Grundfos offers a full range of extremely depend-able, powerful sewage pumps, designed for hand-ling unscreened raw sewage. Our more thanforty years experience in providing specialisedpumps and pumping equipment for all kinds ofwastewater and sewage has taught us what ourcustomers demand from a sewage pump:
Large, powerful pumps for handling unscreened raw sewage
Powerful advantages
> Higher pump efficiency over time
State-of-the-art technology makes the Grundfospumps extremely efficient and highly depend-able. Innovative features such as the uniqueSmartTrim adjustment of impeller clearanceprovide low Cost of Ownership.
> Less downtime
The excellent solids handling capability of ourchannel-impeller pumps guarantees maximumoperating time and substantial reductions inmaintenance costs caused by pump jamming or clogging.
> Lifelong reliability
The sturdy sewage pumps are designed forcontinuous pumping under the most difficultoperating conditions. The well-proven design is based on our long experience in the waste-water business.
At Grundfos we maintain a close dialogue withour customers to constantly improve pumpdesign and performance. Only this way can webuild the long-lasting partnerships on whichour business is founded.
Grundfos
> 2
> 3
Installation options
Submerged installation on auto-coupling, types 1 and 2Submerged installation on auto-coupling system requires a base plate with a 90°bend, fixed to the bottom of the pit. When lowered into the pit along the guiderails, the pump automatically connects to the base plate. The flexible neopreneSmartSeal ensures a leak-proof connection between the pump and the auto-coupling.
Type 1: To prevent sedimentation of sludge in connection with intermittent operation, werecommend a stop level corresponding to the top of the pump housing. For sufficientcooling in connection with continuous operation, the liquid level must always beabove the middle of the motor.
Type 2: Motor cooling is independent of the pumped liquid level, thanks to separate motorcooling.
Vertical dry installation, type 3The Grundfos sewage pumps can be installed either vertically or horizontally tosuit specific application arrangements. All pumps are 100% watertight, allowingfor dry installation with the workspace around the pump remaining clean and dry.The pumps are fully flood-proof if an unexpected flooding should occur.
Motor cooling takes place by means of a cooling jacket.
Submerged installation, portable, types 4 and 5Certain applications, such as construction sites, require portable submersibles. Where aportable submersible is required, hoses of varying lengths and materials can be supplied.
Type 4: To prevent sedimentation of sludge in connection with intermittent operation, werecommend a stop level corresponding to the top of the pump housing. For sufficientcooling in connection with continuous operation, the liquid level must always beabove the middle of the motor.
Type 5: Motor cooling is independent of the pumped liquid level, thanks to separate motor cooling.
Horizontal dry installation, type 6Horizontal dry installation improves the overall efficiency of the system as unneces-sary components and bends are avoided. The feasibility of horizontal dry installationdepends on the floor space available as the system takes up slightly more spacethan a vertically installed pump.
Motor cooling takes place by means of a cooling jacket.
4
Tough and reliable pumps...
The Grundfos submersible sewage pumps are designed to reduce energyconsumption and to keep downtime costs at a minimum. Maintaining peakefficiency throughout the entire lifetime of the system is a key issue:
Lower bearings comprise a singleor a double bearing
Watertight encapsulated motor,insulation class F (155 C), enclosureclass IP 68, with three thermalsensors in the stator windings.
Seal condition monitoring (from frame size50). A monitoring probe in the oil housinggives early warning of seal leakage (optional).
The Grundfos SmartSealgasket system provides a completely leak-proof connection.
Double mechanical shaft seal systemin intermediate oil chamber for reliablesealing between the pumped liquidand the motor. Primary seal withSiC/SiC rings, and SiC/carbon rings in the secondary seal.
o
5 Details > 5
- with many unique features
Watertight cable entry ofcorrosion-resistant polya-
mide, or cast iron with softshapes to prevent damage
to the power cable.
Dynamically balancedpump shaft of stainlesssteel or fully protected
against contact withpumped liquid. Conical
shaft end for safe securing of impeller.
SmartTrim system allows easy adjustment
of factory-set impellerclearance, maintaining
maximum pump efficiency.
In horizontal or vertical dry installations, some of
the pumps can be equippedwith a cooling jacket.
Moisture detector continuously monitors
the motor enclosure, and automatically cuts off the
power in the eventof leakage.
Shaft seal > 6
Advanced sealing technology
47 metres of backflow with no non-return valvesIn the Pihlajanmäki pumping station in Finland, water is being lifted 47 metres. The Grundfos pumps in thisinstallation have no non-return valves. Consequently, when the pumps are stopped, the entire water columnflows back to the pit through the pumps. With this arrangement the liquid in the pit is stirred up and mixed to prevent sedimentation problems.
Automatic flushing of wet pitsThe shaft seals of Grundfos pumps are capable ofrotating in either direction. When pumps are installedwith separate pipework, sludge sedimentation canbe effectively avoided by back flushing the systemat regular intervals.
Extended pump lifeTrouble-free shaft seal operation is ensured bysprings located inside the oil chamber. The springsare completely isolated from the pumped liquid.Automatic removal of air and grit from the sealarea, in combination with silicon carbide primaryseal faces is the best guarantee for trouble-freeoperation and extended pump life.
Reduced dry pit installation costsIn pumping stations with separate pipework foreach pump, costly non-return valves can be avoided.
Motor > 7
Operating conditions
Vertically installed pumps, with stator housingconduit cooling.
Horizontally installed pumps with cooling jacket
Operating conditions andmaximum starting frequency
Pump application is restricted by the followinglimits:
• Maximum ambient temperature andpumped liquid temperature: +40°C
• Storage temperature range: -30°C to +60°C
• Maximum submergence: 20 m
• Voltage tolerance: -10% to +10%
Pump starting frequency should not exceed therecommendations indicated below. For shorterperiods of time a starting frequency of up to double the recommended is permissible.
Range Starts per hour34, 42 2546, 50, 54 2058, 62, 66, 70 15
In dry applications – or in submerged in-stallations at low water level – efficientcooling of the motor is essential. This isachieved either through a cooling jacketencasing the stator housing or by meansof built-in heat conduits transporting theheat away from the motor.
Stator housing conduitsCooling of the motor takes place by transferringexcess heat via the stator housing to the pumpedliquid. Applicable for Grundfos pump ranges 34, 42 and 46.
Cooling jacketSome of the pumped liquid is led into the cool-ing jacket via a clearance behind the impeller.An integrated screening system prevents solidsfrom entering the cooling jacket. By circulatingthe liquid around the motor, excess heat is trans-ferred to the pumped liquid and led away.Applicable for Grundfos pump ranges 50, 54, 58, 62, 66 and 70.
Explosion-proof versionsFor applications involving the risk of explosion,or where otherwise required, explosion-proofversions of the s-pumps are available.
SuperVortex > 8
Grundfos SuperVortex impellers
A unique impeller designThe unique design of the Grundfos SuperVorteximpellers provides high pumping efficiency andless downtime. With a flow range from 4 l/s, theGrundfos SuperVortex-impeller pumps are theoptimum solution for all small pumping stations.
