S9 -201- an affiliate of Perkins Eastman Architects, PC City Department of Buildings in conjunction with an application fora New Building Pennit and Certificate of Occupancy. iv. Storage location: Refuse will be stored in the compactor room and moved to curbside for removal on the day of pick-up by means of maintenance personnel. v. Pick-up : Refuse will be removedatcurbsideperweekas designated by New York City Department of Sanitation. 10. PlumbingandDrainage: a. Approval ofsanitary/storm water house connections to the city se~IS in for connectiontodomesticwaterandfire servicetothecitywatermains onEast 12th and l lthStreetshavebeenobtainedfromtheNewYorkCity Department of:EnvironrnentalProteclion(DEP ApprovaLNo. 15056566). b. Plumbing services are provided with.mill wrap black steel pipeforgas service by Con Ed. One(l) 8" extraheavycastironpipeforbousesewerandone(J)6" ductile ironpressurepipe fordomesticserviceand6" ductile iron pressure pipe for fire protectionarepmvided. Allserviceis viaEast 11th Street c. Water Supply: 1. Potable water will be suppliedviaNewYorkCitypublicwatersystem Anew6'' servicefromtheexisting 12" water main in tbes1reetis extended into the garden level water meter room with a main control valve. The water service is provided with a 6" approved water meter ammgement and a 6'' back:flowpreventer. · The domestic waters1.1pply then continues to a triplexhousepump with one (1) pump standby. Two (2) pumps can operate simultaneously if required. ii. The waterpipingsystemshallconsistoftypeLcoppertubingwith95- 5 tin-antimonysolderedjoinls. ill. Water supply is an up-feed systemoriginatingat triplex, constant speed booster pumps in the garden level Water Meter Room Pumps take suctionfroma6-inchmete1edsupplyfromEastllthndStreet municipal water main. A reduced pressurebackflow valve(RPZ) is positioneddoW1Streamfromthemeter. iv. Hot water from the base building will be sub-metered to the commercial space. v. There will be a total oftbree(3) domestic hotwaterindirectstorage tanks .located in tbe mechanical room in theRooftop Boiler Room (TurbomaxT-109 or equivalent, 119 gallon capacity) and will be supplied from the HV AC boileIS. vi. DedicatedhotwaterandhotwaterreturnriseIS will be provided. Distribution of the ris ets will be via a pipe chase from the gan:ienlevel to the rooftop boiler room H0twater, hot water return and cold water ripping will be fully insulated. vii. Every hot water recirculationpipetotheduplexwaterheateIS shall be provided with a hot watercirculationpumpwithatleast Yi h.p. motor that will run continuously and be provided with a pump by-pass line. viii. There will be as.inglewatermeterfora ll of the residential Condominium Units. Water Charges will be borne bythe CondominiumAssociationasacommonexpensetotheindividual Condominium Unit Owneis. Water will be sub-metered to the commercial spaces. ix. Interior hose bibs will be provided fora.LI mechanical rooms and refuse rooms. Non-fieeze wall hydrants will be located around the perimeter of the building atsidewalklevelandonall terraces.

S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

S9

-201-

an affiliate of Perkins Eastman Architects, PC

City Department of Buildings in conjunction with an application fora New Building Pennit and Certificate of Occupancy.

iv. Storage location: Refuse will be stored in the compactor room and moved to curbside for removal on the day of pick-up by means of maintenance personnel.

v. Pick-up : Refuse will be removedatcurbsideperweekas designated by New York City Department of Sanitation.

10. PlumbingandDrainage:

a. Approval of sanitary/storm water house connections to the city se~IS in for connectiontodomesticwaterandfire servicetothecitywatermains onEast 12th and l lthStreetshavebeenobtainedfromtheNewYorkCity Department of:EnvironrnentalProteclion(DEP ApprovaLNo. 15056566).

b. Plumbing services are provided with.mill wrap black steel pipeforgas service by Con Ed. One(l) 8" extraheavycastironpipeforbousesewerandone(J)6" ductile ironpressurepipe fordomesticserviceand6" ductile iron pressure pipe for fire protectionarepmvided. Allserviceis viaEast 11th Street

c. Water Supply: 1. Potable water will be suppliedviaNewYorkCitypublicwatersystem

Anew6'' servicefromtheexisting 12" water main in tbes1reetis extended into the garden level water meter room with a main control valve. The water service is provided with a 6" approved water meter ammgement and a 6'' back:flowpreventer. · The domestic waters1.1pply then continues to a triplexhousepump with one (1) pump standby. Two (2) pumps can operate simultaneously if required.

ii. The waterpipingsystemshallconsistoftypeLcoppertubingwith95-5 tin-antimonysolderedjoinls.

ill. Water supply is an up-feed systemoriginatingat triplex, constant speed booster pumps in the garden level Water Meter Room Pumps take suctionfroma6-inchmete1edsupplyfromEastllthndStreet municipal water main. A reduced pressurebackflow valve(RPZ) is positioneddoW1Streamfromthemeter.

iv. Hot water from the base building will be sub-metered to the commercial space.

v. There will be a total oftbree(3) domestic hotwaterindirectstorage tanks .located in tbe mechanical room in theRooftop Boiler Room (TurbomaxT-109 or equivalent, 119 gallon capacity) and will be supplied from the HV AC boileIS.

vi. DedicatedhotwaterandhotwaterreturnriseIS will be provided. Distribution of the ris ets will be via a pipe chase from the gan:ienlevel to the rooftop boiler room H0twater, hot water return and cold water ripping will be fully insulated.

vii. Every hot water recirculationpipetotheduplexwaterheateIS shall be provided with a hot watercirculationpumpwithatleast Yi h.p. motor that will run continuously and be provided with a pump by-pass line.

viii. There will be as.inglewatermeterfora ll of the residential Condominium Units. Water Charges will be borne bythe CondominiumAssociationasacommonexpensetotheindividual Condominium Unit Owneis. Water will be sub-metered to the commercial spaces.

ix. Interior hose bibs will be provided fora.LI mechanical rooms and refuse rooms. Non-fieeze wall hydrants will be located around the perimeter of the building atsidewalklevelandonall terraces.

