Upload
others
View
25
Download
1
Embed Size (px)
Citation preview
Safety Manual
Series 854 ATG/XTG level gauges
Table of Contents
Part No.: 4417808_Rev01 854 ATG/XTG level gauge
Safety Manual i
CHAPTER 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1 About this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1.1 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1.2 Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1.3 Related Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.2 Basic Skills and Knowledge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.3 Safety Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.3.1 Safety Instrumented Systems, Functions and Integrity Levels . . . . . . . . . . . 1-2
1.3.2 What standard to use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
CHAPTER 2 Functions, Architecture and Compliance . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.1 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.2 Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.3 Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.4 Safety-related Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.5 Safety Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.5.1 Safety design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.5.2 Technical Data Servo 845 ATG/XTG. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.6 Servo Auto Test 854 ATG/XTG. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.6.1 Principle of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2.7 Fault Detection and Reaction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
CHAPTER 3 Implementation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.2 Assumptions and Constraints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.3 New Installation or Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.3.1 New Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.3.2 Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.4 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.4.1 Hardware Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.4.2 Software Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.4.3 Configuration – Servo Auto Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3.4.4 Configuration – Alarm Relay setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3.4.5 Configuration – Analog level output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
3.5 Verification of the Safety Instrumented Function(s) . . . . . . . . . . . . . . . . 3-7
CHAPTER 4 Maintenance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.2 Diagnostic items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.3 Proof Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Table of Contents
854 ATG/XTG level gauge
Safety Manual
Part No.: 4417808_Rev01
ii
Introduction
Part No.: 4417808_Rev01 854 ATG/XTG level gauge
Safety Manual 1 - 1
CHAPTER 1 INTRODUCTION
1.1 About this Manual
1.1.1 Purpose
The Safety Manual provides information about the 854 ATG/XTG level
gauge that is relevant for integration of this servo-based level gauge
into a Safety Instrumented System (SIS). This manual is aimed at
technical personnel responsible for such integration.
1.1.2 Content
Chapter Title Contents Description
Introduction This chapter.
Functions, Architecture and
Compliance
Specification of the Safety Instrumented Functions (SIF) that are applied and the
architecture(s) these SIFs need to operate. Furthermore relevant certification and
compliance information is given.
Implementation Description of - or reference to - details how to achieve and implement the applicable
SIFs.
Maintenance Requirements Description of - or reference to - details how to maintain the required Safety Integrity
Levels of the implemented SIFs.
1.1.3 Related Documents
• IEC 61508 (2010),
• IEC 61511 (2004),
• Instruction Manual Series 854 ATG level gauge; Part No.: 4416220,
• Installation guide 854 ATG level gauge; Part No.: 4416225,
• Instruction Manual Series 854 XTG level gauge; Part No.: 4416275,
• Installation guide 854 XTG level gauge; Part No.: 4416276,
• Instruction Manual SPU II Hard Alarm Contacts; Part No.: 4416223,
• Instruction Manual spot temperature and analog output; Part No.:
4416644.
1.2 Basic Skills and Knowledge
Before you start to work on the 854 ATG/XTG level gauge it is assumed
that you are certified to do work on safety related systems and devices
(i.e. certified Enraf Service Specialist), and that you have appropriate
knowledge of:
• The concepts and functioning of the 854 ATG/XTG level gauge,
• The applicable process and equipment under control within the SIS,
• This Safety Manual,
• Site procedures,
• Applicable safety standards (e.g. IEC 61508 and IEC 61511).
Introduction
854 ATG/XTG level gauge
Safety Manual
Part No.: 4417808_Rev01
1 - 2
1.3 Safety Standards
1.3.1 Safety Instrumented Systems, Functions and Integrity Levels
Processes and Equipment Under Control (PUC/EUC) in the process
industry require a high level of safety. Safety Instrumented Systems
(SIS) are used to perform Safety Instrumented Functions (SIF).
Instrumentation that is used for SIFs, must meet minimum standards
and performance levels. Standards like IEC 61508 and IEC 61511 have
been developed for this purpose. One of the performance criteria that
these standards apply is the Safety Integrity Level (SIL).
IEC 61508 details the design requirements for achieving the required
SIL. The safety integrity requirements for each individual safety function
may differ. The safety function and SIL requirements are derived from
hazard analyses and risk assessments. The higher the level of adapted
safety integrity, the lower the likelihood of dangerous failure of the SIS.