Full performance curve withoutoperating limitations and vibrationsDue to the special power characteristics of theGrundfos SuperVortex-impeller pumps, it is possibleto run the pumps right up to the maximum flow on the curves without any risk of overloading themotor. The steep performance curve means minimal flow fluctuation with varying heads.
No clogging or jammingIn a SuperVortex-impeller pump, the flow is en-tirely outside the impeller. The design of the im-peller ensures that long fibres, rags, etc. pass freelythrough the pumps without getting caught andwithout causing clogging or jamming. This meansless downtime and, consequently, reduced servicecosts and higher pumping efficiency.
The design of the SuperVortex-impeller pumpsalso prevents the common problem of jammingbetween wear rings. A Grundfos SuperVortex-impeller pump needs no wear rings!
Conventional vortex impellerIn pumps fitted with a conventional vortex impeller,turbulent disturbance is liable to form around theimpeller. This will disrupt the flow pattern and resultin lower pumping efficiency and reduced head.
Grundfos SuperVortex impellerThe liquid passes freely outside the impellerwithout any turbulent disturbance.
Channel impellers > 9
Efficient impeller design
Non-clogging impeller vane designConventional double-channel impellers are susceptible to clogging, as fibrous material tendsto enter both channels and get caught on theleading edge. But thanks to the recessed leadingedge design of the Grundfos double-channelimpeller, the problem of clogging is virtuallyeliminated.
Tested under real conditions, this special double-channel impeller design combined with a freepassage of minimum 100 mm enable the Grundfosdouble-channel impellers to handle unscreenedsewage in heavy-duty applications. Maximumefficiency is 80-85%.
Large free passage for superior solids handlingCompromising on the ability to handle solids inorder to obtain higher pumping efficiency sub-stantially increases the risk of clogging. Moreclogging means more downtime and increasedoperating costs.
The Grundfos channel-impeller pumps are capableof handling solids up to Ø 145 mm. The full freepassage, however, is much larger. The result isless clogging and less downtime.
Semi-axial long-vane impeller designThe length of an impeller vane is a key factor indetermining the length of fibres that can passthrough a pump without getting caught. TheGrundfos channel-impellers are of semi-axialdesign with extra long vanes. This provides maxi-mum performance and eliminates problems withfibres or rags getting caught in the impeller.
Technical data > 10
Performance overview and type key
Performance overview – Grundfos range of submersible sewage pumps
Type key
Example S1X244A H1 S 1 X 24 4 A H 1 Type rangeGRUNDFOS submersible wastewater pumpsType of impellerV = SuperVortex1 = Single-channel2 = Two-channel3 = Three-channelVersionBlank =Non-explosion-proof, X =Explosion-proof Rated motor power PN in kWNumber of polesPump generationHead classificationE = Extra low head L =Low head M = Medium head H = High head S = Super-high headType of installation1 =Submerged installation on auto-coupling2 =Submerged installation on auto-coupling
Motor cooling is independent of pumped liquid level3 =Vertical dry installation with base stand4 =Submerged installation, portable5 =Submerged installation, portable. Motor
cooling is independent of pumped liquid level.6 =Horizontal dry installation w. base stand and bracket
1 SuperVortex impeller, low and high head, ranges 34, 42, 46 and 50
2 Channel impeller, medium head,
ranges 42, 46, 50, 54, 58 and 62 3 Channel impeller, low head,
ranges 54, 58 and 62 4 Channel impeller, medium head,
ranges 66 and 70 5 Channel impeller, high head,
ranges 46, 50, 54, 58 and 62 6 Channel impeller, high head,
ranges 66 and 70
Area Description
5 10 20 30 40 50 100 200 300 400 500 1000
2
3
4
6
8
10
20
30
40
60
80
H[m]
20 40 60 80 100 200 400 600 800 1000 2000
60 Hz
1 2 3 4
65
1500Q [l/s]
Q [m³/h]3000
Performance > 11
SuperVortex-impeller pumps
Low and high head - ranges 34, 42, 46 and 50
Electrical and technical data
Pump curve
Pump type IS/IN
Submerged installation Submerged installation, portable
Motor 380 V[380/660 V*]
SV 014 BL 34 ø 80 ø 80 60 100 100 75 ø 80 63 2.2 1715 5.8 4.7SV 014 B 34 ø 80 ø 80 60 100 100 75 ø 80 63 2.2 1715 5.8 4.7SV 024 B 34 ø 80 ø 80 60 100 100 75 ø 80 63 2.2 1715 5.8 4.7SV 034 B 34 ø 80 ø 80 60 - - - ø 80 63 3.0 1680 7.5 3.7SV 034 CH 42 ø 80 - - 100 80 110 - - 3.6 1725 10.0 6.0SV 044 CH 42 ø 80 ø 80 100 100 80 100 ø 80 100 4.6(3.6) 1730(1690) 11.9(10) 5(6)SV 052 C 42 ø 80 ø 100 100 - - - ø 100 100 5.2 3460 12 7.7SV 054 CH 42 ø 80 ø 80 100 - - - ø 80 100 4.6 1710 11.9 5SV 074 B* 46 ø 100 ø 100 135 - - - ø 100 135 6.5 1750 16 5.8SV 084 B* 46 ø 100 ø 100 125 - - - ø 100 125 8 1725 18.4 5SV 092 BH* 50 ø 80 ø 80 170 - - - ø 100 170 10.4 3535 23.1 9.8SV 122 BH* 50 ø 80 ø 80 170 - - - ø 100 170 12.5 3515 27 8.4
Dry installation
Pump range
Max. solidssize [mm]
Outlet[mm]
Weight[kg]
Weight[kg]
Hose[mm]
Weight[kg]
nN
[min-1]IN
[A]PN
[kW]InletDN
OutletDNNo.
123456789
101112
() Motor data in brackets apply to installations 2, 3, 5 and 6. *These data concern the 380/660 V types.