Page 2: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

S9

-202-

an affiliate of Perkins Eastman Architects, PC

d. Water Pressure: Domestic water pressure will be approximately 30 ps iat the 6th.floor and will be maintained by thetriplexboos t-er pLunps in the amenity level.

e. Sanitary Sewage System: The sanitary sewage system will be a gravity type that _is connected to East 1211tand llthStreet mu11icipalseweis.

i. Sanitary draioageand venting is provided viacast-ironbell and spigot and no-hubsanitruyrisei.s toeverytloor.

ii. Sanitaiywastefromeve1y fixture locatedabovetheamenitylevelis gra v ily fed to a combined sanitruy ands torms e~r in the garoen level. The fixtures and1loordrains io thegardenlevel willdischargevia too (2) duplexsewerejector pumps (ITTFlyghtmodelFP-3068-29 or equivalent), one ( 1) located in the East Uth Street gruden level and one (1) located i11 theEa.st l lthStreetamenity level.

iii. All plumbing fixtures shall be t1apped and vented. All fixture traps shall be provided with a clean out

£ StormDrainageSystem: i. Sto nn water from the roof and terraceswiU be directed to a storm water

detentiontaoklocatedinthegardenlevel Thedischarge:fromthetank will be restricted by a control flow device to theexis1iog 36" combined publicsewerin F.ast 11th Street via an8" line.

ii. Storm waterfro1nthecourtyard will be drained byareadrnins toa 6' x 6' c 9' deep sump pump located in the amenity level. Duplexsump pumps wiU be provided will be manufactured by f lygt modelDP3068 or equivalent. In theeventofpo~outage anemei:gencypoweroutlet is located in thecow1yan:iforaportablegeneratortomnthepumps.

iii. Stonnpip ingwill be belland s_pigot andno-hubcastirontbrougbout and sized to adequately drain all stotm water falling ontheprope1ty.

iv. Storm drains will be locatedatalltermceandrooflevels. The system will bes ized per New York City BuildingCode.

v. Overflowdrains will be located alongside storm drains as listed above. The system will be sized per New York City Building Code.

vi. All elevator pits shall be provided with submersibles ump pumps that discharge to thestonndrainagesystem. Sump pumps will be Stancor SE-50 or equivalent.

vii. Allstonn water leaders anddrainsshallhavea minimumslopeof 1/8" pitch.

viii. Thestormwaterdetectiontankwill be poured in place concrete with tankvolume of3.749cubicfeet Stormflowof3.8559 cubic feetper second will be restricted to 0.25 cubic feet per second by means of detention facilities and controlled flow devices.

g. Fire Protection System: 1. The entire building will be protected throughoutwitha combination

automatic wet fires prlnkler and standpipe system in accordance with NFPA 13& 14, the2008 City ofNewYork:BuildingandFireCodes.

ii. The sprinkler and stancpipesystem will bes upplied with water from the new6-inch fire protection water service connected to the New York City water main in East 11th Street A double detector chock backflow preven1erwith by-pass meter will beins1alled. Pressureforthi<; system will be augmented by a 500 GPM automatic fire and jockey pumps installed ina pump room in tbe amenity level.Afire pwnp(Arnura Model #5-4&3-l l or equivalent) will be instaUed to provide adequate pressure and flowfortheentire building. Asocondazy on-site fire watersuctiontankwillbe provided and as required bytbeNYC

Page 3: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

S9

-203-

an affiliate of Perkins Eastman Architects, PC

BuiJdingCode. Theprimaiy water supply will be from the city water main with as econdary s uwly from the suction tank. a, arges for water used in the sprinkler and standpipe system will be borne by the Condominium Association as a commonexpenseto theindividual condominium unit Owners.

iii. One 6" fires tandpipe will be a combined fires tandpipe and sprinkler system. ThesprinkJer/standpiperiser wiU be centrally located in the residential scissor type egress stairs (Stair A I B).

iv.. The compactor chute will have a dedicated sprinkler riser. v. A sprinkler system will be installed throughout the buildjng and will be

controlled bya controlassembly located in the amenity level co ropactor room The standpipe riser will have a 2-1'2" fire hose valve on every staircase landing. A three-way manifold will be installed at the rooflevelstrurcaselanding.

vi. Tile combined.fire protections ystem will be provided with Siamese connectionsonEast 11th Street East 12th Street, and A venueA.

vii. Sprinklerpipingwill be steel witb tbreadedjoi.nis.Jlipingand fittings 2" and larger will be provided with Victaulic type grooved fittings.

viii. Tbe residential tenantandheatedareas will be provided with a wet system. Sprinklers will be quickresponse pendant or side-wall type and uprighttypem exposed ceilings. Thedwellingunitsand residential corrld01s will be provided withresidential type sprinkler heads. The parking area on the first floor .is subjectto :freezing and will be pmvxied with a dry pipe sp1inkler system.

ix. The sprinkler ruid stancpipe installation will be inspected ands igned offpriortoobtaininga CertificateofOccupancy.

x A Job by fire departme.nthose cabinetandlockedkeyboxwillbe located at the lobby level.

11. Heating:

a. Space Heating in select common locations and building-wide domestl'.: hot water will be provided with hot waterfromtwo (2) natural gas .fired LAA.RS RBEOS non-condensing boilers in the rooftop boiler room The input for every boiler will be approximately 2400 MBH. The boilers will be contro&d by a Tekmar275 or equivalent boiler control pane~ which will receive inputs from bot water storage tanks and outside airsensorand will provide a signal to modulate the boilers and associated pmnps. Boilers will be installed on concrete pads with vibration isolators.

b. The pool area is served by a split pool AC/dehumidification unit with hot water coil and remote dry cooler located on the roof(Seresco model NE-007 or equivalent).

c. Two (2) 35 gpm pumps provide hot water for building space heating. T-oo (2) 170 GPM pumps provide hot water to two (2) Instantaneous indirectbot water heaters (TurbomaxModel T-109 or equivalent) for the generation of domestic hot water.

d. Condominium Units will be heated and cooled by variable refrigerant fhw (VRF) systems with heat recovery (LG or equivaleat). Tbe indoor units serving the apartments wiU be horizontal, ducted, ceiling-hLmg heat pUII4JS. The indoor heat pumps will be ducted to linear bar grilles and rectangum registers anddifftlsers toprovideproperairflowin all living spaces.Amenity spaces are also served by VRFs. Conidors are served by chilled watedhot'

Page 4: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

89

-204-

an affiliate of Perkins Eastman Architects, PC

water fan coil units coupled with VRF condensing units. Condensing units will be mounted on the roof with vibration isolators.

e. Master bathrooms are provided with electric radiant floor heating. "·

f. Capacities of the heating systems for the common areas and dwelling units are siz.ed to meet the New York City Building Code and New York State Energy Code, providing a minimum interior temperatute of 70 degrees Fahrenheit at an outside air temperature of 13 degrees Fahrenheit.

