A Labs21 2012 Annual Conference Pre-Conference Training Session

Safely Cut Your Laboratory Energy Usage in Half

Page 2: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 2

Your Presenters

• Wendell C. Brase Vice Chancellor, Administrative and Business Services Chair, University of California Climate Solutions Steering Group

• Matt Gudorf Campus Energy Manager

• Marc A. Gomez Assistant Vice Chancellor for Facilities Management and Environmental Health & Safety

• David Kang Industrial Hygiene Energy Specialist

• Fred R. Bockmiller Manager, Engineering Group

Page 3: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 3

Learning Outcomes

1. Why focus on laboratories? 2. Can we afford a “smart lab” retrofit? 3. Are savings greater than 50% really possible? 4. Can these savings only be realized with new

construction? 5. Can we afford to keep a “smart lab” smart? 6. What if our energy costs differ from those in

California?

Page 4: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 4

Why laboratories?

They use 2/3 of the energy at research universities!

Page 5: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 6: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 6

What is a “Smart Lab”

• “Smart Labs” are newly constructed or retrofitted laboratories that reduce building

system energy consumption by 50% or more, augment established safety protocols

and designs, and provide a data stream effectively commissioning the building

at all times.

Page 7: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 7

Smart Lab Evolution • UC Irvine’s Smart Labs Initiative includes multiple features

that were piloted and verified before campuswide deployment.

• Making the deep energy cuts that are required to meet a 50% savings goal requires that theories be tested, perceptions changed, and results evaluated.

Page 8: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

UCI’s Goal is to reduce lab energy consumption by 50%

Implement Smart Labs CDCV, ESDVR, Day Lighting and Lighting Controls, Low Pressure

Drop Filters, Remove Duct Noise Attenuators, Static Pressure Reset

Verify savings and use added

tools to constantly

commission labs

Measurement &

Verification

Set Goals & Targets

Analysis &

Development

Energy Improvement

Measures

Review data, Labs21 Toolkit,

Scope out energy project

Lab Efficiency Cycle

Page 9: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 9

Retrofitting or New Construction With the exception of the building shell, all Smart Labs retrofits can be completed in occupied buildings with minimal lab interruptions. • Service interruptions are directed in the contract for duration, timing, and notification

that must be given. • Scope of work may or may not include temporary supply and exhaust fans • Contractors must work with air flowing both supply and exhaust with all shutdowns

minimized even when this increases the number of steps or amount of work • Town hall meetings prior to construction with building occupants • Posted construction schedules in hallways and email updates • 2-week in-person notice given to each individual lab

Page 10: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 10

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 11: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 11

Prerequisites of a Smart Lab

1. Constant air volume (CAV) to variable air volume (VAV) 2. Pneumatic to direct digital control 3. Individual exhaust to manifolded exhaust 4. Differential pressure control for pumps 5. Thermostat location and other existing challenges

Page 12: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 12

When building load varies …

Shouldn’t the HVAC system follow? – Constant Air Volume – supply and exhaust flow rate remains the

same independent of: • Fume hood sash position • Thermal demand • Occupancy

– Variable Air Volume – supply and exhaust changes depending on:

• Fume hood sash position • Thermal Demand • Occupancy

Page 13: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Variable | Constant Air Volume

Constant

Vent

ilatio

n Ra

te (C

FM)

Variable

CAV CFM VAV CFM

Savings

Page 14: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Constant Volume Control Valves

Constant Volume Dual Duct Mixing Boxes

Typical Lab Prior to Retrofit

Page 15: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Typical Lab Post-Retrofit

Mixing boxes for temperature control and control valves for flow control

Variable volume control valves

Page 16: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

New Mixing Boxes

Duct static pressure must be equal to prevent backflow

Temperature control of supply air

Control of flow (CFM) of supply air

Dual Duct to Control Valve Connection for Lab Supply Air and Proper Setup

Page 17: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Pneumatic Control to Direct Digital Control

Direct Digital Controls

• Do not require frequent calibration • Can perform complex sequences • Can receive instructions from a master computer • Can transmit to a master computer information such as damper

position, room temperature, supply air quantity, and supply air temperature

Page 18: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 18

Individual Exhaust Some buildings have 1 exhaust fan per fume hood, zone, or possibly multiple zones • Typically small motors • No variable frequency drives installed • No redundancy in case of failure • No static pressure control • High level of maintenance required

Page 19: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 19

Manifolded Exhaust N+1 Exhaust Fans connected to a common plenum • Premium efficient motors • Variable frequency drives installed • Control based on static pressure of the exhaust duct

responding to increase or decrease in demand • Redundancy allowing for increased safety and no lab

downtime during service

Page 20: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 20

Manifold Exhaust Duct • Use a high quality, properly braced, industrial grade isolation damper • Inspect for leaking air • Check for proper slope to avoid pooling water

Page 21: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Constant Flow to Variable Flow For maximum energy savings, reliability, and turn down, convert building heating water systems to variable volume. • Add Variable Frequency drives to the pumps • Replace 3-way valves with Pressure Independent Control Valves (PIC-V)

• Valve leakage wastes energy. Do not just close the bypass the best practice is to replace the valve.

• Check each VAV box for valve leakage, replacement of 2-way valves may be necessary. Leak-by is a significant energy waste.

• Install differential pressure monitoring and reset schedule

Page 22: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 22

Heat-generating equipment placed next to thermostats wastes energy.

Location, Location, Location

Page 23: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 23

Fixing the Known

If you have known issues in your lab, you need to address them now or as part of the retrofit (Smart Lab retrofits can resolve your deferred maintenance nightmare). • Failed lab air control valves • Stuck dampers • Broken actuators • Static pressure sensors that are failed or need recommissioning • Dirty duct work • Occupant installed snorkels, ductwork taps, other interesting

“improvements” • Over ridden VFD’s

Page 24: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 24

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 25: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 25

Monitoring and Verification Capabilities

1. What level of metering do you have? 2. What level of metering do you need? 3. Where is the information you need? 4. What metrics should I trend and make decisions with?

Page 26: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 26

ZONE-LEVEL USE

BUILDING SYSTEM USE

TOTAL ENERGY USE

Look Closer … Find More Savings

BUILDING Electric and Gas Meter

EMS HVAC, pumps, chillers

EMS, CDCV Fume hood use,

IAQ, thermal demand

Submetering lighting, plug load

EMS boiler, water heater

CDCV, EMS reheat

At the zone level, measurement and verification resolution are so high That you are essentially constantly commissioning the building .