0 4 8 12 16 20 24 28 32 36 40 Q [l/s]0
4
8
12
16
20
24
28
32
36
40
44
48
H[m]
0 20 40 60 80 100 120 140
SV60 Hz
ISO 9906 Annex A
1
2
3
4
5
6
7
8
9
10
11
12
Q [m³/h]
Performance >12
Channel-impeller pumps
Medium head - ranges 42, 46, 50, 54, 58 and 62
Electrical and technical data
High head - ranges 46, 50, 54, 58 and 62
Pump curve
Pump type IS/IN
Submerged installation Submerged installation, portable
Motor 380 V[380/660 V]*
S1 034 C 42 ø100 ø100 110 100 100 135 ø100 110 4.6(3.6) 1690(1715) 11.5(9.6) 5(6)S1 044 C 42 ø100 ø100 110 100 100 135 ø100 110 4.6(3.6) 1690(1715) 11.5(9.6) 5(6)S1 054 C 42 ø100 ø100 110 - - - ø100 110 4.6 1690 11.9 5S1 074 AM* 46 ø100 ø100 135 - - - ø100 135 6.5 1750 16 5.8S1 084 AM* 46 ø100 ø100 130 - - - ø100 130 8 1725 18.4 5S1 094 BM* 50 ø100 ø100 180/190** 150 100 190 ø100 190 10 1765 22.4 6.9S1 134 BM* 50 ø100 ø100 190/210** 150 100 190 ø100 190 13.5 1745 22.7 7.5S1 164 M* 54 ø100 ø130 250/270** 150 125 270/320*** ø130 250/270**** 15.5(17.5) 1745(1735) 39(41.2) 4.9(4.6)S1 204 M* 54 ø100 ø130 250/300** 150 125 300/320*** ø130 250/300**** 20(22.5) 1745(1735) 41.2(47.3) 5.8(5)S1 314 AM* 58 ø100 ø125 450,500/540** 200 125 460 ø125 430/460**** 31(32) 1750 63.2(64.3) 5.4(5.3)S1 424 M* 62 ø100 ø125 600/650** 200 125 650/635*** ø125 600/650**** 40(42) 1775(1775) 88.4(92.2) 7.6S1 074 AH* 46 ø80 ø100 140 - - - ø100 140 6.5 1750 16 5.8S1 084 AH* 46 ø80 ø100 130 - - - ø100 130 8 1730 18.4 5S1 094 AH* 50 ø80 ø100 160/200** 100 100 200/210*** ø100 160/200**** 10 1765 22.4 6.9S1 114 AH* 50 ø80 ø100 160/200** 100 100 200 ø100 160/200**** 11 1760 23.6 7.5S1 134 AH* 50 ø80 ø100 200/235** 100 100 235 ø100 200/235**** 13.5 1745 27.7 7.5S1 164 H* 54 ø80 ø100 250/285** 150 100 285 ø100 250/285**** 15.5(17.5) 1740 39(41.2) 4.9(4.6)S1 204 H* 54 ø80 ø100 280/315** 150 100 315 ø100 280/315**** 20(22.5) 1745(1735) 43.7(47.3) 5.8(5)S1 244 H* 58 ø80 ø125 400/430** 150 125 470 ø125 435 25( 28) 1760(1750) 50.6(56.3) 6.8(6.1)S1 314 H* 58 ø80 ø125 400/430** 150 125 460/490*** ø125 420/430**** 31 1735 64.5 5.3S1 424 H* 62 ø80 ø125 580/615** 150 125 670/635*** ø125 640/670**** 40(42) 1770(1775) 82.3(92.2) 5.9(7.6)S1 524 H* 62 ø80 ø125 570/610** 150 125 650/635*** ø125 600/610**** 48(52) 1765(1760) 1025(110.2) 6.4(6.2)
Dry installation
Pump range
Max. solidssize [mm]
Outlet[mm]
Weight[kg]
Weight[kg]
Hose[mm]
Weight[kg]
nN
[min-1]IN
[A]PN
[kW]InletDN
OutletDN
() Motor data in brackets apply to installations 2, 3, 5 and 6.
* These data concern the 380/660 V types. *** installation type 3/installation type 6
** installation type 1/installation type 2 **** installation type 4/installation type 5
No.
123456789
10111213141516171819202122
0 10 20 30 40 50 60 70 80 90 100 110 Q [l/s]0
5
10
15
20
25
30
35
40
45
50
55
60
65
H[m ]
0 50 100 150 200 250 300 350 400 Q [m³/h]
S160 Hz
ISO 9906 Annex A
22
21
19
20
16
18
15
17
1413
12
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 Q [l/s]0
4
8
12
16
20
24
28
32
36
40
44
48
52
H[m]
0 50 100 150 200 250 300 350 400 450 500 Q [m³/h]
S160 Hz
ISO 9906 Annex A
1
2
34
56
7
8
9
10
11
Performance > 13
Low head - ranges 54, 58 and 62
Electrical and technical data
Medium head - ranges 66 and 70
Pump curve
Pump type IS/IN
Submerged installation Submerged installation, portable
Motor380/660 V
S1 164 AL 54 ø100 ø200 355/370* 200 200 370/390** ø200 355/370*** 15.5(17.5) 1750(1740) 39(41.2) 4.9(4.6)S1 204 AL 54 ø100 ø200 355/390* 200 200 390 ø200 355/390*** 20(22.5) 1745(1735) 41.2(47.3) 5.8(5)S1 314 L 58 ø115 ø200 490/550* 250 200 550 ø200 490/550*** 31(32) 1735 63.3(64.5) 5.4(5.3)S2 314 AL 58 ø100 ø200 470/510* 250 200 510 ø200 470/510*** 31(32) 1735 63.3(64.5) 5.4(5.3)S2 424 AL 62 ø100 ø200 655/650* 250 200 650 ø200 600/650*** 40(42) 1775(1775) 94.4(92.2) 7.6S2 524 AL 62 ø100 ø200 615/655* 250 200 655/695** ø200 615/655*** 48(52) 1765(1760) 102.5(110.5) 6.4(6.2)S2 328 M 66 ø 145 ø 300 810/915* - - - - - 32 875 72.6 6.5S2 408 M 66 ø 145 ø 300 810/915* - - - - - 41 875 90.2 5.4S2 578 M 66 ø 145 ø 300 950 - - - - - 57 875 118.6 5.6S2 578 H 66 ø 120 ø 250 950 - - - - - 57 875 118.6 5.6S3 578 L 70 ø 115 ø 500 1300 - - - - - 57 875 118.6 5.6S3 808 L 70 ø 115 ø 500 1500/1590* - - - - - 80 880 155.8 6.7S3 808 M 70 ø 120 ø 300 1370/1520* - - - - - 80 880 155.8 6.7S2 808 H 70 ø 120 ø 250 1200 - - - - - 80 880 155.8 6.7S2 1106 M 70 ø 145 ø 300 1240/1270* - - - - - 110 1180 213.1 7.3S2 1106 H 70 ø 120 ø 250 1240/1270* - - - - - 110 1180 213.1 7.3S3 1406 L 70 ø 115 ø 500 1700/1830* - - - - - 140 1185 276 8.7S3 1406 M 70 ø 120 ø 300 1390/1520* - - - - - 140 1185 276 8.7S2 1406 H 70 ø 120 ø 250 1300/1320* - - - - - 140 1185 276 8.7
Dry installation
Pump range
Max. solidssize [mm]
Outlet[mm]
Weight[kg]
Weight[kg]
Hose[mm]
Weight[kg]
nN
[min-1]IN
[A]PN
[kW]InletDN
OutletDN
() Motor data in brackets apply to installations 2, 3, 5 and 6.
* installation type 1/installation type 2
** installation type 3/installation type 6
*** installation type 4/installation type 5
No.
