18
Business Sensitive 1 Ryan James Battelle Senior Research Scientist Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

Business Sensitive 1

Ryan James Battelle Senior Research Scientist Judy Lopez AFCEC/CZTQ Water Quality

Demonstration and Validation of Real Time Water Quality Monitoring Technologies

Page 2: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

Background

•  January 2014 - AFCEC issued a statement of need pertaining to Safe Drinking Water Act (SDWA) violations, specifically referencing total coliform rule violations and disinfection byproduct problems across the Air Force

• Battelle responded with a white paper describing an idea of implementing water quality monitoring as well as automated coliform analysis

• May-July 2014 Battelle submitted full proposal describing a plan to help address some of the SDWA concerns including trihalomethane monitoring

• Monitoring conducted May 2015 through August 2016

Business Sensitive 2

Page 3: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

Objectives

• Demonstrate and validate (Dem-Val) a comprehensive water monitoring approach to possibly reduce or eliminate SDWA violations § Pathogen detection

§ Water quality monitoring

§ Disinfection byproduct monitoring

• Provide option that if successful, could be transitioned to broader Air Force use

Business Sensitive 3

Page 4: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

Water Quality Monitoring •  ENDETEC KAPTA 3000TM: in-pipe real-time

water quality monitoring (chlorine, conductivity, pressure, and temperature) indicators of conditions favorable for SDWA violations

•  All data transmission via cellular signal, there will be no use of Air Force computer or communication networks

•  All instrumentation will be for monitoring; no treatment, process, or flow control technologies will be tested or used

•  ENDETEC TECTA B-16TM: automated instrument/method that is EPA approved for regulatory analysis for total coliforms and E. coli

Business Sensitive 4

TECTA B-16TM

KAPTA 3000TM

Page 5: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

ENDETEC KAPTA 3000TM

• Chemical-free operation • Annual maintenance

•  In-pipe placement

• Measurement of active chlorine (HOCl) vs. free chlorine – not the typical chlorine residual metric

• Pressure measured with a piezo electric sensor

• Conductivity measured as well

Business Sensitive 5

KAPTA 3000TM Functionality

Page 6: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

Wright-Patterson Air Force Base •  Minimum 2” pipe with flow

•  Accessible for sampling and install (not-buried)

•  Strong cell phone signal for data collection

•  7 sites installed and monitored from June 2015 through August 2016

•  Data collected on base unit (KAPTALink) located 60 miles from sensors

Business Sensitive 6

Page 7: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

Wright-Patterson Air Force Base

Business Sensitive 7

Page 8: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

KAPTA 3000 Chlorine Results

Business Sensitive 8

Page 9: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

KAPTA 3000 Chlorine Results

Business Sensitive 9

Page 10: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

KAPTA 3000 Conductivity Results

Business Sensitive 10

Page 11: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

KAPTA 3000 Conductivity Results

Business Sensitive 11

Page 12: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

Aqua Metrology Systems THM-100™ • AF distribution system experiencing

periodic violations in various areas of the Safe Drinking Water Act (SDWA)

• AMS THM-100 uses automated “purge and trap” with spectrometric detection

• Side-stream continuous monitoring • Grab sample monitoring using same unit

• Demonstrated instrument that employs cloud-based data collection

Business Sensitive 12

THM-100TM

Page 13: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

Altus, OK Air Force Base •  Drinking water sources with THM

levels that exceed regulatory levels

•  Installed Aqua Metrology THM-100 for continuous analysis

•  Has revealed episodic changes in THM levels not before identified

•  Altus is extending monitoring for 2 additional years

Business Sensitive 13

Page 14: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

THM-100™ Results

Business Sensitive 14

Page 15: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

THM-100™ Grab Sample Results

Business Sensitive 15

Page 16: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

Continuous Data

Business Sensitive 16

THM-100™

KAPTA 3000

Page 17: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

Potential for Technology Transfer • Active vs free chlorine and

locations are a limitation

• Data communication is convenient-30 probes can be placed per base unit

•  TECTA B-16 EPA-approved for regulatory use; 16 samples at a time

• Extremely simple to operate

•  THM-100™ applicable for any high THM base

• Alert functionality convenient operation feature

• Continuous monitoring offers many advantages vs infrequent grab sampling

• Battelle very familiar and can coordinate process

Business Sensitive 17

Page 18: Ryan James Battelle Senior Research Scientist Judy Lopez …€¦ · Judy Lopez AFCEC/CZTQ Water Quality Demonstration and Validation of Real Time Water Quality Monitoring Technologies

Contact Information

Battelle Contact Ryan James, Project Manager

614-424-7954

[email protected]

Air Force Contact Judy Lopez

AFCEC/CZTQ Water Quality

210-925-0616

[email protected]