12. Gas:

a. Type: Con Ed will supply low pressure gas service from the existing street gas main in F.ast 11th Street.

b. Meters:Therewill befo ur(4) meters. One (1) meter will be for the building heating and domestic hot water boilers, one (1) will be forresidential unit gas cooking ranges, one (l) will be for gas dryers, and one (1) will be for Penthorn;e E. With the exception of Penthouse E, all gas usage, both for common areas an.dforthe individualres ideotialCondominiurnUnits, wiU be borne by the indiv id ua lres idential Condominium Unit Owners as a com1mn expense. Penthouse Ewill have its own meterand will be billed individually by ConEcl.

c. Piping: Piping is steel with threaded malleable iron fittings.

13. AirConditioning:

a. Air conditioning (and heating) for the Condominium Units is provided variable re.fiigerant flow (VRF) systems with heat recovery (LG or equivalent). The heat pump units shall be complete with allrequiredbloweis, controls, valves, coils, dampers, filters and 7-day programmable room thennostats.

b. Bedrooms and living rooms of every will unit be served by one of six (6) different vertical heat-pumps units depending on the individual load requirement of the respective rooms as indicated below.

HEAT SERVICE COOLING FAN PUMP CAPACITY MOTOR

UNIT NO. (BTU/Hr.) SPEED

1 RESIDENTIAL

28,000 MED APARTMENTS

2 RESIDENTIAL

36,200 MED APARTMENTS

3 RESIDENTIAL

42,000 MED APARTMENTS

4 RESIDENTIAL

48,000 MED APARTMENTS

5 RESIDENTIAL

19,100 MED APARTMENTS

6 RESIDENTIAL 24,200 MED APARTMENTS

NOMINAL AIR FWW CFM

(approximately)

750

950

1150

1400

500

600

Page 5: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

89

-205-

an affiliate of Perkins Eastman Architects, PC

16 RESIDENTIAL 12,300 WW APARTMENT

17 RESIDENTIAL 28,000 WW APARTMENT

18 RESIDENTIAL 76,400 MED APARTMENT

19 RESIDENTIAL

76,400 MED APARTMENT

20 RESIDENTIAL

19,100 MED APARTMENT

c. Individual Condominium Units are designed to meet all requirements ofNY City En.ergy Code. Cooling capacities are based on ASHRAB and ARl conditions of approximately 89 deg F DBI approximately 73 deg WB outsi:le, approximately 78 deg F DBI approximately 63 deg F WB inside air.

d. Amenity spaces are also served by VRFs . Corridors are served by chilled water/hot water fan coil units coupled with VRF condensing units.

e. A separate pack.aged or split air-cooled HVAC unit (or equivalent) will be provided for the elevator control room

f. All energy consumed for air-conditioning common areas will be billed by the utility and bome by tbeCondominiumAssociationas a common expense to the individual Condominium Unit Owners.

g. All energy consumed for air-conditioning and heating residential units will be sub-metered and billed to tenants based on actual constm1ption via LG Tenant Billing System(orequivalent).

h. Air cooled condensing units will be installed onsteeldunnageandvibrafion isolators. Utility fans will be installed on concrete curbs and vibratbn isolators.

14. Ventilation:

a. Eveiy residential Condominium Unit bathroom will be provided with rnechanicalexhaust by fans connected to exhaust shaft-ways in accotdance with New York City code requirements.

b. Eve.ry bathroom within eveiy aprutment will be provided with a Constant Air Regulator (CAR). The CAR will maintain a continuous exhaustof30 CFM. The toilet exhaust fans, located on the rooflevel, will run continuously.

c. Eveiy kitchen within eveiy apartment will be provided with a Constant Air Regulator (CAR). The CAR will maintain a continuous exhaust of 50 CFM. The kitchen exhaust fans, located on the rooflevei will run continuously. In addition, penthouse kitchens will be intermittently exhausted to the outside via range hood.

d. All bathroom and kitchen exhaust branches connectingto risers will be provided with an internal boot or a fire damper.

e. There will be approximately twelve (L2) toilet exhaust risers exhausting to approximately seven("!) fans, approximately fourteen (14) kitchen exhaust

300

600

1800

1800

500

Page 6: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

S9

-206-

an affiliate of Perkins Eastman Architects, PC

risers exhausting to approximately six (6) fans and two (2) trash chute exhausts.

f. The interior public conidors will be provided with ventilation airviafan coil units with ducted outside air connections and outside air fans.

g. The gas meterroom will be ventilated via a passive vent system in accotdance with the local utility company.

h. The outside air ventilation requirements for the Condominium Units on the amenity through 6th floors are met by means of trickle vents installed in w.indows. Penthouse level units are provided with ducted fresh air.

i. The elevator control rooms on the roof serving PE-1, PE-2, PE-3 and PE-4 will be provided with a dedicated split heat pump sys·tem. Ventilation is provided forthe hydraulic elevator control room located in the amenity level via l 8x8 duct terminating at a side wall louver

j. The top of the elevator shafts is provided with a 12 square foot louver with a 9 square foot motorized damper. The motorized damper is held in a closed position and will open whengiven_signal:fromthe local area smoke detector.

k. The top ofevezy stair bulkhead is provided with a gooseueckwith mo to rued damper. The motoriz.ed damper is electronically held in a closed position aod will open when given signal from the local area smoke detector.