Page 27: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Building Management System

Page 28: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 28

Cost-Effective Submetering Meter Specs

• 12 channels per board • Meter accuracy +/- 0.5%

(0.25% typical) • V, I, active energy, reactive

energy, power factor

Current Transformer Specs

• Sensor accuracy +/- 1% • Current transformers 60-400 amps • Clamp-on installation

Page 29: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 29

Clamp-on CTs installed

Meter installed Connected to Internet

Page 30: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 30

00 140610KWH

mel r okC o r p o r a t i o n

dangerh igh vol t age

Acquisition SW SQL Express DB

00 140610KWH

mel r okC o r p o r a t i o n

dangerh igh vol t age

Database Server

Multiple Users

EnerACQ User Interface

User PC

EnerACQ User Interface

User PC

Individual 12 Channel Meters

System Description

Page 31: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Visualization of Lab Energy Use

Page 32: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 32

Total Building Load

Watts / Square Foot Therms / Square Foot

Lighting Watts / Square Foot Interior Load vs Exterior Load Daytime Load vs Nighttime Load Lighting Load per Floor

HVAC Watts / Square Foot Therms / Square foot Daytime Load vs Nighttime Load CFM per Zone

Plug Load Watts / Square Foot Daytime Load vs Nighttime Load Plug Load per Floor Fixed Load vs User Load

LEED® Energy Star® Labs 21 Benchmarks

Information that is actionable

Metrics That Can Lead to Action

Page 33: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 33

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 34: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 34

Smart Lab Characteristics

1. Building Envelope

2. Lighting

3. Mechanical System

4. Lab Equipment Selection

Page 35: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 35

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 36: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Building Envelope

Building shell is No. 1 driver

HVAC system size

Lighting requirements

Environmental impact

Page 37: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Building Envelope Window shades

Light-colored concrete

Shaded entry via setback and overhang elements

Page 38: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 38

Building Envelope

Light shelves

Ultra high-performance glazing

Page 39: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

T-24 Cool-roof material R-30 roof insulation

Building Envelope

Page 40: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 40

Building Envelope

Landscape belts at building perimeters reduce heat and reflection impacts Drought-tolerant vegetation uses minimal reclaimed water

Page 41: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 41

Right-Sized Air Handlers & Exhaust

Page 42: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Increased duct size

Low-pressure drop filters

NEMA premium efficiency motors

Low-Velocity Air Handling Units 350 fpm Face Velocity

Page 43: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 43

Why use high volume ductwork? Low-Velocity Exhaust Ductwork

• Low pressure drop laboratory air system design • Low velocity air distribution system • Low velocity exhaust ductwork

Increased duct size

Page 44: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 44

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 45: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 45

Lighting

• Lighting should be as flexible as possible. • Provide task lighting when additional illumination • is needed. • Encourage occupants to be conscious of their

lighting needs. • Do not discount the synergistic savings from

eliminating heat produced by over-illuminated spaces.

Page 46: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 46

Lab Area LPD from 1.1 to 0.6

Lab Prep LPD from 1.0 to 0.4

Prep Room LPD from 2.0 to 1.0

Corridor LPD

from 0.6 to 0.3

What Is Your Lighting Power Density? LPD = (Watts / Area) x Occupancy Sensor x Circuiting Strategy x Day lighting

Page 47: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 47

Non Daylighting Areas

32 Watt T8

25 Watt T8

NLO Ballast .87-.90 BF

RLO Ballast .71 BF

This retrofit on a 4 lamp fixture, on 4380 hours a year, saves 170 kWh per year. UC Irvine retrofitted ~15,000 fixtures campuswide, saving 2,550,000 kWh per year!

We had ZERO complaints!

Page 48: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 48

Automatic Daylighting Controls

Lab areas within 15 feet of windows and all private offices and conference rooms are equipped with automatic daylighting controls.

Page 49: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Daylighting Without the Glare Perforated window blinds

Page 50: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 50

Sequence

Auto on to 50% Manual on to 100% Auto off

Page 51: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 51

Lighting is controlled per lab bay -- not per lab -- to maximize savings.

Lighting

Page 52: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Lighting

Lighting is controlled per lab bay -- not per lab -- to maximize savings.

Page 53: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

LED Task Lighting

Magnetically mounted LED task lighting

Page 54: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 54

Bi-Level Lighting in Stairwells and Corridors

Corridor lighting is often on all year, 24 hours a day, and represents a good opportunity for occupancy sensing.

Bi-level lighting in stairwells is another opportunity that should not be overlooked.

Page 55: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 55

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 56: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

PARTICIPATORY

EXERCISE

Haaaaaa Paaaaaaa

Page 57: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

A aaa aaa aaa 20 aaaaaaaa aa 12 aaaaa a aaa 6 aaaa a aaaaa

4 aaaa T8 32 aaaa aaaa 2 aaaaaaa aaaaa NLO aaaaaaa

a85aa91BF aaaaaaa aa 112 aaaaa aaa aaaaaaa

Yaaa aaaa aa aaaaa aa a0a105 aaa aWa

Oaaaaaaaa aaaaaaa aaaa a45 aaa aaa aaaa 3a

aaaaaaaaa aa a 30a aaaaaaa

Ia aaaa a300 to re-circuit the laba aaaaaaaaa aa 70a aa aaa aaaa aaaaaaa aa aaaa 2 aa 4 aaaaa

4 aaaa T8 25 aaaa 2 aaaaaaa aaaaaaaaaa IS RLO aaaaaaa a71BF

aaaaaaa aa 73 aaaaa aaa aaaaaaa aaaa aaa 4 aaaaa aa

aaa 38 aaaaa aaa aaaaaaa aaaa 2 aaaaa aa aaaa a100

Waaa aa aaa aaaaaa aaaaaaaa

Page 58: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

1. Eaaaaaaa aaaa aa aaaaaaa aaa aaaaa

– 20 aaaaaaaa a a112 aaaaaa1000a a 6 aaaa a 12 aaaaa a 52 aaaaa a aa105 a a880a59 aaa aaaa

2. Caaa aa aaaaaaaaa

– a45 a 3 a a300 a a100 a 20 a a2a435

3. Naa aaaa aa aaaaaaa aaa aaaaa

– 12 Haaaa aaa aaa a a7 aaaaaaaaa aaaaaa aaaaaaa a 8a4 Haaaa aaa aaa

– 20 Faaaaaaa a a73 aaaaaa1000a a 6 aaaa a a8a4 Haaaa a a3 aaaaaaaaaaaaa aaaaaaaa

a 52 aaaaa a a0a105 a a120a53

– 20 Faaaaaaa a a38 aaaaaa1000a a 6 aaaa a a8a4 Haaaa a a7 aaaaaaaaaaaaa aaaaaaaa

a 52 aaaaa a a0a105 a a146a40

– a120a53 a a146a40 a a266a93

$880.59 – a266a93 a a613a66 a2435 a a613a66 a 3a97 aaaaa

Page 59: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 59

The training session will resume in 10 minutes.

