-D H/P 60 Hz208/230 V460 V

RXLQ72-240TATJURXLQ72-240TAYDU

USACanada Design manual Jun. 2018

575 V RXLQ72-240TAYCU Canada

EDUS341819-C H/P 60 Hz208/230 V460 V

RXLQ72-240TATJURXLQ72-240TAYDU

USACanada Capacity table

book Jun. 2018575 V RXLQ72-240TAYCU Canada

EDUS331608B-M H/P 60 Hz 208/230 V RXTQ36TAVJ9RXTQ48/60TAVJU USA General

information Feb. 2018

EDUS331608B-N H/P 60 Hz 208/230 V RXTQ36TAVJ9RXTQ48/60TAVJU USA Installation Jan. 2018

EDUS331608B-R H/P 60 Hz 208/230 V RXTQ36TAVJ9RXTQ48/60TAVJU USA Specification Jan. 2018

Water cooled

EDUS301716-MH/PH/RH/PH/R

60 Hz60 Hz60 Hz60 Hz

208/230 V208/230 V460 V460 V

RWEQ96-432TATJURWEQ96-432TAYDU USA General

information Mar. 2018

EDUS301716-NH/PH/RH/PH/R

60 Hz60 Hz60 Hz60 Hz

208/230 V208/230 V460 V460 V

RWEQ96-432TATJURWEQ96-432TAYDU USA Installation Mar. 2018

EDUS301716-RH/PH/RH/PH/R

60 Hz60 Hz60 Hz60 Hz

208/230 V208/230 V460 V460 V

RWEQ96-432TATJURWEQ96-432TAYDU USA Specification Mar. 2018

Page 78: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

76

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

Refrigerant Type Product Series Book No. Type Hz Volts Model name Area Note Published in

R410A

VRV Indoor units

EDUS391400A-F14 – 60 Hz – FXFQ07-48TVJU USA

Ceiling Mounted Cassette (Round Flow with Sensing) Type

May 2018

EDUS391776-F9 – 60 Hz – FXZQ05-18TAVJU USA VISTA™ 2 x 2 Cassette Unit Mar. 2018

EDUS391437-F15 – 60 Hz – FXUQ18-36PVJU USA4-Way Blow Ceiling-Suspended Type

May 2015

EDUS391533-F16 – 60 Hz – FXEQ07-24PVJU USA One Way Blow Cassette Type Oct. 2015

EDUS39-600-F2 – 60 Hz – FXDQ07-24MVJU USASlim Ceiling Mounted Duct Type

Sep. 2006

EDUS391777-F17 – 60 Hz – FXSQ05-54TAVJU USAMSP Concealed Ducted Unit

Mar. 2018

EDUS391503A-F4 – 60 Hz – FXMQ07-54PBVJU USA

Ceiling Mounted Duct Type (Middle and High Static Pressure)