These standards also address the safety-related sensors and final
elements regardless of the technology used.
The 854 ATG/XTG level gauge can be used for a specific SIF that
demands SIL 1 or SIL 2 (HFT = 0). If used in a redundant
arrangement, the 854 ATG/XTG level gauge can be applied in safety
loops that require SIL 3 (HFT = 1).
1.3.2 What standard to use
IEC 61508 has been developed as a generic standard. A framework of
standards, incl. IEC 61511, for specific industry sectors were based on
this one. The information in the table below is meant as a guideline.
Standard Typical application within the process industry
IEC 61508
Functional safety of electrical /
electronic / programmable
electronic (E/E/PE) safety-
related systems
If you are a manufacturer, it is strongly recommended that you apply the IEC 61508.
This generic standard is intended to provide guidance on how to develop E/E/PE
safety-related devices as used in Safety Instrumented Systems (SIS).
The IEC 61508 serves as a basis for the development of sector standards (e.g. for
the machinery sector, the process sector, the nuclear sector, etc.).
It can serve as stand-alone standard for those sectors where a sector specific
standard does not exist.
IEC 61511
Functional safety - Safety
instrumented systems for the
process industry sector
If you are an owner/user, it is strongly recommended that you apply the IEC 61511.
This standard addresses the application of SISs for the process industries. It requires
a process hazard and risk assessment to be carried out, to enable the specification
for SISs to be derived.
In this standard a SIS includes all components and subsystems necessary to carry
out the safety instrumented function from sensor(s) to final element(s).
The standard is intended to lead to a high level of consistency in underlying
principles, terminology and information within the process industries.
This should have both safety and economic benefits.
Functions, Architecture and Compliance
Part No.: 4417808_Rev01 854 ATG/XTG level gauge
Safety Manual 2 - 1
CHAPTER 2 FUNCTIONS, ARCHITECTURE AND COMPLIANCE
2.1 Functions
Beside its standard functions the 854 ATG/XTG level gauge can also be
used for a Safety Instrumented Function (SIF) for storage tanks in the
oil and gas industry. This function is:
• the SIL compliant “overfill protection” and/or “underfill protection”.
To establish that the safety parameters for this function of the 854 ATG/
XTG level gauge are in the range of SIL 2, it is necessary to:
• use the correct architecture; see chapter 2.2 "Architecture",
• apply the function correctly; for further details see,
• chapter 3 "Implementation",
• chapter 4 "Maintenance Requirements".
2.2 Architecture
“Overfill protection” and/or “underfill protection” in the range of SIL 2
for the 854 ATG/XTG level gauge can be established with the
standard architecture. However, specific hardware and software
requirements do apply; for further details see chapter 3.4
"Configuration".
2.3 Compliance
Organization Relevant details
The 854 ATG/XTG level gauge is considered to be a Type B system in the meaning of
IEC 61508. If implemented and maintained correctly, the safety parameters for the
“overfill protection” and/or “underfill protection” are in the range of SIL 2.
Details of the assessment and certification by TÜV Rheinland are recorded in:
Report No. V 56.05/14
Certificate No. V 56.05/14
Functions, Architecture and Compliance
854 ATG/XTG level gauge
Safety Manual
Part No.: 4417808_Rev01
2 - 2
2.4 Safety-related Data
The table below specifies the applicable data relating to IEC 61508:
Entity / parameter Value Remarks
Safety Integrity Level SIL 2 As single channel safety related subsystem. With a
structure establishing a hardware fault tolerance of 1
the device is usable in SIL 3 applications.
Classification of the device Type B
Mode of operation Low demand mode High demand mode Continuous operation
Acc. to IEC 61508-4, 3.5.16 and
Acc. to IEC 61511-1, 3.2.43,2
Probability of Dangerous Failure on Demand
PFDavg = 5.48E-05
For the calculation of PFDavg an assumed test interval of
Ti = 1 year has been assumed *1
Hardware fault tolerance HFT 0
Diagnostic coverage DC 90 %
Safe Failure Fraction (SFF) SFF = 92.7 % *2
Probability of Failure per Hour PFH = 1.25E-08 1/h
MTBF dangerous failures MTBFD 8.00E07 h 9132 y
Dangerous failure rate λD = 1.13E-07 1/h 113 FIT
Safe failure rate λS = 4.62E-08 1/h 46 FIT
Total Failure Rate λD + λS = 1.71E-07 1/h
59 FIT
MTBF total 5.84E+06
667 y
Proof Test Interval To be defined Refer to Figure 2-1.