Page 60: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 60

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 61: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 61

Mechanical System

• Maximize occupant comfort • Minimize air change rates • Maintain lab safety • Provide a right-sized system that is

both variable and efficient • Make use of dashboards to review energy

consumption and indoor air quality

Page 62: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 62

What is an Air Change Rate Air Change Rate - Imperial Units Air change rate - air changes per hour - can be expressed in imperial Units as

n = 60 q / V Where n = air changes per hour q = fresh air flow through the room (Cubic Feet per Minute, cfm) V = volume of the room (Cubic Feet)

q = supply in CFM

V = Length x Width x Height

Page 63: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Autoclaves Ultra-low temp freezers Refrigerators Incubators Water purification systems Microscopes Computers Shake tables

Lighting Occupants Building shell Windows

6-10 ACH

High air change rates often exceed all of the lab’s process and operational loads.

Mechanical System Balance

Page 64: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Autoclaves Ultra-low temp freezers Refrigerators Incubators Water purification systems Microscopes Computers Shake tables

Lighting Occupants Building shell Windows

6-10 ACH

Balance to the room is brought about by adding varying amounts of reheat.

Mechanical System Balance

Page 65: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

2-4 ACH

Autoclaves Ultra-low Temp Freezers Refrigerators Incubators Water purification systems Microscopes Computers Shake tables

Lighting Occupants Building Shell Windows

Lowering the air change rate with the installation of a CDCV system swings the balance the other way.

Mechanical System Balance

Page 66: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

2-4 ACH

Autoclaves Ultra -low temp freezers Refrigerators Incubators Water purification systems Microscopes Computers Shake tables

Lighting Occupants Building Shell Windows

Lower air change rates more closely match the natural lab process load, reducing both fan power and reheat.

Mechanical System Balance

Page 67: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 67

Lab HVAC Load

Process heat gain from lab equipment is the primary source of internal heat gain in many facilities. • Autoclaves • Ultra-low temperature freezers • Refrigerators • Incubators • Water purification systems • Microscopes • Computers • Shake tables

You need a plan to deal with the heat!

Page 68: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Dealing with the heat is the only way to reduce air change rates

Equipment corridors have slot exhaust grills to remove heat from the space.

Freezer Heat Rejection Slot exhaust diffusers

Equipment corridors with slot exhaust grills are located on each floor to reduce lab heat gain.

Page 69: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 69

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 70: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 70

Centralized Demand Controlled Ventilation

• Monitors the indoor air quality of multiple zones through a network of structured cables and air data routers

• Analyzes the sampled air with a series of sensors • Provides the lab air control system with an input for

increased ventilation when necessary. • The system is only an input to your lab air control system,

no different than a thermostat, or sash position sensor.

Target is 4 air changes per hour in occupied labs and 2 air changes per hour in unoccupied labs.

Page 71: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Demand-Controlled Ventilation Completed In Construction

Page 72: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 72

1. Room sensor mounted in general exhaust duct samples a packet of air

2. Packet of air is routed to the Sensor Suite

3. Sensors measure indoor air quality

4. Information Management System determines need for increased ventilation, commands VAV controllers, and serves data to a web server.

5. System monitoring is available via a web based interface.

CDCV

Page 73: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 73

Lab Room 101 Lab Room 102 Classroom 103 Supply Air Reference

Probe

Web Based User Interface

BMS Connectivity

Sensor Suite with TVOC,

CO2, dewpoint & particulate

sensors

Air Data Router

Vacuum Pump

Server

Room Sampling

Port

Supply Air Duct

General Exhaust Duct

GEX Duct Probe (typ.)

Air Data Router

CDCV System Architecture

Page 74: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 74

CDCV Components Sensor Suite

Structured Cable

Duct Probe

Vacuum Pump

Air Data Router

Page 75: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 75

CDCV - Sensors

Type Sensors Activation Range

Units Low High

TVOC PID (10.63V) 0.1 1.0 ppm

TVOC Metal Oxide (MOS) 0.3 3.0 ppm

CO2 NDIR 300 3,000 ppm

Particulate Optical 500,000 5,000,000 pcf

CO Electrochem 2 20 ppm

Page 76: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 76

Smart Labs - Added Features

UC Irvine seeks to continuously update the lab air control system with safety and energy saving features. Safety • Red Buttons • Lab display unit (LDU) Energy Savings • Occupancy sensors

Page 77: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 77

Red Buttons

Red Button – In the event of a chemical spill or other event requiring increased ventilation in a lab, an emergency ventilation override button has been installed. Pressing this button will increase air change rates to maximum while maintaining negative lab pressurization.

Page 78: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Lab Display Units

• Currently in use in Gross Hall • Programmed to display ACH,

occupancy status and ventilation offset information within lab

• Provide real-time feedback to lab occupants

Page 79: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 79

Smart Lab “Safety Net”

Occupant Training Describes Smart Lab features

Page 80: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 80

Laboratory is a “System”

HVAC elements must work together as a system for contaminant control: 1. Primary control − Local exhaust ventilation (at source

of contaminant generation) 2. Secondary control − Dilution of room air (ACH)

A key focus of the bench top risk assessment is to drive contaminants into primary controls whenever possible.

Page 81: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 81

Primary (Source) Control – Fume Hood

Page 82: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 82

Primary (Source) Control - Snorkel

Page 83: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 83

Primary (Source) Control - Glove Box

Page 84: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 84

Laboratory is a “System”

For contaminant control, critical to have: • All HVAC elements in balance and maintained • Fume hood commissioning & placement • Good air mixing to avoid contaminant build-up &

achieve effective dilution

Page 85: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 85

Air Mixing for Good Air Quality

• Air diffusers are key to promote better air mixing • Explore various diffuser styles • Evaluate air mixing − smoke studies or computational

fluid dynamics (CFD) • Separate air diffusers and air returns

Page 86: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 86

Good Air Mixing − Fabric Air Diffuser

Less air turbulence to fume hoods

Page 87: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 87

Air Changes per Hour (ACH) (secondary control – dilution ventilation)

• 6+ ACH 4/2 ACH setback with occupancy sensing

• CDCV senses chemical and increases ACH • Sensor failure must “fail safe” to 6 ACH

– Sensor suite does not detect all chemicals • Visual signal to occupant of ACH • Emergency exhaust red button

Page 88: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 88

Question: Is Increased ACH Safer?