May 2018

EDUS39-900A-F11 – 60 Hz – FXMQ72/96MVJU USACeiling Mounted Duct Type

May 2010

EDUS39-600-F5 – 60 Hz – FXHQ12-36MVJU USACeiling Suspended Type

Sep. 2006

EDUS391100-F6 – 60 Hz – FXAQ07-24PVJU USA Wall Mounted Type Jan. 2012

EDUS391502-F7 – 60 Hz – FXLQ07-24MVJUFXNQ07-24MVJU USA

Floor Standing TypeConcealed Floor Standing Type

Jul. 2015

Engineering Data FXTQ-TA – 60 Hz – FXTQ09-60TAVJUA

FXTQ09-60TAVJUD USA Air Handling Unit Sep. 2016

EDUS39-900A-F10 – 60 Hz – FXMQ48-96MFVJU USAOutdoor Air Processing Unit

May 2010

EDUS391434-B – 60 Hz – BSQ36-96TVJ USA Single Branch Selector Unit Aug. 2015

EDUS391434-B – 60 Hz – BS4-12Q54TVJ USA Multi Branch Selector Unit Aug. 2015

Controls and networks

EDUS391000-C – – –

BRC1E71, BRC4C/7C/7E, BRC2A71DCS302C71, DCS301C71,DST301BA61, DCS601C71KRP1C74/75

USA

Remote controllerControl devices

Adaptor

Aug. 2010

EDUS721438 – – – BRC1E73 USANavigation remote controller

Apr. 2015

EDUS721212 – – – DCM601A71DCM601A72 USA

intelligent Touch Manager

Oct. 2012

EDUS72-608 – – – DCS601C71 USAintelligent Touch Controller

Dec. 2006

EDUS72-749 – – – DMS502B71 USAInterface for use in BACnet®

Oct. 2007

Option for all type OHUS07-1 – – – For indoor and outdoor units USA Option

handbook Nov. 2007

Energy Recovery Ventilator (VAM) EDUS711116A – 60 Hz – VAM300-1200GVJU USAEnergy Recovery Ventilator

Jun. 2017

EDUS341819-D, C as shown by .C/O : Cooling onlyH/P : Heat pumpH/R : Heat recovery

Page 79: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

77

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

2. Guide Specifications2.1 Guide Specifications

GeneralUnit shall be air cooled, split type multi-system air conditioner consisting of one outdoor unit and plural indoor units, each having capability to cool or heat independently for the requirements of the rooms.Upto13differenttypeindoorunitscanbeconnectedtoonerefrigerantcircuitandcontrolledindividually.Compressor shall be equipped with inverter controller, and capable of changing the rotating speed to follow variations in cooling and heating load.Outdoor unit shall be suitable for mix-match connection of following models.

�� Ceiling Mounted Cassette Type (Round Flow with Sensing)�� VISTA™ 2 × 2 Cassette Unit�� 4-Way Blow Ceiling-Suspended Type�� One Way Blow Cassette Type�� Slim Ceiling Mounted Duct Type�� MSP Concealed Ducted Unit�� Ceiling Mounted Duct Type (Middle and High Static Pressure)�� Ceiling Mounted Duct Type�� Ceiling Suspended Type�� Wall Mounted Type�� Floor Standing Type�� Concealed Floor Standing Type�� Air Handling Unit

�� Refrigerant: R410A

2.1.1 TA Series Outdoor UnitThe actual refrigerant piping length shall be extended up to 540 ft. (165 m) with 164 ft. (50 m) (1)leveldifferencewithoutanyoiltraps.�� Airconditionershalloperatecontinuouslyattheambienttemperatureof23°F(-5°C)incooling-22°F(-30°C)inheating.

Both indoor unit and outdoor unit are assembled, tested, and charged with refrigerant at the factory. 1: The value is based on the case where the outdoor unit is located above indoor unit. Where the outdoor unit is located under the indoor unit, the leveldifferenceisamaximumof130ft.(40m).

Outdoor UnitThe outdoor unit shall be a factory assembled unit housed in a sturdy weatherproof casing constructed form rust-proofed mild steel panels coated withabakedenamelfinish.�� The outdoor unit shall be modular in design and should be allowed for side by side installation.

CompressorThecompressorshallbeofhighlyefficienthermeticscrolltypeandequippedwithinvertercontrolcapableofchangingthespeedinaccordancetothe cooling or heating load requirement.�� Theoutdoorunitshallhavethemulti-stepofcapacitycontroltomeetloadfluctuationandindoorunitindividualcontrol.

Heat ExchangerTheheatexchangershallbeconstructedwithcoppertubesmechanicallybondedtoaluminumfinstoformacrossfincoil.�� Thealuminumfinsshallbecoveredbyanti-corrosionresinfilm.

Refrigerant CircuitTherefrigerantcircuitshallincludeliquidandgasshutoffvalvesandsolenoidvalves.All necessary safety devices shall be provided to ensure the safety operation of the system.