I. Ductwork on the roof will be provided by duct wrap. Refrigerant piping will be enclosed in insulation.

m Ventilation rates for the building areas are approximately as follow.;: i. Public Corridor. 50 CFM percorridorcontinuous. ii. Bathrooms: 30 CFM continuous.

iii. Kitchens: 50 CFM continuous. iv. Penthouse Kitchens: 50 CFM continuou; exhaust and 500 CFM of

intermittent exhaust. v. Refuse Rooms: 50 CFM continuous.

vi. Amenity Spaces: Outside air in compliance with NYC 2008 Mechanical Code.

15. ElectricalSystem:

a. The Con Ed electric se1vice will enterthe building underground onEast 1111i Street. Newtransfon:ner and bus vaults will be provided by Con Ed and will be tied to an existing trans fonner vault through a bank of conduits encased in concretemnniug insidethe building's amenity level. ·

b. There will be one (1) electrical roomlocated on the amenity level and one (1) PointofFntryroom(P.O.E). Theelectricalserviceroomwill contain the main electrical switchgear and main Consolidated Edis on electric meters . There will be one(I) building/common areas meter, six(6) future connnerciaVcommunity facility tenant meters in the amenity levelmain electrical room and eighty-two (82) iodivid ual residential Condominium Unit meters located in electrical closets on every other floor.

c. The building is served bythefollowingswitches: i. One ( J) 800A/800A switch/fuse for-fire p·ump.

ii. Two (2) 1600A/ 1600A switches/fuses to feed the following: 1. Seven (7) 200/200A switch/fuse for the commercials pace

tenants. 2. One ( 1) 200/200A switch/fuse for community facility tenant.

Page 7: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

89

-207-

an affiliate of Perkins Eastman Architects, PC

3. One{.l) 1600/1600A switch/fuseforhoure panel. iii. One (1)2500A/2500Aswitcb/fuse thatfeedsforn·(4)600A/600A

s witches/:fiisesforfour(4) tenant meter banks. iv. Fo ur(4)600A tenant meter banks. Thei:earetwo(2) meter banks in

Located in the 12th Street building electticalroom on the first-floor adjacent to the service corridor, and two (2) in the main electrical room in the garden level.

d. The Service End Box (SEC), main switchboard, and the firn pwnp service switch are located in the main electrical room in the amenity level.

e. Electrical service to the Co ncbminium Units is as follow.;: i. IOOA 120/208volt, 1 phase, 3 wire serviceforone(l) bedroom

condominiums. ii. l25A 120/208volt, 1 phase, 3 wire servicefortwo(2) bedroom

condominiums. iii. lSOA 120/208volt, 1 phase, 3 wire serviceforthree(3) bedroom

condominiums. iv. lSOA 120/208volt, lphase,3wireserviceforfour(4)bedroom

condominiums.

f. AU services provided to condomin iwns are adequate to serve the demand loads as calculated per 2008 NEC and supplemented by NYC.

g. Electric se1vicewill he provided byConF..<li;onforeachresidential unit for billing by Con&I isonfor their own.energyconsumptioue.xceptforheating and cooling. Electricity service forthebuildingcommonareaload, as well as residential units heating and cooling load, will be provided by a ConF.dism meter.

Electricity consumption for heating and cooling for each residential Unit will be individually electronically sul>-metered and billed to the Un.it resident based actual consumption for each unit. The total energy constHilp tion cost lessthe cost of the electrical consumption fort he resideotialheating and cooling thereof will be paid by the Board and will be borne by the Unit Owner as pa.it of the Comrmn Charges.

Billing of the electrical consumption for each unit Cooling and Heating system will be provided by a thirdparty billingcornpanycontractedbytheBoard. Blch Unit Owner or other resident shall berequired to pay bills for electricity consumxl orused in UnitOwner's Uniteitherto the Board, orthecompanyengagedbythe Board to perform such seivices as directed by the Board.

The third party billing company wi.ll read the cooling/heating systemelectri: meters monthly and will proc~ a bill based on the actual consurnptim of each building unit. Resident electric bill from a third party billing company will contain infonnation including opening and closing meter reads, a breakdown of dolhr amounts billed, the total charge fo rthe period and total amount due. Other feature of this meter will include a non-volatile memory.

Inno eventwill the totalannualrates (including a monthly admin istrativechruge) exceed the utility's tariffed residential rate ford irectmetered service to such residents as speclfied in Part 96.2b3 Residential Sub metering-(Public Seivi:e Law, §§65,66).

h. All residential units have a minimum ofone (I) circuit for every living room, bedroomand bathroom, one (1) circuit for every washer, dryer,

Page 8: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

89

-208-

an affiliate of Perkins Eastman Architects, PC

dishwasher, garbage disposal, one (1) circuitforcombination smoke/carbon monoxide detector, and one (1) circuit for air handling units.

i. GFI type receptacles are provided in all bathrooms, above kitchen counters, and on terraces and balconies. Branch circuiting is provided in accordance with NEC/NYC supplement.

j. Arc fault type circuit breakersareprovidedforevezy ISA &20A, 120V circuits in all units per NEC/NYC supplement.

k. Tamper resistant typereceptacles are provided in all dwelling units per NEC/NYC supplement

I. Evezy unit is provided with light fod:ures in hallways, kitchens, and bathrooms.

m Receptacles are provided in bedrooms, living areas, bathrooms and kitchens in accordanceperNF.C/NYCsupplement.

n. All residential units are provided with a combinationcarbonmonoxide I smoke detector located in every bedroomand outside the bedrooms within 15'. The detector is wired to 120-volt local power and will be self-contained with its own sounding device.

o. LED type lighting fixtures are provided in theresidentialunits as follows:

i. Recessed fod:ures in kitchens, bathrooms and hallways;

ii. Surface mounted fixtures in kitchens, master bathrooms, secondaty bathrooms, walk-in closets and closets;

iii. Pendant fixture in powder rooms;

iv. Linear task light fixtures in kitchens.

p. Switches are providedforoverhead lighting in bathrooms, bedrooms, and kitchens. Switched outJets are provided in bedrooms and living rooms.

16. LowVoltageSystem;:

a. Every unit is provided with an audio intercoms tation to provide two-way communication between units and the concierge desk at the 12111 Street lobby.

b. Every unit is provided with television outlets in all bedrooms and living area wired to local structured wiring cabinet.

c. Everyunitis provided witb voice/dataoutlets in all bedrooms and living areas wired to locals tructured wiring cabinet.

d. Security cameras are provided in elevators, at all entrances, in the garage, and in select co1Tidors.