123456789
10111213141516171819
0 100 200 300 400 500 600 700 800 900 Q [l/s]0
5
10
15
20
25
30
35
40
45
50
H[m]
0 500 1000 1500 2000 2500 3000 Q [m³/h]
S2, S360 Hz
ISO 9906 Annex A
17
16
15
13
14
7
8
9
10
11
12
19
18
0 20 40 60 80 100 120 140 160 180 200220 240260280300 Q [l/s]0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
H[m ]
0 100 200 300 400 500 600 700 800 900 1000 Q [m³/h]
S1, S260 Hz
ISO 9906 Annex A
1
2
3
4
5
6
14
Channel-impeller pumps
Technical data >
0 20 40 60 80100120140160180200220240260280300320340360Q [l/s]0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
H[m]
0 100 200 300 400 500 600 700 800 900 1000 11001200 Q [m³/h]
S1, S260 Hz
ISO 9906 Annex A
5
6
3
4
1
2
Electrical and technical data
High head - ranges 66 and 70
Pump curve
Pump type IS/IN
Submerged installation Submerged installation, portable
Motor 380/660 V
S2 704 AM 66 ø100 ø200 900/990* - - - - - 73 1775 146.5 6.9S1 704 H 66 ø100 ø200 800/830* - - - - - - - - -S2 1004 AM 70 ø100 ø200 1100/1210* - - - - - 95 1780 178.1 7.5S2 1004 H 70 ø90 ø200 1100/1200* - - - - - 95 1780 178.1 7.5S2 1204 AM 70 ø100 ø200 1100/1210* - - - - - 120 1770 221.5 7.5S2 1204 H 70 ø90 ø200 1030/1320* - - - - - 120 1770 221.5 7.5
Dry installation
Pump range
Max. solidssize [mm]
Outlet[mm]
Weight[kg]
Weight[kg]
Hose[mm]
Weight[kg]
nN
[min-1]IN
[A]PN
[kW]InletDN
OutletDN
() Motor data in brackets apply to installations 2, 3, 5 and 6. * Installation type 1/installation type 2
No.
123456
Stator housing Cast iron EN-JL1040Pump housing Cast iron EN-JL1040Impeller Impeller cast iron/ductile iron EN-JL1040/EN-JS1050Pump shaft, pump ranges 34 to 62 Stainless steel 1.4460 329Pump shaft, pump ranges 66 and 70* Steel 1.7225Bolts and nuts Stainless steel 1.4436 316Cooling jacket, pump ranges 50 to 62 Ductile iron EN-JS1050 80-55-06Cooling jacket, pump ranges 66 and 70 Hot dip galvanized steel Rst 37-2O-rings NBRO-rings, mechanical shaft seal FKMBearings Heavy-duty prelubricated ball or roller bearingsPrimary shaft seal SiC/SiCSecondary shaft seal SiC/carbonLifting bracket, pump ranges 34 to 46 Cast stainless steel 1.4408 316Lifting bracket, pump ranges 50 to 54 Ductile iron EN-JS1050 80-55-06Lifting bracket, pump range 58 Galvanized steel Rst 37-2Cables EPDMCable entry PA/cast ironSurface protection 150 my two-component epoxy coatingOil SAE 10 W 30
* Shaft is not in contact with pumped liquid.
Part Material DIN/EN AISI
Material specifications
Technical data >15
Submerged installation on auto-coupling (types 1 and 2)
SuperVortex-impeller pumps
DN A B C D E F G H K L M N O ØP ØR ØS ØT U V X Y ØZ
Pump range/type
34SV 014 BL 80/100 640 555 85 455 270 130 150 130 99 160 184 206 60 180SV 014 B 80/100 640 555 85 455 270 130 150 130 99 160 184 206 60 180SV 024 B 80/100 640 555 85 455 270 130 150 130 99 160 184 206 60 180SV 034 B 80/100 640 555 85 455 270 130 150 130 99 160 184 206 60 18042SV 034 CH 80/100 695 615 80 475 270 155 155 155 99 160 184 206 60 180SV 044 CH 80/100 695 615 80 475 270 155 155 155 99 160 184 206 60 180SV 052 C 100/80 795 615 180 520 310 150 150 150 120 260 180 220 60 180SV 054 CH 80/100 695 615 80 475 270 155 155 155 99 160 184 206 60 180 46SV 074 B 100/80 775 645 130 560 330 170 175 220 120 260 180 220 60 180SV 084 B 100/80 775 645 130 560 330 170 175 220 120 260 180 220 60 180 50 SV 092 BH 100/80 965 805 100 705 465 180 180 190 120 260 180 220 60 180SV 122 BH 100/80 965 805 100 705 465 180 180 190 120 260 180 220 60 180
Sizes DN 80/100 or DN 100/80 means that it is possible to fit either a DN 80 or a DN 100 flange on the discharge side of the baseplate.The only difference is the pump connection, which is either 80 mm or 100 mm.
220 18 20 123 167 65 80 48220 18 20 123 167 65 80 48220 18 20 123 167 65 80 48220 18 20 123 167 65 80 48
220 18 20 123 167 65 80 48220 18 20 123 167 65 80 48220 18 20 205 180 121 180 48220 18 20 123 167 65 80 48
220 18 20 205 180 121 180 48220 18 20 205 180 121 180 48
220 18 20 205 180 121 180 48220 18 20 205 180 121 180 48
Dimensions [mm]
Dimensions and installation
Technical data >16
Dimensions and installation
Channel-impeller pumps
DN A B C D E F G H K L M N O ØP ØR ØS ØT U V X Y ØZ
Pump range/type
42S1 034 C 100/80 770 670 100 545 320 165 175 160 120 260 180 220 60 180 S1 044 C 100/80 770 670 100 545 320 165 175 160 120 260 180 220 60 180S1 054 C 100/80 770 670 100 545 320 165 175 160 120 260 180 220 60 18046S1 074 AM 100 775 675 100 590 360 170 190 220 120 260 180 220 60 180S1 084 AM 100 775 675 100 590 360 170 190 220 120 260 180 220 60 180S1 074 AH 100 770 655 115 575 340 175 185 220 120 260 180 220 60 180S1 084 AH 100 770 655 115 575 340 175 185 220 120 260 180 220 60 18050S1 094 AL 150 1120 915 205 730 455 210 240 190 250 380 280 500 100 240S1 134 AL 150 1120 915 205 730 455 210 240 190 250 380 280 500 100 240S1 094 BM 100 1035 935 100 610 375 180 190 190 120 260 180 220 60 180S1 134 BM 100 1035 935 100 610 375 180 190 190 120 260 180 220 60 180S1 114 AH 100 1000 890 100 585 350 180 185 190 120 260 180 220 60 180S1 134 AH 100 1000 890 100 585 350 180 185 190 120 260 180 