*
1) If other proof test interval shall be used, the diagram (Figure 2-1) shows how the PDFavg is related to Ti.
*2) The SFF takes into account the failure detection provided by all mechanical, electronics and software
components of the device.
TABLE 2-1 Safety-related data
FIGURE 2-1 PDFavg over Ti
Functions, Architecture and Compliance
Part No.: 4417808_Rev01 854 ATG/XTG level gauge
Safety Manual 2 - 3
2.5 Design and technical input
2.5.1 Safety design
FIGURE 2-2 shows a schematic diagram of the SIL compliant design.
The SIL compliant design comprises of the optional 2 hardware alarm
relay output contacts, located on the SPU II board (Servo Processing
Unit), and/or the 4-20 mA analog level output, which circuit is located on
the HCU option board.
FIGURE 2-2 Safety design
The servo board controls the position of the displacer and thereby
‘measures’ the product level. Via the IPC (Inter Processor
Communication) bus, the level information is transferred to the XPU 2
board and the Option board. Continuous checks on the validity of the
level value by checking on the correct position of the drum & stepper
motor, guarantees a high diagnostic coverage (DC = 90%).
The 2 x SPDT relay contacts can activate at high level threshold setting
(overfill protection), or low level threshold setting (underfill protection).
Refer to section 3.4.2 Software configuration).
The 4-20 mA analog level output is a passive output, which means it
requires an external DC supply voltage between 12 and 64 V. As the
4-20 mA signal reflects the level value, the threshold setting on overfill
or underfill value must be made in the logic solver.
Functions, Architecture and Compliance
854 ATG/XTG level gauge
Safety Manual
Part No.: 4417808_Rev01
2 - 4
2.5.2 Technical Data Servo 854 ATG/XTG
Parameter Range
Allowable differential Pressure Max. 40 bar (4 MPa, 580 psi) (model dependent)
Temperature: Process
Ambient
-200 °C to + 200 °C (-328 °F to +392 °F)
-40 °C to + 65 °C (-40 °F to +149 °F)
TABLE 2-2 Technical Data Servo 854 ATG/XTG
To establish SIL compliant “overfill protection” and/or “underfill protection” a sophisticated diagnostic test has been developed to
prove that the gauge is able to measure an upward and/or downward
movement of the product, reliably and covering the diagnostics.
This test is called the Servo Auto Test 1, and can be executed
automatically at a user defined interval. It can also be prompted by a
dedicated command for Proof Test purposes. Provided the required
configuration is established, the user can set this test to application
needs.
1. The “Servo Auto Test” feature is covered by U.S.
Patent No. 8,997,549 and other patents pending.
2.6 Servo Auto Test 854 ATG/XTG
The Servo Auto Test makes use of the existing “Principle of
measurement” as described in the Instruction Manual, and has the
following features:
• it is executed automatically and autonomously,
• it is executed immediately after tank loading, as this is a critical
moment,
• it is executed at regular intervals to prove that the moving parts of the
gauge can move as intended,
• in case of a detected failure,
• the appropriate alarm is initiated,
• the applicable hardware relays are activated/de-activated
(depending on the mode),
• during execution the display shows only the asterisk sign (*) in the level status, all other effects of the test are hidden,
• i.e. level and relays,
• for installed equipment (e.g. CIU’s) and systems,
• the installed base can be upgraded (for applicable prerequisites see
chapter 3.3 "New Installation or Upgrade").
Functions, Architecture and Compliance
Part No.: 4417808_Rev01 854 ATG/XTG level gauge
Safety Manual 2 - 5
2.6.1 Principle of Operation
Starting from the situation that the displacer (D) is in rest at the product
level (PL), the Servo Auto Test consists of these basic steps:
1. The displacer is raised over
a configurable distance
(cd).
2. The wire tension (wt) is
measured while the
displacer is being raised.
3. Appropriate actions are
initiated, only in case the
wire tension exceeds the
predetermined limit (X)
caused by a mechanical
obstruction.
4. The displacer is lowered to
the product level.
NOTE: The duration of a Servo Auto Test mainly depends on
the configuration settings.
A typical Servo Auto Test running at default settings
may take approximately 15 seconds.