Page 80: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

78

RXLQ-TATJU / RXLQ-TAYDU / RXLQ-TAYCU EDUS341819-D

Safety DevicesThe following safety devices shall be part of the outdoor unit.High pressure switch, Fan driver overload protector, Overcurrent fuse, Inverter overload protector, Leak detecting device.

Oil Recovery SystemUnit shall be equipped with an oil recovery system to ensure stable operation with long refrigerant piping.

2.1.2 Indoor UnitsEach indoor unit shall be of the Ceiling Mounted Cassette Type (Round Flow with Sensing), VISTA™ 2 × 2 Cassette Unit, 4-Way Blow Ceiling-Suspended Type, One Way Blow Cassette Type, Slim Ceiling Mounted Duct Type, MSP Concealed Ducted Unit, Ceiling Mounted Duct Type (Middle and High Static Pressure), Ceiling Mounted Duct Type, Ceiling Suspended Type, Wall Mounted Type, Floor Standing Type, Concealed FloorStandingType,orAirHandlingUnit.Itshallhaveelectroniccontrolvalvewhichcontrolsrefrigerantflowrateinrespondtoloadvariationsofthe room. The fan shall be of the multi blade type and statically and dynamically balanced to ensure low noise and vibration free operation.�� The address of the indoor unit shall be set automatically in case of individual and group control.�� In case of centralized control, it shall be set by remote controller.

ControlComputerized PID control shall be used to maintain a correct room temperature.Unit shall be equipped with a self-diagnosis for easy and quick maintenance and service.The Navigation remote controller shall memorize the latest malfunction code for easy maintenance.�� Itshallbeabletocontrolupto16indoorunitsandchangefanspeedandangleofswingflapindividuallyinthegroup.

Central Remote Controller (Option)A multi-functional centralized control equipment (central remote controller) shall be supplied as optional accessory.�� It shall be able to control up to 64 Zones of 64 indoor unit groups (each group consists of max. 16 indoor units) or 128 indoor units with the following

functions.a) Temperature setting for each Zone, or group, or indoor unit.b) ON/OFF as a Zone or individual unit.c) Indication of operating condition.d) Select one of 10 operation modes for each Zone.�� The controller shall have wide screen LCD and can be wired by a non-polar 2-wire transmission cable to a distance of 3280 ft. (1000 m) away from

the indoor unit.

Unified ON / OFF Controller (Option)UnifiedON/OFFcontrollershallbesuppliedasoptionalaccessory.It shall be able to control up to 16 indoor unit groups (each group consists of max. 16 indoor units) or 128 indoor units with the following functions.a) ON/OFF as a zone or individual unit.b) Indication of operation condition of each group.c) Select one of 4 operation modes.

It shall be wired by a non-polar 2-wire transmission cable to a distance of 3280 ft. (1000 m) away from indoor unit.

Schedule Timer (Option)A schedule timer shall be supplied as optional accessory.�� It shall be able to set operation schedule of up to 128 indoor units.

The operation schedule shall include twice ON/OFF a day and holiday.�� It shall be able to set 8 patterns of schedule combined with centralized controller.

intelligent Touch Controller (Option)Air-conditioning management system that can be controlled by a compact all-in-one unit.

intelligent Touch Manager (Option)Air-conditioning management system that can be controlled by a compact all-in-one unit.

Page 81: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU
Page 82: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU
Page 83: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU
Page 84: RXLQ-TATJU, 208 / 230 V RXLQ-TAYDU, 460 V RXLQ-TAYCU, …...For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. 14 RXLQ-TATJU / RXLQ-TAYDU

1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.

Cautions on product corrosion

Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.

Read the user’s manual carefully before using this product. The user’s manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.

If you have any enquiries, please contact your local importer, distributor and/or retailer.

©All rights reserved 06/18 FS

●Specifications, designs and other content appearing in this brochure are current as of June 2018 but subject to change without notice.

VRV Air Conditioning System is the world’s first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982.VRV is the trade mark of Daikin Industries, Ltd., which is derived from the technology we call “variable refrigerant volume.”