“Specification of Airflow Rates in Laboratories” by Tom Smith, Exposure Control Technologies, Conclusions:

– ACH as a metric for dilution is “too simplistic”. – Must consider other factors that lead to exposure, (i.e.

contaminant generation rate, air mixing, etc.) – “Increased airflow [may increase] contaminant generation

and distribution throughout the space” – May lead to “false sense of safety”

Page 89: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 89

Answer: Not Necessarily

Alternatives to simply increasing ACH:

– Base air exchange rate on contaminant generation – Review lab practices, especially outside fume hood – Attain proper air mix ratios – Reduce overall ACH to save energy and increase ACH as

needed via “smart controls

Page 90: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 90

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 91: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 91

Implementing CDCV

Risk Assessment of Lab Bench Top Processes to Ensure Safety in Smart Labs

• Energy savings can be achieved without compromising safety • Lab ACH determination requires:

– Active EH&S involvement in bench top risk assessment of lab operations with lab staff

– Contaminant source control – Reassessment when lab changes occur – Current/complete chemical inventories

Page 92: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 92

Step 1 - Lab Bench Top Risk Assessment Process

Conduct room-by-room hazard screening – Industrial hygienist (IH) evaluates worker exposure – Review chemicals inventory/operations – Interview lab staff – Review engineering controls – Focus is outside of fume hood

Page 93: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 93

Lab Bench Top Screening Process

• Compare screening data with risk assessment criteria

• Enter screening data in database – If follow-up needed, no ACH reduction – If no follow-up needed, reduce ACH

Page 94: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 94

Risk Assessment Criteria High-risk labs – no ventilation reduction

– Biosafety Level 3 (airborne biohazard)

– Highly toxic gases – Special ventilation requirements – Chemicals/operations identified as high risk by bench top

assessment or follow-up exposure monitoring – Fire area control limits exceeded

Page 95: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 95

Risk Assessment Criteria

• Chemicals of Concern – Acutely toxic by inhalation – Asphyxiants – Anesthetic gases – Carcinogens – Reproductive toxins – Air contaminants that have occupational exposure

limits (PELs, TLVs) – Strong odor producers

Page 96: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 96

Risk Assessment Criteria

Fire Concern – Flammables/combustibles/toxics - amounts stored over

fire control area limits – 6 ACH at all times – Reduce amounts!

Page 97: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 97

Risk Assessment Criteria

Animal Allergen Concern Airborne Allergens (proteins) from animal dander – No exposure limits for allergens – 6+ ACH at all times in 24/7 animal areas The most allergenic animals are: – Mice – Rats – Guinea pigs

Page 98: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 98

Step 2 − Industrial Hygiene Follow-Up

Post Initial Risk Assessment • Follow-up for chemicals of concern

– Lab staff exposure monitoring studies – Work with lab staff to improve work practices

Page 99: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 99

Step 2 − Industrial Hygiene Follow-Up Post Initial Risk Assessment

• Follow-up for chemicals of concern – Ventilation reduction possible if exposures can be

controlled (improved work practices) – ACH may be increased until work practices are

improved

Page 100: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 100

High or Low Hazard Lab?

Page 101: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 101

High or Low Hazard Lab?

Page 102: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 102

High or Low Hazard Lab?

Page 103: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 103

High or Low Hazard Lab?

Page 104: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge
Page 105: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 105

Page 106: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 106

CDCV and Risk − Challenges

• Lack of “universal” CDCV sensor for all chemicals • Ongoing need for risk assessments of lab operations • Changes in research operations and staff • Incomplete chemical inventories • Great variety of hazardous operations and chemicals • Uncertainty of health effects of chemicals

Page 107: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 107

CDCV and Risk − Challenges EH&S resource demand for

– Ongoing need for hazard assessments – Exposure monitoring – Work practice corrections – Potential complaint investigations – Training

Page 108: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 108

Risk Assessment − Next Steps

• Develop system to identify changes in lab operations • Re-assess bench top operations:

– New researchers arrive – Lab moves (notification!) – Periodic re-assessments

• Promote current/complete chemical inventories

Lowered ACH is not “sustainable” without EH&S risk assessments and management of change!

Page 109: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 109

Lab ACH Reductions

Based on Risk Assessments Results to Date • 13 lab buildings (~250 labs) • 1540 lab rooms assessed • 1346 lab rooms - reduced ACH (~87%) • 194 lab rooms - not reduced ACH (~13%)

Page 110: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 110

Risk Assessment Conclusions

• Energy savings can be achieved without compromising safety

• Lab ACH determination requires: – Flexibility (evolving process) – Contaminant source control – Active EH&S involvement in risk assessment of lab

operations with lab staff – Reassessment when lab changes occur

Page 111: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 111

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 112: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

PARTICIPATORY

EXERCISE

Haaaaaa Paaaaaaa

Page 113: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 113

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 114: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 114

Low Flow/High Performance Fume Hoods

Quick Summary • Another potential solution in the energy savings tool kit • Provides the ability to add fume hoods to buildings

with limited HVAC capacity • Designed to perform at lower face velocities • Study completed to compare low flow vs. standard

fume hoods

Page 115: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 115

Fume Hood Regulations

• Federal OSHA Standard – Face velocity not specified – 13 Carcinogens exception

• Cal-OSHA Standard – 100 fpm face velocity

• Low flow fume hoods allowed in 49 states

Page 116: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 116

Traditional Hood Design

• Components & Air Flow

Page 117: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 117

Low Flow Fume Hood Design

• Components & Air Flow

Sash

UniqueAirfoil Design Deeper

Work Surface

Exhaust Plenum

Baffle

Increased Hood Depth

Advanced Baffle Design

Page 118: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 118

Study Objectives

1. Can low flow fume hoods operating at less than 100 fpm provide equal or better protection than a traditional fume hood operating at 100 fpm?

2. What is the minimum velocity and operating conditions where satisfactory performance can be confidently provided?

3. What factors affect performance? • average face velocity • turbulence of face velocity • cross draft velocity • pedestrian walk-bys

Page 119: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 119

Low-Flow Fume Hood Study Conclusions

• All hoods - performed best at 18” sash height – All tracer gas results were well under 0.1ppm “as used”

ASHRAE criteria – At 100, 80, and 60 fpm

• All low flow hoods performed better than standard hood at 80 & 100 fpm full open sash

Page 120: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Low-Flow vs. Standard Fume Hood Study Results Highest Average Concentration for Tracer Gas Tests

Page 121: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 121

Factors Affecting Performance

• Continuous cross draft (50 fpm) most impactful at 45

to hood • Walk-by drafts were less impactful • Hood placement critical to avoid cross drafts

Page 122: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 122

Low-Flow Fume Hood Next Steps

• Cal OSHA - granted UC Irvine permanent variance for use with conditions – 80 fpm average face velocity – ASHRAE 110 testing annually for 3 years, then every 3rd year

thereafter • Requesting modification to variance to allow use campus-

wide, then UC wide • Creating decision tree for use!