220 60 180S1 094 AH 100 1000 890 100 585 350 180 185 190 120 260 180 220 60 180 54S1 164 AL 200 1215 1020 195 930 590 265 315 235 300 400 540 600 150 295S1 204 M 150 1180 995 185 715 432 215 235 210 250 380 280 500 100 240S1 164 M 150 1180 995 185 715 432 215 235 210 250 380 280 500 100 240S1 164 H 100 1050 960 90 670 390 215 230 210 200 260 325 375 75 180 S1 204 H 100 1050 960 90 670 390 215 230 210 200 260 325 375 75 180S1 204 AL 200 1215 1020 195 930 590 265 315 235 300 400 540 600 150 29558S1 314 AM 150 1365 1210 155 780 475 235 235 235 250 380 280 500 100 240S1 244 H 150 1355 1175 180 785 492 225 240 215 250 380 280 500 100 240S1 314 H 150 1355 1175 180 785 492 225 240 215 250 380 280 500 100 240S1 314 L 200 1410 1225 185 1005 640 290 345 265 250 400 540 600 150 295S2 314 AL 200 1410 1195 215 1010 640 290 345 265 250 400 540 600 100 28562S1 424 H 150 1540 1390 150 830 512 250 260 250 250 380 280 500 100 240S1 424 M 150 1555 1420 135 830 512 250 260 250 250 380 280 500 100 240S1 524 H 150 1540 1390 150 830 512 250 260 250 250 380 280 500 100 240S2 424 AL 200 1585 1425 160 1130 750 300 360 275 300 400 540 600 150 295S2 524 AL 200 1585 1425 160 1130 750 300 360 275 300 400 540 600 150 29566S1 704 H 200 1675 1495 180 1050 690 285 305 290 300 400 540 600 150 295S2 328 M 300 1715 1540 175 1310 790 440 525 355 400 400 620 700 150 400S2 408 M 300 1715 1540 175 1310 790 440 525 355 400 400 620 700 150 400S2 578 H 250 1700 1535 165 1365 840 445 480 400 350 400 620 700 150 350S2 578 M 300 1915 1765 150 1310 790 440 525 355 400 400 620 700 150 400S2 704 AM 200 1670 1485 185 975 550 350 380 320 300 400 540 600 150 295
220 18 20 205 180 121 180 48220 18 20 205 180 121 180 48220 18 20 205 180 121 180 48
220 18 20 205 180 121 180 48220 18 20 205 180 121 180 48220 18 20 205 180 121 180 48220 18 20 205 180 121 180 48
285 22 24 320 265 115 165 77285 22 24 320 265 115 165 77220 18 20 205 180 121 180 48220 18 20 205 180 121 180 48220 18 20 205 180 121 180 48220 18 20 205 180 121 180 48220 18 20 205 180 121 180 48
340 22 28 460 320 140 20 88285 22 24 320 265 115 165 77285 22 24 320 265 115 165 77220 18 24 230 223 80 80 60220 18 24 230 223 80 80 60340 22 28 460 320 140 20 88
285 22 24 320 265 115 165 77285 22 24 320 265 115 165 77285 22 24 320 265 115 165 77340 22 28 460 320 70 20 88285 22 28 460 265 140 20 88
285 22 24 320 265 115 165 77285 22 24 320 320 115 165 77285 22 24 320 265 115 165 77340 22 28 460 320 140 20 88340 22 28 460 320 140 20 88
340 22 28 460 320 140 20 88445 23 28 500 420 205 270 88445 23 28 500 420 205 270 88395 23 28 500 370 205 270 88445 23 28 500 420 205 270 88340 22 28 460 320 70 20 88
Dimensions [mm]
70S2 1004 H 200 1785 1610 175 955 590 285 285 285 300 400 540 600 150 295S2 1004 AM 200 1800 1615 185 975 550 350 380 320 300 400 540 600 150 295S2 1106 H 250 1830 1665 165 1365 840 445 480 400 350 400 620 700 150 350S2 1106 M 300 2040 1890 150 1310 790 440 525 355 400 400 620 700 150 400S2 1204 H 200 1785 1610 175 1155 790 285 285 285 300 400 540 600 150 295S2 1204 AM 200 1815 1615 200 1005 640 285 320 290 300 400 540 600 150 295S2 1406 H 250 1985 1820 165 1365 840 445 480 400 350 400 620 700 150 350S2 808 H 250 1830 1665 165 1365 840 445 480 400 350 400 620 700 150 350S3 578 L 500 2000 1680 320 2085 1305 630 715 550 600 700 900 1000 250 620S3 1406 L 500 2130 1810 320 2085 1305 630 715 550 600 700 900 1000 250 620S3 1406 M 300 2040 1890 150 1310 790 440 525 355 400 400 620 700 150 400S3 808 L 500 2130 1810 320 2085 1305 630 715 550 600 700 900 1000 250 620S3 808 M 300 2035 1890 145 1310 790 440 525 355 400 400 620 700 150 400
340 22 28 460 320 70 20 88340 22 28 460 320 70 20 88395 23 28 500 575 205 30 88445 23 28 500 420 205 270 88340 22 28 460 390 70 20 88340 22 28 460 320 70 20 88395 23 28 500 370 206 270 88395 23 28 500 575 205 30 88670 27 28 800 655 75 30 88670 27 28 800 655 75 30 88445 23 28 500 420 205 270 88670 27 28 800 655 75 30 88445 23 28 500 420 205 270 88
17 Technical data >
SuperVortex-impeller pumps
DN1 DN2 A B C D E F G H ØJ ØK ØL ØM ØN ØP
Pump range/type
34 SV 014 BL 100 100 1025 545 425 347 217 255 270 30˚ M16 180 225 180 24SV 014 B 100 100 1025 545 425 347 217 255 270 30˚ M16 180 225 180 24 SV 024 B 100 100 1025 545 425 347 217 255 270 30˚ M16 180 225 180 24 42 SV 034 CH 100 100 1055 525 425 372 217 320 270 30˚ M16 180 225 180 24 SV 044 CH 100 100 1055 525 425 372 217 320 270 30˚ M16 180 225 180 24
Dimensions [mm]
191919
1919
Vertical dry installation (type 3)
Technical data >18
Dimensions and installation
DN1 DN2 A B C D E F G H ØJ ØK ØL ØM ØN ØPPump range/type