FIGURE 2-3 shows a graph that represents the actual and measured
product levels. The latter in fact is the level of the displacer. The displacer level correctly follows the actual product level, while at set intervals a Servo Auto Test occurs. This indicates that the level gauge is in a healthy state and the moving parts of the gauge can move as intended.
The Servo Auto Test occurrences take place at a set interval when the
product level is stable, or assumed to be stable. This is the case at
product levels PL1 and PL2. During tank filling the Servo Auto Test is
temporarily disabled. After end of filling is detected a certain time lapse (tl) passes 1 before the Servo Auto Test is started again. Afterwards Servo Auto Test occurrences take place at the set interval again.
1. For details about parameters and settings
refer to chapter 3.4.2 "Software Configuration"
Functions, Architecture and Compliance
854 ATG/XTG level gauge
Safety Manual
Part No.: 4417808_Rev01
2 - 6
The product level (PL) is shown as a function of time
where PL1 is the initial stable level and PL2 is the stable
level after the tank was filled.
FIGURE 2-3 Servo Auto Test occurrences
2.7 Fault Detection and Reaction
During a Servo Auto Test fault detection is conducted as follows:
1. in case the wire tension exceeds its predetermined limit while the
displacer is raised, the displacer cycle is interrupted;
the displacer will be lowered to the product level;
2. a second displacer cycle is started;
in case this cycle is also interrupted the displacer will be lowered to
the product level again;
3. a third displacer cycle is started; in case this cycle is also interrupted the displacer will remain at the
blocked level;
4. a failure state has now occurred.
Functions, Architecture and Compliance
Part No.: 4417808_Rev01 854 ATG/XTG level gauge
Safety Manual 2 - 7
Upon a fault detection the 854 ATG/XTG level gauge will initiate fault
reaction as follows:
• relevant product levels are set to “fail” in their corresponding protocol
records (B, D, ZLQ); other product levels keep their last recorded values (innage, ullage
and corrected product levels),
• all product level statuses are set to “fail”,
data item [ES] (Error SPU request) is set to code 0607 (Servo Auto Test
fail),
relays (if present) are set in accordance with their “gauge fail” status
configuration,
• the displacer is kept at the blocked level,
• new gauge servo commands are not executed, unless the gauge is
in maintenance mode.
NOTE: Be aware that the cause of a failure must be
removed before you reset the gauge. Otherwise the
gauge will come into a fail state again.
The fail state of the 854 ATG/XTG level gauge due to a Servo Auto Test
failure ends when one or more of these actions occur:
• the user initiates a reset directly via the reset command (item [RS]),
• the user initiates a reset indirectly via the exit command (item [EX]),
• a power down / power up sequence.
Two typical fault situations exist in which faults are detected as
described above. Figures 2-4 and 2-5 both show a graph that also
represents the actual product level and the displacer level. Each figure
shows a typical situation. They represent identical failure states - under
different conditions - as a result of a mechanical obstruction.
Functions, Architecture and Compliance
854 ATG/XTG level gauge
Safety Manual
Part No.: 4417808_Rev01
2 - 8
FIGURE 2-4 shows fault situation 1 (FS1). The product level is raising
due to tank filling. Before it actually stops, end of filling is detected as a
result of an obstruction. After a certain time lapse (for details see 3.4.2)
a Servo Auto Test is initiated and the wire tension exceeds the limit in
three subsequent attempts. One of the results of the fault reaction is
that filling is stopped. In this situation PL2 represents the intended
product level after filling.
FIGURE 2-4 Failure State example - during tank filling
FIGURE 2-5 shows fault situation 2 (FS2). The product level is stable, in
this case at PL2. The Servo Auto Test is initiated at set intervals. During
a Servo Auto Test the wire tension exceeds the limit in three
subsequent attempts.
FIGURE 2-5 Failure State example - product level is stable
Part No.: 4417808_Rev01 854 ATG/XTG level gauge
Safety Manual 3 - 1
Implementation
CHAPTER 3 IMPLEMENTATION
3.1 General
This chapter provides the information that is relevant for correct
implementation of the safety-related function(s) of the 854 ATG/XTG
level gauge.
3.2 Assumptions and Constraints
The user must install, implement and use the 854 ATG/XTG level gauge
according to the conditions that are specified in this manual. The SIL
compliant “overfill protection” and/or “underfill protection” will operate as
intended when:
• the standard architecture is present,
• the correct configuration is installed and commissioned.
Any servo-based level gauge of the type 854 ATG/XTG level gauge that
does not comply with these features cannot be used for this purpose.