Page 123: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 123

Decision Tree for Low Flow Fume Hood Retrofits or Replacements

1 Does the room have more than one fume hood? Yes = potential candidate No = potential candidate— Go to question six.

2 Can the lab space accommodate the deeper footprint of a low flow hood?

Yes = potential candidate No = not a candidate— END

3 Is the building Constant Volume?

Yes = potential candidate. No = potential candidate— However, the existing hoods should have hood occupancy sensors and a control system already (such as setback or sash closers) which reduce potential savings of Low Flow Hood as a replacement for an existing hood.

4 Is the hood served by a single fan? Yes = potential candidate— Skip to question five. No = potential candidate— Skip to question eleven.

5 Is the fan belt driven? Yes = potential candidate— Go to question ten. No = Go to question seven.

6 Does the hood serve as the minimum ventilation system for the space? Yes = not a candidate— END No = potential candidate— Return to question two.

7 Does the direct drive fan have a variable speed drive? Yes = potential candidate—Skip to question nine. No = potential candidate

8 Does the direct drive fan have a throttling valve at the inlet? Yes = potential candidate No = not a candidate—END

9 Is the variable speed drive already running at minimum? Yes = not a candidate— END No = potential candidate

10 Will reducing flow adversely affect the stack discharge velocity? Yes = not a candidate— END No = candidate— END

11 Does the manifolded system have a bypass? Yes = candidate— END No = not a candidate— END

Page 124: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 124

The training session will resume in 10 minutes.

Page 125: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 125

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 126: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 126

JUST SAY NO TO BYPASS AIR Exhaust Stack Discharge Volume Reduction

Page 127: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 127

Exhaust Stack Discharge Volume Reduction (ESDVR)

What is bypass and how much energy is wasted? If so much energy is wasted, what can we do about it? Steps in the wind-tunnel study process Stack extensions Other implementation results Next steps: wind-responsive controls Participatory exercise

Page 128: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 128

What is a bypass?

The bypass brings outside air from the roof through the fan to ensure design velocity out the top of the stack regardless of flow through the building, thus creating a constant-volume system out of a variable-volume system and wasting energy.

This is a High-Plume Discharge Fan. Bypasses are also fitted to systems with other types of fans.

Page 129: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 129

Why have a bypass?

• Allows the system to operate safely and maintain a minimum velocity of discharge to ensure that the plume of air rises up sufficiently to avoid re-entrainment to the building or contamination of adjacent buildings.

• Allows constant-speed and volume fans to work with variable-volume flow from the building

• Provide a simple means of controlling static pressure in the exhaust ducting

Page 130: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Lab Exhaust Diagram

Peak Wind

Exhaust Fan Bypass Damper Plenum

Fume Hood Building Air Intake

Balcony

3500

FPM

Page 131: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 131

How much energy is wasted?

• If building flow is 25,000 cfm and required flow from the stack to attain 3,500 fpm is 50,000 cfm, the energy wasted is 50% at a minimum.

• By reducing the flow in the stack one also reduces the pressure drop in the stack and therefore the effect on energy savings is compounded.

• Each situation is specific to the site.

Page 132: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 132

If so much energy is wasted, what can we do about it?

• Detailed modeling in a wind tunnel to determine the minimum exhaust velocity required as opposed to standard practice

• Install variable-speed drives to reduce fan flow • Program control system to run multiple fans in parallel with a goal of 0%

bypass

Page 133: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

One can’t just close bypass and turn down exhaust volume. Re-entrainment at balcony

2000

-250

0 FP

M

What about closing bypass and letting fans “ride the curve”?

Peak Wind

Building air intake

Page 134: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Increase stack height

2000-2500 FPM

What about raising stack height?

Peak Wind

2000-2500 FPM Bypass closed

Page 135: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 135

Steps in the wind-tunnel study process 1. Build model of campus

Page 136: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 136

Steps in the wind-tunnel study process

1. Build model of campus 2. Install model stacks

Page 137: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Steps in the wind-tunnel study process

1. Build model of campus 2. Install model stacks

3. Install air sampling points (“receptors”)

Page 138: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 138

Flow Visualization | Natural Sciences 1

Page 139: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 139

Flow Visualization | Natural Sciences 1

Page 140: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 140

Stack Extensions

1. Extraordinary savings 1. Small costs up front 2. Passive system that has no maintenance costs 3. Reduced fan energy in one case by 78%

2. But what about the “ugliness” factor?

Page 141: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 141

The Ugliness Non-Factor: Before

Page 142: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 142

The Ugliness Non-Factor: After

Page 143: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 143

Implementation

• Install variable frequency drives (VFD)

• Close bypass dampers • No stack extension needed • Annual energy savings: 581,749 kWh

Sprague Hall

Page 144: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 144

Implementation

• Install variable frequency drives (VFD)

• Static pressure reset • 4’ stack extensions • Annual energy savings: 928,722 kWh

Natural Sciences II

Page 145: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 145

Implementation

• No stack extensions • Install variable frequency

drives (VFD) • Static pressure reset • Annual energy savings: 286,594 kWh

Hewitt Hall

Page 146: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 146

Install anemometer 2000-2500 FPM

Peak Wind

Can we do better?

2000-2500 FPM

Bypass closed or open If building flow insufficient to provide velocity needed

Page 147: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 147

No Wind Install anemometer

1500-2000 FPM

Can we do better?

Bypass closed until fans at minimum speed, then throttle As needed to maintain static pressure

Page 148: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

0102030405060708090

1 3 5 7 9 11 13 15 17 19 21 23

CFM

x 1

000

Time

Typical Design

1% Design

Required by Dispersion

Required by High Air Change Rate

Required by Low Air Change Rate

ESDVR Savings Without Wind Sensing ESDVR Energy Savings With Wind Sensing

Typical Timeline Exit Velocity Requirements

Page 149: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 149

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 150: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

PARTICIPATORY

EXERCISE

Haaaaaa Paaaaaaa

Page 151: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 151

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 152: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 152

Plug Load

• Outside the direct control of the facility manager • Growing rapidly with increases in automated lab

equipment • Control or containment? • What is your experience?

Page 153: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 153

A Pristine (Unassigned) Lab

Page 154: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 154

Page 155: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 155

Page 156: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 156

Page 157: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 157

Page 158: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 158

Page 159: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 159

Page 160: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 160

Page 161: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 161

Page 162: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 162

Page 163: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 163

Page 164: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 164

Page 165: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Haa aaaa aaa

aaaaaaaaa aaaa aaaaa

Page 166: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 166

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 167: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 167

• Air change rates (ACR) • Internal air quality (IAQ) • Sash position of each fume hood • Occupancy • Relative humidity • Temperature • Total supply • Total exhaust

CDCV System Dashboard and Data Trends for Each Zone

Page 168: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Visualization of lab HVAC use

Page 169: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

• Fume hood usage range • This hood shows usage between 0%

open and 65% open.