42 S1 034 C 100 100 1095 600 425 425 257 335 270 30 M16 180 220 180 24S1 044 C 100 100 1095 600 425 425 257 335 270 30 M16 180 220 180 2450 S1 094 AL 150 125 1570 815 600 590 380 435 300 30 M20 280 250 210 24S1 134 AL 150 125 1570 815 600 590 380 435 300 30 M20 280 250 210 24S1 094 BM 150 100 1575 805 600 492 312 380 300 30 M20 240 250 180 24S1 134 BM 150 100 1575 805 600 492 312 380 300 30 M20 240 250 180 24S1 114 AH 100 100 1365 625 425 465 285 375 270 30 M20 180 220 180 24S1 134 AH 100 100 1365 625 425 465 285 375 270 30 M20 180 220 180 24S1 094 AH 100 100 1365 625 425 465 285 375 270 30 M20 180 220 180 2454 S1 164 AL 200 200 1735 920 700 765 500 550 350 30 M20 295 - 295 24S1 204 M 150 125 1645 840 600 575 360 445 300 30 M20 240 250 210 24S1 164 M 150 125 1645 840 600 575 360 445 300 30 M20 240 250 210 24S1 164 H 150 100 1610 815 600 570 355 440 300 30 M20 240 250 180 24S1 204 H 150 100 1610 815 600 570 355 440 300 30 M20 240 250 180 24S1 204 AL 200 200 1735 920 700 765 500 550 350 30 M20 295 - 295 2458 S1 314 AM 200 125 1962 980 697 635 400 470 350 30 M20 295 250 210 24S1 244 H 150 125 1830 830 600 655 420 470 300 30 M20 240 250 210 24S1 314 H 150 125 1830 830 600 655 420 470 300 30 M20 240 250 210 24S1 314 L 250 200 2075 1065 825 840 550 610 400 30 M20 350 - 295 28S2 314 AL 250 200 2120 1110 825 840 550 605 400 30 M20 350 - 295 2862 S1 424 H 150 125 2055 895 600 690 440 513 300 30 M20 240 250 210 24S1 424 M 200 125 2140 968 697 690 440 552 350 30 M20 295 250 210 24S1 524 H 150 125 2055 895 600 690 440 513 300 30 M20 240 250 210 24S2 424 AL 250 200 2305 1120 825 960 660 670 400 30 M20 350 340 295 28S2 524 AL 250 200 2305 1120 825 960 660 670 400 30 M20 350 340 295 28
Dimensions [mm]
1919
19191919191919
241919191924
191919 2424
1919192424
0
0
66 S1 704 H 250 200 2355 1075 825 890 600 595 400 30 M20 350 - 295 28S2 328 M 300 300 2805 1490 1152 1140 700 880 630 30 M24 515 - 400 28S2 408 M 300 300 2805 1490 1152 1140 700 880 630 30 M24 515 - 400 28S2 578 H 300 250 2410 1110 855 1190 750 870 450 30 M20 400 - 350 28S2 578 M 300 300 2805 1490 1152 1140 700 880 630 30 M24 515 - 400 28S2 704 AM 250 300 2345 1072 828 810 460 700 400 30 M20 350 340 295 2870 S2 1004 H 250 200 2470 1080 825 785 500 570 400 30 M20 350 - 295 28S2 1004 AM 250 200 2470 1072 828 810 460 700 400 30 M20 350 340 295 28S2 1106 H 300 250 2540 1110 855 1190 750 870 450 30 M20 400 - 350 28S2 1106 M 300 300 2930 1490 1152 1275 760 1015 630 30 M24 515 - 400 28S2 1204 H 250 200 2470 1080 825 785 500 570 400 30 M20 350 - 295 28S2 1204 AM 250 200 2470 1072 828 810 460 700 400 30 M20 350 340 295 28S2 1406 H 300 250 2695 1110 855 1190 750 870 450 30 M20 400 - 350 28S2 808 H 300 250 2540 1110 855 1190 750 870 450 30 M20 400 - 350 28S3 1406 M 400 300 3085 1490 1152 1140 700 880 630 30 M24 515 470 400 28S3 808 M 400 300 2930 1490 1152 1140 700 880 630 30 M24 515 470 400 28
242424242424
24242424242424242424
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Channel-impeller pumps
19 Technical data >
Vertical dry installation, concrete foundation
DN1 DN2 A B C D E F G H K L M N ØOPump range/type
S3 578 L 500 500 1300 461 495 1845 1200 1270 550 620 1100 1180 700 300 28S3 1406 L 500 500 1580 461 495 1830 1200 1270 550 620 1100 1180 700 300 28S3 808 L 500 500 1425 461 495 1830 1200 1270 550 620 1100 1180 700 300 28
Dimensions [mm]
Channel-impeller pumps
Technical data >20
DN A B C D E F G H Pump range/type
34 SV 014 BL 80 640 305 490 150 125 305 305 160SV 014 B 80 640 305 490 150 125 305 305 160SV 024 B 80 640 305 490 150 125 305 305 160SV 034 B 80 640 305 490 150 125 305 305 16042 SV 044 CH 80 725 305 490 155 155 310 355 195SV 052 C 100 725 305 545 150 150 300 335 190SV 054 CH 80 725 305 490 155 155 310 355 19546 SV 074 B 100 755 305 580 175 220 395 385 240SV 084 B 100 755 305 580 175 220 395 385 24050 SV 092 BH 100 930 350 555 180 180 370 460 290SV 122 BH 100 930 350 555 180 180 370 460 290
Dimensions [mm]
Dimensions and installation
Submerged installation, portable (types 4 and 5)
SuperVortex-impeller pumps
Technical data > 21
Channel-impeller pumps
DN A B C D E F G H Pump range/type
42 S1 034 C 100 765 305 570 175 160 335 415 270S1 044 C 100 765 305 570 175 160 335 415 270S1 054 C 100 765 305 570 175 160 335 415 27046 S1 074 AM 100 775 305 610 190 220 410 415 270S1 084 AM 100 775 305 610 190 220 410 415 270S1 074 AH 100 745 305 600 185 220 405 380 235S1 084 AH 100 745 305 600 185 220 405 380 23550 S1 094 AL 150 1065 350 870 240 190 430 590 310S1 134 AL 150 1065 350 870 240 190 430 590 310S1 094 BM 100 1080 350 640 190 190 380 450 305S1 134 BM 100 1080 350 640 190 190 380 450 305S1 114 AH 100 1020 350 615 185 190 375 435 290S1 134 AH 100 1020 350 615 185 190 375 435 290S1 094 AH 100 1020 350 615 185 190 375 435 29054 S1 164 AL 200 1125 550 1200 315 235 590 750 315S1 204 M 150 1105 550 915 235 210 550 585 305S1 164 M 150 1105 550 915 235 210 550 585 305S1 164 H 100 1070 550 775 230 210 550 550 280S1 204 H 100 1070 550 775 230 210 550 550 280S1 204 AL 200 1125 550 1200 315 235 590 750 31558 S1 314 AM 150 1345 550 955 235 235 470 640 360S1 244 H 150 1315 550 975 240 215 550 620 340S1 314 H 150 1315 550 975 240 215 550 620 340S1 314 L 200 1390 550 1265 345 275 620 815 380S2 314 AL 200 1390 550 1265 345 275 620 815 38062 S1 424 H 150 1530 700 1070 260 250 510 650 370S1 424 M 150 1540 700 1070 260 250 510 645 365S1 524 H 150 1530 700 1070 260 250 510 650 370S2 424 AL 200 1555 700 1435 360 350 710 805 370S2 524 AL 200 1555 700 1435 360 350 7 10 805 370
Dimensions [mm]
Technical data >22
Dimensions and installation