17. Fire and Smoke Detection Systems:

a. FireAlarmSystem: A codecompliantR-2Smoke/Sprinkleralannsystemis provided and includes the following:

i. Smoke detectors are placed in allmechanicaVelectricaV utility rooms, elevator lobbies, and elevator machine rooms, on top of elevator shafts and on top of stairs. In addition the boiler room and the launchy room have heat detectors and carbon monoxide detectors.

Page 9: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

9

-209-

an affiliate of Perkins Eastman Architects, PC

ii. Tamper switches are provided for the incomings prinkler service, on every s taitwell landing, and integral tampers witches provided on the fire pump.

m. W aterflow switches are provided on evecy stairwell landing. iv. Motorized dampers are provided at the top of elevatorshafts ands tairs. v. Sprinkler/ smoke alann panel, communicator and remote annunciator

are provided as partofthesystem vi. A lockabledisconnect/fi15ed cutout is provided to power the sprinkler/

smoke alarms ystemand is connected ahead of the mains ervice switch. vii. Monitoringmodulesareprovidedforthefirepumpandforlowand

high alarms for the suction tank. viii One (1) pulls tation and remote annunciator have been provided in the

lobbyofeverytheNorthandSouthBuildings. ix. A communicator is provided for Central Station monitoring. x Control relays areprovidedforelevatms recall, releaseoflockeddoms

and for activation of motoriz.ed dampers in top of elevator shaft

18. Television System and TelevisionReceptionFacilities:

a. Cable television will be provided by NYC Time W arnerCable or Veriwn FIOS. Apartments will be provided with a Structure Wire Cabinet (SWC) for termination oflowvoltage wiring and powered via the local 120V e lectrical pan.el with as ingle 20 Amp circuit for controls. Eve1y Living room and Bedroom will be provi<.letl wilh a TV outlet and wired with a shielded cable, as perapproved providerrecommendations.

19. Public Area Lighting:

a. Public sidewalks street lighting will remain as currently provided.

b. The residential lob hies and entrances will be provided with recessed doMlights, cove lights, lighting and suspended fixtures.

c. Corridors will be lit with recessed downlights.

d. Stairwells will be lit at eveiy landing with surface ceiling mounted fluorescent fixtures with emergency battery pack

e. Amenity level mechanical areas will be lit with pendant or surface mounted fluorescent lighting with emergency battery pack which will be controlled by a light switch.

f. Lighting circuits in the common areas are connected to the house meter.

g. Emergency lighting in utility rooms is provided by battery packs. Inverters are provided forenwrgency lighting for fixtures in residential corridors.

h. Lighting circuits in some backofhouse spaces andsta.uwells are controlled viaoccupancysensorsandwired to the housemeter.Forsafetypurposes, some back of house lighting is controlled by single and/or three way switches.

1. Lighting in common hallways usedas emergency lighting is wired for24-hour operation.

Page 10: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

89

-210-

an affiliate of Perkins Eastman Architects, PC

j. Perimeter ands ite lighting is controlled via time clocks and photocells and connected to the house meter.

20. GaragesandParkingAreas:

a. There is an at-grade parking facility with capacity for five (5) vehicles and one (l)ADA vehicle.

b. The parking garage will be lit withpenmntorsurfucemountedfluorescent lighting with emergency batteiy packwltlch will be controlled by a light switch.

c. The parking garage will be unattended.

d. Ventilation: The parking garage will be providedwithanexhaust fan which will energiz.e when CO monitors detect CO concentration in excess of safe limits. A droppedceilingwithbareelementwaterbaseboardwillbeprovidedtoprevent parks from freezing and prevent cold floors above.

e. Fire Protection: The parking garage will be provided by a diy pipe sprinkler system Thediypipevalvewill be located in theamenitylevel.

21. Swimming Pook

a. There is one(l)swimmingpoollooatedinsidethebuiJdingin the amenity level. The pool will have poured concrete and Gunite walls and floor and plaster and tile finish on allinreriorpoolsurfaces. The swi:rmningpoolroom's walls will.be aluminum framed glass, painted sheetrock, and tile.

ApproximatePoolDimensions:50'-0" x 15'-0" Recessed Stair/Bench:21'-11-3/4" x 3'-6" Depth: Varies 3'-6" to 4'-0" Maximum Bathers: 33

b. Doorstobelockedatalltimeswhenpoolis notsupervised.

c. FiltrationSystem: i. High Rate Sand filter- 36" diameter fiberglass reinforced vinyl ester

resin tank. ii. Pentair Whisperflow Model XFK-8 or equivalent filter pump and

strainer(plastic). TMl Salt-PureModel2XMCGor equivalent salt chlorine generator.

iii. Ultraviolet disinfection: TMl Salt-Pure Model SS-UV-158 or equivalent

iv. Supplemental sodiumhypochlorite disinfection: Accutab Powerbase Model 1030 or equivalent.

v. All piping to bePVCunlessstatedotherwise.

d. Pool Heater: Stainless steel brazed plate heat exchanger, 425,000 BTUH. Alfa I.avalorequivalent,fumishedcompletewithHone)'\\ellIA006Eorequivalent manual resetAquastat including 1/2" NPT brass well.

Page 11: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

9

-211-

an affiliate of Perkins Eastman Architects, PC

e. The s wimming pool will be lit with low voltage underwater lighting fu1:ures moun ted onthes idewalls of the pool. Thepoolandpooldeckroom will be lit with recessed downlights. LED floor moWlted lightingfat uies will provide some ambient up lighting arow1d the perimeterofthe pooldeck:.

22. Tennis courts, playgrounds, and recreation facilities:

a. Tennis courts: No tennis courts will be provided.

b. Playgrounds: No playground will be providedatthepremises.

c. Otherrecreationfacilities:A Fitnes, Center, SteamRoom, Sauna, Lounge, and Children's Playroom are located at the amenity level.