• Change in average sash position from the month prior • Red indicates poorer average green indicates improved

average sash management

Monitoring Fume Hood Usage

Page 170: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 170

Smart Labs are not just controls and sensors. Smart Labs provide real time feedback as well as monthly reporting data that is actionable. Return on investment is directly affected by lab practices.

How many hoods are in use right now in your lab and how far open are the sashes?

Page 171: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

0.0

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10.0

0

5,000

10,000

15,000

20,000

25,000

30,000

35,000

Sun

day

4/3

/11

18

:11

Mo

nd

ay 4

/4/1

1 2

:24

Mo

nd

ay 4

/4/1

1 1

0:5

0

Mo

nd

ay 4

/4/1

1 1

9:0

0

Tue

sday

4/5

/11

3:1

3

Tue

sday

4/5

/11

12

:38

Tue

sday

4/5

/11

20

:45

We

dn

esd

ay 4

/6/1

1 4

:55

We

dn

esd

ay 4

/6/1

1 1

4:5

6

Thu

rsd

ay 4

/7/1

1 0

:46

Thu

rsd

ay 4

/7/1

1 1

1:0

9

Thu

rsd

ay 4

/7/1

1 2

1:0

4

Frid

ay 4

/8/1

1 7

:55

Frid

ay 4

/8/1

1 1

8:2

6

Satu

rday

4/9

/11

2:3

7

Satu

rday

4/9

/11

10

:47

AC

H

CFM

Total Flow & ACHAll labs, Sunday to Saturday

Total Supply

Total ACH

Total Flow and ACH Profile Six-Day Period

Page 172: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 172

0

2

4

6

8

10

12

14

Sund

ay 4

/3/1

1 18

:11

Mon

day

4/4/

11 2

:24

Mon

day

4/4/

11 1

0:50

Mon

day

4/4/

11 1

9:00

Tues

day

4/5/

11 3

:13

Tues

day

4/5/

11 1

2:38

Tues

day

4/5/

11 2

0:45

Wed

nesd

ay 4

/6/1

1 4:

55

Wed

nesd

ay 4

/6/1

1 14

:56

Thur

sday

4/7

/11

0:46

Thur

sday

4/7

/11

11:0

9

Thur

sday

4/7

/11

21:0

4

Frid

ay 4

/8/1

1 7:

55

Frid

ay 4

/8/1

1 18

:26

Satu

rday

4/9

/11

2:37

Satu

rday

4/9

/11

10:4

7

ACH

Typical Lab flow profileSingle Lab, Sunday to Saturday

RM 1200B.RM 1200 ACH

Air Change Rates for Room 1200 Graphed Over Six Days

Page 173: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 173

The delta between 6 air changes per hour in previous labs designs and the 4/2 ACH of Gross Hall is yielding ~$58,000 per year in energy savings.

What does energy savings look like?

Page 174: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

HDP1 is a distribution board on the 1st floor. It is responsible for feeding several equipment loads, autoclave units EQ2, EQ3, and EQ4. HDP1 is fed directly from the main switchboard at 480/277 volts. The board maximum current rating is 225 amps. The largest load on HDP1 is the medium autoclave EQ2, which is rated at 75kVA.

Auto

clav

e In

Gro

ss H

all

60 kW peak

Zone-Level Resolution Can Lead to Peak Demand Savings

Page 175: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Gross Hall average site demand ranges from a baseline of 148kW to an average peak of 205 kW

Autoclave EQ2

Did running the autoclave on peak just cost you $600 in demand charges?

Zone-Level Resolution Can Lead to Peak Demand Savings

Page 176: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 176

Hewitt Hall vs. Gross Hall

Designed in 2001 • Exceeded Title 24 by 23.7% • Biomedical research • Lighting upgrade in 2009 • Exhaust stack discharge velocity

Reduction in 2009 • Re-commissioned in 2010 • 76,905 square feet

Designed in 2009 • Exceeded Title 24 by 50.4% • Biomedical research • Designated LEED Platinum - NC • 94,705 square feet

Page 177: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Gross Hall’s Lab Utilization Nearly Twice Hewitt Hall’s

0%

20%

40%

60%

80%

100%

Gross Hall Hewitt Hall

58% 27%

Percent Occupied by Building (7 days)

Page 178: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

-

1.00

2.00

3.00

4.00

5.00

6.000:

15

1:00

1:45

2:30

3:15

4:00

4:45

5:30

6:15

7:00

7:45

8:30

9:15

10:0

0

10:4

5

11:3

0

12:1

5

13:0

0

13:4

5

14:3

0

15:1

5

16:0

0

16:4

5

17:3

0

18:1

5

19:0

0

19:4

5

20:3

0

21:1

5

22:0

0

22:4

5

23:3

0

Wat

ts p

er S

quar

e Fo

ot

Time of Day

Watts / Gross Square Foot

Hewitt Hall

Gross Hall

Building Load Per Square Foot

Page 179: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Previous Best Practice

Space Type Gross Hall

0.9 watts/sqft

Offices 0.49 watts/sqft

1.1 watts/sqft

Labs

0.66 watts/sqft

1 watts/sqft

Overall Conditioned Space 0.61 watts/sqft

00.10.20.30.40.50.60.70.80.9

1

0:15

1:30

2:45

4:00

5:15

6:30

7:45

9:00

10:1

511

:30

12:4

514

:00

15:1

516

:30

17:4

519

:00

20:1

521

:30

22:4

50:

00

Wat

ts P

er S

quar

e Fo

ot

24 Hour Actual Watts Per SQFT

Hewitt Hall Watts Per Sqft Gross Hall Watts Per Sqft

02468

101214161820

0:15

1:15

2:15

3:15

4:15

5:15

6:15

7:15

8:15

9:15

10:1

511

:15

12:1

513

:15

14:1

515

:15

16:1

517

:15

18:1

519

:15

20:1

521

:15

22:1

523

:15

kW

24 Hour Demand Curves

Hewitt Hall 2nd Floor Lighting Demand

Gross Hall 2nd Floor Lighting Demand

0.3W/1000 x 8760 x$0.105kWh= $0.2759 /SqFt

Lighting

Page 180: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 180

Benchmarking It is easy to see how campus labs compare to each other but what about across the country?

http://labs21benchmarking.lbl.gov/CompareData.php

Page 181: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Adding Hewitt and Gross Halls