3.3 New Installation or Upgrade
3.3.1 New Installation
In case you have purchased an 854 ATG/XTG level gauge that is
suitable for SIL compliant “overfill protection” and/or “underfill
protection”, this function is included by design. This means that the
required architecture, hardware and software are present in the device.
Correct implementation of the function is obtained by setting the
required configuration during commissioning.
3.3.2 Upgrade
In case you own an 854 ATG/XTG level gauge, the SIL compliant
“overfill protection” and/or “underfill protection” can be included by
upgrading the device. By ordering the option for SIL compliant “overfill
protection” you will receive the required features. Implementation of the
upgrade needs to be done by a qualified Service Engineer.
Implementation of the upgrade implies:
• for models that have an XPU-2 board installed, a firmware update
(EPROM) is required,
• for models that have an XPU-1 board installed, this must be replaced
by an XPU-2 board including firmware (EPROM),
• for models that have an SPU-2 board without Alarm relays installed, this must be replaced by an SPU-2 board with Alarm relays if SIL is required by relay contact.
854 ATG/XTG level gauge
Safety Manual
Part No.: 4417808_Rev01
3 - 2
Implementation
• for models that have no HCU board or HCU board without analog level output installled, this must be replaced by an HCU board with analog level output if SIL is required by analog level output.
• “commissioning” is done according to the instructions in the
854 ATG/XTG level gauge Instruction Manual.
3.4 Configuration
Hardware and software features contribute to the SIL compliant “overfill
protection” and/or “underfill protection”. TABLE 3-1 specifies the
relevant boards the 854 ATG/XTG level gauge must consist of and the
relevant firmware. Further details are described in the next paragraphs.
3.4.1 Hardware Configuration
This paragraph describes aspects of the design and integration of the
applicable hardware. The required hardware configuration of the 854
ATG/XTG level gauge is achieved by correct use of the specified
hardware elements (see TABLE 3-1). No further requirements apply to
the hardware configuration.
Board type Revision Firmware Version
XPU-2 current EPROM ≥ H2.8
SPU-1 current No density option ≥ A2.3
With density option ≥ C2.3
SPU-2 1 current No density option ≥ B2.3
With density option ≥ D2.3
HCU 2 current With Analog output ≥ A2.2
1. SPU-2 board is used, when SIL function is achieved through alarm relays. 2. HCU board is used, when SIL function is achieved through the analog level output. HCU board can be used in combination with SPU-1 or
SPU-2 board.
TABLE 3-1 Required boards and firmware
3.4.2 Software Configuration
The following paragraphs describe the steps to achieve the correct
software configuration of the 854 ATG/XTG level gauge. They are:
• execution of the software settings (commissioning), • configuration Servo Auto Test (refer to 3.4.3)
• configuration Relay contacts (refer to 3.4.4) • configuration Analog level output (refer to 3.4.5)
• verification of the function (refer to 3.5).
Part No.: 4417808_Rev01 854 ATG/XTG level gauge
Safety Manual 3 - 3
Implementation
3.4.3 Configuration – Servo Auto Test
To guarantee correct functioning of the “overfill protection” and/or “underfill protection” the Servo Auto Test configuration parameters must be set correctly.
TABLE 3-2 provides an overview of the applicable items and their
settings for configuration (N/A means: not applicable).
Item Description Default 1 Min - Max values 1 Eng. unit 2 Prot. level 3
[SE] Servo Auto Test enabled <E> N/A N/A 1
[SH] Servo Auto Test raise height +000.0200 +000.0100 - +000.2500 see [LD] 2
[SI] Servo Auto Test interval time 00060 00001 - 40320 minutes 1
[SY] Servo Auto Test invalidates
display and level
<N> N/A N/A 1
[XI] Servo Auto Test level movement
detector sample interval
60 10 - 200 seconds 1
[XT] Servo Auto Test level movement
detector trip distance
+000.0030 +000.0010 - +000.3000 see [LD] 1
1. Values for heights and distances are given in meters.
2. LD is the standard item to set the Level Dimension:
(M = metres; F = feet; I = inches; P = fractions).
3. Protection levels are provided for all items, depending
on the importance of an item.
TABLE 3-2 Software settings (servo auto test)
Relevant configuration details per item are described below.
Item [SE].
In case compliant “overfill protection” is required the default value <E>
must be kept. In case this function is not required set the value to <D>.