23. Permits andCerLilications:

a. PLUMBING-DOB# 121823688 Underground Roughing Gas test Fixtures Backflow Preventers Tap Letters Water Meter Permits Boiler Approval

b. SPRINKLERINSPECflON AND SIGN-OFF -DOB# 122046678 Roughing and Hydrostatic Finis h inspection & Final s ign-off

c. STANDPIPE INSPECTION AND SIGN-OFF -DOB# 122046678 Roughing and Hydrostatic Finish inspection & Final sign-off Fire Pump Inspection - FDNY

d. FIRE ALARM INSPECTION AND SIGN-OFFWI1HFD-DOB #122009398

Inspection Central Office Connection Battalion Chief W alk-thru Certify Letter of Defect

e. BOILER APPLICA TIONFD- DOB# 122010484 Inspection and sign-off with Boiler Division

f. BUILDER'S PA VEMENTPLANSIGNOFF-DOB# 121897803 Highway Department Sign-off Core Reports Engineer Affidavit BP-11 Catch Bas in Letter Inspection by Highway Department Department of Parks Tree Planting Permits

Page 12: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-212-

89 an affiliate of Perkins Eastman Architects, PC

Updated Paving Plan (if rqd.)

g. BUILDER'S PA VEMENTPLANSIGNOFF-DOB# 121897803 Highway Department Sign-off Core Reports Engineer Affidavit BP-11 Catch Basin Letter Inspection by Highway Department Department of Parks Tree Planting Permits Updated Paving Plan (ifrqd.)

h . FOUNDATIONWORK-FULLBUILDING-DOB# 121823688 Controlled Inspections

Piling Sub grade Underpinning Shoring Structural Stability Concrete Cast-in-place Concrete Design Mix Concrete Test Cylinders Final Inspection Final Cost Affidavit

i. TEMPORARYCONSTRUCTIONFENCE -DOB# 121823688 Progress Inspections Final Inspection

j. UNDERPINNING, SHEETINGANDSHORING -DOB# 121823688 Special Inspections

Underpinning Shoring Structural Stability Final Inspection Final Cost Affidavit

k. The following reoccurring ins~ctions will be the responsibility of the Condominium:

Required Inspections and Permits Timeframe City Agency

Local Law# 11 Inspection Eveiy 5 Years DOB

Local Law #87 Inspection Evety 10 Years DOB

Boiler Inspection Annual DOB

INAC Annual Permits Annual FDNY

Backflow Prevention Inspection Annual DOB

Elevator Categoiy 1 Annual DOB

Elevator Categoiy 5 Eveiy 5 Years DOB

Boiler Triennial Ins pection Eveiy 3 Year DEP

Standpipe Sprinkler Eve1y 5 Years Eveiy 5 Years DOB

Monthly and Quarterly Testing of Fire A larm Monthly DOB

Page 13: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-213-

89 an affiliate of Perkins Eastman Architects, PC

Monthly Sprinkler Inspection Monthly DOB

PoolPennit Annual DOH

24. Additionalltems, Violations:

a. As ofthedateofthisreporttherearenooutstandingviolations.Anyviolations shallberemovedpriortoobtainingthePennanentCertificateofOccupancy.

25. Unit Information:

~oom ,iving

:itchcn

;edrooms

Jaster Baths

econdBaths

offller Rooms '.lose ts

Valk-In Closets

!alls

,aundry Closet

a. Number of residential units: 82 residential units.

b. Totalnumberofresidentialroom;: Total number, as definedbytheGeneral Provisions of the New York City Zoning Resolution, Sections 12-10, "Rooms", paragraph "a", will be as follow.;:

Unit Type Quantity of Room; per Total Type Unit RooIIl.5

Studios 0 0 0 1 Bedroom 21 3;5 73.5 2Bedroom 44 4.5 198 3 Bedroom 13 5.5 71.5 4Bedroom 4 6.5 26 Total 82 369

c. Typeandgradeof finishmaterials (all residential units): as listed or approved equal.

Floor Ceiling Walls Base F.ngineered Wood Painted Drywall Painted Drywall Painted Wood Plank F.ngineered Wood Painted Drywall Painted Drywall Painted Wood Plank F.ngineered Wood Painted D.cywall; Painted Drywall Painted Wood Plank Painted Concrete Stone Tile Painted Drywall Stone Tile, Painted Stone Tile

Dtvwall Stone Tile Painted Drywall Stone Too, Stone" Tile

Ceramic Too, Painted Drywall

Ceramic Tile Painted Drywall Ceramic Tile Stone Tile F.ngineered Wood Painted Drywall Painted Drywall Painted Wood Plank Engineered Wood Painted Drywall Painted Drywall Painted Wood Plank F.ngineered Wood Painted Drywall Painted Drywall Painted Wood Plank Porcelain Tile Painted Drywall Painted Drywall Porcelain Tile

Page 14: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

89

-214-

an affiliate of Perkins Eastman Architects, PC

d. Bathroom fixtures: (Typical and Master Baths): as listed or approved equal.

Master Bathrooms Water Closet: One-piece toilet; Toto Carlyle Cotton #01 Lavatory: Duravit 030549 Stark 3 White Lavatory Faucet: Waterworks Studio Highgate HGLS 10 Lavatory Countertop: Stone slab Bathtub: Signature Undennount

HGXS70

Bathtub Spout: Waterworks Studio Highgate Shower Head&Arm(atbathtuhi): Waternorks Studio Highgate HGSHOl Shower System (combined shower+ tub): Waterworks Studio ~gate

Shower Controls (master bath tubs): W at.erworks Studio HighgateHGXT40 Control Valve: Waterworks Studio Highgate HGPBlO

Secondary Bathrooms Water Closet: One-piece toilet; Toto Carlyle Cotton #01 Lavatory: Duravit 030549 Stark 3 White Lavatory Faucet: Waterworks Studio Highgate HGLSlO Lavatory Countertop: Stone slab Bathtub: Signature Undennount Bathtub Spout: Waterworks Studio Highgate Shower Controls (shower+tub): Waternorks Studio Highgate HGXT40 Control Valve: Waterworks Studio Highgate HGPBlO Showerhead & Arm: Waterworks Studio Highgate HGSOl Handshower: Waterworks Studio Highgate HGHS30