• Hewitt is right at the average • Gross Hall beats the most efficient lab

benchmarked by 18%

Page 182: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Lab Air Flow vs. Time • The HVAC savings of 1 CFM/ft2 at $4-5 per CFM can reduce

operational significantly. • A 1 CFM reduction at Hewitt Hall in just the open lab bays

would reduce operational cost by $83,250 per year

0.00

0.20

0.40

0.60

0.80

1.00

1.20

1.40

1.60

1.80

8/17

/11

13:4

1

8/17

/11

21:4

1

8/18

/11

5:41

8/18

/11

13:4

1

8/18

/11

21:4

1

8/19

/11

5:41

8/19

/11

13:4

1

8/19

/11

21:4

1

8/20

/11

5:42

8/20

/11

13:4

2

8/20

/11

21:4

2

8/21

/11

5:44

8/21

/11

13:4

4

8/21

/11

21:4

4

8/22

/11

5:46

8/22

/11

13:4

6

8/22

/11

21:4

6

8/23

/11

5:48

8/23

/11

13:4

8

8/23

/11

21:4

8

8/24

/11

5:49

8/24

/11

13:4

9

8/24

/11

21:4

9

8/25

/11

5:50

8/25

/11

13:5

0

8/25

/11

21:5

0

8/26

/11

5:52

8/26

/11

13:5

2

8/26

/11

21:5

2

8/27

/11

5:53

8/27

/11

13:5

3

8/27

/11

21:5

3

8/28

/11

5:55

8/28

/11

13:5

6

8/28

/11

21:5

6

8/29

/11

5:57

8/29

/11

13:5

7

8/29

/11

21:5

7

8/30

/11

5:59

CFM

/ Sq

. Ft.

CFM / Square Foot ComparisonGross Hall vs. Hewitt Hall

Gross CFM/ Sq. Ft.

Hewitt CFM / Sq. Ft.

1.53 CFM/ ft2 average.

0.52 CFM/ ft2 average.

Page 183: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

AHU + EF + Pumps + Chilled Water Building Square Feet

0

1

2

3

4

5

6

0:15

0:45

1:15

1:45

2:15

2:45

3:15

3:45

4:15

4:45

5:15

5:45

6:15

6:45

7:15

7:45

8:15

8:45

9:15

9:45

10:1

510

:45

11:1

511

:45

12:1

512

:45

13:1

513

:45

14:1

514

:45

15:1

515

:45

16:1

516

:45

17:1

517

:45

18:1

518

:45

19:1

519

:45

20:1

520

:45

21:1

521

:45

22:1

522

:45

23:1

523

:45

Wat

ts p

er S

quar

e fo

ot

Hewitt Hall Gross Hall Gross Total Building Hewitt Hall Total Building

1 Watt /1000 x 8760 hours x $0.105kWh= $0.92 /SqFt

Page 184: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 184

Comparing Two Similar Floors

Hewitt Hall – 2nd floor Gross Hall – 2nd floor

Page 185: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Lab Air Supply and Exhaust Hewitt Hall – 2nd floor • 6 Air changes per hour minimum • No set back during unoccupied periods • Zone presence sensors on fume hoods

Gross Hall – 2nd floor • 4 Air changes per hour minimum occupied • 2 Air Changes per hour minimum unoccupied • Zone presence sensors on fume hoods • Centralized Demand Controlled Ventilation

system adjusting ACH for indoor air quality.

Lab 2501 Lab 2200

Page 186: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Evidence of Where Building’s HVAC Energy Savings are Achieved

• Air change rates are dynamic responding to occupancy, IAQ, sash position, and thermal demands

• Lab 2200 averages 4 air changes per hour

• Air change rates are dependent on sash position and thermal demand.

• Lab 2501 averages 8 air changes per hour Hewitt Hall

Lab 2501

Gross Hall Lab 2200

Page 187: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 187

Continuous Commissioning

-- Meaningful analysis and reports -- Actionable information -- Verification of actions taken:

physical and behavioral

CDCV • Find failed lab air control

valves • Review of fume hood sash

management • Ensure safe lab air quality • Find excessive air flows

due to point sources of heat

Submetering • Monitoring of fans, pumps,

and lighting control systems

• Verification of energy retrofits

• Reduce demand charges by modifying operations

BMS • Locate simultaneous

heating and cooling • Reset of static pressure to

minimum required • Control run times of office

areas

Page 188: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 188

Troubleshooting a CO2 leak With the CDCV System

• Researcher connects 4 tanks of CO2 to the lab distribution system and within 8 hours they are empty.

• To find the leak the research staff could have spent hours soaping lines and connections and wasting additional gas listening for the leak.

Page 189: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 189

Suspected location of CO2 leak

Researcher first plotted all rooms for CO2

Page 190: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 190

The leak was quickly located and repaired!

Researcher Then Plotted the Room with the Suspected CO2 Leak

Page 191: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 191

The Knowledge Center has been used to locate lab equipment placed too close or under thermostats.

Discovery of Lab Equipment Driving Thermal Demand

Page 192: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 192

The training session will resume in 10 minutes.

Page 193: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 193

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 194: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 194

Return on Investment Commissioning

– Cx, Rx, MBCx is approximately $2 per SqFt – Hewitt Hall MBCx $131,309 – Net present value for 10 years (MBCx every 5 years) Hewitt Hall

$113,590

$(100,000.00)

$(50,000.00)

$-

$50,000.00

$100,000.00

$150,000.00

$200,000.00

$250,000.00

1 2 3 4 5 6 7 8 9 10 11

Cumulative Cash Flow MBCx Project

MBCx Cumulative Cash Flow MBCx Net Savings

MBCx

Page 195: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 195

$(200,000.00) $-

$200,000.00 $400,000.00 $600,000.00 $800,000.00

$1,000,000.00 $1,200,000.00 $1,400,000.00

1 2 3 4 5 6 7 8 9 10 11

Cumulative Cash Flow

Smart CCx Cumulative Cash Flow Smart CCx Net Savings

Sub metering and monitoring your lab can be very competitive with the cost of a single commissioning effort.

CDCV ~$3.12 per SqFt Sub metering $0.20 per SqFt Hewitt Hall Sub Metering and CDCV $302,888 Net present value for Hewitt Hall continuous commissioning (10 years) $665,903

Page 196: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Return on Investment Smart CCx − although a larger initial investment − provides for greater long-term savings as well as strategic analysis, monitoring, and savings that cannot be accomplished with traditional MBCx.

$(200,000.00)

$-

$200,000.00

$400,000.00

$600,000.00

$800,000.00

$1,000,000.00

$1,200,000.00

$1,400,000.00

1 2 3 4 5 6 7 8 9 10 11

Cumulative Cash Flow MBCx vs. SMART CCx

Smart CCx Cumulative Cash Flow Smart CCx Net Savings MBCx Cumulative Cash Flow MBCx Net Savings

Page 197: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 197

Results:

Laboratory Building BEFORE Smart Lab Retrofit

Name Type1

Estimated Average

ACH

VAV or CV

More efficient

than code?