Items [SH] and [SI]. The default settings provide for most common applications. The user
can adapt the values in accordance with application or process needs.
Item [SY].
With this item the visibility of Servo Auto Test details on a display and
host system is controlled. Preferably the default value <N> of this item is
kept. If the value is set to <Y> the host system can show that the gauge
is in test.
854 ATG/XTG level gauge
Safety Manual
Part No.: 4417808_Rev01
3 - 4
Implementation
Items [XI] and [XT].
These items are related to the movement detector that samples the
level in the tank at regular intervals. They are also closely related to
each other. They are used to determine if the product level in a tank is
stable or moving.
With item [XI] the user determines the time between two consecutive
samples by the movement detector. Item [XT] represents the trip
distance. If the absolute difference between two samples exceeds the
trip distance it is assumed that the tank is being loaded or unloaded.
This movement detection is necessary to disable the Servo Auto Test
during loading and unloading of the tank. It is also used to determine
that the product movement stops and a Servo Auto Test can be initiated
again. Detection takes place after a certain time lapse. In theory the minimum
time lapse is zero (0) seconds and the maximum time lapse is 2 x [XI].
Although the default values for items [XI] and [XT] are based on field data
and experience, they cannot be automatically used. As circumstances
of different tank systems can strongly vary, appropriate values have to
be determined for any specific system.
It is advised to follow the steps below in the given order to determine the
values for these items to avoid over or underrated responses.
1. Determine the maximum deviation of the measured product level in
the tank when the product level is stable (PLSTAB-Δ), i.e. no loading or
unloading. Level deviations can occur due to weather conditions,
e.g. wind on a floating roof tank system.
2. Set the value of item [XT] in the engineering units of the gauge so that
it equals: PLSTAB-Δ + 1 mm.
3. Determine the average product level increase per second during
loading of the tank in the engineering units of the gauge. This is
variable A.
4. Calculate item [XI] as follows: [XI] = [XT] / (1/2 A).
The greater the value for item [XI] the longer it will take before the Servo
Auto Test is executed after tank loading is finished. Preferably, this
period must be as short as possible to prevent tank overfill due to a
mechanical obstruction.
This effect occurs because tank loading and unloading does not start
and stop suddenly. If these would occur abruptly parts of the tank
system can get damaged (e.g. pipes). Therefore opening and closing of
valves and starting and stopping of pumps is done gradually.
Part No.: 4417808_Rev01 854 ATG/XTG level gauge
Safety Manual 3 - 5
Implementation
3.4.4 Configuration – Alarm relay setting
TABLE 3-3 provides an overview of the applicable items and their settings for configuration (N/A means: not applicable).
Item Description Default 1 Min - Max values 1 Eng. unit 2 Prot. level 3
[AH] Level alarm hysteresis +000.0100 -999.9999 - +999.9999 see [LD] 1
[HA] High level alarm +026.0000 -999.9999 - +999.9999 see [LD] 1
[HH] High high level alarm +026.1000 -999.9999 - +999.9999 see [LD] 2
[LA] Low level alarm +002.0000 -999.9999 - +999.9999 see [LD] 1
[LL] Low low level alarm +001.9000 -999.9999 - +999.9999 see [LD] 1
[RY] Relay alarm mode <HA-LA-> N/A N/A 2
[RZ] Relay mode <DEDE> N/A N/A 2
1. Values for heights and distances are given in meters.
2. LD is the standard item to set the Level Dimension:
(M = metres; F = feet; I = inches; P = fractions).
3. Protection levels are provided for all items, depending
on the importance of an item.
TABLE 3-3 Software settings (alarm relay settings) Relevant configuration details per item are described below.
Item [AH]. With this item a hysteresis is set around the alarm value. The default setting is 10 mm; in case of very turbulent product surface conditions, the hysteresis value can be set larger.
Item [HA]. With this item a high level alarm set point is given. Depending on the
setting of item [RY], this can be used in the “overfill protection”.
Item [HH]. With this item a high high level alarm set point is given. Depending on
the setting of item [RY], this can be used in the “overfill protection”.
Item [LA]. With this item a low level alarm set point is given. Depending on the
setting of item [RY], this can be used in the “underfill protection”.
Item [LL]. With this item a low low level alarm set point is given. Depending on the
setting of item [RY], this can be used in the “underfill protection”.
Item [RY].