Powder Rooms Water Closet: One-piece toilet; Toto Carlyle Cotton #01 Lavatory: DW'avit 030549 Stark 3 White Lavatory Faucet: Waterworks Studio Highgate HGLS40 Lavatory Countertop: Stone Slab

e. Kitchen and Launcty fixtures: as listed or approved equal

Item Description Kitchen Types

Refrigerator 30" Sub-Zero IT-30CI KIA, Kl, Kl-I, K2A, K2, K2C, K2C2

Refrigerator 36" Sub-Zero IT-36CI Kl-2,Kl-C,Kl-D,K2D,K2Dl,1(2[)2, K4C5,K4C7

Refrigerator 24" Sub-Zero IC-24Rl K4Cl, K4C2, K4C3, K4C4

Refrigerator 30" Sub-Zero IC-24R K4C6

Freezer 18" Sub-Zero IC-18FI K4Cl, K4C2, K4C3, K4C4, K4C6

Wine Refrigerator 15" Marvel MLI5WSF2 KIA, Kl, Kl-I, Kl-2, K2A, K2, K2G K2C-2

Wine Refrigerator 24" Sub-Zero 424GIO KI-C, KI-D, K2D, K2DI, K2D2, K4C3, K4C5, K4C6, K4C7

Page 15: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-215-

S9 an affiliate of Perkins Eastman Architects, PC

Wine Refrigerator 27" Sub-Zero 427G K4Cl, K4C2, K4C4

Gas Cooktop 30" WolfCG304P/S KlA,Kl,Kl-l,Kl-2,Kl-C,K2A,K2, K2C,K2C-2

Gas Cooktop 36" WolfCG365P/S Kl-D, K2D, K2Dl, K2D2, K4CI, K4C2,K4C3,K4C4,K4C5

Drawer Microwave 24" WolfMD24TE/S All

Oven 30" Wolf S030F/S KlA,Kl,Kl-l,Kl-2,Kl-C,K2A,K2, K2C,K2C-2

Double Oven 30" Wolf D030PE/S/PH K4Cl,K4C2,K4C3,K4C4,K4C6

Dishwasher Bosch SHV7PT53UC All

Disposal WasteKing SS800TC All

Range Hood Best Ul02 30" KIA,Kl,K.l-l,Kl-2,Kl-C,K2A,K2, K2C,K2C-2

Range Hood Best UI02 36" Kl-D, K2D, K2Dl, K2D2, K4Cl, K4C2, K4C3, K4C4, K4C5

GA, G-B,. G-C, 3F, 3J, 3K, PH-A, PH-Exterior Gas Grill Weber Summit S-460 B, PH-C, PH-D, PH-E, PH-F, PH-G,

PH-H Commercial W ashtlr Maytag MHP30PR Common Laundry Room

Connnercial Dryer Maytag MDG25PR Common Laundry Room

Washer Bosch WA T28402UC Garden - 6th Fl

Dryer Bosch WTG86402UC Garden - 6th Fl

Washer Whirlpool WFW95HEDU PH

Dryer Whirlpool WGD95HEDW PH

Kitchen Cabinets 18cm Chipboard w/ Lacquer

All or Wood Veneer

Kitchen Countertops Stone Slab All

26. Finish Schedule of Spaces OtherThan Within Residential Units:

Room Floor Ceiling Walls Lobby Concrete Painted Dtywall Painted Drywal~ Wood

Veneer, Mirror Fitness Room Resilient Flooring Painted Drywall Painted Drywall, Wood

Veneer, Mirror Fitness Room Toilet Ceramic Tile Painted Drywall Painted Drywall, Stone Tile

Children's Playroom Carpet Pa inted Dtywall Pain ted D1y wall, wan. Covering

Bike Room Painted/Sealed Exposed Concrete Painted Concrete, CMU Concrete

Mechanical Rooms Sealed Concrete Exposed Concrete Exposed Concrete CMU

Compactor Room Painted Concrete Exposed Concrete Painted Concrete, CMU

Page 16: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-216-

S9 an affiliate of Perkins Eastman Architects, PC

Laundry Room Ceramic Tile Painted Drywall Painted Concrete, CMU

Service Corridor Painted Concrete Exposed Concrete Painted Concrete/CMU

Residential Corridors Carpet Painted Drywall, Wall Covering Painted Drywall, Wall Covering, Wood Veneer

Refuse Rooms Ceramic Tile Painted Drywall Painted Drywall

Stairs A/B Painted Concrete Painted Concrete Painted Concrete/Drywall

27. Additional Information Required:

Unit

Garden 1 2 3

Second Fir D(Duplex)

E p Q R

a. Site plan: Seeattachedherein.

b. Areamap: NotApplicable

c. Residential Unit Floor plans: See attached herein.

d. Floor-to-ceiling heights withinapartmentunits:

Unit Area (SF)

1027 1195 1072

1976 1037 906 873 976

i. In the garden units, theceilingheights are 10'6".0n the2ndthrough6'11 floors, the ceiling heights in living rooms, dining rooms and bedrooms rangefrom9' 11' to 10'7". The ceiling heights in public corridors, foyers, kitchens, po\\derrooms and bathrooms will be typically 8'7" to 9'0".

ii. AtthePenthoureunits, the ceiling heights in livingrooms, dining rooms and bedmoms will typically be either 13'5" or 15'9". The ceiling heigtits in public corridors, foyers,kitchens,powderrooms and bathrooms will be approximately be either 10' 8" ·Of 13 '5".

iii. On all floors, atbeamdrops and/orwherethere are concealed mechanical pipes or ducts or dropped ceilings or smoke bafiles, height may be lower than the above stated heights and may alsovaryfrom roomtoroom

Outdoor Unit Unit Area(SF) OutdoorArea(SF) Terrace Area

(SF) p 662

433 Q 1439 393 R 1190 398 s 934

T 765 355 u 795

Fifth Fir A 744 B 1092 c 1221

Page 17: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-217-

S9 an affiliate of Perkins Eastman Architects, PC

s u

Third Flr A B c D E F H J K L M N p

Q R s T u

Fourth Fir A B c D E F H J K L

M N

1164 D 1635 1158 E 824

F 1188 744 G 1358 1092 K 1257 1221 M 1628 1265 p 1267 1194 Q 1150 1686 1502 R 1604 666 s 1244 1149 642 u 1185 1112 680 Sixth Fir 608 A 744 1345 B 1092 669 c 1221 662 D 1635 1439 F 1188 1190 G 1358 934 K 1257 765 M 1628 795 p 1267