Croul Hall P 6.6 VAV ~ 20%

McGaugh Hall B 9.4 CV No

Reines Hall P 11.3 CV No

Natural Sciences 2 P,B 9.1 VAV ~20%

Biological Sciences 3 B 9.0 VAV ~30%

Calit2 E 6.0 VAV ~20%

Gillespie Neurosciences M 6.8 CV ~20%

Sprague Hall M 7.2 VAV ~20%

Hewitt Hall M 8.7 VAV ~20%

Engineering Hall E 8.0 VAV ~30%

Averages 8.2 VAV ~20%

AFTER Smart Lab Retrofit

kWh Savings

Therm Savings

Total Savings

41% 60% 55%

40% 66% 47%

70% 76% 72%

48% 62% 50%

45% 81% 60%

46% 78% 62%

58% 81% 61%

58% 82% 71%

58% 77% 69%

59% 78% 61%

55% 76% 58%

Type: P = Physical Sciences, B = Biological Sciences, E = Engineering, M = Medical Sciences

Page 198: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 198

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 199: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 199

Future of Smart Labs at UC Irvine

Research and development of Smart Labs is an ongoing process that will continue to make our labs more energy efficient and safer. • Minimum Fume Hood Flow Study • LED Lighting System • New Lab Display Units

Page 200: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 200

Minimum Fume Hood Flow Study

• UC Irvine desires to reduce energy use in labs by minimizing the exhaust flow through VAV fume hoods when the sash is closed

• Evaluate whether exhaust flow can be safely reduced below current design flow of 25 cfm/ft2 of work surface

• Determine the min recommended exhaust flow for VAV hoods located throughout the UCI campus.

Page 201: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 201

AIHA/ANSI Z9.5 Laboratory Standard

• The new ANSI Z9.5 Standard recommends basing the minimum flow on the internal volume of the fume hood and internal air change per hour(ACH) where a range of 375 ACH to as low as 150 ACH is proposed

• 375 ACH is roughly equivalent to 25 cfm/ft2 and150 ACH is roughly equivalent to 10 cfm/ft2

Page 202: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 202

AIHA/ANSI Z9.5 Laboratory Standard

Safety Considerations: • The processes and materials generated within the

hoods • Hood containment and dilution of hazardous

concentrations within the hood • Potential for increased corrosion • The ability to measure and control flow • Effect on duct transport and stack discharge velocities

Page 203: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 203

Preliminary Test Results New Safe Flow Set Points

Current flow set point is 375 ACH

Minimum ACH for safe containment – ACH min

Flow reduction from design from 375 ACH

6 ft Hood A

5 ft Hood B

6 ft Hood C

5 ft Hood D

ACH Min 165 230 200 220

Flow Reduction - ACH 210 145 175 155

Page 204: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 204

Energy Savings

• To be determined over the next 6 to 12 months

Page 205: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 205

Implementation Plan

• Implement in one building • Full campus roll-out

Page 206: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 206

LED Lighting System • LED lights with integrated smart controls • Precisely control lighting levels • Occupancy, daylighting, and temperature sensors at

each fixture • Real-time energy management and reporting • Real-time monitoring of each fixture and group • Demand response capable

Page 207: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 207

LED lighting fixtures • Pendant Mount

• 2x2 or 2x4 • Can

Page 208: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 208

LED Lighting System

• Real time and historic monitoring

• Trend energy use • Failure Notfication

Page 209: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 209

Lab Display Units

UCI working with CalIT2 are developing a new LDU that displays – Ventilation Data – Environmental Health and Safety Hazard and Emergency Information – Energy Saving Tutorial

Page 210: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 210

Lab Display Units

Touchscreen Android based display Graphical output of any Bacnet point Capable of showing • Training videos • Chemical

inventories • Scheduling • Contact

information

Page 211: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 211

Today’s Agenda

• Welcome and Introductions • UC Irvine’s Smart Labs Initiative • Introduction to Smart Labs • Prerequisites for Smart Labs • Submetering • Smart Labs Characteristics

– Building Envelope – Lighting

Participatory Exercise • BREAK

– Mechanical System • Centralized Demand

Controlled Ventilation • Lab Bench Top Risk

Assessment • Participatory Exercise

• Low-Flow Fume Hoods • BREAK • Exhaust Stack Discharge Volume

Reduction – Participatory Exercise

• Plug Load • Dashboards and Energy Savings • BREAK • Return on Investment and

Commissioning • The Future of Smart Labs • Conclusion and Wrap-Up

Page 212: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Smart Lab Energy Design Parameters Parameters/Features Recent Best Practices Smart Lab

Air-handler/filtration airspeeds 400 ft./min. max. 350 ft./min. max.

Total system (supply + exhaust) pressure-drop ~6 in.w.g. <5 in.w.g.

Duct noise attenuators Few None

Occupied lab air-changes/hr. (ACH) 6 ACH 4 ACH w/contaminant sensing

Unoccupied air-change setback No setback 2 ACH w/contaminant sensing + reduced

thermal inputs while building “coasts” during setback

Low-flow/high-performance fume hoods and/or automatic sash-closers No Yes, where hood density warrants

Exhaust stack discharge velocity ~3,000 FPM

No fixed standard; building-by-building analysis typical

1,000-1,500 FPM >1,500 FPM only if/when necessary to

avoid re-entrainment

Lab illumination power-density ~.9 watt/SF <.6 watt/SF w/LED task lighting where needed

Fixtures near windows on daylight sensors No Yes

ENERGY STAR freezers and refrigerators Some Most

Outperform CA Title 24 20-25% >50%

Page 213: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 213

Smart Labs Summary

Reduce building energy consumption by ~50% Reduce air changes with CDCV Reduce illumination power density Reduce building exhaust discharge air speeds Increased staff oversight Increased mechanical repairs to more complex systems Increased software updates/adjustments to control

systems Increased EH&S oversight of labs Significant energy $avings

Page 214: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

Page 214

Revisiting the Learning Outcomes

1. Why focus on laboratories? 2. Can we afford a “smart lab” retrofit? 3. Are savings greater than 50% really possible? 4. Can these savings only be realized with new

construction? 5. Can we afford to keep a “smart lab” smart? 6. What if our energy costs differ from those in

California?

Page 215: Safely Cut Your Laboratory Energy Usage in Half · Safely Cut Your Laboratory Energy Usage in Half . Page 2 . Your Presenters • Wendell C. Brase . ... • Exhaust Stack Discharge

QUESTIONS? Wendell Brase Matt Gudorf Marc Gomez David Kang Fred Bockmiller