This item ‘links’ two of the setting of items [HA], [HH], [LA] and [LL] to the
two alarm relays and defines the alarm mode.
The first three characters are related to alarm relay 1 and the last three
characters are related to alarm relay 2.
854 ATG/XTG level gauge
Safety Manual
Part No.: 4417808_Rev01
3 - 6
Implementation
The linking is straight forward: characters 1 and 2 (for alarm relay 1) and
characters 4 and 5 (for alarm relay 2) contain the alarm setting
according the item notation: HA, HH, LA or LL.
The alarm mode in character 3 (for alarm relay 1) and 6 (for alarm
relay 2) is one of the following characters with the meaning:
• T relay will always be active if alarm level is reached.
• - relay will only be active if alarm level is reached and there is no
test status active.
• W relay will only be active if alarm level is reached and there is no
test status active and there is no water dip measurement active.
Item [RZ]. This item defines the relay mode as follows:
Character 1 (for alarm relay 1) and character 3 (for alarm relay 2) sets
the operational mode: • E normally energized
• D normally de-energized
For safe fail operation, the normally energized operation mode must be
selected.
Character 2 (for alarm relay 1) and character 4 (for alarm relay 2) sets
the fail mode: • E energize relay on gauge fail
• D de-energize relay on gauge fail
For safe fail operation, the de-energized fail mode must be selected.
A fail safe operation of the alarm relay is obtained by using the Normally
Closed relay contact in combination with the Normally Energized
operation mode.
3.4.5 Configuration – Analog level output
TABLE 3-4 provides an overview of the applicable items and their settings for configuration (N/A means: not applicable).
Item Description Default 1 Min - Max values 1 Eng. unit 2 Prot. level 3
[AM] Analog 4 mA level +000.0000 -999.9999 - +999.9999 see [LD] 1
[AN] Analog 20 mA level +000.0000 -999.9999 - +999.9999 see [LD] 1
[AK] Analog output mode <D> N/A N/A 1
1. Values for heights and distances are given in meters.
2. LD is the standard item to set the Level Dimension:
(M = metres; F = feet; I = inches; P = fractions).
3. Protection levels are provided for all items, depending
on the importance of an item.
TABLE 3-4 Software settings (analog level output)
Part No.: 4417808_Rev01 854 ATG/XTG level gauge
Safety Manual 3 - 7
Implementation
Relevant configuration details per item are described below.
Item [AM]. This item contains the level value which must correspond to 4 mA.
Item [AN]. This item contains the level value which must correspond to 20 mA.
Item [AK]. This item selects under what conditions the analog output current will
operate. It contains one character and means:
• L Iout is set to 3.5 mA in case of invalid level or level fail and no
last valid level available.
• M Iout is set to 22 mA in case of invalid level or level fail and no last
valid level available.
• A Iout is set to 3.5 mA in case of level fail.
• B Iout is set to 22 mA in case of level fail.
• I Iout is set to 3.5 mA in case of level fail and invalid level.
• J Iout is set to 22 mA in case of level fail and invalid level.
When none of the above conditions is met with settings L, M, A, B, I or
J, the output current (Iout) reflects the level value.
The recommended fail safe condition for the analog output is with
setting I or J.
3.5 Verification of the Safety Instrumented Function(s)
To verify the correct functioning of the “overfill protection” and/or
“underfill protection” function, carry out the procedure of chapter 4.3
"Proof Testing".
854 ATG/XTG level gauge
Safety Manual
Part No.: 4417808_Rev01
3 - 8
Implementation
Maintenance Requirements
Part No.: 4417808_Rev01 854 ATG/XTG level gauge
Safety Manual 4 - 1
CHAPTER 4 MAINTENANCE REQUIREMENTS
4.1 Purpose
This chapter provides the information that is relevant for correct
maintenance of the safety-related function(s) of the 854 ATG/XTG level
gauge.
4.2 Diagnostic items
To determine correct functioning of the “overfill protection” and/or “underfill protection” with the Servo Auto Test a number of diagnostic items are available.
TABLES 4-1 till 4-3 provides an overview of the applicable diagnostic
items and their corresponding value ranges (N/A means: not
applicable).