DN1 DN2 A B C D E F G H ØL M O P Q RPump range/type
34 SV 014 BL 100 100 600 260 - 417 217 - - 118 20 - - 200 190SV 014 B 100 100 600 260 - 417 217 - - 118 20 - - 200 190SV 024 B 100 100 600 260 - 417 217 - - 118 20 - - 200 19042SV 034 CH 100 100 635 250 - 437 217 - - 102 20 150 57 220 230SV 044 CH 100 100 635 250 - 437 217 - - 102 20 150 57 220 230
Dimensions [mm]
250250250
300300
SuperVortex-impeller pumps
Horizontal dry installation (type 6)
23 Technical data >
DN1 DN2 A B C D E F G H K ØL M N O PPump range/type
42 S1 034 C 100 100 695 250 - 477 257 335 175 175 - 20 150 - 60S1 044 C 100 100 695 250 - 477 257 335 175 175 - 20 150 - 6050 S1 094 AL 150 125 955 - - 680 380 435 - 200 - 18 500 - 130S1 134 AL 150 125 955 - - 680 380 435 - 200 - 18 500 - 130S1 094 BM 150 100 970 - - 612 312 380 - 175 - 20 500 - 115S1 134 BM 150 100 970 - - 612 312 380 - 175 - 20 500 - 115S1 114 AH 100 100 935 - - 585 285 375 - 195 - 18 500 - 115S1 134 AH 100 100 935 - - 585 285 375 - 195 - 18 500 - 115S1 094 AH 100 100 935 - - 585 285 375 - 195 - 18 500 - 11554 S1 164 AL 200 200 1100 - - 875 500 550 - 220 - 18 500 - 115S1 204 M 150 125 1020 - - 735 360 445 235 220 - - 500 - 100S1 164 M 150 125 1020 - - 735 360 445 235 220 - - 500 - 100S1 164 H 150 100 1010 - - 730 355 440 - 213 - 18 500 - 115S1 204 H 150 100 1010 - - 730 355 440 - 213 - 18 500 - 115S1 204 AL 200 200 1100 - - 875 500 550 - 220 - 18 500 - 11558 S1 314 AM 200 125 1262 815 - 775 400 536 268 280 - 18 500 - 115S1 244 H 150 125 1223 815 - 795 420 450 - 250 - 18 500 - 115S1 314 H 150 125 1223 815 - 795 420 450 - 250 - 18 500 - 115S1 314 L 250 200 1273 1015 - 925 550 670 - 267 - 18 500 - 115S2 314 AL 250 200 1273 1015 - 925 550 670 - 267 - 18 500 - 11562 S1 424 H 150 125 1450 815 - 815 440 510 - 290 - 18 500 - 115S1 424 M 200 125 1440 820 - 815 440 510 260 265 - 20 500 - 115S1 524 H 200 125 1440 815 - 815 440 550 - 267 - 18 500 - 115S2 424 AL 250 200 1465 1015 - 1035 660 670 - 280 - 18 500 - 115S2 524 AL 250 200 1465 1015 - 1035 660 670 - 280 - 18 500 - 115
220 230 300220 230 300 300 390 -300 390 -300 390 450300 390 450300 390 450300 390 450300 390 450 375 390 -375 390 -375 390 -375 390 -375 390 -375 390 - 375 390 450375 390 450375 390 450375 390 450375 390 450 375 390 -375 390 -375 390 -375 390 -375 390 -
Dimensions [mm]
Q R
Channel-impeller pumps
<-
<-
<-
Prope for seal condition monitoring Cable length 10 m 96476770The OCT monitoring probe is inserted in the oil OCT3460020 Cable length 20 m 96476771chamber. It ensures that any seal leakage is registered Cable length 30 m 96476772immediately. The OCT probe is available for the pump ranges 50, 54 and 58
OCT3460030
OCT3460010
Description
Pumpoutlet[mm]
Pumprange
ProductnumberBase plate discharge flange PN10
Auto-coupling
Cast iron base plate incl. bend.
Auto-coupling
Steel base plate excl. bend, incl. galvanized bolts and gaskets.*200 mm higher than product number 96066479
Cast iron bend, 90
PN 10.
Guide bar bracket
Upper holder in stainless steel for twin guide rails.
80 54 • 96066496
100 54 • 96066472
150 46 • 96066467
200 46 • 96066482
250 46 • 96066493
300 • 96066479
300* • 96066478
500 • 96065432
600 • 96066503
DN
80/80 96060928
80/100 96060929
100/100 96060930
100/150 96060931
150/150 96060934
150/200 96060935
200/200 96060938
200/300 96060940
250/250 96060942
250/300 96060943
250/350 96060944
300/300 96060946
300/400 96060947
400/500 96060950
500/500 96060951
600/600 96060952
80/100 50 • • 96067990
80/100 54 • • 96067992
150 • 96457261
200 • 96067996
250 • 96067999
300 • 96067999
500 • 96068001
600 • 96459313
80 50 • • 96066506
100 50 • • 96066511
100 54 • 96066471
150 • 96066466
200 • 96066481
>-
>->->->->-
DN
80
DN
100
DN
150
DN
200
DN
250
DN
300
DN
500
DN
60
0
>-
Non-return valve
Cast iron ball-type, PN 10.
DN80 96060975
DN100 96060973
DN150 96060976
DN200 96060977
DN250 96004421
DN300 96004422
Additional informationType
Automatic water in oil and motor insulation resistance check
The SARI 2 monitors the motor insulation resistance as well as the water content in the oil chamber between the two mechanical shaft seals. In case of deterioration of the motor insulation, the SARI 2 will provide an early warning, allowing for the necessary prevenative main-tenance before any motor damage occurs.
SARI 2 96061602All ranges
0
Accessories >24
Accessories
Accessories > 25
Accessories
Controller type, electrical data and product numbers
LC 107 controller, pneumatic versionwith level bells and tube for 1 pump 3 x 400 V, direct-on-line starting.
LCD 107 controller, pneumatic versionwith level bells and tube for 2 pumps 3 x 400 V, direct-on-line starting.
LC 108 controller for float switches for 1 pump 3 x 400 V, direct-on-line starting.
LC 108 controller for float switches for 1 pump 3 x 400 V, star-deltastarting.
LCD 108 controller for float switches for 2 pumps 3 x 400 V, direct-on-line starting.
LCD 108 controller for float switches for 2 pumps 3 x 400 V, star-deltastarting.
Description
Product numberOperating
currentper pump
[A]
Mainsswitch
required[A]
Grundfosproduct no.