Q 1150 744 R 1604 1092 s 1244 1221 Penthouse 1265 A 1621 241 1194 B 1744 518 1686 c 1658 942 666 D 1744 1297 1149 E 3482 1364 1112 F 1782 931 608 G 2258 840 1345 H 1987 958 669

e. Approximate totalareaofeveiyunit:

The grosssquaiefootarea oftheUo_itssetforth in the floor plans and inScheduh A to 1he Offering Plan are within reasonable tolerances and were obtained by using the method customarily used in New York City to measure rental, cooperative and condominiwnapartmen1s. The units we1e measured from the exterior si:.le of the exterior walls (perimeter columns and mechanical pipes/duels/shafts/ rue not deducted) to the corridor/common elements side of interior walls separating one Unit fro m another Uni4 or separatinga Unit from public corridrns, stairs, eevatms and other mechanical equipments paces or any Common Elements or Limited Common Elements, and to the midpoint of the demising inte1ior wall:; and partitionsseparatingone Unit.from another Unit Any common elements baited within a unit shall not be considered a pa1to fs uch unit As is customary in J\ew York City, thesesquarefuot rueasexceed the useable floo r area of Every UnJt.

Page 18: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-218-

89 an affiliate of Perkins Eastman Architects, PC

aa. No further units will be added to the building.

bb. The subject building is a new construction project, as such no asbestos containing materol is present in insulating or fireproofing material anywhere in the building.

cc. The subject building is a new construction project, as such no lead based paint has been used anywhere in the building.

dd. All references herein to dimensions, areas, heights and thlcknesS:'.s ofconstruction materials are approximate within reaso;iabletolerances. Allinake and model numb era ofappl.iances, fixtuiac; and equipmentaresubjecttochange,inthesponsor'sdiscretionand/orbaseduponavailabilityatthetitre thatthe build i.ng is substantially complete. Sponsor reserves the right to substitute applianre<;,fixttues and equipment withs ubstantiallys imilar appliances, futures and equiprnentofcomparableor better quality.

ee. The following documents shall be transmitted to the Condominium management upon transfer of control: final as-built drawings; operation & maintenance manuals for mechanical equiprrmt; equipment warranties; NDLroof wan-anty; major equipment start-up sheets; original testing and balancing reports for HVAC system

Navid Maqami, AIA Principal

Page 19: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-219-

438 E 12TH STREET NEW YORK, NEW YORK 10009

NORTH TO SOUTH SECTION

I I ROOF ROOF

I I I "'"ruow

'== ~I I 1- ~EI

I SIXlHFLOOR I SIXTH.FLOOR

I Rrllf flll!ffl I 'lftH FLfJ<lR

l FORTH FLOOR I I I I f<MHHFLOOR I I lHIAOR.OOR I I I I TH~O FLOOR I

I II I SECOhtlFLOOR I I I I SECOM> FLOOA I E. 12THST. l068Y I

L.,.,,,.,1.0,m I I I GARDEN I GHtOEHl\.00/1

E, 11n1ST.

BWL.tNm; SERVICES

I 11 Ii BUILD!$ SERVICES

._____,-----.__

0 10' 20' 30' 40'

12.03.2015

Page 20: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-220-

438 E 12TH STREET NEW YORK, NEW YORK 10009

WEST TO EAST SECTION

-

I """

Pit

SIXTII FLOC"

I flf111flDOO

f\)RIHROOR

~~IL~

i f'il5TR.ODR A\9/VEA

.wa.n.W

i 11 n

a_____r-..__r--

0 1 O' 20' 30' 40'

12.03.2015

Page 21: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-221-

438 E 12TH STREET NEW YORK, NEW YORK 10009

11 TH STREET SOUTH ELEVATION

~

0 10' 20' 30' 40'

12.03.2015

Page 22: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-222-

438 E 12TH STREET NEW YORK, NEW YORK 10009

AVENUE A EAST ELEVATION

E.111HST. E. 121HST •

....___,---.___

0 10' 20' 30' 40'

12.03.2015

Page 23: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-223-

438 E 12TH STREET NEW YORK, NEW YORK 10009

12TH STREET NORTH ELEVATION

AVE.A

~

o 1 o· 20· 30· 40·

12.03.2015

Page 24: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-224-

438 E 12TH STREET NEW YORK, NEW YORK 10009

GARDEN WEST ELEVATION

E.12TH ST. £. 11lHST.

0 10' 20' 30' 40'

12.03.2015

Page 25: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-225-

438 E 12TH STREET NEW YORK, NEW YORK 10009

GARDEN SOUTH ELEVATION

.... ,

~

o 1 o· 20· 30' 40'

12.03.2015

Page 26: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-226-

438 E 12TH STREET NEW YORK, NEW YORK 10009

GARDEN NORTH ELEVATION

AVE.A

0 10' 20' 30' 40'

12.03.2015

Page 27: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-227-

438 E 12TH STREET NEW YORK, NEW YORK 10009

GARDEN EAST ELEVATION

E.11 TI-l if, E. 12THST.

~

0 10' 20' 30' 40'

12.03.2015

Page 28: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

438 E 12TH STREET NEW YORK, NEW YORK 10009

SITE PLAN

~

o 1 o· 20· 30· 40·

-228-

BLOCK 439 TAX LOT 26 BUILDING ADDRESS: 438 EAT 12TH STREET NEW YORK, NY COMMUNITY DISTRICT: MANHATIAN 3 COMMUNITY DISTRICT ZONING DISTRICT: RSB & R7A/C2-5 (MAP 12C) BUILDING OCCUPANCY CLASSIFICATION: R-2 RESIDENTIAL BUILDING CONSTRUCTION CLASSIFICATION: TYPE 1-B, FULLY SPRINKLERED

12.03.2015

Page 29: S9 Perkins Eastman Architects, PC an affiliate of · S9 -203-an affiliate of Perkins Eastman Architects, PC BuiJdingCode. Theprimaiy water supply will be from the city water main

-229-

438 E 12TH STREET NEW YORK, NEW YORK 10009

GARDEN & AMENITIES FLOOR PLAN

~

0 10' 20' 30' 40'

12.03.2015