Item Description Default 1 Min - Max values 1 Eng. unit 2 Prot. level 3
[PE] Level at which the Servo Auto
Test last failed
+999.9999 +999.9999 - +999.9999 see [LD] 1
[PL] Level at which the Servo Auto
Test was last executed
+999.9999 +999.9999 - +999.9999 see [LD] 1
[PX] Minimum level at which the
Servo Auto Test was performed
+999.9999 +999.9999 - +999.9999 see [LD] 1
[PY] Maximum level at which the
Servo Auto Test was performed
+999.9999 +999.9999 - +999.9999 see [LD] 1
[PZ] Highest number of Servo Auto
Test retries
0 0 - 9 N/A 1
[SN] Number of executed Servo Auto
Tests
00000 00000 - 99999 N/A 0
[SQ] Servo Auto Test status N/A N/A N/A 0
[SZ] Time elapsed since last Servo
Auto Test
00000 00000 - 99999 minutes 0
1. Values for heights and distances are given in meters.
2. LD is the standard item to set the Level Dimension:
(M = metres; F = feet; I = inches; P = fractions).
3. Protection levels are provided for all items, depending
on the importance of an item.
TABLE 4-1 Diagnostic parameters (related to Servo Auto test)
Maintenance Requirements
854 ATG/XTG level gauge
Safety Manual
Part No.: 4417808_Rev01
4 - 2
Item Description Default Min - Max values Eng. unit Prot. level 1
[RX] Relay status - - N/A N/A 0
[ES] Error SPU request 0000 0000 - 0999 N/A 0
1. Protection levels are provided for all items, depending
on the importance of an item.
TABLE 4-2 Diagnostic parameters (related to Alarm relays)
Item Description Default Min - Max values Eng. unit Prot. level 1
[AO] Analog output current @+.00000000E+00 @+.35000000E+01 –
@+.22000000E+02
mA 0
[AQ] Analog output status 0 N/A N/A 0
[EA] Error analog output xx00 2200 - 3399 N/A 0
1. Protection levels are provided for all items, depending
on the importance of an item.
TABLE 4-3 Diagnostic parameters (related to Analog level output)
Relevant details about these diagnostic items are described in chapter
4.3 "Proof Testing".
4.3 Proof Testing
To make sure that the safety rated loops remains SIL compliant a proof
test has to be performed. For proof test interval refer to chapter 2.4 and
Figure 2-1.
Points of attention:
• For Proof Testing opening of the 854 ATG/XTG is not required
unless test results or other findings demand internal maintenance
and/or repair.
• Proof Test procedure can be performed by Service Engineer from:
• the control system, using available diagnostic tools, such as
Engauge,
• as an alternative at the gauge, using a Portable Enraf Terminal
(PET).
• It is advised to compare the test results with historic data, if available.
In this way trends in behavior can be determined.
Maintenance Requirements
Part No.: 4417808_Rev01 854 ATG/XTG level gauge
Safety Manual 4 - 3
Follow the steps below in the sequence given:
1. Determine that the examined gauges are certified for SIL compliant
“overfill protection” and/or “underfill protection”. If not OK - contact plant management for further action.
If OK - continue with the next step.
2. Determine the actual status and values of the relevant configuration
items for each gauge (refer to TABLES 3-2 and/or 3-3 and/or 3-4).
Record this data for later reference.
Make sure that the values of the configuration items comply with the
settings as conducted during commission and/or approved changes.
Pay special attention to item [SE] ‘Servo Auto Test enabled’; this
should have the default value [E], enabled. If not OK - contact plant management for further action.
If OK - continue with the next step.
3. Perform functional and performance test of the gauge in following
steps:
• Repeatability test,
• Balance test,
• Check status of servo auto test related items,
• Analysis of error codes and counters,
• Verification of Level measurement,
• Perform a test to activate the safety alarm through lock test or level simulation.
4. Analyze the results of step 3. above:
• look for unusual and/or exceptional behavior,
• compare the data with historical data, and look for trends,
• prepare a report for plant management; discuss any highlights,
• initiate preventive and/or corrective maintenance if necessary.
5. Reset the relevant diagnostic items to their default values.
This applies to the items that have a ‘Protection level 1’ (see TABLE
4-1).
6. Finally, execute the required certification renewal procedure.
Maintenance Requirements
854 ATG/XTG level gauge
Safety Manual
Part No.: 4417808_Rev01
4 - 4
Honeywell Enraf
Delftechpark 39
2628 XJ Delft
The Netherlands
Tel: +31 (0)15-2701 100
Email: [email protected]
www.honeywellenraf.com
4417808 - Revision 1
July 2015
© 2015 Honeywell International Inc.