1.0 - 2.9 25 96 00 24 671.6 - 5.0 25 96 00 24 68 3.7 - 12.0 25 96 00 24 69 12.0 - 23.0 40 96 00 24 70 1.0 - 2.9 25 96 00 24 74 1.6 - 5.0 25 96 00 24 753.7 - 12.0 25 96 00 24 7612.0 - 23.0 40 96 00 24 77
Level controller
* * ** * ** * ** * *
* * ** * ** * ** * *
1.0 - 2.9 25 96 43 39 91 96 43 39 92 96 43 39 93 96 43 39 941.6 - 5.0 25 96 43 39 95 96 43 39 96 96 43 39 97 96 43 39 98 3.7 - 12.0 25 96 43 39 99 96 43 40 00 96 43 40 01 96 43 40 02 12.0 - 23.0 40 96 43 40 03 96 43 40 04 96 43 40 05 96 43 40 066.4 - 20.0 25 96 43 79 28 * * *20.8 - 30.0 40 96 43 79 50 * * *20.8 - 59.0 80 96 43 79 70 * * *24.2 - 72.0 96 43 79 90 * * *1.0 - 2.9 25 96 43 40 39 96 43 40 40 96 43 40 41 96 43 40 421.6 - 5.0 25 96 43 40 43 96 43 40 44 96 43 40 45 96 43 40 46 3.7 - 12.0 25 96 43 40 47 96 43 40 48 96 43 40 49 96 43 40 50 12.0 - 23.0 40 96 43 40 51 96 43 40 52 96 43 40 53 96 43 40 546.4 - 20.0 25 96 43 80 32 * * * 20.8 - 30.0 40 96 43 80 52 * * *20.8 - 59.0 80 96 43 80 72 * * *24.2 - 72.0 96 43 80 92 * * ***
**
WithHour counter
WithStart counter
WithCombined hour and
start counter
* Has to be bought separately. Please see Accessories on page 26.** Depends on local standards.
Float switch with 10 m cable 96003332Float switch with 20 m cable 96003695Float switch with 10 m cable (for explosion-proof version) 96003421Float switch with 20 m cable (for explosion-proof version) 96003536Bracket for two float switches 96003338
ProductnumberDescription
Lifting chainGalvanized lifting chain with lifting linkand safety hook, length 6 m.
Type Pump range
Max. load 1100 kg 96468285Max. load 2000 kg 96468290Max. load 3200 kg 96468295Max. load 8000 kg 96468300
Alarm status monitoring
The ASM 3 alarm status module is designed for moni-toring motor temperature and possible moisture leaks in submersible pump motors. The ASM 3 decodes the internal protection circuit P1-P2 of the pump in such a way that the thermal alarm and moisture alarm, which are normally connected in series, can be separated. The ASM 3 registers the status of the internal protection circuit of the pump. The pump must be prepared for ASM 3.
ASM3 110 V All ranges 96060434
ASM3 230 V All ranges 96069934
(Cont. next page).
Accessories > 26
Accessories
LC 110 controller for elec-trodes for 1 pump 3 x 400 V, direct-on-line starting.
LCD 110 controller for elec-trodes for 2 pumps 3 x 400 V, direct-on-line starting.
Description
Operatingcurrent
per pump [A]
Mainsswitch
required[A]
Withhour counter
Grundfosproduct no.
Withbattery
Withcombined hour and
start counter
1.0 - 2.9 25 96 48 41 01 96 48 37 07 96 48 37 23 96 48 37 62 96 48 37 78 96 48 37 951.6 - 5.0 25 96 48 41 02 96 48 37 08 96 48 37 24 96 48 36 63 96 48 37 79 96 48 37 963.7 - 12.0 25 96 48 41 03 96 48 37 09 96 48 37 25 96 48 37 64 96 48 37 80 96 48 37 9712.0 - 23.0 40 96 48 41 04 96 48 37 10 96 48 37 26 96 48 37 65 96 4837 82 96 48 37 98 1.0 - 2.9 25 96 48 41 09 96 48 37 15 96 48 37 31 96 48 37 70 96 48 37 87 96 48 38 131.6 - 5.0 25 96 48 41 10 96 48 37 16 96 48 37 32 96 48 36 71 96 48 37 88 96 48 38 143.7 - 12.0 25 96 48 41 11 96 48 37 17 96 48 37 33 96 48 37 72 96 48 37 89 96 48 38 1512.0 - 23.0 40 96 48 41 12 96 48 37 18 96 48 37 34 96 48 37 73 96 48 37 90 96 48 38 16
Level controller
Withhour counterand battery
Withcombined hour and
start counterand battery
Product number
DescriptionProductnumber
Picture
Accessories for LC/LCD 110
1 electrode with 10 m cable 96 07 62 89
3 electrodes with 10 m cable 96 07 61 89
4 electrodes with 10 m cable 91 71 34 37
Bracket for electrodes 91 71 31 96
Accessories
Picture Description
Productnumber
9.6 V 96 00 25 20
400 V 96 00 25 15
Battery back-up
Hour counter
External mains switch for supply cable
400 V 96 00 25 17
400 V 96 00 25 19
25 A 96 00 25 11
40 A 96 00 25 12
80 A 96 00 25 13
96 44 03 00
Start counter
Combined hour and start counter
LC-Ex4 safe barrier, for use in potentially explosive enviroments, for float switch applications, for use with the above mentioned float switches
The range >27
The Grundfos wastewater rangeBrochures available (50 Hz)
Stainless steel heavy-dutysubmersible pumps
Brochure covers the Grundfosrange of heavy-duty stainless
steel pumps (SEN) for aggressiveand corrosive environments.
Submersible sewagegrinder pumps
Brochure covers the newGrundfos range of sewage grinder
pumps (SEG) for pumping ofwastewater with toilet discharge.
Heavy-duty submersiblesewage pumps 1.65 - 29 kWBrochure covers the Grundfos range
of submersible channel-impellerpumps from 1.65 kW up to 21 kW
and SuperVortex pumps up to 29 kW. All designed for handling
unscreened raw sewage.
Portable dewatering pumps
Brochure covers the Grundfos rangeof portable dewatering pumps (DW)from 0.8 kW to 20 kW for pumping
raw water with abrasives.
Lifting stationsBrochure covers Grundfos lifting stations for individual as well as multi-user applications.
LC/LCD level controllersBrochure covers the Grundfosrange of controls for the waste-water pumping systems.
Mixers and flowmakersBrochure covers the new range
of mixers and flowmakers foroptimal control of liquids and solids throughout the waste-
water treatment process.
The KP/AP stainless steel rangeBrochure covers a wide range ofhigh quality stainless steel pumpsfor a variety of domestic and commercial applications.
Super-heavy-duty submersible sewage andraw water pumpsBrochure covers the Grundfos rangeof super-heavy-duty channelpumps, axial flow pumps, and pro-peller pumps from 7.5 kW up to520 kW.
Heavy-duty submersiblesewage pumps 15 - 155 kW
Brochure covers the Grundfosrange of sewage pumps from 15 kW
up to 155 kW for handling of rawsewage in heavy-duty applications.
Being responsible is our foundationThinking ahead makes it possible
Innovation is the essence
www.grundfos.com
Business with an attitude
Knowledge The sharing of knowledge, experience
and expertise across our global network will always
lead our business forward.
Innovation Combining the best technology with
fresh ways of thinking, we will continue to develop
even better pumps, systems, services and standards.
Solution With a complete product range, capable
of providing every conceivable water solution, we are
the most complete player on the market.
96
51
24 3
4 0
8 0
3